SECTION 33 13 00 DISINFECTION

View the file

Other files

File Type Posted
W911S6-17-B-0001-0001.pdf PDF
Revised_Technical_Exhibit_A_Through_E__21_March_2017.xlsx XLSX spreadsheet
Technical_Exhibit_A_Through_E__11NOV16.xlsx XLSX spreadsheet
Site_visit_sign_in_roster_(2).pdf PDF
W911S6-1-B-0001_Site_Visit_Slides_DPG_Road_Maintenance_13_Mar_2017.pptx PPTX presentation
SECTION_01_74_13_Progress_Cleaning.docx DOCX document
Section_02_41_13.13_Pavement_Removal.docx DOCX document
Technical_Exhibit_A_Through_E__11NOV16.xlsx XLSX spreadsheet
Section_32_12_36.14_Chip_Seal_Coat.docx DOCX document
SECTION_31_37_00_Riprap_or_rock_lining.docx DOCX document
SECTION_01_71_16_Acceptance.docx DOCX document
Section_33_05_13.13_Utility_Grade_Adjustment.docx DOCX document
Section_32_12_36.15_Micro-Surface_Seal.docx DOCX document
SECTION_33_11_00_Water_Distribution_and_Transmission.docx DOCX document
SECTION_33_08_00_Commissioning_of_Water_Utilities.docx DOCX document
Section_32_12_15_HMA_for_Airfields.docx DOCX document
Section_32_11_23_Untreated_Aggregate_Base_Course.docx DOCX document
Section_33_11_00.07_Polyvinyl_Chloride_Pipe.docx DOCX document
SECTION_32_01_16_Recycled_Asphalt_Paving.docx DOCX document
SECTION_05_05_10_Metal_Galvanizing.docx DOCX document
SECTION_32_13_73_Concrete_Paving_Joint_Sealants.docx DOCX document
Section_01_55_26_Traffic_Control.docx DOCX document
Section_01_78_39_Record_Documents.docx DOCX document
Section_01_71_23.16_Construction_Surveying.docx DOCX document
SECTION_05_12_00_Structural_Steel.docx DOCX document
SECTION_03_61_00_Cementitious_Grouting.docx DOCX document
SECTION_32_12_16.19_Cold_Mix_Asphalt.docx DOCX document
SECTION_33_31_00_Sanitary_Sewerage_Systems.docx DOCX document
Section_32_12_16_Hot_Mix_Asphalt_for_Roads.docx DOCX document
Section_32_17_23_Pavement_Markings.docx DOCX document
Section_32_31_13_Chain_Link_Fence.docx DOCX document
SECTION_03_39_00_Concrete_Curing.docx DOCX document
Section_01_77_00_Closeout_Procedures.docx DOCX document
SECTION_03_11_00_Concrete_Forming.docx DOCX document
SECTION_31_23_23.23_Compaction.docx DOCX document
Section_32_11_28_Cold_Recycled_Asphalt_Base.docx DOCX document
Section_31_05_19.13_Geotextiles.doc DOC document
SECTION_33_11_11_Relocate_Water_Meters_and_Fire_Hydrants.docx DOCX document
SECTION_03_20_00_Concrete_Reinforcing.docx DOCX document
Section_32_01_13.61_Slurry_Seal.docx DOCX document
SECTION_05_05_23_Bolts_Nuts_and_Accessories.docx DOCX document
SECTION_03_40_00_Precast_Concrete.docx DOCX document
Section_31_11_00_Clearing_and_Grubbing.docx DOCX document
Section_32_12_19.19_Open-Graded_Surface_Course.docx DOCX document
SECTION_31_05_19.19_Geogrids_Geocomposites.docx DOCX document
SECTION_05_56_00_Metal_Castings.docx DOCX document
SECTION_01_11_00_SUMMARY_of_WORK.docx DOCX document
Section_34_71_13_Vehicle_Barriers.docx DOCX document
SECTION_32_12_43_Porous_Paving.docx DOCX document
SECTION_01_66_00_Product_Storage_and_Protection.docx DOCX document
Show 40 more

Latest 50 of 87 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SECTION 33 13 00

SECTION 33 13 00

DISINFECTION

PART 1GENERAL
1.1SECTION INCLUDES
A.Disinfection of potable water system.
B.Test and report results.
1.2REFERENCES
A.AWWA B300: AWWA Standard for Hypochlorites.
B.AWWA B301: AWWA Standard for Liquid Chlorine.
C.AWWA C651: AWWA Standard for Disinfecting Water Mains.
D.State of Utah: Public Drinking Water Regulations, Part 2, Section 12.
1.3DEFINITIONS
A.Disinfectant Residual: The quantity of disinfectant in treated water.
B.ppm: Parts per million.
1.4SUBMITTALS
A.Contractor's evidence of experience in disinfection.
B.Bacteriological laboratory's evidence of certification.
C.Disinfection Report: 3 copies containing:
1.Date issued.
2.Project name and location.
3.Treatment contractor's name, address and phone number.
4.Type and form of disinfectant used.
5.Time and date of disinfectant injection started.
6.Time and date of disinfectant injection completed.
7.Test locations.
8.Initial and follow-up disinfectant residuals in ppm for each outlet tested.
9.Time and date of flushing start.
10.Time and date of flushing completion.
11.Disinfectant residual after flushing in ppm for each outlet tested.
12.Flush water disposal location and acceptance by local agency.
D.Bacteriological Report: 3 copies including:
1.Date issued.
2.Project name and location.
3.Laboratory's name, certification number, address, and phone number.
4.Time and date of water Sample collection.
5.Name of person collecting Samples.
6.Test locations.
7.Time and date of laboratory test start.
8.Coliform bacteria test results for each outlet tested.
9.Certification that water conforms or fails to conform to bacterial standards of State of Utah public drinking water regulations.
10.Bacteriologist's signature.
1.5QUALITY ASSURANCE
A.Bacteriological Laboratory: Certified by State of Utah.
1.6PRODUCT HANDLING
A.Store and protect disinfectant in accordance with manufacturer's recommendations to protect against damage or contamination. Do not use unsuitable disinfectant.
B.Follow all instruction labeling for safe handling and storage of disinfectant materials.
1.7REGULATORY REQUIREMENTS
A.Conform to State of Utah public drinking water regulations.
PART 2PRODUCTS
2.1DISINFECTANT
A.Liquid Chlorine: AWWA B301 with chlorine 99.5 percent pure by volume.
B.Sodium Hypochlorite: AWWA B300 with not less than 100 grams per liter available chlorine.
C.Calcium Hypochlorite: AWWA B300 with 65 to 70 percent available chlorine by weight in granular form.
D.Powder, tablet, or gas according to manufacturer's specification.
2.2ALKALI
A.Caustic Soda or Soda Ash.
2.3ACID
A.Hydrochloric (Muriatic) type.
PART 3EXECUTION
3.1PREPARATION
A.Provide necessary signs, barricades, and notices to prevent accidental exposure to disinfecting materials, consuming disinfecting water, or disturbing the system being disinfected.
B.Make sure the potable water system is complete, clean, and that the system to be disinfected is not connected to the existing system.
3.2DISINFECTION OF WATER LINES
A.Use one method defined under AWWA C651 that is acceptable to COR.
B.After pressure testing per Section 33 08 00, flush system through hydrants or if a hydrant does not exist, install a tap of sufficient size to provide 2.5 feet per second flushing velocity in the line.
C.Starting at outlet closest to water source, bleed water from each outlet until chlorine residual reaches outlet. Repeat process at each outlet throughout system.
D.Collect a bacteriological water sample at end of line to be tested. If sample fails bacteriological test, flush system and retest. Continue flushing and retesting until a good sample is obtained.
E.If flushing does not produce a passing bacteriological test disperse disinfectant throughout system to obtain 10 to 25 ppm of free chlorine residual.
F.Flush the chlorinated water from the main until chlorine measurements show the concentration in the water leaving the main is no higher than that generally prevailing in the system or is acceptable for domestic use.
G.After a negative bacteriological sample is obtained, let the system relax for 24 hours. Flush and collect a subsequent bacteriological sample for testing. If the subsequent test is negative then water line is acceptable.
3.3FIELD QUALITY CONTROL
A.Bacteriological Test:
1.Collect Samples for testing no sooner than 16 hours after system flushing.
2.Analyze water samples per State of Utah requirements.
3.If bacteriological test proves water quality to be unacceptable, repeat system treatment.
4.Do not place water systems into service until a negative bacteriological test is made. Provide a copy of the negative bacteriological test to COR.
B.Disposal of Disinfectant:
1.Legally dispose of disinfecting water and ensure no chlorine buildup or damage to the environment.

END OF SECTION

DISINFECTION Page 1