This file contains detailed HVAC system design specifications and analysis for a Bomber Agile Common Hangar (BACH) project at Tinker Air Force Base, specifically documenting heating and cooling load calculations, system sizing, psychrometrics, and zone heat balance data for multiple air handling units (AHUs) and fan coil units (FCUs). The design calculations cover AHU-1 through AHU-4 and FCU-1 through FCU-7, with detailed specifications for each unit including supply air temperatures, airflow rates, ventilation requirements, fan performance, and zone-by-zone heating and cooling loads.

The technical specifications show the HVAC systems are sized for a facility with multiple zones requiring precise temperature and humidity control, with cooling supply temperatures generally at 55°F and heating supply temperatures ranging from 76-95°F. The calculations indicate significant cooling loads (up to 45.2 tons for AHU-4) and heating requirements, with detailed psychrometric analysis for both summer and winter design conditions. The systems utilize chilled water for cooling and hot water for heating, with chilled water supply temperature of 44°F and hot water supply temperature of 140°F. Fan systems are specified with total static pressures of 2.00-4.00 inches water gauge and various airflow rates sized for the specific zones they serve.

View the file

Other files

File Type Posted
WWYK263009_65 Design Analysis_Part12_Part2.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part6_Part1.pdf PDF
WWYK263009_65 Design Analysis_Part18_Part6.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part1.pdf PDF
WWYK263009_65 Design Analysis Part 28_Part3.pdf PDF
WWYK263009_65 Drawings_Volume 2_Part5.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part6_Part2.pdf PDF
WWYK263009_65_NG-LCCA_BLCC_Summary Report.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part4_Part7.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part4.pdf PDF
WWYK263009_65 Design Analysis_Part22_Part4_Part3.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part4_Part1.pdf PDF
WWYK263009_65 Design Analysis_Part17.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part19_Part3.pdf PDF
WWYK263009_65 Design Analysis_Part10.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part8.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part1.pdf PDF
WWYK263009_65_NG_energy model results.pdf PDF
Bomber Agile Common Hangar Industry Forum Presentation.pdf PDF
WWYK263009_65 Drawings_Volume 2_Part6.pdf PDF
WWYK263009_65 Design Analysis_Part22_Part4_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part18_Part2.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part4_Part4.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part7.pdf PDF
WWYK263009_65 Design Analysis_Part21.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part6_Part4_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part23.pdf PDF
WWYK263009_65 Design Analysis_Part22_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part4.pdf PDF
WWYK263009_65 Design Analysis_Part19_Part2.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part3.pdf PDF
WWYK263009_65 Design Analysis_Part20.pdf PDF
WWYK263009_65 Design Analysis Part 28_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part26.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part5.pdf PDF
WWYK263009_65 Design Analysis_Part19_Part4.pdf PDF
WWYK263009_65 Design Analysis_Part27.pdf PDF
WWYK263009_65 Design Analysis_Part18_Part5.pdf PDF
WWYK263009_65 Design Analysis_Part15.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part3.pdf PDF
WWYK263009_65 Design Analysis Part 28_Part4.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part9.pdf PDF
WWYK263009_65 Design Analysis_Part9.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part4.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part1.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part5.pdf PDF
WWYK263009_65_NG-LCCA_BLCC results.pdf PDF
WWYK263009_65 Design Analysis_Part7.pdf PDF
Show 40 more

Latest 50 of 95 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FCU-3 Input Data Project: TAFB BACH HAP6.2 11/04/2024

Prepared by: LARSON DESIGN GROUP 11:21 AM

Sizing Data:

Cooling Supply Temperature n/a F Supply Fan Airflow n/a CFM Ventilation Airflow n/a CFM Heating Supply Temperature n/a F

Hydronic Sizing Specifications:

Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F

Safety Factors:

Cooling Sensible 15 % Cooling Latent 10 % Heating 25 %

Zone Sizing Data:

Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads

5. Equipment Data Changeover Controller:

Used No

Hourly Analysis Program 6.2 Page 21 of 33

FCU-4 Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

1. General Details:

Air System Name FCU-4 Equipment Type Chilled Water AHU Air System Type Single Zone CAV Space Model: TAFB BACH Notes:

2. System Components:

Ventilation Air Data:

Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 0 %

Central Cooling Data:

Supply Air Temperature 55.0 F Cooling Source Chilled Water Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:

Supply Temperature 95.0 F Heating Source Hot Water Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:

Fan Type Forward Curved Configuration Draw-thru Fan Performance 2.00 in wg Overall Efficiency 54 %

Duct System Data:

Supply Duct Data:

Duct Leakage 0 %

Return Duct or Plenum Data:

Return Air Via Ducted Return

3. Zone Components:

Assigned Zones:

Zone Zone Name

1 FCU-4

Number of zones 1

Thermostats and Zone Data:

Zone

Cooling T-Stat Occ.

Cooling T-Stat Unocc.

Heating T-Stat Occ.

Heating T-Stat Unocc.

T-Stat Throttling

Range Diversity

Factor

Direct Exhaust

Fan

(F) (F) (F) (F) (F) (%) (kW)

All 76.0 82.0 69.0 65.0 1.00 100 0.0

Thermostat Schedule Default Fan/Thermostat Schedule Unoccupied Cooling is Available

Supply Terminals Data:

Zone Terminal Type Air

Distribution

Air Distribution

Effectiveness Specification

Air Distribution

Effectiveness Minimum Airflow

Design Supply Temp. Fan Perf.

Fan Efficiency

All Diffuser (no reheat)

Ceiling supply / ceiling return

Not Used - 765.0 CFM - - -

4. Sizing Data (Computer-Generated):

System Sizing Data:

Hourly Analysis Program 6.2 Page 22 of 33

FCU-4 Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

Sizing Data:

Cooling Supply Temperature n/a F Supply Fan Airflow n/a CFM Ventilation Airflow n/a CFM Heating Supply Temperature n/a F

Hydronic Sizing Specifications:

Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F

Safety Factors:

Cooling Sensible 15 % Cooling Latent 10 % Heating 25 %

Zone Sizing Data:

Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads

5. Equipment Data Changeover Controller:

Hourly Analysis Program 6.2 Page 23 of 33

FCU-5 Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

1. General Details:

Air System Name FCU-5 Equipment Type Chilled Water AHU Air System Type Single Zone CAV

Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 0 %

Central Cooling Data:

Supply Air Temperature 55.0 F Cooling Source Chilled Water Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:

Supply Temperature 95.0 F Heating Source Hot Water Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:

Fan Type Forward Curved Configuration Draw-thru Fan Performance 2.00 in wg Overall Efficiency 54 %

Duct System Data:

Supply Duct Data:

Duct Leakage 0 %

Return Duct or Plenum Data:

Return Air Via Ducted Return

3. Zone Components:

Assigned Zones:

Zone Zone Name

1 FCU-5

Number of zones 1

Thermostats and Zone Data:

Zone

Cooling T-Stat Occ.

Cooling T-Stat Unocc.

Heating T-Stat Occ.

Heating T-Stat Unocc.

T-Stat Throttling

Range Diversity

Factor

Direct Exhaust

Fan

(F) (F) (F) (F) (F) (%) (kW)

All 76.0 82.0 69.0 65.0 1.00 100 0.0

Thermostat Schedule Default Fan/Thermostat Schedule Unoccupied Cooling is Available

Supply Terminals Data:

Zone Terminal Type Air

Distribution

Air Distribution

Effectiveness Specification

Air Distribution

Effectiveness Minimum Airflow

Design Supply Temp. Fan Perf.

Fan Efficiency

All Diffuser (no reheat)

Ceiling supply / ceiling return

Not Used - 650.0 CFM - - -

4. Sizing Data (Computer-Generated):

Hourly Analysis Program 6.2 Page 24 of 33

FCU-5 Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

Sizing Data:

Cooling Supply Temperature n/a F Supply Fan Airflow n/a CFM Ventilation Airflow n/a CFM Heating Supply Temperature n/a F

Hydronic Sizing Specifications:

Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F

Safety Factors:

Cooling Sensible 15 % Cooling Latent 10 % Heating 25 %

Zone Sizing Data:

Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads

5. Equipment Data Changeover Controller:

Hourly Analysis Program 6.2 Page 25 of 33

FCU-6 Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

1. General Details:

Air System Name FCU-6 Equipment Type Chilled Water AHU Air System Type Single Zone CAV

Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 0 %

Central Cooling Data:

Supply Air Temperature 55.0 F Cooling Source Chilled Water Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:

Supply Temperature 95.0 F Heating Source Hot Water Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:

Fan Type Forward Curved Configuration Draw-thru Fan Performance 2.00 in wg Overall Efficiency 54 %

Duct System Data:

Supply Duct Data:

Duct Leakage 0 %

Return Duct or Plenum Data:

Return Air Via Ducted Return

3. Zone Components:

Assigned Zones:

Zone Zone Name

1 FCU-6

Number of zones 1

Thermostats and Zone Data:

Zone

Cooling T-Stat Occ.

Cooling T-Stat Unocc.

Heating T-Stat Occ.

Heating T-Stat Unocc.

T-Stat Throttling

Range Diversity

Factor

Direct Exhaust

Fan

(F) (F) (F) (F) (F) (%) (kW)

All 76.0 82.0 69.0 65.0 1.00 100 0.0

Thermostat Schedule Default Fan/Thermostat Schedule Unoccupied Cooling is Available

Supply Terminals Data:

Zone Terminal Type Air

Distribution

Air Distribution

Effectiveness Specification

Air Distribution

Effectiveness Minimum Airflow

Design Supply Temp. Fan Perf.

Fan Efficiency

All Diffuser (no reheat)

Ceiling supply / ceiling return

Not Used - 545.0 CFM - - -

4. Sizing Data (Computer-Generated):

Hourly Analysis Program 6.2 Page 26 of 33

FCU-6 Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

Sizing Data:

Cooling Supply Temperature n/a F Supply Fan Airflow n/a CFM Ventilation Airflow n/a CFM Heating Supply Temperature n/a F

Hydronic Sizing Specifications:

Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F

Safety Factors:

Cooling Sensible 15 % Cooling Latent 10 % Heating 25 %

Zone Sizing Data:

Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads

5. Equipment Data Changeover Controller:

Hourly Analysis Program 6.2 Page 27 of 33

FCU-7 Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

1. General Details:

Air System Name FCU-7 Equipment Type Chilled Water AHU Air System Type Single Zone CAV

Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 0 %

Central Cooling Data:

Supply Air Temperature 55.0 F Cooling Source Chilled Water Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:

Supply Temperature 95.0 F Heating Source Hot Water Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:

Fan Type Forward Curved Configuration Draw-thru Fan Performance 2.00 in wg Overall Efficiency 54 %

Duct System Data:

Supply Duct Data:

Duct Leakage 0 %

Return Duct or Plenum Data:

Return Air Via Ducted Return

3. Zone Components:

Assigned Zones:

Zone Zone Name

1 FCU-7

Number of zones 1

Thermostats and Zone Data:

Zone

Cooling T-Stat Occ.

Cooling T-Stat Unocc.

Heating T-Stat Occ.

Heating T-Stat Unocc.

T-Stat Throttling

Range Diversity

Factor

Direct Exhaust

Fan

(F) (F) (F) (F) (F) (%) (kW)

All 76.0 82.0 69.0 65.0 1.00 100 0.0

Thermostat Schedule Default Fan/Thermostat Schedule Unoccupied Cooling is Available

Supply Terminals Data:

Zone Terminal Type Air

Distribution

Air Distribution

Effectiveness Specification

Air Distribution

Effectiveness Minimum Airflow

Design Supply Temp. Fan Perf.

Fan Efficiency

All Diffuser (no reheat)

Ceiling supply / ceiling return

Not Used - 545.0 CFM - - -

4. Sizing Data (Computer-Generated):

Hourly Analysis Program 6.2 Page 28 of 33

FCU-7 Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

Sizing Data:

Cooling Supply Temperature n/a F Supply Fan Airflow n/a CFM Ventilation Airflow n/a CFM Heating Supply Temperature n/a F

Hydronic Sizing Specifications:

Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F

Safety Factors:

Cooling Sensible 15 % Cooling Latent 10 % Heating 25 %

Zone Sizing Data:

Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads

5. Equipment Data Changeover Controller:

Hourly Analysis Program 6.2 Page 29 of 33

Mini Splits Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

1. General Details:

Air System Name Mini Splits Equipment Type Split AHU Air System Type Single Zone CAV

Airflow Control Constant Ventilation Airflow Ventilation Sizing Method Sum of Space OA Airflows Unocc. Damper Position Closed Damper Leak Rate 0 %

Central Cooling Data:

Supply Air Temperature 58.0 F Cooling Source Air-Cooled DX Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Central Heating Data:

Supply Temperature 95.0 F Heating Source Air Source Heat Pump Schedule JFMAMJJASOND Capacity Control Cycled or Staged Capacity - Fan On

Supply Fan Data:

Fan Type Forward Curved Configuration Draw-thru Fan Performance 2.00 in wg Overall Efficiency 54 % Fan Control 1-speed, cooling and heating

Duct System Data:

Supply Duct Data:

Duct Leakage 0 %

Return Duct or Plenum Data:

Return Air Via Ducted Return

3. Zone Components:

Assigned Zones:

Zone Zone Name

1 Mini Splits

Number of zones 1

Thermostats and Zone Data:

Zone

Cooling T-Stat Occ.

Cooling T-Stat Unocc.

Heating T-Stat Occ.

Heating T-Stat Unocc.

T-Stat Throttling

Range Diversity

Factor

Direct Exhaust

Fan

(F) (F) (F) (F) (F) (%) (kW)

All 75.0 80.0 70.0 65.0 1.50 100 0.0

Thermostat Schedule Default Fan/Thermostat Schedule Unoccupied Cooling is Available

Supply Terminals Data:

Zone Terminal Type Air

Distribution

Air Distribution

Effectiveness Specification

Air Distribution

Effectiveness Minimum Airflow

Design Supply Temp. Fan Perf.

Fan Efficiency

All Diffuser (no reheat)

Ceiling supply / ceiling return

Not Used - 0.00 CFM/person - - -

4. Sizing Data (Computer-Generated):

Hourly Analysis Program 6.2 Page 30 of 33

Mini Splits Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

System Sizing Data:

Sizing Data:

Cooling Supply Temperature n/a F Supply Fan Airflow n/a CFM Ventilation Airflow n/a CFM Heating Supply Temperature n/a F

Hydronic Sizing Specifications:

Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F

Safety Factors:

Cooling Sensible 15 % Cooling Latent 10 % Heating 25 %

Zone Sizing Data:

Zone Airflow Sizing Method Sum of space airflow rates Space Airflow Sizing Method Individual peak space loads

5. Equipment Data Central Cooling Unit - Air-Cooled DX Design OADB 95.0 F Design EWB 67.0 F Equipment Sizing Auto-Sized Capacity Oversizing Factor 0 % AHRI Performance Rating 11.000 EER DX System Configuration 1-stage, 1 compressor, 1 circuit Low Temperature Cutoff OAT 0.0 F

Central Heating Unit - ASHP Design OADB 47.0 F Design EDB 70.0 F Equipment Sizing Auto-Sized Capacity Oversizing Factor 0 % AHRI Performance Rating 3.300 COP Cutoff OAT -15.0 F Auxiliary Heating:

Auxiliary Heating Type Electric Resistance Auxiliary Heating Upper Cutoff 40.0 F

Hourly Analysis Program 6.2 Page 31 of 33

Unit Heaters Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

1. General Details:

Air System Name Unit Heaters Equipment Type Terminal Units Air System Type 2-Pipe Fan Coil Space Model: TAFB BACH Ventilation Direct Ventilation

2. Dedicated Outdoor Air System Components:

(Dedicated Outdoor Air System not used: no inputs)

3. Zone Components:

Assigned Zones:

Zone Zone Name

1 Heating Only Spaces

Number of zones 1

Thermostats and Zone Data:

Zone

Cooling T-Stat Occ.

Cooling T-Stat Unocc.

Heating T-Stat Occ.

Heating T-Stat Unocc.

T-Stat Throttling

Range Diversity

Factor

Direct Exhaust

Fan

(F) (F) (F) (F) (F) (%) (kW)

All 75.0 80.0 60.0 55.0 1.00 n/a 0.0

Thermostat Schedule Default Fan/Thermostat Schedule Unoccupied Cooling is Available

Common Terminal Unit Data:

Cooling Coil:

Not Used

Heating Coil:

Design Supply Temp. 73.0 F Heating Source Hot Water Schedule JFMAMJJASOND

Fan Control 1-Speed Fan Ventilation Sizing Method Sum of Space OA Airflows

Terminal Units Data:

Zone Terminal Type Air

Distribution

Air Distribution

Effectiveness Specification

Air Distribution

Effectiveness Minimum Airflow

Design Supply Temp. Fan Perf.

Fan Efficiency

All Fan coil Ceiling supply / ceiling return

Not Used - 0.00 CFM/person - 0.25 in wg 50 %

4. Sizing Data (Computer-Generated):

System Sizing Data:

Sizing Data:

Heating Supply Temperature n/a F

Hydronic Sizing Specifications:

Chilled Water Supply Temperature 44.0 F Chilled Water Delta-T 10.0 F Hot Water Supply Temperature 140.0 F Hot Water Delta-T 20.0 F

Safety Factors:

Cooling Sensible 15 % Cooling Latent 10 % Heating 25 %

Zone Sizing Data:

Zone Airflow Sizing Method Sum of space airflow rates

Hourly Analysis Program 6.2 Page 32 of 33

Unit Heaters Input Data

Prepared by: LARSON DESIGN GROUP 11:21 AM

Space Airflow Sizing Method Individual peak space loads

5. Equipment Data No equipment data required for this system.

Hourly Analysis Program 6.2 Page 33 of 33

Proposed Building BACH Input Data

Prepared by: LARSON DESIGN GROUP 11:24 AM

1. General Details:

Name Proposed Building BACH Energy Sim. Status Needs Recalculation Baseline-90° Status Not Calculated Baseline-180° Status Not Calculated Baseline-270° Status Not Calculated

2. Plants Included in this Alternative:

Plant Name Design Sizing Energy Simulation

Proposed Boiler Plant Needs Recalculation Not Calculated

Proposed Chiller Plant Needs Recalculation Needs Recalculation

Summary Needs Recalculation Needs Recalculation

3. Air Systems Included in this Alternative:

Air System # Zones

AHU-1 8

AHU-2 5

AHU-3 4

AHU-4 21

FCU-1&2 1

FCU-3 1

FCU-4 1

FCU-5 1

FCU-6 1

FCU-7 1

Unit Heaters 1

AHU-A 1

AHU-B 1

AHU-C 1

AHU-D 1

Mini Splits 1

4. Space Models Included in this Alternative:

Summary Calculation Status:

Design Sizing Needs Recalculation Energy Simulation Not Calculated

Space Model: TAFB BACH (for TAFB BACH) Design Sizing Needs Recalculation Energy Simulation Not Calculated

Zone Air System

1-01 AHU-1

1-02 AHU-1

1-03 AHU-1

1-04 AHU-1

1-05 AHU-1

1-06 AHU-1

1-07 AHU-1

1-08 AHU-1

2-01 AHU-2

2-02 AHU-2

2-03 AHU-2

2-04 AHU-2

2-05 AHU-2

3-01 AHU-3

3-02 AHU-3

3-03 AHU-3

3-04 AHU-3

Hourly Analysis Program 6.2 Page 1 of 2

Proposed Building BACH Input Data

Prepared by: LARSON DESIGN GROUP 11:24 AM

4-01 AHU-4

4-02 AHU-4

4-03 AHU-4

4-04 AHU-4

4-05 AHU-4

4-06 AHU-4

4-07 AHU-4

4-08 AHU-4

4-09 AHU-4

4-10 AHU-4

4-11 AHU-4

4-12 AHU-4

4-13 AHU-4

4-14 AHU-4

4-15 AHU-4

4-16 AHU-4

4-17 AHU-4

4-18 AHU-4

4-19 AHU-4

4-20 AHU-4

4-21 AHU-4

FCU-1&2 FCU-1&2

FCU-3 FCU-3

FCU-4 FCU-4

FCU-5 FCU-5

FCU-6 FCU-6

FCU-7 FCU-7

Hangar Bay - A AHU-A

Hangar Bay - B AHU-B

Hangar Bay - C AHU-C

Hangar Bay - D AHU-D

Heating Only Spaces Unit Heaters

Mini Splits Mini Splits

5. Miscellaneous Energy (no items defined)

6. Meters Electric Oklahoma - EIA 2022 Natural Gas Gas Rate Oklahoma - EIA 2022

7. Miscellaneous Data Average Building Power Factor 100.00 % Source Electric Generating Efficiency 28.00 % Additional Floor Area 0.0 sqft

Hourly Analysis Program 6.2 Page 2 of 2

Building Load Calculations

Air System Sizing Summary for AHU-1 (In Alternative: Proposed Building BACH)

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Air System Information Air System Name AHU-1 Equipment Class CW AHU Air System Type VAV

Number of zones 8 Floor Area 11707.4 sqft Location Tinker Afb, OK, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data Total coil load 23.1 Tons Total coil load 276.9 MBH Sensible coil load 236.8 MBH Coil CFM at peak load 8041 CFM Sum of peak zone CFM 8487 CFM Sensible heat ratio 0.855 CFM/Ton 348.4 sqft/Ton 507.3 BTU/(hr sqft) 23.7 Water flow @ 10.0 F rise 55.42 gpm

Peak coil load occurs at August 15:00

OA DB / WB 100.4 / 73.5 F

Entering DB / WB 80.2 / 64.1 F Leaving DB / WB 52.2 / 52.1 F Resulting RH 45 % Design supply temp. 55.0 F Zone T-stat Check 8 of 8 OK Max zone temperature deviation 0.0 F

Supply Fan Sizing Data Design CFM 8436 CFM Design CFM occurs at August 16:00 Design CFM/sqft 0.72 CFM/sqft Sum of peak zone CFM 8487 CFM VAV Fan Diversity 0.6 %

Fan motor BHP 9.24 BHP Fan motor kW 7.33 kW Fan total static 4.00 in wg

Outdoor Ventilation Air Data Design airflow CFM 1369 CFM CFM/sqft 0.12 CFM/sqft

CFM/person 31.65 CFM/person

Hourly Analysis Program 6.2 Page 1 of 81

Zone Sizing Summary for AHU-1

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Air System Information Air System Name AHU-1 Equipment Class CW AHU Air System Type VAV

Number of zones 8 Floor Area 11707.4 sqft Location Tinker Afb, OK, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

1-01 485 194 0.95 8.0 0.80 0.0 0.00 0

1-02 1392 557 0.72 26.1 2.61 0.0 0.00 0

1-03 981 392 0.90 26.1 2.61 0.0 0.00 0

1-04 959 384 0.59 19.6 1.96 0.0 0.00 0

1-05 1219 488 0.66 28.2 2.82 0.0 0.00 0

1-06 420 168 0.82 6.9 0.69 0.0 0.00 0

1-07 1716 686 0.92 46.3 4.63 0.0 0.00 0

1-08 1316 526 0.56 44.3 4.43 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

1-01 10.5 August 17:00 2.3 509.8

1-02 30.1 September 16:00 17.0 1927.2

1-03 21.2 September 15:00 16.9 1089.8

1-04 20.7 August 14:00 12.7 1634.2

1-05 26.4 September 15:00 18.3 1837.5

1-06 9.1 August 17:00 2.6 512.4

1-07 37.1 August 15:00 30.1 1861.3

1-08 28.5 August 16:00 28.8 2335.3

Hourly Analysis Program 6.2 Page 2 of 81

Zone Sizing Summary for AHU-1

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

1-01

119 DOCK OFFICE 8.4 August 17:00 386 1.6 425.7 0.91

127A MT 2.2 September 16:00 100 0.6 84.2 1.19

1-02

118A CORRIDOR 7.4 September 16:00 341 3.0 794.5 0.43

118VEST. 2.3 August 17:00 108 0.8 110.0 0.98

121 MENS 5.3 August 17:00 245 1.8 390.6 0.63

122 JAN 1.2 September 16:00 54 0.4 48.2 1.13

123 WOMENS 3.4 September 16:00 156 1.4 284.6 0.55

124 WELL 2.0 September 16:00 92 0.7 96.5 0.95

126 VEST. 8.9 September 15:00 409 8.9 202.7 2.02

1-03

107 PSC 18.3 August 15:00 845 15.7 942.2 0.90

107A Corridor 3.0 September 16:00 139 1.3 147.6 0.94

1-04

105 CORRIDOR 11.3 August 14:00 520 10.9 1129.9 0.46

108 DOCK OFFICE 9.6 August 17:00 445 1.8 504.3 0.88

1-05

104 TOOL CRIB 26.4 September 15:00 1219 18.3 1837.5 0.66

1-06

103 TOOL CHECKOUT 5.9 August 17:00 271 1.7 368.3 0.74

104C TC OFFICE 3.2 August 16:00 149 0.9 144.1 1.03

1-07

104A COMPOSITE 37.1 August 15:00 1716 30.1 1861.3 0.92

1-08

100 VEST. 2.2 August 16:00 101 0.7 75.1 1.34

100A CORRIDOR 7.5 August 15:00 346 8.5 306.4 1.13

101 FOM STORAGE 14.3 August 16:00 658 17.7 1547.6 0.43

101A FOM OFF. 4.6 July 16:00 215 1.8 406.3 0.53

Hourly Analysis Program 6.2 Page 3 of 81

Air System Heat Balance Summary for AHU-1

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Table 1. System Loads

DESIGN COOLING - JULY 15:00 DESIGN HEATING

OA DB / WB 100.4 F / 73.5 F OA DB / WB 0.0 F / 0.0 F

COMPONENT LOADS Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Zone Conditioning - 171761 17183 - 111344 0

Plenum Load - 0 0 - 0 0

Return Fan Load 7198 CFM 0 - 7356 CFM 0 -

Ventilation Load 1369 CFM 34312 21664 1369 CFM 92923 0

Supply Fan Load 7786 CFM 23282 - 7944 CFM -23721 -

Zone Fan Coil Fans Load - 0 - - 0 -

>> Total System Loads - 229356 38847 - 180545 0

Central Cooling Coil - 230468 40062 - -21279 0

Terminal Reheat Coils - 0 - - 202183 -

>> Total Conditioning - 230468 40062 - 180904 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Table 2. Zone Heat Balance Loads

DESIGN COOLING - JULY 15:00 DESIGN HEATING

OA DB / WB 100.4 F / 73.5 F OA DB / WB 0.0 F / 0.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 3113 sqft 10011 - 3113 sqft 10254 -

Roof Convection 4185 sqft 11713 - 4185 sqft 10613 -

Window Convection 572 sqft 4624 - 572 sqft 6969 -

Skylight Convection 0 sqft 0 - 0 sqft 0 -

Door Convection 337 sqft 1721 - 337 sqft 2266 -

Floor Convection 11707 sqft 19410 - 11707 sqft 22653 -

Interior Wall Convection 29727 sqft 47829 - 29727 sqft 21439 -

Ceiling Convection 7517 sqft 0 - 7517 sqft 0 -

Overhead Lighting Convection 8399 W 15837 - 0 W 0 -

Task Lighting Convection 0 W 0 - 0 W 0 -

Electric Equipment Convection 11958 W 30603 - 0 W 0 -

People Convection 43 3329 11367 0 0 0

Infiltration 325 CFM 8353 3467 404 CFM 28818 0

Miscellaneous Equipment - 0 0 - 0 0

Air Internal Energy Change - 0 - 0 0

Safety Factor 15% / 10% 23015 1483 25% 25753 0

>> Total Zone Loads - 176445 16318 - 128765 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room air. Therefore, the effect of solar heat gain is found in the surface convection line items.

Hourly Analysis Program 6.2 Page 4 of 81

System Psychrometrics for AHU-1

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

DESIGN COOLING DAY AT AUGUST 15:00

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 100.3 0.01244 1369 400 34312 21734

Vent - Return Mixing Outlet 80.2 0.00972 8041 700 - -

Central Cooling Coil Outlet 52.2 0.00865 8041 700 236797 40146

Supply Fan Outlet 55.0 0.00865 8041 700 23987 -

Cold Supply Duct Outlet 55.0 0.00865 8041 700 - -

Zone Air - 76.0 0.00909 7453 751 177385 17198

Zone Direct Exhaust Outlet 76.0 0.00865 588 699 - -

Return Air Outlet 76.0 0.00916 7453 762 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.031 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4529.3 BTU/(hr-CFM) Site Altitude = 1291.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

1-01 10125 Cooling 10132 76.0 459 894 0 0

1-02 27818 Cooling 27818 76.0 1262 699 0 0

1-03 21004 Cooling 21022 76.0 952 852 0 0

1-04 19913 Cooling 19923 76.0 903 787 0 0

1-05 25969 Cooling 25985 76.0 1178 761 0 0

1-06 8533 Cooling 8535 76.0 387 760 0 0

1-07 36659 Cooling 36676 76.0 1663 740 0 0

1-08 27287 Cooling 27294 76.0 1238 690 0 0

Hourly Analysis Program 6.2 Page 5 of 81

System Psychrometrics for AHU-1

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 0.0 0.00082 1369 400 -92923 0

Vent - Return Mixing Outlet 54.7 0.00082 7944 400 - -

Central Cooling Coil Outlet 52.1 0.00082 7944 400 21279 0

Supply Fan Outlet 55.0 0.00082 7944 400 23721 -

Cold Supply Duct Outlet 55.0 0.00082 7944 400 - -

Zone Air - 66.2 0.00082 7356 400 -111344 0

Zone Direct Exhaust Outlet 65.5 0.00082 588 400 - -

Return Air Outlet 66.1 0.00082 7356 400 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.031 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4529.3 BTU/(hr-CFM) Site Altitude = 1291.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

1-01 -3032 Heating -3032 69.0 194 400 5842 0

1-02 -52405 Heating -10929 65.5 1392 400 26107 0

1-03 -33847 Heating -14777 66.1 981 400 26055 0

1-04 -38936 Heating -9280 65.4 959 400 19569 0

1-05 -47185 Heating -15303 65.2 1219 400 28217 0

1-06 -3333 Heating -3333 69.0 168 400 5766 0

1-07 -63555 Heating -26742 66.0 1716 400 46321 0

1-08 -56806 Heating -27947 67.0 1316 400 44307 0

Hourly Analysis Program 6.2 Page 6 of 81

Air System Sizing Summary for AHU-2

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Air System Information Air System Name AHU-2 Equipment Class CW AHU Air System Type VAV

Number of zones 5 Floor Area 7115.9 sqft Location Tinker Afb, OK, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data Total coil load 14.7 Tons Total coil load 176.2 MBH Sensible coil load 144.3 MBH Coil CFM at peak load 4515 CFM Sum of peak zone CFM 4858 CFM Sensible heat ratio 0.819 CFM/Ton 307.5 sqft/Ton 484.6 BTU/(hr sqft) 24.8 Water flow @ 10.0 F rise 35.26 gpm

Peak coil load occurs at July 15:00

OA DB / WB 100.4 / 73.5 F

Entering DB / WB 82.5 / 65.5 F Leaving DB / WB 52.2 / 52.1 F Resulting RH 46 % Design supply temp. 55.0 F Zone T-stat Check 5 of 5 OK Max zone temperature deviation 0.0 F

Supply Fan Sizing Data Design CFM 4829 CFM Design CFM occurs at July 16:00 Design CFM/sqft 0.68 CFM/sqft Sum of peak zone CFM 4858 CFM VAV Fan Diversity 0.6 %

Fan motor BHP 5.29 BHP Fan motor kW 4.20 kW Fan total static 4.00 in wg

Outdoor Ventilation Air Data Design airflow CFM 1205 CFM CFM/sqft 0.17 CFM/sqft

CFM/person 35.94 CFM/person

Hourly Analysis Program 6.2 Page 7 of 81

Zone Sizing Summary for AHU-2

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Air System Information Air System Name AHU-2 Equipment Class CW AHU Air System Type VAV

Number of zones 5 Floor Area 7115.9 sqft Location Tinker Afb, OK, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

2-01 1224 490 0.99 27.5 2.75 0.0 0.00 0

2-02 914 366 0.88 21.5 2.15 0.0 0.00 0

2-03 710 284 0.51 19.2 1.92 0.0 0.00 0

2-04 1515 606 0.64 48.2 4.83 0.0 0.00 0

2-05 495 198 0.46 13.3 1.33 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

2-01 26.5 July 14:00 17.9 1230.4

2-02 19.8 July 15:00 13.9 1032.7

2-03 11.3 July 16:00 12.5 1401.2

2-04 32.8 July 16:00 31.4 2365.6

2-05 9.1 July 17:00 8.6 1086.1

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

2-01

026 DLA/IPV 19.3 July 14:00 892 12.6 921.6 0.97

027 VEST. 2.3 July 20:00 106 0.8 85.2 1.24

028 CORRIDOR 5.0 July 14:00 232 4.5 223.6 1.04

2-02

025 COMPOSITE 19.8 July 15:00 914 13.9 1032.7 0.88

2-03

018 VEST. 1.0 July 19:00 64 0.5 85.8 0.75

019 CORRIDOR 1.7 June 16:00 107 1.2 335.8 0.32

020 JAN 1.1 July 18:00 67 0.5 90.3 0.74

022 MENS 3.5 July 17:00 221 1.9 460.6 0.48

023 WOMENS 2.5 July 16:00 155 4.6 337.1 0.46

024 VEST. 1.5 July 16:00 97 3.8 91.7 1.05

2-04

007 CORRIDOR 14.7 July 15:00 679 22.2 1524.7 0.45

012 DOCK OFFICE 18.1 July 17:00 837 9.1 840.9 1.00

2-05

008 DOCK OFFICE 5.0 July 18:00 269 2.1 467.4 0.57

009 MENS 1.5 July 16:00 80 1.1 302.3 0.26

010 JAN 0.2 July 17:00 13 0.2 43.9 0.28

011 WOMENS 2.5 July 16:00 134 5.2 272.4 0.49

Hourly Analysis Program 6.2 Page 8 of 81

Air System Heat Balance Summary for AHU-2

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Table 1. System Loads

DESIGN COOLING - JULY 15:00 DESIGN HEATING

OA DB / WB 100.4 F / 73.5 F OA DB / WB 0.0 F / 0.0 F

COMPONENT LOADS Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Zone Conditioning - 99931 13612 - 70601 0

Plenum Load - 0 0 - 0 0

Return Fan Load 3467 CFM 0 - 3631 CFM 0 -

Ventilation Load 1205 CFM 33817 19578 1205 CFM 73485 0

Supply Fan Load 4515 CFM 13489 - 4829 CFM -14327 -

Zone Fan Coil Fans Load - 0 - - 0 -

>> Total System Loads - 147238 33190 - 129759 0

Central Cooling Coil - 144284 31923 - 0 0

Terminal Reheat Coils - 0 - - 129615 -

>> Total Conditioning - 144284 31923 - 129615 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Table 2. Zone Heat Balance Loads

DESIGN COOLING - JULY 15:00 DESIGN HEATING

OA DB / WB 100.4 F / 73.5 F OA DB / WB 0.0 F / 0.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 2017 sqft 3846 - 2017 sqft 6305 -

Roof Convection 7116 sqft 15488 - 7116 sqft 16435 -

Window Convection 0 sqft 0 - 0 sqft 0 -

Skylight Convection 0 sqft 0 - 0 sqft 0 -

Door Convection 595 sqft 2166 - 595 sqft 4006 -

Floor Convection 7116 sqft 8071 - 7116 sqft 13614 -

Interior Wall Convection 21676 sqft 25168 - 21676 sqft 12075 -

Ceiling Convection 0 sqft 0 - 0 sqft 0 -

Overhead Lighting Convection 4781 W 9684 - 0 W 0 -

Task Lighting Convection 0 W 0 - 0 W 0 -

Electric Equipment Convection 5710 W 14613 - 0 W 0 -

People Convection 34 2540 8125 0 0 0

Infiltration 169 CFM 4337 1771 210 CFM 14965 0

Miscellaneous Equipment - 0 0 - 0 0

Air Internal Energy Change - 0 - 0 0

Safety Factor 15% / 10% 12887 990 25% 16850 0

>> Total Zone Loads - 98801 10886 - 84249 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 9 of 81

System Psychrometrics for AHU-2

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

DESIGN COOLING DAY AT JULY 15:00

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 100.3 0.01244 1205 400 33817 19578

Vent - Return Mixing Outlet 82.5 0.01016 4515 683 - -

Central Cooling Coil Outlet 52.2 0.00865 4515 683 144284 31923

Supply Fan Outlet 55.0 0.00865 4515 683 13489 -

Cold Supply Duct Outlet 55.0 0.00865 4515 683 - -

Zone Air - 76.1 0.00929 3467 737 99931 13612

Zone Direct Exhaust Outlet 76.3 0.00926 1205 649 - -

Return Air Outlet 76.0 0.00933 3467 786 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.031 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4529.3 BTU/(hr-CFM) Site Altitude = 1291.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

2-01 25379 Cooling 25396 76.0 1151 812 0 0

2-02 19419 Cooling 19432 76.0 881 777 0 0

2-03 13491 Cooling 13498 76.3 603 632 0 0

2-04 31665 Cooling 31683 76.0 1436 770 0 0

2-05 9907 Cooling 9911 76.2 445 674 0 0

Hourly Analysis Program 6.2 Page 10 of 81

System Psychrometrics for AHU-2

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 0.0 0.00082 1205 400 -73485 0

Vent - Return Mixing Outlet 43.8 0.00082 4829 400 - -

Central Cooling Coil Outlet 43.8 0.00082 4829 400 0 0

Supply Fan Outlet 46.7 0.00082 4829 400 14327 -

Cold Supply Duct Outlet 46.7 0.00082 4829 400 - -

Zone Air - 58.7 0.00082 3631 400 -70601 0

Zone Direct Exhaust Outlet 58.8 0.00082 1205 400 - -

Return Air Outlet 58.4 0.00082 3631 400 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.031 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4529.3 BTU/(hr-CFM) Site Altitude = 1291.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

2-01 -132871 Heating -14297 57.1 1217 400 27464 0

2-02 -100025 Heating -11701 57.0 908 400 21453 0

2-03 -99016 Heating -10006 59.2 706 400 19162 0

2-04 -156834 Heating -27216 60.2 1506 400 48244 0

2-05 -78658 Heating -7391 58.3 492 400 13291 0

Hourly Analysis Program 6.2 Page 11 of 81

Air System Sizing Summary for AHU-3

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Air System Information Air System Name AHU-3 Equipment Class CW AHU Air System Type VAV

Number of zones 4 Floor Area 5959.8 sqft Location Tinker Afb, OK, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data Total coil load 15.8 Tons Total coil load 189.2 MBH Sensible coil load 157.2 MBH Coil CFM at peak load 5012 CFM Sum of peak zone CFM 5220 CFM Sensible heat ratio 0.831 CFM/Ton 317.9 sqft/Ton 378.1 BTU/(hr sqft) 31.7 Water flow @ 10.0 F rise 37.85 gpm

Peak coil load occurs at July 16:00

OA DB / WB 100.4 / 73.5 F

Entering DB / WB 82.0 / 65.1 F Leaving DB / WB 52.2 / 52.1 F Resulting RH 46 % Design supply temp. 55.0 F Zone T-stat Check 4 of 4 OK Max zone temperature deviation 0.0 F

Supply Fan Sizing Data Design CFM 5220 CFM Design CFM occurs at July 16:00 Design CFM/sqft 0.88 CFM/sqft Sum of peak zone CFM 5220 CFM VAV Fan Diversity 0.0 %

Fan motor BHP 5.72 BHP Fan motor kW 4.54 kW Fan total static 4.00 in wg

Outdoor Ventilation Air Data Design airflow CFM 1233 CFM CFM/sqft 0.21 CFM/sqft

CFM/person 61.66 CFM/person

Hourly Analysis Program 6.2 Page 12 of 81

Zone Sizing Summary for AHU-3

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Air System Information Air System Name AHU-3 Equipment Class CW AHU Air System Type VAV

Number of zones 4 Floor Area 5959.8 sqft Location Tinker Afb, OK, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

3-01 1286 514 0.85 29.0 2.90 0.0 0.00 0

3-02 1005 402 0.89 23.7 2.37 0.0 0.00 0

3-03 1104 442 0.88 26.0 2.60 0.0 0.00 0

3-04 1826 730 0.89 43.2 4.33 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

3-01 27.8 July 16:00 18.8 1519.4

3-02 21.7 July 16:00 15.4 1128.2

3-03 23.9 July 16:00 16.9 1254.9

3-04 39.5 July 16:00 28.1 2057.4

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

3-01

006 SHEET METAL 27.8 July 16:00 1286 18.8 1519.4 0.85

3-02

005 TIRE (OPEN) SHOP 21.7 July 16:00 1005 15.4 1128.2 0.89

3-03

004 ENGINE SHOP 23.9 July 16:00 1104 16.9 1254.9 0.88

3-04

001 VEST. 2.3 July 19:00 106 0.8 86.1 1.23

002 CORRIDOR 5.5 July 16:00 253 4.8 243.2 1.04

003 LANDING GEAR SHOP 31.8 July 16:00 1470 22.5 1728.1 0.85

Hourly Analysis Program 6.2 Page 13 of 81

Air System Heat Balance Summary for AHU-3

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Table 1. System Loads

DESIGN COOLING - JULY 15:00 DESIGN HEATING

OA DB / WB 100.4 F / 73.5 F OA DB / WB 0.0 F / 0.0 F

COMPONENT LOADS Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Zone Conditioning - 110023 12997 - 65588 0

Plenum Load - 0 0 - 0 0

Return Fan Load 4987 CFM 0 - 5220 CFM 0 -

Ventilation Load 1233 CFM 30907 17994 1233 CFM 71523 0

Supply Fan Load 4987 CFM 14873 - 5220 CFM -15489 -

Zone Fan Coil Fans Load - 0 - - 0 -

>> Total System Loads - 155803 30990 - 121622 0

Central Cooling Coil - 156786 31961 - 0 0

Terminal Reheat Coils - 0 - - 121903 -

>> Total Conditioning - 156786 31961 - 121903 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Table 2. Zone Heat Balance Loads

DESIGN COOLING - JULY 15:00 DESIGN HEATING

OA DB / WB 100.4 F / 73.5 F OA DB / WB 0.0 F / 0.0 F

Zone Heat Balance Component Details Sensible [BTU/hr]

Latent [BTU/hr]

Details Sensible [BTU/hr]

Latent [BTU/hr]

Exterior Wall Convection 1869 sqft 4429 - 1869 sqft 5778 -

Roof Convection 5960 sqft 17615 - 5960 sqft 14904 -

Window Convection 0 sqft 0 - 0 sqft 0 -

Skylight Convection 0 sqft 0 - 0 sqft 0 -

Door Convection 427 sqft 1792 - 427 sqft 2839 -

Floor Convection 5960 sqft 9950 - 5960 sqft 13263 -

Interior Wall Convection 11041 sqft 20418 - 11041 sqft 7821 -

Ceiling Convection 0 sqft 0 - 0 sqft 0 -

Overhead Lighting Convection 5053 W 7446 - 0 W 0 -

Task Lighting Convection 0 W 0 - 0 W 0 -

Electric Equipment Convection 11261 W 28818 - 0 W 0 -

People Convection 20 1770 9100 0 0 0

Infiltration 212 CFM 5445 2242 263 CFM 18785 0

Miscellaneous Equipment - 0 0 - 0 0

Air Internal Energy Change - 0 - 0 0

Safety Factor 15% / 10% 14652 1134 25% 15847 0

>> Total Zone Loads - 112336 12476 - 79237 0

Key:

Positive values are cooling loads Negative values are heating loads

Positive values are heating loads Negative values are cooling loads

Note 1: Surface convection line items show the combined effects of conductive heat gain to the surface and radiative heat gains absorbed at the surface which are then convected to room air.

Note 2: Lighting, equipment, and people line items include only the direct convective heat gain from the heat source to the room air. The radiative portion of the heat gain is first absorbed by surfaces in the room and then later convected from the surface to the air.

Therefore the effect of the radiative portion of the heat gain is found in the surface convection line items.

Note 3: Solar heat gain is absorbed by surfaces in the room, re-radiated to other surfaces, and finally convected from the surfaces to room

Hourly Analysis Program 6.2 Page 14 of 81

System Psychrometrics for AHU-3

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

DESIGN COOLING DAY AT JULY 16:00

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 100.2 0.01244 1233 400 30759 18027

Vent - Return Mixing Outlet 82.0 0.01001 5012 602 - -

Central Cooling Coil Outlet 52.2 0.00864 5012 602 157243 31926

Supply Fan Outlet 55.0 0.00864 5012 602 14940 -

Cold Supply Duct Outlet 55.0 0.00864 5012 602 - -

Zone Air - 76.0 0.00921 5012 668 110565 12953

Return Air Outlet 76.0 0.00922 5012 668 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.031 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4529.3 BTU/(hr-CFM) Site Altitude = 1291.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

3-01 27334 Cooling 27348 76.0 1240 669 0 0

3-02 21342 Cooling 21355 76.0 968 690 0 0

3-03 23444 Cooling 23458 76.0 1063 682 0 0

3-04 38388 Cooling 38404 76.0 1741 647 0 0

Hourly Analysis Program 6.2 Page 15 of 81

System Psychrometrics for AHU-3

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent Temp Humidity Airflow CO2 Level Heat Heat Component Location (F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)

Ventilation Air Inlet 0.0 0.00082 1233 400 -71523 0

Vent - Return Mixing Outlet 43.0 0.00082 5220 400 - -

Central Cooling Coil Outlet 43.0 0.00082 5220 400 0 0

Supply Fan Outlet 45.8 0.00082 5220 400 15489 -

Cold Supply Duct Outlet 45.8 0.00082 5220 400 - -

Zone Air - 56.3 0.00082 5220 400 -65588 0

Return Air Outlet 56.3 0.00082 5220 400 - -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.031 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4529.3 BTU/(hr-CFM) Site Altitude = 1291.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone Sensible Zone Zone Zone CO2 Heating Heating Load T-stat Cond Temp Airflow Level Coil Unit Zone Name (BTU/hr) Mode (BTU/hr) (F) (CFM) (ppm) (BTU/hr) (BTU/hr)

3-01 -149337 Heating -15557 55.9 1286 400 28977 0

3-02 -116231 Heating -12965 56.1 1005 400 23670 0

3-03 -126596 Heating -14200 56.2 1104 400 26008 0

3-04 -207385 Heating -22874 56.6 1826 400 43249 0

Hourly Analysis Program 6.2 Page 16 of 81

Air System Sizing Summary for AHU-4

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Air System Information Air System Name AHU-4 Equipment Class CW AHU Air System Type VAV

Number of zones 21 Floor Area 16195.6 sqft Location Tinker Afb, OK, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data Total coil load 45.2 Tons Total coil load 542.4 MBH Sensible coil load 449.1 MBH Coil CFM at peak load 15724 CFM Sum of peak zone CFM 16424 CFM Sensible heat ratio 0.828 CFM/Ton 347.9 sqft/Ton 358.3 BTU/(hr sqft) 33.5 Water flow @ 10.0 F rise 108.54 gpm

Peak coil load occurs at August 15:00

OA DB / WB 100.4 / 73.5 F

Entering DB / WB 79.3 / 64.2 F Leaving DB / WB 52.2 / 52.1 F Resulting RH 47 % Design supply temp. 55.0 F Zone T-stat Check 21 of 21 OK Max zone temperature deviation 0.0 F

Supply Fan Sizing Data Design CFM 16354 CFM Design CFM occurs at August 15:00 Design CFM/sqft 1.01 CFM/sqft Sum of peak zone CFM 16424 CFM VAV Fan Diversity 0.4 %

Fan motor BHP 17.92 BHP Fan motor kW 14.21 kW Fan total static 4.00 in wg

Outdoor Ventilation Air Data Design airflow CFM 2133 CFM CFM/sqft 0.13 CFM/sqft

CFM/person 8.78 CFM/person

Hourly Analysis Program 6.2 Page 17 of 81

Zone Sizing Summary for AHU-4

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Air System Information Air System Name AHU-4 Equipment Class CW AHU Air System Type VAV

Number of zones 21 Floor Area 16195.6 sqft Location Tinker Afb, OK, USA

Sizing Calculation Information Calculation Months Jan to Dec Sizing Data Calculated

Zone CFM Sizing Peak zone sensible load Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Zone Name

Design Supply Airflow

(CFM)

Minimum Supply Airflow

(CFM)

Zone CFM/sqft

Reheat Coil

Capacity

(MBH)

Reheat Coil

Water gpm

@ 20.0 F

Zone Htg Unit

Coil Capacity

(MBH)

Zone Htg Unit Water gpm

@ 20.0 F

Mixing Box Fan Airflow

(CFM)

4-01 767 307 3.29 17.5 1.75 0.0 0.00 0

4-02 751 300 1.80 12.4 1.24 0.0 0.00 0

4-03 496 198 1.18 15.4 1.54 0.0 0.00 0

4-04 629 252 1.14 10.4 1.04 0.0 0.00 0

4-05 1707 683 0.79 48.1 4.81 0.0 0.00 0

4-06 1575 630 0.73 26.0 2.60 0.0 0.00 0

4-07 457 183 1.01 17.8 1.78 0.0 0.00 0

4-08 1145 458 1.53 41.9 4.19 0.0 0.00 0

4-09 817 327 0.72 33.3 3.34 0.0 0.00 0

4-10 673 269 0.73 19.3 1.93 0.0 0.00 0

4-11 1350 540 0.99 55.6 5.57 0.0 0.00 0

4-12 291 116 1.07 9.6 0.96 0.0 0.00 0

4-13 812 325 0.96 18.1 1.81 0.0 0.00 0

4-14 327 131 0.80 5.4 0.54 0.0 0.00 0

4-15 492 197 1.25 15.8 1.58 0.0 0.00 0

4-16 508 203 1.24 19.7 1.97 0.0 0.00 0

4-17 469 188 1.61 19.3 1.93 0.0 0.00 0

4-18 626 250 1.50 25.8 2.58 0.0 0.00 0

4-19 1081 433 0.92 17.8 1.78 0.0 0.00 0

4-20 1057 423 0.95 29.5 2.95 0.0 0.00 0

4-21 396 158 1.21 8.5 0.85 0.0 0.00 0

Hourly Analysis Program 6.2 Page 18 of 81

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Zone Peak Sensible Loads

Zone Zone Zone

Cooling Time of Heating Floor

Sensible Peak Sensible Load Area

Zone Name (MBH) Cooling Load (MBH) (sqft)

4-01 16.6 August 16:00 11.3 233.5

4-02 16.2 August 17:00 5.6 416.9

4-03 10.7 August 15:00 10.0 419.4

4-04 13.6 August 16:00 5.1 553.4

4-05 36.9 August 15:00 31.3 2148.2

4-06 34.1 August 15:00 8.7 2149.2

4-07 9.9 August 17:00 11.6 450.2

4-08 24.8 August 15:00 27.2 746.4

4-09 17.7 August 17:00 21.7 1138.1

4-10 14.6 August 16:00 12.5 926.7

4-11 28.2 August 15:00 36.2 1368.9

4-12 6.3 August 15:00 6.3 272.7

4-13 17.6 August 15:00 11.8 845.0

4-14 7.1 August 16:00 2.5 407.9

4-15 10.6 August 15:00 10.3 394.0

4-16 11.0 August 16:00 12.8 409.6

4-17 8.8 August 15:00 12.6 291.7

4-18 13.0 August 14:00 16.8 416.5

4-19 23.4 August 15:00 5.6 1170.3

4-20 22.9 August 15:00 19.2 1110.9

4-21 8.6 August 18:00 5.5 326.0

Hourly Analysis Program 6.2 Page 19 of 81

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Space Loads and Airflows

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

4-01

218J CONF 16.6 August 16:00 767 11.3 233.5 3.29

4-02

218I CONF 16.2 August 17:00 751 5.6 416.9 1.80

4-03

218E OFFICE 3.7 August 15:00 170 4.3 139.2 1.22

218F OFFICE 3.4 August 15:00 155 1.3 137.8 1.13

218G OFFICE 3.7 August 15:00 170 4.4 142.3 1.20

4-04

218A OFFICE 3.4 August 16:00 158 1.3 138.9 1.14

218B OFFICE 3.4 August 16:00 158 1.3 138.7 1.14

218C OFFICE 3.4 August 16:00 157 1.3 138.5 1.14

218D OFFICE 3.4 August 15:00 156 1.3 137.2 1.14

4-05

218 AMXS (1) 36.9 August 15:00 1707 31.3 2148.2 0.79

4-06

218 AMXS (2) 26.3 August 15:00 1217 7.4 2017.4 0.60

218H COPY 7.8 August 14:00 358 1.3 131.9 2.72

4-07

214 RECEPTION 3.3 August 17:00 153 3.7 211.0 0.72

214A DEPUTY 3.1 August 17:00 145 2.5 117.7 1.23

214B DEPUTY 3.5 August 16:00 159 5.4 121.5 1.31

4-08

215 BRK 24.8 August 15:00 1145 27.2 746.4 1.53

4-09

201 CORRIDOR 7.5 August 17:00 345 11.2 661.6 0.52

211 JAN 1.2 August 17:00 55 1.2 40.8 1.34

212 WOMENS 4.6 August 17:00 212 4.8 250.0 0.85

213 STOR 1.2 August 17:00 58 1.2 42.7 1.35

216 M 1.6 August 17:00 73 1.6 71.1 1.03

217 W 1.6 August 17:00 74 1.7 71.9 1.03

4-10

205 STOR 3.6 August 16:00 168 2.0 167.9 1.00

210 MENS 5.2 August 18:00 239 6.0 335.2 0.71

219 CORRIDOR 5.8 August 16:00 269 4.5 423.6 0.63

4-11

209 SCHED OFF 28.2 August 15:00 1350 36.2 1368.9 0.99

4-12

209A OFFICE 2.5 August 16:00 116 1.5 130.8 0.89

209B OFFICE 3.8 August 15:00 175 4.8 141.9 1.23

4-13

206 CTR TRNG 17.6 August 15:00 812 11.8 845.0 0.96

4-14

203 SFTWR 7.1 August 16:00 327 2.5 407.9 0.80

4-15

202K COLLAB 10.6 August 15:00 492 10.3 394.0 1.25

4-16

202B OFFICE 3.7 August 16:00 170 4.3 137.4 1.24

202C OFFICE 3.7 August 16:00 169 4.3 136.8 1.24

202D OFFICE 3.7 August 16:00 169 4.2 135.4 1.25

4-17

202E OFFICE 3.7 August 16:00 198 4.4 140.4 1.41

202F OFFICE 5.1 August 14:00 270 8.2 151.3 1.79

4-18

Hourly Analysis Program 6.2 Page 20 of 81

Project: TAFB BACH HAP6.2 10/25/2024

Prepared by: LARSON DESIGN GROUP 8:37 AM

Zone Name / Space Name

Cooling Sensible

(MBH)

Time of Peak

Sensible Load

Air Flow

(CFM)

Heating Load

(MBH)

Floor Area (sqft)

Space CFM/sqft

202H OFFICE 3.9 August 13:00 185 4.5 138.9 1.33

202I OFFICE 3.8 August 13:00 182 4.3 134.9 1.35

202J OFFICE 5.4 August 15:00 259 8.0 142.7 1.81

4-19

202 OPEN OFFICE (1) 16.0 August 15:00 738 3.8 1046.6 0.71

202G COPY/FILE 7.6 August 13:00 349 1.8 123.7 2.82

4-20

202 OPEN OFFICE (2) 22.9 August 15:00 1057 19.2 1110.9 0.95

4-21

214C COMMAND SUITE 8.6 August 18:00 396 5.5 326.0 1.21

Hourly Analysis Program 6.2 Page 21 of 81

Air System Heat Balance Summary for AHU-4

Project: TAFB…