03_10 44 16_Amd0005.pdf
PDF 35 KB Posted
- Attached to
- FY24 MCON P-614 JOINT CONSOLIDATED COMMUNICATIONS CENTER, US JOINT REGION MARIANAS, ANDERSEN, GUAM
- Solicitation number
- N6274225R1303
About this file
This specification document details requirements for fire extinguishers and related equipment for the FY24 MCON P-614 Joint Consolidated Communications Center project at Andersen Air Force Base in Guam. The specification covers fire extinguisher types, materials, and installation specifications, including dry chemical and clean agent extinguishers with 5-pound and 15-pound capacities. Key technical requirements include corrosion-resistant aluminum extinguisher shells, forged brass valves, fusible plugs, safety releases, and pressure gauges.
The document specifies precise installation requirements, including placement in compliance with NFPA standards, using recessed, semi-recessed, and surface-type aluminum cabinets. Fire extinguishers must be fully charged, ready for operation, and come with a manufacturer's warranty. The specification mandates compliance with multiple fire safety codes including NFPA 1, NFPA 10, NFPA 101, and UL standards for dry chemical and clean agent fire extinguishers. Contractors must submit detailed shop drawings, product data, certifications, and replacement parts lists for government approval.
View the file
Other files
Show 40 more
Latest 50 of 89 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY24 MCON P-614 JOINT CONSOLIDATED COMMUNICATIONS CENTER 1737021
JOINT REGION MARIANAS, ANDERSEN AIR FORCE BASE
SECTION 10 44 16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM E814 (2023a) Standard Test Method for Fire Tests of Penetration Firestop Systems
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 1 (2018) Fire Code
NFPA 10 (2022; ERTA 1 2021) Standard for Portable Fire Extinguishers
NFPA 101 (2021; TIA 21-1) Life Safety Code
NFPA 241 (2022) Standard for Safeguarding Construction, Alteration, and Demolition Operations
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.106 Flammable Liquids
29 CFR 1910.157 (2003) Portable Fire Extinguishers
UNDERWRITERS LABORATORIES (UL)
UL 299 (2012) Dry Chemical Fire Extinguishers
UL 2129 (2017) UL Standard for Safety Halocarbon Clean Agent Fire Extinguishers
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Cabinets; G
SD-03 Product Data
SECTION 10 44 16 Page 1
Amendment No. 0005 10 44 16 FIRE EXTINGUISHERS, dated March 27, 2025
FIRE EXTINGUISHERS
11/19
Fire Extinguishers; G
Accessories; G
Cabinets; G
Replacement Parts List; G
SD-07 Certificates
Fire Extinguishers Certifications; G
Manufacturer's Warranty with Inspection Tag; G
1.3 DELIVERY, STORAGE, AND HANDLING
Protect materials from weather, soil, and damage during delivery, storage, and construction.
Deliver materials in their original packages, containers, or bundles bearing the brand name and the name and type of the material.
1.4 WARRANTY
Guarantee that Fire Extinguishers are free of defects in materials, fabrication, finish, and installation and that they will remain so for a period of not less than 6 years after completion.
Submit the manufacturer's warranty with inspection tag.
PART 2 PRODUCTS
Submit fabrication drawings consisting of fabrication and assembly details performed in the factory and product data for the following items: Fire Extinguishers; Accessories, cabinets, Wall Brackets.
2.1 SYSTEM DESCRIPTION
2.1.1 Types
Submit fire extinguishers certifications showing compliance with local codes and regulations.
Provide fire extinguishers conforming to NFPA 10 . Provide quantity and placement in compliance with the applicable sections of NFPA 1, NFPA 101 , NFPA 241 , , 29 CFR 1910.106 and 29 CFR 1910.157 .
Provide dry chemical type fire extinguishers compliant with UL 299 .
Provide clean agent type fire extinguishers compliant with UL 2129 .
2.1.2 Material
Provide corrosion-resistant aluminum extinguisher shell.
2.1.3 Size
5 pounds (3A:40B:C) for dry chemical extinguishers and 15 pounds
SECTION 10 44 16 Page 2
Amendment No. 0005 10 44 16 FIRE EXTINGUISHERS, dated March 27, 2025
(2A:10B:C) for clean agent extinguishers.
2.1.4 Accessories
Forged brass valve
Fusible plug
Safety release
Pressure gage
2.2 EQUIPMENT
2.2.1 Cabinets
2.2.1.1 Material
Provide aluminum cabinets.
2.2.1.2 Type
Provide recessed type cabinets where indicated.
Provide semi-recessed cabinet for walls where indicated.
Provide surface type cabinets where indicated.
Provide a fire rated cabinet, listed and labeled to comply with ASTM E814 for fire resistance wall rating.
2.2.1.3 Size
Dimension cabinets to accommodate the specified fire extinguishers.
PART 3 EXECUTION
3.1 INSTALLATION
Install Fire Extinguishers where indicated on the drawings. Verify exact locations prior to installation.
Provide extinguishers which are fully charged and ready for operation upon installation. Provide extinguishers complete with Manufacturer's Warranty with Inspection Tag attached.
Install fire extinguishers in locations indicated and in compliance with requirements of authorities having jurisdiction.
Comply with the manufacturer's recommendations for all installations.
3.2 PROTECTION
3.2.1 Repairing
Remove and replace damaged and unacceptable portions of completed work with new work at no additional cost to the Government.
Submit replacement parts list indicating specified items replacement part, SECTION 10 44 16 Page 3 replacement cost, and name, address and contact for replacement parts distributor.
3.2.2 Cleaning
Clean all surfaces of the work, and adjacent surfaces which are soiled as a result of the work. Remove from the site all construction equipment, tools, surplus materials and rubbish resulting from the work.
-- End of Section --
SECTION 10 44 16 Page 4
| 10 44 16 - FIRE EXTINGUISHERS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 DELIVERY, STORAGE, AND HANDLING |
| 1.4 WARRANTY |
| PART 2 PRODUCTS |
| 2.1 SYSTEM DESCRIPTION |
| 2.1.1 Types |
| 2.1.2 Material |
| 2.1.3 Size |
| 2.1.4 Accessories |
| 2.2 EQUIPMENT |
| 2.2.1 Cabinets |
| 2.2.1.1 Material |
| 2.2.1.2 Type |
| 2.2.1.3 Size |
| PART 3 EXECUTION |
| 3.1 INSTALLATION |
| 3.2 PROTECTION |
| 3.2.1 Repairing |
| 3.2.2 Cleaning |