This solicitation seeks firms to provide construction services for alterations to an F-35 aircraft hangar at Truax Field Air National Guard Base in Madison, Wisconsin. Work includes demolishing 19,913 square feet of hangar shop space and reconfiguring the area for F-35 maintenance operations, including lavatories, offices, break rooms, and repair shops. An additional 19,803 square feet of hangar space will be modified to accommodate F-35 aircraft, along with fire suppression and aircraft utility system upgrades. The solicitation also includes options for a fire protection runoff storage trench and slab infill. Interested parties must register in the System for Award Management and attend a pre-bid conference on February 16, 2021 to be eligible to respond prior to the March 8, 2021 closing date. The contract will be a firm-fixed-price award for one year. The estimated value is between $10-25 million. The soliciting agency is the Department of the Army National Guard.

View the file

Other files for this federal contract opportunity

Other files attached to F-35 Alter Hangar 406, newest first.
File Type Posted
SF1419 Abstract of Offers - No Hubzone Preference.pdf PDF
W50S9F21B00010007.pdf PDF
406 Questions and Answers_142-143.pdf PDF
23 07 00_Add04.pdf PDF
C-102_Add03.pdf PDF
C-101_Add03.pdf PDF
Specs TOC_Add03.pdf PDF
01 50 00_Add03.pdf PDF
406 Questions and Answers_26-112.pdf PDF
G-001_Add02.pdf PDF
E-101_Add02.pdf PDF
01 50 00_Add02.pdf PDF
12 21 00_Add02.pdf PDF
10 14 00.20_Add02.pdf PDF
05 40 00_Add02.pdf PDF
01 78 00_Add02.pdf PDF
Specs TOC_ Add02.pdf PDF
A-301_Add02.pdf PDF
A-901_Add02.pdf PDF
A-801_Add02.pdf PDF
A-101_Add02.pdf PDF
01 45 00.00 10_Add02.pdf PDF
W50S9F21B00010004.pdf PDF
C-141_Add02.pdf PDF
A-131_Add01.R1.pdf PDF
C-121_Add01.R1.pdf PDF
406 Questions and Answers_1-25.pdf PDF
Specs TOC_Add01.R1.pdf PDF
07 24 00_Add01.R1.pdf PDF
09 67 23.13_Add01.R1.pdf PDF
32 92 19_Add01.R1.pdf PDF
A-201_Add01.R1.pdf PDF
C-101_Add01.R1.pdf PDF
Geotechnical Report_Add01.R1.pdf PDF
W50S9F21B00010003.pdf PDF
10 22 39_Add01.R1.pdf PDF
W50S9F21B00010002.pdf PDF
B.07.406 Site Visit Sign In 22Feb21.pdf PDF
W50S9F21B00010001.pdf PDF
406 Site Visit Sign In.pdf PDF
ATTACHMENT 1-Truax F-35 B406 XGFG182008 Specs Vol 1 of 2 Dated 31 July 2020.pdf PDF
ATTACHMENT 5-Justification and Approval Andover.pdf PDF
ATTACHMENT 2-Truax F-35 B406 XGFG182008 Specs Vol 2 of 2 Dated 31 July 2020.pdf PDF
ATTACHMENT 3-Truax F35 B406 XGFG182008 Plans Dated 31 July 2020.pdf PDF
ATTACHMENT 7-Justification and Approval Best Lock.pdf PDF
W50S9F-21-B-0001.pdf PDF
ATTACHMENT 6-Justification and Approval Monaco.pdf PDF
ATTACHMENT 8-406 Submittal Log.xlsx XLSX spreadsheet
ATTACHMENT 9-SFS Form 12.xls XLS spreadsheet
ATTACHMENT 10-PRE-BID CONFERENCE AND SITE VISIT INSTRUCTIONS.pdf PDF
Show all 50

F-35 Alter Hangar 406 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NS

HYDRAULIC REFERENCE NODE

OS&Y VALVE WITH TAMPER

SWITCH

CONNECT TO EXISTING

SYSTEM

CHECK VALVE

WATERFLOW SWITCH

PRESSURE REDUCING VALVE

POST INDICATOR VALVE

UPRIGHT SPRINKLER

PENDENT SPRINKLER

SIDEWALL SPRINKLER

WET PIPE SYSTEM

PIPE ELEVATION AFF

FIRE DEPARTMENT

CONNECTION

PIPE CONTINUATION

DIRECTION OF FLOW

DENOTES HANGER LOCATION

BRANCH LINE RESTRAINT

LATERAL SEISMIC BRACE

LONGITUDINAL SEISMIC BRACE

FOUR-WAY SEISMIC BRACE

NON-SPRINKLERED SPACE

SMALL ROOM RULE

SP

[ X'-X"]

SRR

FIRE PROTECTION SYMBOLS FIRE ALARM/ MNS SYMBOLS

XX

s

F

C

M

ANN

FIRE ALARM/ MASS NOTIFICATION CONTROL

PANEL

REMOTE ANNUNCIATOR PANEL

FIRE ALARM/ MNS STROBE - WALL MOUNT

-XX DENOTES CANDELA RATING

FIRE ALARM/ MNS STROBE - CEILING MOUNT

-XX DENOTES CANDELA RATING

SPEAKER - WALL MOUNT

-WP DENOTES WEATHERPROOF

FIRE ALARM/COMBINATION SPEAKER

/STROBE - CEILING MOUNT

-XX DENOTES CANDELA RATING

FIRE ALARM/ MNS SPEAKER - CEILING MOUNT

-WP DENOTES WEATHERPROOF

SMOKE DETECTOR - PHOTOELECTRIC

DUCT SMOKE DETECTOR

HEAT DETECTOR

FIRE ALARM MANUAL PULL STATION

ADDRESSABLE INITIATING DEVICE MODULE

ADDRESSABLE CONTROL (RELAY) MODULE

PRESSURE SWITCH

WATERFLOW SWITCH

TAMPER SWITCH

EXTERIOR FIRE ALARM BELL

TRANSIENT VOLTAGE SURGE SUPPRESSOR

REMOTE TEST STATION

LOCAL OPERATING CONSOLE

RADIO TRANSMITTER

RADIO RECEIVER

ANTENNA

REMOTE POWER SUPPLY

TEMPERATURE SENSOR

KNOX BOX

TVSS

RTS

FMCP

D

LOC

XX

C

C

XX

RT

RPS

RR

FIRE PROTECTION GENERAL NOTES

1. FIRE PROTECTION SYSTEMS SHALL COMPLY WITH PROJECT

SPECIFICATIONS, UFC 3-600-01, UFC 4-211-01, ETL 15-01-03, NFPA 13,

NFPA 20, NFPA 24, AND ALL APPLICABLE CODES AND STANDARDS.

2. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE A GENERAL

ARRANGEMENT OF WORK. GENERAL DESIGN CONCEPTS INDICATED

MUST BE FOLLOWED OR BETTERED. THE BID SHALL INCLUDE OFFSETS,

ADDITIONAL PIPING, VALVES, AND FIRE PROTECTION EQUIPMENT AS

REQUIRED TO MEET CONSTRUCTION CONDITIONS FOR PROPER

OPERATION. DEVELOP AND SUBMIT COORDINATION DRAWINGS.

3. PIPING WILL NOT BE SHOWN FOR THE SPRINKLER SYSTEM. THE

CONTRACTOR SHALL PROVIDE FINAL ROUTING FOR ALL PIPING AND

SHALL PROVIDE SHOP DRAWINGS THAT INCLUDE: EXACT DIMENSIONED

ROUTING OF ALL PIPE, PIPE SIZES, DIMENSIONED TIE-IN LOCATIONS AT

EXISTING PIPING, AND FIRE RATED CONSTRUCTION PENETRATIONS

DETAILS. THE CONTRACTOR SHALL AVOID INTERFERENCES WITH

OTHER PIPING, EQUIPMENT, CODE REQUIRED CLEARANCES, AND THE

WORK OF OTHER DISCIPLINES. FIELD ROUTED LIQUID-FILLED PIPING

SHALL NOT BE ROUTED ABOVE ELECTRICAL OR ELECTRONIC

EQUIPMENT.

4. INSTALLING CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND

LICENSES.

5. DESIGN AND INSTALLATION SUBJECT TO FINAL INSPECTION AND

APPROVAL BY CONTRACTING OFFICER.

6. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS SHALL

BE DONE ONLY WITH THE WRITTEN APPROVAL OF THE CONTRACTING

OFFICER.

7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, RATED WALLS,

CEILINGS, FLOOR, ROOFS, ETC. FLASH AND COUNTERFLASH ANY ROOF

PENETRATIONS.

8. METHOD OF HANGING PIPES, HEADERS, AND BRANCHLINES SHALL BE

IN ACCORDANCE WITH NFPA 13.

9. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE

UNDERWRITER'S LABORATORIES, INC. AND/OR THE FACTORY MUTUAL

LABORATORIES. VALVES SHALL BE FACTORY MARKED "UL" AND/OR

"FM" OR EQUIVALENT, 175 psi WORKING PRESSURE.

10. ALL NORMALLY OPEN VALVES ON THE FIRE PROTECTION SYSTEM

SHALL BE ELECTRICALLY SUPERVISED AND SHALL BE THE

RESPONSIBILITY OF THE FIRE SPRINKLER CONTRACTOR.

11. PROVIDE A PERMANENTLY ATTACHED HYDRAULIC NAME PLATE

STATING THE REQUIRED DESIGN CRITERIA FOR EACH HYDRAULICALLY

DESIGNED SYSTEM IN ACCORDANCE WITH NFPA 13.

12. ONLY NEW MATERIALS SHALL BE USED IN THE INSTALLATION OF

THESE SYSTEMS.

13. ALL SUPPORTS SHALL BE ATTACHED TO THE BUILDING'S STRUCTURAL

FRAME IN ACCORDANCE WITH NFPA 13.

14. INSTALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S

INSTRUCTIONS.

15. ROD STIFFERNER REQUIRED FOR ALL-THREAD ROD HANGERS OVER 6'

IN LENGTH.

16. INSTALL UNIONS IN PIPES 2" AND SMALLER, ADJACENT TO EACH

VALVE. UNIONS ARE NOT REQUIRED ON FLANGED DEVICES OR IN

PIPING INSTALLATIONS USING GROOVED MECHANICAL COUPLINGS.

17. SAFEGUARDING DURING CONSTRUCTION SHALL BE IN ACCORDANCE

WITH ARMY CORPS OF ENGINEERING MANUAL (EM), EM-385-1-1, SAFETY

AND HEALTH REQUIREMENTS MANUAL AND NFPA 241. CONTRACTOR

SHALL COORDINATE SPECIFIC PLAN FOR FIRE PROTECTION DURING

CONSTRUCTION WITH THE CONTRACTING OFFICER.

18. SPRINKLERS INSTALLED IN HIGH HEAT AREAS, INCLUDING BUT NOT

LIMITED TO, ATTIC SPACES, OR IN CLOSE PROXIMITY TO UNIT HEATERS,

SHALL HAVE A TEMPERATURE CLASSIFICATION IN ACCORDANCE WITH

NFPA 13.

19. EQUIPMENT SHALL BE INSTALLED WITH A MINIMUM CLEARANCE OF 36"

ACCESS TO AND IN FRONT OF ALL EQUIPMENT AND 6" BEHIND THE

EQUIPMENT.

1. FIRE ALARM/MASS NOTIFICATION SYSTEMS SHALL COMPLY WITH

UFC 3-600-01, UFC 4-021-01, ETL 15-01-03, NFPA 70, NFPA 72, AND

PROJECT SPECIFICATIONS.

2. PENETRATIONS IN FIRE RATED ASSEMBLIES SHALL BE FIRE-

STOPPED WITH LISTED MATERIALS/ ASSEMBLIES IN ACCORDANCE

WITH THE PROJECT SPECIFICATIONS.

3. FIRE SUPPRESSION SYSTEM WATERFLOW AND CONTROL VALVE

SUPERVISORY SWITCHES SHALL BE MONITORED BY THE BUILDING

FIRE ALARM/ MASS NOTIFICATION SYSTEM.

4. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR

COORDINATION OF SYSTEM REQUIREMENTS WITH ALL

CONDITIONS OF THE BUILDING AND SITE INCLUDING, BUT NOT

LIMITED TO, BLIND SPACES, SHELVING, LIGHTS, HVAC GRILLES AND

DIFFUSERS, PIPING, DUCT WORK, DOORS, WINDOWS, EQUIPMENT

PLATFORMS, WALLS (FIRE RATED AND NON FIRE RATED), BEAMS,

JOISTS, COLUMNS, HVAC EQUIPMENT, ELECTRICAL PANELS AND

EQUIPMENT, CEILINGS, AREAS WITHOUT CEILINGS, WALL

CONSTRUCTION, FLOORS AND ALL CONSTRUCTION, EQUIPMENT

AND BUILDING APPURTENANCES.

5. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR

PERFORMING, DOCUMENTING, AND CERTIFYING REQUISITE

INSPECTION AND TESTS IN ACCORDANCE WITH APPLICABLE

CODES AND STANDARDS FOR ALL FIRE ALARM EQUIPMENT

FURNISHED UNDER THIS PROJECT. AFTER COMPLETING THE

TESTING, THE CONTRACTOR SHALL DEMONSTRATE FULL

OPERATIONAL CAPABILITY OF THE FIRE ALARM/ MASS

NOTIFICATION SYSTEM, AS WELL AS FULL COMPLIANCE WITH ALL

DESIGN DOCUMENTS, CODES AND STANDARDS.

6. CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS MATERIAL

FOR A COMPLETE INSTALLATION.

7. EACH CONVENTIONAL FIRE ALARM DEVICE MUST HAVE ITS OWN

MONITOR MODULE.

8. ALL CONDUCTORS SHALL BE INSTALLED IN METALLIC CONDUITS.

9. ALL FIRE ALARM MODULES LOCATED WITHIN 15' OF A

SPRINKLER/STANDPIPE SYSTEM RISER SHALL BE WEATHERPROOF

WITH LIQUID TIGHT CONDUIT.

10. ALL CONDUIT FROM ANY FIRE ALARM DEVICE CONNECTED TO A

DEVICE THAT MAY BE IN CONTACT WITH WATER SHALL BE LIQUID

TIGHT. THIS INCLUDES, BUT IS NOT LIMITED TO, WATERFLOW

SWITCHES, PRESSURE SWITCHES & TAMPER SWITCHES.

11. TELECOMMUNICATIONS CONDUIT SHALL BE INSTALLED IN

ACCORDANCE WITH DIVISION 27 OF THE PROJECT

SPECIFICATIONS.

12. PROVIDE A LABEL ON THE EXTERIOR OF EACH FIRE ALARM DEVICE

THAT MATCHES THE DEVICE NUMBER (ADDRESS) AT THE FMCP.

DEVICE ID NUMBERS SHALL BE VISIBLE FROM THE FLOOR TO THE

MAXIMUM EXTENT PRACTICAL. MONITOR MODULES &

CONTROL/RELAY MODULES SHALL ALSO BE LABELED AS TO WHAT

THEY CONTROL.

13. ALL WIRING, CONDUIT, AND DEVICES LOCATED IN HAZARDOUS

ATMOSPHERES, AS DEFINED BY NFPA 70, SHALL BE EXPLOSION

PROOF. REFER TO THE ELECTRICAL PLANS FOR LOCATIONS.

FIRE ALARM/MNS GENERAL NOTES

ABOVE FINISHED FLOOR

AUTOMATIC TRANSFER SWITCH

BACKFLOW PREVENTER

CLEAN AGENT SYSTEM CONTROL PANEL

CANDELA

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CHECK VALVE

CHEMICAL

CEMENT LINED DUCTILE IRON PIPE

CONTROL PANEL

DECIBEL

FIRE ALARM

FIRE ALARM BELL

FIRE ALARM CONTROL PANEL

FIRE DEPARTMENT CONNECTION

FIRE EXTINGUISHER

FIRE EXTINGUISHER CABINET

FACTORY MUTUAL

FIBER OPTIC

FIBER OPTIC TRANSCEIVER MODULE

FIRE PUMP CONTROLLER

FLOW SWITCH

FIRE SEPARATION DISTANCE

GOVERNMENT FURNISHED GOVERNMENT INSTALLED

HIGH-EXPANSION FOAM

IN ACCORDANCE WITH

INTERNATIONAL BUILDING CODE

MANUFACTURER

MASS NOTIFICATION SYSTEM

NOTIFICATION APPLIANCE CIRCUIT

NORMALLY CLOSED

NATIONAL FIRE PROTECTION ASSOCIATION

OUTSIDE STEM AND YOKE

PUMP

POST INDICATOR VALVE

PRESSURE REDUCING VALVE

RISER CHECK VALVE

RELEASING SERVICE FIRE ALARM CONTROL UNIT

SOUNDER BASE

SCHEDULE

PHOTOELECTRIC SMOKE DETECTOR

SIGNALING LINE CIRCUIT

TANK

TO BE DETERMINED

TAMPER SWITCH

TRANSIENT VOLTAGE SURGE SUPPRESSOR

UNIFIED FACILITIES CRITERIA

UNDERWRITER'S LABORATORIES

UNLESS OTHERWISE NOTED

UNITED STATES AIR FORCE

VALVE

VARIABLE FREQUENCY DRIVE

WEATHERPROOF

ZONE CONTROL ASSEMBLY

AFF

ATS

BFP

CACP

CD

CFCI

CHKV

CHEM

CLDIP

CP

DB

FA

FAB

FACP

FDC

FE

FEC

FM

FO

FOTM

FPC

FS

FSD

GFGI

HEF

IAW

IBC

MFG

MNS

NAC

NC

NFPA

OS&Y

P

PIV

PRV

RCV

RSFAC

SB

SCH

SD

SLC

T

TBD

TS

TVSS

UFC

UL

UON

USAF

V

VFD

WP

ZCA

FIRE PROTECTION ABBREVIATIONS

T

K

HEF GENERATOR

HEF START/ STOP STATIONS

BLUE ROTATING BEACON

SURGE TANK

DET-TRONICS X3301 MULTISPECTRUM IR OPTICAL

FLAME DETECTOR

FLOW CONTROL VALVE

SOLENOID

DISCONNECT SWITCH

RELEASING SERVICE FIRE ALARM CONTROL UNIT

ST

DS

S

RSFACU

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

07/31/20 TYPE B3 FINAL

/9

/2

:0

:1

A

M B

IM

/T ru a x F ie ld

A N

G B

F -3

A lt e r B u ild in g

/3

-1

.0

-F -C e n tr a l-

.r v t

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

F -3

A L T

E R

B U

IL

D

IN

G

F-001

FIRE PROTECTION

LEGEND AND

SYMBOLS

XGFG182008ANG NO.:

3141300-190289.01

MAL

KF

July 31, 2020

RAB

3 03/08/21 ADDENDUM - 03

Sheets
F-001 - FIRE PROTECTION LEGEND AND SYMBOLS
F-102 - FIRE PROTECTION PLAN

File details come from the government source that posted it. Updated .