WWYK263009_65 Design Analysis_Part18_Part3.pdf
PDF 195 KB Posted
- Solicitation number
- W912BV25S0014
About this file
This is a structural engineering design analysis document containing masonry wall calculations for a shelter area in the Bomber Agile Common Hangar (BACH) project at Tinker Air Force Base. The analysis includes detailed calculations for two masonry walls (SW1 and SW5) designed according to TMS 402-16 ASD code standards, with both walls having a height of 15 feet and utilizing CMU 2.0-60 material with full grouting. SW1 is 10 feet long with 8-#6 vertical reinforcement bars at 16-inch spacing, while SW5 is 13 feet long with 20-#7 vertical reinforcement bars at 8-inch spacing. Both walls show acceptable performance ratios under various load combinations including dead loads, wind loads, and roof live loads.
The document is part of the 65% design submittal package (specifically section 14.7 Interior Design Appendix) and includes detailed material specifications, geometry configurations, load conditions, and structural analysis results with interaction diagrams for axial compression, tension, and shear forces. All calculations indicate the walls meet design requirements with "OK" global status, demonstrating sufficient structural capacity for their intended use as part of a FEMA storm shelter within the facility.
View the file
Other files
Show 40 more
Latest 50 of 95 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Current Date: 11/13/2024 9:02 AM
Units system: English
File name: P:\Projects\019503\02 Design\Struc\Calculations\Shelter\Masonry Wall Analysis\Area A Shelter\SW1 Uplift.msw
Design Results Masonry wall
General Information
Global status : OK
Design code : TMS 402-16 ASD
Materials:
Material : CMU 2.0-60
Mortar type : Port/Mort - M/S
Grouting type : Full grouting
Masonry compression strength (F`m) : 2 [Kip/in2]
Steel tension strength (fy) : 60 [Kip/in2]
Steel allowable tension strength (Fs) : 32 [Kip/in2]
Joint reinforcement allowable tension strength (Fs) : 30 [Kip/in2]
Steel elasticity modulus (Es) : 29000 [Kip/in2]
Masonry elasticity modulus (Em) : 1800 [Kip/in2]
Masonry unit weight : 0.135 [Kip/ft3]
Geometry
Total height : 15.00 [ft]
Total length : 10.00 [ft]
Foundation type : Continuous
Wall bottom restraint : Pinned
Column bottom restraint : Fixed
Rigidity elements : None
Number of stories: 1
Story Story height Wall thickness Effective unit weight
[ft] [in] [Kip/ft3]
1 15.00 7.63 0.14
Load Conditions
ID Comb. Category Description
DL No DL Dead Load
W No WIND Wind Load
Lr No LLR Roof Live Load
Wz No WIND Wind in Z
D1 Yes DL
D2 Yes DL+0.6W
D3 Yes 0.6DL+0.6W
D4 Yes DL+Lr
D5 Yes DL+0.75Lr
Page1
D6 Yes DL+0.45W+0.75Lr
S1 Yes DL
D7 Yes DL+0.6Wz
D8 Yes DL+0.45Wz+0.75Lr
D9 Yes 0.6DL+0.6Wz
Loads
Concentrated loads:
Story Condition Direction Magnitude Eccentricity Distance
[Kip] [in] [ft]
1 W Horizontal 1.60 0.00 0.00
Distributed loads:
Consider self weight : DL
Story Condition Direction Magnitude Eccentricity
[Kip/ft] [ft]
1 DL Vertical 0.66 0.00
1 W Vertical -2.00 0.00
1 Lr Vertical 1.10 0.00
1 Wz Vertical -2.00 0.00
Out-of-plane loads:
Story Condition Magnitude
[Kip/ft2]
1 Wz 0.17
Parapet Wz 0.17
Bearing Wall Design
Status : OK
Page2
Geometry
Level Segment X Coordinate Y Coordinate Width Height
[ft] [ft] [ft] [ft]
0 1 0.00 0.00 10.00 15.00
Vertical reinforcement
Segment Bars Spacing Ld
[in] [in]
1 8-#6 16.00 63.77
Combined axial flexure
Page3
Segment Condition P M Ma Ratio
[Kip] [Kip*ft] [Kip*ft]
1 D9(Max) -4.37 -28.35 35.46 0.80
Interaction diagrams, P vs. M
Axial compression
Segment Condition P Pa Ratio
[Kip] [Kip]
1 D4(Bottom) 30.08 299.63 0.10
Axial tension
Segment Condition ft Fs Ratio
[Kip/in2] [Kip/in2]
1 D9(Top) 1.19 32.00 0.04
Shear
Segment Condition fv Fv Ratio
[Kip/in2] [Kip/in2]
1 D9(Max) 0.007 0.050 0.15
Shear Wall Design
Status : OK
Page4
Geometry
Level Segment X Coordinate Y Coordinate Width Height
[ft] [ft] [ft] [ft]
0 1 0.00 0.00 10.00 15.00
Reinforcement
Vertical reinforcement Horizontal reinforcement
Segment Bars Spacing Ld Bars Spacing Ld
[in] [in] [in] [in]
1 8-#6 16.00 63.77 -- 0.00 0.00
Combined axial flexure
Page5
Segment Condition P M Ma Ratio
[Kip] [Kip*ft] [Kip*ft]
1 D3(Bottom) -0.50 -14.00 608.41 0.02
Interaction diagrams, P vs. M
Axial compression
Segment Condition P Pa Ratio
[Kip] [Kip]
1 D4(Bottom) 30.08 299.49 0.10
Axial tension
Segment Condition ft Fs Ratio
[Kip/in2] [Kip/in2]
1 D9(Top) 1.11 32.00 0.03
Shear
Segment Condition fv Fv Ratio
[Kip/in2] [Kip/in2]
1 D3(Max) 0.001 0.050 0.02
Notes
Page6
* P = Axial load
* Pa = Allowable compressive force due to axial load.
* M = Moment at the section under consideration.
* Ma = Wall allowable moment due to axial force or lintel pure flexure allowable moment
* fa = Calculated compressive stress due to axial load only
* fb = Calculated compressive stress due to axial flexure only
* ft = Calculated axial tension
* Fa = Allowable compressive stress due to axial load only
* Fb = Allowable compressive stress due to axial flexure only
* fv = Calculated shear stress
* Fs = Allowable tensile or compressive stress
* Fv = Allowable shear stress
* ld = Embedment length
* As = Effective cross sectional area of reinforcement
* δs = Calculated deflection
* δmax = Maximum allowable deflection
Page7
Current Date: 11/13/2024 9:08 AM
Units system: English
File name: P:\Projects\019503\02 Design\Struc\Calculations\Shelter\Masonry Wall Analysis\Area A Shelter\SW5.msw
Design Results Masonry wall
General Information
Global status : OK
Design code : TMS 402-16 ASD
Materials:
Material : CMU 2.0-60
Mortar type : Port/Mort - M/S
Grouting type : Full grouting
Masonry compression strength (F`m) : 2 [Kip/in2]
Steel tension strength (fy) : 60 [Kip/in2]
Steel allowable tension strength (Fs) : 32 [Kip/in2]
Joint reinforcement allowable tension strength (Fs) : 30 [Kip/in2]
Steel elasticity modulus (Es) : 29000 [Kip/in2]
Masonry elasticity modulus (Em) : 1800 [Kip/in2]
Masonry unit weight : 0.135 [Kip/ft3]
Geometry
Total height : 15.00 [ft]
Total length : 13.00 [ft]
Foundation type : Continuous
Wall bottom restraint : Pinned
Column bottom restraint : Fixed
Rigidity elements : None
Number of stories: 1
Story Story height Wall thickness Effective unit weight
[ft] [in] [Kip/ft3]
1 15.00 7.63 0.14
Load Conditions
ID Comb. Category Description
DL No DL Dead Load
Wi No WIND Wind Load (in plane)
Lr No LLR Roof Live Load
Wop No WIND Wind Load (out of plane positive)
Won No WIND Wind Load (out of plane negative)
Wu No WIND Wind Load (uplift)
D13 Yes 1.4DL
D14 Yes 1.2DL+0.5Lr
D15 Yes 1.2DL+1.6Lr
Page1
D16 Yes 1.2DL+0.5Wi
D17 Yes 1.2DL+0.5Wop
D18 Yes 1.2DL+0.5Won
D19 Yes 1.2DL+0.5Wu
D20 Yes 1.2DL+0.5Wi+1.6Lr
D21 Yes 1.2DL+1.6Lr+0.5Wop
D22 Yes 1.2DL+1.6Lr+0.5Won
D23 Yes 1.2DL+1.6Lr+0.5Wu
D24 Yes 1.2DL+Wi
D25 Yes 1.2DL+Wop
D26 Yes 1.2DL+Won
D27 Yes 1.2DL+Wu
D28 Yes 1.2DL+Wi+0.5Lr
D29 Yes 1.2DL+0.5Lr+Wop
D30 Yes 1.2DL+0.5Lr+Won
D31 Yes 1.2DL+0.5Lr+Wu
D32 Yes 0.9DL+Wi
D33 Yes 0.9DL+Wop
D34 Yes 0.9DL+Won
D35 Yes 0.9DL+Wu
S1 Yes DL
S2 Yes DL+Lr
S3 Yes DL+0.75Lr
S4 Yes DL+0.6Wi
S5 Yes DL+0.6Wop
S6 Yes DL+0.6Won
S7 Yes DL+0.6Wu
S8 Yes DL+0.45Wi+0.75Lr
S9 Yes DL+0.45Wop+0.75Lr
S10 Yes DL+0.45Won+0.75Lr
S11 Yes DL+0.45Wu+0.75Lr
S12 Yes 0.6DL+0.6Wi
S13 Yes 0.6DL+0.6Wop
S14 Yes 0.6DL+0.6Won
S15 Yes 0.6DL+0.6Wu
Loads
Concentrated loads:
Story Condition Direction Magnitude Eccentricity Distance
[Kip] [in] [ft]
1 Wi Horizontal 24.81 0.00 0.00
Distributed loads:
Consider self weight : DL
Story Condition Direction Magnitude Eccentricity
[Kip/ft] [ft]
1 DL Vertical 0.20 0.00
1 Wi Vertical 0.18 0.00
1 Lr Vertical 0.34 0.00
1 Wu Vertical -0.60 0.00
Out-of-plane loads:
Page2
Story Condition Magnitude
[Kip/ft2]
1 Wop -0.17
1 Won 0.16
Parapet Wop -0.17
Parapet Won 0.16
Bearing Wall Design
Status : OK
Geometry
Level Segment X Coordinate Y Coordinate Width Height
[ft] [ft] [ft] [ft]
0 1 0.00 0.00 13.00 15.00
Vertical reinforcement
Page3
Segment Bars Spacing Ld
[in] [in]
1 20-#7 8.00 86.80
Combined axial flexure
Segment Condition P M Ma Ratio
[Kip] [Kip*ft] [Kip*ft]
1 D29(Max) 14.87 61.42 64.24 0.96
Interaction diagrams, P vs. M
Axial compression
Segment Condition P Pa Ratio
[Kip] [Kip]
1 D20(Bottom) 30.89 384.64 0.08
Axial tension
Segment Condition ft Fs Ratio
[Kip/in2] [Kip/in2]
1 D35(Top) 0.22 32.00 0.01
Shear
Page4
Segment Condition fv Fv Ratio
[Kip/in2] [Kip/in2]
1 D33(Max) 0.013 0.053 0.24
Shear Wall Design
Status : OK
Geometry
Level Segment X Coordinate Y Coordinate Width Height
[ft] [ft] [ft] [ft]
0 1 0.00 0.00 13.00 15.00
Reinforcement
Page5
Vertical reinforcement Horizontal reinforcement
Segment Bars Spacing Ld Bars Spacing Ld
[in] [in] [in] [in]
1 20-#7 8.00 86.80 -- 0.00 0.00
Combined axial flexure
Segment Condition P M Ma Ratio
[Kip] [Kip*ft] [Kip*ft]
1 D28(Bottom) 27.21 -361.80 1645.20 0.22
Interaction diagrams, P vs. M
Axial compression
Segment Condition P Pa Ratio
[Kip] [Kip]
1 D20(Bottom) 30.89 384.44 0.08
Axial tension
Segment Condition ft Fs Ratio
[Kip/in2] [Kip/in2]
1 D35(Top) 0.21 32.00 0.01
Shear
Page6
Segment Condition fv Fv Ratio
[Kip/in2] [Kip/in2]
1 D32(Bottom) 0.022 0.055 0.40
Notes
* P = Axial load
* Pa = Allowable compressive force due to axial load.
* M = Moment at the section under consideration.
* Ma = Wall allowable moment due to axial force or lintel pure flexure allowable moment
* fa = Calculated compressive stress due to axial load only
* fb = Calculated compressive stress due to axial flexure only
* ft = Calculated axial tension
* Fa = Allowable compressive stress due to axial load only
* Fb = Allowable compressive stress due to axial flexure only
* fv = Calculated shear stress
* Fs = Allowable tensile or compressive stress
* Fv = Allowable shear stress
* ld = Embedment length
* As = Effective cross sectional area of reinforcement
* δs = Calculated deflection
* δmax = Maximum allowable deflection
Page7
Bomber Agile Common Hangar (BACH) Project No.: WWYK263009 Tinker Air Force Base, Oklahoma 65% Design Submittal
Design Analysis - 1575
14.7 INTERIOR DESIGN APPENDIX
14.7.1 65% SID Binder
14.7.2 65% FFE Binder
| SECTION 14 - APPENDICES |
| 14.7 INTERIOR DESIGN APPENDIX |