WWYK263009_65 Design Analysis Part 28_Part2.pdf

PDF 12 MB Posted

Attached to
Bomber Agile Common Hangar; 4-Dock Hangar at Tinker Air Force Base
Solicitation number
W912BV25S0014
Issued by

About this file

These files contain submittal sheets, specifications and engineering drawings for HVAC equipment including air-cooled scroll chillers, ductless mini-split systems, unit heaters, and wall heaters.

The documents detail technical specifications for multiple pieces of HVAC equipment: YORK YLAA air-cooled scroll chillers (40-230 tons capacity), LG Multi V™ S heat pump outdoor units (3-4 ton), Reznor EGHB industrial suspended unit heaters, EHA forced-air architectural wall heaters, and EHC commercial wall heaters. The documents provide comprehensive details on features, performance ratings, physical dimensions, electrical requirements, control options, and installation parameters. Key equipment features described include factory-assembled packages, BACnet/Modbus controls compatibility, multiple efficiency level options, and various sound attenuation capabilities. The drawings include detailed dimensional diagrams, mounting specifications, and connection requirements. Equipment options like variable speed drives, pump packages, and protective coatings are also detailed.

View the file

Other files

File Type Posted
WWYK263009_65 Design Analysis_Part12_Part2.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part6_Part1.pdf PDF
WWYK263009_65 Design Analysis_Part18_Part6.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part1.pdf PDF
WWYK263009_65 Design Analysis Part 28_Part3.pdf PDF
WWYK263009_65 Drawings_Volume 2_Part5.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part6_Part2.pdf PDF
WWYK263009_65_NG-LCCA_BLCC_Summary Report.pdf PDF
WWYK263009_65 Design Analysis_Part24.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part4_Part7.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part4.pdf PDF
WWYK263009_65 Design Analysis_Part22_Part4_Part3.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part4_Part1.pdf PDF
WWYK263009_65 Design Analysis_Part17.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part19_Part3.pdf PDF
WWYK263009_65 Design Analysis_Part10.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part8.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part1.pdf PDF
WWYK263009_65_NG_energy model results.pdf PDF
Bomber Agile Common Hangar Industry Forum Presentation.pdf PDF
WWYK263009_65 Drawings_Volume 2_Part6.pdf PDF
WWYK263009_65 Design Analysis_Part22_Part4_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part18_Part2.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part4_Part4.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part7.pdf PDF
WWYK263009_65 Design Analysis_Part21.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part6_Part4_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part23.pdf PDF
WWYK263009_65 Design Analysis_Part22_Part2.pdf PDF
WWYK263009_65 Design Analysis_Part4.pdf PDF
WWYK263009_65 Design Analysis_Part19_Part2.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part3.pdf PDF
WWYK263009_65 Design Analysis_Part20.pdf PDF
WWYK263009_65 Design Analysis_Part26.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part5.pdf PDF
WWYK263009_65 Design Analysis_Part19_Part4.pdf PDF
WWYK263009_65 Design Analysis_Part27.pdf PDF
WWYK263009_65 Design Analysis_Part18_Part5.pdf PDF
WWYK263009_65 Design Analysis_Part15.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part3.pdf PDF
WWYK263009_65 Design Analysis Part 28_Part4.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part9.pdf PDF
WWYK263009_65 Design Analysis_Part9.pdf PDF
WWYK263009_65 Design Analysis_Part12_Part4.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part7_Part1.pdf PDF
WWYK263009_65 Drawings_Volume 1_Part1_Part5.pdf PDF
WWYK263009_65_NG-LCCA_BLCC results.pdf PDF
WWYK263009_65 Design Analysis_Part7.pdf PDF
Show 40 more

Latest 50 of 95 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SDV

270487

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

04/05/2021

OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2021

S o lid E d g e

SDV-1-1

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SINGLE DUCT TERMINAL

VARIABLE VOLUME

ROUND DISCHARGE

COLLAR

INLET SIZES WIDTH HEIGHT

D W H A B L

4 3

/8 (98)

5 4 /8 (124)

6 5 /8 (149)

7 6 /8 (175)

8 7 /8 (200)

9 8 /8 (225)

10 9 /8 (251)

12 11

/8 (302) 16 (406) 15 (381)

14 13

/8 (352) 20 (508) 17

/2 (445)

16 15

/8 (403) 24 (610) 18 (457)

UNIT

SIZE

/8 (162)

/8 (111)

LENGTH

10 (254)

14 (356) 12

/2 (318)

/4 (489)5

/16 (135)

12 (305)

8 (203)

/16 (97) 15

/4 (400)

STANDARD CONSTRUCTION:

• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS

REQUIREMENTS OF NFPA 90A AND UL181.

• 22 GAUGE GALVANIZED STEEL HOUSING. MECHANICALLY SEALED, LEAK

RESISTANT CONSTRUCTION.

• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT DUCT

CONNECTION.

• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.

• 1/2" (13mm) GALVANIZED DAMPER SHAFT WITH POSITION INDICATOR.

• LEFT HAND UNIT SHOWN (CLH) RIGHT HAND AVAILABLE.

UNIT OPTIONS:

� NEMA1 CONTROLS ENCLOSURE (PS)

� DISCONNECT SWITCH (DSW)

� 20 GAUGE CASING (20GA)

� HANGER BRACKETS (HB)

� BOTTOM REMOVABLE SENSOR (RS)

� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)

BOTTOM ACCESS DOOR:

� ACCESS DOOR WITH SCREWS (AD)

� ACCESS DOOR WITH SNAP LATCHES (ADL)

� ACCESS DOOR WITH QUARTER TURN LATCHES (ADQ)

CONTROLS OPTIONS:

� FIELD MOUNTED CONTROLS, SUPPLIED BY OTHERS (FLD)

� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)

CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP):

� DIGITAL CONTROLS (DIG)

� PNEUMATIC CONTROLS (PNEU)

H

W 4 3/4" (121)

9 1/2" (241)

2" (51)

18 1/2" (470)

A

DOPTIONAL NEMA1

CONTROLS

ENCLOSURE

LINER OPTIONS:

� FIBERGLASS 1" (25mm) (FG1)

� FIBER FREE FOAM 1/2" (13mm) (FF50)

� FIBER FREE FOAM 3/4" (19mm) (FF75)

� FIBER FREE FOAM 1" (25mm) (FF1)

� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)

� SOLID METAL WITH FG1 (SM1)

� CLEANROOM ANGLES WITH FB1 (CRAF1)

� PERFORATED METAL WITH FB1 (AFPM1)

6 3/8" (162)

SIZE 4 & 5 ONLY

L 4" (102)

D

3 5/16" (84)

B

MULTI-POINT

SENSOR

OPTIONAL ACCESS DOOR

ROUND

DISCHARGE

COLLAR

UNIT OPTIONS:

� NEMA1 CONTROLS ENCLOSURE (PS)

� DISCONNECT SWITCH (DSW)

� 20 GAUGE CASING (20GA)

� HANGER BRACKETS (HB)

� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)

BOTTOM ACCESS DOOR:

� ACCESS DOOR WITH QUARTER TURN LATCHES (ADQ)

• SIZES 4 TO 8 ACCESS SIZE IS 10" (254) X 12" (305)

• SIZES 9 TO 16 ACCESS SIZE IS 12" (305) X 12" (305)

270456

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

04/05/2021

OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2021

S o lid E d g e

SDV-1-1

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SINGLE DUCT TERMINAL

VARIABLE VOLUME

CERTIFIED LOW LEAKAGE

INLET SIZES WIDTH HEIGHT

D W H A B L

4 3

/8 (98)

5 4

/8 (124)

6 5

/8 (149)

7 6

/8 (175)

8 7

/8 (200)

9 8

/8 (225)

10 9

/8 (251)

12 11

/8 (302) 16 (406) 15 (381)

14 13

/8 (352) 20 (508) 17

/2 (445)

16 15

/8 (403) 24 (610) 18 (457)

UNIT

SIZE

/8 (162)

/8 (111)

LENGTH

10 (254)

14 (356) 12

/2 (318)

/4 (489)5

/16 (135)

12 (305)

8 (203)

/16 (97) 15 /4 (400)

H

W 4 3/4" (121)

9 1/2" (241)

2" (51) 18 1/2" (470) B

A L D

OPTIONAL NEMA1

CONTROLS

ENCLOSURE

6 3/8" (162)

SIZE 4 & 5 ONLY

CONTROLS OPTIONS:

� FIELD MOUNTED CONTROLS, SUPPLIED BY OTHERS (FLD)

� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)

CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP):

� DIGITAL CONTROLS (DIG)

� PNEUMATIC CONTROLS (PNEU)

LINER OPTIONS:

� FIBERGLASS 1" (25mm) (FG1)

� FIBER FREE FOAM 1/2" (13mm) (FF50)

� FIBER FREE FOAM 3/4" (19mm) (FF75)

� FIBER FREE FOAM 1" (25mm) (FF1)

� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)

� SOLID METAL WITH FG1 (SM1)

� CLEANROOM ANGLES WITH FB1 (CRAF1)

� PERFORATED METAL WITH FB1 (AFPM1)

STANDARD CONSTRUCTION:

• FACTORY LEAK TESTED CASING UP TO 1.5% OF MAX FLOW AT 6" W.G.

• FACTORY LEAK TESTED DAMPER UP TO 1% OF MAX FLOW AT 6" W.G.

• LEAKAGE CERTIFICATION LABEL PROVIDED BY FACTORY.

• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS

REQUIREMENTS OF NFPA 90A AND UL181.

• 22 GAUGE GALVANIZED STEEL HOUSING. MECHANICALLY SEALED,

LEAK RESISTANT CONSTRUCTION.

• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT

DUCT CONNECTION.

• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.

• 1/2" (13mm) GALVANIZED DAMPER SHAFT WITH POSITION INDICATOR.

• LEFT HAND UNIT SHOWN (CLH) RIGHT HAND AVAILABLE.

MULTI-POINT SENSOR OPTIONAL ACCESS DOOR

270472

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

04/05/2021

OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2021

S o lid E d g e

SDV-1-1

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SINGLE DUCT TERMINAL

VARIABLE VOLUME

CERTIFIED LOW LEAKAGE

WATER COIL

H

W 4 3/4" (121)

9 1/2" (241)

2" (51)

18 1/2" (470)

A

INLET SIZES WIDTH HEIGHT

D W H A B L

4 3

/8 (98)

5 4

/8 (124)

6 5

/8 (149)

7 6

/8 (175)

8 7

/8 (200)

9 8

/8 (225)

10 9

/8 (251)

12 11

/8 (302) 16 (406) 15 (381)

14 13

/8 (352) 20 (508) 17

/2 (445)

16 15

/8 (403) 24 (610) 18 (457)

UNIT

SIZE

/8 (162)

/8 (111)

LENGTH

10 (254)

14 (356) 12

/2 (318)

/4 (489)5

/16 (135)

12 (305)

8 (203)

/16 (97) 15

/4 (400)

UNIT OPTIONS:

� NEMA1 CONTROLS ENCLOSURE (PS)

� DISCONNECT SWITCH (DSW)

� 20 GAUGE CASING (20GA)

� HANGER BRACKETS (HB)

� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)

UNIT ACCESS DOOR:

� ACCESS DOOR WITH QUARTER TURN LATCHES (ADQ)

• SIZES 4 TO 8 ACCESS SIZE IS 10" (254) X 12" (305)

• SIZES 9 TO 16 ACCESS SIZE IS 12" (305) X 12" (305)

D

OPTIONAL NEMA1

CONTROL

ENCLOSURE

CONTROLS OPTIONS:

� FIELD MOUNTED CONTROLS, SUPPLIED BY OTHERS (FLD)

� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)

CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP):

� DIGITAL CONTROLS (DIG)

� PNEUMATIC CONTROLS (PNEU)

LINER OPTIONS:

� FIBERGLASS 1" (25mm) (FG1)

� FIBER FREE FOAM 1/2" (13mm) (FF50)

� FIBER FREE FOAM 3/4" (19mm) (FF75)

� FIBER FREE FOAM 1" (25mm) (FF1)

� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)

� SOLID METAL WITH FG1 (SM1)

� CLEANROOM ANGLES WITH FB1 (CRAF1)

� PERFORATED METAL WITH FB1 (AFPM1)

6 3/8" (162)

SIZE 4 & 5 ONLY

STANDARD CONSTRUCTION:

• FACTORY LEAK TESTED CASING UP TO 1.5% OF MAX FLOW AT 6" W.G.

• FACTORY LEAK TESTED DAMPER UP TO 1% OF MAX FLOW AT 6" W.G.

• LEAKAGE CERTIFICATION LABEL PROVIDED BY FACTORY.

• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS

REQUIREMENTS OF NFPA 90A AND UL181.

• 22 GAUGE GALVANIZED STEEL HOUSING. MECHANICALLY SEALED, LEAK

RESISTANT CONSTRUCTION.

• RECTANGULAR DISCHARGE WITH SLIP AND DRIVE CLEAT DUCT CONNECTION.

• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.

• 1/2" (13mm) GALVANIZED DAMPER SHAFT WITH POSITION INDICATOR.

• LEFT HAND UNIT SHOWN (CLH) RIGHT HAND AVAILABLE.

MULTI-POINT

SENSOR

OPTIONAL ACCESS

DOOR

EXTERNALLY

WRAPPED

1" (25) FOIL FACED

FIBERGLASS BOARD

L 1&2 ROW = 5" (127)

3&4 ROW = 7 1/4" (184)

A

272770

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

02/01/2023

OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2023

S o lid E d g e

SDV-1-1

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SINGLE DUCT TERMINAL

VARIABLE VOLUME

CERTIFIED LOW LEAKAGE

ATTENUATORS

CONTROLS OPTIONS:

� FIELD MOUNTED, CONTROLS SUPPLIED BY OTHERS (FLD)

� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)

CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP):

� DIGITAL CONTROLS (DIG)

� PNEUMATIC CONTROLS (PNEU)

ATT= 35 13/16" (910)

ATT5= 55 1/2" (1410)

W

H

4 3/4" (121)

9 1/2" (241)

D

OPTIONAL NEMA1

CONTROLS

ENCLOSURE

6 3/8" (162)

SIZE 4 & 5 ONLY

INLET SIZES WIDTH HEIGHT

D W H A B L

4 3 /8 (98)

5 4 /8 (124)

6 5 /8 (149)

7 6 /8 (175)

8 7 /8 (200)

9 8 /8 (225)

10 9 /8 (251)

12 11 /8 (302) 16 (406) 15 (381)

14 13 /8 (352) 20 (508) 17

/2 (445)

16 15 /8 (403) 24 (610) 18 (457)

UNIT

SIZE

/8 (162)

/8 (111)

LENGTH

10 (254)

14 (356) 12

/2 (318)

/4 (489)5

/16 (135)

12 (305)

8 (203)

/16 (97) 15 /4 (400)

LINER OPTIONS:

� FIBERGLASS 1" (25mm) (FG1)

� FIBER FREE FOAM 1/2" (13mm) (FF50)

� FIBER FREE FOAM 3/4" (19mm) (FF75)

� FIBER FREE FOAM 1" (25mm) (FF1)

� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)

� SOLID METAL WITH FG1 (SM1)

� CLEANROOM ANGLES WITH FB1 (CRAF1)

� PERFORATED METAL WITH FB1 (AFPM1)

UNIT OPTIONS:

� NEMA1 CONTROLS ENCLOSURE (PS)

� DISCONNECT SWITCH (DSW)

� 20 GAUGE CASING (20GA)

� HANGER BRACKETS (HB)

� BOTTOM REMOVABLE SENSOR (RS)

� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)

BOTTOM ACCESS DOOR:

� ACCESS DOOR WITH QUARTER TURN LATCHES (ADQ)

• SIZES 4 TO 8 ACCESS SIZE IS 10" (254) X 12" (305)

• SIZES 9 TO 16 ACCESS SIZE IS 12" (305) X 12" (305)

STANDARD CONSTRUCTION:

• FACTORY LEAK TESTED CASING UP TO 1.5% OF MAX FLOW AT 6" W.G.

• FACTORY LEAK TESTED DAMPER UP TO 1% OF MAX FLOW AT 6" W.G.

• LEAKAGE CERTIFICATION LABEL PROVIDED BY FACTORY.

• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS

REQUIREMENTS OF NFPA 90A AND UL181.

• 22 GAUGE GALVANIZED STEEL HOUSING. MECHANICALLY SEALED,

LEAK RESISTANT CONSTRUCTION.

• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT

DUCT CONNECTION.

• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.

• 1/2" (13mm) GALVANIZED DAMPER SHAFT WITH POSITION INDICATOR.

• LEFT HAND UNIT SHOWN (CLH) RIGHT HAND AVAILABLE.

MULTI-POINT

SENSOR

2" (51) 18 1/2" (470) B

A L

OPTIONAL ACCESS DOOR

273390

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

04/05/2021

OF REVSHEET 1 1© Copyright PRICE INDUSTRIES 2021

S o lid E d g e

SDV-1-1

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SINGLE DUCT TERMINAL

VARIABLE VOLUME

CERTIFIED LOW LEAKAGE

WATER COIL

OVERSIZED

UNIT OPTIONS:

� NEMA1 CONTROLS ENCLOSURE (PS)

� DISCONNECT SWITCH (DSW)

� 20 GAUGE CASING (20GA)

� HANGER BRACKETS (HB)

� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)

BOTTOM ACCESS DOOR:

� ACCESS DOOR WITH SCREWS (AD)

� ACCESS DOOR WITH SNAP LATCHES (ADL)

� ACCESS DOOR WITH QUARTER TURN LATCHES (ADQ)

STANDARD CONSTRUCTION:

• FACTORY LEAK TESTED CASING UP TO 1.5% OF MAX FLOW AT 6" W.G.

• FACTORY LEAK TESTED DAMPER UP TO 1% OF MAX FLOW AT 6" W.G.

• LEAKAGE CERTIFICATION LABEL PROVIDED BY FACTORY.

• DIMENSIONAL TABLE REPRESENTS OVERSIZED CONSTRUCTION (OS).

• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS REQUIREMENTS

OF NFPA 90A AND UL181.

• 22 GAUGE GALVANIZED STEEL HOUSING. MECHANICALLY SEALED, LEAK RESISTANT

CONSTRUCTION.

• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT DUCT CONNECTION.

• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.

• 1/2" (13mm) GALVANIZED DAMPER SHAFT WITH POSITION INDICATOR.

• LEFT HAND UNIT SHOWN (CLH), RIGHT HAND AVAILABLE.

CONTROLS OPTIONS:

� FIELD MOUNTED CONTROLS, SUPPLIED BY OTHERS (FLD)

� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)

CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP):

� DIGITAL CONTROLS (DIG)

� PNEUMATIC CONTROLS (PNEU)

LINER OPTIONS:

� FIBERGLASS 1" (25mm) (FG1)

� FIBER FREE FOAM 1/2" (13mm) (FF50)

� FIBER FREE FOAM 3/4" (19mm) (FF75)

� FIBER FREE FOAM 1" (25mm) (FF1)

� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)

� SOLID METAL WITH FG1 (SM1)

� CLEANROOM ANGLES WITH FB1 (CRAF1)

� PERFORATED METAL WITH FB1 (AFPM1)

H

W 4 3/4" (121)

9 1/2" (241)

2" (51)

18 1/2" (470)

A

D

OPTIONAL NEMA1

CONTROL

ENCLOSURE

6 3/8" (162)

SIZE 4 & 5 ONLY

MULTI-POINT

SENSOR

OPTIONAL ACCESS

DOOR

EXTERNALLY

WRAPPED

1" (25) FOIL FACED

FIBERGLASS BOARD

L 1&2 ROW = 5" (127)

3&4 ROW = 7 1/4" (184)

INLET SIZES WIDTH HEIGHT

D W H A B L

4 400 (189) 3

/8 (98)

5 500 (236) 4

/8 (124)

6 550 (260) 5

/8 (149)

7 800 (378) 6

/8 (175)

8 1100 (519) 7

/8 (200)

9 1400 (661) 8

/8 (225)

10 1800 (850) 9

/8 (251)

12 2600 (1227) 11

/8 (302) 20 (508) 17 /2 (445)

14 3700 (1746) 13

/8 (352) 24 (610)

16 5000 (2360) 15

/8 (403) 38 (965)

MAX CFM (L/S)

UNIT

SIZE

/8 (162)

LENGTH

10 (254)12 (305)

/8 (111)

/2 (318) 14 (356)

16 (406) 15 (381)

18 (457)

/16 (97)

/16 (135)

/4 (400)

/4 (489)

B

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

C

SDV

273957

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

02/06/2023

OF REVSHEET 1 7© Copyright PRICE INDUSTRIES 2023

S o lid E d g e

SINGLE DUCT TERMINAL

VARIABLE VOLUME

STANDARD CONSTRUCTION:

• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS REQUIREMENTS OF NFPA 90A AND UL181.

• 22GA. ZINC COATED STEEL HOUSING. MECHANICALLY SEALED, LEAK RESISTANT CONSTRUCTION.

• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT DUCT CONNECTION.

• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.

• 1/2" (13mm) ZINC PLATED DAMPER SHAFT WITH POSITION INDICATOR.

• SIZES 4 & 5 USE AN INLET REDUCER.

UNIT OPTIONS:

� NEMA1 CONTROLS ENCLOSURE (PS)

� DISCONNECT SWITCH (DSW)

� 20 GAUGE CASING (20GA)

� HANGER BRACKETS (HB)

� BOTTOM REMOVABLE SENSOR (RS)

� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)

� ACCESS DOOR (AD)

CONTROLS OPTIONS:

� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)

� FIELD MOUNTED, CONTROLS SUPPLIED BY OTHERS (FLD)

� DIGITAL CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP)

LINER OPTIONS:

� FIBERGLASS 1" (25mm) (FG1)

� FIBER FREE FOAM 1/2" (13mm) (FF50)

� FIBER FREE FOAM 3/4" (19mm) (FF)

� FIBER FREE FOAM 1" (25mm) (FF1)

� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)

� SOLID METAL WITH FG1 (SM1)

� CLEANROOM ANGLES WITH FB1 (CRAF1)

WIDTH HEIGHT INLET SIZES

W H D L A B

4 400 189 3 7/8 (98)

5 500 236 4 7/8 (124)

6 550 260 5 7/8 (149)

7 800 378 6 7/8 (175)

8 1100 519 7 7/8 (200)

9 1400 661 8 7/8 (225)

10 1800 850 9 7/8 (251)

12 2600 1227 16 (406) 15 (381) 11 7/8 (302)

14 3700 1746 20 (508) 17 1/2 (445) 13 7/8 (352)

16 5000 2360 24 (610) 15 7/8 (403)

24 x 16 8400 3964 38 (965) 23 7/8 (603) x 15 7/8 (403) 15 1/2 (394) 3 1/2 (89) 2 3/4 (70)

MAX

CFM

UNIT

SIZE

6 3/8 (162)

4 3/8 (111)

LENGTH

MAX L/S

10 (254)

14 (356) 12 1/2 (318)

19 1/4 (489) 5 5/16 (135)

12 (305)

8 (203)

3 13/16 (97)15 3/4 (400)

18 (457)

CONTROLS/PIPING PACKAGE

OPPOSITE SIDE

PIPING PACKAGE

3-WAY DETAIL

D

H 9 229

4 3/4 120 W 6 5/8 169 18 3/8 466 B

1&2 ROW=5 (127)

3&4 ROW=7 1/4 (184)

OPTIONAL NEMA1

CONTROL

ENCLOSURE A L

6 3/4 173

6 5/8 167

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SDV

273957

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

02/06/2023

OF REVSHEET 2 7© Copyright PRICE INDUSTRIES 2023

S o lid E d g e

SINGLE DUCT TERMINAL

VARIABLE VOLUME

STANDARD CONSTRUCTION:

• 1/2" (13mm) THICK INTERNAL FIBERGLASS INSULATION WHICH MEETS REQUIREMENTS OF NFPA 90A AND UL181.

• 22GA. ZINC COATED STEEL HOUSING. MECHANICALLY SEALED, LEAK RESISTANT CONSTRUCTION.

• RECTANGULAR DISCHARGE OPENING WITH SLIP AND DRIVE CLEAT DUCT CONNECTION.

• MULTI-POINT, CENTER AVERAGING AIRFLOW SENSOR.

• 1/2" (13mm) ZINC PLATED DAMPER SHAFT WITH POSITION INDICATOR.

• SIZES 4 & 5 USE AN INLET REDUCER.

• EXTENSION REQUIRED WHEN CONTROLS SAME SIDE AS PIPING PACKAGE

UNIT OPTIONS:

� NEMA1 CONTROLS ENCLOSURE (PS)

� DISCONNECT SWITCH (DSW)

� 20 GAUGE CASING (20GA)

� HANGER BRACKETS (HB)

� BOTTOM REMOVABLE SENSOR (RS)

� BRASS AIRFLOW SENSOR GAUGE TAPS (GT)

� ACCESS DOOR (AD)

� EXTENSION ACCESS DOOR WITH SCREWS (ADD)

� EXTENSION ACCESS DOOR WITH SNAP LATCHES (ADDL)

� EXTENSION ACCESS DOOR QUARTER TURN LATCHES (ADDQ)

CONTROLS OPTIONS:

� FACTORY MOUNTED DIGITAL CONTROLS, SUPPLIED BY OTHERS (FAC)

� FIELD MOUNTED, CONTROLS SUPPLIED BY OTHERS (FLD)

� DIGITAL CONTROLS SUPPLIED AND MOUNTED BY PRICE (EHP)

LINER OPTIONS:

� FIBERGLASS 1" (25mm) (FG1)

� FIBER FREE FOAM 1/2" (13mm) (FF50)

� FIBER FREE FOAM 3/4" (19mm) (FF)

� FIBER FREE FOAM 1" (25mm) (FF1)

� FOIL FACED FIBERGLASS BOARD 1" (25mm) (FB1)

� SOLID METAL WITH FG1 (SM1)

� CLEANROOM ANGLES WITH FB1 (CRAF1)

PIPING PACKAGE

CONTROLS/PIPING PACKAGE

SAME SIDE

3-WAY DETAIL

15 1/2 393

1&2 ROW=5 (127)

3&4 ROW=7 1/4 (184)

L

18 3/8 467

D 4 3/4 120

6 5/8 167 W

H9 229

OPTIONAL NEMA1

CONTROL

ENCLOSURE

B

PIPING PACKAGE

EXTENSION

WIDTH HEIGHT INLET SIZES

W H D L A B

4 400 189 3 7/8 (98)

5 500 236 4 7/8 (124)

6 550 260 5 7/8 (149)

7 800 378 6 7/8 (175)

8 1100 519 7 7/8 (200)

9 1400 661 8 7/8 (225)

10 1800 850 9 7/8 (251)

12 2600 1227 16 (406) 15 (381) 11 7/8 (302)

14 3700 1746 20 (508) 17 1/2 (445) 13 7/8 (352)

16 5000 2360 24 (610) 15 7/8 (403)

24 x 16 8400 3964 38 (965) 23 7/8 (603) x 15 7/8 (403) 15 1/2 (394) 3 1/2 (89) 2 3/4 (70)

MAX

CFM

UNIT

SIZE

6 3/8 (162)

4 3/8 (111)

LENGTH

MAX L/S

10 (254)

14 (356) 12 1/2 (318)

19 1/4 (489) 5 5/16 (135)

12 (305)

8 (203)

3 13/16 (97)15 3/4 (400)

18 (457)

A

6 3/4 173

6 5/8 169

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SDV

273957

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

02/06/2023

OF REVSHEET 3 7© Copyright PRICE INDUSTRIES 2023

S o lid E d g e

SINGLE DUCT TERMINAL

VARIABLE VOLUME

NOTES:

1. VALVES TO BE ASSEMBLED, TESTED AND SHIPPED

AS DEPICTED

2. REFER TO SUBMITTED TERMINAL UNIT SCHEDULE

FOR UNIT AND COIL HANDING

3. EXTENSION PROVIDED WHEN CONTROLS AND COIL

HANDING ARE ON THE SAME SIDE

4. EXTENSION INSULATED TO MATCH TERMINAL UNIT LINER

5. PRESS CONNECTION BETWEEN VALVES AND COIL

RIGHT HAND CONTROL & RIGHT HAND

PIPING PACKAGE

LEFT HAND CONTROL & LEFT HAND

PIPING PACKAGE

LEFT HAND CONTROL & RIGHT HAND

PIPING PACKAGE

RIGHT HAND CONTROL & LEFT HAND

PIPING PACKAGE

PIPING PACKAGE

ORIENTATION

PIPING PACKAGE

EXTENSION

OPTIONAL NEMA1

CONTROLS ENCLOSURE

OPTIONAL NEMA1

CONTROLS ENCLOSURE

OPTIONAL NEMA1

CONTROLS ENCLOSURE

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SDV

273957

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

02/06/2023

OF REVSHEET 4 7© Copyright PRICE INDUSTRIES 2023

S o lid E d g e

SINGLE DUCT TERMINAL

VARIABLE VOLUME

NOTES:

1. VALVES TO BE ASSEMBLED, TESTED AND SHIPPED

AS DEPICTED

2. REFER TO SUBMITTED TERMINAL UNIT SCHEDULE

FOR UNIT AND COIL HANDING

3. EXTENSION PROVIDED WHEN CONTROLS AND COIL

HANDING ARE ON THE SAME SIDE

4. EXTENSION INSULATED TO MATCH TERMINAL UNIT LINER

5. 'E' DIMENSION IS TAKEN FROM TOP OF UNIT TO RETURN PIPE

E (RH COIL) E (LH COIL) F E F E F E F

4-6 3/8 (11) 1 (25) 6 1/4 (159) 1/2 (13) 6 7/8 (175) 5/8 (17) 5 3/4 (147) 5/8 (17) 6 3/8 (163)

7-8 3/8 (11) 1 (25) 8 3/4 (222) 5/8 (17) 8 7/8 (227) 5/8 (17) 8 1/4 (211) 5/8 (17) 8 7/8 (227)

9-10 5/8 (17) 1 1/4 (33) 10 3/4 (274) 5/8 (17) 11 3/8 (290) 5/8 (17) 10 3/4 (274) 5/8 (17) 11 3/8 (290)

12 5/8 (17) 1 1/4 (33) 13 1/4 (338) 5/8 (17) 13 7/8 (354) 5/8 (17) 13 1/4 (338) 5/8 (17) 13 7/8 (354)

14 5/8 (17) 1 1/4 (33) 15 3/4 (401) 5/8 (17) 16 3/8 (417) 5/8 (17) 15 3/4 (401) 5/8 (17) 16 3/8 (417)

16 5/8 (17) 1 1/4 (33) 15 3/4 (401) 5/8 (17) 16 3/8 (417) 5/8 (17) 15 3/4 (401) 5/8 (17) 16 3/8 (417)

24X16 5/8 (17) 1 1/4 (33) 15 3/4 (401) 5/8 (17) 16 3/8 (417) 5/8 (17) 15 3/4 (401) 5/8 (17) 16 3/8 (417)

UNIT SIZE

2 ROW 3 ROW 4 ROW1 ROW

PIPING PACKAGE COILS

CENTER DIMENSIONS

CONTROLS/PIPING PACKAGE SAME SIDE

CONTROLS/PIPING PACKAGE OPPOSITE SIDE

E

F

F

E

PRICE PROVIDED TCV, 3 1/2" MAX

TCV BY OTHERS, HEIGHT VARIABLE

DEPENDENT ON MODEL

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SDV

273957

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

02/06/2023

OF REVSHEET 5 7© Copyright PRICE INDUSTRIES 2023

S o lid E d g e

SINGLE DUCT TERMINAL

VARIABLE VOLUME

WATER COIL NOTES

B

AIRFLOW

L

SLIP & DRIVE

CONNECTIONSUPPLY

RETURN

COIL CONNECTIONS COIL CONNECTIONS

1,2,3,4 ROWS 1,2 ROW 3,4 ROWS 1,2,3,4 ROWS 1,2 ROW 3,4 ROWS

4,5,6 305 203 22 127 184 4,5,6 12 8 7/8 5 7 1/4

7,8 305 254 22 127 184 7,8 12 10 7/8 5 7 1/4

9,10 356 318 22 127 184 9,10 14 12 1/2 7/8 5 7 1/4

12 406 381 22 127 184 12 16 15 7/8 5 7 1/4

14 508 445 22 127 184 14 20 17 1/2 7/8 5 7 1/4

16 610 457 22 127 184 16 24 18 7/8 5 7 1/4

24 X 16 965 457 22 127 184 24 X 16 38 18 7/8 5 7 1/4

NOMINAL

SIZE

B

(WIDTH)

C

(HEIGHT)

L

SI UNITS (mm)

NOMINAL

SIZE

IMPERIAL UNITS (in)

B

(WIDTH)

C

(HEIGHT)

L

C

SEE NOTE #6

NOTE:

1. FABRICATED FROM 22 GA. GALVANIZED STEEL 7. CONFIGURATION OF COIL CONNECTION VARIES

MECHANICALLY SEALED, LEAK RESISTANT WITH GPM RANGE SELECTIONS.

CONSTRUCTION. 8. PERFORMANCE RATED AND CERTIFIED IN ACCORDANCE

2. HOT WATER COILS HAVE COPPER TUBES AND WITH THE CURRENT EDITION OF AHRI STANDARD 410.

ALUMINUM FINS WITH O.D. SWEAT CONNECTIONS. 9. STANDARD COILS SUPPLIED WITH 10 FINS PER INCH.

3. REFER TO SUBMITTED TERMINAL UNIT SCHEDULE FOR 10. WATER CONNECTIONS ORIENTED TOWARDS DISCHARGE

AIR VOLUMES AND REHEAT COIL CAPACITIES. OR INLET, DEPENDING ON CONFIGURATION SELECTED.

4. METHOD OF VENTING PROVIDED ON PIPING PACKAGE. 11. IT IS NOT RECOMMENDED TO REVERSE 3 & 4 ROW COILS.

5. HANDING OF WATER COIL CONNECTIONS IS DETERMINED INDICATE HANDING WHILE ORDERING

WHEN VIEWED FROM AIR INLET SIDE WITH ACCESS 12. IMAGES NOT REPRESENTATIVE OF SUPPLY AND RETURN

DOOR ON BOTTOM. RIGHT HAND COIL CONNECTION LOCATIONS

ILLUSTRATED ABOVE.

6. ALLOW 1 1/2" [38] MINIMUM CLEARANCE FOR

INSTALLATION AT THIS END.

OPTIONS:

HC (HIGH CAPACITY) WATER COIL

HIGH CAPACITY COIL SUPPLIED WITH 12 FINS PER INCH.

1 AND 2 ROW COILS AVAILABLE.

7/8 ( 22 ) DIA @ 4 1/4 ( 108 )

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SDV

273957

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

02/06/2023

OF REVSHEET 6 7© Copyright PRICE INDUSTRIES 2023

S o lid E d g e

SINGLE DUCT TERMINAL

VARIABLE VOLUME

� ADD - DUAL ACCESS DOOR WITH SCREWS � ADDL - DUAL ACCESS DOOR WITH SNAP LATCHES

� ADDQ - DUAL ACCESS DOOR WITH QUARTER TURN LATCHES

CONSTRUCTION NOTES:

• EXTENSION INSULATED TO MATCH TERMINAL UNIT LINER.

• STANDARD DOOR SIZES PROVIDED AT 4" (102) X 6 3/4" (171).

• BOTTOM ACCESS DOORS FOR INSPECTION AND MAINTENANCE OF COIL.

• GASKETED PERIMETER INCLUDED WITH ALL FASTENER STYLES.

• INSULATED, 22 GAUGE GALVANIZED DUAL WALL ACCESS DOOR.

(NON-DUAL WALL WITH FIBER FREE)

DUAL COIL

ACCESS DOORS

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

SDV

273957

PROJECT:

ENGINEER:

CUSTOMER:

SUBMITTAL DATE: SPEC. SYMBOL:

Submittal Sheet

02/06/2023

OF REVSHEET 7 7© Copyright PRICE INDUSTRIES 2023

S o lid E d g e

SINGLE DUCT TERMINAL

VARIABLE VOLUME

3 3/16 (81)

2 (51)1 (25)

1 1/2 (38)

3/4 (19)

O1/2 (13)

NOTES:

• HANGER BRACKET ARE 12 GAUGE GALVANIZED STEEL.

• 4 BRACKETS PER UNIT. 2 BRACKETS PER EXTENSION

• LAYOUT INDICATES SUGGESTED HANGER BRACKET LOCATIONS.

• BRACKETS ARE SHIPPED LOOSE FOR FIELD INSTALLATION FOR USE WITH FASTENERS AND THREADED HANGER RODS

(BY OTHERS).

HANGER BRACKETS

2 ( 51 ) TYP

2 52 TYP

2 49 TYP

2 51 TYP

2 51 TYP

2 ( 51 ) TYP

2 ( 51 ) TYP

Ductless Mini-Split Air Conditioning Units

Job Name/Location

Date:

PO No.:

Architect: GC:

Engr: Mech:

Rep:

(Company) (Project Manager)

Tag #:

• Night Quiet Operation

• Fault Detection and Diagnosis

Standard Features:

For continual product development, LG reserves the right to change specifications without notice.

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

1. For AHRI rating, refer to the AHRI website http://www.ahridirectory.org.

2. The combination ratio must be between 50 – 130%.

3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard

3745.

4. Communication cable between ODU, IDU(s), and Central Controller must be a minimum of 2‐conductor, 18 AWG, twisted, stranded, and shielded. Ensure the communication cable shield is properly grounded to the ODU chassis only. Do not ground the communication cable at any other point. Wiring must comply with all applicable local and national codes.

5. Nominal data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95‐105%.

6. Power wiring cable size must comply with the applicable local and national codes.

7. The voltage tolerance is ± 10%.

Notes:

Optional Accessories:

For: File Resubmit Approval Other

Performance:

Cooling Mode:

Rated Capacity (Btu/h) Power Input1 (kW)

Heating Mode:

Rated Capacity (Btu/h) Power Input1 (kW)

Rated Capacity is based on the following conditions:

Cooling Indoor: 80°F DB / 67°F WB Outdoor: 95°F DB

Heating:

Indoor: 70°F DB Outdoor: 47°F DB / 43°F WB

Electrical:

Power Supply (V/Hz/Ø)

MOP (A)

MCA (A)

Rated Amps (A)

Compressor (A) Fan (A) x Qty.

208‐230V / 60 / 1

Refrigerant Charge (lbs) Liquid Line (in, OD) Vapor Line (in, OD)

Piping:

*Installation of an optional Low Ambient Wind Baffle Kit will allow operation down to ‐9.9°F in cooling mode.

Cooling (°F DB)* Heating (°F WB)

23 ‐ 122

Operating Range:

Refrigerant Type Refrigerant Control Max Number of Indoor Units2

Sound Pressure3 dB(A) Net Unit Weight (lbs) Shipping Weight (lbs) Communication Cable4 (No x AWG) Heat Exchanger Coating

R410A

EEV

2 x 18 GoldFin™

Unit Data:

Type Quantity Oil / Type

PVE/FVC68D

Compressor:

Type Quantity Motor / Drive Air Flow Rate (CFM)

Brushless Digitally Controlled/Direct

Fan:

Multi V™ S Heat Pump

Ø5/8 Braze

-4 to +61

2.77

6.6

43,000

0.5 x 2

Low Ambient Baffle Kit ZLABGP04A (2 required)

38,000

3,885

SB_MultiV_S_HP_ARUN038GSS4_2022_12_02_071548

DC Inverter Starting

Axial Flow Fan

3.22

3.0 Ton Outdoor Unit

19.5

ARUN038GSS4

Ø3/8 Braze

For continual product development, LG reserves the right to change specifications without notice.

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 2 of 3

Job Name/Location:

Tag No.:

Date:

PO No.:Multi V™ S Heat Pump

SB_MultiV_S_HP_ARUN038GSS4_2022_12_02_071548

3.0 Ton Outdoor Unit

ARUN038GSS4

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 3 of 3

Job Name/Location:

Tag No.:

Date:

PO No.:

AHRI Data:

Indoor Unit Type Cooling Capacity (95°F) EER2 (95°F) SEER2 High Heating

Capacity (47°F) Low Heating

Capacity (17°F) HSPF2 Low Heating Capacity (5°F)

Heating COP at 5°F

Non‐Ducted Indoor Units

Ducted Indoor Units

51,000

Multi V™ S Heat Pump

2.1633,000

10.60

10.6051,00020.10

20.10

38,000

2.1638,000

SB_MultiV_S_HP_ARUN038GSS4_2022_12_02_071548

39,000

39,00033,000

3.0 Ton Outdoor Unit

ARUN038GSS4

14.00

14.00

Job Name/Location

PO No.:

Architect: GC:

Engr: Mech:

Rep:

(Company) (Project Manager)

Tag #:

• Night Quiet Operation

• Fault Detection and Diagnosis

Standard Features:

For continual product development, LG reserves the right to change specifications without notice.

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

1. For AHRI rating, refer to the AHRI website http://www.ahridirectory.org.

2. The combination ratio must be between 50 – 130%.

3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard

3745.

4. Communication cable between ODU, IDU(s), and Central Controller must be a minimum of 2‐conductor, 18 AWG, twisted, stranded, and shielded. Ensure the communication cable shield is properly grounded to the ODU chassis only. Do not ground the communication cable at any other point. Wiring must comply with all applicable local and national codes.

5. Nominal data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95‐105%.

6. Power wiring cable size must comply with the applicable local and national codes.

7. The voltage tolerance is ± 10%.

Notes:

Optional Accessories:

For: File Resubmit Approval Other

Performance:

Cooling Mode:

Rated Capacity (Btu/h) Power Input1 (kW)

Heating Mode:

Rated Capacity (Btu/h) Power Input1 (kW)

Rated Capacity is based on the following conditions:

Cooling Indoor: 80°F DB / 67°F WB Outdoor: 95°F DB

Heating:

Indoor: 70°F DB Outdoor: 47°F DB / 43°F WB

Electrical:

Power Supply (V/Hz/Ø)

MOP (A)

MCA (A)

Rated Amps (A)

Compressor (A) Fan (A) x Qty.

208‐230V / 60 / 1

Refrigerant Charge (lbs) Liquid Line (in, OD) Vapor Line (in, OD)

Piping:

*Installation of an optional Low Ambient Wind Baffle Kit will allow operation down to ‐9.9°F in cooling mode.

Cooling (°F DB)* Heating (°F WB)

23 ‐ 122

Operating Range:

Refrigerant Type Refrigerant Control Max Number of Indoor Units2

Sound Pressure3 dB(A) Net Unit Weight (lbs) Shipping Weight (lbs) Communication Cable4 (No x AWG) Heat Exchanger Coating

R410A

EEV

2 x 18 GoldFin™

Unit Data:

Type Quantity Oil / Type

PVE/FVC68D

Compressor:

Type Quantity Motor / Drive Air Flow Rate (CFM)

Brushless Digitally Controlled/Direct

Fan:

Multi V™ S Heat Pump

Ø5/8 Braze

-4 to +61

4.3

6.6

54,000

0.5 x 2

Low Ambient Baffle Kit ZLABGP04A (2 required)

48,000

3,885

SB_MultiV_S_HP_ARUN048GSS4_2022_12_02_071549

DC Inverter Starting

Axial Flow Fan

4.2

4.0 Ton Outdoor Unit

23.1

ARUN048GSS4

Ø3/8 Braze

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 2 of 3

Job Name/Location:

Tag No.:

Date:

PO No.:Multi V™ S Heat Pump

SB_MultiV_S_HP_ARUN048GSS4_2022_12_02_071549

4.0 Ton Outdoor Unit

ARUN048GSS4

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 3 of 3

Job Name/Location:

Tag No.:

Date:

PO No.:

AHRI Data:

Indoor Unit Type Cooling Capacity (95°F) EER2 (95°F) SEER2 High Heating

Capacity (47°F) Low Heating

Capacity (17°F) HSPF2 Low Heating Capacity (5°F)

Heating COP at 5°F

Non‐Ducted Indoor Units

Ducted Indoor Units

54,500

Multi V™ S Heat Pump

2.1636,000

10.20

10.2054,50020.00

20.00

48,000

2.1648,000

SB_MultiV_S_HP_ARUN048GSS4_2022_12_02_071549

39,000

39,00036,000

4.0 Ton Outdoor Unit

ARUN048GSS4

13.20

13.20

Job Name/Location:

PO No.:

Architect: GC:

Engr: Mech:

Rep:

(Company) (Project Manager)

For: File Resubmit Approval Other

Tag #:

For a complete list of available accessories, contact your LG representative.

For continual product development, LG reserves the right to change specifications without notice.

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

Notes:

1. See Engineering Manual for sensible and latent capacities.

2. Max. power input is rated at maximum setting value.

3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.

4. If a Third-Party Dry Contact and an LG internal heater or an LG Auxiliary Heater Kit is installed, supplemental heat capability cannot be controlled by the Third-Party Thermostat.

5. All communication cable between Main outdoor units to indoor units / heat recovery units to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the Main outdoor unit chassis only. Do not ground the outdoor unit to indoor units / heat recovery units communication cable at any other point. Wiring must comply with all applicable local and national codes.

6. Power wiring is field provided and must comply with the applicable local and national codes.

7. This unit comes with a dry nitrogen charge.

8. All capacities are net with a combination ratio between 95 – 105%.

9. Must follow installation instructions in the applicable LG installation manual.

Performance:

Total Cooling Capacity (Btu/h)1

Heating Capacity (Btu/h)1

Max Power Input (W)2

H / M / L Power Input at Factory Default (W)

Electrical:

Power Supply (V/Hz/Ø) Rated Amps

208-230 / 60 / 1

Piping:

Refrigerant Liquid Line (in., O.D.)

Vapor Line (in., O.D.)

Condensate Condensate Line (in., I.D.)

Factory Installed Pump

No

Controls Features:

Optional Accessories:

Unit Data:

Refrigerant Type Refrigerant Control Sound Pressure dB(A) (H / M / L)3

Standard Filter Type Unit Net Weight (lbs.)

Unit Shipping Weight (lbs.)

R410A

EEV

Washable

Fan:

Type Quantity Motor/Drive Motor Quantity Air Flow Rate H / M / L (CFM)

Cross Flow

Brushless Digitally Controlled/Direct

• Auto changeover (Heat Recovery only)

• Auto operation

• Auto restart

• Dual thermistor control

• Dual setpoint control

• Multiple auxillary heater applications

• Timer (on/off)

• Weekly schedule

• Auto direction/ swing (up/down)

• Fan speed control

• Jet cool (fast cooling)

• Filter life display

• Child lock

• Group control

• Hot start

• Self diagnostics

• External on/off control

• Wi-Fi compatible

• Auto Fan

• Leak Detection

Wireless Remote Controller - PWLSSB21H MultiSITE™ CRC2 Controller - PREMTBVC2 MultiSITE™ CRC2+ Controller - PREMTBVC3 MultiSITE™ CRC2+Z Controller - PREMTBVC4 Simple Remote Controller - PREMTC00U Standard III Remote Controller – PREMTB100 Standard III Remote Controller – PREMTBB10 Remote Temperature Button Sensor - ZRTBS01 Simple Dry Contact (1 contact, 24 VAC external power) - PDRYCB100 Dry Contact for Third Party Thermostat - PDRYCB3204

Dry Contact for Economizer - PDRYCB400 Auxillary Heater Kit - PRARS14

Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

Multi V™ Standard Wall Mounted Unit

5/8 Flare

32,000 30,000

49 / 44 / 42

3/8 Flare

SB_MultiV_Wall_Mounted_ARNU303SVA4_2023_09_20_113552

812 / 706 / 600

54 / 43 / 31

ARNU303SVA4

30,000 Btu/h Indoor Unit

0.51 http://www.ahridirectory.org

Tag No.:

Date:

PO No.:

For continual product development, LG reserves the right to change specifications without notice.

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

Multi V™ Standard Wall Mounted Unit

SB_MultiV_Wall_Mounted_ARNU303SVA4_2023_09_20_113552

ARNU303SVA4

30,000 Btu/h Indoor Unit

PO No.:

Architect: GC:

Engr: Mech:

Rep:

(Company) (Project Manager)

For: File Resubmit Approval Other

Tag No.:

For a complete list of available accessories, contact your LG representative.

For continual product development, LG reserves the right to change specifications without notice.

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com

Notes:

1. See Engineering Manual for sensible and latent capacities.

2. Maximum power input is rated at maximum setting value.

3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.

4. Communication cable between (main) outdoor unit to indoor units / heat recovery units to be 18 AWG, 2-conductor, twisted, stranded, shielded. Ensure the communication cable shield is properly grounded to the (main) outdoor unit chassis only. DO NOT ground the outdoor unit to indoor units / heat recovery units communication cable at any other point. Wiring must comply with all applicable local and national codes.

5. Power wiring is field provided, and must comply with the applicable local and national codes.

6. This unit comes with a dry nitrogen charge.

7. All capacities are net with a combination ratio between 95 – 105%.

8. Must follow installation instructions in the applicable LG installation manual.

Performance:

Total Cooling Capacity (Btu/h)1

Heating Capacity (Btu/h)1

Maximum Power Input2

L/M/H Power Input at Factory Default (W)

Rated capacity is certified under AHRI Standard 1230. Ratings are subject to change without notice. Current certified ratings are available at www.ahridirectory.org.

Electrical:

Power Supply (V/Hz/Ø) Rated Amps

208-230/60/1

Piping:

Refrigerant Liquid Line (in., O.D.)

Vapor Line (in., O.D.)

Condensate Condensate Line (in., I.D.)

Factory Installed Pump

5/8 No

Controls Features:

Unit Data:

Refrigerant Type Refrigerant Control Sound Pressure dB(A) (H/M/L)3

Filter Type Unit Net Weight (lbs.)

Unit Shipping Weight (lbs.)

R410A

EEV

Washable

Fan:

Fan Type Fan Quantity Motor/Drive Motor Quantity Air Flow Rate H/M/L (CFM)

Cross Flow

Brushless Digitally Controlled/Direct

• Auto changeover

• Auto operation

• Auto restart

• Child lock

• Dual thermistor control

• Forced operation

• Group control

• High ceiling

• Hot start

• Self diagnostics

• Timer (on/off)

• Weekly schedule

• Auto direction / swing (up / down)

• Fan speed control

• Jet cool (fast cooling)

• Dual setpoint control

• Filter life display

• Wi-Fi compatible

• Leak detection

• Auto fan

• External on/off control

Optional Accessories:

Wireless Remote Controller - PQWRHQ0FDB MultiSITE™ CRC1 Controller - PREMTBVC0 MultiSITE™ CRC1+ Controller - PREMTBVC1 Simple Remote Controller - PREMTC00U Premium Remote Controller - PREMTA000 Remote Temperature Button Sensor - ZRTBS01 Simple Dry Contact (1 contact, 24 VAC external power) - PDRYCB100 Dry Contact for Third-Party Thermostat - PDRYCB320 Dry Contact for Economizer - PDRYCB400 Auxiliary Heater Kit - PRARH1 Wi-Fi Module - PWFMDD200

48,100

Multi V™ Ceiling Suspended

5/8 Flare

51,200

3/8 Flare

SB_MV_CeilingSuspended_ARNU483V2A4_2021_01_22_110547

1,024 / 848 / 706

91 / 79 / 66

ARNU483V2A4

48,100 Btu/h Indoor Unit

184 47 / 44 / 41

0.97

Tag No.:

Date:

PO No.:

For continual product development, LG reserves the right to change specifications without notice.

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com Page 2 of 2

Multi V™ Ceiling Suspended

SB_MV_CeilingSuspended_ARNU483V2A4_2021_01_22_110547

ARNU483V2A4

48,100 Btu/h Indoor Unit

Unit Heaters

Electric Heater Catalog . Page 6

EGHB INDUSTRIAL SUSPENDED UNIT HEATER

FEATURES

COLOR

• Standard: almond

FINISH

• Standard: epoxy/polyester powder paint

VOLTAGE

• 208V, 240V, 277V, 347V, 480V, 600V, 1 or 3-phase

CONSTRUCTION

• 18 and 20-gauge steel

• High-limit temperature control with automatic reset

FAN

• Motor mounted in cold compartment

• Thermally-protected motor

• Totally enclosed and factory-lubricated ball bearing motor

(except for 15 to 25kW at 208/240V)

• 58 dBA fan (2 to 10kW), 67 dBA fan (15 to 30kW) and 77 dBA fan (40 to 60kW)

• Fan delay purges heater of residual heat

HEATING ELEMENT

• Durable tubular heating elements; stainless steel (2 to 10kW);

• Concentric disposition of heating elements

• Factory sealed element upon request

CONTROL

• All models have a factory-installed contactor

• 240/208V control circuit standard (with transformer if necessary)

• 24V relay, with or without transformer available

• Built-in thermostat available

• 120V control circuit available

Manufacturer highly recommends to use a wall thermostat for greater comfort.

Any remote thermostat or relay must be connected to the heater control terminal block.

INSTALLATION

• Horizontal wall or ceiling mounting using one of two supplied brackets which allow 360° rotation (Horizontal mounting only for 40kW, 50kW and 60kW secured by 4 hooks [ceiling only])

• Vertical mounting using 4 threaded rods 1/2 inch X 13 UNC (not included) (except option -MD)

• Large and easily accessible control compartment

• Maximum recommended height (horizontal): 2 to 10kW: 8 ft. (2.4 m); 15 to 30kW: 10 ft. (3 m); 40 to 60kW: 15 ft. (4.5 m)

• Protective screen allows lower mounting height (except 40 to 60kW)

• Minimum height of 8 ft. (2.4 m) for 40 to 60kW heaters

• 30 °C (85 °F) maximum operating ambient temperature

WARRANTY

• 1-year warranty against defects

APPLICATION

• Commercial hall, warehouse, stairwell, factory

Electric Heater Catalog. Page 7

EGHB INDUSTRIAL SUSPENDED UNIT HEATER continued

MODELS

1 Models with the indications "3/1" can be field converted from 3 to 1-phase.

2 2-pole contactor is standard with single and 3-phase units. 3-pole contactor may be required by some codes for 3-phase.

3 For the U.S. only: The nominal current of the unit must not exceed 80% of the capacity of the disconnect.

4 For single or multiple unit control.

5 IR24: 24V signal by others (multiple units per thermostat). IR2B: for 24V thermostat on each unit.

6 All heaters have a 240V control circuit unless otherwise specified.

7 Field installed. Same thermostat as Option IC11.

8 CL1A thermostat requires option BT1.

Standard color is almond.

Size 2 3 4 5 7 10 15 20 25 30 40 50 60

Heating Capacity kW 2 3 4 5 7.5 10 15 15 20 20 25 25 30 40 50 60

MBH 7 10 14 17 26 34 51 51 68 68 85 85 102 136 171 205

Airflow cfm 510 510 510 700 700 700 1300 1400 1300 1400 1300 1400 1400 2000 2000 2000

Temperature Rise °F 13 18 25 23 34 45 36 34 49 45 61 56 68 63 79 95

°C 7 10 14 13 19 25 20 19 27 25 34 31 38 35 44 53

Motor

HP 1/30 1/30 1/30 1/30 1/30 1/30 1/8 1/3 1/8 1/3 1/8 1/3 1/3 3/4 3/4 3/4

@ 277V and lower RPM 1550 1550 1550 1550 1550 1550 1550 1550 1550

@ 480V and Higher RPM 1550 1550 1550 1550 1550 1550 1725 1725 1725 1725 1140 1140 1140

Ship Weight Lbs 45 45 45 45 45 45 85 85 85 85 85 85 85 150 150 150

Kg 20 20 20 20 20 20 39 39 39 39 39 39 39 68 68 68

Factory Installed Options

Supply Voltage/ Phase

208/1 AK2

208/3 AK5

208/3-1 1 AK15

240/1 AK3E

240/3 AK6E

240/3-1 1 AK16

277/1 AK4

347/1 AK34

480/1 AK9E

480/3 AK7E

600/3 AK8E

Triple Pole Contactor (3ph) 2 AN6

Disconnect Switch 3

40A BA14

80A BA15

100A BA16

Branch Circuit Fusing BA12

Unit Mounted Summer Fan Switch BF4A

Control Voltage

208V, 240V, 277V STD

24V relay with transformer 4 BT1

120V contactor with transformer BT2

Manual High Limit BD6 Summer Fan Relay

24V, remote control (Fan Switch must be ordered separately)

CV24

Internal Thermostat IC11

Field Installed Options (shipped separately)

Size 2 3 4 5 7 10 15 20 25 30 40 50 60

24V Relay Kit 5 Without transformer IR24

240V transformer 6 IR2B

Unit Mounted Thermostat Kit 7 IT13

Wall Mounted Thermostats

Single-pole, low-voltage thermostat 8 CL1A

Single-pole, single stage thermostat CL5

Vertical Cone Diffuser CD70

Electric Heater Catalog . Page 8

I

B

H

D

A

C

E

F

G (min.)

4 Threaded Rods

(1/2" - 13 UNC)

(Not Included)

Standard Installation

Side View Motor in Cold Section

Small Area Large Area

Motor

Fan

Heating Elements

Louvres

EGHB INDUSTRIAL SUSPENDED UNIT HEATER continued

2 - 10kW 15 - 30kW 40 - 60kW mm inch mm inch mm inch

A 305 12 444 17 1/2 585 23 B 419 16 1/2 556 21 7/8 641 25 1/4 C 432 17 572 22 1/2 870 34 1/4 D 357 14 1/16 470 18 1/2 - - E 290 11 7/16 407 16 - - F 490 19 5/16 630 24 13/16 924 36 3/8 G 305 12 305 12 305 12 H 123 4 7/8 148 5 13/16 305 12 I 428 16 7/8 592 23 5/16 890 35

Weight kg lb kg lb kg lb 20 45 39 85 68 150

DIMENSIONS

Electric Heater Catalog . Page 20

FEATURES

COLOR

• White or almond options

FINISH

• Standard: epoxy/polyester powder paint

• Optional: anodized aluminum

VOLTAGE

• 120V, 208V, 240/208V, 277V, 347V, 480V, 600V, 1-phase

CONSTRUCTION

• Extruded aluminum front grille, 1/8 in. (3.2 mm) thick

• Bottom air outlet

• High-limit temperature control with automatic reset

FAN

• Closed, factory-lubricated motor

• 160 cfm fan (single unit: 55 dBA); 2 X 160 cfm fan (double unit:

58 dBA), 3 X 160 cfm fan (triple unit: 61 dBA)

• Fan delay purges heater of residual heat

HEATING ELEMENT

CONTROL

• Built-in tamper proof thermostat included

• 24V relay, with or without transformer available

Note: Thermostat is not included in heater with factory installed relay. Any remote thermostat or relay must be connected to the heater control terminal block.

INSTALLATION

10 in. (25.4 cm).

• Adaptor for surface mounting available.

• Up to 3 units can be mounted side-by-side

WARRANTY

• 3-year warranty against defects

APPLICATION

• Apartment building, commercial building, entrance way, stairwell, garage

EHA FORCED-AIR ARCHITECTURAL WALL HEATER

KOE Ø22 mm

KOE Ø7/8"

KOE Ø22 mm

KOE Ø7/8"

408 mm 16 1/16"

810 mm 31 7/8"

767 mm 30 3/16"

1227 mm 48 5/16"

1185 mm 46 5/8"

578 mm 22 3/4"

40 mm 1 9/16"

368 mm 14 7/16"

51 mm 2"

212 mm 8 5/16"

74 mm 2 7/8" 55 mm

2 3/16"

34 mm 1 5/16"

506 mm 19 7/8"

34 mm 1 5/16"

51 mm 2"

51 mm 2"

Installation (All Models)Side View (All Models)

Surface

Recessed

Front ViewFront View Front ViewSide View

Top View Top ViewTop View

Required Wall Depth Opening

Single Unit Double Unit Triple Unit

109 mm 4 5/16"

107 mm 4 3/16"

584 mm 23"

Electric Heater Catalog. Page 21

EHA FORCED-AIR ARCHITECTURAL WALL HEATER continued

MODELS

Size 1 2 3 4 5

Heating Capacity W 1500 2000 3000 4000 4800

BTUH 5125 6825 10250 13660 16400

Ship Weight Lbs 24 24 24 24 24

Kg 10.9 10.9 10.9 10.9 10.9

Factory Installed Options

Supply Voltage/Phase

120/1 AK1E

208/1 AK2

240/1 1 AK3E

277/1 AK4

480/1 AK9E

Cabinet Color (Lead times may be increased for color other than white)

White HK1

Almond HK2

Thermostat Hidden, tamper-proof, built-in thermostat STD

Control Voltage

120V, 208V, 240V, 277V & 480V STD

24V Relay with transformer 2 BT1

Disconnect Switch 3 Up to 277V, 2-pole, 20A BA21

600V max., 3-pole, 40A BA14

Field Installed Options (shipped separately)

Size 1 2 3 4 5

Color Matched Trim Packages Surface mounting box required for non-recessed units HY6

1 Units with Option AK3E (240V supply voltage) can be connected to 208V power supply, but heating output will be reduced by 25%.

2 Built-in transformer is not included with 24V control voltage (Option BT1).

3 For the U.S. only: The nominal current of the unit must not exceed 80% of the capacity of the disconnect.

Electric Heater Catalog . Page 22

EHC COMMERCIAL WALL HEATER

FEATURES

COLOR

• White or almond options

FINISH

• Standard: epoxy/polyester powder paint

VOLTAGE

• 120V, 208V, 240/208V, 277V, 347V, 480V, 600V, 1 or 3-phase

CONSTRUCTION

• 18-gauge steel front cover

• Bottom air outlet

• High-limit temperature control with automatic reset

FAN

• Closed, factory-lubricated motor

• 160 cfm fan (single unit: 55 dBA); 2 X 160 cfm fan (double unit:

58 dBA); 3 X 160 cfm fan (triple unit: 61 dBA)

• Fan delay purges heater of residual heat

HEATING ELEMENT

CONTROL

• Built-in thermostat included with control knob or tamper proof

• 24V relay, with or without transformer available

Note: Thermostat is not included in heater with factory installed relay. Any remote thermostat or relay must be connected to the heater control terminal block.

INSTALLATION

10 in. (25.4 cm).

• Adaptor for surface mounting available.

• Up to 3 units can be mounted side-by-side

WARRANTY

• 1-year warranty against defects

APPLICATION

• Apartment building, commercial building, entrance way, stairwell, garage

KOE Ø22 mm

KOE Ø7/8"

KOE Ø22 mm

KOE Ø7/8"

368 mm 14 7/16" 51 mm

2" 212 mm 8 5/16"

74 mm 2 7/8" 55 mm

2 3/16"

34 mm 1 5/16"

506 mm 19 7/8"

34 mm 1 5/16"

51 mm 2"

51 mm 2"

Installation (All Models)Side View (All Models)

Surface

Recessed

Front View Front View Front ViewSide View

Top View Top ViewTop View

Required Wall Depth Opening

Single Unit

104 mm 4 1/8"

410 mm 16 1/8"

810 mm 31 7/8"

767 mm 30 3/16"

1227 mm 48 5/16"

1185 mm 46 5/8"

561 mm 22 1/16"

33 mm 1 5/16"

104 mm 4 1/8"

561 mm 22 1/16"

Double Unit Triple Unit

Electric Heater Catalog. Page 23

EHC COMMERCIAL WALL HEATER continued

MODELS

Size 1 2 3 4 5 6 8 12

Heating Capacity W 1500 2000 3000 4000 4800 6000 8000 12000

BTUH 5125 6825 10250 13660 16400 20500 27620 40975

Ship Weight Lbs 24 24 24 24 24 90.0 50 90.0

Kg 10.9 10.9 10.9 10.9 10.9 40.9 22.7 40.9

Factory Installed Options

Supply Voltage/ Phase

120/1 AK1E

208/1 AK2

208/3 AK5

240/1 1 AK3E

240/3 AK6E

347/1 AK34

480/1 AK9E

480/3 AK7E

600/1 AK10

600/3 AK8E

Cabinet Color White HK1

Almond HK2

Control Voltage 208V, 240V 2 STD

Unit Mounted Fan Switch BF23

Disconnect Switch 3

Up to 277V, 2-pole, 20A BA21

600V, 3-pole, 40A BA14

600V, 3-pole, 80A BA15

Field Installed Options (shipped separately)

Size 1 2 3 4 5 6 8 12

Color Matched Trim Packages

Surface mounting box required for non-recessed units HY6

1" recessed trim kit HY4A

2" recessed trim kit HY4B

1 Units with Option AK3E (240V supply voltage) can be connected to 208V power supply, but heating output will be reduced by 25%.

2 208V/240V control (& fan motor) is standard on all units.

3 For the U.S. only: The nominal current of the unit must not exceed 80% of the capacity of the disconnect.

Electric Heater Catalog . Page 28

MECHANICAL THERMOSTATS

MODELS

CL5

Mechanical, wall mounted, line voltage thermostat, single-pole, single-throw.

Not for use with model EXB.

CL1A

Wall mounted, single-pole, low-voltage thermostat. Not for use with model

EXB.

CX1

Explosion resistant, wall mounted thermostat, 40°80°F.

ELECTRICAL FUNDAMENTALS

The relationship between Wattage (heat) output and the applied Voltage of electric resistance heating elements is determined by a precise physical rule defined as Ohm’s Law which states that the current in a resistance heating element is directly proportional to the applied Voltage.

Ohm’s Law is traditionally expressed as:

The same equation using the conventional abbreviation for voltage is:

An unknown electrical value can be derived by using any two known values in one of the variations of Ohm’s Law shown at the right.

I = E Where: I = Amperes (Current) R E = Voltage

R = Ohms (Resistance)

I = V Where: I = Amperes (Current) R V = Voltage

R = Ohms (Resistance)

OHM’S LAW

W I

W

RIR

W V

V R

W I

V I

V R

VI

I2R

WR

2V W

V

(VOLTS)

I

(AMPS)

(OHMS)

R

(WATTS)

W

WATTS

AMPERES

VOLTS

VOLTS = WATTS x OHMS

VOLTS =

VOLTS = AMPERES x OHMS

VOLTS

AMPERES

WATTS

AMPERES2

VOLTS2

WATTS

OHMS

OHMS =

OHMS =

OHMS = VOLTS2

OHMS

WATTS

WATTS = VOLTS x AMPERES

WATTS = AMPERES2 x OHMS

WATTS =

VOLTS

OHMS

WATTS

VOLTS

WATTS

OHMS

AMPERES

AMPERES =

AMPERES =

AMPERES =

Electric Heater Catalog. Page 29

ELECTRIC CURRENT TABLE

FAQ

What is required for properly sizing a heater in my room?

- If you have a room with 8 feet ceiling height; you can calculate the square footage times 10 watts per square foot.

- If your ceiling is higher than 8 feet; calculate the cubic footage L x W x H and multiply by I watt per square foot.

- If you plan on heating a garage calculate the cubic footage L x W x H and multiply by I watt per square foot and multiply the square footage for each garage door by 48 (watts per square foot) and add this amount to the cubic footage. This will be the amount required to heat the garage.

Are 120 volts and 240 volts heaters interchangeable?

- A 240 volts heater run at 120 volts will produce 1/4 of the rated wattage. A 120 volts heater run at 240 volts will be destroyed and could cause fire damage to the building.

If I know the BTU's required; how do I calculate the watts required?

- Watts = BTU/3.412 (I Watt = 3.41 BTU)

Calculating Temperature Rise?

- Sometimes your heater does not feel like it is putting out enough heat. Why not, you ask?

- Temperature rise is calculated by taking the kW times the constant 3167 divided by the CFM. For instance:

5kW x 3167/300CFM = 15835/300CFM = 52.8 °F. If your ambient temperature is 60 °F the outlet air is 112 °F.

Power kW

Voltage (ph) 120V (1) 208V (1) 208V (3) 240V (1) 240V (3) 277V (1)

0.3 2.50 1.45 0.83 1.25 0.72 1.09

0.4 3.34 1.92 1.11 1.67 0.97 1.45

0.5 4.17 2.41 1.39 2.09 1.21 1.81

0.6 5.00 2.89 1.66 2.50 1.45 2.17

0.75 6.25 3.61 2.09 3.13 1.81 2.71

0.8 6.67 3.85 2.23 3.34 1.93 2.89

1.0 8.34 4.81 2.78 4.17 2.41 3.61

1.2 10.00 5.77 3.34 5.00 2.89 4.34

1.25 10.42 6.01 3.47 5.21 3.01 4.52

1.4 11.67 6.73 3.89 5.84 3.38 5.06

1.5 12.50 7.22 4.17 6.25 3.61 5.42

1.6 13.34 7.70 4.45 6.67 3.86 5.78

1.75 14.59 8.42 4.87 7.30 4.22 6.32

2.0 16.67 9.62 5.56 8.34 4.82 7.22

2.25 18.75 10.82 6.25 9.38 5.42 8.13

2.5 20.84 12.02 6.95 10.42 6.02 9.03

3.0 25.00 14.43 8.34 12.50 7.23 10.83

4.0 33.34 19.23 11.12 16.67 9.64 14.44

4.5 37.50 21.64 12.50 18.75 10.84 16.25

5.0 41.67 24.04 13.90 20.84 12.05 18.05

6.0 50.00 28.85 16.68 25.00 14.45 21.66

7.5 62.50 36.06 20.84 31.25 18.06 27.08

8.0 66.67 38.47 22.23 33.34 19.27 28.88

9.0 75.00…