F-001_Add03.pdf
PDF 113 KB Posted
- Attached to
- F-35 Alter Hangar 406 Federal contract opportunity
- Solicitation number
- W50S9F-21-B-0001
- Issued by
- Department of the Army National Guard
About this file
This solicitation seeks firms to provide construction services for alterations to an F-35 aircraft hangar at Truax Field Air National Guard Base in Madison, Wisconsin. Work includes demolishing 19,913 square feet of hangar shop space and reconfiguring the area for F-35 maintenance operations, including lavatories, offices, break rooms, and repair shops. An additional 19,803 square feet of hangar space will be modified to accommodate F-35 aircraft, along with fire suppression and aircraft utility system upgrades. The solicitation also includes options for a fire protection runoff storage trench and slab infill. Interested parties must register in the System for Award Management and attend a pre-bid conference on February 16, 2021 to be eligible to respond prior to the March 8, 2021 closing date. The contract will be a firm-fixed-price award for one year. The estimated value is between $10-25 million. The soliciting agency is the Department of the Army National Guard.
View the file
Other files for this federal contract opportunity
Show all 50
F-35 Alter Hangar 406 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NS
HYDRAULIC REFERENCE NODE
OS&Y VALVE WITH TAMPER
SWITCH
CONNECT TO EXISTING
SYSTEM
CHECK VALVE
WATERFLOW SWITCH
PRESSURE REDUCING VALVE
POST INDICATOR VALVE
UPRIGHT SPRINKLER
PENDENT SPRINKLER
SIDEWALL SPRINKLER
WET PIPE SYSTEM
PIPE ELEVATION AFF
FIRE DEPARTMENT
CONNECTION
PIPE CONTINUATION
DIRECTION OF FLOW
DENOTES HANGER LOCATION
BRANCH LINE RESTRAINT
LATERAL SEISMIC BRACE
LONGITUDINAL SEISMIC BRACE
FOUR-WAY SEISMIC BRACE
NON-SPRINKLERED SPACE
SMALL ROOM RULE
SP
[ X'-X"]
SRR
FIRE PROTECTION SYMBOLS FIRE ALARM/ MNS SYMBOLS
XX
s
F
C
M
ANN
FIRE ALARM/ MASS NOTIFICATION CONTROL
PANEL
REMOTE ANNUNCIATOR PANEL
FIRE ALARM/ MNS STROBE - WALL MOUNT
-XX DENOTES CANDELA RATING
FIRE ALARM/ MNS STROBE - CEILING MOUNT
-XX DENOTES CANDELA RATING
SPEAKER - WALL MOUNT
-WP DENOTES WEATHERPROOF
FIRE ALARM/COMBINATION SPEAKER
/STROBE - CEILING MOUNT
-XX DENOTES CANDELA RATING
FIRE ALARM/ MNS SPEAKER - CEILING MOUNT
-WP DENOTES WEATHERPROOF
SMOKE DETECTOR - PHOTOELECTRIC
DUCT SMOKE DETECTOR
HEAT DETECTOR
FIRE ALARM MANUAL PULL STATION
ADDRESSABLE INITIATING DEVICE MODULE
ADDRESSABLE CONTROL (RELAY) MODULE
PRESSURE SWITCH
WATERFLOW SWITCH
TAMPER SWITCH
EXTERIOR FIRE ALARM BELL
TRANSIENT VOLTAGE SURGE SUPPRESSOR
REMOTE TEST STATION
LOCAL OPERATING CONSOLE
RADIO TRANSMITTER
RADIO RECEIVER
ANTENNA
REMOTE POWER SUPPLY
TEMPERATURE SENSOR
KNOX BOX
TVSS
RTS
FMCP
D
LOC
XX
C
C
XX
RT
RPS
RR
FIRE PROTECTION GENERAL NOTES
1. FIRE PROTECTION SYSTEMS SHALL COMPLY WITH PROJECT
SPECIFICATIONS, UFC 3-600-01, UFC 4-211-01, ETL 15-01-03, NFPA 13,
NFPA 20, NFPA 24, AND ALL APPLICABLE CODES AND STANDARDS.
2. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE A GENERAL
ARRANGEMENT OF WORK. GENERAL DESIGN CONCEPTS INDICATED
MUST BE FOLLOWED OR BETTERED. THE BID SHALL INCLUDE OFFSETS,
ADDITIONAL PIPING, VALVES, AND FIRE PROTECTION EQUIPMENT AS
REQUIRED TO MEET CONSTRUCTION CONDITIONS FOR PROPER
OPERATION. DEVELOP AND SUBMIT COORDINATION DRAWINGS.
3. PIPING WILL NOT BE SHOWN FOR THE SPRINKLER SYSTEM. THE
CONTRACTOR SHALL PROVIDE FINAL ROUTING FOR ALL PIPING AND
SHALL PROVIDE SHOP DRAWINGS THAT INCLUDE: EXACT DIMENSIONED
ROUTING OF ALL PIPE, PIPE SIZES, DIMENSIONED TIE-IN LOCATIONS AT
EXISTING PIPING, AND FIRE RATED CONSTRUCTION PENETRATIONS
DETAILS. THE CONTRACTOR SHALL AVOID INTERFERENCES WITH
OTHER PIPING, EQUIPMENT, CODE REQUIRED CLEARANCES, AND THE
WORK OF OTHER DISCIPLINES. FIELD ROUTED LIQUID-FILLED PIPING
SHALL NOT BE ROUTED ABOVE ELECTRICAL OR ELECTRONIC
EQUIPMENT.
4. INSTALLING CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND
LICENSES.
5. DESIGN AND INSTALLATION SUBJECT TO FINAL INSPECTION AND
APPROVAL BY CONTRACTING OFFICER.
6. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS SHALL
BE DONE ONLY WITH THE WRITTEN APPROVAL OF THE CONTRACTING
OFFICER.
7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, RATED WALLS,
CEILINGS, FLOOR, ROOFS, ETC. FLASH AND COUNTERFLASH ANY ROOF
PENETRATIONS.
8. METHOD OF HANGING PIPES, HEADERS, AND BRANCHLINES SHALL BE
IN ACCORDANCE WITH NFPA 13.
9. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE
UNDERWRITER'S LABORATORIES, INC. AND/OR THE FACTORY MUTUAL
LABORATORIES. VALVES SHALL BE FACTORY MARKED "UL" AND/OR
"FM" OR EQUIVALENT, 175 psi WORKING PRESSURE.
10. ALL NORMALLY OPEN VALVES ON THE FIRE PROTECTION SYSTEM
SHALL BE ELECTRICALLY SUPERVISED AND SHALL BE THE
RESPONSIBILITY OF THE FIRE SPRINKLER CONTRACTOR.
11. PROVIDE A PERMANENTLY ATTACHED HYDRAULIC NAME PLATE
STATING THE REQUIRED DESIGN CRITERIA FOR EACH HYDRAULICALLY
DESIGNED SYSTEM IN ACCORDANCE WITH NFPA 13.
12. ONLY NEW MATERIALS SHALL BE USED IN THE INSTALLATION OF
THESE SYSTEMS.
13. ALL SUPPORTS SHALL BE ATTACHED TO THE BUILDING'S STRUCTURAL
FRAME IN ACCORDANCE WITH NFPA 13.
14. INSTALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S
INSTRUCTIONS.
15. ROD STIFFERNER REQUIRED FOR ALL-THREAD ROD HANGERS OVER 6'
IN LENGTH.
16. INSTALL UNIONS IN PIPES 2" AND SMALLER, ADJACENT TO EACH
VALVE. UNIONS ARE NOT REQUIRED ON FLANGED DEVICES OR IN
PIPING INSTALLATIONS USING GROOVED MECHANICAL COUPLINGS.
17. SAFEGUARDING DURING CONSTRUCTION SHALL BE IN ACCORDANCE
WITH ARMY CORPS OF ENGINEERING MANUAL (EM), EM-385-1-1, SAFETY
AND HEALTH REQUIREMENTS MANUAL AND NFPA 241. CONTRACTOR
SHALL COORDINATE SPECIFIC PLAN FOR FIRE PROTECTION DURING
CONSTRUCTION WITH THE CONTRACTING OFFICER.
18. SPRINKLERS INSTALLED IN HIGH HEAT AREAS, INCLUDING BUT NOT
LIMITED TO, ATTIC SPACES, OR IN CLOSE PROXIMITY TO UNIT HEATERS,
SHALL HAVE A TEMPERATURE CLASSIFICATION IN ACCORDANCE WITH
NFPA 13.
19. EQUIPMENT SHALL BE INSTALLED WITH A MINIMUM CLEARANCE OF 36"
ACCESS TO AND IN FRONT OF ALL EQUIPMENT AND 6" BEHIND THE
EQUIPMENT.
1. FIRE ALARM/MASS NOTIFICATION SYSTEMS SHALL COMPLY WITH
UFC 3-600-01, UFC 4-021-01, ETL 15-01-03, NFPA 70, NFPA 72, AND
PROJECT SPECIFICATIONS.
2. PENETRATIONS IN FIRE RATED ASSEMBLIES SHALL BE FIRE-
STOPPED WITH LISTED MATERIALS/ ASSEMBLIES IN ACCORDANCE
WITH THE PROJECT SPECIFICATIONS.
3. FIRE SUPPRESSION SYSTEM WATERFLOW AND CONTROL VALVE
SUPERVISORY SWITCHES SHALL BE MONITORED BY THE BUILDING
FIRE ALARM/ MASS NOTIFICATION SYSTEM.
4. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR
COORDINATION OF SYSTEM REQUIREMENTS WITH ALL
CONDITIONS OF THE BUILDING AND SITE INCLUDING, BUT NOT
LIMITED TO, BLIND SPACES, SHELVING, LIGHTS, HVAC GRILLES AND
DIFFUSERS, PIPING, DUCT WORK, DOORS, WINDOWS, EQUIPMENT
PLATFORMS, WALLS (FIRE RATED AND NON FIRE RATED), BEAMS,
JOISTS, COLUMNS, HVAC EQUIPMENT, ELECTRICAL PANELS AND
EQUIPMENT, CEILINGS, AREAS WITHOUT CEILINGS, WALL
CONSTRUCTION, FLOORS AND ALL CONSTRUCTION, EQUIPMENT
AND BUILDING APPURTENANCES.
5. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR
PERFORMING, DOCUMENTING, AND CERTIFYING REQUISITE
INSPECTION AND TESTS IN ACCORDANCE WITH APPLICABLE
CODES AND STANDARDS FOR ALL FIRE ALARM EQUIPMENT
FURNISHED UNDER THIS PROJECT. AFTER COMPLETING THE
TESTING, THE CONTRACTOR SHALL DEMONSTRATE FULL
OPERATIONAL CAPABILITY OF THE FIRE ALARM/ MASS
NOTIFICATION SYSTEM, AS WELL AS FULL COMPLIANCE WITH ALL
DESIGN DOCUMENTS, CODES AND STANDARDS.
6. CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS MATERIAL
FOR A COMPLETE INSTALLATION.
7. EACH CONVENTIONAL FIRE ALARM DEVICE MUST HAVE ITS OWN
MONITOR MODULE.
8. ALL CONDUCTORS SHALL BE INSTALLED IN METALLIC CONDUITS.
9. ALL FIRE ALARM MODULES LOCATED WITHIN 15' OF A
SPRINKLER/STANDPIPE SYSTEM RISER SHALL BE WEATHERPROOF
WITH LIQUID TIGHT CONDUIT.
10. ALL CONDUIT FROM ANY FIRE ALARM DEVICE CONNECTED TO A
DEVICE THAT MAY BE IN CONTACT WITH WATER SHALL BE LIQUID
TIGHT. THIS INCLUDES, BUT IS NOT LIMITED TO, WATERFLOW
SWITCHES, PRESSURE SWITCHES & TAMPER SWITCHES.
11. TELECOMMUNICATIONS CONDUIT SHALL BE INSTALLED IN
ACCORDANCE WITH DIVISION 27 OF THE PROJECT
SPECIFICATIONS.
12. PROVIDE A LABEL ON THE EXTERIOR OF EACH FIRE ALARM DEVICE
THAT MATCHES THE DEVICE NUMBER (ADDRESS) AT THE FMCP.
DEVICE ID NUMBERS SHALL BE VISIBLE FROM THE FLOOR TO THE
MAXIMUM EXTENT PRACTICAL. MONITOR MODULES &
CONTROL/RELAY MODULES SHALL ALSO BE LABELED AS TO WHAT
THEY CONTROL.
13. ALL WIRING, CONDUIT, AND DEVICES LOCATED IN HAZARDOUS
ATMOSPHERES, AS DEFINED BY NFPA 70, SHALL BE EXPLOSION
PROOF. REFER TO THE ELECTRICAL PLANS FOR LOCATIONS.
FIRE ALARM/MNS GENERAL NOTES
ABOVE FINISHED FLOOR
AUTOMATIC TRANSFER SWITCH
BACKFLOW PREVENTER
CLEAN AGENT SYSTEM CONTROL PANEL
CANDELA
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CHECK VALVE
CHEMICAL
CEMENT LINED DUCTILE IRON PIPE
CONTROL PANEL
DECIBEL
FIRE ALARM
FIRE ALARM BELL
FIRE ALARM CONTROL PANEL
FIRE DEPARTMENT CONNECTION
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FACTORY MUTUAL
FIBER OPTIC
FIBER OPTIC TRANSCEIVER MODULE
FIRE PUMP CONTROLLER
FLOW SWITCH
FIRE SEPARATION DISTANCE
GOVERNMENT FURNISHED GOVERNMENT INSTALLED
HIGH-EXPANSION FOAM
IN ACCORDANCE WITH
INTERNATIONAL BUILDING CODE
MANUFACTURER
MASS NOTIFICATION SYSTEM
NOTIFICATION APPLIANCE CIRCUIT
NORMALLY CLOSED
NATIONAL FIRE PROTECTION ASSOCIATION
OUTSIDE STEM AND YOKE
PUMP
POST INDICATOR VALVE
PRESSURE REDUCING VALVE
RISER CHECK VALVE
RELEASING SERVICE FIRE ALARM CONTROL UNIT
SOUNDER BASE
SCHEDULE
PHOTOELECTRIC SMOKE DETECTOR
SIGNALING LINE CIRCUIT
TANK
TO BE DETERMINED
TAMPER SWITCH
TRANSIENT VOLTAGE SURGE SUPPRESSOR
UNIFIED FACILITIES CRITERIA
UNDERWRITER'S LABORATORIES
UNLESS OTHERWISE NOTED
UNITED STATES AIR FORCE
VALVE
VARIABLE FREQUENCY DRIVE
WEATHERPROOF
ZONE CONTROL ASSEMBLY
AFF
ATS
BFP
CACP
CD
CFCI
CHKV
CHEM
CLDIP
CP
DB
FA
FAB
FACP
FDC
FE
FEC
FM
FO
FOTM
FPC
FS
FSD
GFGI
HEF
IAW
IBC
MFG
MNS
NAC
NC
NFPA
OS&Y
P
PIV
PRV
RCV
RSFAC
SB
SCH
SD
SLC
T
TBD
TS
TVSS
UFC
UL
UON
USAF
V
VFD
WP
ZCA
FIRE PROTECTION ABBREVIATIONS
T
K
HEF GENERATOR
HEF START/ STOP STATIONS
BLUE ROTATING BEACON
SURGE TANK
DET-TRONICS X3301 MULTISPECTRUM IR OPTICAL
FLAME DETECTOR
FLOW CONTROL VALVE
SOLENOID
DISCONNECT SWITCH
RELEASING SERVICE FIRE ALARM CONTROL UNIT
ST
DS
S
RSFACU
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
07/31/20 TYPE B3 FINAL
/9
/2
:0
:1
A
M B
IM
/T ru a x F ie ld
A N
G B
F -3
A lt e r B u ild in g
/3
-1
.0
-F -C e n tr a l-
.r v t
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
F -3
A L T
E R
B U
IL
D
IN
G
F-001
FIRE PROTECTION
LEGEND AND
SYMBOLS
XGFG182008ANG NO.:
3141300-190289.01
MAL
KF
July 31, 2020
RAB
3 03/08/21 ADDENDUM - 03