WWYK263009_65 Drawings_Volume 2_Part5.pdf

PDF 4 MB Posted

Attached to
Bomber Agile Common Hangar; 4-Dock Hangar at Tinker Air Force Base
Solicitation number
W912BV25S0014
Issued by

About this file

These are electrical and grounding plan drawings for the Bomber Agile Common Hangar project at Tinker Air Force Base, prepared by Mason and Hanger for the US Army Corps of Engineers Tulsa District. The drawings include detailed electrical power plans, panel schedules, one-line diagrams, and grounding/lightning protection plans for both floors and roof areas of the hangar facility.

The drawings show electrical distribution systems including switchboards, panels, transformers and circuiting for a 480Y/277V and 208Y/120V power system. Grounding details include static ground grids, building ground loops, lightning protection air terminals, and bonding requirements. The drawings are at 65% design stage dated November 20, 2024, under contract numbers W912BV-20-D-0008 and W912BV-20-D-0032. Key areas covered include hangar bays, support spaces, and administrative areas across multiple floor plans divided into Areas A through D. The drawings contain specific technical details like panel schedules showing circuit breaker sizes, loads, and demand calculations as well as one-line diagrams depicting the electrical distribution hierarchy.

View the file

Other files

File Type Posted
WWYK263009_65 Design Analysis_Part12_Part2.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part6_Part1.pdf PDF
WWYK263009_65 Design Analysis_Part18_Part6.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part1.pdf PDF
WWYK263009_65 Design Analysis Part 28_Part3.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part6_Part2.pdf PDF
WWYK263009_65_NG-LCCA_BLCC_Summary Report.pdf PDF
WWYK263009_65 Design Analysis_Part24.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part4_Part7.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part4.pdf PDF
WWYK263009_65 Design Analysis_Part22_Part4_Part3.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part4_Part1.pdf PDF
WWYK263009_65 Design Analysis_Part17.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part19_Part3.pdf PDF
WWYK263009_65 Design Analysis_Part10.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part8.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part1.pdf PDF
WWYK263009_65_NG_energy model results.pdf PDF
Bomber Agile Common Hangar Industry Forum Presentation.pdf PDF
WWYK263009_65 Drawings_Volume 2_Part6.pdf PDF
WWYK263009_65 Design Analysis_Part22_Part4_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part18_Part2.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part4_Part4.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part7.pdf PDF
WWYK263009_65 Design Analysis_Part21.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part6_Part4_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part23.pdf PDF
WWYK263009_65 Design Analysis_Part22_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part4.pdf PDF
WWYK263009_65 Design Analysis_Part19_Part2.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part3.pdf PDF
WWYK263009_65 Design Analysis_Part20.pdf PDF
WWYK263009_65 Design Analysis Part 28_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part26.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part5.pdf PDF
WWYK263009_65 Design Analysis_Part19_Part4.pdf PDF
WWYK263009_65 Design Analysis_Part27.pdf PDF
WWYK263009_65 Design Analysis_Part18_Part5.pdf PDF
WWYK263009_65 Design Analysis_Part15.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part3.pdf PDF
WWYK263009_65 Design Analysis Part 28_Part4.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part9.pdf PDF
WWYK263009_65 Design Analysis_Part9.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part4.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part1.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part5.pdf PDF
WWYK263009_65_NG-LCCA_BLCC results.pdf PDF
WWYK263009_65 Design Analysis_Part7.pdf PDF
Show 40 more

Latest 50 of 95 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C J

C J

C J

C J

C J

C J

C J

C J

CJ

C J

C J

C J

C J

C J

C J

C J

C J

C J C

J C

J C

J C

J C

J C

J C

J C

J C

J C

J C

J C

J C

J C

J C

J C

J C

J

CJ CJ CJ CJ CJ CJ

JJ

JJ JJ

A

B

C

D

J

E

V

H

F

W

U

G

003001 002

SL2T1 SL2T2

CTR TRNG

202K

COLLAB

CORRIDOR

OPEN OFFICE

202A

ELEC

202B

OFFICE

202C

OFFICE

202D

OFFICE

202E

OFFICE

202F

OFFICE

202G

COPY/FILE

202H

OFFICE

202I

OFFICE

202J

OFFICE

EP410

B1

WP

SEE EP121

O

DC

DC

DC

DC

DC

DC

DCDC

42"

42"

FP-SL2R5 FP-SL2R5

FP-SL2R5FP-SL2R5

DC-FP

FP

DC-FP

FP

DC-FP

FP

DC-FP

FP

DC-FP

FP FP

DC-FP

FP

DC-FP

FP

DC-FP

FP

DC-FP

FP

DC-FPDC-FP

FP

DC-FP

FP

DC-FP

FP

DC-FP

FP

DC-FP

FP

DC-FP

FP

DC-FP

FP

DC-FP

FP FP

DC-FP

FP

DC-FP

T V

-6

A

FP

FP

FP

FP

FP FP

FP

FP

FP

FP

FP

FP

FP

FP

FP FP

FP

FP

FP

FP

SL2T1-3

SL2T1-2

SL2T1-1

SL2T2-1

SL2T2-3

SL2T2-4

SL2T2-2

SL2R4-8 SL2R4-8

SL2R4-8

SL2R4-8

SL2R4-8

S L R

-8 SL2R4-7

SL2R4-7

SL2R4-7

SL2R4-6

SL2R4-7

SL2R4-7

S L R

-7

S L R

-7

SL2R4-2

SL2R4-2

SL2R4-2

SL2R4-6

SL2R4-6

SL2R4-2

S L R

-8

SL2R4-3

SL2R4-3

SL2R4-3 SL2R4-3

SL2R4-3

SL2R4-1

SL2R4-6

SL2R4-6

SL2R4-4

SL2R4-1 SL2R4-1

SL2R4-1

SL2R4-5

SL2R4-3 SL2R4-3

SL2R4-3

SL2R4-6

SL2R4-6

S L R

-6

FP-SL2R5 FP-SL2R5

5 7

6 9

FP

FP

5 1

FP

FP

SL2R4-19

SL2R3-2

SL2R3-2

SL2R3-2 SL2R3-2

SL2R3-2

SL2R3-2

SL2R3-2

S L R

-1

SL2R3-1

3.51.5 2.8

G.9

F.8

E.7

C.6

D.7

B.4

C.8

D.8

E.8

G.1

H.1

2.61.6 2.3 2.9 3.9

C

A B

D

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

N

PLAN

NORTH

SCALE:

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

4'-0" 8'-0" 16'-0"

1/8" = 1'-0"

KEYPLAN

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP123

S E

C O

N D

F L O

O R

P

O W

E R

P L A

N

A R

E A

C

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: 1/8" = 1'-0"EP123

SECOND FLOOR - POWER PLAN - AREA CA1

GENERAL SHEET NOTES

1 FOR LEGENDS SEE SHEET E-001.

2 FOR GENERAL NOTES SEE SHEET E-002.

3 FOR ABBREVIATIONS SEE SHEET E-003.

SHEET KEYNOTES

D E

S

IG

N

/2

/2

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

TT

RR

SS

NN

JJ

N

J

AA

PP

MM

KK

DD

P

M

CC

X

LL

W

HH

GG

FF

EE

BB

Z

Y

T

S

R

K

L

003001 002

SH2L

SL2R3

SL2M AHU-4

VAV 4-6

VAV 4-4

VAV 4-5

VAV 4-3

VAV 4-2

VAV 4-1

VAV 4-8

VAV 4-9

VAV 4-13

VAV 4-12 VAV 4-11

VAV 4-10

CTR TRNG

CORRIDOR

SC2

STAIR

218I

CONF

218J

CONF

218H

COPY

AMXS

218G

OFFICE

SA1

STAIR

218F

OFFICE

218E

OFFICE

218D

OFFICE

218C

OFFICE

218B

OFFICE

218A

OFFICE

BRK

SB2

STAIR

E2

ELEV

218K

ELEC

CORRIDOR

WOMENS

W

M

STOR

MENS

JAN

SCHED OFF

CORRIDOR

209B

OFFICE

209A

OFFICE

ELEC

CTR TRNG

MECH

SEE EP127

EP410

D8

FCU-3

FCU-1

VAV 4-7

UH-3

3.51.5 2.8

R.3

P.3

M.4

N.3

L.5

K.2

J.3

K.1

L.4

P.2

2.6

N.1

P.9

1.6 2.3 2.9

R.5

M.1

3.9

L.3

J.9

R.9

SH2M1-7

SH2M1-7

SH2M1-7

SH2M1-7

SH2M1-7

SH2M1-7

SH2M1-8

SH2M1-8

SH2M1-8

SH2M1-8

SH2M1-8

SH2M1-8

SH2M1-8

SL2M-1

SH2M1-9,11,13

SH2M1-7

SH2M1-8

C

A B

D

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

N

PLAN

NORTH

SCALE:

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

4'-0" 8'-0" 16'-0"

1/8" = 1'-0"

KEYPLAN

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP125

S E

C O

N D

F L O

O R

H

V A

C P

O W

E R

P L A

N

A R

E A

A

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: 1/8" = 1'-0"EP125

SECOND FLOOR - HVAC POWER PLAN - AREA AA1

GENERAL SHEET NOTES

1 FOR LEGENDS SEE SHEET E-001.

2 FOR GENERAL NOTES SEE SHEET E-002.

3 FOR ABBREVIATIONS SEE SHEET E-003.

SHEET KEYNOTES

D E

S

IG

N

/2

E E

E

E

E

E

E

E

E

E

A

B

C

D

J

E

V

H

F

W

U

G

003001 002

SL2T2SL2T1

VAV 4-14

VAV 4-20

VAV 4-16

VAV 4-15

VAV 4-17

VAV 4-21

VAV 4-18

VAV 4-19

202J

OFFICE

202I

OFFICE

202H

OFFICE

202F

OFFICE

202E

OFFICE

202D

OFFICE

202C

OFFICE

202B

OFFICE

202A

ELEC

OPEN OFFICE

202K

COLLAB

SFTWR

CTR TRNG

CORRIDOR

COMM

SC2

STAIR

CTR TRNG

AC-6

SEE EP125

EP410

B1

EF-3

UH-4

MAU-1

3.51.5 2.8

G.9

F.8

E.7

C.6

D.7

B.4

C.8

D.8

E.8

G.1

H.1

2.61.6 2.3 2.9 3.9

SL2M-2

SH2M2-11

SH2M2-11

SH2M2-11

SH2M2-11

SH2M2-11

SH2M2-11

SH2M2-11

SH2M2-11

SLDR5-22

SLDR5-21,23,25

C

A B

D

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

N

PLAN

NORTH

SCALE:

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

4'-0" 8'-0" 16'-0"

1/8" = 1'-0"

KEYPLAN

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP127

S E

C O

N D

F L O

O R

H

V A

C P

O W

E R

P L A

N

A R

E A

C

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: 1/8" = 1'-0"EP127

SECOND FLOOR - HVAC POWER PLAN - AREA CA1

GENERAL SHEET NOTES

1 FOR LEGENDS SEE SHEET E-001.

2 FOR GENERAL NOTES SEE SHEET E-002.

3 FOR ABBREVIATIONS SEE SHEET E-003.

SHEET KEYNOTES

D E

S

IG

N

/2

E

E

TT

RR

SS

NN

JJ

N

J

AA

PP

MM

KK

DD

P

M

CC

X

LL

W

HH

GG

FF

EE

BB

Z

Y

T

S

R

K

L

003001 002

HVU-1 (SUPPLY)

S E

E E

P

SEE EP133

DOAS-3

HVU-1(EXHAUST)

HVU-1(HOUSE)

3.51.5 2.8

R.3

P.3

M.4

N.3

L.5

K.2

J.3

K.1

L.4

P.2

2.6

N.1

P.9

1.6 2.3 2.9

R.5

M.1

3.9

L.3

J.9

R.9

SH2M2-8,10

SH2M1-1,3,5

SLDR1-21

SH2M1-2,4,6

C

A B

D

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

N

PLAN

NORTH

SCALE:

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

4'-0" 8'-0" 16'-0"

1/8" = 1'-0"

KEYPLAN

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP131

R O

O F

P

O W

E R

A

N D

H V

A C

P O

W E

R P

L A

N

A R

E A

A

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: 1/8" = 1'-0"EP131

ROOF - POWER AND HVAC POWER PLAN - AREA AA1

SHEET KEYNOTES

GENERAL SHEET NOTES

1 FOR LEGENDS SEE SHEET E-001.

2 FOR GENERAL NOTES SEE SHEET E-002.

3 FOR ABBREVIATIONS SEE SHEET E-003.

D E

S

IG

N

/2

E

E

TT

RR

6 7 0058 95

SS

NN

JJ

N

J

AA

PP

MM

KK

DD

P

M

CC

X

LL

W

HH

GG

FF

EE

BB

Z

Y

T

S

R

K

L

HVU-3(SUPPLY)

DOAS-2

SEE EP134

S E

E E

P

HVU-3(EXHAUST)

HVU-3(HOUSE)

R.3

P.3

M.4

N.3

L.5

K.2

J.3

K.1

L.4

P.2

N.1

P.9

R.5

M.1

5.8

L.3

J.9

R.9

NH1M1-28,30,32

NH1M1-15,17,19

NLDR1-13

NH1M1-27,29,31

C

A B

D

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

N

PLAN

NORTH

SCALE:

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

4'-0" 8'-0" 16'-0"

1/8" = 1'-0"

KEYPLAN

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP132

R O

O F

P

O W

E R

A

N D

H V

A C

P O

W E

R P

L A

N

A R

E A

B

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: 1/8" = 1'-0"EP132

ROOF - POWER AND HVAC POWER PLAN - AREA BA1

SHEET KEYNOTES

GENERAL SHEET NOTES

1 FOR LEGENDS SEE SHEET E-001.

2 FOR GENERAL NOTES SEE SHEET E-002.

3 FOR ABBREVIATIONS SEE SHEET E-003.

D E

S

IG

N

/2

E

E

E

E

B

C

D

J

E

V

H

F

W

U

G

003001 002

HVU-2(EXHAUST)

S E

E E

P

SEE EP131

O

DOAS-1

HVU-2(SUPPLY)

HVU-2(HOUSE)

3.51.5 2.8

G.9

F.8

E.7

C.6

D.7

B.4

C.8

D.8

E.8

G.1

H.1

2.61.6 2.3 2.9 3.9

EF-3

MAU-1

SLDR5-22

SLDR5-21,23,25

SH2M2-1,3

SLDR5-24

SH2M2-2,4,6

SH2M2-5,7,9

C

A B

D

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

N

PLAN

NORTH

SCALE:

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

4'-0" 8'-0" 16'-0"

1/8" = 1'-0"

KEYPLAN

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP133

R O

O F

P

O W

E R

A

N D

H V

A C

P O

W E

R P

L A

N

A R

E A

C

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: 1/8" = 1'-0"EP133

ROOF - POWER AND HVAC POWER PLAN - AREA CA1

SHEET KEYNOTES

GENERAL SHEET NOTES

1 FOR LEGENDS SEE SHEET E-001.

2 FOR GENERAL NOTES SEE SHEET E-002.

3 FOR ABBREVIATIONS SEE SHEET E-003.

D E

S

IG

N

/2

E

B

6 7 0058 95

C

D

J

E

V

H

F

W

U

G

HVU-4(EXHAUST)

O

SEE EP132

S

E E

E P

HVU-4(SUPPLY)

HVU-4(HOUSE)

G.9

F.8

E.7

C.6

D.7

B.4

C.8

D.8

E.8

G.1

H.1

5.8

NLDR4-26

NH1M1-33,35,37

NH1M1-34,36,38

C

A B

D

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

N

PLAN

NORTH

SCALE:

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

4'-0" 8'-0" 16'-0"

1/8" = 1'-0"

KEYPLAN

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP134

R O

O F

P

O W

E R

A

N D

H V

A C

P O

W E

R P

L A

N

A R

E A

D

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: 1/8" = 1'-0"EP134

ROOF - POWER AND HVAC POWER PLAN - AREA DA1

GENERAL SHEET NOTES

1 FOR LEGENDS SEE SHEET E-001.

2 FOR GENERAL NOTES SEE SHEET E-002.

3 FOR ABBREVIATIONS SEE SHEET E-003.

SHEET KEYNOTES

D E

S

IG

N

/2

AA

K

T-S1L1

SLSB

SHMSB

LCP-1

SH1M1

SL1R3

2.8

K.2

K.1

2.61.6 2.3 2.9

J.9

E1

EG503

SL1R3-19

SL1R3-19

SL1R3-19

SL1F

SH1L

6 7

L

N H

L

L

R A

N H

M

NT1-1

NHMSB

M T

S -1

M E

T E

R

D H

H R

A

NLSB

S P

D

L C

P -3

S P

D

N L F

F A

C P

N L F

-1

N L R

-1

NL1R2-14

L.4

5.8

L.3

M

2.62.3

M.1

M

FF

MACH RM

E1

ELEV

60"

36"

ECB

ELEVATOR

SHMSB-13

M.4

2.62.3

M.136"

K

SL2R3

SH2L

2.6

J.9

SL2M

SL2R3-15

SH2M1

SL2R2

2.62.3

SL2R2-28

S L R

S H

M

SL2R4-18

3.5

G.9

3.9

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

N

PLAN

NORTH

SCALE:

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

2'-0" 4'-0" 8'-0"

1/4" = 1'-0"

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP410

E N

L A

R G

E D

P L A

N S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

GENERAL SHEET NOTES

1 FOR LEGENDS SEE SHEET E-001.

2 FOR GENERAL NOTES SEE SHEET E-002.

3 FOR ABBREVIATIONS SEE SHEET E-003.

SHEET KEYNOTES

1 PROVIDE ELEVATOR SHUNT TRIP

ENCLOSED CIRCUIT BREAKER WITH

AUXILIARY CONTACTS. SHUNT TRIP

SHALL OPERATE BY ACTUATION OF THE

SPRINKER FLOW SWITCH. AUXILIARY

CONTACTS SHALL BE CONNECTED TO

THE ELEVATOR EQUIPMENT TO PREVENT

AUTOMATIC LOWERING OF THE

ELEVATOR CAR WHEN THE BREAKER LINE

CONTACTS ARE OPEN.

SCALE: 1/4" = 1'-0"EP111

ENLARGED PLAN - ELECTRIC ROOM 113G1

SCALE: 1/4" = 1'-0"EP112

ENLARGED PLAN - ELECTRIC ROOM 016G5

SCALE: 1/4" = 1'-0"EP121

ENLARGED PLAN - ELEVATORD1

SCALE: 1/4" = 1'-0"EP111

ENLARGED PLAN - ELEVATOR PITD5

ELEVATOR PITELEVATOR TOP OF SHAFT

SCALE: 1/4" = 1'-0"EP121

ENLARGED PLAN - ELECTRICAL ROOM 208G8

SCALE: 1/4" = 1'-0"EP121

ENLARGED PLAN - ELECTRIC ROOM 218KD8

SCALE: 1/4" = 1'-0"EP123

ENLARGED PLAN - ELECTRIC ROOM 202AB1

D E

S

IG

N

/2

SLDR2-20

SLDR2-18

SLDR2-22,24,26

SLDR1-16,18,20 SLDR1-11,13,15

SLDR2-2,4,6

SLDR2-23,25

SHMSB-1

SHMSB-2

SLDR2-29,31,33

FIRST FLOOR

100' - 0"

SLDR3-15

SLDR3-16

SLDR3-19,21,23

SLDR3-20,22,24

SLDR3-25,27,29

SLDR3-26,28,30

SLDR3-17

SLDR3-18

SLDR3-31,33,35

SLDR3-32,34,36

SLDR3-38,40

SLDR3-37,39

SHMSB-5

SHMSB-6

V

SHMSB-8

SLDR4-28,30,32

SLDR4-17

SLDR4-18

SLDR4-31,33,35

SLDR4-19

SLDR4-20

SLDR4-34,36,38

SLDR4-37,39,41

SLDR4-40,42

SHMSB-7

H.1

FIRST FLOOR

100' - 0"

SLDR5-6

SLDR5-4

SLDR6-11

SLDR6-13

SHMSB-3 SHMSB-4

SLDR5-15,17SLDR6-27,29

SLDR6-22,24,26 SLDR5-14,16,18

SLDR6-21,23,25

SLDR5-9,11,13

SLDR6-10,12,14

SLDR5-8,10,12

NHMSB-6

NLDR8-8,10

NLDR8-9,11,13

NLDR8-12,14,16

NLDR8-15,17,19

NLDR8-6

NLDR8-7

NLDR7-18,20,22

NLDR7-19,21,23

NLDR7-32,34,36

NLDR7-33,35 NHMSB-5

NLDR7-8 NLDR7-1

NLDR2-19,21,23NLDR2-16,18,20

NLDR2-11,13,15

NLDR2-10,12

NHMSB-7

NLDR1-7,9,11

NLDR1-8,10,12

NLDR1-21,23,25

NLDR1-22,24

NHMSB-8

NLDR1-6

NLDR2-17 NLDR2-14

NLDR1-5

NHMSB-2

NLDR5-31,33

NLDR5-30,32,34

NLDR5-25,27,29

NLDR5-24,26,28

NLDR4-27,29,31

NLDR4-33,35,37

NLDR4-34,36,38

NLDR4-39,41

NHMSB-1

NLDR4-22

NLDR4-24

NLDR5-35

NLDR5-36

F.8

YK

NHMSB-4

NLDR3-18,20

NLDR3-19,21,23

NLDR3-22,24,26

NLDR3-28

NLDR3-25,27,29

NLDR3-30

NLDR3-33,35,37

NLDR3-31

NLDR3-32

NLDR3-34,36,38

NLDR3-40,42,44

NLDR3-39,41

NHMSB-3

J.9

C

A B

D

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

SCALE:

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

4'-0" 8'-0" 16'-0"

1/8" = 1'-0"

KEYPLAN

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP500

P O

W E

R C

E N

T E

R E

L E

V A

T

IO

N S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: 1/2" = 1'-0"EP500

POWER CENTER ELEVATION - SW NOSEG1

SCALE: 1/2" = 1'-0"EP500

POWER CNTER ELEVATION 2 - SW WINGD1

SCALE: 1/2" = 1'-0"EP500

POWER CENTER ELEVATION - SE WINGA1

SCALE: 1/2" = 1'-0"EP500

POWER CENTER ELEVATION - SE NOSEG5

SCALE: 1/2" = 1'-0"EP500

POWER CENTER ELEVATION - NE NOSED5

SCALE: 1/2" = 1'-0"EP500

POWER CENTER ELEVATION - NW NOSEA5

SCALE: 1/2" = 1'-0"EP500

POWER CENTER ELEVATION - NE WINGG8

SCALE: 1/2" = 1'-0"EP500

POWER CENTER ELEVATION - NW WINGD8

D E

S

IG

N

/2

NOTES:

1. PROVIDE TWO (2) 1 1/4" CONDUITS FROM FLOOR BOX

COMMUNICATIONS COMPARTMENT TO CONSOLIDATION

POINT ABOVE CEILING. ONE CONDUIT MUST BE USED FOR

CABLING COMMUNICATIONS AS SHOWN. THE OTHER MUST

HAVE ONLY A PULLSTRING FOR FUTURE USE. ENSURE

FLOOR BOX IS FIXED PROPERLY NOT TO EXCEED BEND

RADIUS OF OSP CABLE AFTER TERMINATION.

RECESSED HATCH WITH

CARPET/TILE INSERT AND

WIRE PASS THROUGH

SLOTS.

4 COMPARTMENT CAST IRON

RECESSED FLOOR BOX.

DATA/TELEPHONE

OUTLETS UP TO FOUR

(4) ON EACH SIDE.

QUANTITY AS NOTED.

PROVIDE UP TO THREE (3)

DUPLEX OUTLETS (QUANTITY

SHOWN ON DRAWINGS)

FULLY ADJUSTABLE

LEVELING COLLAR

SYSTEM FURNITURE

POWER WHIP 3/4"

FURNISHED BY SYSTEM

FURNITURE PROVIDER.

SERVICE FITTING SINGLE

HOLE FACEPLATE.

COORDINATE DIAMETER

WITH SYSTEM FURNITURE

SUPPLIER.

NOTE:

PROVIDE AFTERSET INSERT, EXTENSIONS,

ADAPTERS, AND NIPPLES AS REQUIRED TO

CONNECT TO FLOOR BOX PER

MANUFACTURER'S REQUIREMENTS.

10-7/8"

8-1/2"

4-1/8"

90 DEGREE

CONNECTOR

FLEXIBLE CORD WITH

CONNECTOR SUPPLIED WITH

SYSTEMS FURNITURE

FLUSH MOUNTED

STAINLESS STEEL

COVER PLATE

RECESSED

MOUNTING BOX

3/4" CONDUIT

CONDUCTORS AS

REQUIRED FOR SYSTEMS

FURNITURE CONNECTION

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP501

D E

T A

IL

S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: NTSEP501

POWER/COMMUNICATION - FLOOR BOXF1

SCALE: NTSEP501

POWER - SYSTEMS FURNITURE (FLOOR)F5

SCALE: NTSEP501

POWER - SYSTEMS FURNITURE (WALL)F9

D E

S

IG

N

/2

PLAN

SECTION

NOTE 4

DUCTBANK ENTRANCE - REFER TO SITE PLANS

FOR EXACT ENTRANCE QUANITIES (TYPICAL)

NOTE 1

FINISHED GRADE OR PAVEMENT

PROVIDE LOCKABLE CAST IRON COVER AND FRAME

WITH LOGO AS INDICATED ON THE DRAWINGS

CONCRETE COLLAR, HEIGHT AS REQ'D BUT MIN 150mm

BELOW FINISHED GRADE.

EXTEND AND EXOTHERMICALLY BOND TO

95mm|2 COMPOUND GRID GROUNDING

CONDUCTOR RUN ABOVE DUCTBANK,

SEE SHEET E1-121.

CABLE RACKS (NON-METALLIC)

GROUNDING ASSEMBLY INSTALLED AND

BONDED TO REINFORCING STEEL (EQUAL

TO AC LIGHTNING SECURITY #P692)

EXTEND AND EXOTHERMICALLY

BOND TO ALL GND ROD & METALLIC

EQUIPMENT WITHIN MANHOLE

DUCTBANK ENTRANCE

(VARIES)

21mmD X 3048mm LONG COPPER

CLAD STEEL GROUND ROD

NOTE 4

COORDINATE THE PLACEMENT OF

PULLING-IN IRONS TO SUIT THE

DIRECTION OF THE CONDUCTOR

PULLS (TYPICAL)

300mm X 300mm SUMP

MANHOLE NOTES:

CABLE RACK

STANCHIONS

(TYPICAL)

PULLING-IN IRONS

75mm (MIN)

BOTH SIDES

75mm (MIN) BOTH SIDES

380mm (MIN)

1100mm (MAX)

IN REPRESENTATIONAL AREAS, INSTALL SUCH THAT NO PORTION

OF THE CONCRETE MANHOLE COLLAR IS VISIBLE

CABLES AND CONDUCTORS

ENTERING/EXITING MANHOLES AND

HANDHOLES SHALL BE RACKED AS

INDICATED TO NOT EXCEED THE

MAXIMUM BENDING RADIUS OF THE

CABLES AND CONDUCTORS. (TYPICAL)

PROVIDE MANHOLE ACCESS

LADDER TO EXTEND AT LEAST

900mm ABOVE THE COVER FRAME.

REFER TO NOTE-6

THE MANHOLE DEPTH SHALL BE DEPENDENT ON THE DEPTH OF THE

INCOMING/OUTGOING DUCTBANKS AND THE INVERTS SET BY THE CIVIL PROFILES.

REFER TO ED1-XXX SERIES DRAWINGS FOR DUCTBANK ROUTING AND

MANHOLELOCATIONS AND REFER TO CIVIL DRAWINGS FOR INVERTS. MANHOLE

INTERIOR HEIGHT SHALL BE A MINIMUM OF1830mm.

PROVIDE MANHOLE COVER WITH TAMPERPROOF BOLTS.

PROVIDE COVER LOGO AS INDICATED ON SITE PLAN - MEDIUM-VOLTAGE ELECTRIC

POWER (MV), LOW-VOLTAGE ELECTRIC POWER (E), COMMUNICATION (C) AND SIGNAL

(S).

REFER TO THE MANHOLE-HANDHOLE SCHEDULE ON THIS SHEET FOR MINIMUM SIZES.

REFER TO STRUCTURAL DRAWINGS FOR STRUCTURAL DETAILS AND REBAR

REQUIREMENTS NOT SHOWN ABOVE.

PROVIDE ONE HEAVY-DUTY LADDER OF TYPE AND REQUIRED LENGTH PER

SPECIFICATION SECTION 337119 (ONE PORTABLE LADDER FOR USE IN ALL

MANHOLES).

1.

2.

3.

4.

5.

6.

LOGO

LOGO

LO

G

O

LO

G

O

TIE

R

TIER

T

IE

R

T

IE

R

LIFTING BOLT - 4 PLACES

SKID RESISTANT

SURFACE

THRU HOLE DEEP

COUNTERBORE

SELF ALIGNING REPLACEABLE

S.S EZ-NUT 4 PLACES

PULL SLOT W/ CENTER PIN (2

PLACES)

MANHOLE ENTRANCE POINT. PROVIDE

SEPARATION JOINT FOR SEISMIC MOVEMENT

(IF REQUIRED). TYPICAL OF ALL DUCTBANK

ENTRANCE POINTS.

EPC-40-PVC UNDERGROUND

DUCT (TYPICAL)

WALL OF MANHOLE

PROVIDE

END BELLS

DUCTBANK (SEE SECTIONS)

HANDHOLE/PULLBOX NOTES:

PROVIDE COMPOSITE CONCRETE BOX, UL LISTED, WITH OPEN

BOTTOM (UNLESS NOTED OTHERWISE).

REFER TO MANHOLE/HANDHOLE SCHEDULE ON THIS DRAWING.

PROVIDE ALL BOXES WITH SECURE COVER LOCKDOWN OPTION

FOR TAMPERPROOF BOLTS.

PROVIDE BOXES RATED FOR ROADWAY OR SIDEWALK LOADING

AS REQUIRED.

BOX SHALL BE INSTALLED ACCORDING TO

MANUFACTURER'S WRITTEN INSTRUCTIONS.

COLOR FOR ALL BOXES SHALL BE STANDARD CONCRETE GRAY.

SLOPE GRADE AWAY FROM MANHOLE/HANDHOLE COVERS AS

REQUIRED TO PREVENT FUTURE WATER BUILD-UP OR

INFILTRATION .

THE HANDHOLE/PULLBOX DETAIL IS TYPICAL FOR BOTH

ELECTRICAL POWER AND COMMUNICATIONS SYSTEMS

CONDUITS/DUCTS.

1.

2.

3.

4.

5.

6.

7.

8.

SECTION

A-A

CONCRETE ENCASEMENT

TYPICAL HANDHOLE COVER

PVC CONDUIT

COMPACTED BACKFILL

ALTERNATE CONDUIT INSTALLATION:

WHERE CONDUITS CAN DRAIN BACK

TO THE PREVIOUS HANDHOLE OR

MANHOLE, CONDUITS MAY ENTER

THE HANDHOLE HORIZONTALLY

150mm - 200mm GRAVEL OR

CRUSHED ROCK FOR DRAINAGE

CONDUIT INSTALLATION FOR

CABLE/CONDUCTOR PULLING-IN

POINT. SEAL CONDUITS WATERTIGHT

FOLLOWING CABLE/CONDUCTOR

INSTALLATION.

FOLLOWING CONDUCTOR

INSTALLATION, SEAL CONDUIT

ENDS

WATERTIGHT (TYPICAL FOR SPARE

CONDUITS)

TOP OF CONDUIT:

750mm BELOW PAVEMENT 600mm

BELOW GRASS

PVC CONDUIT - SLOPE

1:300 FOR MIDPOINT OF

DUCTBANK TOWARDS THE

HANDHOLE OR MANHOLE

(TYPICAL)

DUCTBANK

CONCRETE

ENCASEMENT

PLAN

AA OPEN BOTTOM

COMPACTED

BACKFILL

CONCRETE

ENCASEMENT

220mm

22mmØ

230mm

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP502

D E

T A

IL

S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: NTSEP502

CAST-IN PLACE ELECTRICAL POWER & COMMUNICATIONS MANHOLE DETAILA1

SCALE: NTSEP502

PRECAST POLYMER CONCRETE HANDHOLE/PULLBOX DETAILA8

SCALE: NTSEP502

DUCTBANK ENTRANCEG1

SCALE: NTSEP502

PRECAST HANDHOLE/PULLBOX INSTALLATION DETAILG3

SCALE: NTSEP502

PULLING IRONF5

D E

S

IG

N

/2

H.V.

L.V.

Y

GFI

SPD

NB GB 4

A

/3 P

A

/3 P

A

/3 P

2000A/3P

A

/3 P

2000/5

MAIN SWITCHBOARD 'SHMSB', 3000A, 480Y/277V, 3-PHASE, 4-WIRE, XXKAIC

A

/3 P

A

/3 P

A

/3 P

PANEL

SH2M1

600A

PANEL

SH1L

100A

500KCMIL

MAIN

BONDING

JUMPER

#3/0 GEC TO MAIN

GROUNDING BUS

BAR (MGB)

UTILITY PAD MOUNT TRANSFORMER PROVIDED BY OG&E. POINT OF

DEMARCATION FOR OG&E IS THE SECONDARY CABLE TERMINATION LUGS.

PANEL

SHDR

800A

TRANSFORMER

GROUND,

PROVIDED BY

OG&E

GROUND

BUS

NEUTRAL BUS

PANEL

SH1M2

400A

WH

MV UTILITY, PROVIDED BY OG&E

Y

#2/0G

'T-S1L2' 480V- 208Y/120

225 KVA

PANEL

SLDR2

800A

PANEL

SLDR1

400A

PANEL

SLDR3

400A

Y

A

/3 P

PANEL

SL1R1

225A

A

/3 P

PANEL

SL1R2

225A

A

/3 P

PANEL

SL1ELEV

150A

A

/3 P

PANEL

SL1R3

225A

PANEL

SL1T1

100A

A

/3 P

PANEL

SL1T2

100A

PANEL

SL2T1

100A

A

/3 P

PANEL

SL2R2

100A

1600A-3P

'T-S1L1' 480V- 208Y/120

500 KVA

SWITCHBOARD 'SLSB' 1600A, 208Y/120V, 3-PHASE, 4-WIRE, IG BUS, XXKAIC

A

/3 P

PANEL

SH2L

100A

LTG LTG MECH

PLUM 2

A

/3 P

PANEL

SL1M

225A

MECH

PLUM

ELEV TELE/

COMM

PANEL

SL2T2

100A

TELE/

COMM

TELE/

COMM

TELE/

COMM

POWER

POWER

POWERPOWER

MECH

PLUM

PANEL

SL2M

225A

HANGAR

HANGAR HANGARHANGAR

A

/3 P

PANEL

SL2R1

100A

A

/3 P

PANEL

SL2R3

100A

POWERPOWER

(3 )S

P A

R E

S A

/3 P

F4-600F4-400F3-600F4-100F4-100 F4-800

F4-1600

F3-800F4-35

F4-225 F4-225 F4-225 F4-150 F4-225

F4-100

F4-100 F4-100 F4-100 F4-100 F4-100 F4-225

F3-350

F4-800

F4-400 F4-400

A

/3 P

PANEL

SL2R4

100A

F4-100

POWER

#3/0G

6 PARALLEL RUNS OF 4-500KCMIL EACH IN 4" CONDUIT. ROUTE FOUR

ADDITIONAL 4" CONDUITS WITH PULL WIRES AS SPARES. PROVIDED BY HANGAR

CONSTRUCTION CONTRACT. CONDUCTORS TERMINATED BY OG&E USING

COMPRESSION LUGS PROVIDED BY HANGAR CONSTRUCTION CONTRACT.

(3 )S

P A

C E

S

/3 P

A

/3 P

PANEL

SH2M2

600A

MECH

PLUM

F4-600

A

/3 P

PANEL

SH1M1

225A

MECH

PLUM

F4-225

VFD

CHILLER

F3-600

(3 )S

P A

R E

S A

/3 P

(3 )S

P A

C E

S

/3 P

A

/3 P

A

/3 P

A

/3 P

1 11

METER

F4-100

A

/3 P

MECH

PLUM

PANEL

SLDR4

400A

HANGAR

PANEL

SL1R4

100A

POWER

PANEL

SL1R5

100A

POWER

F4-400

A

/3 P

F4-100

A

/3 P

F4-100

A

/3 P

F4-100

PANEL

SL1F

100A

LIFE

SAFETY

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP601

P O

W E

R O

N E

L

IN

E D

IA

G

R A

M S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: NTSEP601

SERVICE 1 - ONE-LINE DIAGRAMB1

SHEET KEYNOTES

1 NEMA 3R ENCLOSURE.

DESIGN NOTE:

TAFB REQUIRES 20%

SPARE BREAKERS

BASED ON THE

CAPACITY OF THE

MAXIMUM NUMBER OF

BREAKER SPACES IN

EACH DISTRIBUTION

ENCLOSURE.

DESIGN NOTE:

TAFB REQUIRES 20%

SPARE BREAKERS

BASED ON THE

CAPACITY OF THE

MAXIMUM NUMBER OF

BREAKER SPACES IN

EACH DISTRIBUTION

ENCLOSURE.

D E

S

IG

N

/2

Y

GFI

SPD

NB GB 4

A

/3 P

A

/3 P

A

/3 P

2500A/3P

A

/3 P

2500/5

A

/3 P

A

/3 P

PANEL

NH1M2

400A

PANEL

NH1L

200A

PANEL

NH1M1

800A

500KCMIL MAIN

BONDING JUMPER

#3/0 GEC TO MAIN

GROUNDING BUS

BAR (MGB)

7 PARALLEL RUNS OF 4-500KCMIL EACH IN 4" CONDUIT. ROUTE THREE

ADDITIONAL 4" CONDUITS WITH PULL WIRES AS SPARES. PROVIDED BY HANGAR

CONSTRUCTION CONTRACT. CONDUCTORS TERMINATED BY OG&E USING

COMPRESSION LUGS PROVIDED BY HANGAR CONSTRUCTION CONTRACT.

UTILITY PAD MOUNT TRANSFORMER PROVIDED BY

OG&E. POINT OF DEMARCATION FOR OG&E IS THE

SECONDARY CABLE TERMINATION LUGS.

PANEL

NHND

800A

TRANSFORMER GROUND,

PROVIDED BY OG&E

GROUND BUSNEUTRAL BUS

WH

MV UTILITY, PROVIDED BY OG&E

(3 )S

P A

R E

S A

/3 P

Y

#2/0G

'NT1-2'

480V- 208Y/120

225 KVA

PANEL

NL1R2

800A

PANEL

NL1R1

400A

PANEL

NL1R3

400A

Y

(3 )S

P A

C E

S

/3 P

PANEL

NLDR1

100A

PANEL

NLDR2

225A

PANEL

NLDR3

225A

PANEL

NLDR4

225A

A

/3 P

PANEL

NL1T

100A

A

/3 P

(3 )S

P A

R E

S A

/3 P

(3 )S

P A

C E

S

/3 P

1600A-3P

MAIN SWITCHBOARD 'NHMSB', 3000A, 480Y/277V, 3-PHASE, 4-WIRE, XXKAIC

SWITCHBOARD 'NLSB' 1600A, 208Y/120V, 3-PHASE, 4-WIRE, XXKAIC

'NT1-1'

480V- 208Y/120

500 KVA

BASE/

METER

MTS-1

GEN

CONN

CABINET

PANEL

DH

200A

4-500KCMIL IN A 4" CONDUIT.

POWER

MECH

PLUM

MECH

PLUM

PANEL

NL1M

225A

LIGHTING MECH

PLUM

POWER POWER POWER

POWER

POWER POWER POWER TELE/

COMM

PANEL

NLDR5

225A

POWER

A

/3 P

PANEL

NLDR6

225A

POWER

A

/3 P

PANEL

NH1R

225A

POWER

F4-200 F4-800 F4-800F4-400 F4-225

F3-350

F4-800

F4-400F4-400

F4-100 F4-225 F4-225 F4-225 F4-225 F4-225 F4-100 F4-225

F3-800

F4-1600

#3/0G

F4-35

F4-200

F4-200

F4-200

A

/3 P

A

/3 P

A

/3 P

A

/3 P

A

/3 P

1 1 1

WH

METER

SPDF4-35

A

/3 P

PANEL

NLDR7

225A

POWER

F4-225

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP602

P O

W E

R O

N E

L

IN

E D

IA

G

R A

M S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: NTSEP602

SERVICE 2 - ONE-LINE DIAGRAMB1

SCALE: NTS

SERVICE 3 - ONE-LINE DIAGRAM

SHEET KEYNOTES

1 NEMA 3R ENCLOSURE.

DESIGN NOTE:

TAFB REQUIRES 20%

SPARE BREAKERS

BASED ON THE

CAPACITY OF THE

MAXIMUM NUMBER OF

BREAKER SPACES IN

EACH DISTRIBUTION

ENCLOSURE.

DESIGN NOTE:

TAFB REQUIRES 20%

SPARE BREAKERS

BASED ON THE

CAPACITY OF THE

MAXIMUM NUMBER OF

BREAKER SPACES IN

EACH DISTRIBUTION

ENCLOSURE.

D E

S

IG

N

/2

Y

100/5

UTILITY PAD MOUNT TRANSFORMER PROVIDED BY

OG&E. POINT OF DEMARCATION FOR OG&E IS THE

SECONDARY CABLE TERMINATION LUGS.

WH

MV UTILITY, PROVIDED BY OG&E

4 - #1 AWG CU IN A 2" CONDUIT. ROUTE ONE ADDITIONAL 2" SPARE

CONDUIT WITH PULL WIRE, PROVIDED BY HANGAR CONSTRUCTION

CONTRACT. CONDUCTORS TERMINATED BY OG&E USING COMPRESSION

LUGS PROVIDED BY HANGAR CONSTRUCTION CONTRACT.

METER

SPD

NB GB

A

/3 P

PHASE

MONITOR

#6 AWG CU GEC

TO GROUND ROD

GROUND

BUS

NEUTRAL BUS

ENCLOSURE

COOLING

SYSTEM

Y

'T1' 480V-

120V, 1PH

6 KVA

#8 GEC

PUMP 1

VFD

#6 AWG

CU MAIN

BONDING

JUMPER POWER

MONITOR

OL

DEVICE

PUMP 1

5 HP

PUMP 1

VFD

OL

DEVICE

PUMP 1

5 HP

RTU

PANEL

NEMA 5-20R

DUPLEX

GFCI

RECEPTACLE

PUMP 1

SAFE-TL

PUMP 2

SAFE-TL

PUMP 1 TEMP.

FLOAT SWITCHES

PUMP 2 TEMP.

FLOAT SWITCHES

UPS WITH

24VDC

BATTERY

MULTISMART

CONTROLLER

L E

V E

L P

R O

B E

P U

M P

S

E A

L L

E A

K

P U

M P

S

E A

L L

E A

K

P U

M P

T

H E

R M

A L

P U

M P

T

H E

R M

A L

P U

M P

O

L

P U

M P

O

L

P U

M P

C

U R

R E

N T

P U

M P

C

U R

R E

N T

P U

M P

C

A L L

P U

M P

C

A L L

HMI

I/O MODULE

C O

N T

R O

L P

A N

E L

IN

T R

U S

IO

N

B A

C K

U P

H

IG

H L

E V

E L

P O

W E

R M

O N

IT

O

R

P H

A S

E M

O N

IT

O

R

100 AMP,3PH, 480Y/277V CAMLOCK

GENERATOR RECEPTACLE.

100A, 3PH, 4W,

480Y/277V, MANUAL

TRANSFER SWITCH

4-POLE

A

/2 P

A

/1 P

100A, 3P

ENCLOSED CIRCUIT

BREAKER

CONDENSATION

HEATER

TRANSFORMER

GROUND,

PROVIDED BY

OG&E

100A, 3P

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP603

P O

W E

R O

N E

L

IN

E D

IA

G

R A

M S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

SCALE: NTSEP603

SERVICE 4 - LIFT STATION ONE-LINE DIAGRAMB2

D E

S

IG

N

/2

AN

R P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP604

P A

N E

L S

C H

E D

U L E

S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

Notes:

Total Est. Demand Current: 120 A

Total Conn. Current: 120 A

Total Est. Demand: 99764 VA

Total Conn. Load: 99764 VA

Other 99764 VA 100.00% 99764 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 120 A 120 A 120 A

Total Load: 33255 VA 33255 VA 33255 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 1662... 12

9 1662... 10

7 1662...

3 20 A Other

5 1662... 6

3 1662... 4

1 1662...

3 20 A Other

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 225 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: ELEC 016 Volts: 480Y/277V A.I.C. Rating: 35000

Branch Panel: DH

Notes:

Total Est. Demand Current: 0 A

Total Conn. Current: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 0 A 0 A 0 A

Total Load: 0 VA 0 VA 0 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 6

3 4

1 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: HANGAR BAY 000 Volts: 480Y/277V A.I.C. Rating: 22000

Branch Panel: SHDR

Notes:

Total Est. Demand Current: 16 A

Total Conn. Current: 16 A

Total Est. Demand: 13585 VA

Total Conn. Load: 13585 VA

HVAC 13585 VA 100.00% 13585 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 21 A 18 A 12 A

Total Load: 5560 VA 4699 VA 3325 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 831 VA 18

15 831 VA 1374... 1 20 A HVAC 16

HVAC HANGAR BAY 000 20 A 3

831 VA 2235... 1 20 A HVAC 14

11 831 VA 831 VA 12

9 831 VA 831 VA 10

HVAC 20 A 3

831 VA 831 VA

3 20 A HVAC HANGAR BAY 000

5 831 VA 0 VA 6

3 831 VA 0 VA 4

HVAC HANGAR BAY 000 20 A 3

831 VA 0 VA

3 20 A HVAC HANGAR DOCK #3 136

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: ELEC 110 Volts: 480Y/277V A.I.C. Rating: 22000

Branch Panel: SH1M1

Notes:

Total Est. Demand Current: 63 A

Total Conn. Current: 63 A

Total Est. Demand: 52625 VA

HVAC 19371 VA 100.00% 19371 VA Total Conn. Load: 52625 VA

Motor 33254 VA 100.00% 33254 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 64 A 63 A 63 A

Total Load: 17708 VA 17458 VA 17458 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 4212... 24

21 4212... 22

Motor AIR 112 20 A 3

4212... 250 VA 1 20 A HVAC Room 108 20

17 4212... 3880... 18

15 4212... 3880... 16

Motor MECH 111 20 A 3

4212... 3880...

3 20 A HVAC MECH 111

11 831 VA 2661... 12

9 831 VA 2661... 10

HVAC HANGAR BAY 000 20 A 3

831 VA 2661...

3 20 A Motor MECH 111

5 831 VA 831 VA 6

3 831 VA 831 VA 4

HVAC 20 A 3

831 VA 831 VA

3 20 A HVAC

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: MECH 111 Volts: 480Y/277V A.I.C. Rating: 22000

Branch Panel: SH1M2

Notes:

Total Est. Demand Current: Not Computed

Total Conn. Current: Not Computed

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps:

Total Load: 0 VA 0 VA 0 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 6

3 4

1 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A

Mounting: SURFACE Wires: Not Computed Mains Rating:

Supply From: Phases: Not Computed Mains Type: MCB

Location: HANGAR BAY 000 Volts: None A.I.C. Rating: 22000

Branch Panel: H2AA

D E

S

IG

N

/2

P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP605

P A

N E

L S

C H

E D

U L E

S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

Notes:

Total Est. Demand Current: 0 A

Total Conn. Current: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 0 A 0 A 0 A

Total Load: 0 VA 0 VA 0 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 6

3 4

1 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: ELEC 016 Volts: 480Y/277V A.I.C. Rating: 22000

Branch Panel: NH1L

Notes:

Total Est. Demand Current: 282 A

Total Conn. Current: 282 A

Total Est. Demand: 234089 VA

Total Conn. Load: 234089 VA

HVAC 234089 VA 100.00% 234089 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 285 A 280 A 280 A

Total Load: 79012 VA 77538 VA 77538 VA

41 42

39 40

37 2194... 6983... 38

35 2194... 6983... 36

HVAC 20 A 3

2194... 6983...

3 20 A HVAC

31 6983... 9699... 32

29 6983... 9699... 30

HVAC 20 A 3

6983... 9699...

3 20 A HVAC

25 831 VA 831 VA 26

23 831 VA 831 VA 24

HVAC 20 A 3

831 VA 831 VA

3 20 A HVAC HANGAR BAY 000

19 2194... 831 VA 20

17 2194... 831 VA 18

HVAC 20 A 3

2194... 831 VA

3 20 A HVAC

13 831 VA 831 VA 14

11 831 VA 831 VA 12

HVAC HANGAR BAY 000 20 A 3

831 VA 831 VA

3 20 A HVAC

7 HVAC 20 A 1 1424... 50 VA 1 20 A HVAC 8

5 3603... 2217... 6

3 3603... 2217... 4

HVAC 20 A 3

3603... 2217...

3 20 A HVAC

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: ELEC 016 Volts: 480Y/277V A.I.C. Rating: 22000

Branch Panel: NH1M1

Notes:

Total Est. Demand Current: 9 A

Total Conn. Current: 9 A

Total Est. Demand: 7482 VA

Total Conn. Load: 7482 VA

HVAC 7482 VA 100.00% 7482 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 9 A 9 A 9 A

Total Load: 2494 VA 2494 VA 2494 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 831 VA 12

9 831 VA 10

HVAC 20 A 3

831 VA 8

5 831 VA 831 VA 6

3 831 VA 831 VA 4

HVAC HANGAR BAY 000 20 A 3

831 VA 831 VA

3 20 A HVAC

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: MECH 015 Volts: 480Y/277V A.I.C. Rating: 22000

Branch Panel: NH1M2

Notes:

Total Est. Demand Current: 66 A

Equipment 168 VA 70.00% 118 VA Total Conn. Current: 66 A

Receptacle 1560 VA 100.00% 1560 VA Total Est. Demand: 23792 VA

HVAC 14065 VA 100.00% 14065 VA Total Conn. Load: 23842 VA

Motor 8049 VA 100.00% 8049 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 82 A 63 A 55 A

Total Load: 9762 VA 7448 VA 6632 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 Motor MECH 111 20 A 1 1920... 1920... 1 20 A Motor MECH 111 14

11 Motor MECH 111 20 A 1 1920... 1145... 12

9 2174... 1145...

2 20 A Motor AIR 112

COMM 114 20 A 2

2174... 2174... 8

5 1394... 2174...

2 20 A FIRE 113

3 1394... 2736... 1 20 A Receptacle CLOSET 125A 4

HVAC 20 A 3

1394... 180 VA 1 20 A HVAC 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 150 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type:

Location: MECH 111 Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: SL1M

D E

S

IG

N

/2

P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP606

P A

N E

L S

C H

E D

U L E

S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

Notes:

Total Est. Demand Current: Not Computed

Total Conn. Current: Not Computed

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps:

Total Load: 0 VA 0 VA 0 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 6

3 4

1 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A

Mounting: SURFACE Wires: Not Computed Mains Rating:

Supply From: Phases: Not Computed Mains Type: MCB

Location: HANGAR BAY 000 Volts: None A.I.C. Rating: 3500

Branch Panel: L2AA

Notes:

Total Est. Demand Current: 19 A

Total Conn. Current: 19 A

Equipment 264 VA 70.00% 185 VA Total Est. Demand: 6945 VA

Receptacle 1320 VA 100.00% 1320 VA Total Conn. Load: 7024 VA

HVAC 5440 VA 100.00% 5440 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 23 A 42 A 0 A

Total Load: 2354 VA 4670 VA 0 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 6

3 2174... 2496... 1 20 A Room 021D 4

HVAC 20 A 2

2174... 180 VA 1 20 A Equipment 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 150 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type:

Location: MECH 015 Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: NL1M

Notes:

Total Est. Demand Current: Not Computed

Total Conn. Current: Not Computed

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps:

Total Load: 0 VA 0 VA 0 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 6

3 4

1 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 225 A

Mounting: SURFACE Wires: Not Computed Mains Rating:

Supply From: Phases: Not Computed Mains Type: MCB

Location: ELEC 016 Volts: None A.I.C. Rating: 35000

Branch Panel: L2RA

Notes:

Total Est. Demand Current: 38 A

Total Conn. Current: 45 A

Receptacle 14940 VA 83.47% 12470 VA Total Est. Demand: 13749 VA

HVAC 320 VA 100.00% 320 VA Total Conn. Load: 16216 VA

Motor 1176 VA 100.00% 1176 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 52 A 37 A 49 A

Total Load: 6080 VA 4440 VA 5724 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20 A 1 500 VA 20

17 Receptacle 20 A 1 480 VA 360 VA 1 20 A Receptacle 18

15 Receptacle 20 A 1 1320... 1320... 1 20 A Receptacle 16

13 Receptacle 20 A 1 180 VA 1320... 1 20 A Receptacle 14

11 Receptacle 20 A 1 1320... 1320... 1 20 A Receptacle 12

9 10

7 Receptacle 20 A 1 1320... 1080... 1 20 A Receptacle 8

5 Receptacle 20 A 1 1260... 1176... 1 20 A Motor 6

3 Receptacle 20 A 1 1080... 720 VA 1 20 A Receptacle 4

1 Receptacle 20 A 1 720 VA 960 VA 1 20 A Other 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 150 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type:

Location: Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: NL1R1

Notes:

Total Est. Demand Current: 36 A

Total Conn. Current: 44 A

Total Est. Demand: 12860 VA

Total Conn. Load: 15720 VA

Receptacle 15720 VA 81.81% 12860 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 54 A 45 A 35 A

Total Load: 6300 VA 5280 VA 4140 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 Receptacle 20 A 1 1320... 360 VA 1 20 A Receptacle 14

11 Receptacle 20 A 1 180 VA 1320... 1 20 A Receptacle 12

9 Receptacle 20 A 1 1320... 1320... 1 20 A Receptacle 10

7 Receptacle 20 A 1 1080... 1320... 1 20 A Receptacle 8

5 Receptacle 20 A 1 1320... 1320... 1 20 A Receptacle 6

3 Receptacle 20 A 1 1320... 1320... 1 20 A Receptacle 4

1 Receptacle 20 A 1 1320... 900 VA 1 20 A Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: HANGAR BAY 000 Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: NL1R2

D E

S

IG

N

/2

P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP607

P A

N E

L S

C H

E D

U L E

S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

Notes:

Total Est. Demand Current: 112 A

Total Conn. Current: 112 A

Receptacle 6180 VA 100.00% 6180 VA Total Est. Demand: 40170 VA

Other 31112 VA 100.00% 31112 VA Total Conn. Load: 40170 VA

Motor 3528 VA 100.00% 3528 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 128 A 106 A 102 A

Total Load: 15294 VA 12675 VA 12232 VA

41 42

39 40

37 38

35 0 VA 0 VA 36

Other 20 A 2

0 VA 0 VA 34

31 Motor 20 A 1 1176... 0 VA

3 20 A Other

29 Receptacle 20 A 1 360 VA 180 VA 1 20 A Receptacle 30

27 Receptacle 20 A 1 360 VA 360 VA 1 20 A Receptacle 28

25 360 VA 1 20 A Receptacle 26

23 0 VA 24

21 0 VA 0 VA 22

Other 20 A 3

0 VA 0 VA 20

17 2773... 0 VA

3 20 A Other

15 2773... 864 VA 1 20 A Other 16

Other 20 A 3

2773... 6733... 14

11 Other 20 A 1 864 VA 6733... 12

9 Other 20 A 1 864 VA 6733...

3 20 A Other

7 Motor 20 A 1 1176... 1560... 1 20 A Receptacle 8

5 Receptacle 20 A 1 360 VA 1176... 1 20 A Motor 6

3 Receptacle 20 A 1 360 VA 360 VA 1 20 A Receptacle 4

1 Receptacle 20 A 1 1560... 360 VA 1 20 A Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 150 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type:

Location: HANGAR BAY 000 Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: NLDR7

Notes:

Total Est. Demand Current: 84 A

Receptacle 5760 VA 100.00% 5760 VA Total Conn. Current: 84 A

HVAC 320 VA 100.00% 320 VA Total Est. Demand: 30360 VA

Other 21928 VA 100.00% 21928 VA Total Conn. Load: 30360 VA

Motor 2352 VA 100.00% 2352 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 91 A 79 A 85 A

Total Load: 10833 VA 9469 VA 10057 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 6733... 26

23 6733... 24

Other 20 A 3

6733... 22

19 0 VA 864 VA 1 20 A Other 20

17 0 VA 864 VA 1 20 A Other 18

Other 20 A 3

0 VA 0 VA 16

13 0 VA 0 VA 14

11 0 VA 0 VA

3 20 A Other

Other 20 A 3

0 VA 0 VA 10

7 Receptacle 20 A 1 1560... 0 VA 2 20 A Other

5 Receptacle 20 A 1 900 VA 1560... 1 20 A Receptacle 6

3 Motor 20 A 1 1176... 1560... 1 20 A Receptacle 4

1 20 A 1 500 VA 1176... 1 20 A Motor 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: HANGAR BAY 000 Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: NLDR8

Notes:

Total Est. Demand Current: 13 A

Total Conn. Current: 13 A

Total Est. Demand: 4620 VA

Total Conn. Load: 4620 VA

Receptacle 4620 VA 100.00% 4620 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 13 A 23 A 5 A

Total Load: 1440 VA 2640 VA 540 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 180 VA 1 20 A Receptacle 26

23 24

21 22

19 20

17 Receptacle 20 A 1 540 VA 18

15 1080... 1 20 A Receptacle 16

13 14

11 12

9 10

7 8

5 6

3 Receptacle 20 A 1 1560... 4

1 Receptacle 20 A 1 1260... 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 150 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type:

Location: LO STOR 128 Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: SL1R1

Notes:

Total Est. Demand Current: 43 A

Total Conn. Current: 57 A

Total Est. Demand: 15350 VA

Total Conn. Load: 20700 VA

Receptacle 20700 VA 74.15% 15350 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 62 A 48 A 66 A

Total Load: 7260 VA 5760 VA 7680 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 Receptacle 20 A 1 720 VA 22

19 Receptacle 20 A 1 1320... 20

17 Receptacle 20 A 1 1080... 1320... 1 20 A Receptacle 18

15 Receptacle 20 A 1 1080... 1080... 1 20 A Receptacle 16

13 Receptacle 20 A 1 540 VA 540 VA 1 20 A Receptacle 14

11 Receptacle 20 A 1 1080... 1080... 1 20 A Receptacle 12

9 Receptacle 20 A 1 540 VA 540 VA 1 20 A Receptacle 10

7 Receptacle 20 A 1 900 VA 1080... 1 20 A Receptacle 8

5 Receptacle 20 A 1 1560... 1560... 1 20 A Receptacle 6

3 Receptacle 20 A 1 720 VA 1080... 1 20 A Receptacle 4

1 Receptacle 20 A 1 1440... 1440... 1 20 A Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 150 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type:

Location: HANGAR BAY 000 Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: SL1R2

Notes:

Total Est. Demand Current: 53 A

Total Conn. Current: 78 A

Total Est. Demand: 18980 VA

Total Conn. Load: 27960 VA

Receptacle 27960 VA 67.88% 18980 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 95 A 79 A 63 A

Total Load: 11120 VA 9260 VA 7580 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 Receptacle 20 A 1 1560... 28

25 Receptacle 20 A 1 1260... 1560... 1 20 A Receptacle 26

23 Receptacle 20 A 1 540 VA 24

21 Receptacle 20 A 1 1080... 720 VA 1 20 A Receptacle 22

19 Receptacle 20 A 1 540 VA 720 VA 1 20 A Receptacle 20

17 Receptacle 20 A 1 1320... 1320... 1 20 A Receptacle 18

15 Receptacle 20 A 1 1320... 1320... 1 20 A Receptacle 16

13 Receptacle 20 A 1 1320... 1320... 1 20 A Receptacle 14

11 440 VA 1320... 1 20 A Receptacle 12

9 440 VA 1320... 1 20 A Receptacle 10

Receptacle 20 A 3

440 VA 1320... 1 20 A Receptacle 8

5 Receptacle 20 A 1 1320... 1320... 1 20 A Receptacle 6

3 Receptacle 20 A 1 180 VA 1320... 1 20 A Receptacle 4

1 Receptacle 20 A 1 1320... 1320... 1 20 A Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: ELEC 110 Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: SL1R3

Notes:

Total Est. Demand Current: 4 A

Total Conn. Current: 4 A

Total Est. Demand: 1440 VA

Total Conn. Load: 1440 VA

Receptacle 1440 VA 100.00% 1440 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 7 A 7 A 0 A

Total Load: 720 VA 720 VA 0 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 10

7 8

5 6

3 Receptacle 20 A 1 360 VA 360 VA 1 20 A Receptacle 4

1 Receptacle 20 A 1 360 VA 360 VA 1 20 A Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: COMM 114 Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: SL1T2

D E

S

IG

N

/2

P

M

E L

I

I R Y

N G

E S

I

D

NOT FOR

CONSTRUCTION

US Army Corps of Engineers

SHEET ID

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

X

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

M A

R K

D E

S C

R

IP

T

IO

N

D A

T E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

A

B

C

D

E

F

G

H

J

2 3 4 5 6 7 8 9 10 11 12

300 West Vine Street Suite 1500 Lexington, KY 40507

(859) 252-9980

Mason and Hanger

S N

A L L

W B

V -2

-D

-0

W B

V -2

-D

-0

EP608

P A

N E

L S

C H

E D

U L E

S

T

IN

K E

R A

IR

F

O R

C E

B A

S E

O

K

T U

L S

A D

IS

T

R

IC

T E

S

T S

T R

E E

T T

U L S

A O

K

-4

E N

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

E N

G

IN

E E

R

IN

G B

R A

N C

H

T C

R A

D D

O C

K

K A

P P

IA

J W

E D

E L

N O

V E

M B

E R

D

E S

IG

N

B O

M B

E R

A G

IL

E

C O

M M

O N

H A

N G

A R

W W

Y K

Notes:

Total Est. Demand Current: 41 A

Total Conn. Current: 55 A

Total Est. Demand: 14870 VA

Total Conn. Load: 19740 VA

Receptacle 19740 VA 75.33% 14870 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 53 A 62 A 50 A

Total Load: 6300 VA 7440 VA 6000 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 Receptacle 20 A 1 480 VA 360 VA 1 20 A Receptacle 18

15 Receptacle 20 A 1 720 VA 1080... 1 20 A Receptacle 16

13 Receptacle 20 A 1 960 VA 540 VA 1 20 A Receptacle 14

11 Receptacle 20 A 1 1560... 1440... 1 20 A Receptacle 12

9 Receptacle 20 A 1 1320... 1440... 1 20 A Receptacle 10

7 Receptacle 20 A 1 1080... 720 VA 1 20 A Receptacle 8

5 Receptacle 20 A 1 1440... 720 VA 1 20 A Receptacle 6

3 Receptacle 20 A 1 1920... 960 VA 1 20 A Receptacle 4

1 Receptacle 20 A 1 1440... 1560... 1 20 A Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A

Mounting: SURFACE Wires: 4 Mains Rating:

Supply From: Phases: 3 Mains Type: MCB

Location: CORRIDOR 007 Volts: 208Y/120V A.I.C. Rating: 35000

Branch Panel: NL1R3

Notes:

Total Est. Demand Current: 88 A

Receptacle 3480 VA 100.00% 3480 VA Total Conn. Current: 88 A

HVAC 900 VA 100.00% 900 VA Total Est. Demand: 31553 VA

Other 21928 VA 100.00% 21928 VA Total Conn. Load: 31553 VA

Motor…