The document outlines specific cybersecurity controls including user account types definition (AC-2), session lock requirements after defined periods of inactivity (AC-11), and wireless access restrictions (AC-18). Key requirements include implementing authentication for users/devices accessing wireless systems, establishing configuration and connection requirements for wireless access, and maintaining session locks until proper authentication procedures are completed. The controls are categorized as either "Designer" implementation items, "DoD-Defined Enclave" requirements, or "Designer Impractical" designations, with references to specific UFGS (Unified Facilities Guide Specifications) sections for implementation guidance.
View the file
Other files
Show 40 more
Latest 50 of 95 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Johnson Controls
Form 150.72-EG6 (1023)
Five and six fan isolator locations YLAA0100Sx, YLAA0120Sx, YLAA0092Hx, YLAA0101Hx
Isolator locations, continued
Eight fan isolator locations YLAA0125Hx, YLAA 0136Sx, YLAA0155Sx, YLAA0139Hx
TOP
VIEW
LD18439
TOP
VIEW
LD18440
All dimensions are inches unless otherwise specified.
Dimensions indicate isolator mounting centerlines.
Johnson Controls 39
Ten fan isolator locations YLAA 0170Sx, YLAA0156Hx, YLAA0175Hx
Twelve fan isolator locations YLAA0200Hx, YLAA0230Hx
Isolator locations, continued
TOP
VIEW
LD18441
LD21040
TOP
VIEW
All dimensions are inches unless otherwise specified.
Dimensions indicate isolator mounting centerlines.
Isolator details, continued 2 in. deflection spring isolator
3/4”3/4”
7/8”7/8”
3/8”3/8” GAPGAP
3/4” 3/4”
TYP. (4)TYP. (4)
5/8”5/8” 2-3/4”2-3/4”
1-1/8”1-1/8”
2-3/4”2-3/4”
PP
STOP &STOP &
8-3/8”8-3/8”
OPER.OPER.
HEIGHTHEIGHT
* Weight range Model part number Color lb kg Up to 391 Up to 177 029-25336-006
(688690) Green
392 to 604 178 to 274 029-25336-008 (688691)
Dark brown
605 to 740 275 to 336 029-25336-009 (688692)
Red
741 to 1,020 337 to 463 029-25336-010 (688693)
Red/Black
1,021 to 1,437 464 to 652 029-25336-011 (688694)
Pink
1,438 to 2,244 653 to 1,018 029-25336-012 (688695)
Pink/Gray
2,245 to 2,618 1,019 to 1,188 029-25336-013 (688697)
Pink/Gray/Orange
2,619 to 3,740 1,189 to 1,696 029-25336-014 (688698)
Pink/Gray/Dark brown
* Value is de-rated by 15%
Notes:
1. All dimensions are in inches, interpret in accordance with ANSI Y14.
2. Equipment must be bolted or welded to the top plate to meet allowable seismic ratings.
3. All springs are designed for 50% overload capacity with exception of the 029-25336-013 and 029-25336-014.
4. Consult Johnson Controls for concrete installation.
Table 6 - 2 in. deflection spring isolator weight and color
Johnson Controls 41
LD18443
Isolator details, continued
1 in. deflection spring isolator
Mount type
Dimension data, in.
W D L B C T H
Type A 3 5/8 7 3/4 6 1/2 4 3/4 1/2 5 5/8 Type B 3 5/8 10 1/2 9 1/4 7 3/4 9/16 6
Type A model part number
Color code Rated capacity for units with all load points less than 1,785 lb (810 kg) lb kg
029-25334-002 (433668)
Black Up to 434 Up to 197
029-25334-003 (433669)
Dark green 435 to 765 198 to 347
029-25334-004 (433670)
Gray 766 to 1,020 348 to 463
029-25334-005 (433871)
White 1,021 to 1,156 464 to 524
029-25334-006 (433872)
Gray/Red 1,157 to 1,785 525 to 810
Type B model part number
Color code Rated capacity for units with any load point above 1,518 lb (689 kg) lb kg
029-25334-008 (433997)
Dark purple Up to 1148 Up to 521
029-25334-009 (433998)
Dark green 1,149 to 1,530 522 to 694
029-25334-010 (433999)
Gray 1,531 to 2,040 695 to 925
029-25334-012 (434000)
White 2,041 to 2,312 926 to 1,049
029-25334-013 (434001)
Gray/Red 2,313 to 3,570 1,050 to 1,619
Table 7 - 1 in. deflection spring isolator dimensions
Table 8 - 1 in. deflection spring isolator weight and color
Isolator details, continued Elastomeric isolator specifications
LD17304
CDCD
HFHF
BT
BT
AL
L
AL
L
W
W
DW
DW
MOLDED
DURULENEMOLDED
DURULENE
R = 0.280 Slot Typ 2 Places
Ø = AD Thru Typ 2 Places
Model part number Dimension data, in. (mm)
L W HF AL AD BT CD DW
Type A 029-25335-001 (434002)
5.50 (139.7)
3.38 (85.85)
2.88 (73.15)
4.13 (104.90)
0.56 (14.22)
0.25 (6.35)
1/2-13 UNC X 1
(M27 X 3)
2.50 (63.50)
Type B 029-25335-002 (434004) Type B 029-25335-004 (434005)
6.25 (158.75)
4.63 (117.6)
2.75 (69.85)
5.00 (127.00)
0.56 (14.22)
0.38 (9.65)
1/2-13 UNC X 1
(M27 X 3)
3.00 (76.20)
Model part number Isolator color Weight range lb kg 029-25335-001 (434002) Charcoal Up to 825 Up to 374
029-25335-002 (434004) Brick red 826 to 1,688 375 to 766
029-25335-004 (434005) Charcoal 1,689 to 4,000 767 to 1,814
Table 9 - Elastomeric isolator dimensions
Table 10 - Elastomeric isolator dimensions, weight, and color
Johnson Controls 43
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per NEC Article 430-24. If the optional factory mounted control transformer is provided, add the following MCA values to the electrical tables for the system providing power to the transformer:
• -17, add 2.5 amps
• -28, add 2.3 amps
• -40, add 1.5 amps
• -46, add 1.3 amps
• -58, add 1 amps
2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included in the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not recommended in applica-tions where brown outs, frequent starting and stopping of the unit, and/or operation at ambient temperatures in excess of 95ºF (35ºC) is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest mo-tor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 440-22.
5. Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Otherwise, HACR-type circuit break-ers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit.
6. The incoming wire range is the minimum and maximum wire size that can be ac-commodated by the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires per phase must be determined based on the NEC, using copper connectors only. Field wiring must also comply with local codes.
7. A ground lug is provided for each compressor system to accommodate a field grounding conductor per NEC, Table 250-95. A control circuit grounding lug is also supplied.
8. The supplied disconnect is a disconnecting means as defined in the NEC 100, and is intended for isolating the unit for the available power supply to perform main-tenance and troubleshooting. This disconnect is not intended to be a load break device.
9. Field wiring by others which complies to the NEC and local codes.
Notes:
Electrical notes
Legend
ACR-LINE Across the line start C.B. Circuit breaker D.E. Dual element fuse DISC SW Disconnect switch FACT MOUNT CB Factory mounted circuit breaker FLA Full load amps HZ Hertz MAX Maximum MCA Minimum circuit ampacity MIN Minimum MIN NF Minimum non-fused RLA Rated load amps S.P. WIRE Single point wiring UNIT MTD SERV SW Unit mounted service (non-fused disconnect switch) LRA Locked rotor amps
Voltage code -17 = 208-3-60 -28 = 230-3-60 -40 = 380-3-60 -46 = 460-3-60 -58 = 575-3-60
Electrical notes, continued
Johnson Controls 45
Pump Horse power rpm 208 V-3-60 Hz 230 V-3-60 Hz 380 V-3-60 Hz 460 V-3-60 Hz 575 V-3-60 Hz
FLA LRA FLA LRA FLA LRA FLA LRA FLA LRA
A 5 3,600 15.4 4.6 13 3.9 7.9 2.4 6.5 2 5.2 1.6 B 7.5 3,600 23.2 7 18.4 5.5 11.1 3.3 9.2 2.8 7.4 2.2 C 10 3,600 28.3 8.5 24 7.2 15.1 4.5 12 3.6 9.6 2.9 D 3 1,800 9.5 2.9 8 2.4 4.7 1.4 4 1.2 3.2 1 E 15 3,600 43 12.9 36.4 10.9 22 6.6 18.2 5.5 14.6 4.4 F 7.5 3,600 23.2 7 18.4 5.5 11.1 3.3 9.2 2.8 7.4 2.2 G 10 3,600 28.3 8.5 24 7.2 15.1 4.5 12 3.6 9.6 2.9 H 15 3,600 43 12.9 36.4 10.9 22 6.6 18.2 5.5 14.6 4.4 I 5 1,800 15.4 4.6 13 3.9 7.9 2.4 6.5 2 5.2 1.6 J 15 3,600 43 12.9 36.4 10.9 22 6.6 18.2 5.5 14.6 4.4 K 20 3,600 54 16.2 45 13.5 28.7 8.6 22.5 6.8 18 5.4 L 3 1,800 9.5 2.9 8 2.4 4.7 1.4 4 1.2 3.2 1 M 10 3,600 23.2 7 18.4 5.5 11.1 3.3 9.2 2.8 7.4 2.2 N 20 3,600 54 16.2 45 13.5 28.7 8.6 22.5 6.8 18 5.4 P 5 1,800 15.4 4.6 13 3.9 7.9 2.4 6.5 2 5.2 1.6 R 15 3,600 43 12.9 36.4 10.9 22 6.6 18.2 5.5 14.6 4.4 S 3 3,600 9.5 2.9 8 2.4 4.7 1.4 4 1.2 3.2 1 T 5 3,600 15.4 4.6 13 3.9 7.9 2.4 6.5 2 5.2 1.6 U 10 3,600 28.3 8.5 24 7.2 15.1 4.5 12 3.6 9.6 2.9 V 10 1,800 28.3 8.5 24 7.2 15.1 4.5 12 3.6 9.6 2.9
V kVA 2 3
208 9.6 14.4 230 8.7 13.0 380 5.3 7.9 460 4.3 6.5 575 3.5 5.2
Variable speed pump electrical data Table 11 - Variable speed pump electrical data
Table 12 - Control transformer load
YLAA Global market Single point supply terminal block
Molded case switch single point supply
Molded case circuit breaker single point supply
V Hz Installed lug Installed lug Alternate lug Installed lug Alternate lug
208 60 (1) # 6 - 500 — — (1) 4 - 300 — 230 60 (1) # 6 - 500 — — (1) 4 - 300 — 380 60 (1) # 6 - 500 — — (1) 4 - 300 — 460 60 (1) # 6 - 500 — — (1) 4 - 300 — 575 60 (1) # 6 - 500 — — (1) 4 - 300 —
208 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 230 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 380 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 — 460 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 — 575 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 —
208 60 (1) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 230 60 (1) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 380 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 — 460 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 — 575 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 —
208 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 230 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 380 60 (1) # 6 - 500 (1) 250 - 500 (2) 3/0 - 250 (1) 6 - 350 — 460 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 — 575 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 —
208 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 230 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 380 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 — 460 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 — 575 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 —
208 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 230 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 380 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (1) 6 - 350 — 460 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 — 575 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 —
208 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (3) 2/0 - 400 (2) 250 - 500 230 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (3) 2/0 - 400 (2) 250 - 500 380 60 (1) # 6 - 500 (1) 250 - 500 (2) 3/0 - 250 (2) 3/0 - 250 (1) 250 - 500 460 60 (1) # 6 - 500 (1) 250 - 500 (2) 3/0 - 250 (1) 6 - 350 — 575 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 —
208 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 230 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 380 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 460 60 (1) # 6 - 500 (1) 250 - 500 (2) 3/0 - 250 (1) 6 - 350 — 575 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 —
208 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 230 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 380 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 460 60 (1) # 6 - 500 (1) 250 - 500 (2) 3/0 - 250 (1) 6 - 350 — 575 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 —
Wiring lugs
Note: Alternate lugs are available in the panel for field electricians and contractors, if other lug arrangements are necessary for the installed lugs on the non-fused disconnect switch and circuit breaker panels.
Table 13 - Wiring lugs
Johnson Controls 47
YLAA Global market Single point supply terminal block
Molded case switch single point supply
Molded case circuit breaker single point supply
V Hz Installed lug Installed lug Alternate lug Installed lug Alternate lug
0100/0101
208 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 230 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 380 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 460 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 575 60 (1) # 6 - 500 (1) 6 - 350 — (1) 6 - 350 —
0120/0125
208 60 (2) # 6 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 230 60 (2) # 6 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 380 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 400/460 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 575 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500
208 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 230 60 — — — — — 380 60 (2) # 6 - 500 (3) 2/0 - 400 (2) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 400/460 60 (1) # 6 - 500 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 575 60 (1) # 6 - 500 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250
208 60 (3) 2/0 - 400 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 230 60 (3) 2/0 - 400 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 380 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 460 60 (2) # 6 - 500 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 575 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500
0150/0155/0156
208 60 (3) 2/0 - 400 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 230 60 (3) 2/0 - 400 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 380 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 400/460 60 (2) # 6 - 500 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 575 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500
0170/0175/0200
208 60 (4) 4/0 - 500 (4) 4/0 - 500 — (3) 2/0 - 400 (2) 250 - 500 230 60 (4) 4/0 - 500 (4) 4/0 - 500 — (3) 2/0 - 400 (2) 250 - 500 380 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 460 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 3/0 - 250 (1) 250 - 500 575 60 (1) # 6 - 500 (2) 3/0 - 250 (1) 250 - 500 (2) 3/0 - 250 (1) 250 - 500
208 60 (4) 4/0 - 500 (4) 4/0 - 500 — (4) 4/0 - 500 — 230 60 (4) 4/0 - 500 (4) 4/0 - 500 — (4) 4/0 - 500 — 460 60 (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400 (2) 250 - 500 (3) 2/0 - 400 575 60 (2) # 6 - 500 — — (2) 3/0 - 250 (1) 250 - 500
Wiring lugs, continued
Note: Alternate lugs are provided in the panel for field electricians and contractors, if other lug arrangements are necessary for the installed lugs on the non-fused disconnect switch and circuit breaker panels.
Table 12 - Wiring lugs, continued
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max.
dual elem.
CB
System 1 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 172 250 200 200 33.3 239 33.3 239 — — 2 7.6 44 230 60 171 250 200 200 33.3 239 33.3 239 — — 2 7.4 37 380 60 119 150 125 125 23.7 145 23.7 145 — — 2 4.5 23.1 460 60 92 150 100 100 17.9 125 17.9 125 — — 2 4 19 575 60 66 100 70 70 12.8 80 12.8 80 — — 2 2.9 15.3
208 60 248 400 250 250 51.3 300 51.3 300 — — 2 7.6 44 230 60 248 400 250 250 51.3 300 51.3 300 — — 2 7.4 37 380 60 137 200 150 150 28 139 28 139 — — 2 4.5 23.1 460 60 114 150 125 125 23.1 150 23.1 150 — — 2 4 19 575 60 96 150 110 110 19.9 109 19.9 109 — — 2 2.9 15.3
208 60 276 400 300 300 57.7 284 57.7 284 — — 2 7.6 44 230 60 275 400 300 300 57.7 330 57.7 330 — — 2 7.4 37 380 60 149 200 175 175 30.9 192 30.9 192 — — 2 4.5 23.1 460 60 130 200 150 150 26.9 180 26.9 180 — — 2 4 19 575 60 103 150 110 110 21.5 132 21.5 132 — — 2 2.9 15.3
208 60 306 400 350 350 48.5 249 48.5 249 48.5 249 2 7.6 44 230 60 305 400 350 350 48.5 288 48.5 288 48.5 288 2 7.4 37 380 60 170 250 200 200 27.6 159 27.6 159 27.6 159 2 4.5 23.1 460 60 150 200 175 175 24.4 145 24.4 145 24.4 145 2 4 19 575 60 112 150 125 125 17.4 109 17.4 109 17.4 109 2 2.9 15.3
208 60 334 400 350 350 48.5 249 48.5 249 48.5 249 2 7.6 44 230 60 333 400 350 350 48.5 249 48.5 249 48.5 249 2 7.4 37 380 60 191 250 225 225 27.6 159 27.6 159 27.6 159 2 4.5 23.1 460 60 169 200 175 175 24.4 145 24.4 145 24.4 145 2 4 19 575 60 120 150 125 125 17.4 109 17.4 109 17.4 109 2 2.9 15.3
208 60 363 600 400 400 57.7 284 57.7 284 57.7 284 2 7.6 44 230 60 363 600 400 400 57.7 330 57.7 330 57.7 330 2 7.4 37 380 60 201 250 225 225 30.9 192 30.9 192 30.9 192 2 4.5 23.1 460 60 177 250 200 200 26.9 180 26.9 180 26.9 180 2 4 19 575 60 134 200 150 150 21.5 132 21.5 132 21.5 132 2 2.9 15.3
208 60 363 400 400 400 57.7 284 57.7 284 57.7 284 2 7.6 44 230 60 363 400 400 400 57.7 330 57.7 330 57.7 330 2 7.4 37 380 60 201 250 225 225 30.9 192 30.9 192 30.9 192 2 4.5 23.1 460 60 177 250 200 200 26.9 180 26.9 180 26.9 180 2 4 19 575 60 134 200 150 150 21.5 132 21.5 132 21.5 132 2 2.9 15.3
Electrical data without pumps R-410A
Notes: 1. Reference PIN 59 for pump models.
2. Use this table along with Variable speed pump electrical data on page 45 to determine electrical data of the unit plus the pump.
3. Does not include the control transformer. See Table 12 on page 45.
Table 14 - Electrical data without pumps R-410A
Johnson Controls 49
Electrical data without pumps R-410A, continued
Notes: 1. Reference PIN 59 for pump models.
2. Use this table along with Variable speed pump electrical data on page 45 to determine electrical data of the unit plus the pump.
3. Does not include the control transformer. See Table 12 on page 45.
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max.
dual elem.
CB
System 1 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 391 600 450 450 57.7 284 57.7 284 57.7 284 2 7.6 44 230 60 390 600 450 450 57.7 330 57.7 330 57.7 330 2 7.4 37 380 60 211 250 250 250 30.9 192 30.9 192 30.9 192 2 4.5 23.1 460 60 184 250 200 200 26.9 180 26.9 180 26.9 180 2 4 19 575 60 146 200 150 150 21.5 132 21.5 132 21.5 132 2 2.9 15.3
208 60 406 600 450 450 57.7 284 57.7 284 57.7 284 3 7.6 44 230 60 405 600 450 450 57.7 330 57.7 330 57.7 330 3 7.4 37 380 60 220 400 250 250 30.9 192 30.9 192 30.9 192 3 4.5 23.1 460 60 192 250 225 225 26.9 180 26.9 180 26.9 180 3 4 19 575 60 152 200 150 150 21.5 132 21.5 132 21.5 132 3 2.9 15.3
208 60 450 600 500 500 57.7 284 57.7 284 57.7 284 2 7.6 44 230 60 449 600 500 500 57.7 330 57.7 330 57.7 330 2 7.4 37 380 60 260 400 300 300 30.9 192 30.9 192 30.9 192 2 4.5 23.1 460 60 220 400 250 250 26.9 180 26.9 180 26.9 180 2 4 19 575 60 175 250 200 200 21.5 132 21.5 132 21.5 132 2 2.9 15.3
208 60 458 600 500 500 57.7 284 57.7 284 57.7 284 2 7.6 44 230 60 456 600 500 500 57.7 330 57.7 330 57.7 330 2 7.4 37 380 60 264 400 300 300 30.9 192 30.9 192 30.9 192 2 4.5 23.1 460 60 224 400 250 250 26.9 180 26.9 180 26.9 180 2 4 19 575 60 178 250 200 200 21.5 132 21.5 132 21.5 132 2 2.9 15.3
208 60 497 800 600 600 106.2 523 106.2 523 — — 3 7.6 44 230 60 496 800 600 600 106.2 578 106.2 578 — — 3 7.4 37 380 60 300 400 350 350 64.3 355 64.3 355 — — 3 4.5 23.1 460 60 250 400 300 300 53.1 290 53.1 290 — — 3 4 19 575 60 198 250 225 225 42.5 255 42.5 255 — — 3 2.9 15.3
208 60 512 800 600 600 106.2 523 106.2 523 — — 4 7.6 44 230 60 511 800 600 600 106.2 578 106.2 578 — — 4 7.4 37 380 60 309 400 350 350 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 258 400 300 300 53.1 290 53.1 290 — — 4 4 19 575 60 204 250 225 225 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 579 800 600 600 106.2 523 106.2 523 106.2 523 4 7.6 44 230 60 577 800 600 600 106.2 578 106.2 578 106.2 578 4 7.4 37 380 60 338 600 400 400 64.3 355 64.3 355 64.3 355 4 4.5 23.1 460 60 285 400 300 300 53.1 290 53.1 290 53.1 290 4 4 19 575 60 226 400 250 250 42.5 255 42.5 255 42.5 255 4 2.9 15.3
Table 13 - Electrical data without pumps R-410A, continued
Notes: 1. Reference PIN 59 for pump models.
2. Use this table along with Variable speed pump electrical data on page 45 to determine electrical data of the unit plus the pump.
3. Does not include the control transformer. See Table 12 on page 45.
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max.
dual elem.
CB
System 1 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 555 800 600 600 85.1 394 85.1 394 85.1 394 4 7.6 44 230 60 553 800 600 600 85.1 436 85.1 436 85.1 436 4 7.4 37 380 60 329 400 350 350 49.3 252 49.3 252 49.3 252 4 4.5 23.1 460 60 274 400 300 300 40.7 212 40.7 212 40.7 212 4 4 19 575 60 217 400 250 250 32.6 168 32.6 168 32.6 168 4 2.9 15.3
208 60 618 800 700 700 106.2 523 106.2 523 106.2 523 4 7.6 44 230 60 617 800 700 700 106.2 578 106.2 578 106.2 578 4 7.4 37 380 60 374 600 400 400 64.3 355 64.3 355 64.3 355 4 4.5 23.1 460 60 311 400 350 350 53.1 290 53.1 290 53.1 290 4 4 19 575 60 246 400 300 300 42.5 255 42.5 255 42.5 255 4 2.9 15.3
208 60 634 800 700 700 106.2 523 106.2 523 106.2 523 6 7.6 44 230 60 632 800 700 700 106.2 578 106.2 578 106.2 578 6 7.4 37 380 60 383 600 400 400 64.3 355 64.3 355 64.3 355 6 4.5 23.1 460 60 319 400 350 350 53.1 290 53.1 290 53.1 290 6 4 19 575 60 252 400 300 300 42.5 255 42.5 255 42.5 255 6 2.9 15.3
208 60 740 1,000 800 800 106.2 523 106.2 523 106.2 523 5 7.6 44 230 60 738 1,000 800 800 106.2 578 106.2 578 106.2 578 5 7.4 37 380 60 447 600 500 500 64.3 355 64.3 355 64.3 355 5 4.5 23.1 460 60 372 600 400 400 53.1 290 53.1 290 53.1 290 5 4 19 575 60 295 400 350 350 42.5 255 42.5 255 42.5 255 5 2.9 15.3
208 60 740 1,000 800 800 106.2 523 106.2 523 106.2 523 5 7.6 44 230 60 738 1,000 800 800 106.2 578 106.2 578 106.2 578 5 7.4 37 380 60 447 600 500 500 64.3 355 64.3 355 64.3 355 5 4.5 23.1 460 60 372 600 400 400 53.1 290 53.1 290 53.1 290 5 4 19 575 60 295 400 350 350 42.5 255 42.5 255 42.5 255 5 2.9 15.3
208 60 734 1,000 800 800 102.8 574 102.8 574 102.8 574 6 7.6 44 230 60 731 1,000 800 800 102.8 635 102.8 635 102.8 635 6 7.4 37 380 60 443 600 500 500 62.2 355 62.2 355 62.2 355 6 4.5 23.1 460 60 369 600 400 400 51.4 280 51.4 280 51.4 280 6 4 19 575 60 292 400 300 300 41.1 225 41.1 225 41.1 225 6 2.9 15.3
208 60 959 1,200 1,000 1,000 138.8 943 138.8 943 138.8 943 6 7.6 44 230 60 956 1,200 1,000 1,000 138.8 943 138.8 943 138.8 943 6 7.4 37 380 60 599 800 600 600 87.2 564 87.2 564 87.2 564 6 4.5 23.1 460 60 504 600 600 600 73 408 73 408 73 408 6 4 19 575 60 359 600 400 400 51.9 375 51.9 375 51.9 375 6 2.9 15.3
Electrical data without pumps R-410A, continued
Johnson Controls 51
Notes: 1. Reference PIN 59 for pump models.
2. Use this table along with Variable speed pump electrical data on page 45 to determine electrical data of the unit plus the pump.
3. Does not include the control transformer. See Table 12 on page 45.
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max. dual elem. CB
System 2 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 172 250 200 200 33.3 239 33.3 239 — — 2 7.6 44 230 60 171 250 200 200 33.3 239 33.3 239 — — 2 7.4 37 380 60 119 150 125 125 23.7 145 23.7 145 — — 2 4.5 23.1 460 60 92 150 100 100 17.9 125 17.9 125 — — 2 4 19 575 60 66 100 70 70 12.8 80 12.8 80 — — 2 2.9 15.3
208 60 248 400 250 250 51.3 300 51.3 300 — — 2 7.6 44 230 60 248 400 250 250 51.3 300 51.3 300 — — 2 7.4 37 380 60 137 200 150 150 28 139 28 139 — — 2 4.5 23.1 460 60 114 150 125 125 23.1 150 23.1 150 — — 2 4 19 575 60 96 150 110 110 19.9 109 19.9 109 — — 2 2.9 15.3
208 60 276 400 300 300 57.7 284 57.7 284 — — 2 7.6 44 230 60 275 400 300 300 57.7 330 57.7 330 — — 2 7.4 37 380 60 149 200 175 175 30.9 192 30.9 192 — — 2 4.5 23.1 460 60 130 200 150 150 26.9 180 26.9 180 — — 2 4 19 575 60 103 150 110 110 21.5 132 21.5 132 — — 2 2.9 15.3
208 60 306 400 350 350 57.7 284 57.7 249 — — 2 7.6 44 230 60 305 400 350 350 57.7 330 57.7 288 — — 2 7.4 37 380 60 170 250 200 200 30.9 192 30.9 139 — — 2 4.5 23.1 460 60 150 200 175 175 26.9 180 26.9 180 — — 2 4 19 575 60 112 150 125 125 21.5 132 21.5 132 — — 2 2.9 15.3
208 60 334 400 350 350 48.5 249 48.5 249 48.5 249 2 7.6 44 230 60 333 400 350 350 48.5 249 48.5 249 48.5 249 2 7.4 37 380 60 191 250 225 225 27.6 159 27.6 159 27.6 159 2 4.5 23.1 460 60 169 200 175 175 24.4 145 24.4 145 24.4 145 2 4 19 575 60 120 150 125 125 17.4 109 17.4 109 17.4 109 2 2.9 15.3
208 60 363 600 400 400 48.5 249 48.5 249 48.5 249 2 7.6 44 230 60 363 600 400 400 48.5 288 48.5 288 48.5 288 2 7.4 37 380 60 201 250 225 225 27.6 159 27.6 159 27.6 159 2 4.5 23.1 460 60 177 200 200 200 24.4 145 24.4 145 24.4 145 2 4 19 575 60 134 150 150 150 17.4 109 17.4 109 17.4 109 2 2.9 15.3
208 60 363 400 400 400 48.5 249 48.5 249 48.5 249 2 7.6 44 230 60 363 400 400 400 48.5 288 48.5 288 48.5 288 2 7.4 37 380 60 201 250 225 225 27.6 159 27.6 159 27.6 159 2 4.5 23.1 460 60 177 200 200 200 24.4 145 24.4 145 24.4 145 2 4 19 575 60 134 150 150 150 17.4 109 17.4 109 17.4 109 2 2.9 15.3
Notes: 1. Reference PIN 59 for pump models.
2. Use this table along with Variable speed pump electrical data on page 45 to determine electrical data of the unit plus the pump.
3. Does not include the control transformer. See Table 12 on page 45.
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max. dual elem. CB
System 2 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 391 600 450 450 57.7 284 57.7 284 57.7 284 2 7.6 44 230 60 390 600 450 450 57.7 330 57.7 330 57.7 330 2 7.4 37 380 60 211 250 250 250 30.9 192 30.9 192 30.9 192 2 4.5 23.1 460 60 184 200 200 200 26.9 180 26.9 180 26.9 180 2 4 19 575 60 146 150 150 150 21.5 132 21.5 132 21.5 132 2 2.9 15.3
208 60 406 600 450 450 57.7 284 57.7 284 57.7 284 3 7.6 44 230 60 405 600 450 450 57.7 330 57.7 330 57.7 330 3 7.4 37 380 60 220 250 250 250 30.9 192 30.9 192 30.9 192 3 4.5 23.1 460 60 192 250 225 225 26.9 180 26.9 180 26.9 180 3 4 19 575 60 152 200 150 150 21.5 132 21.5 132 21.5 132 3 2.9 15.3
208 60 450 600 500 500 106.2 523 106.2 523 — — 3 7.6 44 230 60 449 600 500 500 106.2 578 106.2 578 — — 3 7.4 37 380 60 260 400 300 300 64.3 355 64.3 355 — — 3 4.5 23.1 460 60 220 250 250 250 53.1 290 53.1 290 — — 3 4 19 575 60 175 200 200 200 42.5 255 42.5 255 — — 3 2.9 15.3
208 60 458 600 500 500 106.2 523 106.2 523 — — 4 7.6 44 230 60 456 600 500 500 106.2 578 106.2 578 — — 4 7.4 37 380 60 264 400 300 300 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 224 250 250 250 53.1 290 53.1 290 — — 4 4 19 575 60 178 200 200 200 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 497 600 600 600 106.2 523 106.2 523 — — 3 7.6 44 230 60 496 600 600 600 106.2 578 106.2 578 — — 3 7.4 37 380 60 300 400 350 350 64.3 355 64.3 355 — — 3 4.5 23.1 460 60 250 400 300 300 53.1 290 53.1 290 — — 3 4 19 575 60 198 250 225 225 42.5 255 42.5 255 — — 3 2.9 15.3
208 60 512 600 600 600 106.2 523 106.2 523 — — 4 7.6 44 230 60 511 600 600 600 106.2 578 106.2 578 — — 4 7.4 37 380 60 309 400 350 350 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 258 400 300 300 53.1 290 53.1 290 — — 4 4 19 575 60 204 250 225 225 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 579 800 600 600 57.7 284 57.7 284 57.7 284 4 7.6 44 230 60 577 800 600 600 57.7 330 57.7 330 57.7 330 4 7.4 37 380 60 338 400 400 400 30.9 192 30.9 192 30.9 192 4 4.5 23.1 460 60 285 400 300 300 26.9 180 26.9 180 26.9 180 4 4 19 575 60 226 250 250 250 21.5 132 21.5 132 21.5 132 4 2.9 15.3
Johnson Controls 53
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max. dual elem. CB
System 2 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 555 800 600 600 106.2 523 106.2 523 — — 4 7.6 44 230 60 553 800 600 600 106.2 578 106.2 578 — — 4 7.4 37 380 60 329 400 350 350 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 274 400 300 300 53.1 290 53.1 290 — — 4 4 19 575 60 217 400 250 250 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 618 800 700 700 106.2 523 106.2 523 — — 4 7.6 44 230 60 617 800 700 700 106.2 578 106.2 578 — — 4 7.4 37 380 60 374 400 400 400 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 311 400 350 350 53.1 290 53.1 290 — — 4 4 19 575 60 246 400 300 300 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 634 800 700 700 106.2 523 106.2 523 — — 4 7.6 44 230 60 632 800 700 700 106.2 578 106.2 578 — — 4 7.4 37 380 60 383 400 400 400 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 319 400 350 350 53.1 290 53.1 290 — — 4 4 19 575 60 252 400 300 300 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 740 800 800 800 106.2 523 106.2 523 106.2 523 5 7.6 44 230 60 738 800 800 800 106.2 578 106.2 578 106.2 578 5 7.4 37 380 60 447 600 500 500 64.3 355 64.3 355 64.3 355 5 4.5 23.1 460 60 372 400 400 400 53.1 290 53.1 290 53.1 290 5 4 19 575 60 295 400 350 350 42.5 255 42.5 255 42.5 255 5 2.9 15.3
208 60 740 800 800 800 106.2 523 106.2 523 106.2 523 5 7.6 44 230 60 738 800 800 800 106.2 578 106.2 578 106.2 578 5 7.4 37 380 60 447 600 500 500 64.3 355 64.3 355 64.3 355 5 4.5 23.1 460 60 372 400 400 400 53.1 290 53.1 290 53.1 290 5 4 19 575 60 295 400 350 350 42.5 255 42.5 255 42.5 255 5 2.9 15.3
208 60 734 1,000 800 800 102.8 574 102.8 574 102.8 574 6 7.6 44 230 60 731 1,000 800 800 102.8 635 102.8 635 102.8 635 6 7.4 37 380 60 443 600 500 500 62.2 355 62.2 355 62.2 355 6 4.5 23.1 460 60 369 600 400 400 51.4 280 51.4 280 51.4 280 6 4 19 575 60 292 400 300 300 41.1 225 41.1 225 41.1 225 6 2.9 15.3
208 60 959 1,200 1,000 1,000 138.8 943 138.8 943 138.8 943 6 7.6 44 230 60 956 1,200 1,000 1,000 138.8 943 138.8 943 138.8 943 6 7.4 37 380 60 599 800 600 600 87.2 564 87.2 564 87.2 564 6 4.5 23.1 460 60 504 600 600 600 73 408 73 408 73 408 6 4 19 575 60 359 600 400 400 51.9 375 51.9 375 51.9 375 6 2.9 15.3
Notes: 1. Reference PIN 59 for pump models.
2. Use this table along with Variable speed pump electrical data on page 45 to determine electrical data of the unit plus the pump.
3. Does not include the control transformer. See Table 12 on page 45.
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max. dual elem. CB
System 1 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 172 250 200 200 33.3 255 33.3 255 — — 2 7.6 44 230 60 171 250 200 200 33.3 255 33.3 255 — — 2 7.4 37 380 60 95 150 110 110 18.1 172.8 18.1 172.8 — — 2 4.5 23.1 460 60 81 100 90 90 15.4 140 15.4 140 — — 2 4 19 575 60 66 100 70 70 12.9 107.6 12.9 107.6 — — 2 2.9 15.3
208 60 225 400 250 250 45.9 335.5 45.9 335.5 — — 2 7.6 44 230 60 225 400 250 250 45.9 335.5 45.9 335.5 — — 2 7.4 37 380 60 119 150 125 125 23.8 183 23.8 183 — — 2 4.5 23.1 460 60 104 150 110 110 20.6 141 20.6 141 — — 2 4 19 575 60 73 100 80 80 14.5 109 14.5 109 — — 2 2.9 15.3
208 60 276 400 300 300 57.7 284 57.7 284 — — 2 7.6 44 230 60 275 400 300 300 57.7 330 57.7 330 — — 2 7.4 37 380 60 149 200 175 175 30.9 192 30.9 192 — — 2 4.5 23.1 460 60 130 200 150 150 26.9 180 26.9 180 — — 2 4 19 575 60 103 150 110 110 21.5 132 21.5 132 — — 2 2.9 15.3
208 60 306 400 350 350 57.7 284 57.7 249 — — 2 7.6 44 230 60 305 400 350 350 57.7 330 57.7 288 — — 2 7.4 37 380 60 170 250 200 200 30.9 192 30.9 139 — — 2 4.5 23.1 460 60 150 200 175 175 26.9 180 26.9 180 — — 2 4 19 575 60 112 150 125 125 21.5 132 21.5 132 — — 2 2.9 15.3
208 60 334 400 350 350 48.5 249 48.5 249 48.5 249 2 7.6 44 230 60 333 400 350 350 48.5 249 48.5 249 48.5 249 2 7.4 37 380 60 191 250 225 225 27.6 159 27.6 159 27.6 159 2 4.5 23.1 460 60 169 200 175 175 24.4 145 24.4 145 24.4 145 2 4 19 575 60 120 150 125 125 17.4 109 17.4 109 17.4 109 2 2.9 15.3
208 60 363 600 400 400 48.5 249 48.5 249 48.5 249 2 7.6 44 230 60 363 600 400 400 48.5 288 48.5 288 48.5 288 2 7.4 37 380 60 201 250 225 225 27.6 159 27.6 159 27.6 159 2 4.5 23.1 460 60 177 200 200 200 24.4 145 24.4 145 24.4 145 2 4 19 575 60 134 150 150 150 17.4 109 17.4 109 17.4 109 2 2.9 15.3
208 60 363 400 400 400 48.5 249 48.5 249 48.5 249 2 7.6 44 230 60 363 400 400 400 48.5 288 48.5 288 48.5 288 2 7.4 37 380 60 201 250 225 225 27.6 159 27.6 159 27.6 159 2 4.5 23.1 460 60 177 200 200 200 24.4 145 24.4 145 24.4 145 2 4 19 575 60 134 150 150 150 17.4 109 17.4 109 17.4 109 2 2.9 15.3
Electrical data without pumps R-454B Table 15 - Electrical data without pumps R-454B
Johnson Controls 55
Electrical data without pumps R-454B, continued
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max. dual elem. CB
System 1 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 391 600 400 400 57.7 284 57.7 284 57.7 284 2 7.6 44 230 60 390 600 400 400 57.7 330 57.7 330 57.7 330 2 7.4 37 380 60 211 250 225 225 30.9 192 30.9 192 30.9 192 2 4.5 23.1 460 60 184 250 200 200 26.9 180 26.9 180 26.9 180 2 4 19 575 60 146 200 150 150 21.5 132 21.5 132 21.5 132 2 2.9 15.3
208 60 406 600 450 450 57.7 284 57.7 284 57.7 284 3 7.6 44 230 60 405 600 450 450 57.7 330 57.7 330 57.7 330 3 7.4 37 380 60 220 400 250 250 30.9 192 30.9 192 30.9 192 3 4.5 23.1 460 60 192 250 200 200 26.9 180 26.9 180 26.9 180 3 4 19 575 60 152 200 175 175 21.5 132 21.5 132 21.5 132 3 2.9 15.3
208 60 450 600 500 500 57.7 284 57.7 284 57.7 284 2 7.6 44 230 60 449 600 500 500 57.7 330 57.7 330 57.7 330 2 7.4 37 380 60 260 400 300 300 30.9 192 30.9 192 30.9 192 2 4.5 23.1 460 60 220 400 250 250 26.9 180 26.9 180 26.9 180 2 4 19 575 60 175 250 200 200 21.5 132 21.5 132 21.5 132 2 2.9 15.3
208 60 458 600 500 500 57.7 284 57.7 284 57.7 284 2 7.6 44 230 60 456 600 500 500 57.7 330 57.7 330 57.7 330 2 7.4 37 380 60 264 400 300 300 30.9 192 30.9 192 30.9 192 2 4.5 23.1 460 60 224 400 250 250 26.9 180 26.9 180 26.9 180 2 4 19 575 60 178 250 200 200 21.5 132 21.5 132 21.5 132 2 2.9 15.3
208 60 497 800 600 600 106.2 652 106.2 652 — — 3 7.6 44 230 60 496 800 600 600 106.2 652 106.2 652 — — 3 7.4 37 380 60 300 400 350 350 64.3 355 64.3 355 — — 3 4.5 23.1 460 60 250 400 300 300 53.1 316 53.1 316 — — 3 4 19 575 60 198 250 225 225 42.5 255 42.5 255 — — 3 2.9 15.3
208 60 512 800 600 600 106.2 652 106.2 652 — — 4 7.6 44 230 60 511 800 600 600 106.2 652 106.2 652 — — 4 7.4 37 380 60 309 400 350 350 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 258 400 300 300 53.1 316 53.1 316 — — 4 4 19 575 60 204 250 225 225 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 579 800 600 600 106.2 652 106.2 652 106.2 652 4 7.6 44 230 60 577 800 600 600 106.2 652 106.2 652 106.2 652 4 7.4 37 380 60 338 600 400 400 64.3 355 64.3 355 64.3 355 4 4.5 23.1 460 60 285 400 300 300 53.1 316 53.1 316 53.1 316 4 4 19 575 60 226 400 250 250 42.5 255 42.5 255 42.5 255 4 2.9 15.3
Table 14 - Electrical data without pumps R-454B, continued
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max. dual elem. CB
System 1 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 555 800 600 600 85.1 506 85.1 506 85.1 506 4 7.6 44 230 60 553 800 600 600 85.1 506 85.1 506 85.1 506 4 7.4 37 380 60 329 400 3 50 350 49.3 280 49.3 280 49.3 280 4 4.5 23.1 460 60 274 400 300 300 40.7 212 40.7 212 40.7 212 4 4 19 575 60 217 400 250 250 32.6 168 32.6 168 32.6 168 4 2.9 15.3
208 60 618 800 700 700 106.2 652 106.2 652 106.2 652 4 7.6 44 230 60 617 800 700 700 106.2 652 106.2 652 106.2 652 4 7.4 37 380 60 374 600 400 400 64.3 355 64.3 355 64.3 355 4 4.5 23.1 460 60 311 400 350 350 53.1 316 53.1 316 53.1 316 4 4 19 575 60 246 400 250 250 42.5 255 42.5 255 42.5 255 4 2.9 15.3
208 60 634 800 700 700 106.2 652 106.2 652 106.2 652 6 7.6 44 230 60 632 800 700 700 106.2 652 106.2 652 106.2 652 6 7.4 37 380 60 383 600 400 400 64.3 355 64.3 355 64.3 355 6 4.5 23.1 460 60 319 400 350 350 53.1 316 53.1 316 53.1 316 6 4 19 575 60 252 400 300 300 42.5 255 42.5 255 42.5 255 6 2.9 15.3
208 60 740 1,000 800 800 106.2 652 106.2 652 106.2 652 5 7.6 44 230 60 738 1,000 800 800 106.2 652 106.2 652 106.2 652 5 7.4 37 380 60 447 600 500 500 64.3 355 64.3 355 64.3 355 5 4.5 23.1 460 60 372 600 400 400 53.1 316 53.1 316 53.1 316 5 4 19 575 60 295 400 300 300 42.5 255 42.5 255 42.5 255 5 2.9 15.3
208 60 740 1,000 800 800 106.2 652 106.2 652 106.2 652 5 7.6 44 230 60 738 1,000 800 800 106.2 652 106.2 652 106.2 652 5 7.4 37 380 60 447 600 500 500 64.3 355 64.3 355 64.3 355 5 4.5 23.1 460 60 372 600 400 400 53.1 316 53.1 316 53.1 316 5 4 19 575 60 295 400 300 300 42.5 255 42.5 255 42.5 255 5 2.9 15.3
208 60 734 1,000 800 800 102.8 635 102.8 635 102.8 635 6 7.6 44 230 60 731 1,000 800 800 102.8 635 102.8 635 102.8 635 6 7.4 37 380 60 443 600 500 500 62.2 355 62.2 355 62.2 355 6 4.5 23.1 460 60 369 600 400 400 51.4 316 51.4 316 51.4 316 6 4 19 575 60 292 400 300 300 41.1 258 41.1 258 41.1 258 6 2.9 15.3
208 60 904 1,200 1,000 1,000 130.1 761 130.1 761 130.1 761 6 7.6 44 230 60 902 1,200 1,000 1,000 130.1 761 130.1 761 130.1 761 6 7.4 37 380 60 498 600 500 500 71.1 475 71.1 475 71.1 475 6 4.5 23.1 460 60 472 600 500 500 67.9 344 67.9 344 67.9 344 6 4 19 575 60 339 400 350 350 48.7 296 48.7 296 48.7 296 6 2.9 15.3
Electrical data without pumps R-454B, continued
Johnson Controls 57
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max. dual elem. CB
System 2 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 172 250 200 200 33.3 255 33.3 255 — — 2 7.6 44 230 60 171 250 200 200 33.3 255 33.3 255 — — 2 7.4 37 380 60 95 150 110 110 18.1 172.8 18.1 172.8 — — 2 4.5 23.1 460 60 81 100 90 90 15.4 140 15.4 140 — — 2 4 19 575 60 66 100 70 70 12.9 107.6 12.9 107.6 — — 2 2.9 15.3
208 60 225 400 250 250 45.9 335.5 45.9 335.5 — — 2 7.6 44 230 60 225 400 250 250 45.9 335.5 45.9 335.5 — — 2 7.4 37 380 60 119 150 125 125 23.8 183 23.8 183 — — 2 4.5 23.1 460 60 104 150 110 110 20.6 141 20.6 141 — — 2 4 19 575 60 73 100 80 80 14.5 109 14.5 109 — — 2 2.9 15.3
208 60 276 400 300 300 57.7 284 57.7 284 — — 2 7.6 44 230 60 275 400 300 300 57.7 330 57.7 330 — — 2 7.4 37 380 60 149 200 175 175 30.9 192 30.9 192 — — 2 4.5 23.1 460 60 130 200 150 150 26.9 180 26.9 180 — — 2 4 19 575 60 103 150 110 110 21.5 132 21.5 132 — — 2 2.9 15.3
208 60 306 400 350 350 57.7 284 57.7 284 — — 2 7.6 44 230 60 305 400 350 350 57.7 330 57.7 330 — — 2 7.4 37 380 60 170 250 200 200 30.9 192 30.9 192 — — 2 4.5 23.1 460 60 150 200 175 175 26.9 180 26.9 180 — — 2 4 19 575 60 112 150 125 125 21.5 132 21.5 132 — — 2 2.9 15.3
208 60 334 400 350 350 48.5 257 48.5 257 48.5 257 2 7.6 44 230 60 333 400 350 350 48.5 288 48.5 288 48.5 288 2 7.4 37 380 60 191 250 225 225 27.6 172 27.6 172 27.6 172 2 4.5 23.1 460 60 169 200 175 175 24.4 145 24.4 145 24.4 145 2 4 19 575 60 120 150 125 125 17.4 114 17.4 114 17.4 114 2 2.9 15.3
208 60 363 600 400 400 48.5 257 48.5 257 48.5 257 2 7.6 44 230 60 363 600 400 400 48.5 288 48.5 288 48.5 288 2 7.4 37 380 60 201 250 225 225 27.6 172 27.6 172 27.6 172 2 4.5 23.1 460 60 177 200 200 200 24.4 145 24.4 145 24.4 145 2 4 19 575 60 134 150 150 150 17.4 114 17.4 114 17.4 114 2 2.9 15.3
208 60 363 400 400 400 48.5 257 48.5 257 48.5 257 2 7.6 44 230 60 363 400 400 400 48.5 288 48.5 288 48.5 288 2 7.4 37 380 60 201 250 225 225 27.6 172 27.6 172 27.6 172 2 4.5 23.1 460 60 177 200 200 200 24.4 145 24.4 145 24.4 145 2 4 19 575 60 134 150 150 150 17.4 114 17.4 114 17.4 114 2 2.9 15.3
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max. dual elem. CB
System 2 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 391 600 400 400 57.7 284 57.7 284 57.7 284 2 7.6 44 230 60 390 600 400 400 57.7 330 57.7 330 57.7 330 2 7.4 37 380 60 211 250 225 225 30.9 192 30.9 192 30.9 192 2 4.5 23.1 460 60 184 250 200 200 26.9 180 26.9 180 26.9 180 2 4 19 575 60 146 200 150 150 21.5 132 21.5 132 21.5 132 2 2.9 15.3
208 60 406 600 450 450 57.7 284 57.7 284 57.7 284 3 7.6 44 230 60 405 600 450 450 57.7 330 57.7 330 57.7 330 3 7.4 37 380 60 220 400 250 250 30.9 192 30.9 192 30.9 192 3 4.5 23.1 460 60 192 250 200 200 26.9 180 26.9 180 26.9 180 3 4 19 575 60 152 200 175 175 21.5 132 21.5 132 21.5 132 3 2.9 15.3
208 60 450 600 500 500 106.2 652 106.2 652 — — 3 7.6 44 230 60 449 600 500 500 106.2 652 106.2 652 — — 3 7.4 37 380 60 260 400 300 300 64.3 355 64.3 355 — — 3 4.5 23.1 460 60 220 400 250 250 53.1 316 53.1 316 — — 3 4 19 575 60 175 250 200 200 42.5 255 42.5 255 — — 3 2.9 15.3
208 60 458 600 500 500 106.2 652 106.2 652 — — 4 7.6 44 230 60 456 600 500 500 106.2 652 106.2 652 — — 4 7.4 37 380 60 264 400 300 300 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 224 400 250 250 53.1 316 53.1 316 — — 4 4 19 575 60 178 250 200 200 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 497 800 600 600 106.2 652 106.2 652 — — 3 7.6 44 230 60 496 800 600 600 106.2 652 106.2 652 — — 3 7.4 37 380 60 300 400 350 350 64.3 355 64.3 355 — — 3 4.5 23.1 460 60 250 400 300 300 53.1 316 53.1 316 — — 3 4 19 575 60 198 250 225 225 42.5 255 42.5 255 — — 3 2.9 15.3
208 60 512 800 600 600 106.2 652 106.2 652 — — 4 7.6 44 230 60 511 800 600 600 106.2 652 106.2 652 — — 4 7.4 37 380 60 309 400 350 350 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 258 400 300 300 53.1 316 53.1 316 — — 4 4 19 575 60 204 250 225 225 42.5 255 42.5 255 — — 4 2.9 15.3
Johnson Controls 59
YLAA V Hz MCA Min. N/F disc SW
Min. dual elem.
fuse and
CB
Max. dual elem. CB
System 2 Compr. 1 Compr. 2 Compr. 3 Std. flow fans
RLA LRA RLA LRA RLA LRA Qty. FLA LRA
208 60 579 800 600 600 57.7 284 57.7 284 57.7 284 4 7.6 44 230 60 577 800 600 600 57.7 330 57.7 330 57.7 330 4 7.4 37 380 60 338 600 400 400 30.9 192 30.9 192 30.9 192 4 4.5 23.1 460 60 285 400 300 300 26.9 180 26.9 180 26.9 180 4 4 19 575 60 226 400 250 250 21.5 132 21.5 132 21.5 132 4 2.9 15.3
208 60 555 800 600 600 106.2 652 106.2 652 — — 4 7.6 44 230 60 553 800 600 600 106.2 652 106.2 652 — — 4 7.4 37 380 60 329 400 350 350 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 274 400 300 300 53.1 316 53.1 316 — — 4 4 19 575 60 217 400 250 250 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 618 800 700 700 106.2 652 106.2 652 — — 4 7.6 44 230 60 617 800 700 700 106.2 652 106.2 652 — — 4 7.4 37 380 60 374 600 400 400 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 311 400 350 350 53.1 316 53.1 316 — — 4 4 19 575 60 246 400 250 250 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 634 800 700 700 106.2 652 106.2 652 — — 4 7.6 44 230 60 632 800 700 700 106.2 652 106.2 652 — — 4 7.4 37 380 60 383 600 400 400 64.3 355 64.3 355 — — 4 4.5 23.1 460 60 319 400 350 350 53.1 316 53.1 316 — — 4 4 19 575 60 252 400 300 300 42.5 255 42.5 255 — — 4 2.9 15.3
208 60 740 1,000 800 800 106.2 652 106.2 652 106.2 652 5 7.6 44 230 60 738 1,000 800 800 106.2 652 106.2 652 106.2 652 5 7.4 37 380 60 447 600 500 500 64.3 355 64.3 355 64.3 355 5 4.5 23.1 460 60 372 600 400 400 53.1 316 53.1 316 53.1 316 5 4 19 575 60 295 400 300 300 42.5 255 42.5 255 42.5 255 5 2.9 15.3
208 60 740 1,000 800 800 106.2 652 106.2 652 106.2 652 5 7.6 44 230 60 738 1,000 800 800 106.2 652 106.2 652 106.2 652 5 7.4 37 380 60 447 600 500 500 64.3 355 64.3 355 64.3 355 5 4.5 23.1 460 60 372 600 400 400 53.1 316 53.1 316 53.1 316 5 4 19 575 60 295 400 300 300 42.5 255 42.5 255 42.5 255 5 2.9 15.3
208 60 734 1,000 800 800 102.8 635 102.8 635 102.8 635 6 7.6 44 230 60 731 1,000 800 800 102.8 635 102.8 635 102.8 635 6 7.4 37 380 60 443 600 500 500 62.2 355 62.2 355 62.2 355 6 4.5 23.1 460 60 369 600 400 400 51.4 316 51.4 316 51.4 316 6 4 19 575 60 292 400 300 300 41.1 258 41.1 258 41.1 258 6 2.9 15.3
208 60 904 1,200 1,000 1,000 130.1 761 130.1 761 130.1 761 6 7.6 44 230 60 902 1,200 1,000 1,000 130.1 761 130.1 761 130.1 761 6 7.4 37 380 60 498 600 500 500 71.1 475 71.1 475 71.1 475 6 4.5 23.1 460 60 472 600 500 500 67.9 344 67.9 344 67.9 344 6 4 19 575 60 339 400 350 350 48.7 296 48.7 296 48.7 296 6 2.9 15.3
Wiring diagram
Johnson Controls 61
LD18444
Wiring diagram, continued
MANUAL MOTOR STARTER COMP
FIELD MOUNTED AND WIRED ON REMOTE EVAP
UNITS
ARE NOT SUPPLIED BY JOHNSON CONTROLS
ENTERING CHILLED TEMP
MOTOR PROTECTOR COMP
Johnson Controls 63
A. This drawing is based on IEC symbols.
B. Field wiring to be in accordance with the relevant electrical code as well as all other applicable codes and specifications.
C. All sources of supply shown on this diagram to be taken from one main isolator, not shown or supplied by the chiller manufacturer.
D. Green and yellow wire is used for earth, multicolored cable used for low voltage. Red wire used for AC control, blue wire for neutral, black wire for AC and DC power. Use orange wire for interlock control wiring supplied by external source.
E. Legend designation depicts component abbreviations. Number prefix located, if applicable, on schematic circuit, refers to system thereon, e.g.= 1-FHP2 refers to high pressure cutout number 2 on system 1.
F. All wiring to control section voltage free contacts requires a supply provided by the customer maximum volt-age 240 V. The customer must take particular care when deriving the supplies for the voltage free terminals with regard to a common point of isolation. As a result, these circuits when used must be fed through the common point of isolation the voltage to these circuits is removed when the common point of isolation to the unit is opened. This common point of isolation is not supplied. The voltage free contacts are rated at 100 VA. All inductive devices (relays) switch by the voltage free contacts must have their coil suppressed using standard r/c suppressors.
G. Customer voltage free contacts connected to terminal 13 must be rated at 30 V 5 mA.
H. Do not mount controls, for example relays, in any section of the control panel. Additionally, do not run control wiring not connected to the control panel through the panel. If you do not follow these precautions, electrical noise can cause malfunctions or damage to the unit and its controls.
1. Refer to the installation, commissioning, operation, and maintenance manual for customer connections and customer connection notes, non compliance to these instructions invalidate unit warranty.
2. Wiring and components for compressor 3 only fitted when unit has 3 compressors on the system. 1-BMP3 is replaced by a link across terminals 134 and 135. 2-BMP3 is replaced by a link across terminals 234 and 235.
3. FHP2 is only fitted on 0089 and above. When not fitted 1-FHP2 is replaced by a link across terminals 132 and 139. 2-FHP2 is replaced by a link across terminals 232 and 239.
4. Fitted on units with hot gas bypass option.
5. EMS option is wired as shown.
6. This wiring must be used for old display 031-0110-000.
7. Network connection point.
8. Printer port.
9. Remote emergency stop can be wired between terminal l and 5 after removing link.
10. Power factor correction accessory. Power factor correction fitted to each compressor contactor.
11. Not fitted on compressors with internal motor protection. For system 1 terminals 132 and 133, 133 and
134 And 134 and 135 are linked. For system 2 terminals 232 and 233, 233 and 234 and 234 and 235 are linked.
12. Only fitted on systems with three or four fans.
13. Only fitted on systems with four fans.
14. Only fitted on systems with five fans.
15. Only fitted on systems with six fans.
16. Input switch disconnect or circuit breaker option replaces input terminal block.
17. Input switch disconnect and system circuit breaker option replaces input terminal block.
18. 115 V control circuit requires a 115 V supply unless control circuit transformer -T2 and -F3 are fitted.
19. For optional hydro kit. Heater -EPH is fitted and wired as shown. On single pump -KP1, -QMMSP1 and
-MP1 are fitted and wired as shown. On two pump hydro kits -KP2, -QMMSP2 and -MP2 are also fitted and wired as shown.
20. Current measurement option wired as shown.
21. Only fitted on systems with single speed fans.
22. Only fitted on systems with two speed fans.
23. Optional compressor manual motors starters.
24. See sheet 3 of connection diagram for power input options.
User control wiring
LD13130
XTBC1
A- A+
INTERNAL WIRING TO OPTIONAL REMOTE TEMP. RESET BOARD
FLOW SWITCH
REMOTE UNLOAD STEP 1
PWM REMOTE TEMP RESET
INTERNAL WIRING TO 2-KCR CONTROL RELAY
INTERNAL WIRING TO 1-KCR CONTROL RELAY
REMOTE START / STOP
XTBC2
L
GND
INTERNAL WIRING TO EVAPORATOR HEATER
INTERNAL 120 VAC WIRING TO F1 FUSE
INTERNAL 120 VAC WIRING (TYPICALLY FROM CONTROL TRANSFORMER)
INTERNAL NEUTRAL WIRING
INTERNAL NEUTRAL WIRING
INTERNAL NEUTRAL WIRING (TYPICALLY FROM CONTROL TRANSFORMER)
INTERNAL WIRING TO HOT GAS SOLENOID VALVE
SYSTEM 2 ALARM DRY CONTACTS (OPEN = ALARM)
SYSTEM 2 RUN DRY CONTACTS (CLOSE = RUN)
SYSTEM 1 RUN DRY CONTACTS (CLOSE = RUN)
EVAPORATOR PUMP DRY CONTACTS (CLOSE = RUN
BASED ON DAILY SCHEDULE)
SYSTEM 1 ALARM DRY CONTACTS (OPEN = ALARM)
Normally jumpered.
Can be used as
EMERGENCY STOP
contacts from an external source.
User control wiring inputs
User control wiring outputs
Johnson Controls 65
Application data
Unit location
The YLAA chillers are designed for outdoor installation. When selecting a site for installa-tion, adhere to the following conditions:
A. For outdoor locations of the unit, select a place having an adequate supply of fresh air for the condenser.
B. Avoid locations beneath windows or between structures where normal operating sounds may be objectionable.
C. Installation sites may be either on a roof, or at ground level. See Foundation.
D. The condenser fans are the propeller-type, and are not recommended for use with duct work in the condenser air stream.
E. When it is required to surround the units, it is recommended that the screening be able to pass the required chiller CFM without exceeding 0.1 in. of water external static pressure.
F. Protection against corrosive environments is available by supplying the units with ep-oxy coating on the condenser coils. The epoxy coils are offered with any units being installed at the seashore or where salt spray may hit the unit.
In installations where winter operation is intended and snow accumulations are expected, additional height must be provided to ensure normal condenser air flow.
Recommended clearances for units are given in dimensions. When the available space is less, the units must be equipped with the discharge pressure transducer option to permit high pressure unloading in the event that air recirculation were to occur.
Foundation
Mount the unit on a flat and level foundation, ground, or roof, which is capable of support-ing the entire operating weight of the equipment. See Physical data and nominal ratings on page 23 for the operating weights.
Roof locations – Choose a spot with adequate structural strength to safely support the entire weight of the unit and service personnel. Care must be taken not to damage the roof during installation. If the roof is bonded, consult the building contractor or architect for spe-cial installation requirements. Use spring-type isolators for roof installations to minimize the transmission of vibration into the building structure.
Ground level installations – It is important to install units on a substantial base that does not settle, causing strain on the liquid lines and resulting in possible leaks. A one-piece concrete slab with footers extending below the frost line is highly recommended.