WWYK263009_65 Design Analysis Part 28_Part2.pdf
PDF 12 MB Posted
- Solicitation number
- W912BV25S0014
About this file
These files contain submittal sheets, specifications and engineering drawings for HVAC equipment including air-cooled scroll chillers, ductless mini-split systems, unit heaters, and wall heaters.
The documents detail technical specifications for multiple pieces of HVAC equipment: YORK YLAA air-cooled scroll chillers (40-230 tons capacity), LG Multi V™ S heat pump outdoor units (3-4 ton), Reznor EGHB industrial suspended unit heaters, EHA forced-air architectural wall heaters, and EHC commercial wall heaters. The documents provide comprehensive details on features, performance ratings, physical dimensions, electrical requirements, control options, and installation parameters. Key equipment features described include factory-assembled packages, BACnet/Modbus controls compatibility, multiple efficiency level options, and various sound attenuation capabilities. The drawings include detailed dimensional diagrams, mounting specifications, and connection requirements. Equipment options like variable speed drives, pump packages, and protective coatings are also detailed.
View the file
Other files
Show 40 more
Latest 50 of 95 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SDV
270487
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
04/05/2021
OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2021
S o lid E d g e
SDV-1-1
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SINGLE DUCT TERMINAL
VARIABLE VOLUME
ROUND DISCHARGE
COLLAR
INLET SIZES WIDTH HEIGHT
D W H A B L
4 3
/8 (98)
5 4 /8 (124)
6 5 /8 (149)
7 6 /8 (175)
8 7 /8 (200)
9 8 /8 (225)
10 9 /8 (251)
12 11
/8 (302) 16 (406) 15 (381)
14 13
/8 (352) 20 (508) 17
/2 (445)
16 15
/8 (403) 24 (610) 18 (457)
UNIT
SIZE
/8 (162)
/8 (111)
LENGTH
10 (254)
14 (356) 12
/2 (318)
/4 (489)5
/16 (135)
12 (305)
8 (203)
/16 (97) 15
/4 (400)
STANDARD CONSTRUCTION:
• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS
REQUIREMENTS OF NFPA 90A AND UL181.
• 22 GAUGE GALVANIZED STEEL HOUSING. MECHANICALLY SEALED, LEAK
RESISTANT CONSTRUCTION.
• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT DUCT
CONNECTION.
• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.
• 1/2" (13mm) GALVANIZED DAMPER SHAFT WITH POSITION INDICATOR.
• LEFT HAND UNIT SHOWN (CLH) RIGHT HAND AVAILABLE.
UNIT OPTIONS:
� NEMA1 CONTROLS ENCLOSURE (PS)
� DISCONNECT SWITCH (DSW)
� 20 GAUGE CASING (20GA)
� HANGER BRACKETS (HB)
� BOTTOM REMOVABLE SENSOR (RS)
� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)
BOTTOM ACCESS DOOR:
� ACCESS DOOR WITH SCREWS (AD)
� ACCESS DOOR WITH SNAP LATCHES (ADL)
� ACCESS DOOR WITH QUARTER TURN LATCHES (ADQ)
CONTROLS OPTIONS:
� FIELD MOUNTED CONTROLS, SUPPLIED BY OTHERS (FLD)
� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)
CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP):
� DIGITAL CONTROLS (DIG)
� PNEUMATIC CONTROLS (PNEU)
H
W 4 3/4" (121)
9 1/2" (241)
2" (51)
18 1/2" (470)
A
DOPTIONAL NEMA1
CONTROLS
ENCLOSURE
LINER OPTIONS:
� FIBERGLASS 1" (25mm) (FG1)
� FIBER FREE FOAM 1/2" (13mm) (FF50)
� FIBER FREE FOAM 3/4" (19mm) (FF75)
� FIBER FREE FOAM 1" (25mm) (FF1)
� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)
� SOLID METAL WITH FG1 (SM1)
� CLEANROOM ANGLES WITH FB1 (CRAF1)
� PERFORATED METAL WITH FB1 (AFPM1)
6 3/8" (162)
SIZE 4 & 5 ONLY
L 4" (102)
D
3 5/16" (84)
B
MULTI-POINT
SENSOR
OPTIONAL ACCESS DOOR
ROUND
DISCHARGE
COLLAR
UNIT OPTIONS:
� NEMA1 CONTROLS ENCLOSURE (PS)
� DISCONNECT SWITCH (DSW)
� 20 GAUGE CASING (20GA)
� HANGER BRACKETS (HB)
� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)
BOTTOM ACCESS DOOR:
� ACCESS DOOR WITH QUARTER TURN LATCHES (ADQ)
• SIZES 4 TO 8 ACCESS SIZE IS 10" (254) X 12" (305)
• SIZES 9 TO 16 ACCESS SIZE IS 12" (305) X 12" (305)
270456
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
04/05/2021
OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2021
S o lid E d g e
SDV-1-1
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SINGLE DUCT TERMINAL
VARIABLE VOLUME
CERTIFIED LOW LEAKAGE
INLET SIZES WIDTH HEIGHT
D W H A B L
4 3
/8 (98)
5 4
/8 (124)
6 5
/8 (149)
7 6
/8 (175)
8 7
/8 (200)
9 8
/8 (225)
10 9
/8 (251)
12 11
/8 (302) 16 (406) 15 (381)
14 13
/8 (352) 20 (508) 17
/2 (445)
16 15
/8 (403) 24 (610) 18 (457)
UNIT
SIZE
/8 (162)
/8 (111)
LENGTH
10 (254)
14 (356) 12
/2 (318)
/4 (489)5
/16 (135)
12 (305)
8 (203)
/16 (97) 15 /4 (400)
H
W 4 3/4" (121)
9 1/2" (241)
2" (51) 18 1/2" (470) B
A L D
OPTIONAL NEMA1
CONTROLS
ENCLOSURE
6 3/8" (162)
SIZE 4 & 5 ONLY
CONTROLS OPTIONS:
� FIELD MOUNTED CONTROLS, SUPPLIED BY OTHERS (FLD)
� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)
CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP):
� DIGITAL CONTROLS (DIG)
� PNEUMATIC CONTROLS (PNEU)
LINER OPTIONS:
� FIBERGLASS 1" (25mm) (FG1)
� FIBER FREE FOAM 1/2" (13mm) (FF50)
� FIBER FREE FOAM 3/4" (19mm) (FF75)
� FIBER FREE FOAM 1" (25mm) (FF1)
� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)
� SOLID METAL WITH FG1 (SM1)
� CLEANROOM ANGLES WITH FB1 (CRAF1)
� PERFORATED METAL WITH FB1 (AFPM1)
STANDARD CONSTRUCTION:
• FACTORY LEAK TESTED CASING UP TO 1.5% OF MAX FLOW AT 6" W.G.
• FACTORY LEAK TESTED DAMPER UP TO 1% OF MAX FLOW AT 6" W.G.
• LEAKAGE CERTIFICATION LABEL PROVIDED BY FACTORY.
• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS
REQUIREMENTS OF NFPA 90A AND UL181.
• 22 GAUGE GALVANIZED STEEL HOUSING. MECHANICALLY SEALED,
LEAK RESISTANT CONSTRUCTION.
• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT
DUCT CONNECTION.
• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.
• 1/2" (13mm) GALVANIZED DAMPER SHAFT WITH POSITION INDICATOR.
• LEFT HAND UNIT SHOWN (CLH) RIGHT HAND AVAILABLE.
MULTI-POINT SENSOR OPTIONAL ACCESS DOOR
270472
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
04/05/2021
OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2021
S o lid E d g e
SDV-1-1
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SINGLE DUCT TERMINAL
VARIABLE VOLUME
CERTIFIED LOW LEAKAGE
WATER COIL
H
W 4 3/4" (121)
9 1/2" (241)
2" (51)
18 1/2" (470)
A
INLET SIZES WIDTH HEIGHT
D W H A B L
4 3
/8 (98)
5 4
/8 (124)
6 5
/8 (149)
7 6
/8 (175)
8 7
/8 (200)
9 8
/8 (225)
10 9
/8 (251)
12 11
/8 (302) 16 (406) 15 (381)
14 13
/8 (352) 20 (508) 17
/2 (445)
16 15
/8 (403) 24 (610) 18 (457)
UNIT
SIZE
/8 (162)
/8 (111)
LENGTH
10 (254)
14 (356) 12
/2 (318)
/4 (489)5
/16 (135)
12 (305)
8 (203)
/16 (97) 15
/4 (400)
UNIT OPTIONS:
� NEMA1 CONTROLS ENCLOSURE (PS)
� DISCONNECT SWITCH (DSW)
� 20 GAUGE CASING (20GA)
� HANGER BRACKETS (HB)
� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)
UNIT ACCESS DOOR:
� ACCESS DOOR WITH QUARTER TURN LATCHES (ADQ)
• SIZES 4 TO 8 ACCESS SIZE IS 10" (254) X 12" (305)
• SIZES 9 TO 16 ACCESS SIZE IS 12" (305) X 12" (305)
D
OPTIONAL NEMA1
CONTROL
ENCLOSURE
CONTROLS OPTIONS:
� FIELD MOUNTED CONTROLS, SUPPLIED BY OTHERS (FLD)
� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)
CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP):
� DIGITAL CONTROLS (DIG)
� PNEUMATIC CONTROLS (PNEU)
LINER OPTIONS:
� FIBERGLASS 1" (25mm) (FG1)
� FIBER FREE FOAM 1/2" (13mm) (FF50)
� FIBER FREE FOAM 3/4" (19mm) (FF75)
� FIBER FREE FOAM 1" (25mm) (FF1)
� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)
� SOLID METAL WITH FG1 (SM1)
� CLEANROOM ANGLES WITH FB1 (CRAF1)
� PERFORATED METAL WITH FB1 (AFPM1)
6 3/8" (162)
SIZE 4 & 5 ONLY
STANDARD CONSTRUCTION:
• FACTORY LEAK TESTED CASING UP TO 1.5% OF MAX FLOW AT 6" W.G.
• FACTORY LEAK TESTED DAMPER UP TO 1% OF MAX FLOW AT 6" W.G.
• LEAKAGE CERTIFICATION LABEL PROVIDED BY FACTORY.
• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS
REQUIREMENTS OF NFPA 90A AND UL181.
• 22 GAUGE GALVANIZED STEEL HOUSING. MECHANICALLY SEALED, LEAK
RESISTANT CONSTRUCTION.
• RECTANGULAR DISCHARGE WITH SLIP AND DRIVE CLEAT DUCT CONNECTION.
• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.
• 1/2" (13mm) GALVANIZED DAMPER SHAFT WITH POSITION INDICATOR.
• LEFT HAND UNIT SHOWN (CLH) RIGHT HAND AVAILABLE.
MULTI-POINT
SENSOR
OPTIONAL ACCESS
DOOR
EXTERNALLY
WRAPPED
1" (25) FOIL FACED
FIBERGLASS BOARD
L 1&2 ROW = 5" (127)
3&4 ROW = 7 1/4" (184)
A
272770
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
02/01/2023
OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2023
S o lid E d g e
SDV-1-1
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SINGLE DUCT TERMINAL
VARIABLE VOLUME
CERTIFIED LOW LEAKAGE
ATTENUATORS
CONTROLS OPTIONS:
� FIELD MOUNTED, CONTROLS SUPPLIED BY OTHERS (FLD)
� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)
CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP):
� DIGITAL CONTROLS (DIG)
� PNEUMATIC CONTROLS (PNEU)
ATT= 35 13/16" (910)
ATT5= 55 1/2" (1410)
W
H
4 3/4" (121)
9 1/2" (241)
D
OPTIONAL NEMA1
CONTROLS
ENCLOSURE
6 3/8" (162)
SIZE 4 & 5 ONLY
INLET SIZES WIDTH HEIGHT
D W H A B L
4 3 /8 (98)
5 4 /8 (124)
6 5 /8 (149)
7 6 /8 (175)
8 7 /8 (200)
9 8 /8 (225)
10 9 /8 (251)
12 11 /8 (302) 16 (406) 15 (381)
14 13 /8 (352) 20 (508) 17
/2 (445)
16 15 /8 (403) 24 (610) 18 (457)
UNIT
SIZE
/8 (162)
/8 (111)
LENGTH
10 (254)
14 (356) 12
/2 (318)
/4 (489)5
/16 (135)
12 (305)
8 (203)
/16 (97) 15 /4 (400)
LINER OPTIONS:
� FIBERGLASS 1" (25mm) (FG1)
� FIBER FREE FOAM 1/2" (13mm) (FF50)
� FIBER FREE FOAM 3/4" (19mm) (FF75)
� FIBER FREE FOAM 1" (25mm) (FF1)
� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)
� SOLID METAL WITH FG1 (SM1)
� CLEANROOM ANGLES WITH FB1 (CRAF1)
� PERFORATED METAL WITH FB1 (AFPM1)
UNIT OPTIONS:
� NEMA1 CONTROLS ENCLOSURE (PS)
� DISCONNECT SWITCH (DSW)
� 20 GAUGE CASING (20GA)
� HANGER BRACKETS (HB)
� BOTTOM REMOVABLE SENSOR (RS)
� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)
BOTTOM ACCESS DOOR:
� ACCESS DOOR WITH QUARTER TURN LATCHES (ADQ)
• SIZES 4 TO 8 ACCESS SIZE IS 10" (254) X 12" (305)
• SIZES 9 TO 16 ACCESS SIZE IS 12" (305) X 12" (305)
STANDARD CONSTRUCTION:
• FACTORY LEAK TESTED CASING UP TO 1.5% OF MAX FLOW AT 6" W.G.
• FACTORY LEAK TESTED DAMPER UP TO 1% OF MAX FLOW AT 6" W.G.
• LEAKAGE CERTIFICATION LABEL PROVIDED BY FACTORY.
• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS
REQUIREMENTS OF NFPA 90A AND UL181.
• 22 GAUGE GALVANIZED STEEL HOUSING. MECHANICALLY SEALED,
LEAK RESISTANT CONSTRUCTION.
• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT
DUCT CONNECTION.
• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.
• 1/2" (13mm) GALVANIZED DAMPER SHAFT WITH POSITION INDICATOR.
• LEFT HAND UNIT SHOWN (CLH) RIGHT HAND AVAILABLE.
MULTI-POINT
SENSOR
2" (51) 18 1/2" (470) B
A L
OPTIONAL ACCESS DOOR
273390
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
04/05/2021
OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2021
S o lid E d g e
SDV-1-1
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SINGLE DUCT TERMINAL
VARIABLE VOLUME
CERTIFIED LOW LEAKAGE
WATER COIL
OVERSIZED
UNIT OPTIONS:
� NEMA1 CONTROLS ENCLOSURE (PS)
� DISCONNECT SWITCH (DSW)
� 20 GAUGE CASING (20GA)
� HANGER BRACKETS (HB)
� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)
BOTTOM ACCESS DOOR:
� ACCESS DOOR WITH SCREWS (AD)
� ACCESS DOOR WITH SNAP LATCHES (ADL)
� ACCESS DOOR WITH QUARTER TURN LATCHES (ADQ)
STANDARD CONSTRUCTION:
• FACTORY LEAK TESTED CASING UP TO 1.5% OF MAX FLOW AT 6" W.G.
• FACTORY LEAK TESTED DAMPER UP TO 1% OF MAX FLOW AT 6" W.G.
• LEAKAGE CERTIFICATION LABEL PROVIDED BY FACTORY.
• DIMENSIONAL TABLE REPRESENTS OVERSIZED CONSTRUCTION (OS).
• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS REQUIREMENTS
OF NFPA 90A AND UL181.
• 22 GAUGE GALVANIZED STEEL HOUSING. MECHANICALLY SEALED, LEAK RESISTANT
CONSTRUCTION.
• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT DUCT CONNECTION.
• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.
• 1/2" (13mm) GALVANIZED DAMPER SHAFT WITH POSITION INDICATOR.
• LEFT HAND UNIT SHOWN (CLH), RIGHT HAND AVAILABLE.
CONTROLS OPTIONS:
� FIELD MOUNTED CONTROLS, SUPPLIED BY OTHERS (FLD)
� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)
CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP):
� DIGITAL CONTROLS (DIG)
� PNEUMATIC CONTROLS (PNEU)
LINER OPTIONS:
� FIBERGLASS 1" (25mm) (FG1)
� FIBER FREE FOAM 1/2" (13mm) (FF50)
� FIBER FREE FOAM 3/4" (19mm) (FF75)
� FIBER FREE FOAM 1" (25mm) (FF1)
� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)
� SOLID METAL WITH FG1 (SM1)
� CLEANROOM ANGLES WITH FB1 (CRAF1)
� PERFORATED METAL WITH FB1 (AFPM1)
H
W 4 3/4" (121)
9 1/2" (241)
2" (51)
18 1/2" (470)
A
D
OPTIONAL NEMA1
CONTROL
ENCLOSURE
6 3/8" (162)
SIZE 4 & 5 ONLY
MULTI-POINT
SENSOR
OPTIONAL ACCESS
DOOR
EXTERNALLY
WRAPPED
1" (25) FOIL FACED
FIBERGLASS BOARD
L 1&2 ROW = 5" (127)
3&4 ROW = 7 1/4" (184)
INLET SIZES WIDTH HEIGHT
D W H A B L
4 400 (189) 3
/8 (98)
5 500 (236) 4
/8 (124)
6 550 (260) 5
/8 (149)
7 800 (378) 6
/8 (175)
8 1100 (519) 7
/8 (200)
9 1400 (661) 8
/8 (225)
10 1800 (850) 9
/8 (251)
12 2600 (1227) 11
/8 (302) 20 (508) 17 /2 (445)
14 3700 (1746) 13
/8 (352) 24 (610)
16 5000 (2360) 15
/8 (403) 38 (965)
MAX CFM (L/S)
UNIT
SIZE
/8 (162)
LENGTH
10 (254)12 (305)
/8 (111)
/2 (318) 14 (356)
16 (406) 15 (381)
18 (457)
/16 (97)
/16 (135)
/4 (400)
/4 (489)
B
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
C
SDV
273957
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
02/06/2023
OF REVSHEET 1 7© Copyright PRICE INDUSTRIES 2023
S o lid E d g e
SINGLE DUCT TERMINAL
VARIABLE VOLUME
STANDARD CONSTRUCTION:
• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS REQUIREMENTS OF NFPA 90A AND UL181.
• 22GA. ZINC COATED STEEL HOUSING. MECHANICALLY SEALED, LEAK RESISTANT CONSTRUCTION.
• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT DUCT CONNECTION.
• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.
• 1/2" (13mm) ZINC PLATED DAMPER SHAFT WITH POSITION INDICATOR.
• SIZES 4 & 5 USE AN INLET REDUCER.
UNIT OPTIONS:
� NEMA1 CONTROLS ENCLOSURE (PS)
� DISCONNECT SWITCH (DSW)
� 20 GAUGE CASING (20GA)
� HANGER BRACKETS (HB)
� BOTTOM REMOVABLE SENSOR (RS)
� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)
� ACCESS DOOR (AD)
CONTROLS OPTIONS:
� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)
� FIELD MOUNTED, CONTROLS SUPPLIED BY OTHERS (FLD)
� DIGITAL CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP)
LINER OPTIONS:
� FIBERGLASS 1" (25mm) (FG1)
� FIBER FREE FOAM 1/2" (13mm) (FF50)
� FIBER FREE FOAM 3/4" (19mm) (FF)
� FIBER FREE FOAM 1" (25mm) (FF1)
� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)
� SOLID METAL WITH FG1 (SM1)
� CLEANROOM ANGLES WITH FB1 (CRAF1)
WIDTH HEIGHT INLET SIZES
W H D L A B
4 400 189 3 7/8 (98)
5 500 236 4 7/8 (124)
6 550 260 5 7/8 (149)
7 800 378 6 7/8 (175)
8 1100 519 7 7/8 (200)
9 1400 661 8 7/8 (225)
10 1800 850 9 7/8 (251)
12 2600 1227 16 (406) 15 (381) 11 7/8 (302)
14 3700 1746 20 (508) 17 1/2 (445) 13 7/8 (352)
16 5000 2360 24 (610) 15 7/8 (403)
24 x 16 8400 3964 38 (965) 23 7/8 (603) x 15 7/8 (403) 15 1/2 (394) 3 1/2 (89) 2 3/4 (70)
MAX
CFM
UNIT
SIZE
6 3/8 (162)
4 3/8 (111)
LENGTH
MAX L/S
10 (254)
14 (356) 12 1/2 (318)
19 1/4 (489) 5 5/16 (135)
12 (305)
8 (203)
3 13/16 (97)15 3/4 (400)
18 (457)
CONTROLS/PIPING PACKAGE
OPPOSITE SIDE
PIPING PACKAGE
3-WAY DETAIL
D
H 9 229
4 3/4 120 W 6 5/8 169 18 3/8 466 B
1&2 ROW=5 (127)
3&4 ROW=7 1/4 (184)
OPTIONAL NEMA1
CONTROL
ENCLOSURE A L
6 3/4 173
6 5/8 167
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SDV
273957
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
02/06/2023
OF REVSHEET 2 7© Copyright PRICE INDUSTRIES 2023
S o lid E d g e
SINGLE DUCT TERMINAL
VARIABLE VOLUME
STANDARD CONSTRUCTION:
• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS REQUIREMENTS OF NFPA 90A AND UL181.
• 22GA. ZINC COATED STEEL HOUSING. MECHANICALLY SEALED, LEAK RESISTANT CONSTRUCTION.
• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT DUCT CONNECTION.
• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.
• 1/2" (13mm) ZINC PLATED DAMPER SHAFT WITH POSITION INDICATOR.
• SIZES 4 & 5 USE AN INLET REDUCER.
• EXTENSION REQUIRED WHEN CONTROLS SAME SIDE AS PIPING PACKAGE
UNIT OPTIONS:
� NEMA1 CONTROLS ENCLOSURE (PS)
� DISCONNECT SWITCH (DSW)
� 20 GAUGE CASING (20GA)
� HANGER BRACKETS (HB)
� BOTTOM REMOVABLE SENSOR (RS)
� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)
� ACCESS DOOR (AD)
� EXTENSION ACCESS DOOR WITH SCREWS (ADD)
� EXTENSION ACCESS DOOR WITH SNAP LATCHES (ADDL)
� EXTENSION ACCESS DOOR QUARTER TURN LATCHES (ADDQ)
CONTROLS OPTIONS:
� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)
� FIELD MOUNTED, CONTROLS SUPPLIED BY OTHERS (FLD)
� DIGITAL CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP)
LINER OPTIONS:
� FIBERGLASS 1" (25mm) (FG1)
� FIBER FREE FOAM 1/2" (13mm) (FF50)
� FIBER FREE FOAM 3/4" (19mm) (FF)
� FIBER FREE FOAM 1" (25mm) (FF1)
� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)
� SOLID METAL WITH FG1 (SM1)
� CLEANROOM ANGLES WITH FB1 (CRAF1)
PIPING PACKAGE
CONTROLS/PIPING PACKAGE
SAME SIDE
3-WAY DETAIL
15 1/2 393
1&2 ROW=5 (127)
3&4 ROW=7 1/4 (184)
L
18 3/8 467
D 4 3/4 120
6 5/8 167 W
H9 229
OPTIONAL NEMA1
CONTROL
ENCLOSURE
B
PIPING PACKAGE
EXTENSION
WIDTH HEIGHT INLET SIZES
W H D L A B
4 400 189 3 7/8 (98)
5 500 236 4 7/8 (124)
6 550 260 5 7/8 (149)
7 800 378 6 7/8 (175)
8 1100 519 7 7/8 (200)
9 1400 661 8 7/8 (225)
10 1800 850 9 7/8 (251)
12 2600 1227 16 (406) 15 (381) 11 7/8 (302)
14 3700 1746 20 (508) 17 1/2 (445) 13 7/8 (352)
16 5000 2360 24 (610) 15 7/8 (403)
24 x 16 8400 3964 38 (965) 23 7/8 (603) x 15 7/8 (403) 15 1/2 (394) 3 1/2 (89) 2 3/4 (70)
MAX
CFM
UNIT
SIZE
6 3/8 (162)
4 3/8 (111)
LENGTH
MAX L/S
10 (254)
14 (356) 12 1/2 (318)
19 1/4 (489) 5 5/16 (135)
12 (305)
8 (203)
3 13/16 (97)15 3/4 (400)
18 (457)
A
6 3/4 173
6 5/8 169
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SDV
273957
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
02/06/2023
OF REVSHEET 3 7© Copyright PRICE INDUSTRIES 2023
S o lid E d g e
SINGLE DUCT TERMINAL
VARIABLE VOLUME
NOTES:
1. VALVES TO BE ASSEMBLED, TESTED AND SHIPPED
AS DEPICTED
2. REFER TO SUBMITTED TERMINAL UNIT SCHEDULE
FOR UNIT AND COIL HANDING
3. EXTENSION PROVIDED WHEN CONTROLS AND COIL
HANDING ARE ON THE SAME SIDE
4. EXTENSION INSULATED TO MATCH TERMINAL UNIT LINER
5. PRESS CONNECTION BETWEEN VALVES AND COIL
RIGHT HAND CONTROL & RIGHT HAND
PIPING PACKAGE
LEFT HAND CONTROL & LEFT HAND
PIPING PACKAGE
LEFT HAND CONTROL & RIGHT HAND
PIPING PACKAGE
RIGHT HAND CONTROL & LEFT HAND
PIPING PACKAGE
PIPING PACKAGE
ORIENTATION
PIPING PACKAGE
EXTENSION
OPTIONAL NEMA1
CONTROLS ENCLOSURE
OPTIONAL NEMA1
CONTROLS ENCLOSURE
OPTIONAL NEMA1
CONTROLS ENCLOSURE
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SDV
273957
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
02/06/2023
OF REVSHEET 4 7© Copyright PRICE INDUSTRIES 2023
S o lid E d g e
SINGLE DUCT TERMINAL
VARIABLE VOLUME
NOTES:
1. VALVES TO BE ASSEMBLED, TESTED AND SHIPPED
AS DEPICTED
2. REFER TO SUBMITTED TERMINAL UNIT SCHEDULE
FOR UNIT AND COIL HANDING
3. EXTENSION PROVIDED WHEN CONTROLS AND COIL
HANDING ARE ON THE SAME SIDE
4. EXTENSION INSULATED TO MATCH TERMINAL UNIT LINER
5. 'E' DIMENSION IS TAKEN FROM TOP OF UNIT TO RETURN PIPE
E (RH COIL) E (LH COIL) F E F E F E F
4-6 3/8 (11) 1 (25) 6 1/4 (159) 1/2 (13) 6 7/8 (175) 5/8 (17) 5 3/4 (147) 5/8 (17) 6 3/8 (163)
7-8 3/8 (11) 1 (25) 8 3/4 (222) 5/8 (17) 8 7/8 (227) 5/8 (17) 8 1/4 (211) 5/8 (17) 8 7/8 (227)
9-10 5/8 (17) 1 1/4 (33) 10 3/4 (274) 5/8 (17) 11 3/8 (290) 5/8 (17) 10 3/4 (274) 5/8 (17) 11 3/8 (290)
12 5/8 (17) 1 1/4 (33) 13 1/4 (338) 5/8 (17) 13 7/8 (354) 5/8 (17) 13 1/4 (338) 5/8 (17) 13 7/8 (354)
14 5/8 (17) 1 1/4 (33) 15 3/4 (401) 5/8 (17) 16 3/8 (417) 5/8 (17) 15 3/4 (401) 5/8 (17) 16 3/8 (417)
16 5/8 (17) 1 1/4 (33) 15 3/4 (401) 5/8 (17) 16 3/8 (417) 5/8 (17) 15 3/4 (401) 5/8 (17) 16 3/8 (417)
24X16 5/8 (17) 1 1/4 (33) 15 3/4 (401) 5/8 (17) 16 3/8 (417) 5/8 (17) 15 3/4 (401) 5/8 (17) 16 3/8 (417)
UNIT SIZE
2 ROW 3 ROW 4 ROW1 ROW
PIPING PACKAGE COILS
CENTER DIMENSIONS
CONTROLS/PIPING PACKAGE SAME SIDE
CONTROLS/PIPING PACKAGE OPPOSITE SIDE
E
F
F
E
PRICE PROVIDED TCV, 3 1/2" MAX
TCV BY OTHERS, HEIGHT VARIABLE
DEPENDENT ON MODEL
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SDV
273957
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
02/06/2023
OF REVSHEET 5 7© Copyright PRICE INDUSTRIES 2023
S o lid E d g e
SINGLE DUCT TERMINAL
VARIABLE VOLUME
WATER COIL NOTES
B
AIRFLOW
L
SLIP & DRIVE
CONNECTIONSUPPLY
RETURN
COIL CONNECTIONS COIL CONNECTIONS
1,2,3,4 ROWS 1,2 ROW 3,4 ROWS 1,2,3,4 ROWS 1,2 ROW 3,4 ROWS
4,5,6 305 203 22 127 184 4,5,6 12 8 7/8 5 7 1/4
7,8 305 254 22 127 184 7,8 12 10 7/8 5 7 1/4
9,10 356 318 22 127 184 9,10 14 12 1/2 7/8 5 7 1/4
12 406 381 22 127 184 12 16 15 7/8 5 7 1/4
14 508 445 22 127 184 14 20 17 1/2 7/8 5 7 1/4
16 610 457 22 127 184 16 24 18 7/8 5 7 1/4
24 X 16 965 457 22 127 184 24 X 16 38 18 7/8 5 7 1/4
NOMINAL
SIZE
B
(WIDTH)
C
(HEIGHT)
L
SI UNITS (mm)
NOMINAL
SIZE
IMPERIAL UNITS (in)
B
(WIDTH)
C
(HEIGHT)
L
C
SEE NOTE #6
NOTE:
1. FABRICATED FROM 22 GA. GALVANIZED STEEL 7. CONFIGURATION OF COIL CONNECTION VARIES
MECHANICALLY SEALED, LEAK RESISTANT WITH GPM RANGE SELECTIONS.
CONSTRUCTION. 8. PERFORMANCE RATED AND CERTIFIED IN ACCORDANCE
2. HOT WATER COILS HAVE COPPER TUBES AND WITH THE CURRENT EDITION OF AHRI STANDARD 410.
ALUMINUM FINS WITH O.D. SWEAT CONNECTIONS. 9. STANDARD COILS SUPPLIED WITH 10 FINS PER INCH.
3. REFER TO SUBMITTED TERMINAL UNIT SCHEDULE FOR 10. WATER CONNECTIONS ORIENTED TOWARDS DISCHARGE
AIR VOLUMES AND REHEAT COIL CAPACITIES. OR INLET, DEPENDING ON CONFIGURATION SELECTED.
4. METHOD OF VENTING PROVIDED ON PIPING PACKAGE. 11. IT IS NOT RECOMMENDED TO REVERSE 3 & 4 ROW COILS.
5. HANDING OF WATER COIL CONNECTIONS IS DETERMINED INDICATE HANDING WHILE ORDERING
WHEN VIEWED FROM AIR INLET SIDE WITH ACCESS 12. IMAGES NOT REPRESENTATIVE OF SUPPLY AND RETURN
DOOR ON BOTTOM. RIGHT HAND COIL CONNECTION LOCATIONS
ILLUSTRATED ABOVE.
6. ALLOW 1 1/2" [38] MINIMUM CLEARANCE FOR
INSTALLATION AT THIS END.
OPTIONS:
HC (HIGH CAPACITY) WATER COIL
HIGH CAPACITY COIL SUPPLIED WITH 12 FINS PER INCH.
1 AND 2 ROW COILS AVAILABLE.
7/8 ( 22 ) DIA @ 4 1/4 ( 108 )
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SDV
273957
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
02/06/2023
OF REVSHEET 6 7© Copyright PRICE INDUSTRIES 2023
S o lid E d g e
SINGLE DUCT TERMINAL
VARIABLE VOLUME
� ADD - DUAL ACCESS DOOR WITH SCREWS � ADDL - DUAL ACCESS DOOR WITH SNAP LATCHES
� ADDQ - DUAL ACCESS DOOR WITH QUARTER TURN LATCHES
CONSTRUCTION NOTES:
• EXTENSION INSULATED TO MATCH TERMINAL UNIT LINER.
• STANDARD DOOR SIZES PROVIDED AT 4" (102) X 6 3/4" (171).
• BOTTOM ACCESS DOORS FOR INSPECTION AND MAINTENANCE OF COIL.
• GASKETED PERIMETER INCLUDED WITH ALL FASTENER STYLES.
• INSULATED, 22 GAUGE GALVANIZED DUAL WALL ACCESS DOOR.
(NON-DUAL WALL WITH FIBER FREE)
DUAL COIL
ACCESS DOORS
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SDV
273957
PROJECT:
ENGINEER:
CUSTOMER:
SUBMITTAL DATE: SPEC. SYMBOL:
Submittal Sheet
02/06/2023
OF REVSHEET 7 7© Copyright PRICE INDUSTRIES 2023
S o lid E d g e
SINGLE DUCT TERMINAL
VARIABLE VOLUME
3 3/16 (81)
2 (51)1 (25)
1 1/2 (38)
3/4 (19)
O1/2 (13)
NOTES:
• HANGER BRACKET ARE 12 GAUGE GALVANIZED STEEL.
• 4 BRACKETS PER UNIT. 2 BRACKETS PER EXTENSION
• LAYOUT INDICATES SUGGESTED HANGER BRACKET LOCATIONS.
• BRACKETS ARE SHIPPED LOOSE FOR FIELD INSTALLATION FOR USE WITH FASTENERS AND THREADED HANGER RODS
(BY OTHERS).
HANGER BRACKETS
2 ( 51 ) TYP
2 52 TYP
2 49 TYP
2 51 TYP
2 51 TYP
2 ( 51 ) TYP
2 ( 51 ) TYP
Ductless Mini-Split Air Conditioning Units
Job Name/Location
Date:
PO No.:
Architect: GC:
Engr: Mech:
Rep:
(Company) (Project Manager)
Tag #:
• Night Quiet Operation
• Fault Detection and Diagnosis
Standard Features:
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
1. For AHRI rating, refer to the AHRI website http://www.ahridirectory.org.
2. The combination ratio must be between 50 – 130%.
3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard
3745.
4. Communication cable between ODU, IDU(s), and Central Controller must be a minimum of 2‐conductor, 18 AWG, twisted, stranded, and shielded. Ensure the communication cable shield is properly grounded to the ODU chassis only. Do not ground the communication cable at any other point. Wiring must comply with all applicable local and national codes.
5. Nominal data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95‐105%.
6. Power wiring cable size must comply with the applicable local and national codes.
7. The voltage tolerance is ± 10%.
Notes:
Optional Accessories:
For: File Resubmit Approval Other
Performance:
Cooling Mode:
Rated Capacity (Btu/h) Power Input1 (kW)
Heating Mode:
Rated Capacity (Btu/h) Power Input1 (kW)
Rated Capacity is based on the following conditions:
Cooling Indoor: 80°F DB / 67°F WB Outdoor: 95°F DB
Heating:
Indoor: 70°F DB Outdoor: 47°F DB / 43°F WB
Electrical:
Power Supply (V/Hz/Ø)
MOP (A)
MCA (A)
Rated Amps (A)
Compressor (A) Fan (A) x Qty.
208‐230V / 60 / 1
Refrigerant Charge (lbs) Liquid Line (in, OD) Vapor Line (in, OD)
Piping:
*Installation of an optional Low Ambient Wind Baffle Kit will allow operation down to ‐9.9°F in cooling mode.
Cooling (°F DB)* Heating (°F WB)
23 ‐ 122
Operating Range:
Refrigerant Type Refrigerant Control Max Number of Indoor Units2
Sound Pressure3 dB(A) Net Unit Weight (lbs) Shipping Weight (lbs) Communication Cable4 (No x AWG) Heat Exchanger Coating
R410A
EEV
2 x 18 GoldFin™
Unit Data:
Type Quantity Oil / Type
PVE/FVC68D
Compressor:
Type Quantity Motor / Drive Air Flow Rate (CFM)
Brushless Digitally Controlled/Direct
Fan:
Multi V™ S Heat Pump
Ø5/8 Braze
-4 to +61
2.77
6.6
43,000
0.5 x 2
Low Ambient Baffle Kit ZLABGP04A (2 required)
38,000
3,885
SB_MultiV_S_HP_ARUN038GSS4_2022_12_02_071548
DC Inverter Starting
Axial Flow Fan
3.22
3.0 Ton Outdoor Unit
19.5
ARUN038GSS4
Ø3/8 Braze
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 2 of 3
Job Name/Location:
Tag No.:
Date:
PO No.:Multi V™ S Heat Pump
SB_MultiV_S_HP_ARUN038GSS4_2022_12_02_071548
3.0 Ton Outdoor Unit
ARUN038GSS4
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 3 of 3
Job Name/Location:
Tag No.:
Date:
PO No.:
AHRI Data:
Indoor Unit Type Cooling Capacity (95°F) EER2 (95°F) SEER2 High Heating
Capacity (47°F) Low Heating
Capacity (17°F) HSPF2 Low Heating Capacity (5°F)
Heating COP at 5°F
Non‐Ducted Indoor Units
Ducted Indoor Units
51,000
Multi V™ S Heat Pump
2.1633,000
10.60
10.6051,00020.10
20.10
38,000
2.1638,000
SB_MultiV_S_HP_ARUN038GSS4_2022_12_02_071548
39,000
39,00033,000
3.0 Ton Outdoor Unit
ARUN038GSS4
14.00
14.00
Job Name/Location
PO No.:
Architect: GC:
Engr: Mech:
Rep:
(Company) (Project Manager)
Tag #:
• Night Quiet Operation
• Fault Detection and Diagnosis
Standard Features:
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
1. For AHRI rating, refer to the AHRI website http://www.ahridirectory.org.
2. The combination ratio must be between 50 – 130%.
3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard
3745.
4. Communication cable between ODU, IDU(s), and Central Controller must be a minimum of 2‐conductor, 18 AWG, twisted, stranded, and shielded. Ensure the communication cable shield is properly grounded to the ODU chassis only. Do not ground the communication cable at any other point. Wiring must comply with all applicable local and national codes.
5. Nominal data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95‐105%.
6. Power wiring cable size must comply with the applicable local and national codes.
7. The voltage tolerance is ± 10%.
Notes:
Optional Accessories:
For: File Resubmit Approval Other
Performance:
Cooling Mode:
Rated Capacity (Btu/h) Power Input1 (kW)
Heating Mode:
Rated Capacity (Btu/h) Power Input1 (kW)
Rated Capacity is based on the following conditions:
Cooling Indoor: 80°F DB / 67°F WB Outdoor: 95°F DB
Heating:
Indoor: 70°F DB Outdoor: 47°F DB / 43°F WB
Electrical:
Power Supply (V/Hz/Ø)
MOP (A)
MCA (A)
Rated Amps (A)
Compressor (A) Fan (A) x Qty.
208‐230V / 60 / 1
Refrigerant Charge (lbs) Liquid Line (in, OD) Vapor Line (in, OD)
Piping:
*Installation of an optional Low Ambient Wind Baffle Kit will allow operation down to ‐9.9°F in cooling mode.
Cooling (°F DB)* Heating (°F WB)
23 ‐ 122
Operating Range:
Refrigerant Type Refrigerant Control Max Number of Indoor Units2
Sound Pressure3 dB(A) Net Unit Weight (lbs) Shipping Weight (lbs) Communication Cable4 (No x AWG) Heat Exchanger Coating
R410A
EEV
2 x 18 GoldFin™
Unit Data:
Type Quantity Oil / Type
PVE/FVC68D
Compressor:
Type Quantity Motor / Drive Air Flow Rate (CFM)
Brushless Digitally Controlled/Direct
Fan:
Multi V™ S Heat Pump
Ø5/8 Braze
-4 to +61
4.3
6.6
54,000
0.5 x 2
Low Ambient Baffle Kit ZLABGP04A (2 required)
48,000
3,885
SB_MultiV_S_HP_ARUN048GSS4_2022_12_02_071549
DC Inverter Starting
Axial Flow Fan
4.2
4.0 Ton Outdoor Unit
23.1
ARUN048GSS4
Ø3/8 Braze
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 2 of 3
Job Name/Location:
Tag No.:
Date:
PO No.:Multi V™ S Heat Pump
SB_MultiV_S_HP_ARUN048GSS4_2022_12_02_071549
4.0 Ton Outdoor Unit
ARUN048GSS4
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 3 of 3
Job Name/Location:
Tag No.:
Date:
PO No.:
AHRI Data:
Indoor Unit Type Cooling Capacity (95°F) EER2 (95°F) SEER2 High Heating
Capacity (47°F) Low Heating
Capacity (17°F) HSPF2 Low Heating Capacity (5°F)
Heating COP at 5°F
Non‐Ducted Indoor Units
Ducted Indoor Units
54,500
Multi V™ S Heat Pump
2.1636,000
10.20
10.2054,50020.00
20.00
48,000
2.1648,000
SB_MultiV_S_HP_ARUN048GSS4_2022_12_02_071549
39,000
39,00036,000
4.0 Ton Outdoor Unit
ARUN048GSS4
13.20
13.20
Job Name/Location:
PO No.:
Architect: GC:
Engr: Mech:
Rep:
(Company) (Project Manager)
For: File Resubmit Approval Other
Tag #:
For a complete list of available accessories, contact your LG representative.
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
Notes:
1. See Engineering Manual for sensible and latent capacities.
2. Max. power input is rated at maximum setting value.
3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. If a Third-Party Dry Contact and an LG internal heater or an LG Auxiliary Heater Kit is installed, supplemental heat capability cannot be controlled by the Third-Party Thermostat.
5. All communication cable between Main outdoor units to indoor units / heat recovery units to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the Main outdoor unit chassis only. Do not ground the outdoor unit to indoor units / heat recovery units communication cable at any other point. Wiring must comply with all applicable local and national codes.
6. Power wiring is field provided and must comply with the applicable local and national codes.
7. This unit comes with a dry nitrogen charge.
8. All capacities are net with a combination ratio between 95 – 105%.
9. Must follow installation instructions in the applicable LG installation manual.
Performance:
Total Cooling Capacity (Btu/h)1
Heating Capacity (Btu/h)1
Max Power Input (W)2
H / M / L Power Input at Factory Default (W)
Electrical:
Power Supply (V/Hz/Ø) Rated Amps
208-230 / 60 / 1
Piping:
Refrigerant Liquid Line (in., O.D.)
Vapor Line (in., O.D.)
Condensate Condensate Line (in., I.D.)
Factory Installed Pump
No
Controls Features:
Optional Accessories:
Unit Data:
Refrigerant Type Refrigerant Control Sound Pressure dB(A) (H / M / L)3
Standard Filter Type Unit Net Weight (lbs.)
Unit Shipping Weight (lbs.)
R410A
EEV
Washable
Fan:
Type Quantity Motor/Drive Motor Quantity Air Flow Rate H / M / L (CFM)
Cross Flow
Brushless Digitally Controlled/Direct
• Auto changeover (Heat Recovery only)
• Auto operation
• Auto restart
• Dual thermistor control
• Dual setpoint control
• Multiple auxillary heater applications
• Timer (on/off)
• Weekly schedule
• Auto direction/ swing (up/down)
• Fan speed control
• Jet cool (fast cooling)
• Filter life display
• Child lock
• Group control
• Hot start
• Self diagnostics
• External on/off control
• Wi-Fi compatible
• Auto Fan
• Leak Detection
Wireless Remote Controller - PWLSSB21H MultiSITE™ CRC2 Controller - PREMTBVC2 MultiSITE™ CRC2+ Controller - PREMTBVC3 MultiSITE™ CRC2+Z Controller - PREMTBVC4 Simple Remote Controller - PREMTC00U Standard III Remote Controller – PREMTB100 Standard III Remote Controller – PREMTBB10 Remote Temperature Button Sensor - ZRTBS01 Simple Dry Contact (1 contact, 24 VAC external power) - PDRYCB100 Dry Contact for Third Party Thermostat - PDRYCB3204
Dry Contact for Economizer - PDRYCB400 Auxillary Heater Kit - PRARS14
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
Multi V™ Standard Wall Mounted Unit
5/8 Flare
32,000 30,000
49 / 44 / 42
3/8 Flare
SB_MultiV_Wall_Mounted_ARNU303SVA4_2023_09_20_113552
812 / 706 / 600
54 / 43 / 31
ARNU303SVA4
30,000 Btu/h Indoor Unit
0.51 http://www.ahridirectory.org
Tag No.:
Date:
PO No.:
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
Multi V™ Standard Wall Mounted Unit
SB_MultiV_Wall_Mounted_ARNU303SVA4_2023_09_20_113552
ARNU303SVA4
30,000 Btu/h Indoor Unit
PO No.:
Architect: GC:
Engr: Mech:
Rep:
(Company) (Project Manager)
For: File Resubmit Approval Other
Tag No.:
For a complete list of available accessories, contact your LG representative.
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
Notes:
1. See Engineering Manual for sensible and latent capacities.
2. Maximum power input is rated at maximum setting value.
3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Communication cable between (main) outdoor unit to indoor units / heat recovery units to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the (main) outdoor unit chassis only. DO NOT ground the outdoor unit to indoor units / heat recovery units communication cable at any other point. Wiring must comply with all applicable local and national codes.
5. Power wiring is field provided, and must comply with the applicable local and national codes.
6. This unit comes with a dry nitrogen charge.
7. All capacities are net with a combination ratio between 95 – 105%.
8. Must follow installation instructions in the applicable LG installation manual.
Performance:
Total Cooling Capacity (Btu/h)1
Heating Capacity (Btu/h)1
Maximum Power Input2
L/M/H Power Input at Factory Default (W)
Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.
Electrical:
Power Supply (V/Hz/Ø) Rated Amps
208-230/60/1
Piping:
Refrigerant Liquid Line (in., O.D.)
Vapor Line (in., O.D.)
Condensate Condensate Line (in., I.D.)
Factory Installed Pump
5/8 No
Controls Features:
Unit Data:
Refrigerant Type Refrigerant Control Sound Pressure dB(A) (H/M/L)3
Filter Type Unit Net Weight (lbs.)
Unit Shipping Weight (lbs.)
R410A
EEV
Washable
Fan:
Fan Type Fan Quantity Motor/Drive Motor Quantity Air Flow Rate H/M/L (CFM)
Cross Flow
Brushless Digitally Controlled/Direct
• Auto changeover
• Auto operation
• Auto restart
• Child lock
• Dual thermistor control
• Forced operation
• Group control
• High ceiling
• Hot start
• Self diagnostics
• Timer (on/off)
• Weekly schedule
• Auto direction / swing (up / down)
• Fan speed control
• Jet cool (fast cooling)
• Dual setpoint control
• Filter life display
• Wi-Fi compatible
• Leak detection
• Auto fan
• External on/off control
Optional Accessories:
Wireless Remote Controller - PQWRHQ0FDB MultiSITE™ CRC1 Controller - PREMTBVC0 MultiSITE™ CRC1+ Controller - PREMTBVC1 Simple Remote Controller - PREMTC00U Premium Remote Controller - PREMTA000 Remote Temperature Button Sensor - ZRTBS01 Simple Dry Contact (1 contact, 24 VAC external power) - PDRYCB100 Dry Contact for Third-Party Thermostat - PDRYCB320 Dry Contact for Economizer - PDRYCB400 Auxiliary Heater Kit - PRARH1 Wi-Fi Module - PWFMDD200
48,100
Multi V™ Ceiling Suspended
5/8 Flare
51,200
3/8 Flare
SB_MV_CeilingSuspended_ARNU483V2A4_2021_01_22_110547
1,024 / 848 / 706
91 / 79 / 66
ARNU483V2A4
48,100 Btu/h Indoor Unit
184 47 / 44 / 41
0.97
Tag No.:
Date:
PO No.:
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 2 of 2
Multi V™ Ceiling Suspended
SB_MV_CeilingSuspended_ARNU483V2A4_2021_01_22_110547
ARNU483V2A4
48,100 Btu/h Indoor Unit
Unit Heaters
Electric Heater Catalog . Page 6
EGHB INDUSTRIAL SUSPENDED UNIT HEATER
FEATURES
COLOR
• Standard: almond
FINISH
• Standard: epoxy/polyester powder paint
VOLTAGE
• 208V, 240V, 277V, 347V, 480V, 600V, 1 or 3-phase
CONSTRUCTION
• 18 and 20-gauge steel
• High-limit temperature control with automatic reset
FAN
• Motor mounted in cold compartment
• Thermally-protected motor
• Totally enclosed and factory-lubricated ball bearing motor
(except for 15 to 25kW at 208/240V)
• 58 dBA fan (2 to 10kW), 67 dBA fan (15 to 30kW) and 77 dBA fan (40 to 60kW)
• Fan delay purges heater of residual heat
HEATING ELEMENT
• Durable tubular heating elements; stainless steel (2 to 10kW);
• Concentric disposition of heating elements
• Factory sealed element upon request
CONTROL
• All models have a factory-installed contactor
• 240/208V control circuit standard (with transformer if necessary)
• 24V relay, with or without transformer available
• Built-in thermostat available
• 120V control circuit available
Manufacturer highly recommends to use a wall thermostat for greater comfort.
Any remote thermostat or relay must be connected to the heater control terminal block.
INSTALLATION
• Horizontal wall or ceiling mounting using one of two supplied brackets which allow 360° rotation (Horizontal mounting only for 40kW, 50kW and 60kW secured by 4 hooks [ceiling only])
• Vertical mounting using 4 threaded rods 1/2 inch X 13 UNC (not included) (except option -MD)
• Large and easily accessible control compartment
• Maximum recommended height (horizontal): 2 to 10kW: 8 ft. (2.4 m); 15 to 30kW: 10 ft. (3 m); 40 to 60kW: 15 ft. (4.5 m)
• Protective screen allows lower mounting height (except 40 to 60kW)
• Minimum height of 8 ft. (2.4 m) for 40 to 60kW heaters
• 30 °C (85 °F) maximum operating ambient temperature
WARRANTY
• 1-year warranty against defects
APPLICATION
• Commercial hall, warehouse, stairwell, factory
Electric Heater Catalog. Page 7
EGHB INDUSTRIAL SUSPENDED UNIT HEATER continued
MODELS
1 Models with the indications "3/1" can be field converted from 3 to 1-phase.
2 2-pole contactor is standard with single and 3-phase units. 3-pole contactor may be required by some codes for 3-phase.
3 For the U.S. only: The nominal current of the unit must not exceed 80% of the capacity of the disconnect.
4 For single or multiple unit control.
5 IR24: 24V signal by others (multiple units per thermostat). IR2B: for 24V thermostat on each unit.
6 All heaters have a 240V control circuit unless otherwise specified.
7 Field installed. Same thermostat as Option IC11.
8 CL1A thermostat requires option BT1.
Standard color is almond.
Size 2 3 4 5 7 10 15 20 25 30 40 50 60
Heating Capacity kW 2 3 4 5 7.5 10 15 15 20 20 25 25 30 40 50 60
MBH 7 10 14 17 26 34 51 51 68 68 85 85 102 136 171 205
Airflow cfm 510 510 510 700 700 700 1300 1400 1300 1400 1300 1400 1400 2000 2000 2000
Temperature Rise °F 13 18 25 23 34 45 36 34 49 45 61 56 68 63 79 95
°C 7 10 14 13 19 25 20 19 27 25 34 31 38 35 44 53
Motor
HP 1/30 1/30 1/30 1/30 1/30 1/30 1/8 1/3 1/8 1/3 1/8 1/3 1/3 3/4 3/4 3/4
@ 277V and lower RPM 1550 1550 1550 1550 1550 1550 1550 1550 1550
@ 480V and Higher RPM 1550 1550 1550 1550 1550 1550 1725 1725 1725 1725 1140 1140 1140
Ship Weight Lbs 45 45 45 45 45 45 85 85 85 85 85 85 85 150 150 150
Kg 20 20 20 20 20 20 39 39 39 39 39 39 39 68 68 68
Factory Installed Options
Supply Voltage/ Phase
208/1 AK2
208/3 AK5
208/3-1 1 AK15
240/1 AK3E
240/3 AK6E
240/3-1 1 AK16
277/1 AK4
347/1 AK34
480/1 AK9E
480/3 AK7E
600/3 AK8E
Triple Pole Contactor (3ph) 2 AN6
Disconnect Switch 3
40A BA14
80A BA15
100A BA16
Branch Circuit Fusing BA12
Unit Mounted Summer Fan Switch BF4A
Control Voltage
208V, 240V, 277V STD
24V relay with transformer 4 BT1
120V contactor with transformer BT2
Manual High Limit BD6 Summer Fan Relay
24V, remote control (Fan Switch must be ordered separately)
CV24
Internal Thermostat IC11
Field Installed Options (shipped separately)
Size 2 3 4 5 7 10 15 20 25 30 40 50 60
24V Relay Kit 5 Without transformer IR24
240V transformer 6 IR2B
Unit Mounted Thermostat Kit 7 IT13
Wall Mounted Thermostats
Single-pole, low-voltage thermostat 8 CL1A
Single-pole, single stage thermostat CL5
Vertical Cone Diffuser CD70
Electric Heater Catalog . Page 8
I
B
H
D
A
C
E
F
G (min.)
4 Threaded Rods
(1/2" - 13 UNC)
(Not Included)
Standard Installation
Side View Motor in Cold Section
Small Area Large Area
Motor
Fan
Heating Elements
Louvres
EGHB INDUSTRIAL SUSPENDED UNIT HEATER continued
2 - 10kW 15 - 30kW 40 - 60kW mm inch mm inch mm inch
A 305 12 444 17 1/2 585 23 B 419 16 1/2 556 21 7/8 641 25 1/4 C 432 17 572 22 1/2 870 34 1/4 D 357 14 1/16 470 18 1/2 - - E 290 11 7/16 407 16 - - F 490 19 5/16 630 24 13/16 924 36 3/8 G 305 12 305 12 305 12 H 123 4 7/8 148 5 13/16 305 12 I 428 16 7/8 592 23 5/16 890 35
Weight kg lb kg lb kg lb 20 45 39 85 68 150
DIMENSIONS
Electric Heater Catalog . Page 20
FEATURES
COLOR
• White or almond options
FINISH
• Standard: epoxy/polyester powder paint
• Optional: anodized aluminum
VOLTAGE
• 120V, 208V, 240/208V, 277V, 347V, 480V, 600V, 1-phase
CONSTRUCTION
• Extruded aluminum front grille, 1/8 in. (3.2 mm) thick
• Bottom air outlet
• High-limit temperature control with automatic reset
FAN
• Closed, factory-lubricated motor
• 160 cfm fan (single unit: 55 dBA); 2 X 160 cfm fan (double unit:
58 dBA), 3 X 160 cfm fan (triple unit: 61 dBA)
• Fan delay purges heater of residual heat
HEATING ELEMENT
CONTROL
• Built-in tamper proof thermostat included
• 24V relay, with or without transformer available
Note: Thermostat is not included in heater with factory installed relay. Any remote thermostat or relay must be connected to the heater control terminal block.
INSTALLATION
10 in. (25.4 cm).
• Adaptor for surface mounting available.
• Up to 3 units can be mounted side-by-side
WARRANTY
• 3-year warranty against defects
APPLICATION
• Apartment building, commercial building, entrance way, stairwell, garage
EHA FORCED-AIR ARCHITECTURAL WALL HEATER
KOE Ø22 mm
KOE Ø7/8"
KOE Ø22 mm
KOE Ø7/8"
408 mm 16 1/16"
810 mm 31 7/8"
767 mm 30 3/16"
1227 mm 48 5/16"
1185 mm 46 5/8"
578 mm 22 3/4"
40 mm 1 9/16"
368 mm 14 7/16"
51 mm 2"
212 mm 8 5/16"
74 mm 2 7/8" 55 mm
2 3/16"
34 mm 1 5/16"
506 mm 19 7/8"
34 mm 1 5/16"
51 mm 2"
51 mm 2"
Installation (All Models)Side View (All Models)
Surface
Recessed
Front ViewFront View Front ViewSide View
Top View Top ViewTop View
Required Wall Depth Opening
Single Unit Double Unit Triple Unit
109 mm 4 5/16"
107 mm 4 3/16"
584 mm 23"
Electric Heater Catalog. Page 21
EHA FORCED-AIR ARCHITECTURAL WALL HEATER continued
MODELS
Size 1 2 3 4 5
Heating Capacity W 1500 2000 3000 4000 4800
BTUH 5125 6825 10250 13660 16400
Ship Weight Lbs 24 24 24 24 24
Kg 10.9 10.9 10.9 10.9 10.9
Factory Installed Options
Supply Voltage/Phase
120/1 AK1E
208/1 AK2
240/1 1 AK3E
277/1 AK4
480/1 AK9E
Cabinet Color (Lead times may be increased for color other than white)
White HK1
Almond HK2
Thermostat Hidden, tamper-proof, built-in thermostat STD
Control Voltage
120V, 208V, 240V, 277V & 480V STD
24V Relay with transformer 2 BT1
Disconnect Switch 3 Up to 277V, 2-pole, 20A BA21
600V max., 3-pole, 40A BA14
Field Installed Options (shipped separately)
Size 1 2 3 4 5
Color Matched Trim Packages Surface mounting box required for non-recessed units HY6
1 Units with Option AK3E (240V supply voltage) can be connected to 208V power supply, but heating output will be reduced by 25%.
2 Built-in transformer is not included with 24V control voltage (Option BT1).
3 For the U.S. only: The nominal current of the unit must not exceed 80% of the capacity of the disconnect.
Electric Heater Catalog . Page 22
EHC COMMERCIAL WALL HEATER
FEATURES
COLOR
• White or almond options
FINISH
• Standard: epoxy/polyester powder paint
VOLTAGE
• 120V, 208V, 240/208V, 277V, 347V, 480V, 600V, 1 or 3-phase
CONSTRUCTION
• 18-gauge steel front cover
• Bottom air outlet
• High-limit temperature control with automatic reset
FAN
• Closed, factory-lubricated motor
• 160 cfm fan (single unit: 55 dBA); 2 X 160 cfm fan (double unit:
58 dBA); 3 X 160 cfm fan (triple unit: 61 dBA)
• Fan delay purges heater of residual heat
HEATING ELEMENT
CONTROL
• Built-in thermostat included with control knob or tamper proof
• 24V relay, with or without transformer available
Note: Thermostat is not included in heater with factory installed relay. Any remote thermostat or relay must be connected to the heater control terminal block.
INSTALLATION
10 in. (25.4 cm).
• Adaptor for surface mounting available.
• Up to 3 units can be mounted side-by-side
WARRANTY
• 1-year warranty against defects
APPLICATION
• Apartment building, commercial building, entrance way, stairwell, garage
KOE Ø22 mm
KOE Ø7/8"
KOE Ø22 mm
KOE Ø7/8"
368 mm 14 7/16" 51 mm
2" 212 mm 8 5/16"
74 mm 2 7/8" 55 mm
2 3/16"
34 mm 1 5/16"
506 mm 19 7/8"
34 mm 1 5/16"
51 mm 2"
51 mm 2"
Installation (All Models)Side View (All Models)
Surface
Recessed
Front View Front View Front ViewSide View
Top View Top ViewTop View
Required Wall Depth Opening
Single Unit
104 mm 4 1/8"
410 mm 16 1/8"
810 mm 31 7/8"
767 mm 30 3/16"
1227 mm 48 5/16"
1185 mm 46 5/8"
561 mm 22 1/16"
33 mm 1 5/16"
104 mm 4 1/8"
561 mm 22 1/16"
Double Unit Triple Unit
Electric Heater Catalog. Page 23
EHC COMMERCIAL WALL HEATER continued
MODELS
Size 1 2 3 4 5 6 8 12
Heating Capacity W 1500 2000 3000 4000 4800 6000 8000 12000
BTUH 5125 6825 10250 13660 16400 20500 27620 40975
Ship Weight Lbs 24 24 24 24 24 90.0 50 90.0
Kg 10.9 10.9 10.9 10.9 10.9 40.9 22.7 40.9
Factory Installed Options
Supply Voltage/ Phase
120/1 AK1E
208/1 AK2
208/3 AK5
240/1 1 AK3E
240/3 AK6E
347/1 AK34
480/1 AK9E
480/3 AK7E
600/1 AK10
600/3 AK8E
Cabinet Color White HK1
Almond HK2
Control Voltage 208V, 240V 2 STD
Unit Mounted Fan Switch BF23
Disconnect Switch 3
Up to 277V, 2-pole, 20A BA21
600V, 3-pole, 40A BA14
600V, 3-pole, 80A BA15
Field Installed Options (shipped separately)
Size 1 2 3 4 5 6 8 12
Color Matched Trim Packages
Surface mounting box required for non-recessed units HY6
1" recessed trim kit HY4A
2" recessed trim kit HY4B
1 Units with Option AK3E (240V supply voltage) can be connected to 208V power supply, but heating output will be reduced by 25%.
2 208V/240V control (& fan motor) is standard on all units.
3 For the U.S. only: The nominal current of the unit must not exceed 80% of the capacity of the disconnect.
Electric Heater Catalog . Page 28
MECHANICAL THERMOSTATS
MODELS
CL5
Mechanical, wall mounted, line voltage thermostat, single-pole, single-throw.
Not for use with model EXB.
CL1A
Wall mounted, single-pole, low-voltage thermostat. Not for use with model
EXB.
CX1
Explosion resistant, wall mounted thermostat, 40°80°F.
ELECTRICAL FUNDAMENTALS
The relationship between Wattage (heat) output and the applied Voltage of electric resistance heating elements is determined by a precise physical rule defined as Ohm’s Law which states that the current in a resistance heating element is directly proportional to the applied Voltage.
Ohm’s Law is traditionally expressed as:
The same equation using the conventional abbreviation for voltage is:
An unknown electrical value can be derived by using any two known values in one of the variations of Ohm’s Law shown at the right.
I = E Where: I = Amperes (Current) R E = Voltage
R = Ohms (Resistance)
I = V Where: I = Amperes (Current) R V = Voltage
R = Ohms (Resistance)
OHM’S LAW
W I
W
RIR
W V
V R
W I
V I
V R
VI
I2R
WR
2V W
V
(VOLTS)
I
(AMPS)
(OHMS)
R
(WATTS)
W
WATTS
AMPERES
VOLTS
VOLTS = WATTS x OHMS
VOLTS =
VOLTS = AMPERES x OHMS
VOLTS
AMPERES
WATTS
AMPERES2
VOLTS2
WATTS
OHMS
OHMS =
OHMS =
OHMS = VOLTS2
OHMS
WATTS
WATTS = VOLTS x AMPERES
WATTS = AMPERES2 x OHMS
WATTS =
VOLTS
OHMS
WATTS
VOLTS
WATTS
OHMS
AMPERES
AMPERES =
AMPERES =
AMPERES =
Electric Heater Catalog. Page 29
ELECTRIC CURRENT TABLE
FAQ
What is required for properly sizing a heater in my room?
- If you have a room with 8 feet ceiling height; you can calculate the square footage times 10 watts per square foot.
- If your ceiling is higher than 8 feet; calculate the cubic footage L x W x H and multiply by I watt per square foot.
- If you plan on heating a garage calculate the cubic footage L x W x H and multiply by I watt per square foot and multiply the square footage for each garage door by 48 (watts per square foot) and add this amount to the cubic footage. This will be the amount required to heat the garage.
Are 120 volts and 240 volts heaters interchangeable?
- A 240 volts heater run at 120 volts will produce 1/4 of the rated wattage. A 120 volts heater run at 240 volts will be destroyed and could cause fire damage to the building.
If I know the BTU's required; how do I calculate the watts required?
- Watts = BTU/3.412 (I Watt = 3.41 BTU)
Calculating Temperature Rise?
- Sometimes your heater does not feel like it is putting out enough heat. Why not, you ask?
- Temperature rise is calculated by taking the kW times the constant 3167 divided by the CFM. For instance:
5kW x 3167/300CFM = 15835/300CFM = 52.8 °F. If your ambient temperature is 60 °F the outlet air is 112 °F.
Power kW
Voltage (ph) 120V (1) 208V (1) 208V (3) 240V (1) 240V (3) 277V (1)
0.3 2.50 1.45 0.83 1.25 0.72 1.09
0.4 3.34 1.92 1.11 1.67 0.97 1.45
0.5 4.17 2.41 1.39 2.09 1.21 1.81
0.6 5.00 2.89 1.66 2.50 1.45 2.17
0.75 6.25 3.61 2.09 3.13 1.81 2.71
0.8 6.67 3.85 2.23 3.34 1.93 2.89
1.0 8.34 4.81 2.78 4.17 2.41 3.61
1.2 10.00 5.77 3.34 5.00 2.89 4.34
1.25 10.42 6.01 3.47 5.21 3.01 4.52
1.4 11.67 6.73 3.89 5.84 3.38 5.06
1.5 12.50 7.22 4.17 6.25 3.61 5.42
1.6 13.34 7.70 4.45 6.67 3.86 5.78
1.75 14.59 8.42 4.87 7.30 4.22 6.32
2.0 16.67 9.62 5.56 8.34 4.82 7.22
2.25 18.75 10.82 6.25 9.38 5.42 8.13
2.5 20.84 12.02 6.95 10.42 6.02 9.03
3.0 25.00 14.43 8.34 12.50 7.23 10.83
4.0 33.34 19.23 11.12 16.67 9.64 14.44
4.5 37.50 21.64 12.50 18.75 10.84 16.25
5.0 41.67 24.04 13.90 20.84 12.05 18.05
6.0 50.00 28.85 16.68 25.00 14.45 21.66
7.5 62.50 36.06 20.84 31.25 18.06 27.08
8.0 66.67 38.47 22.23 33.34 19.27 28.88
9.0 75.00…