E-501_Add02.pdf

PDF 222 KB Posted

Attached to
F-35 Alter Hangar 406 Federal contract opportunity
Solicitation number
W50S9F-21-B-0001
Issued by
Department of the Army National Guard

About this file

This solicitation is for a firm fixed-price construction contract to alter an F-35 Aircraft Hangar at Dane County Regional Airport - Truax Field in Madison, Wisconsin. The scope of work includes demolishing aircraft shop spaces and reconfiguring the area for F-35 maintenance operations. Additional work involves modifying hangar spaces to accommodate F-35 aircraft, including fire suppression and aircraft systems. The project is governed by F-35 facility requirements and specifications. Subcontracting plans are required from large businesses. The contract duration is 365 days from notice to proceed. The solicitation closes on March 8, 2021 and there will be a public bid opening. Interested parties must register in SAM and check the website periodically for amendments. The NAICS code is 236220 with a $39.5 million size standard. The magnitude is estimated between $10-25 million. Award will be to the responsive and responsible lowest bidder.

View the file

Other files for this federal contract opportunity

Other files attached to F-35 Alter Hangar 406, newest first.
File Type Posted
Abstract of Offers with Hubzone Preference.pdf PDF
W50S9F21B00010006.pdf PDF
406 Questions and Answers_113-141.pdf PDF
F-102_Add03.pdf PDF
T-001 Add03.pdf PDF
E-101_Add03.pdf PDF
32 13 14.13_Add03.pdf PDF
21 13 18.00 10_Add03.pdf PDF
W50S9F21B00010005.pdf PDF
C-121_Add03.pdf PDF
C-504_Add03.pdf PDF
34 71 13.19_Add03.pdf PDF
01 45 00.00 10_Add03.pdf PDF
22 31 00_Add03.pdf PDF
T-121 Add03.pdf PDF
W50S9F21B00010004.pdf PDF
C-141_Add02.pdf PDF
G-011_Add02.pdf PDF
AD101_Add02.pdf PDF
C-101_Add02.pdf PDF
SD111_Add02.pdf PDF
A-201_Add02.pdf PDF
10 28 13_Add02.pdf PDF
A-311_Add02.pdf PDF
Asbestos and Lead Inspection.pdf PDF
Repair Roofs 406 Warranty Cert.pdf PDF
A-401_Add02.pdf PDF
04 20 00_Add02.pdf PDF
A-501_Add02.pdf PDF
A-601_Add02.pdf PDF
02 83 00_Add02.pdf PDF
01 14 00_Add02.pdf PDF
01 11 00_Add02.pdf PDF
W50S9F21B00010003.pdf PDF
10 22 39_Add01.R1.pdf PDF
07 27 26_Add01.R1.pdf PDF
A-131_Add01.R1.pdf PDF
W50S9F21B00010002.pdf PDF
B.07.406 Site Visit Sign In 22Feb21.pdf PDF
B.07.406 Site Visit Sign In 19Feb21.pdf PDF
Pre-Bid Slides - F-35 406.pptx PPTX presentation
W50S9F21B00010001.pdf PDF
W50S9F-21-B-0001.pdf PDF
ATTACHMENT 6-Justification and Approval Monaco.pdf PDF
ATTACHMENT 8-406 Submittal Log.xlsx XLSX spreadsheet
ATTACHMENT 9-SFS Form 12.xls XLS spreadsheet
ATTACHMENT 10-PRE-BID CONFERENCE AND SITE VISIT INSTRUCTIONS.pdf PDF
ATTACHMENT 4-Justification and Approval Advantor.pdf PDF
ATTACHMENT 1-Truax F-35 B406 XGFG182008 Specs Vol 1 of 2 Dated 31 July 2020.pdf PDF
ATTACHMENT 5-Justification and Approval Andover.pdf PDF
Show all 50

F-35 Alter Hangar 406 has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

#3/0 GRD

#3/0 GRD

#2 GRD

#6 GRD

TO TELECOM ROOM

GROUNDING BUSBAR

(TGB)

#3/0 GRD

#3/0 GRD

TO TELECOM ROOM

GROUNDING BUSBAR

(TGB)

CABLE TRAY

TELECOM EQUIPMENT

RACK(S)

MAIN TELECOM ROOM

MAIN GROUNDING BUSBAR (TMGB)

STREET SIDE OF BUILDING

WATER METER. CONNECT TO

METALLIC WATER MAIN

WITHIN 5'-0" OF WATER

SERVICE ENTRANCE.

PROVIDE

JUMPER ACROSS WATER

METER.

MAIN BUILDING GROUND BUS

PROVIDE EXOTHERMIC WELD FOR

CONNECTION OF CONDUCTORS TO

GROUND BUS OR CONDUCTORS CAN BE

ATTACHED USING CRIMPED ON LUGS

(WITH LISTED CRIMPER) AND BOLTED TO

GROUND BUS.

FIRE PUMP MAIN

SERVICE DISCONNECT

NEUTRAL BUS

NOTES:

1. ALL GROUND CONDUCTORS TO BE

ROUTED IN PVC CONDUIT.

2. ALL GROUND CONDUCTORS ON THIS

DIAGRAM SHALL BE COPPER.

#3/0 AWG

BUILDING STEEL

PROVIDE NEW GROUNDING CONNECTION

AT EXISTING BUILDING STEEL IN ELEC 174.

#3/0 GRD

GROUNDING ELECTRODE CONDUCTOR

SIZED PER NEC 250.66.

3/4" X 10'-0" COPPERWELD GROUND

ROD. SEE FLOOR PLANS AND

SPECIFICATION SECTION 26 05 26.

LIGHTNING PROTECTION GROUND

ACCESS WELL.

REMOVABLE LINK

#3/0 GRD

FIRE PUMP MAIN

SERVICE DISCONNECT

GROUND BUS

HANGAR DOOR MAIN

SERVICE DISCONNECT

NEUTRAL BUS

REMOVABLE LINK

#3/0 GRD

HANGAR DOOR MAIN

SERVICE DISCONNECT

GROUND BUS

REMOVABLE LINK

BUILDING MAIN

SERVICE DISCONNECT

NEUTRAL BUS

REMOVABLE LINK

#3/0 GRD

BUILDING MAIN

SERVICE DISCONNECT

GROUND BUS

#3/0 GRD

MAIN DISTRIBUTION PANEL

GROUND BUS

FINISHED FLOOR

46"

18"

POWER, TELEPHONE AND DATA

RECEPTACLES LOCATED IN

OFFICES AND OTHER FINISHED

AREAS UNLESS NOTED

OTHERWISE.

ALL SWITCHES AND WALL MOUNTED

PHONES. POWER RECEPTACLES

LOCATED IN UNFINISHED AREAS

UNLESS NOTED OTHERWISE.

NOTES:

MOUNTING HEIGHT DIMENSION FOR

ELECTRICAL RECEPTACLES AND

VOICE/DATA OUTLETS ABOVE COUNTER IS

HEIGHT AFF TO BOTTOM OF OUTLET BOX.

BOTTOM OF

OUTLET BOX

1.

CONTINUOUS (360 DEGREE) SWIVEL

GROUNDED RETRACTABLE POWER

CORD W/ SINGLE RECEPTACLE ON END.

FURNISHED W/ 12 FT OF 16-3 SJO CORD

(2 CONDUCTORS PLUS GROUND)

ENCLOSED STEEL CONSTRUCTION,

UL LISTED, LOCKING RATCHET TO

HOLD CORD AT DESIRED LENGTH.

MOUNTS ON 4" OCTAGONAL OUTLET BOX

RECEPTACLE (NEMA 5-20R)

(PROVIDED BY MANUFCTURER OF THE EQUIPMENT)

BALL

STOP

FUSED DISC.

SW. BY E.C.

4#12, 3/4"C.

CONTROL PANEL

BY E.S.

HEATER CABLE

CONNECTION IF

DRAWING INDICATES

NECESSARY

5#16, 3/4"C.

OPEN/CLOSE

PUSH BUTTON

ONE EACH

SIDE BY E.S.

NEMA L6-30 SPECIAL

PURPOSE RECEPTACLE

(TYP.)

U-CHANNEL STRUT

1/2" ALL-THREAD

SUPPORT

EMT CONDUIT

SUPPORTED TO

CEILING

2" 2"18" DIA.

GROUND

PAINT THE WORD "GROUND" IN 1"

BLACK LETTERS AND THE DATE

TESTED IN 1/2" BLACK LETTERS

PAINT RED

PAINT YELLOW

GROUND

RECEPTACLE SET IN

FLOOR

PLAN

3/4"

2-3/4" DIA.

-7

/8

M

IN

F

O R

H A

N G

A R

S

CAST BRONZE COVER,

FRICTION FIT BRASS PIN

CAST BRONZE HOUSING.

IN HANGARS, MAX. RESISTANCE TO

GROUND SHALL BE 25 OHMS FROM

ANY GROUND ROD.

3/4" N.C. THREAD.

3/4" PIPE OR ROD FOR

HANGARS. 3/4" COPPER-

WELD GROUND ROD FOR

HYDRANT REFUELING.

#10 BRASS BALL CHAIN.

FINISHED HANGAR FLOOR

OR APRON PAVEMENT.

ELEVATION

NOTE:

DRILL INTO HANGAR FLOOR

AS REQUIRED.

DOWN CONDUCTOR

GROUND ROD

GROUND ROD

CLAMP

TEST WELL. SEE

DETAIL 8/E-501.

1' MIN.

2' MIN.

OPEN SCHEDULE 80 1" PVC

FURNISHED/INSTALLED BY

EC.

GROUND CLAMP

GROUND ROD

POLYMER CONCRETE

FIBERGLASS REINFORCED

BOX

COVER REFERENCED

ABOVE (TOP VIEW)

GRAVEL OR

CRUSHED STONE

GROUNDING

CONDUCTOR #1/0

COPPER

TOP VIEW (COVER REMOVED)

A A

SECTION A - A

M

IN

24" MIN

UNIVERSAL FLAT SURFACE AIR

TERMINAL BASE MOUNTED

VERTICALLY

CUAT / ALAT - STYLE GENTLY

TAPERED AIR TERMINAL

ALUMINUM UNIVERSAL BASE

MOUNTED WITH STAINLESS

STEEL FASTNERS

CLASS I ALUMINUM

LIGHTNING CONDUCTOR

(24 STRANDS OF 14 AWG

WIRES 98 LBS. PER 1000')

ALUMINUM CABLE

CLIP WITH STAINLESS STEEL

FASTNER - EVERY 3' MAX.

1/2" X 1/2" GENTLY

TAPERED ALUMINUM AIR

TERMINAL

CUAT / ALAT - STYLE GENTLY

TAPERED AIR TERMINAL

UNIVERSAL SWIVEL AIR

TERMINAL BASE

COPPER OR ALUMINUM,

CLASS I OR CLASS II

LIGHTNING PROTECTION

CONDUCTOR

ADHESIVE

CABLE FASTENER

CABLE FASTENER

COPPER OR ALUMINUM

CLASS I OR CLASS II

LIGHTNING PROTECTION

CONDUCTOR

EXTERIOR WALL

M

IN

M

IN

OPEN SCHEDULE 80 1"

PVC

FURNISHED/INSTALLED

BY EC.

EXTERIOR WALL

CAPPING/COPPING

DOWN CONDUCTOR

ROOF SURFACE

ANGLE OF BEND NOT LESS

THAN 90 DEGREES.

RADIUS OF BEND NOT

LESS THAN 8".

DOWN CONDUCTOR

OPEN SCHEDULE 80 1" PVC

FURNISHED/INSTALLED BY EC.

ANGLE OF BEND NOT LESS

THAN 90 DEGREES. RADIUS

OF BEND NOT LESS THAN 8".

GROUND SURFACE

6" ENGINEERED FILL

PREPARED SUBGRADE

CONCRETE PAD WITH #5 AT 12"OC,

EACH WAY TOP AND BOTTOM.

PROVIDE A MINIMUM 3" REBAR

CLEARANCE, TYPICAL. THE TOP

OF THE SLAB SHALL BE A MINIMUM

OF 8" ABOVE ADJACENT GRADE.

PROVIDE MINIMUM 3" CONCRETE

COVER FOR ALL REBAR.

NOTES:

1. TOP OF CONCRETE SLAB MUST BE 8" ABOVE FINISHED GRADE WITH GRADUAL

SLOPE FOR DRAINAGE. WHERE APPLICABLE SLOPE SHALL BE AWAY FROM

BUILDING. EDGES ABOVE GRADE MUST HAVE 1/2" CHAMFER. SLAB SHALL BE OF

ADEQUATE SIZE TO PROJECT AT LEAST 8" BEYOND THE EQUIPMENT ON ALL SIDES.

2. STUB CONDUITS, WITH BUSHINGS, 6" ABOVE TOP OF CONCRETE SLAB. COORDINATE

CONDUIT LOCATIONS WITH EQUIPMENT CABLE ENTRANCE AREAS.

2 HOUR CONCRETE

OR CONCRETE BLOCK WALL

OR 1 HOUR GYPSUM

WALL ASSEMBLY

MINERAL WOOL BATT

INSULATION

(2 HOUR WALL ONLY)

4" DIAMETER

(OR SMALLER)

CONTINUOUS

METAL CONDUIT

STEEL SLEEVE

FIRE STOP SEALANT

SPEC SEAL SSS SEALANT

BY SPECIFIED TECHNOLOGIES.INC,

1"DEPTH ON BOTH SIDES.

NOTE:

SEE SHEET G101 FOR BUILDING WALL RATINGS

(UL SYSTEMS WL1171 FOR 1-HOUR GYPSUM WALL)

(UL SYSTEMS WJ1070 FOR 2-HOUR CONCRETE WALL)

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

Mead & Hunt, Inc.

2440 Deming Way

Middleton, WI 53562 phone: 608-273-6380 meadhunt.com

/2

/2

:3

:1

P M

C R e v it L o c a l\

-1

.0

-E -C e n tr a l-m a tt .f ir k u s m e a d h u n t.

c o m

.r v t

T R

U A

X F

IE

L D

A N

G B

M A

D

IS

O N

W

I

F -3

A L T

E R

B U

IL

D

IN

G

E-501

DETAILS

XGFG182008ANG NO.:

3141300-190289.01

MRF

ARG

July 31, 2020

MRF

NO SCALE1

GROUNDING SYSTEM DETAIL (TYP)

NO SCALE5

DEVICE MOUNTING HEIGHT

NO SCALE3

CORD REEL DETAIL

NO SCALE4

MOTORIZED ROLL-UP DOOR WITH

PUSH BUTTON CONTROL

NO SCALE2

RACK RECEPTACLE DETAIL

NO SCALE6

STATIC GROUND RECEPTACLE

NO SCALE7

GROUND ROD DETAIL

NO SCALE8

GROUND ACCESS WELL - DETAIL

NO SCALE9

AIR TERMINAL BASE

NO SCALE10

AIR TERMINAL BASE

NO SCALE11

CABLE FASTENER

NO SCALE12

CABLE FASTENER

NO SCALE13

CABLE FASTENER

NO SCALE14

BONDING CONNECTOR

NO SCALE15

CONCEALED PVC DETAIL

07/31/20 TYPE B3 FINAL

2 03/03/21 ADDENDUM - 02

NO SCALE16

EQUIPMENT PAD DETAIL

NO SCALE17

FIRESTOP WALL PENETRATION

Sheets
E-501 - DETAILS

File details come from the government source that posted it. Updated .