This solicitation is for a firm fixed-price construction contract to alter an F-35 Aircraft Hangar at Dane County Regional Airport - Truax Field in Madison, Wisconsin. The scope of work includes demolishing aircraft shop spaces and reconfiguring the area for F-35 maintenance operations. Additional work involves modifying hangar spaces to accommodate F-35 aircraft, including fire suppression and aircraft systems. The project is governed by F-35 facility requirements and specifications. Subcontracting plans are required from large businesses. The contract duration is 365 days from notice to proceed. The solicitation closes on March 8, 2021 and there will be a public bid opening. Interested parties must register in SAM and check the website periodically for amendments. The NAICS code is 236220 with a $39.5 million size standard. The magnitude is estimated between $10-25 million. Award will be to the responsive and responsible lowest bidder.
View the file
Other files for this federal contract opportunity
Show all 50
F-35 Alter Hangar 406 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
#3/0 GRD
#3/0 GRD
#2 GRD
#6 GRD
TO TELECOM ROOM
GROUNDING BUSBAR
(TGB)
#3/0 GRD
#3/0 GRD
TO TELECOM ROOM
GROUNDING BUSBAR
(TGB)
CABLE TRAY
TELECOM EQUIPMENT
RACK(S)
MAIN TELECOM ROOM
MAIN GROUNDING BUSBAR (TMGB)
STREET SIDE OF BUILDING
WATER METER. CONNECT TO
METALLIC WATER MAIN
WITHIN 5'-0" OF WATER
SERVICE ENTRANCE.
PROVIDE
JUMPER ACROSS WATER
METER.
MAIN BUILDING GROUND BUS
PROVIDE EXOTHERMIC WELD FOR
CONNECTION OF CONDUCTORS TO
GROUND BUS OR CONDUCTORS CAN BE
ATTACHED USING CRIMPED ON LUGS
(WITH LISTED CRIMPER) AND BOLTED TO
GROUND BUS.
FIRE PUMP MAIN
SERVICE DISCONNECT
NEUTRAL BUS
NOTES:
1. ALL GROUND CONDUCTORS TO BE
ROUTED IN PVC CONDUIT.
2. ALL GROUND CONDUCTORS ON THIS
DIAGRAM SHALL BE COPPER.
#3/0 AWG
BUILDING STEEL
PROVIDE NEW GROUNDING CONNECTION
AT EXISTING BUILDING STEEL IN ELEC 174.
#3/0 GRD
GROUNDING ELECTRODE CONDUCTOR
SIZED PER NEC 250.66.
3/4" X 10'-0" COPPERWELD GROUND
ROD. SEE FLOOR PLANS AND
SPECIFICATION SECTION 26 05 26.
LIGHTNING PROTECTION GROUND
ACCESS WELL.
REMOVABLE LINK
#3/0 GRD
FIRE PUMP MAIN
SERVICE DISCONNECT
GROUND BUS
HANGAR DOOR MAIN
SERVICE DISCONNECT
NEUTRAL BUS
REMOVABLE LINK
#3/0 GRD
HANGAR DOOR MAIN
SERVICE DISCONNECT
GROUND BUS
REMOVABLE LINK
BUILDING MAIN
SERVICE DISCONNECT
NEUTRAL BUS
REMOVABLE LINK
#3/0 GRD
BUILDING MAIN
SERVICE DISCONNECT
GROUND BUS
#3/0 GRD
MAIN DISTRIBUTION PANEL
GROUND BUS
FINISHED FLOOR
46"
18"
POWER, TELEPHONE AND DATA
RECEPTACLES LOCATED IN
OFFICES AND OTHER FINISHED
AREAS UNLESS NOTED
OTHERWISE.
ALL SWITCHES AND WALL MOUNTED
PHONES. POWER RECEPTACLES
LOCATED IN UNFINISHED AREAS
UNLESS NOTED OTHERWISE.
NOTES:
MOUNTING HEIGHT DIMENSION FOR
ELECTRICAL RECEPTACLES AND
VOICE/DATA OUTLETS ABOVE COUNTER IS
HEIGHT AFF TO BOTTOM OF OUTLET BOX.
BOTTOM OF
OUTLET BOX
1.
CONTINUOUS (360 DEGREE) SWIVEL
GROUNDED RETRACTABLE POWER
CORD W/ SINGLE RECEPTACLE ON END.
FURNISHED W/ 12 FT OF 16-3 SJO CORD
(2 CONDUCTORS PLUS GROUND)
ENCLOSED STEEL CONSTRUCTION,
UL LISTED, LOCKING RATCHET TO
HOLD CORD AT DESIRED LENGTH.
MOUNTS ON 4" OCTAGONAL OUTLET BOX
RECEPTACLE (NEMA 5-20R)
(PROVIDED BY MANUFCTURER OF THE EQUIPMENT)
BALL
STOP
FUSED DISC.
SW. BY E.C.
4#12, 3/4"C.
CONTROL PANEL
BY E.S.
HEATER CABLE
CONNECTION IF
DRAWING INDICATES
NECESSARY
5#16, 3/4"C.
OPEN/CLOSE
PUSH BUTTON
ONE EACH
SIDE BY E.S.
NEMA L6-30 SPECIAL
PURPOSE RECEPTACLE
(TYP.)
U-CHANNEL STRUT
1/2" ALL-THREAD
SUPPORT
EMT CONDUIT
SUPPORTED TO
CEILING
2" 2"18" DIA.
GROUND
PAINT THE WORD "GROUND" IN 1"
BLACK LETTERS AND THE DATE
TESTED IN 1/2" BLACK LETTERS
PAINT RED
PAINT YELLOW
GROUND
RECEPTACLE SET IN
FLOOR
PLAN
3/4"
2-3/4" DIA.
-7
/8
M
IN
F
O R
H A
N G
A R
S
CAST BRONZE COVER,
FRICTION FIT BRASS PIN
CAST BRONZE HOUSING.
IN HANGARS, MAX. RESISTANCE TO
GROUND SHALL BE 25 OHMS FROM
ANY GROUND ROD.
3/4" N.C. THREAD.
3/4" PIPE OR ROD FOR
HANGARS. 3/4" COPPER-
WELD GROUND ROD FOR
HYDRANT REFUELING.
#10 BRASS BALL CHAIN.
FINISHED HANGAR FLOOR
OR APRON PAVEMENT.
ELEVATION
NOTE:
DRILL INTO HANGAR FLOOR
AS REQUIRED.
DOWN CONDUCTOR
GROUND ROD
GROUND ROD
CLAMP
TEST WELL. SEE
DETAIL 8/E-501.
1' MIN.
2' MIN.
OPEN SCHEDULE 80 1" PVC
FURNISHED/INSTALLED BY
EC.
GROUND CLAMP
GROUND ROD
POLYMER CONCRETE
FIBERGLASS REINFORCED
BOX
COVER REFERENCED
ABOVE (TOP VIEW)
GRAVEL OR
CRUSHED STONE
GROUNDING
CONDUCTOR #1/0
COPPER
TOP VIEW (COVER REMOVED)
A A
SECTION A - A
M
IN
24" MIN
UNIVERSAL FLAT SURFACE AIR
TERMINAL BASE MOUNTED
VERTICALLY
CUAT / ALAT - STYLE GENTLY
TAPERED AIR TERMINAL
ALUMINUM UNIVERSAL BASE
MOUNTED WITH STAINLESS
STEEL FASTNERS
CLASS I ALUMINUM
LIGHTNING CONDUCTOR
(24 STRANDS OF 14 AWG
WIRES 98 LBS. PER 1000')
ALUMINUM CABLE
CLIP WITH STAINLESS STEEL
FASTNER - EVERY 3' MAX.
1/2" X 1/2" GENTLY
TAPERED ALUMINUM AIR
TERMINAL
CUAT / ALAT - STYLE GENTLY
TAPERED AIR TERMINAL
UNIVERSAL SWIVEL AIR
TERMINAL BASE
COPPER OR ALUMINUM,
CLASS I OR CLASS II
LIGHTNING PROTECTION
CONDUCTOR
ADHESIVE
CABLE FASTENER
CABLE FASTENER
COPPER OR ALUMINUM
CLASS I OR CLASS II
LIGHTNING PROTECTION
CONDUCTOR
EXTERIOR WALL
M
IN
M
IN
OPEN SCHEDULE 80 1"
PVC
FURNISHED/INSTALLED
BY EC.
EXTERIOR WALL
CAPPING/COPPING
DOWN CONDUCTOR
ROOF SURFACE
ANGLE OF BEND NOT LESS
THAN 90 DEGREES.
RADIUS OF BEND NOT
LESS THAN 8".
DOWN CONDUCTOR
OPEN SCHEDULE 80 1" PVC
FURNISHED/INSTALLED BY EC.
ANGLE OF BEND NOT LESS
THAN 90 DEGREES. RADIUS
OF BEND NOT LESS THAN 8".
GROUND SURFACE
6" ENGINEERED FILL
PREPARED SUBGRADE
CONCRETE PAD WITH #5 AT 12"OC,
EACH WAY TOP AND BOTTOM.
PROVIDE A MINIMUM 3" REBAR
CLEARANCE, TYPICAL. THE TOP
OF THE SLAB SHALL BE A MINIMUM
OF 8" ABOVE ADJACENT GRADE.
PROVIDE MINIMUM 3" CONCRETE
COVER FOR ALL REBAR.
NOTES:
1. TOP OF CONCRETE SLAB MUST BE 8" ABOVE FINISHED GRADE WITH GRADUAL
SLOPE FOR DRAINAGE. WHERE APPLICABLE SLOPE SHALL BE AWAY FROM
BUILDING. EDGES ABOVE GRADE MUST HAVE 1/2" CHAMFER. SLAB SHALL BE OF
ADEQUATE SIZE TO PROJECT AT LEAST 8" BEYOND THE EQUIPMENT ON ALL SIDES.
2. STUB CONDUITS, WITH BUSHINGS, 6" ABOVE TOP OF CONCRETE SLAB. COORDINATE
CONDUIT LOCATIONS WITH EQUIPMENT CABLE ENTRANCE AREAS.
2 HOUR CONCRETE
OR CONCRETE BLOCK WALL
OR 1 HOUR GYPSUM
WALL ASSEMBLY
MINERAL WOOL BATT
INSULATION
(2 HOUR WALL ONLY)
4" DIAMETER
(OR SMALLER)
CONTINUOUS
METAL CONDUIT
STEEL SLEEVE
FIRE STOP SEALANT
SPEC SEAL SSS SEALANT
BY SPECIFIED TECHNOLOGIES.INC,
1"DEPTH ON BOTH SIDES.
NOTE:
SEE SHEET G101 FOR BUILDING WALL RATINGS
(UL SYSTEMS WL1171 FOR 1-HOUR GYPSUM WALL)
(UL SYSTEMS WJ1070 FOR 2-HOUR CONCRETE WALL)
SHEET NO.:
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.
Mead & Hunt, Inc.
2440 Deming Way
Middleton, WI 53562 phone: 608-273-6380 meadhunt.com
/2
/2
:3
:1
P M
C R e v it L o c a l\
-1
.0
-E -C e n tr a l-m a tt .f ir k u s m e a d h u n t.
c o m
.r v t
T R
U A
X F
IE
L D
A N
G B
M A
D
IS
O N
W
I
F -3
A L T
E R
B U
IL
D
IN
G
E-501
DETAILS
XGFG182008ANG NO.:
3141300-190289.01
MRF
ARG
July 31, 2020
MRF
NO SCALE1
GROUNDING SYSTEM DETAIL (TYP)
NO SCALE5
DEVICE MOUNTING HEIGHT
NO SCALE3
CORD REEL DETAIL
NO SCALE4
MOTORIZED ROLL-UP DOOR WITH
PUSH BUTTON CONTROL
NO SCALE2
RACK RECEPTACLE DETAIL
NO SCALE6
STATIC GROUND RECEPTACLE
NO SCALE7
GROUND ROD DETAIL
NO SCALE8
GROUND ACCESS WELL - DETAIL
NO SCALE9
AIR TERMINAL BASE
NO SCALE10
AIR TERMINAL BASE
NO SCALE11
CABLE FASTENER
NO SCALE12
CABLE FASTENER
NO SCALE13
CABLE FASTENER
NO SCALE14
BONDING CONNECTOR
NO SCALE15
CONCEALED PVC DETAIL
07/31/20 TYPE B3 FINAL
2 03/03/21 ADDENDUM - 02
NO SCALE16
EQUIPMENT PAD DETAIL
NO SCALE17
FIRESTOP WALL PENETRATION
| Sheets |
| E-501 - DETAILS |
File details come from the government source that posted it. Updated .