These are submittal sheets for variable air volume (VAV) terminal units manufactured by Price Industries. The specifications detail several models including single duct terminal units with electric coils, attenuators, access doors, hanger brackets, and seismic certification options. The units are constructed with galvanized steel housing, fiberglass insulation, and include features like multi-point airflow sensors, galvanized damper shafts, and rectangular discharge openings. Multiple control options are available including field-mounted controls, factory-mounted digital controls, and Price-supplied digital or pneumatic controls. The documents provide detailed dimensions, weights, construction specifications, liner options, and mounting configurations. The seismic certification section includes OSHPD preapproval details for ceiling-suspended installations with weight ranges from 33-260 lbs depending on unit size. Various coil configurations are available with aluminum fins and copper tubes, along with multiple liner material options including fiberglass, fiber-free foam, and foil-faced options.
View the file
Other files
Show 40 more
Latest 50 of 95 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Preliminary
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-2 Sales Order #: -002
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A (Continued) 16-50 - 184T - 40 x 30 x 24 - A2
200.8 Operating Conditions
Operating Condition Usage
(%) CFM
SP (in.H20) Input Adj.
Cell Qty On Off Fail
RPM Hz Fanwheel BHP Each Total
Vel.
(ft/min) Watts FEG
% O.P. FEI
Condition 1 100 7,700 5.40 5.70 2 0 0 3,917 67.8 5.69 11.38 592 10,209 FEG80 3% 1.05 Condition 1 w/ Failed 100 4,373 1.74 2.17 1 0 1 3,928 68 4.09 4.09 673 3,750 FEG80 18% .74 Condition 1 at 60Hz 100 6,925 4.39 4.61 2 0 0 3,466 60 3.94 7.87 533 7,135 FEG80 3% 1.08
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-2 Sales Order #: -002
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A (Continued) 16-50 - 184T - 40 x 30 x 24 - A2
200.9 Bare Fan Sound Power with Coplanar Silencer (dB re: 10E-12 watts) Operating Condition 63 125 250 500 1k 2k 4k 8k LwA Lw
Condition 1 Inlet
Outlet
Condition 1 w/ Failed Inlet
Outlet
Condition 1 at 60Hz Inlet
Outlet
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-2 Sales Order #: -002
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A (Continued) 16-50 - 184T - 40 x 30 x 24 - A2
200.10 AMCA Statement
Nortek Air Solutions LLC certifies that the HPF-A100 fan wheel shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
The AMCA licensed air and/or sound performance data has been modified for installation,appurtenances or accessories, etc. not included in the certified data. The modified performance is not AMCA licensed but is provided to aid in selection and applications of the product. Performance certified is for installation type A: Free Inlet/Free Outlet Power [bhp] excludes drives
FWTRating DLL: Ver-1.6 / May 2022
Coils Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-2 Sales Order #: -002
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
300 Chilled Water Coil 1 : CW1 : Box A 5WC - 20 - 42 x 57 x 10 - 10 AL
300.1 Coil Layout
Right1. Coil Hand Single2. Configuration Straight3. Connection Orientation Red Brass4. Connection Material MPT5. Connection Type
None6. Rack Style None7. Rack Finish 16Ga 304 SS8. Blankoff Material None9. Blankoff Finish
300.2 Construction
11. Quantity
0.52. Serpentine
42.000 in3. Fin Height
57.000 in4. Fin Length
105. Rows
106. Fins per Inch
16.63 ft²7. Face Area
1 in8. Stand Height Tube Detail - Primary Surface
Copper9. Material
0.625 x 0.020 in10.O.D. x Wall
1.500 x 1.299 in11.Spacing Smooth12. Internal
0.028 in13.Return Bends
16Ga 304 SS14.Casing None15.Coating
Fin Detail - Secondary Surface Aluminum16.Material
0.008 in17.Thickness Corrugated, Waffle with Straight Edge18.Configuration
Single Bank, Right Hand, 1 per unit 5WC - 20 - 42 x 57 x 10 - 10 AL
Supply / Return Connections Vent and Drain Quantity
Type
MPT
Pipe Size
1.5 in
Material Red Brass
Type
0.125 in FPT
Vent Location Return Connection
Drain Location Supply Connection
300.3 Condition 1
Entering
7,700 ACFM1. Actual Airflow 7,603 SCFM2. Standard Airflow 1,302 ft3. Elevation
76.0 °F4. Entering Air DB
61.3 °F5. Entering Air WB Prop / 30.0 %6. Fluid Type / %
44.0 °F7. Entering Fluid Temp
25.8 GPM8. Fluid Flow Rate
0.00009. Fluid Fouling Internal
Leaving
194.9 MBH10.Total Capacity
193.5 MBH11.Sensible Capacity
463.16 ft/min12.Actual Face Velocity
52.9 °F13.Leaving Air DB
52.2 °F14.Leaving Air WB
0.95 in.H2015.APD
60.0 °F16.Leaving Fluid Temp
2.04 ft/s17.Fluid Velocity
9.52 ft.H2018.Fluid Pressure Drop
Notes:
1. Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
2. Chilled water velocity is below recommended minimum of 2.5 fps
300.4 Notes / Features
1. Manufacturer: Nortek Air Solutions, 5510 SW 29th Street, Oklahoma City, OK 73179
2. Top and bottom casing flange height is 1.000 in.
3. SCFM is corrected for Elevation and EDB.
4. Coils to be pressure tested at 315 PSI
5. Total operating weight is 834 lb.
6. Total fluid volume is 22.8 Gal.
Components Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-2 Sales Order #: -002
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
500 Filter 1 : FILT1 : Box A
500.1 Pre / Final Size & Quantity
Upstream Face Load1. Loading Galvanized2. Frame Material None3. Frame Finish
(20) C-79-64. Filter Clips 16Ga Galv5. Blankoff / Rack Material None6. Blankoff / Rack Finish
60.125 in W x 45.000 in H7. Bank Size
(3) 20 in x 25 in8. Qty / set & Frame Size 1
(3) 20 in x 20 in9. Qty / set & Frame Size 2
10.Qty / set & Frame Size 3 11.Qty / set & Frame Size 4
500.2 Pre Filter
4.000 in1. Filter Depth MERV 82. Efficiency American Air Filter3. Manufacturer
14. Number of Sets
410.67 ft/min at 7,700 ACFM5. Max Face Velocity PerfectPleat SC6. Model
500.3 Pressure Gage Specifications - Gage 1
Dwyer1. Manufacturer Magnehelic 2002 (0-2" w.c.)2. Model / Range
3. Options
14. Quantity
500.4 Final Filter
4.000 in1. Filter Depth MERV 132. Efficiency American Air Filter3. Manufacturer
14. Number of Sets
410.67 ft/min at 7,700 ACFM5. Max Face Velocity VariCel II6. Model
500.5 Pressure Gage Specifications - Gage 2
Dwyer1. Manufacturer Magnehelic 2002 (0-2" w.c.)2. Model / Range
3. Options
14. Quantity
500.6 Notes / Features
1. All sets of Filters and clips to ship loose inside unit, installed by others.
2. Pressure tap spacer to be included.
Electrical Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-2 Sales Order #: -002
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
700 Electrical Layout Diagram
Note: The FLA and MCA values shown are estimated, see the electrical schematics for the actual values.
Unit Data Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-2 Sales Order #: -002
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
901 Center of Gravity
Size (Inches) X Y Z
Operating Weight (Pounds) Center of Gravity (Inches)
X Y Z
144.00 73.00 56.00 4,256 69.00 34.00 27.00
901.1 Notes
1. Center of gravity and weights are estimates and subject to change.
2. The center of gravity and weights shown above are based on operating weights and do not include packaging materials.
3. A 5% safety factor has been applied to the operating weights.
4. Corner weights apply to rectangular boxes only.
5. Corner weights are to assist in handling of the unit. Some units are not intended to be supported only at the corners. Contact your
Sales Representative for support information.
Unit Data Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-2 Sales Order #: -002
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
901 Center of Gravity (Continued)
901.2 Box A
Size (Inches) X Y Z
Shipping Weight (Pounds) Corner Weights (Pounds)
C1 C2 C3 C4
144.00 73.00 56.00 4,054 1,113 970 918 1,053
◊ Center of gravity, weight, and corner weights shown are based on shipping weight. Values are estimates and subject to change.
P rin te d
(y yy y- M
M -d
d) : 2
3-
-1
Line Item Summary Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
Product Type Factory Finish Design Quantity Cabinet Const. Knockdown Const. Factory SAE Environment Measurement System Wall Thickness
Air Handler None 1 ITF - Integrated Frame None Indoor US Standard 3
Box A Cabinet and Components
* Box Dimensions do not include lifting lugs, electrical panels, pipe connections, door handles, etc. The height dimensions include raised roof seams and sloped roof for outdoor equipment. Box weights do not include roof curbs.
Length (in) Height (in) Width (in) 12" Weight (lb) Weight (lb)
144.00 56.00 73.00 183.81 Cabinet Only 2,206
Exterior Material 16Ga Galv Finish Color N/A Base Structure Steel Tube Base Height 4 in Base Floor Mat. 16Ga Galv Base Insulation Polyurethane Foam
Interior Material 20Ga Galv Insulation HD Fiberglass Roll Base Liner 20Ga Galv
Qty Box A Component Description Weight (lb) 2 3" Thermal Break Factory Door: 24 x 42 Out Swing VW: None 107 1 3" Thermal Break Factory Door: 24 x 45.5 In Swing VW: 10 in x 10 in Thermal Break 68 1 OPENING: (Outside Air) Rectangle 48.00 x 24.00 1
1 DAMPER: Ruskin CD 60 (Galvanized) - 48.000 in (Blade Direction) x 24.000 in -- Actuator: Furnished by Others, Mounted by Others - Wired by Others 59
1 Pre/Final Filter: 3 Columns x 2 Rows 31 3 Pleated Filter SC 20x25x4 M8 (1 Set) - Face Load 5 3 Pleated Filter SC 20x20x4 M8 (1 Set) - Face Load 4 3 Box Filter (No Header) 20x25x4 M13 (1 Set) - Face Load 26 3 Box Filter (No Header) 20x20x4 M13 (1 Set) - Face Load 21 3 FRAME, TYPE 8, 16ga GALV W/CLOSED CELL, 20 X 25 21
20 Filter Clip Farr C-79-6 Gal 2 1 Non-Headered Frame, Filter Standoff 24 X 24 1 3 FRAME, TYPE 8, 16ga GALV W/CLOSED CELL, 20 X 20 19 1 Gage Magnehelic 0-2.0wc Dwyer 2002-ASF 2 1 Gage Magnehelic 0-2.0wc Dwyer 2002-ASF 2 1 5WC-20-42x57x10-10AL, .008F, .020T 16Ga 304 SS, 16Ga 304 SS Blankoff 632 1 Drain Pan 25.00" x 67.00" (16Ga 304 SS) 78
1 FANWALL: (SUPPLY) 16-50 - 184T - 40 x 30 x 24 - A2 (PentaCube) -- ELECTRICAL: Standard, One Fan, Magnesense, Wired to: MSP Panel & VFD Only 444
2 FANWALL Backdraft Damper, HBD-6, 18"(w) x 18"(h) ID 28 2 Motor Toshiba TEAO 3600rpm 5-7HP 230/460 Insul Brngs Keyed 210 1 VFD Only 6" x 46" x 10" NEMA 1 Indoor 21 1 VFD, Yaskawa, 10 HP (Rep Supplied) 0 1 MSP Panel 20" x 16" x 8" NEMA 4 Indoor / Outdoor 67 1 OPENING: (Supply Air) Rectangle 66.00 x 18.00 0
Box A Component Totals 1,849 Box A Cabinet & Component Totals 4,054
Line Item Summary Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
Qty Design Items Weight (lb) 1 Factory Testing: None 0 1 Design Miscellaneous 0
Design Item Totals 0
Weight (lb) Weight (Ea) 4,054
Errors and Warnings Project: The required Project information has not been completed.
Unit Design Options Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
106 Static Pressure Summary
106.1 Condition 1
106.1.1 Supply Air TSP
Tunnel Description APD (in.H20) AirTunnel 1 OA Damper - Damper (Outside Air) 0.02 AirTunnel 1 Filter 1, Pre / Final (Average Pressure Drop) 1.30 AirTunnel 1 Chilled Water Coil 1 0.89 AirTunnel 1 SA Opening (Supply Air) 0.07
Endwall 2 - Supply Air - SA Opening ESP: 3.00 Total Static Pressure: 5.28
Legend: ESP - External Static Pressure, OSA - Outside Air, EXH - Exhaust Air, RA - Return Air, SA - Supply Air
106.2 Notes/Legend
1. Summary report does not include static pressure of components supplied by others in the field unless otherwise noted.
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A 16-50 - 184T - 40 x 30 x 24 - A2
200.1 Configuration / Quantity
Supply Fan1. Function
22. Quantity 1 Rows x 2 Cols3. Array PentaCube4. Construction Upstream Removable5. Inlet Cone Location
Cell Size 6.Height
7.Width
8.Depth
9.Overall Depth
31.25 1,302 ft / 70.0 °F10.Elev. / Temp.
144 lb11.Motor & Wheel Weight 324 lb12.Fan Cell Weight
013.Redundant 014.Empty 015.Ship Loose Fan (Wheel, Motor and Mounting Base)
200.2 Options
Standard Melamine1. Coplanar Insulation No2. Extended Coplanar FBD63. Back Draft Dampers A100 Curved Cone4. Inlet Cone Type None5. Solid Perimeter Material No6. Discharge Safety Guard Steel7. Cell Material
None8. Cell Finish No9. Insulation Retainer None10. Inlet Attenuation 16Ga Galv11.Blankoff Material None12.Blankoff Finish No13.Removal Rail
200.3 Fan Wheel
HPF-A1001. Wheel Type
162. Diameter
13. Balancing Planes
504. Width 39305. Max RPM None6. Wheel Finish
200.4 Motor
Toshiba1. Manufacturer
5.5 / 112. HP Each / Total 2-Pole / 3,4803. Poles / RPM 184T / TEAO4. Frame / Casing 460/3/605. Volts / Phase / Hz
2OA005L1ZVS2106. Model
87.57. Efficiency
1.158. Service Factor
Ceramic Bearings9. Shaft Isolation
6.3 / 12.6 Amps10.FLA Each / Total
3.0 %11.Motor HP Safety Factor
200.5 Variable Frequency Drive
Others1. Furnished by
12. Quantity Yaskawa3. Manufacturer
104. Horsepower 460/3/605. Voltage
14 / 14 Amps6. Input / Output Amps
67.727. Maximum Hertz
No8. Input Line Reactor None9. VFD Communication
Notes:
1. Standalone VFD, not located in electrical panel.
200.6 Control System
No1. Redundant VFD 60Hz Purchased with VFD2. Bypass Circuit Standard3. Drive No4. Optimization Control By Others5. Control Method
Single Fan Airflow Station6. Flow Monitoring One Fan7. Fans to Monitor Magnesense8. Display
200.7 Notes / Features
1. To view patents and other pending U.S. or Canadian applications visit www.nortekair.com/patents.
2. (1) airflow measurement tap. Cone constant = 1671, cone flow differential pressure = 6.50 in.H2O at 4363 CFM per fan.
3. The estimated VFD input watts are based on the motor and VFD efficiency at the selected load and RPM.
4. Fans balanced to a maximum allowable level of 0.022 inches per second peak.
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A (Continued) 16-50 - 184T - 40 x 30 x 24 - A2
200.8 Operating Conditions
Operating Condition Usage
(%) CFM
SP (in.H20) Input Adj.
Cell Qty On Off Fail
RPM Hz Fanwheel BHP Each Total
Vel.
(ft/min) Watts FEG
% O.P. FEI
Condition 1 100 7,410 5.28 5.55 2 0 0 3,801 65.5 5.26 10.53 570 9,357 FEG80 2% 1.08 Condition 1 w/ Failed 100 4,363 1.83 2.26 1 0 1 3,928 67.7 4.14 4.14 671 3,749 FEG80 17% .76 Condition 1 at 60Hz 100 6,868 4.55 4.77 2 0 0 3,481 60 4.04 8.08 528 7,235 FEG80 2% 1.10
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A (Continued) 16-50 - 184T - 40 x 30 x 24 - A2
200.9 Bare Fan Sound Power with Coplanar Silencer (dB re: 10E-12 watts) Operating Condition 63 125 250 500 1k 2k 4k 8k LwA Lw
Condition 1 Inlet
Outlet
Condition 1 w/ Failed Inlet
Outlet
Condition 1 at 60Hz Inlet
Outlet
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A (Continued) 16-50 - 184T - 40 x 30 x 24 - A2
200.10 AMCA Statement
Nortek Air Solutions LLC certifies that the HPF-A100 fan wheel shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
The AMCA licensed air and/or sound performance data has been modified for installation,appurtenances or accessories, etc. not included in the certified data. The modified performance is not AMCA licensed but is provided to aid in selection and applications of the product. Performance certified is for installation type
Coils Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
300 Chilled Water Coil 1 : CW1 : Box A 5WC - 20 - 42 x 57 x 10 - 10 AL
300.1 Coil Layout
Right1. Coil Hand Single2. Configuration Straight3. Connection Orientation Red Brass4. Connection Material MPT5. Connection Type
None6. Rack Style None7. Rack Finish 16Ga 304 SS8. Blankoff Material None9. Blankoff Finish
300.2 Construction
11. Quantity
0.52. Serpentine
42.000 in3. Fin Height
57.000 in4. Fin Length
105. Rows
106. Fins per Inch
16.63 ft²7. Face Area
1 in8. Stand Height Tube Detail - Primary Surface
Copper9. Material
0.625 x 0.020 in10.O.D. x Wall
1.500 x 1.299 in11.Spacing Smooth12. Internal
0.028 in13.Return Bends
16Ga 304 SS14.Casing None15.Coating
Fin Detail - Secondary Surface Aluminum16.Material
0.008 in17.Thickness Corrugated, Waffle with Straight Edge18.Configuration
Single Bank, Right Hand, 1 per unit 5WC - 20 - 42 x 57 x 10 - 10 AL
Supply / Return Connections Vent and Drain Quantity
Type
MPT
Pipe Size
1.5 in
Material Red Brass
Type
0.125 in FPT
Vent Location Return Connection
Drain Location Supply Connection
300.3 Condition 1
Entering
7,410 ACFM1. Actual Airflow 7,317 SCFM2. Standard Airflow 1,302 ft3. Elevation
76.0 °F4. Entering Air DB
61.3 °F5. Entering Air WB Prop / 30.0 %6. Fluid Type / %
44.0 °F7. Entering Fluid Temp
24.6 GPM8. Fluid Flow Rate
0.00009. Fluid Fouling Internal
Leaving
186.0 MBH10.Total Capacity
185.2 MBH11.Sensible Capacity
445.71 ft/min12.Actual Face Velocity
53.0 °F13.Leaving Air DB
52.2 °F14.Leaving Air WB
0.89 in.H2015.APD
60.0 °F16.Leaving Fluid Temp
1.95 ft/s17.Fluid Velocity
8.76 ft.H2018.Fluid Pressure Drop
Notes:
1. Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
2. Chilled water velocity is below recommended minimum of 2.5 fps
300.4 Notes / Features
1. Manufacturer: Nortek Air Solutions, 5510 SW 29th Street, Oklahoma City, OK 73179
2. Top and bottom casing flange height is 1.000 in.
3. SCFM is corrected for Elevation and EDB.
4. Coils to be pressure tested at 315 PSI
5. Total operating weight is 834 lb.
6. Total fluid volume is 22.8 Gal.
Components Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
500 Filter 1 : FILT1 : Box A
500.1 Pre / Final Size & Quantity
Upstream Face Load1. Loading Galvanized2. Frame Material None3. Frame Finish
(20) C-79-64. Filter Clips 16Ga Galv5. Blankoff / Rack Material None6. Blankoff / Rack Finish
60.125 in W x 45.000 in H7. Bank Size
(3) 20 in x 25 in8. Qty / set & Frame Size 1
(3) 20 in x 20 in9. Qty / set & Frame Size 2
10.Qty / set & Frame Size 3 11.Qty / set & Frame Size 4
500.2 Pre Filter
4.000 in1. Filter Depth MERV 82. Efficiency American Air Filter3. Manufacturer
14. Number of Sets
395.20 ft/min at 7,410 ACFM5. Max Face Velocity PerfectPleat SC6. Model
500.3 Pressure Gage Specifications - Gage 1
Dwyer1. Manufacturer Magnehelic 2002 (0-2" w.c.)2. Model / Range
3. Options
14. Quantity
500.4 Final Filter
4.000 in1. Filter Depth MERV 132. Efficiency American Air Filter3. Manufacturer
14. Number of Sets
395.20 ft/min at 7,410 ACFM5. Max Face Velocity VariCel II6. Model
500.5 Pressure Gage Specifications - Gage 2
Dwyer1. Manufacturer Magnehelic 2002 (0-2" w.c.)2. Model / Range
3. Options
14. Quantity
500.6 Notes / Features
Electrical Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
Note: The FLA and MCA values shown are estimated, see the electrical schematics for the actual values.
Unit Data Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
901 Center of Gravity
Size (Inches) X Y Z
Operating Weight (Pounds) Center of Gravity (Inches)
X Y Z
144.00 73.00 56.00 4,256 69.00 34.00 27.00
901.1 Notes
1. Center of gravity and weights are estimates and subject to change.
2. The center of gravity and weights shown above are based on operating weights and do not include packaging materials.
3. A 5% safety factor has been applied to the operating weights.
4. Corner weights apply to rectangular boxes only.
5. Corner weights are to assist in handling of the unit. Some units are not intended to be supported only at the corners. Contact your
Unit Data Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-3 Sales Order #: -003
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
901 Center of Gravity (Continued)
901.2 Box A
Size (Inches) X Y Z
Shipping Weight (Pounds) Corner Weights (Pounds)
C1 C2 C3 C4
144.00 73.00 56.00 4,054 1,113 970 918 1,053
◊ Center of gravity, weight, and corner weights shown are based on shipping weight. Values are estimates and subject to change.
te d
(y yy y- M
M -d
d) : 2
3-
Line Item Summary Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
Product Type Factory Finish Design Quantity Cabinet Const. Knockdown Const. Factory SAE Environment Measurement System Wall Thickness
Air Handler None 1 ITF - Integrated Frame None Indoor US Standard 3
Box A Cabinet and Components
* Box Dimensions do not include lifting lugs, electrical panels, pipe connections, door handles, etc. The height dimensions include raised roof seams and sloped roof for outdoor equipment. Box weights do not include roof curbs.
Length (in) Height (in) Width (in) 12" Weight (lb) Weight (lb)
144.00 50.00 64.00 161.67 Cabinet Only 1,940
Exterior Material 16Ga Galv Finish Color N/A Base Structure Steel Tube Base Height 4 in Base Floor Mat. 16Ga Galv Base Insulation Polyurethane Foam
Interior Material 20Ga Galv Insulation HD Fiberglass Roll Base Liner 20Ga Galv
Qty Box A Component Description Weight (lb) 2 3" Thermal Break Factory Door: 24 x 39.5 Out Swing VW: None 102 1 3" Thermal Break Factory Door: 24 x 43.5 In Swing VW: 10 in x 10 in Thermal Break 66 1 OPENING: (Outside Air) Rectangle 40.00 x 21.00 1
1 DAMPER: Ruskin CD 60 (Galvanized) - 40.000 in (Blade Direction) x 21.000 in -- Actuator: Furnished by Others, Mounted by Others - Wired by Others 43
1 Pre/Final Filter: 2 Columns x 2 Rows 24 4 Pleated Filter SC 20x25x4 M8 (1 Set) - Face Load 7 4 Box Filter (No Header) 20x25x4 M13 (1 Set) - Face Load 35 4 FRAME, TYPE 8, 16ga GALV W/CLOSED CELL, 20 X 25 29
12 Filter Clip Farr C-79-6 Gal 1 1 Non-Headered Frame, Filter Standoff 24 X 24 1 1 Gage Magnehelic 0-2.0wc Dwyer 2002-ASF 2 1 Gage Magnehelic 0-2.0wc Dwyer 2002-ASF 2 1 5WC-24-36x48x10-10AL, .008F, .020T 16Ga 304 SS, 16Ga 304 SS Blankoff 465 1 Drain Pan 25.00" x 58.00" (16Ga 304 SS) 69
1 FANWALL: (SUPPLY) 12-105 - 182T - 36 x 26 x 24 - A2 (PentaCube) -- ELECTRICAL: Standard, One Fan, Magnesense, Wired to: MSP Panel & VFD Only 382
2 FANWALL Backdraft Damper, HBD-6, 18"(w) x 18"(h) ID 28 2 Motor Toshiba TEAO 3600rpm 3-4.5HP 230/460 Insul Brngs Keyed 176 1 VFD Only 6" x 46" x 10" NEMA 1 Indoor 16 1 VFD, Yaskawa, 7.5 HP (Rep Supplied) 0 1 MSP Panel 20" x 16" x 8" NEMA 4 Indoor / Outdoor 67 1 OPENING: (Supply Air) Rectangle 57.00 x 15.00 0
Box A Component Totals 1,515 Box A Cabinet & Component Totals 3,455
Qty Design Items Weight (lb) 1 Factory Testing: None 0 1 Design Miscellaneous 0
Design Item Totals 0
Weight (lb) Weight (Ea) 3,455
Line Item Summary Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
Unit Design Options Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
106 Static Pressure Summary
106.1 Condition 1
106.1.1 Supply Air TSP
Tunnel Description APD (in.H20) AirTunnel 1 OA Damper - Damper (Outside Air) 0.02 AirTunnel 1 Filter 1, Pre / Final (Average Pressure Drop) 1.26 AirTunnel 1 Chilled Water Coil 1 0.90 AirTunnel 1 SA Opening (Supply Air) 0.07
Endwall 2 - Supply Air - SA Opening ESP: 3.00 Total Static Pressure: 5.25
Legend: ESP - External Static Pressure, OSA - Outside Air, EXH - Exhaust Air, RA - Return Air, SA - Supply Air
1. Summary report does not include static pressure of components supplied by others in the field unless otherwise noted.
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A 12-105 - 182T - 36 x 26 x 24 - A2
200.1 Configuration / Quantity
Supply Fan1. Function
22. Quantity 1 Rows x 2 Cols3. Array PentaCube4. Construction Upstream Removable5. Inlet Cone Location
Cell Size 6.Height
7.Width
8.Depth
9.Overall Depth
31.25 1,302 ft / 70.0 °F10.Elev. / Temp.
121 lb11.Motor & Wheel Weight 280 lb12.Fan Cell Weight
013.Redundant 014.Empty 015.Ship Loose Fan (Wheel, Motor and Mounting Base)
200.2 Options
Standard Melamine1. Coplanar Insulation No2. Extended Coplanar FBD63. Back Draft Dampers A100 Curved Cone4. Inlet Cone Type None5. Solid Perimeter Material No6. Discharge Safety Guard Steel7. Cell Material
None8. Cell Finish No9. Insulation Retainer None10. Inlet Attenuation 16Ga Galv11.Blankoff Material None12.Blankoff Finish No13.Removal Rail
200.3 Fan Wheel
HPF-A1001. Wheel Type
122. Diameter
13. Balancing Planes
1054. Width 45965. Max RPM None6. Wheel Finish
200.4 Motor
Toshiba1. Manufacturer
3.5 / 72. HP Each / Total 2-Pole / 3,4803. Poles / RPM 182T / TEAO4. Frame / Casing 460/3/605. Volts / Phase / Hz
2OA003L1ZVS2106. Model
85.57. Efficiency
1.158. Service Factor
Ceramic Bearings9. Shaft Isolation
4.2 / 8.4 Amps10.FLA Each / Total
3.0 %11.Motor HP Safety Factor
200.5 Variable Frequency Drive
Others1. Furnished by
12. Quantity Yaskawa3. Manufacturer
7.54. Horsepower
460/3/605. Voltage
11 / 11 Amps6. Input / Output Amps
74.817. Maximum Hertz
No8. Input Line Reactor None9. VFD Communication
Notes:
1. Standalone VFD, not located in electrical panel.
200.6 Control System
No1. Redundant VFD 60Hz Purchased with VFD2. Bypass Circuit Standard3. Drive No4. Optimization Control By Others5. Control Method
Single Fan Airflow Station6. Flow Monitoring One Fan7. Fans to Monitor Magnesense8. Display
200.7 Notes / Features
1. To view patents and other pending U.S. or Canadian applications visit www.nortekair.com/patents.
2. (1) airflow measurement tap. Cone constant = 969, cone flow differential pressure = 13.45 in.H2O at 3640 CFM per fan.
3. The estimated VFD input watts are based on the motor and VFD efficiency at the selected load and RPM.
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A (Continued) 12-105 - 182T - 36 x 26 x 24 - A2
200.8 Operating Conditions
Operating Condition Usage
(%) CFM
SP (in.H20) Input Adj.
Cell Qty On Off Fail
RPM Hz Fanwheel BHP Each Total
Vel.
(ft/min) Watts FEG
% O.P. FEI
Condition 1 100 5,310 5.23 5.57 2 0 0 4,013 69.2 3.31 6.62 543 6,047 FEG85 0% 1.23 Condition 1 w/ Failed 100 3,640 2.46 3.10 1 0 1 4,339 74.8 3.38 3.38 745 3,127 FEG85 11% 1.01 Condition 1 at 60Hz 100 4,657 4.02 4.29 2 0 0 3,482 60 2.16 4.31 476 3,993 FEG85 0% 1.27
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A (Continued) 12-105 - 182T - 36 x 26 x 24 - A2
200.9 Bare Fan Sound Power with Coplanar Silencer (dB re: 10E-12 watts) Operating Condition 63 125 250 500 1k 2k 4k 8k LwA Lw
Condition 1 Inlet
Outlet
Condition 1 w/ Failed Inlet
Outlet
Condition 1 at 60Hz Inlet
Outlet
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box A (Continued) 12-105 - 182T - 36 x 26 x 24 - A2
200.10 AMCA Statement
Nortek Air Solutions LLC certifies that the HPF-A100 fan wheel shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
The AMCA licensed air and/or sound performance data has been modified for installation,appurtenances or accessories, etc. not included in the certified data. The modified performance is not AMCA licensed but is provided to aid in selection and applications of the product. Performance certified is for installation type
Coils Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
300 Chilled Water Coil 1 : CW1 : Box A 5WC - 24 - 36 x 48 x 10 - 10 AL
300.1 Coil Layout
Right1. Coil Hand Single2. Configuration Straight3. Connection Orientation Red Brass4. Connection Material MPT5. Connection Type
None6. Rack Style None7. Rack Finish 16Ga 304 SS8. Blankoff Material None9. Blankoff Finish
300.2 Construction
11. Quantity
0.41666672. Serpentine
36.000 in3. Fin Height
48.000 in4. Fin Length
105. Rows
106. Fins per Inch
12.00 ft²7. Face Area
1 in8. Stand Height Tube Detail - Primary Surface
Copper9. Material
0.625 x 0.020 in10.O.D. x Wall
1.500 x 1.299 in11.Spacing Smooth12. Internal
0.028 in13.Return Bends
16Ga 304 SS14.Casing None15.Coating
Fin Detail - Secondary Surface Aluminum16.Material
0.008 in17.Thickness Corrugated, Waffle with Straight Edge18.Configuration
Single Bank, Right Hand, 1 per unit 5WC - 24 - 36 x 48 x 10 - 10 AL
Supply / Return Connections Vent and Drain Quantity
Type
MPT
Pipe Size
1.25 in
Material Red Brass
Type
0.125 in FPT
Vent Location Return Connection
Drain Location Supply Connection
300.3 Condition 1
Entering
5,310 ACFM1. Actual Airflow 5,243 SCFM2. Standard Airflow 1,302 ft3. Elevation
76.0 °F4. Entering Air DB
61.3 °F5. Entering Air WB Prop / 30.0 %6. Fluid Type / %
44.0 °F7. Entering Fluid Temp
18.3 GPM8. Fluid Flow Rate
0.00009. Fluid Fouling Internal
Leaving
138.5 MBH10.Total Capacity
136.3 MBH11.Sensible Capacity
442.50 ft/min12.Actual Face Velocity
52.4 °F13.Leaving Air DB
51.8 °F14.Leaving Air WB
0.90 in.H2015.APD
60.0 °F16.Leaving Fluid Temp
2.03 ft/s17.Fluid Velocity
9.84 ft.H2018.Fluid Pressure Drop
Notes:
1. Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
2. Chilled water velocity is below recommended minimum of 2.5 fps
300.4 Notes / Features
1. Manufacturer: Nortek Air Solutions, 5510 SW 29th Street, Oklahoma City, OK 73179
2. Top and bottom casing flange height is 1.000 in.
3. SCFM is corrected for Elevation and EDB.
4. Coils to be pressure tested at 315 PSI
5. Total operating weight is 612 lb.
6. Total fluid volume is 16.6 Gal.
Components Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
500 Filter 1 : FILT1 : Box A
500.1 Pre / Final Size & Quantity
Upstream Face Load1. Loading Galvanized2. Frame Material None3. Frame Finish
(12) C-79-64. Filter Clips 16Ga Galv5. Blankoff / Rack Material None6. Blankoff / Rack Finish
50.063 in W x 40.000 in H7. Bank Size
(4) 20 in x 25 in8. Qty / set & Frame Size 1
9. Qty / set & Frame Size 2 10.Qty / set & Frame Size 3 11.Qty / set & Frame Size 4
500.2 Pre Filter
4.000 in1. Filter Depth MERV 82. Efficiency American Air Filter3. Manufacturer
14. Number of Sets
382.32 ft/min at 5,310 ACFM5. Max Face Velocity PerfectPleat SC6. Model
500.3 Pressure Gage Specifications - Gage 1
Dwyer1. Manufacturer Magnehelic 2002 (0-2" w.c.)2. Model / Range
3. Options
14. Quantity
500.4 Final Filter
4.000 in1. Filter Depth MERV 132. Efficiency American Air Filter3. Manufacturer
14. Number of Sets
382.32 ft/min at 5,310 ACFM5. Max Face Velocity VariCel II6. Model
500.5 Pressure Gage Specifications - Gage 2
Dwyer1. Manufacturer Magnehelic 2002 (0-2" w.c.)2. Model / Range
3. Options
14. Quantity
500.6 Notes / Features
Electrical Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
Note: The FLA and MCA values shown are estimated, see the electrical schematics for the actual values.
Unit Data Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
901 Center of Gravity
Size (Inches) X Y Z
Operating Weight (Pounds) Center of Gravity (Inches)
X Y Z
144.00 64.00 50.00 3,602 70.00 29.00 24.00
901.1 Notes
1. Center of gravity and weights are estimates and subject to change.
2. The center of gravity and weights shown above are based on operating weights and do not include packaging materials.
3. A 5% safety factor has been applied to the operating weights.
4. Corner weights apply to rectangular boxes only.
5. Corner weights are to assist in handling of the unit. Some units are not intended to be supported only at the corners. Contact your
Unit Data Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-4 Sales Order #: -004
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
901 Center of Gravity (Continued)
901.2 Box A
Size (Inches) X Y Z
Shipping Weight (Pounds) Corner Weights (Pounds)
C1 C2 C3 C4
144.00 64.00 50.00 3,455 958 794 772 931
◊ Center of gravity, weight, and corner weights shown are based on shipping weight. Values are estimates and subject to change.
te d
(y yy y- M
M -d
d) : 2
3-
Line Item Summary Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-5 Sales Order #: -005
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
Product Type Factory Finish Design Quantity Cabinet Const. Knockdown Const. Factory SAE Environment Measurement System Wall Thickness
Air Handler None 1 ITF - Integrated Frame None Indoor US Standard 3
Box A Cabinet and Components
* Box Dimensions do not include lifting lugs, electrical panels, pipe connections, door handles, etc. The height dimensions include raised roof seams and sloped roof for outdoor equipment. Box weights do not include roof curbs.
Length (in) Height (in) Width (in) 12" Weight (lb) Weight (lb)
92.50 82.00 109.00 265.96 Cabinet Only 2,050
Exterior Material 16Ga Galv Finish Color N/A Base Structure Steel Tube Base Height 4 in Base Floor Mat. 16Ga Galv Base Insulation Polyurethane Foam
Interior Material 20Ga Galv Insulation HD Fiberglass Roll Base Liner 20Ga Galv
Qty Box A Component Description Weight (lb) 2 3" Thermal Break Factory Door: 24 x 66 Out Swing VW: None 152 1 OPENING: (Outside Air) Rectangle 84.00 x 36.00 1
1 DAMPER: Ruskin CD 60 (Galvanized) - 84.000 in (Blade Direction) x 36.000 in -- Actuator: Furnished by Others, Mounted by Others - Wired by Others 77
1 Pre/Final Filter: 4 Columns x 3 Rows 50 12 Pleated Filter SC 24x24x4 M8 (1 Set) - Face Load 34 12 Box Filter (No Header) 24x24x4 M13 (1 Set) - Face Load 120 12 FRAME, TYPE 8, 16ga GALV W/CLOSED CELL, 24 X 24 92 44 Filter Clip Farr C-79-6 Gal 5 1 Non-Headered Frame, Filter Standoff 24 X 24 1 1 Gage Magnehelic 0-2.0wc Dwyer 2002-ASF 2 1 Gage Magnehelic 0-2.0wc Dwyer 2002-ASF 2 3 5WC-20-21x90x10-10AL, .008F, .020T 16Ga 304 SS, 16Ga 304 SS Blankoff 1,557 1 Drain Pan 30.00" x 103.00" (16Ga 304 SS) 127
Box A Component Totals 2,219 Box A Cabinet & Component Totals 4,269
Box B Cabinet and Components
* Box Dimensions do not include lifting lugs, electrical panels, pipe connections, door handles, etc. The height dimensions include raised roof seams and sloped roof for outdoor equipment. Box weights do not include roof curbs.
Length (in) Height (in) Width (in) 12" Weight (lb) Weight (lb)
77.50 82.00 109.00 293.99 Cabinet Only 1,899
Exterior Material 16Ga Galv Finish Color N/A Base Structure Steel Tube Base Height 4 in Base Floor Mat. 16Ga Galv Base Insulation Polyurethane Foam
Interior Material 20Ga Galv Insulation HD Fiberglass Roll Base Liner 20Ga Galv
Qty Box B Component Description Weight (lb) 1 3" Thermal Break Factory Door: 24 x 60 In Swing VW: 10 in x 10 in Thermal Break 85
1 FANWALL: (SUPPLY) 14-105 - 184T - 34 x 32 x 26 - B3 (PentaCube) -- ELECTRICAL: Standard, One Fan, Magnesense, Wired to: MSP Panel & VFD Only 1,309
6 FANWALL Backdraft Damper, HBD-6, 18"(w) x 18"(h) ID 83 6 Motor Toshiba TEAO 3600rpm 5-7HP 230/460 Insul Brngs Keyed 630 1 VFD Only 9" x 58" x 12" NEMA 1 Indoor 37
Line Item Summary Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-5 Sales Order #: -005
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
Qty Box B Component Description (Cont.) Weight (lb) 1 VFD, Yaskawa, 30 HP (Rep Supplied) 0 1 MSP Panel 30" x 30" x 8" NEMA 4 Indoor / Outdoor 156 1 OPENING: (Supply Air) Rectangle 102.00 x 30.00 0
Box B Component Totals 2,299 Box B Cabinet & Component Totals 4,198
Qty Design Items Weight (lb) 1 Factory Testing: None 0 1 Design Miscellaneous 84
Design Item Totals 84
Weight (lb) Weight (Ea) 8,551
Unit Design Options Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-5 Sales Order #: -005
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
106 Static Pressure Summary
106.1 Condition 1
106.1.1 Supply Air TSP
Tunnel Description APD (in.H20) AirTunnel 1 OA Damper - Damper (Outside Air) 0.02 AirTunnel 1 Filter 1, Pre / Final (Average Pressure Drop) 1.33 AirTunnel 1 Chilled Water Coil 1 1.15 AirTunnel 1 SA Opening (Supply Air) 0.07
Endwall 2 - Supply Air - SA Opening ESP: 4.00 Total Static Pressure: 6.57
Legend: ESP - External Static Pressure, OSA - Outside Air, EXH - Exhaust Air, RA - Return Air, SA - Supply Air
1. Summary report does not include static pressure of components supplied by others in the field unless otherwise noted.
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-5 Sales Order #: -005
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box B 14-105 - 184T - 34 x 32 x 26 - B3
200.1 Configuration / Quantity
Supply Fan1. Function
62. Quantity 2 Rows x 3 Cols3. Array PentaCube4. Construction Upstream Removable5. Inlet Cone Location
Cell Size 6.Height
7.Width
8.Depth
9.Overall Depth
33.25 1,302 ft / 70.0 °F10.Elev. / Temp.
145 lb11.Motor & Wheel Weight 321 lb12.Fan Cell Weight
013.Redundant 014.Empty 015.Ship Loose Fan (Wheel, Motor and Mounting Base)
200.2 Options
Standard Melamine1. Coplanar Insulation No2. Extended Coplanar FBD63. Back Draft Dampers A100 Curved Cone4. Inlet Cone Type None5. Solid Perimeter Material No6. Discharge Safety Guard Steel7. Cell Material
None8. Cell Finish No9. Insulation Retainer None10. Inlet Attenuation 16Ga Galv11.Blankoff Material None12.Blankoff Finish No13.Removal Rail
200.3 Fan Wheel
HPF-A1001. Wheel Type
142. Diameter
13. Balancing Planes
1054. Width 39655. Max RPM None6. Wheel Finish
200.4 Motor
Toshiba1. Manufacturer
5.5 / 332. HP Each / Total 2-Pole / 3,4803. Poles / RPM 184T / TEAO4. Frame / Casing 460/3/605. Volts / Phase / Hz
2OA005L1ZVS2106. Model
87.57. Efficiency
1.158. Service Factor
Ceramic Bearings9. Shaft Isolation
6.3 / 37.8 Amps10.FLA Each / Total
3.0 %11.Motor HP Safety Factor
200.5 Variable Frequency Drive
Others1. Furnished by
12. Quantity Yaskawa3. Manufacturer
304. Horsepower 460/3/605. Voltage
40 / 40 Amps6. Input / Output Amps
68.357. Maximum Hertz
No8. Input Line Reactor None9. VFD Communication
Notes:
1. Standalone VFD, not located in electrical panel.
200.6 Control System
No1. Redundant VFD 60Hz Purchased with VFD2. Bypass Circuit Standard3. Drive No4. Optimization Control By Others5. Control Method
Single Fan Airflow Station6. Flow Monitoring One Fan7. Fans to Monitor Magnesense8. Display
200.7 Notes / Features
1. To view patents and other pending U.S. or Canadian applications visit www.nortekair.com/patents.
2. (1) airflow measurement tap. Cone constant = 1153, cone flow differential pressure = 9.50 in.H2O at 3639 CFM per fan.
3. The estimated VFD input watts are based on the motor and VFD efficiency at the selected load and RPM.
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-5 Sales Order #: -005
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box B (Continued) 14-105 - 184T - 34 x 32 x 26 - B3
200.8 Operating Conditions
Operating Condition Usage
(%) CFM
SP (in.H20) Input Adj.
Cell Qty On Off Fail
RPM Hz Fanwheel BHP Each Total
Vel.
(ft/min) Watts FEG
% O.P. FEI
Condition 1 100 19,425 6.57 6.90 6 0 0 3,891 67.1 4.94 29.61 555 26,150 FEG85 0% 1.19 Condition 1 w/ Failed 100 18,197 5.77 6.20 5 0 1 3,959 68.3 5.11 25.55 624 22,538 FEG85 0% 1.17 Condition 1 at 60Hz 100 17,582 5.40 5.65 6 0 0 3,482 60 3.53 21.17 502 18,827 FEG85 0% 1.20
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-5 Sales Order #: -005
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box B (Continued) 14-105 - 184T - 34 x 32 x 26 - B3
200.9 Bare Fan Sound Power with Coplanar Silencer (dB re: 10E-12 watts) Operating Condition 63 125 250 500 1k 2k 4k 8k LwA Lw
Condition 1 Inlet
Outlet
Condition 1 w/ Failed Inlet
Outlet
Condition 1 at 60Hz Inlet
Outlet
Fans Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-5 Sales Order #: -005
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
200 FANWALL 1 (Supply) : FWT1 : Box B (Continued) 14-105 - 184T - 34 x 32 x 26 - B3
200.10 AMCA Statement
Nortek Air Solutions LLC certifies that the HPF-A100 fan wheel shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
The AMCA licensed air and/or sound performance data has been modified for installation,appurtenances or accessories, etc. not included in the certified data. The modified performance is not AMCA licensed but is provided to aid in selection and applications of the product. Performance certified is for installation type
Coils Project Name: Tinker Air Force Base-BACH
Unit Tag: AHU-5 Sales Order #: -005
Date/Revision: 2023-12-17 / Revision Error 106 N Industrial Blvd. Okarche, Ok 73762
(405) 817-9700 FAX (405) 263-4980
This Document is confidential, copyrighted and property of Nortek Air Solutions LLC.
Design Assistant
9.1.2 / 2.0.2.3
300 Chilled Water Coil 1 : CW1 : Box A 5WC - 20 - 21 x 90 x 10 - 10 AL
300.1 Coil Layout
Right1. Coil Hand Single2. Configuration Straight3. Connection Orientation Red Brass4. Connection Material MPT5. Connection Type
None6. Rack Style None7. Rack Finish 16Ga 304 SS8. Blankoff Material None9. Blankoff Finish
300.2 Construction
31. Quantity
0.52. Serpentine
21.000 in3. Fin Height
90.000 in4. Fin Length
105. Rows
106. Fins per Inch
39.38 ft²7. Face Area
1 in8. Stand Height Tube Detail - Primary Surface
Copper9. Material
0.625 x 0.020 in10.O.D. x Wall
1.500 x 1.299 in11.Spacing Smooth12. Internal
0.028 in13.Return Bends
16Ga 304 SS14.Casing None15.Coating
Fin Detail - Secondary Surface Aluminum16.Material
0.008 in17.Thickness Corrugated, Waffle with Straight Edge18.Configuration
Single Bank, Right Hand, 3 per unit 5WC - 20 - 21 x 90 x 10 - 10 AL
Supply / Return Connections Vent and Drain Quantity
Type
MPT
Pipe Size
1.5 in
Material Red Brass
Type
0.125 in FPT
Vent Location Return Connection
Drain Location Supply Connection
300.3 Condition 1
Entering
19,425 ACFM1. Actual Airflow 19,180 SCFM2. Standard Airflow 1,302 ft3. Elevation
76.0 °F4. Entering Air DB
61.3 °F5. Entering Air WB Prop / 30.0 %6. Fluid Type / %
44.0 °F7. Entering Fluid Temp
79.6 GPM8. Fluid Flow Rate
0.00009. Fluid Fouling Internal
Leaving
602.3 MBH10.Total Capacity
548.3 MBH11.Sensible Capacity
493.33 ft/min12.Actual Face Velocity
50.0 °F13.Leaving Air DB
49.9 °F14.Leaving Air WB
1.15 in.H2015.APD
60.0 °F16.Leaving Fluid Temp
4.20 ft/s17.Fluid Velocity
43.26 ft.H2018.Fluid Pressure Drop
Notes:
1. Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
300.4 Notes / Features
1. Manufacturer: Nortek Air Solutions, 5510 SW 29th Street, Oklahoma City, OK 73179
2. Top and bottom casing flange height is 1.000 in.
3. SCFM…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .