04_25R1303_09 29 00_AMD0011.pdf
PDF 72 KB Posted
- Attached to
- FY24 MCON P-614 JOINT CONSOLIDATED COMMUNICATIONS CENTER, US JOINT REGION MARIANAS, ANDERSEN, GUAM
- Solicitation number
- N6274225R1303
About this file
This document is a technical specification section (Section 09 29 00) for Gypsum Board installation for the FY24 MCON P-614 Joint Consolidated Communications Center project at Andersen Air Force Base, Joint Region Marianas, Guam. The specification provides detailed requirements for gypsum board materials, including glass mat covered gypsum board, abuse-resistant gypsum board, joint treatment materials, and accessories, with extensive technical standards from ASTM, ANSI, and other industry organizations.
Key technical requirements include using gypsum board with minimum recycled content, meeting indoor air quality certifications, and following specific installation and finishing procedures. The specification mandates precise application methods, such as proper framing, board placement, joint treatment, and finishing to different levels depending on the intended surface treatment. Special attention is given to fire-resistant and sound-rated assemblies, with requirements for sealing, patching, and third-party sound rating field testing to ensure compliance with acoustic performance standards.
View the file
Other files
Show 40 more
Latest 50 of 89 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY24 MCON P-614 JOINT CONSOLIDATED COMMUNICATIONS CENTER 1737021
JOINT REGION MARIANAS, ANDERSEN AIR FORCE BASE
SECTION 09 29 00
GYPSUM BOARD
08/16, CHG 4: 02/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI A108.11 (1992; Reaffirmed 2005) Specifications for Interior Installation of Cementitious Backer Units
ASTM INTERNATIONAL (ASTM)
ASTM C475/C475M (2017; R 2022) Standard Specification for Joint Compound and Joint Tape for Finishing Gypsum Board
ASTM C840 (2023) Standard Specification for Application and Finishing of Gypsum Board
ASTM C954 (2022) Standard Specification for Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to
0.112 in. (2.84 mm) in Thickness
ASTM C1002 (2022) Standard Specification for Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
ASTM C1047 (2019) Standard Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base
ASTM C1396/C1396M (2017) Standard Specification for Gypsum Board
ASTM C1629/C1629M (2023) Standard Classification for Abuse-Resistant Nondecorated Interior Gypsum Panel Products and Fiber-Reinforced Cement Panels
ASTM D226/D226M (2017) Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing
ASTM D1037 (2012) Evaluating Properties of Wood-Base Fiber and Particle Panel Materials
SECTION 09 29 00 Page 1
Amendment 0011 09 29 00 GYPSUM BOARD, dated May 7, 2025
ASTM D2394 (2017) Standard Test Methods for Simulated Service Testing of Wood and Wood-Base Finish Flooring
ASTM D3273 (2021) Standard Test Method for Resistance to Growth of Mold on the Surface of Interior Coatings in an Environmental Chamber
ASTM D5420 (2016) Standard Test Method for Impact Resistance of Flat, Rigid Plastic Specimen by Means of a Strike Impacted by a Falling Weight (Gardner Impact)
ASTM E84 (2023) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E90 (2009; R2016) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements
ASTM E336 (2023) Standard Test Method for Measurement of Airborne Sound Attenuation between Rooms in Buildings
ASTM E695 (2022) Standard Test Method of Measuring Relative Resistance of Wall, Floor, and Roof Construction to Impact Loading
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2017; Version 1.2) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
GYPSUM ASSOCIATION (GA)
GA 214 (2010) Recommended Levels of Gypsum Board Finish
GA 216 (2016) Application and Finishing of Gypsum Panel Products
GA 253 (2012) Application of Gypsum Sheathing
GA 600 (2015) Fire Resistance Design Manual Sound
SECTION 09 29 00 Page 2
Control
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2022) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
UL Fire Resistance (2014) Fire Resistance Directory
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Cementitious Backer Units
Glass Mat Covered Gypsum Board
Abuse Resistant Glass Mat Covered Gypsum Board
Accessories
Submit for each type of gypsum board and for cementitious backer units.
Recycled Content for Gypsum Board; S
SD-06 Test Reports
ASTM E90 Factory Test Report; G
ASTM E336 Field Test Report; G
SD-07 Certificates
Asbestos Free Materials; G
Certify that gypsum board types, gypsum backing board types, cementitious backer units, and joint treating materials do not contain asbestos.
Indoor Air Quality for Gypsum Board; S
Indoor Air Quality for Joint Compound; S
Indoor Air Quality for Non-aerosol Adhesives; S
SECTION 09 29 00 Page 3
Indoor Air Quality for Aerosol Adhesives; S
SD-08 Manufacturer's Instructions
Safety Data Sheets
SD-10 Operation and Maintenance Data
Manufacturer Maintenance Instructions
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality Certifications
Submit required indoor air quality certifications in one submittal package.
1.3.1.1 Ceiling and Wall Systems
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.3.1.2 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 DELIVERY, STORAGE, AND HANDLING
1.4.1 Delivery
Deliver materials in the original packages, containers, or bundles with each bearing the brand name, applicable standard designation, and name of manufacturer, or supplier.
1.4.2 Storage
Keep materials dry by storing inside a sheltered building. Where necessary to store gypsum board and cementitious backer units outside, store off the ground, properly supported on a level platform, and protected from direct exposure to rain, snow, sunlight, and other extreme weather conditions. Provide adequate ventilation to prevent condensation. Store per manufacturer's recommendations for allowable temperature and humidity range. Do not store gypsum wallboard with materials which have high emissions of volatile organic compounds (VOCs) or other contaminants. Do not store panels near materials that may offgas or emit harmful fumes, such as kerosene heaters, fresh paint, or adhesives. Do not use materials that have visible moisture or biological growth.
SECTION 09 29 00 Page 4
1.4.3 Handling
Neatly stack gypsum board and cementitious backer units flat to prevent sagging or damage to the edges, ends, and surfaces.
1.5 QUALIFICATIONS
Furnish type of gypsum board work specialized by the installer with a minimum of 3 years of documented successful experience.
1.6 SCHEDULING
The gypsum wallboard must be taped, finished and primed before the installation of the highly-emitting materials. The gypsum wallboard must be installed after the installation and ventilation period of the highly-emitting materials.
Commence application only after the area scheduled for gypsum board work is completely weathertight. The heating, ventilating, and air-conditioning systems must be complete and in operation prior to application of the gypsum board. If the mechanical system cannot be activated before gypsum board is begun, the gypsum board work may proceed in accordance with an approved plan to maintain the environmental conditions specified below. Apply gypsum board prior to the installation of finish flooring and acoustic ceiling.
1.7 ENVIRONMENTAL REQUIREMENTS
Do not expose the gypsum board to excessive sunlight prior to gypsum board application. Maintain a continuous uniform temperature of not less than 50 degrees F and not more than 80 degrees F for at least one week prior to the application of gypsum board work, while the gypsum board application is being done, and for at least one week after the gypsum board is set.
Shield air supply and distribution devices to prevent any uneven flow of air across the plastered surfaces. Provide ventilation to exhaust moist air to the outside during gypsum board application, set, and until gypsum board jointing is dry. In glazed areas, keep windows open top and bottom or side to side 3 to 4 inches. Reduce openings in cold weather to prevent freezing of joint compound when applied. For enclosed areas lacking natural ventilation, provide temporary mechanical means for ventilation.
In unglazed areas subjected to hot, dry winds or temperature differentials from day to night of 20 degrees F or more, screen openings with cheesecloth or similar materials. Avoid rapid drying. During periods of low indoor humidity, provide minimum air circulation following gypsum boarding and until gypsum board jointing complete and is dry.
1.8 FIRE RESISTIVE CONSTRUCTION
Comply with specified fire-rated assemblies for design numbers indicated per UL Fire Resistance or FM APP GUIDE.
PART 2 PRODUCTS
2.1 MATERIALS
Conform to specifications, standards and requirements specified. Provide gypsum board types, gypsum backing board types, cementitious backing units, and joint treating materials manufactured from asbestos free
SECTION 09 29 00 Page 5 materials only. Submit Safety Data Sheets and manufacturer maintenance instructions for gypsum materials including adhesives.
2.1.1 Glass Mat Covered Gypsum Board
ASTM C1396/C1396M . Gypsum board must contain a minimum of 10 percent post-consumer recycled content, or a minimum of 40 percent post-industrial recycled content. Provide data identifying percentage of recycled content for gypsum board. Provide gypsum wall board and panels meeting the emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type). Provide certification or validation of indoor air quality for gypsum board.
2.1.1.1 Type X (Special Fire-Resistant)
48 inch wide, 5/8 inch thick, tapered and featured edges.
2.1.1.2 Mold Resistant / Anti-Microbial Gypsum
ASTM D3273. 48 inch wide, 5/8 inch thick, tapered and featured edges.
2.1.2 Abuse Resistant Glass Mat Covered Gypsum Board
48 inch wide, 5/8 inch thick, tapered edges.
Reinforced gypsum panel with imbedded fiber mesh or lexan backing tested in accordance with the following tests. Hard body impact test must attain a Level 2 performance in accordance with ASTM C1629/C1629M . Provide fasteners that meet manufacturer requirements and specifications stated within this section. Abuse resistant gypsum board, when tested in accordance with ASTM E84, have a flame spread rating of 25 or less and a smoke developed rating of 50 or less.
2.1.2.1 Soft Body Impact Test
ASTM E695 or ASTM D2394 for impact penetration and deformation. ASTM E695 using a 60 lb leather bag filled with steel pellets, resisting no less than 300 ft. lb. cumulative impact energy before failure or ASTM D2394 using
5.5 inch hemispherical projectile resisting no less than 264 ft. lb.
before failure. Provide test specimen stud spacing a minimum 16 inch on center.
2.1.2.2 Hard Body Impact Test
Comply with hard body impact test in accordance with ASTM C1629/C1629M Classification Level 2.
2.1.2.3 Surface Abrasion Test
Comply with test surface abrasion test in accordance with ASTM C1629/C1629M .
2.1.2.4 Indentation Test
ASTM D5420 or ASTM D1037 for indentation resistance. ASTM D5420 using a 32 oz weight with a 5/8 inch hemispherical impacting head dropped once 3 feet creating not more than 0.137 inch indentation or ASTM D1037 using no less than 470 lb weight applied to the 0.438 inch diameter ball to create not more than a 0.0197 inch indentation depth.
SECTION 09 29 00 Page 6
2.1.3 Factory-Laminated Gypsum Board
2.1.3.1 ASTM E90 Factory Test Report
Submit Factory Test Report for proposed STC Rated wall assembly. Test reports must be prepared by an independent acoustical laboratory qualified under the National Voluntary Laboratory Accreditation Program (NVLAP) by the National Institute for Science and Technology (NIST). Test reports must indicate that the sound transmission classification (STC) of the proposed wall and ceiling assembly, based on tests at 16 third-octave band frequencies from 125 to 4,000 hertz, is no less than STC 50 for STC 45 assemblies and no less than STC 55 for STC 50 assemblies when tested in accordance with ASTM E90.
2.1.4 Cementitious Backer Units
In accordance with the Tile Council of America (TCA) Handbook.
2.1.5 Joint Treatment Materials
ASTM C475/C475M. Product must be low emitting VOC types with VOC limits not exceeding 50 g/L. Use all purpose joint and texturing compound containing inert fillers and natural binders, including lime compound.
Pre-mixed compounds must be free of antifreeze, vinyl adhesives, preservatives, biocides and other slow releasing compounds. Provide joint compound materials meeting the emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces reqardless of space type). Provide certification or validation of indoor air quality for joint compound.
2.1.5.1 Embedding Compound
Specifically formulated and manufactured for use in embedding tape at gypsum board joints and compatible with tape, substrate and fasteners.
2.1.5.2 Finishing or Topping Compound
Specifically formulated and manufactured for use as a finishing compound.
2.1.5.3 All-Purpose Compound
Specifically formulated and manufactured to serve as both a taping and a finishing compound and compatible with tape, substrate and fasteners.
2.1.5.4 Setting or Hardening Type Compound
Specifically formulated and manufactured for use with fiber glass mesh tape.
2.1.5.5 Joint Tape
Use cross-laminated, tapered edge, reinforced paper, or fiber glass mesh tape recommended by the manufacturer.
2.1.6 Fasteners
2.1.6.1 Screws
ASTM C1002, Type "G" or Type "S" steel drill screws for fastening gypsum
SECTION 09 29 00 Page 7 board to gypsum board, and steel framing members less than 0.033 inch thick. ASTM C954 steel drill screws for fastening gypsum board to steel framing members 0.033 to 0.112 inch thick. Provide cementitious backer unit screws with a polymer coating.
2.1.7 Adhesives
Provide non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 . Provide aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of GS-36. Provide certification or validation of indoor air quality for non-aerosol adhesives applied on the interior of the building (inside of the weatherproofing system). Provide certification or validation of indoor air quality for aerosol adhesives used on the interior of the building (inside of the weatherproofing system).
2.1.8 Shaftwall Liner Panel
ASTM C1396/C1396M . Conform to the UL Fire Resistance for the Design Numbers(s) indicated for shaftwall liner panels. Manufacture liner panel for cavity shaftwall system, with water-resistant paper faces, bevel edges, single lengths to fit required conditions, 1 inch thick, by 24 inch wide.
2.1.9 Accessories
ASTM C1047. Fabricate from corrosion protected steel or plastic designed for intended use. Accessories manufactured with paper flanges are not acceptable. Flanges must be free of dirt, grease, and other materials that may adversely affect bond of joint treatment. Provide prefinished or job decorated materials.
2.1.10 Asphalt Impregnated Building Felt
Provide a 15 lb asphalt moisture barrier over glass mat covered gypsum board. Conforming to ASTM D226/D226M Type 1 (No. 15) for asphalt impregnated building felt.
2.1.11 Water
Provide clean, fresh, and potable water.
PART 3 EXECUTION
3.1 EXAMINATION
3.1.1 Framing and Furring
Verify that framing and furring are securely attached and of sizes and spacing to provide a suitable substrate to receive gypsum board and cementitious backer units. Verify that all blocking, headers and supports are in place to support plumbing fixtures and to receive soap dishes, grab bars, towel racks, and similar items. Do not proceed with work until
SECTION 09 29 00 Page 8 framing and furring are acceptable for application of gypsum board and cementitious backer units.
3.1.2 Building Construction Materials
Do not install building construction materials that show visual evidence of biological growth.
3.2 APPLICATION OF GYPSUM BOARD
Apply gypsum board to framing and furring members in accordance with ASTM C840 or GA 216 and the requirements specified. Apply gypsum board with separate panels in moderate contact; do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints.
Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings. In vertical application of gypsum board, provide panels in lengths required to reach full height of vertical surfaces in one continuous piece. Lay out panels to minimize waste; reuse cutoffs whenever feasible. Surfaces of gypsum board and substrate members may not be bonded together with an adhesive. Treat edges of cutouts for plumbing pipes, screwheads, and joints with water-resistant compound as recommended by the gypsum board manufacturer. Minimize framing by floating corners with single studs and drywall clips. Provide type of gypsum board for use in each system specified herein as indicated.
3.2.1 Application of Gypsum Board to Steel Framing and Furring
Apply in accordance with ASTM C840, System VIII or GA 216 .
3.2.2 Glass Mat Covered or Fiber Reinforced Gypsum Sheathing
Apply glass mat covered or fiber reinforced gypsum sheathing in accordance to gypsum association publications GA 253 . Follow gypsum sheathing manufacturer's requirements of design details for joints and fasteners and be properly installed to protect the substrate from moisture intrusion.
Do not leave exposed surfaces of the glass mat covered or fiber reinforced gypsum sheathing beyond the manufacturer's recommendation without a weather barrier cladding. Provide continuous asphalt impregnated building felt over sheathing surface in shingle fashion with edges and ends lapped a minimum of 6 inch. Properly flash the openings. Seal all joints, seams, and penetrations with a compatible silicone sealant.
3.2.3 Control Joints
Install expansion and contraction joints in ceilings and walls in accordance with ASTM C840, System XIII or GA 216 . Fill control joints between studs in fire-rated construction with firesafing insulation to match the fire-rating of construction.
3.2.4 Application of Abuse Resistant Gypsum Board
Apply in accordance with applicable system of ASTM C840 as specified or GA 216 . Follow manufacturers written instructions on how to cut, drill and attach board.
SECTION 09 29 00 Page 9
3.3 APPLICATION OF CEMENTITIOUS BACKER UNITS
3.3.1 Application
In wet areas (tubs, shower enclosures, gang shower rooms), apply cementitious backer units in accordance with ANSI A108.11 . Place a 15 lb asphalt impregnated, continuous felt paper membrane behind cementitious backer units, between backer units and studs or base layer of gypsum board. Place membrane with a minimum 6 inch overlap of sheets laid shingle style.
3.3.2 Joint Treatment
ANSI A108.11 .
3.4 FINISHING OF GYPSUM BOARD
Tape and finish gypsum board in accordance with ASTM C840, GA 214 and GA 216 . Finish plenum areas above ceilings to Level 1 in accordance with GA 214 . Finish water resistant gypsum backing board, ASTM C1396/C1396M , to receive ceramic tile to Level 2 in accordance with GA 214 . Finish walls and ceilings to receive a heavy-grade wall covering or heave textured finish before painting to Level 3 in accordance with GA 214 .
Finish walls and ceilings without critical lighting to receive flat paints, light textures, or wall coverings to Level 4 in accordance with GA 214 . Unless otherwise specified, finish all gypsum board walls, partitions and ceilings to Level 5 in accordance with GA 214 . Provide joint, fastener depression, and corner treatment. Tool joints as smoothly as possible to minimize sanding and dust. Do not use self-adhering fiber glass mesh tape with conventional drying type joint compounds; use setting or hardening type compounds only. Provide treatment for water-resistant gypsum board as recommended by the gypsum board manufacturer. Protect workers, building occupants, and HVAC systems from gypsum dust.
3.4.1 Uniform Surface
Wherever gypsum board is to receive eggshell, semigloss or gloss paint finish, or where severe, up or down lighting conditions occur, finish gypsum wall surface in accordance to GA 214 Level 5. In accordance with GA 214 Level 5, apply a thin skim coat of joint compound to the entire gypsum board surface, after the two-coat joint and fastener treatment is complete and dry.
3.5 SEALING
Seal openings around pipes, fixtures, and other items projecting through gypsum board and cementitious backer units as specified in Section 07 92 00 JOINT SEALANTS. Apply material with exposed surface flush with gypsum board or cementitious backer units.
3.5.1 Sealing for Glass Mat Covered Gypsum Board
Apply silicone sealant in a 3/8 inch bead to all joints and trowel flat.
Apply enough of the same sealant to all fasteners penetrating through the glass mat gypsum board surface to completely cover the penetration when troweled flat.
SECTION 09 29 00 Page 10
3.6 FIRE-RESISTANT ASSEMBLIES
Wherever fire-rated construction is indicated, provide materials and application methods, including types and spacing of fasteners, wall and ceiling framing in accordance with the specifications contained in UL Fire Resistance for the Design Number(s) indicated, or GA 600 for the File Number(s) indicated. Joints of fire-rated gypsum board enclosures must be closed and sealed in accordance with UL test requirements or GA requirements. Seal penetrations through rated partitions and ceilings tight in accordance with tested systems.
3.7 SOUND RATED ASSEMBLIES
When sound rated assemblies are required, provide materials and application methods, including panels, insulation, types and spacing of fasteners, wall and ceiling framing in accordance with the contract document and the description of the assembly in the ASTM E90 Factory Test Report. Seal partitions continuously with acoustical foam or sealant (both sides) and finished to match wall wherever it abuts another element such as the floor, ceiling, wall, column, mullion, or another system or assembly.
3.8 PATCHING
Patch surface defects in gypsum board to a smooth, uniform appearance, ready to receive finishes.
3.9 SHAFTWALL FRAMING
Install the shaftwall system in accordance with the system manufacturer's published instructions. Coordinate bucks, anchors, blocking and other items placed in or behind shaftwall framing with electrical and mechanical work. Patch or replace fireproofing materials which are damaged or removed during shaftwall construction.
3.10 SOUND RATED ASSEMBLY FIELD TESTING
Provide third party testing of sound rated assemblies tested in accordance with ASTM E336. Provide the ASTM E336 Field Test Report verifying that the installed assemblies perform no less than five ASTC rating points below the ASTM E90 Factory Test Report. Examine, modify adjust, and retest any installation not meeting the STC Rating until compliance is obtained.
-- End of Section --
SECTION 09 29 00 Page 11
| 09 29 00 - GYPSUM BOARD |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 CERTIFICATIONS |
| 1.3.1 Indoor Air Quality Certifications |
| 1.3.1.1 Ceiling and Wall Systems |
| 1.3.1.2 Adhesives and Sealants |
| 1.4 DELIVERY, STORAGE, AND HANDLING |
| 1.4.1 Delivery |
| 1.4.2 Storage |
| 1.4.3 Handling |
| 1.5 QUALIFICATIONS |
| 1.6 SCHEDULING |
| 1.7 ENVIRONMENTAL REQUIREMENTS |
| 1.8 FIRE RESISTIVE CONSTRUCTION |
| PART 2 PRODUCTS |
| 2.1 MATERIALS |
| 2.1.1 Glass Mat Covered Gypsum Board |
| 2.1.1.1 Type X Special Fire-Resistant |
| 2.1.1.2 Mold Resistant / Anti-Microbial Gypsum |
| 2.1.2 Abuse Resistant Glass Mat Covered Gypsum Board |
| 2.1.2.1 Soft Body Impact Test |
| 2.1.2.2 Hard Body Impact Test |
| 2.1.2.3 Surface Abrasion Test |
| 2.1.2.4 Indentation Test |
| 2.1.3 Factory-Laminated Gypsum Board |
| 2.1.3.1 ASTM E90 Factory Test Report |
| 2.1.4 Cementitious Backer Units |
| 2.1.5 Joint Treatment Materials |
| 2.1.5.1 Embedding Compound |
| 2.1.5.2 Finishing or Topping Compound |
| 2.1.5.3 All-Purpose Compound |
| 2.1.5.4 Setting or Hardening Type Compound |
| 2.1.5.5 Joint Tape |
| 2.1.6 Fasteners |
| 2.1.6.1 Screws |
| 2.1.7 Adhesives |
| 2.1.8 Shaftwall Liner Panel |
| 2.1.9 Accessories |
| 2.1.10 Asphalt Impregnated Building Felt |
| 2.1.11 Water |
| PART 3 EXECUTION |
| 3.1 EXAMINATION |
| 3.1.1 Framing and Furring |
| 3.1.2 Building Construction Materials |
| 3.2 APPLICATION OF GYPSUM BOARD |
| 3.2.1 Application of Gypsum Board to Steel Framing and Furring |
| 3.2.2 Glass Mat Covered or Fiber Reinforced Gypsum Sheathing |
| 3.2.3 Control Joints |
| 3.2.4 Application of Abuse Resistant Gypsum Board |
| 3.3 APPLICATION OF CEMENTITIOUS BACKER UNITS |
| 3.3.1 Application |
| 3.3.2 Joint Treatment |
| 3.4 FINISHING OF GYPSUM BOARD |
| 3.4.1 Uniform Surface |
| 3.5 SEALING |
| 3.5.1 Sealing for Glass Mat Covered Gypsum Board |
| 3.6 FIRE-RESISTANT ASSEMBLIES |
| 3.7 SOUND RATED ASSEMBLIES |
| 3.8 PATCHING |
| 3.9 SHAFTWALL FRAMING |
| 3.10 SOUND RATED ASSEMBLY FIELD TESTING |
File details come from the government source that posted it. Updated .