T-001 Add03.pdf

PDF 130 KB Posted

Attached to
F-35 Alter Hangar 406 Federal contract opportunity
Solicitation number
W50S9F-21-B-0001
Issued by
Department of the Army National Guard

About this file

This solicitation is seeking bids for construction services to alter an F-35 aircraft hangar at Dane County Regional Airport - Truax Field in Madison, Wisconsin. Key details include demolishing approximately 19,913 square feet of existing hangar shop space and modifying another 19,803 square feet of hangar space to accommodate F-35 aircraft. Work will include mechanical, plumbing and electrical systems installation; communications, security, and technology cabling; and fire suppression system modifications. Two optional items are also included. The bid due date is March 8, 2021. Award will be made to the responsive and responsible lowest bidder. Interested contractors should attend the pre-bid conference on February 16, 2021 and register on SAM.gov to access solicitation documents through beta.SAM.gov. The North American Industry Classification code is 236220 and contract performance period is 365 days.

View the file

Other files for this federal contract opportunity

Other files attached to F-35 Alter Hangar 406, newest first.
File Type Posted
Abstract of Offers with Hubzone Preference.pdf PDF
W50S9F21B00010006.pdf PDF
406 Questions and Answers_113-141.pdf PDF
F-102_Add03.pdf PDF
E-101_Add03.pdf PDF
32 13 14.13_Add03.pdf PDF
21 13 18.00 10_Add03.pdf PDF
W50S9F21B00010005.pdf PDF
C-121_Add03.pdf PDF
C-504_Add03.pdf PDF
34 71 13.19_Add03.pdf PDF
01 45 00.00 10_Add03.pdf PDF
22 31 00_Add03.pdf PDF
T-121 Add03.pdf PDF
W50S9F21B00010004.pdf PDF
C-141_Add02.pdf PDF
G-011_Add02.pdf PDF
AD101_Add02.pdf PDF
C-101_Add02.pdf PDF
E-501_Add02.pdf PDF
SD111_Add02.pdf PDF
A-201_Add02.pdf PDF
10 28 13_Add02.pdf PDF
A-311_Add02.pdf PDF
Asbestos and Lead Inspection.pdf PDF
Repair Roofs 406 Warranty Cert.pdf PDF
A-401_Add02.pdf PDF
04 20 00_Add02.pdf PDF
A-501_Add02.pdf PDF
A-601_Add02.pdf PDF
02 83 00_Add02.pdf PDF
01 14 00_Add02.pdf PDF
01 11 00_Add02.pdf PDF
W50S9F21B00010003.pdf PDF
10 22 39_Add01.R1.pdf PDF
07 27 26_Add01.R1.pdf PDF
A-131_Add01.R1.pdf PDF
W50S9F21B00010002.pdf PDF
B.07.406 Site Visit Sign In 22Feb21.pdf PDF
B.07.406 Site Visit Sign In 19Feb21.pdf PDF
Pre-Bid Slides - F-35 406.pptx PPTX presentation
W50S9F21B00010001.pdf PDF
W50S9F-21-B-0001.pdf PDF
ATTACHMENT 6-Justification and Approval Monaco.pdf PDF
ATTACHMENT 8-406 Submittal Log.xlsx XLSX spreadsheet
ATTACHMENT 9-SFS Form 12.xls XLS spreadsheet
ATTACHMENT 10-PRE-BID CONFERENCE AND SITE VISIT INSTRUCTIONS.pdf PDF
ATTACHMENT 4-Justification and Approval Advantor.pdf PDF
ATTACHMENT 1-Truax F-35 B406 XGFG182008 Specs Vol 1 of 2 Dated 31 July 2020.pdf PDF
ATTACHMENT 5-Justification and Approval Andover.pdf PDF
Show all 50

F-35 Alter Hangar 406 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BET

PB

PP

COM

FO

TGB

TSE

A

S

M

N

C

E

ACS

ACP

IDS

PS

SP

S

V

S

S

TECHNOLOGY SYMBOLS

TELEPHONE SERVICE ENTRANCE PROTECTION DEVICE

BUILDING ENTRANCE TERMINAL

COMMUNICATIONS PUNCH BLOCK

COMMUNICATIONS PATCH PANEL

COMMUNICATIONS CABINET

WALL-MOUNTED FIBER OPTIC CABINET

TELECOMMUNICATIONS GROUNDING BUS BAR

2-POST EQUIPMENT RACK

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUS BAR

CABLETRAY

J JUNCTION BOX

CARDREADER

SECURITY SYSTEM SYMBOLS

REX

CARDREADER-PINPAD

KEY PAD

MOTION DETECTOR

STATUS SENSOR / MONITOR

AUDIBLE ALARM

ELECTRIC STRIKE

ACCESS CONTROL SYSTEM

ACCESS CONTROL PANEL

REQUEST TO EXIT

KP

INTRUSION DETECTION SYSTEM

1. THE INFORMATION SHOWN IS BASED ON EXISTING DRAWINGS AND SITE

OBSERVATIONS TO ASSIST THE CONTRACTOR IN BIDDING. THE CONTRACTOR

SHOULD VISIT THE SITE TO VERIFY EXISTING CONDITIONS. THE TECHNOLOGY

SYSTEMS DRAWINGS INDICATE EXISTING TECHNOLOGY SYSTEMS ITEMS TO

BE REMOVED. THE DRAWINGS ARE INTENDED TO INDICATE THE SCOPE OF

WORK REQUIRED AND DO NOT INDICATE EVERY DEVICE, BOX, CONDUIT,

WIRE OR CABLE THAT MUST BE REMOVED.

2. DASHED WALLS ON THE FLOOR PLANS INDICATE EXISTING WALLS BEING

DEMOLISHED. REFER TO THE ARCHITECTURAL DEMOLITION PLANS FOR THE

EXACT EXTENT OF WORK REQUIRED BY THIS PROJECT. REMOVE ALL

DEVICES ON DASHED WALLS NOT SHOWN ON THE CONTRACT DRAWINGS.

REFER TO DEMOLITION DRAWINGS OF OTHER TRADES. WHERE CONTROL

PANELS AND APPURTENANCES THAT HAVE TECHNOLOGY SYSTEMS

CONNECTIONS ARE BEING REMOVED, INCLUDE DISCONNECTION AND

REMOVAL OF ALL ASSOCIATED CONDUIT, WIRING AND CABLING.

3. TECHNOLOGY SYSTEMS ITEMS (E.G. TECHNOLOGY OUTLETS, SECURITY

SYSTEMS DEVICES, AUDIO DEVICES) THAT ARE REMOVED AND NOT

RELOCATED SHALL REMAIN THE PROPERTY OF THE OWNER. DISPOSE OF

MATERIAL THE OWNER DOES NOT WANT TO REUSE OR RETAIN FOR

MAINTENANCE PURPOSES.

4. OBTAIN APPROVAL FROM THE OWNER BEFORE TURNING OFF POWER TO

TECHNOLOGY SYSTEMS EQUIPMENT OR DEVICES. COORDINATE ALL

OUTAGES WITH THE OWNER. CONDUIT CONCEALED IN WALL CONSTRUCTION

MAY BE ABANDONED IN PLACE IF NOT AFFECTED BY OTHER CONSTRUCTION.

5. PROVIDE A BLANK COVERPLATE FOR ALL BOXES IN EXISTING MASONRY

WALLS THAT ARE TO REMAIN IN PLACE. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS ASSOCIATED WITH TYPE AND ATTACHMENT.

6. REMOVE ALL CONDUIT WHERE WALLS ARE BEING REMOVED. WHERE

CONDUIT IS IN THE CONCRETE SLAB, CUT OFF FLUSH, PULL OUT WIRE OR

CABLE AND PLUG. WHERE CONDUIT IS RUN EXPOSED, ALL ASSOCIATED

CLAMPS, SUPPORTS, HANGERS, ETC. SHALL ALSO BE REMOVED.

7. COORDINATE ALL WORK WITH OTHER CONTRACTORS AT THE JOB SITE

BEFORE REMOVING EXISTING TECHNOLOGY SYSTEMS ITEMS AND

INSTALLING NEW ITEMS.

8. EXISTING CONDUIT IN GOOD CONDITION, MAY BE REUSED IN PLACE.

RELOCATED EXISTING CONDUIT SHALL NOT BE ALLOWED.

DEMOLITION GENERAL NOTES

GENERAL NOTES

1. PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT REQUIRED TO INSTALL

COMPLETE TECHNOLOGY SYSTEMS AS INDICATED ON THESE DRAWINGS

AND AS SPECIFIED.

2. MOUNT ALL TECHNOLOGY OUTLETS AT HEIGHTS ABOVE FINISHED FLOOR AS

SHOWN IN THE TECHNOLOGY OUTLET SCHEDULE U.N.O.

3. SEE ELECTRICAL SPECIFICATIONS FOR LOCATIONS WHERE GRS CONDUIT

SHALL BE USED, OR WHERE IMC, EMT, OR PVC CONDUIT MAY BE USED.

4. OFFSET BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS A

MINIMUM OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE-RATED

WALLS SHALL BE OFFSET A MINIMUM OF 24" HORIZONTALLY. 'THRU-THE-

WALL' BOXES SHALL NOT BE ALLOWED WITHOUT THE WRITTEN APPROVAL

OF THE ARCHITECT/ENGINEER.

5. VERIFY ALL EQUIPMENT SIZES AND POWER REQUIREMENTS FOR EQUIPMENT

SUPPLIED BY OTHERS PRIOR TO INSTALLATION OF CONDUIT.

6. MOUNT TECHNOLOGY SYSTEMS EQUIPMENT/DEVICES SO AS TO ALLOW

ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF

TECHNOLOGY SYSTEMS EQUIPMENT/DEVICES ON EQUIPMENT SUPPLIED BY

ANOTHER CONTRACTOR SHALL BE COORDINATED WITH AND APPROVED BY

THAT CONTRACTOR IN ADVANCE OF INSTALLATION.

7. CONCEAL ALL ELECTRICAL CONDUITS AND JUNCTION BOXES. COORDINATE

WITH THE OTHER TRADES AND USE CHASES AND CEILING SPACES

PROVIDED. WHERE BOXES AND CONDUIT ARE NOTED TO BE INSTALLED

EXPOSED, THEY SHALL BE PAINTED TO MATCH THE SURFACE.

8. PROVIDE ALL OPENINGS REQUIRED IN WALLS. REPAIR ALL OPENINGS TO

MATCH EXISTING USING A QUALIFIED CONTRACTOR AT THE EXPENSE OF

THIS CONTRACTOR. GROUT OR SEAL ALL CONDUITS THROUGH WALLS INTO

OPENINGS. FIRESTOP ALL PENETRATIONS THROUGH FLOORS AND FIRE-

RATED WALLS IN A MANNER THAT MAINTAINS THE RATING OF THE FLOOR OR

WALL PENETRATED.

9. TERMINATE ALL TELEPHONE AND DATA JACKS WITH ALL 4 PAIRS TO ALLOW

FOR INTERCHANGEABILITY.

10. INSTALL ALL TELEPHONE AND DATA CABLES IN CONDUIT OR CABLE TRAY.

11. PROVIDE PLASTIC OR NYLON BUSHINGS IN ALL CONDUIT STUBS PRIOR TO

THE INSTALLATION OF CABLES.

LINE TYPE KEY

EXISTING TO BE REMOVED BY THIS

CONTRACTOR (DARK DASHED LINE)

EXISTING TO REMAIN WORK

(THIN SOLID LINE)

NEW WORK BY THIS CONTRACTOR

(DARK SOLID LINE)

NEW WORK UNDER FLOOR BY

THIS CONTRACTOR

AUDIO VISUAL SYMBOLS

LOUDSPEAKER (HORN TYPE)

CEILING-MOUNTED SPEAKER

WALL-MOUNTED SPEAKER

VOLUME CONTROL

SOUND AND PAGING CABINET

PAGING STATION

VIDEO SURVEILLANCE SYMBOLS

F

F

F

F

MOUNTING MODIFIERS:

WALL MOUNT

F APPROXIMATE VIEWING DIRECTION

CAMERA TYPE:

C: DETENTION CORNER

F: FIXED

M: MULTISENSOR

O: FISHEYE

P: PAN-TILT-ZOOM

V: VARIFOCAL

XX

HORIZONTAL VIEWING ANGLE

CAMERA ID

POLE MOUNT

EXTERIOR CORNER MOUNT

DETENTION CORNER MOUNT

VIDEO SURVEILLANCE CAMERA:

CEILING MOUNTF

GENERAL SYMBOLS

9.xxx

T-40X

T-40X

DETAIL NUMBER / SHEET NUMBERx/T-xxx

A

T-40X 1

KEYED NOTE, USED TO DESCRIBE ADDITIONAL

INFORMATION OF WORK REQUIRED, SPECIFIC TO

THE SHEET AND/OR DEAIL IT IS SHOWN WITH

IT ROOM

116 ROOM NAME AND NUMBER

DOOR IDENTIFICATION

BUILDING SECTION

ENLARGED PLAN

INTERIOR ELEVATION

TECHNOLOGY OUTLET SCHEDULE NOTES:

1. REFER TO DIVISION 26 SPECIFICATIONS FOR BOX AND CONDUIT SPECIFICATIONS AND EXECUTION REQUIREMENTS.

SINGLE-PORT TECHNOLOGY OUTLET FOR WALL-MOUNTED PHONE:

- (1) 1" CONDUIT

- (1) 4" SQUARE x 1-1/2" DEEP BACKBOX WITH SINGLE GANG VERTICAL TRIM RING

- (1) STAINLESS STEEL FACEPLATE WITH CATEGORY 6 JACK AND PHONE LUGS

- (1) CATEGORY 6 CABLE

45" AFF TO CENTER

OF BOX U.N.O.

TECHNOLOGY OUTLET SCHEDULE

SYMBOL MOUNTINGDESCRIPTION COMMENTS

TWO-PORT TECHNOLOGY OUTLET:

- (1) 1" CONDUIT

- (1) 4-11/16" SQUARE x 2-1/8" DEEP BACKBOX WITH SINGLE GANG TRIM RING

- (1) SINGLE-GANG, TWO-PORT FACEPLATE

- (2) CATEGORY 6 JACKS

- (2) CATEGORY 6 CABLES

18" AFF TO CENTER

OF BOX U.N.O.

FOUR-PORT TECHNOLOGY OUTLET:

- (1) 1" CONDUIT

- (1) 4-11/16" SQUARE x 2-1/8" DEEP BACKBOX WITH SINGLE GANG TRIM RING

- (1) SINGLE-GANG, FOUR-PORT FACEPLATE

- (4) CATEGORY 6 JACKS

- (4) CATEGORY 6 CABLES

18" AFF TO CENTER

OF BOX U.N.O.

HDMI TECHNOLOGY OUTLET:

- (1) 1 1/4" CONDUIT

- (2) 4-11/16" SQUARE x 2-1/8" DEEP BACKBOX WITH SINGLE GANG TRIM RING

- (2) SINGLE-GANG, HDMI FACEPLATE COUPLER.

HD

TWO-PORT CEILING-MOUNTED TECHNOLOGY OUTLET:

- (1) 1" CONDUIT

- (1) 4-11/16" SQUARE x 2-1/8" DEEP BACKBOX WITH SINGLE GANG TRIM RING

- (1) SINGLE-GANG, TWO-PORT FACEPLATE

- (2) CATEGORY 6 JACKS

- (2) CATEGORY 6 CABLES

FLUSH WITH LAY-IN

CEILING

OWNER TO

PROVIDE HDMI

CABLE BETWEEN

FACEPLATES.

FIBER OPTIC TECHNOLOGY OUTLET:

- (1) 1 1/4" CONDUIT

- (2) 4-11/16" SQUARE x 2-1/8" DEEP BACKBOX WITH SINGLE GANG TRIM RING

- (6) SINGLE-MODE FIBER OPTIC STRANDS

- (3) SM LC DUPLEX COUPLER

SEE SHEET T-501

FOR OUTLET

LAYOUT.

FO

W

TELEVISION TELECOMMUNICATIONS OUTLET:

- (1) 1" CONDUIT STUB

- (1) 4-11/16" SQUARE x 2-1/8" DEEP BACKBOX WITH SINGLE GANG TRIM RING

- (1) SINGLE-GANG, TWO-PORT FACEPLATE

- (1) CATEGORY 6 JACK

- (1) CATEGORY 6 CABLE

- (1) F-F BULKHEAD CONNECTOR COUPLER

- (1) RG-6 CABLE

TV

12" ABOVE

HORIZONTAL

CENTERLINE OF

TELEVISION UNO.

- OUTLET

CONFIGURATION

ASSUMES TV SET-

TOP BOX IS

LOCATED AT

DISPLAY.

TECHNOLOGY SCOPE BID MATRIX

ITEM

FLOOR BOX ROUGH-IN, INCLUDING FLOOR BOXES AND CONDUITS

CABLE TRAY, INCLUDING ALL REQUIRED SUPPORT HARDWARE AND FITTINGS

EQUIPMENT ROOM FITTINGS (PER DIV 27 SPECIFICATIONS)

EQUIPMENT ROOM POWER RECEPTACLES

GROUNDING OF CABLE TRAY AND EQUIPMENT ROOM COMPONENTS

BACKBONE CABLING, TERMINATION COMPONENTS (e.g. WALL-FIELDS), TERMINATION, TESTING AND LABELING

TECHNOLOGY SYSTEMS ROUGH-IN, INCLUDING BACKBOXES, TRIM RINGS, CONDUIT AND SLEEVES

UNDERGROUND CONDUITS IN/OUT OF BUILDING, INCLUDING ASSOCIATED HANDHOLES

PATCH PANELS

TELECOMMUNICATIONS OUTLET (TO) FACEPLATES AND JACKS

HORIZONTAL CABLING, TERMINATIONS, TESTING AND LABELING

GROUND BARS (TMGB, TGB) AND ELECTRICAL SERVICE BONDING

FLOOR BOX AND TELECOMMUNICATION OUTLET (TO) ASSOCIATED POWER RECEPTACLES

SHOWN ON CLIN

T-SERIES

EQUIPMENT ROOM PLYWOOD WALL COVERINGS

ROOF PENETRATION CONDUITS

INFORMATION DISPLAY SYSTEM AND TV OUTLETS, MOUNTS, DISPLAYS AND CABLING

PA SYSTEM ROUGH-IN, INCLUDING BACKBOXES, TRIM RINGS AND CONDUIT

PA SYSTEM COMPONENTS (HEAD-END, MICROPHONES, SPEAKERS/HORNS, VOLUME CONTROLS) AND CABLING

INFORMATION DISPLAY SYSTEM AND TV ROUGH-IN, INCLUDING BACKBOXES, TRIM RINGS AND CONDUIT

ACS FIELD DEVICES (e.g. CARD READERS, STATUS SENSORS, REX) AND CABLING

SECURITY SYSTEMS (ACS, VSS) ROUGH-IN, INCLUDING BACKBOXES, TRIM RINGS AND CONDUIT

ACS DOOR HARDWARE INCLUDING ELECTRIC STRIKES, MAGNETIC LOCKS AND ASSOCIATED POWER SUPPLIES

VSS HEAD-END, CAMERAS, MOUNTS AND CABLING

E AND T-SERIES

T-SERIES

T-SERIES

T-SERIES

E-SERIES (PWR)

T-SERIES

T-SERIES

T-SERIES

T-SERIES

T-SERIES

T-SERIES

E-SERIES (PWR)

T-SERIES

T-SERIES

T-SERIES

T-SERIES

T-SERIES

T-SERIES

T-SERIES

T-SERIES

T-SERIES

T-SERIES

CONTRACT LINE ITEM NUMBER:

CLIN 0001 = BASE BID

CLIN 0002 = COMMUNICATIONS CABLING AND EQUIPMENT

CLIN 0003 = SECURITY CABLING AND EQUIPMENT

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

/8

/2

:0

:1

P M

C R e v it L o c a l\

-1

.0

-E

-C e n tr a l-ry a n .k e n n y A

C

L

.r v t

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

F -3

A L T

E R

B U

IL

D

IN

G

T-001

NOTES, SYMBOLS &

ABBREVIATIONS

XGFG182008ANG NO.:

3141300-190289.01

RKK

JRM

July 31, 2020

MJR

TECHSYS ABBREVIATIONS

& AND

3R NEMA 3R RATED

4X NEMA 4X RATED

@ AT

A/E ARCHITECT / ENGINEER

ACS ACCESS CONTROL SYSTEM

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISH GRADE

ALT ALTERNATE

ANT ANTENNA

AP (WIRELESS) ACCESS POINT

AV AUDIO VISUAL

BET BUILDING ENTRANCE TERMINAL

BID BAGGAGE INFORMATION DISPLAY

BLDG BUILDING

C CONDUIT

CAB CABINET

CATV COMMUNITY ANTENNA TELEVISION

CL CENTERLINE

CLG CEILING

CLIN CONTRACT LINE ITEM NUMBER

COAX COAXIAL

COMM COMMUNICATIONS

DO DOOR OPERATOR

DSS DIGITAL SATELLITE SERVICE

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EMT ELECTRICAL METALLIC TUBING

ETR EXISTING TO REMAIN

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FID FLIGHT INFORMATION DISPLAY

FO FIBER OPTIC

FPD FLAT-PANEL DISPLAY

GC GENERAL CONTRACTOR

GID GATE INFORMATION DISPLAY

GND GROUND

GRC GALVANIZED RIGID CONDUIT

GRS GALVANIZED RIGID STEEL

HH HAND HOLE

HPC HIGH PAIR COUNT

HVAC HEATING, VENTILATION, AIR CONDITIONING

IDF INTERMEDIATE DISTRIBUTION FRAME

IDS INTRUSION DETECTION SYSTEM

IMC INTERMEDIATE METALLIC CONDUIT

IT INFORMATION TECHNOLOGY

ITS INFORMATION TRANSPORT SYSTEMS

JB JUNCTION BOX

MAX MAXIMUM

MDF MAIN DISTRIBUTION FRAME

MH MAN HOLE

MIN MINIMUM

MMFO MULTIMODE FIBER OPTIC

MNS MASS NOTIFICATION SYSTEM

MON MONITOR

MTD MOUNTED

NIC NOT IN CONTRACT

NTS NOT TO SCALE

NTWK NETWORK (DATA)

OC ON CENTER

PA PUBLIC ADDRESS

PROJ PROJECTOR

PTZ PAN - TILT - ZOOM

PVC POLYVINYL CHLORIDE

RCV RECEIVER

REQ'D REQUIRED

SCHED SCHEDULE

SE SERVICE ENTRANCE

SMFO SINGLEMODE FIBER OPTIC

SS STAINLESS STEEL

SYS SYSTEM

TBR TO BE REMOVED

TC TECHNOLOGY CONTRACTOR

TGB TELECOMMUNICATIONS GROUNDING BUSBAR

TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

TO TELECOMMUNICATIONS OUTLET

TSE TELEPHONE SERVICE EQUIPMENT

TV TELEVISION

TYP TYPICAL

UF UNDER FLOOR

UG UNDERGOUND

UNO UNLESS NOTED OTHERWISE

UTP UNSHIELDED TWISTED PAIR

VSS VIDEO SURVEILLANCE SYSTEM

WL WET LOCATION LISTED

WP WEATHERPROOF

WS WORKSTATION

07/31/20 TYPE B3 FINAL

3 03/08/21 ADDENDUM - 03

Sheets
T-001 - NOTES, SYMBOLS & ABBREVIATIONS

File details come from the government source that posted it. Updated .