This document is a technical specification section (Section 08 91 00) for Metal Wall Louvers for the FY24 MCON P-614 Joint Consolidated Communications Center at Andersen Air Force Base in Guam. The specification details requirements for wind-resistant metal wall louvers made of Type 316 stainless steel or aluminum, with specific performance standards including a wind load resistance of at least 30 pounds per square foot and water penetration rating of 0.20 ounces or less per square foot of free area.
Key technical requirements include 18-by-16 mesh stainless steel insect screening, removable and rewirable screen frames, mullions for louvers over 5 feet wide, and a superior performance organic coating finish with a total dry film thickness of at least 1.2 mils. The specification provides detailed instructions for material selection, fabrication, installation, and protection of louvers, including guidelines for handling dissimilar materials to prevent corrosion and ensure proper performance. Sustainability considerations are also addressed, with provisions for documenting recycled content of the wall louvers.
View the file
Other files
Show 40 more
Latest 50 of 89 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY24 MCON P-614 JOINT CONSOLIDATED COMMUNICATIONS CENTER 1737021
JOINT REGION MARIANAS, ANDERSEN AIR FORCE BASE
SECTION 08 91 00
METAL WALL LOUVERS
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. (AMCA)
AMCA 500-L (2015) Laboratory Methods of Testing Louvers for Rating
AMCA 511 (2010; R 2016) Certified Ratings Program for Air Control Devices
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 2605 (2020) Voluntary Specification, Performance Requirements and Test Procedures for Superior Performing Organic Coatings on Aluminum Extrusions and Panels
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Wall Louvers; G
SD-03 Product Data
Recycled Content for Wall Louvers; S
Metal Wall Louvers
SD-04 Samples
Wall Louver Samples; G
1.3 DELIVERY, STORAGE, AND PROTECTION
Deliver materials to the site in an undamaged condition. Carefully store materials off the ground to provide proper ventilation, drainage, and protection against dampness. Louvers must be free from nicks, scratches, and blemishes. Replace defective or damaged materials with new.
SECTION 08 91 00 Page 1
Amendment 0015 08 91 00 METAL WALL LOUVERS, dated May 15, 2025
1.4 DETAIL DRAWINGS
Show all information necessary for fabrication and installation of wall louvers. Indicate materials, sizes, thicknesses, fastenings, and profiles.
1.5 COLOR SAMPLES
Colors of finishes for wall louver samples must closely approximate colors indicated. Where color is not indicated, submit the manufacturer's standard colors to the Contracting Officer for selection.
PART 2 PRODUCTS
2.1 PRODUCT SUSTAINABILITY CRITERIA
For products in this section, where applicable and to extent allowed by performance criteria, provide and document the following:
2.1.1 Recycled Content for Wall Louvers
Recycled content is identified for some products in this section; provide documentation in accordance with Section 01 33 29 SUSTAINABILITY REQUIREMENTS AND REPORTING paragraph RECYCLED CONTENT. Other products listed in this section may be available with recycled content; identify those products that meet project requirements for recycled content, and provide documentation in accordance with Section 01 33 29 SUSTAINABILITY REQUIREMENTS AND REPORTING paragraph RECYCLED CONTENT.
2.2 MATERIALS
2.2.1 Stainless Steel
Type 316, with 2B finish.
2.3 METAL WALL LOUVERS
Wind resistant type, with insect screens and made to withstand a wind load of not less than 30 pounds per square foot . Wall louvers must bear the AMCA certified ratings program seal for air performance and water penetration in accordance with AMCA 500-L and AMCA 511. The rating must show a water penetration of 0.20 or less ounce per square foot of free area at a free velocity of 800 feet per minute.
2.3.1 Formed Metal Louvers
Formed of Type 316 stainless steel sheet not thinner than 16 U.S. gage, or aluminum sheet not less than 0.08 inch thick.
2.3.2 Mullions and Mullion Covers
Same material and finish as louvers. Provide mullions for all louvers more than 5 feet in width at not more than 5 feet on centers. Provide mullion covers on both faces of joints between louvers.
2.3.3 Screens and Frames
For stainless steel louvers, provide 18-by-16 mesh, 0.011 inch Type 316 stainless steel insect screening. Mount screens in removable, rewirable frames of same material and finish as the louvers.
SECTION 08 91 00 Page 2
2.4 FASTENERS AND ACCESSORIES
Provide Type 316 stainless steel screws and fasteners for stainless steel louvers. Provide other accessories as required for complete and proper installation.
2.5 FINISHES
2.5.1 Stainless Steel
Exposed stainless steel surfaces must be factory finished with an organic coating. Color must be as indicated. Louvers must have the same finish.
2.5.1.1 Organic Coating
Clean and prime exposed surfaces. Provide a superior performance finish in accordance with AAMA 2605 with a total dry film thickness of not less than 1.2 mils.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Wall Louvers
Install using stops or moldings, flanges, strap anchors, or jamb fasteners as appropriate for the wall construction and in accordance with manufacturer's recommendations.
3.1.2 Screens and Frames
Attach frames to louvers with screws or bolts.
3.2 PROTECTION FROM CONTACT OF DISSIMILAR MATERIALS
3.2.1 Copper or Copper-Bearing Alloys
Paint copper or copper-bearing alloys in contact with dissimilar metal with heavy-bodied bituminous paint or separate with inert membrane.
3.2.2 Aluminum
Where aluminum contacts metal other than zinc, paint the dissimilar metal with a primer and two coats of aluminum paint.
3.2.3 Metal
Paint metal in contact with mortar, concrete, or other masonry materials with alkali-resistant coatings such as heavy-bodied bituminous paint.
3.2.4 Wood
Paint wood or other absorptive materials that may become repeatedly wet and in contact with metal with two coats of aluminum paint or a coat of heavy-bodied bituminous paint.
-- End of Section --
SECTION 08 91 00 Page 3
| 08 91 00 - METAL WALL LOUVERS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 DELIVERY, STORAGE, AND PROTECTION |
| 1.4 DETAIL DRAWINGS |
| 1.5 COLOR SAMPLES |
| PART 2 PRODUCTS |
| 2.1 PRODUCT SUSTAINABILITY CRITERIA |
| 2.1.1 Recycled Content for Wall Louvers |
| 2.2 MATERIALS |
| 2.2.1 Stainless Steel |
| 2.3 METAL WALL LOUVERS |
| 2.3.1 Formed Metal Louvers |
| 2.3.2 Mullions and Mullion Covers |
| 2.3.3 Screens and Frames |
| 2.4 FASTENERS AND ACCESSORIES |
| 2.5 FINISHES |
| 2.5.1 Stainless Steel |
| 2.5.1.1 Organic Coating |
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.1.1 Wall Louvers |
| 3.1.2 Screens and Frames |
| 3.2 PROTECTION FROM CONTACT OF DISSIMILAR MATERIALS |
| 3.2.1 Copper or Copper-Bearing Alloys |
| 3.2.2 Aluminum |
| 3.2.3 Metal |
| 3.2.4 Wood |
File details come from the government source that posted it. Updated .