This document is a technical specification section (07 60 00) for Flashing and Sheet Metal for the FY24 MCON P-614 Joint Consolidated Communications Center project at Andersen Air Force Base in Guam. The specification provides detailed requirements for sheet metal materials, installation methods, and quality control, focusing on materials like stainless steel, aluminum, and associated components such as downspouts, strainers, and fasteners. The document specifies precise technical standards, including material thicknesses, joint types, welding procedures, and installation techniques, with references to various industry standards from organizations like ASTM, AWS, and SMACNA.
Key technical requirements include using stainless steel or aluminum materials with specific gauges and finishes, implementing weathertight assemblies with proper expansion and contraction considerations, and ensuring precise installation methods such as specific seam types (flat-lock, lap, standing) and fastening techniques. The specification mandates comprehensive quality control measures, including observation of environmental conditions, verification of materials, and inspection of sheet metalwork for proper sizes, thicknesses, fastening, and overall installation quality. Contractors must submit detailed shop drawings, manufacturer's instructions, and maintain a quality control plan throughout the sheet metal installation process.
View the file
Other files
Show 40 more
Latest 50 of 89 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY24 MCON P-614 JOINT CONSOLIDATED COMMUNICATIONS CENTER 1737021
JOINT REGION MARIANAS, ANDERSEN AIR FORCE BASE
SECTION 07 60 00
FLASHING AND SHEET METAL
08/23
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.2/D1.2M (2014; Errata 1 2014; Errata 2 2020) Structural Welding Code - Aluminum
ASTM INTERNATIONAL (ASTM)
ASTM A240/A240M (2024) Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
ASTM B32 (2020) Standard Specification for Solder Metal
ASTM D41/D41M (2011; R 2016) Standard Specification for Asphalt Primer Used in Roofing, Dampproofing, and Waterproofing
ASTM D226/D226M (2017) Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing
ASTM D4586/D4586M (2007; R 2018) Asphalt Roof Cement, Asbestos-Free
NATIONAL ROOFING CONTRACTORS ASSOCIATION (NRCA)
NRCA 0429 (2022) The NRCA Roofing Manual:
Architectural Metal Flashing, Condensation and Air Leakage Control and Reroofing
SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION
(SMACNA)
SMACNA 1793 (2012) Architectural Sheet Metal Manual, 7th Edition
SINGLE PLY ROOFING INDUSTRY (SPRI)
ANSI/SPRI/FM 4435/ES-1 (2017) Test Standard for Edge Systems Used with Low Slope Roofing Systems
SECTION 07 60 00 Page 1
Amendment No. 0008 07 60 00 FLASHING AND SHEET METAL, dated April 14, 2025
1.2 GENERAL REQUIREMENTS
Finished sheet metal assemblies must form a weathertight enclosure without waves, warps, buckles, fastening stresses or distortion, while allowing for expansion and contraction without damage to the system. The sheet metal installer is responsible for cutting, fitting, drilling, and other operations in connection with sheet metal modifications required to accommodate the work of other trades. Coordinate installation of sheet metal items used in conjunction with roofing with roofing work to permit continuous, uninterrupted roofing operations.
1.2.1 General Material Requirements
All materials specified in this Section installed in conjunction with the roofing system must be provided by the roofing system manufacturer, or by a manufacturer approved by the roofing system manufacturer for use in the roofing system, and must form a part of the Warranty as required by the applicable roofing system Section.
1.2.2 Additional Wind Uplift Requirements
All flashing and edge materials specified in this Section must be installed in conjunction with the requirements of the roofing system to meet the requirements of ES-1 wind uplift. Details must include but not limited to ANSI/SPRI/FM 4435/ES-1 (ES-1), "Wind Test Design Standard for Edge Systems" used with Low Slope Roofing Systems, Test Methods: RE-1, RE-2 and RE-3 using uplift roofing details of the NRCA 0429.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Downspouts; G
Recycled Content; S
SD-08 Manufacturer's Instructions
Instructions for Installation; G
Quality Control Plan; G
SD-10 Operation and Maintenance Data
Cleaning and Maintenance; G
1.4 MISCELLANEOUS REQUIREMENTS
1.4.1 Product Data
Indicate thicknesses, dimensions, fastenings, anchoring methods, expansion joints, and other provisions necessary for thermal expansion and contraction. Scaled manufacturer's catalog data may be submitted for factory fabricated items.
SECTION 07 60 00 Page 2
1.4.2 Operation and Maintenance Data
Submit detailed instructions for installation and quality control during installation, cleaning and maintenance, for each type of assembly indicated.
1.5 DELIVERY, HANDLING, AND STORAGE
Package and protect materials during shipment. Uncrate and inspect materials for damage, dampness, and wet-storage stains upon delivery to the job site. Remove from the site and replace damaged materials that cannot be restored to like-new condition. Handle sheet metal items to avoid damage to surfaces, edges, and ends. Store materials in dry, weather-tight, ventilated areas until installation.
PART 2 PRODUCTS
2.1 RECYCLED CONTENT
Provide products with recycled content. Provide data for each product with recycled content, identifying percentage of recycled content.
2.2 MATERIALS
Use stainless steel listed by SMACNA 1793 for a particular item, unless otherwise indicated. Provide materials and configurations in accordance with SMACNA 1793 for each material, while also meeting the minimum thickness requirements specified in this Section.
Provide sheet metal items in 8 to 10 foot lengths. Single pieces less than 8 feet long may be used to connect to factory-fabricated inside and outside corners, and at ends of runs. Factory fabricate corner pieces with minimum 12 inch legs. Provide accessories and other items essential to complete the sheet metal installation. Provide accessories made of the same or compatible materials as the items to which they are applied.
Fabricate sheet metal items of the materials specified below and to the gage, thickness, or weight shown in Table I at the end of this section.
Provide sheet metal items with mill finish unless specified otherwise.
Where more than one material is listed for a particular item in Table I, each is acceptable and may be used, except as follows:
2.2.1 Stainless Steel
Provide in accordance with ASTM A240/A240M , Type 316L or 316, 2D Finish, fully annealed, dead-soft temper, a minimum of 24 gauge.
2.2.2 Solder
Provide in accordance with ASTM B32, 95-5 tin-antimony.
2.2.3 Bituminous Plastic Cement
Provide in accordance with ASTM D4586/D4586M , Type I.
2.2.4 Roofing Felt
Provide in accordance with ASTM D226/D226M Type II.
SECTION 07 60 00 Page 3
2.2.5 Asphalt Primer
Provide in accordance with ASTM D41/D41M.
2.2.6 Fasteners
Use stainless steel fasteners to fasten. Confirm compatibility of fasteners and items to be fastened to avoid galvanic corrosion due to dissimilar materials.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Workmanship
Make lines and angles sharp and true. Free exposed surfaces from visible wave, warp, buckle, and tool marks. Fold back exposed edges neatly to form a 1/2 inch hem on the concealed side. Make sheet metal exposed to the weather watertight with provisions for expansion and contraction.
Make surfaces to receive sheet metal plumb and true, clean, even, smooth, dry, and free of defects and projections. For installation of items not shown in detail or not covered by specifications conform to the applicable requirements of SMACNA 1793, Architectural Sheet Metal Manual. Provide flashing in the angles formed for , curbs, pipes, or other vertical surfaces and wherever indicated and necessary to make the work watertight. Join sheet metal items together as shown in Table II.
3.1.2 Bolts, Rivets, and Screws
Install bolts, rivets, and screws where indicated or required. Provide compatible washers where required to protect surface of sheet metal and to provide a watertight connection. Provide mechanically formed joints in aluminum sheets 0.040 inches or less in thickness.
3.1.3 Seams
Straight and uniform in width and height with no solder showing on the face.
3.1.3.1 Flat-lock Seams
Finish not less than 3/4 inch wide.
3.1.3.2 Lap Seams
Finish soldered seams not less than one inch wide. Overlap seams not soldered, not less than 3 inches.
3.1.3.3 Loose-Lock Expansion Seams
Not less than 3 inches wide; provide minimum one inch movement within the joint. Completely fill the joints with the specified sealant, applied at not less than 1/8 inch thick bed.
3.1.3.4 Standing Seams
Not less than one inch high, double locked without solder.
SECTION 07 60 00 Page 4
3.1.3.5 Flat Seams
Make seams in the direction of the flow.
3.1.4 Soldering
Where soldering is specified, apply to copper, terne-coated stainless steel, zinc-coated steel, and stainless steel items. Pre-tin edges of sheet metal before soldering is begun. Seal the joints in aluminum sheets of 0.040 inch or less in thickness with specified sealants. Do not solder aluminum.
3.1.4.1 Edges
Scrape or wire-brush the edges of lead-coated material to be soldered to produce a bright surface. Flux brush the seams in before soldering.
Treat with soldering acid flux the edges of stainless steel to be pre-tinned. Seal the joints in aluminum sheets of 0.040 inch or less in thickness with specified sealants. Do not solder aluminum.
3.1.5 Welding and Mechanical Fastening
Use welding for aluminum of thickness greater than 0.040 inch. Aluminum
0.040 inch or less in thickness must be butted and the space backed with formed flashing plate; or lock joined, mechanically fastened, and filled with sealant as recommended by the aluminum manufacturer.
3.1.5.1 Welding of Aluminum
Use welding of the inert gas, shield-arc type. For procedures, appearance and quality of welds, and the methods used in correcting welding work, conform to AWS D1.2/D1.2M .
3.1.5.2 Mechanical Fastening of Aluminum
Use No. 12, aluminum alloy, sheet metal screws or other suitable aluminum alloy or stainless steel fasteners. Drive fasteners in holes made with a No. 26 drill in securing side laps, end laps, and flashings. Space fasteners 12 inches maximum on center. Where end lap fasteners are required to improve closure, locate the end lap fasteners not more than 2 inches from the end of the overlapping sheet.
3.1.6 Protection from Contact with Dissimilar Materials
3.1.6.1 Copper or Copper-bearing Alloys
Paint with heavy-bodied bituminous paint surfaces in contact with dissimilar metal, or separate the surfaces by means of moistureproof building felts.
3.1.6.2 Metal Surfaces
Paint surfaces in contact with mortar, concrete, or other masonry materials with alkali-resistant coatings such as heavy-bodied bituminous paint.
SECTION 07 60 00 Page 5
3.1.6.3 Other Absorptive Materials
Paint surfaces that may become repeatedly wet and in contact with metal with two coats of aluminum paint or a coat of heavy-bodied bituminous paint.
3.1.7 Expansion and Contraction
Provide expansion and contraction joints at not more than 32 foot intervals for aluminum and at not more than 40 foot intervals for other metals. Provide an additional joint where the distance between the last expansion joint and the end of the continuous run is more than half the required interval. Space joints evenly.
3.1.8 Downspouts
Space supports for downspouts according to the manufacturer's recommendation for the substrate. Types, shapes and sizes are indicated.
Provide complete including elbows and offsets. Provide downspouts in approximately 10 foot lengths. Provide end joints to telescope not less than 1/2 inch and lock longitudinal joints. Provide gutter outlets with stainless steel wire ball strainers for each outlet. Provide strainers to fit tightly into. Keep downspouts not less than one inch away from walls. Fasten to the walls at top, bottom, and at an intermediate point not to exceed 5 feet on center with leader straps or concealed rack-and-pin type fasteners. Form straps and fasteners of metal compatible with the downspouts.
3.1.8.1 Terminations
Neatly fit into the cast iron drainage connection the downspouts terminating in drainage lines and fill the joints with a portland cement mortar cap sloped away from the downspout. Provide downspouts terminating in splash blocks with cast iron elbow-type fittings. Provide splash blocks as specified.
3.1.9 Through Wall Flashing
Provide through wall flashing as required in the applicable wall system Sections.
3.2 CLEANING
Clean exposed sheet metal work at completion of installation. Remove grease and oil films, handling marks, contamination from steel wool, fittings and drilling debris, and scrub-clean. Free the exposed metal surfaces of dents, creases, waves, scratch marks, and solder or weld marks.
3.3 REPAIRS TO FINISH
Scratches, abrasions, and minor surface defects of finish may be repaired in accordance with the manufacturer's printed instructions and as approved. Repair damaged surfaces caused by scratches, blemishes, and variations of color and surface texture. Replace items which cannot be repaired.
3.4 FIELD QUALITY CONTROL
Establish and maintain a Quality Control Plan for sheet metal used in
SECTION 07 60 00 Page 6 conjunction with roofing to assure compliance of the installed sheet metalwork with the Contract requirements. Remove work that is not in compliance with the Contract and replace or correct. Include quality control, but not be limited to, the following:
a. Observation of environmental conditions; number and skill level of sheet metal workers; condition of substrate.
b. Verification that specified material is provided and installed.
c. Inspection of sheet metalwork, for proper size(s) and thickness(es), fastening and joining, and proper installation.
3.4.1 Procedure
Submit for approval prior to start of roofing work. Include a checklist of points to be observed. Document the actual quality control observations and inspections. Provide a copy of the documentation to the Contracting Officer at the end of each day.
TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES
Sheet Metal Items Aluminum, inch Stainless Steel, inch
Downspouts and leaders .032 .015
Downspout clips and anchors .040 clip .125 anchor
Downspout straps, 2-inch .060 .050
Strainers, wire diameter or gage
.144 diameter .109 diameter
SECTION 07 60 00 Page 7
TABLE II. SHEET METAL JOINTS
TYPE OF JOINT
Item Designation Zinc-Coated Steel and Stainless Steel
Aluminum Remarks
Joint cap for building expansion seam, cleated joint at roof
1.25 inch single lock, standing seam, cleated
1.25 inch single lock, standing
-- End of Section --
SECTION 07 60 00 Page 8
| 07 60 00 - FLASHING AND SHEET METAL |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 GENERAL REQUIREMENTS |
| 1.2.1 General Material Requirements |
| 1.2.2 Additional Wind Uplift Requirements |
| 1.3 SUBMITTALS |
| 1.4 MISCELLANEOUS REQUIREMENTS |
| 1.4.1 Product Data |
| 1.4.2 Operation and Maintenance Data |
1.5 DELIVERY, HANDLING, AND STORAGE
| PART 2 PRODUCTS |
| 2.1 RECYCLED CONTENT |
| 2.2 MATERIALS |
| 2.2.1 Stainless Steel |
| 2.2.2 Solder |
| 2.2.3 Bituminous Plastic Cement |
| 2.2.4 Roofing Felt |
| 2.2.5 Asphalt Primer |
| 2.2.6 Fasteners |
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.1.1 Workmanship |
| 3.1.2 Bolts, Rivets, and Screws |
| 3.1.3 Seams |
| 3.1.3.1 Flat-lock Seams |
| 3.1.3.2 Lap Seams |
| 3.1.3.3 Loose-Lock Expansion Seams |
| 3.1.3.4 Standing Seams |
| 3.1.3.5 Flat Seams |
| 3.1.4 Soldering |
| 3.1.4.1 Edges |
| 3.1.5 Welding and Mechanical Fastening |
| 3.1.5.1 Welding of Aluminum |
| 3.1.5.2 Mechanical Fastening of Aluminum |
| 3.1.6 Protection from Contact with Dissimilar Materials |
| 3.1.6.1 Copper or Copper-bearing Alloys |
| 3.1.6.2 Metal Surfaces |
| 3.1.6.3 Other Absorptive Materials |
| 3.1.7 Expansion and Contraction |
| 3.1.8 Downspouts |
| 3.1.8.1 Terminations |
3.1.9 Through Wall Flashing
| 3.2 CLEANING |
| 3.3 REPAIRS TO FINISH |
| 3.4 FIELD QUALITY CONTROL |
| 3.4.1 Procedure |