03_25R1303_26 33 53_AMD0013.pdf
PDF 630 KB Posted
- Attached to
- FY24 MCON P-614 JOINT CONSOLIDATED COMMUNICATIONS CENTER, US JOINT REGION MARIANAS, ANDERSEN, GUAM
- Solicitation number
- N6274225R1303
About this file
This document is a technical specification (Section 26 33 53) for a Static Uninterruptible Power Supply (UPS) system for the FY24 MCON P-614 Joint Consolidated Communications Center at Andersen Air Force Base in Guam. The specification provides detailed technical requirements for a large-scale UPS system with a 1500 kVA/1500 kW capacity, designed for a redundant configuration with comprehensive performance, environmental, and operational specifications.
Key technical requirements include a three-phase, solid-state, on-line double conversion UPS with specific performance parameters such as input voltage range (±10%/-15%), output voltage regulation (±1% balanced load), battery discharge time of 15 minutes, and high efficiency ratings (97% at full load, 92% at 50% load). The system must include multiple protective features, monitoring capabilities, remote communications interfaces, battery monitoring, hydrogen gas monitoring, and must undergo extensive factory and field testing. The specification covers detailed requirements for the UPS module, battery system, static bypass transfer circuit, control panels, alarms, temperature control, and installation guidelines, ensuring a robust and reliable power infrastructure for the communications center.
View the file
Other files
Show 40 more
Latest 50 of 89 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY24 MCON P-614 JOINT CONSOLIDATED COMMUNICATIONS CENTER 1737021
JOINT REGION MARIANAS, ANDERSEN AIR FORCE BASE
SECTION 26 33 53
STATIC UNINTERRUPTIBLE POWER SUPPLY (UPS)
05/19
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ACOUSTICAL SOCIETY OF AMERICA (ASA)
ASA S1.4 (1983; Amendment 1985; R 2006) Specification for Sound Level Meters (ASA 47)
ASTM INTERNATIONAL (ASTM)
ASTM D709 (2017) Standard Specification for Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE 485 (2020) Recommended Practice for Sizing Lead-Acid Batteries for Stationary Applications
IEEE C2 (2023) National Electrical Safety Code
IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits
IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits
IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2021) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
SECTION 26 33 53 Page 1
Amendment 0013
26 33 53 STATIC UNINTERRUPTIBLE POWER SUPPLY (UPS), dated May 12, 2025
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)
ISO 9001 (2015) Quality Management Systems- Requirements
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA PE 1 (2012; R 2017) Uninterruptible Power Systems (UPS) - Specification and Performance Verification
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 4 2023; ERTA 5 2023; ERTA 6
2023) National Electrical Code
U.S. DEPARTMENT OF DEFENSE (DOD)
U.S. DEPARTMENT OF ENERGY (DOE)
Energy Star (1992; R 2006) Energy Star Energy Efficiency Labeling System (FEMP)
U.S. FEDERAL COMMUNICATIONS COMMISSION (FCC)
FCC Part 15 Radio Frequency Devices (47 CFR 15)
UNDERWRITERS LABORATORIES (UL)
UL 1778 (2014; Reprint Apr 2023) UL Standard for Safety Uninterruptible Power Systems
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in
IEEE 100 .
1.3 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
UPS Drawings; G
UPS Installation; G
SD-03 Product Data
UPS Module; G
Technical Requirements UPS System
SECTION 26 33 53 Page 2
Energy Star Label for Battery Charging Systems and AC-DC/AC-AC Power Supply Products; S
Spare Parts; G
SD-06 Test Reports
Work Plan; G
Factory Test Plan; G
Factory Test Report; G
SD-09 Manufacturer's Field Reports
Initial Inspection and Tests; G
Performance Tests; G
Performance Test Plan; G
Performance Test Report; G
SD-10 Operation and Maintenance Data
UPS Operation and Maintenance, Data Package 5; G
Submit operation and maintenance data in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA and as specified herein.
SD-11 Closeout Submittals
Installation
1.4 OPERATION AND MAINTENANCE MANUALS
1.4.1 Additions to UPS Operation and Maintenance Manuals
In addition to requirements of SD-10 Data Package 5, include the followings on the actual UPS system provided:
a. An outline drawing, front, top, and side views.
b. Prices for spare parts and supply list.
c. Routine and field acceptance test reports.
d. Date of Purchase.
e. Corrective maintenance procedures.
1.4.2 Spare Parts
Furnish the following spare parts, of the same material and workmanship, meeting the same requirements, and interchangeable with the corresponding original parts.
a. Fuses: Two of each type and rating.
SECTION 26 33 53 Page 3
b. Circuit boards: One circuit board for each critical circuit.
c. Air Filters: One set of filters, when used on the UPS unit.
d. Special tools, calibration devices, and instruments required for operation, calibration, and maintenance of the equipment: One complete set.
1.5 QUALITY ASSURANCE
The manufacturer must have a documented quality assurance program including:
a. Inspections of incoming parts, modular assemblies and final product.
b. Final test procedure for the product including proof of performance specifications.
c. The on-site test procedure includes an inspection of controls and indicators after installation of the equipment.
d. ISO 9001 quality certification.
1.5.1 UPS Drawings
Drawings are to include the following: Detail drawings consisting of a complete list of equipment and materials, manufacturer's descriptive and technical literature, battery sizing calculations per IEEE 485 , installation instructions, single-line diagrams, elevations, layout drawings, and details required to demonstrate that the system has been coordinated and will function properly as a unit.
a. One-line diagram.
b. Outline drawings including front elevation, section views, footprints, and overall dimensions.
c. Manufacturer's descriptive and technical literature.
d. Markings and NEMA nameplate data.
e. Battery sizing calculations per IEEE 485 .
f. Wiring and control diagrams with terminals identified, and indicating prewired interconnections between items of equipment and interconnection between the items.
g. Complete list of materials and equipment covering major components.
Ensure the bill of material and the schematic have a direct correlation between items in order to easily identify the various components.
h. Details required to demonstrate that the system has been coordinated and will function properly as a unit.
1.5.2 UPS Installation
Include wiring diagrams and installation details of equipment indicating
SECTION 26 33 53 Page 4 proposed location, layout and arrangement, control panels, accessories, piping, ductwork, and other items that must be shown to ensure a coordinated installation. Wiring diagrams are to identify circuit terminals and indicate the internal wiring for each item of equipment and the interconnection between each item of equipment. Drawings are to indicate adequate clearance for operation, maintenance, and replacement of operating equipment devices. Submittals include the nameplate data, size, and capacity. Submittals also include applicable federal, military, industry, and technical society publication references.
1.5.3 Work Plan
Submit schedules of dates for factory tests, installation, field tests, and operator training for the UPS system. Furnish a list of instrumentation equipment for factory and field test reports.
1.5.4 Factory Test Plan
Submit factory test plans and procedures at least 21 calendar days prior to the tests being conducted. Provide detailed description of test procedures, including test equipment and setups, to be used to ensure the UPS meets the performance specification and explain the test methods to be used. Provide test procedures that include the test required under the paragraph entitled "Factory Testing."
1.5.5 Factory Test Report
Submit a factory test report within 21 calendar days after completion of tests. Receive approval of test prior to shipping unit. Factory test reports are to be signed by an official authorized to certify on behalf of the UPS manufacturer of that the system meets specified requirements in accordance with the requirements set forth in paragraph entitled "Factory Testing". Provide test reports in booklet form tabulating factory tests and measurements performed, upon completion and testing of the installed system. Reports are to state the Contractor's name and address, the name of the project and location, and list the specific requirements which are being certified.
1.5.6 Performance Test Plan
Submit test plans and procedures at least 15 calendar days prior to the start of field tests. Provide detailed description and dates and times scheduled for performance of tests, and detailed description of test procedures, including test equipment (list make and model and provide functional description of the test instruments and accessories) and setups of the tests to be conducted to ensure the UPS meets the performance specification. Explain the test methods to be used. Provide test procedures that include the tests required under the paragraph entitled "Performance Tests."
1.5.7 Performance Test Report
Submit report of test results as specified by paragraph entitled "Performance Tests" within 15 calendar days after completion of tests.
Field test reports are to be signed by an official authorized to certify on behalf of the UPS manufacturer that the system meets specified requirements in accordance with the requirements set forth in paragraph entitled "Performance Tests". Provide test reports in in booklet form tabulating factory tests and measurements performed, upon completion and
SECTION 26 33 53 Page 5 testing of the installed system. Reports are to state the Contractor's name and address, the name of the project and location, and list the specific requirements which are being certified.
1.5.8 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Provide equipment, materials, installation, and workmanship in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.5.8.1 Reference Standard Compliance
Where equipment or materials are specified to conform to industry and technical society reference standards of the organizations such as American National Standards Institute (ANSI), American Society for Testing and Materials (ASTM), National Electrical Manufacturers Association (NEMA), Underwriters Laboratories (UL), and Association of Edison Illuminating Companies (AEIC), submit proof of such compliance. The label or listing by the specified organization will be acceptable evidence of compliance.
1.5.8.2 Independent Testing Organization Certificate
In lieu of the label or listing, submit a certificate from an independent testing organization, competent to perform testing, and approved by the Contracting Officer. The certificate is to state that the item has been tested in accordance with the specified organization's test methods and that the item complies with the specified organization's reference standard.
1.5.9 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.
b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
d. The service organization is to be, in the opinion of the Contracting Officer, reasonably convenient to the site.
e. Provide new parts and materials comprising the UPS system from the current manufacture, of a high grade and free of defects and imperfections, and has not been in prior service except as required
SECTION 26 33 53 Page 6 during aging and factory testing.
1.5.9.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.5.9.2 Material and Equipment Manufacturing Date
Products manufactured more than 6 months prior to date of delivery to site are not acceptable.
1.6 INSPECTION
Inspection before shipment is required. The manufacturer must notify the Government at least 2 weeks before shipping date so that an inspection can be made.
1.7 DELIVERY AND STORAGE
Protect equipment placed in storage from humidity and temperature variations, moisture, water intrusion, dirt, airborne corrosives, or other contaminants. In harsh environments where temperatures exceed non-operational parameters established within this specification, provide an environmentally controlled equipment storage facility to ensure temperature parameters are within equipment specification. Provide documentation of same to the Government when storage is implemented.
1.8 PROJECT/SITE CONDITIONS
1.8.1 Environmental Conditions
The UPS and battery system must be capable of withstanding any combination of the following external environmental conditions without mechanical or electrical damage or degradation of operating characteristics.
a. Operating altitude: Sea level to 3,300 ft. (Systems applied at higher altitudes are to be derated in accordance with the manufacturer's instructions).
b. Non-operating altitude: Sea level to 36,000 ft.
c. Operating ambient temperature range: 32 to 104 degrees F. Range for batteries is 68 to 77 degrees F. Provide batteries that are capable of operating in a larger ambient temperature range of 50 to 86 degrees F, but some degradation of life span is understood when operating outside the range of 68 to 77 degrees F.
d. Non-operating and storage ambient temperature range: Minus 4 to plus 122 degrees F. Range for batteries or UPS modules with internal batteries: 50 to 86 degrees F.
e. Operating relative humidity: 0 to 95 percent, without condensation.
1.8.2 Sound Pressure Levels
Sound pressure levels produced by the UPS, when operating under full rated
SECTION 26 33 53 Page 7 load, at a distance of 5 feet in any direction from the perimeter of the unit, must not exceed 75 dB as measured on the A scale of a Type 1 sound level meter at slow response conforming to ASA S1.4 .
1.8.3 Verification of Dimensions
The Contractor is to become familiar with details of the work, verify dimensions in the field, and is to advise the Contracting Officer of any discrepancy before performing the work. Do not proceed until the discrepancy or unsatisfactory condition(s) have been corrected.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide continuous duty, three-phase, solid state, on-line double conversion reverse transfer static UPS(s). The UPS by means of solid state conversion techniques, must provide continuous regulated AC power to its output terminals, while operating from an input power source, cabinet or rack-mounted direct current (DC) storage battery or other approved means. The performance of the UPS must not be degraded when operating without a system battery, provided the input AC source is within tolerance. Provide an UPS system that conforms to UL 1778 and consists of UPS module, battery system, battery protective device, system cabinet, static bypass transfer switch, controls and monitoring, system protective devices, means of isolating the UPS system from the critical load, and remote monitoring interfaces. Connect input ac power the normal source ac input of the UPS module. Connect alternate power source bypass/maintenance bypass. Connect battery to the dc input of the UPS module through the battery protective device. The following configuration is used:
a. Redundant System.
(1) Two parallel redundant systems that may be operated separately, with only one system active at any time connected to both A and B bus via tie breakers. Each UPS system on either side of the split bus is able to support the total critical load.
2.2 MODES OF OPERATION
2.2.1 Normal
The UPS module rectifier/charger must convert the incoming ac input power to dc power for the inverter and for float charging the battery. The inverter continuously coverts the dc power to ac power to supply the critical load. The inverter output must synchronize with the bypass ac power source, provided that the bypass ac power source is within the specified voltage and frequency range.
2.2.2 Battery - Emergency Operation (Loss or deviation of AC Input Power)
Whenever the ac input power source deviates from the specified tolerances including complete failure, the inverter must draw power from the battery system and supply AC power to the critical load without any interruption or switching transient. The battery system must supply power to the inverter for the specified protection time or until return of ac input source. Provide an audible alarm to indicate the UPS is on battery and provide provisions for a remote alarm signal to be sent via the communication network and a relay output, allowing startup of a secondary
SECTION 26 33 53 Page 8 power source or orderly shutdown of the critical load.
2.2.3 Failure of AC Input Power to Return
If the ac input power fail to return before the battery voltage reaches the discharge limit, then the UPS system must disconnect from the critical load to safeguard the battery.
2.2.4 Recharge
Upon restoration of normal power to the UPS unit, the input converter and output inverter must simultaneously recharge the batteries and provide regulated power to the critical load.
2.2.5 Transfer to Static Bypass AC Power Source
When the UPS controller senses an overload, two or more inverter shutdown signals or degradation of the inverter output, the static bypass switch automatically transfers the critical load from the inverter output to the bypass ac power source without an interruption of power. If the static bypass ac power source is outside of specified tolerance limits, the UPS and the critical load shut down. Transfer to static bypass can also be done manually (requested bypass). Transfer to bypass does not take place under these conditions: 100% stepload; and, loss or return of input power, momentary sags, surges or spikes on the input to the UPS.
2.2.6 Transfer to Inverter
Provide a static bypass switch that is capable of automatically transferring the load back to the inverter output after the inverter overload condition has returned to normal conditions. Transfer only occurs once the two sources are synchronized. UPS system logic is to monitor the number of retransfer's within any one-hour period and is to allow 1 to 3 transfers in order to prevent cyclical transfers caused by overloads.
2.2.7 Off-Battery (Battery Maintenance)
Provide a battery protective device which disconnects the battery from the rectifier/charger and inverter for maintenance. The device may be located external to the UPS cabinet. The UPS module continues to function and meet the performance criteria specified except for the battery back-up time function.
2.2.8 Component Performance
Do not exceed 75% of the working voltage and current ratings as established by the manufacturer on solid-state power components and electronic devices. Do not exceed 75% of the operating temperature of solid-state component sub-assemblies. Use computer grade electrolytic capacitors and operate at no more than 95% of the voltage rating at the rectifier charging voltage.
2.3 GENERAL UPS SYSTEM COMPONENTS AND FABRICATION
2.3.1 Semiconductor Fusing
Protect power semiconductors with fast-acting fuses to prevent cascaded or sequential semiconductor failures. Bolt fuses at both ends to bus bars to ensure mechanical and electrical integrity. Indicator lamp or display
SECTION 26 33 53 Page 9 panel denoting blown fuse conditions must be readily observable by the operator without removing panels or opening cabinet doors.
2.3.2 EMI/RFI Protection
Provide an UPS that complies with and is labeled compliant, with FCC Part 15 , Subclass B, Class A.
2.3.3 Internal Wiring
Wiring practices, materials, and coding must be in accordance with the requirements of NFPA 70 , OSHA, UL 1778 , and other applicable standards.
Protect wire runs in a manner which separates power and control wiring.
Provide control cabling that is at least No. 16 AWG extra-flexible stranded copper. Logic-circuit wiring may be smaller. Provide ribbon cables that are at least minimum No. 22 AWG. Provide control wiring with permanently attached wire numbers.
2.3.4 Internal Assembly
The printed circuit board (PCB) subassemblies are to be mounted in pull-out swing-out trays where feasible. Provide cable connections to the trays that are sufficiently long to allow easy access to all components.
Where not feasible to mount PCB subassemblies in pull-out or swing-out trays, then mount them firmly mounted inside the enclosure. Monitor every PCB subassembly. Include self-test and diagnostic circuitry in the logic circuits such that a fault can be isolated down to the PCB subassembly level. When used, control logic cards are to have test points or logic indicators on the front edge of the control logic card and be labeled.
2.3.5 Cable Lugs and Terminations
2.3.5.1 Cable Lugs
Provide appropriate compression type lugs or pre-drilled bus bars on all ac and dc power connections to the UPS system and battery as required.
Aluminum or bare copper cable lugs are not suitable.
2.3.5.2 Terminations
Supply terminals for making power and control connections. Provide terminal block for field wiring terminals. Provide terminal blocks that are the heavy-duty, strap-screw type or screw terminals that are integrated into removable plugs. Locate terminal blocks for field wiring in one place in each module. Extend control wiring to the terminal block location. Any terminal point is limited to land a maximum of two wires.
Where control wiring is attached to the same point as power wiring, Provide a separate terminal where control wiring is attached to the same point as power wiring, . If bus duct is used, provide bus stubs where bus duct enters cabinets.
2.3.6 Cabinets
Install the UPS system in cabinets of heavy-duty structure meeting the NEMA PE 1 standards for floor mounting. Provide a structurally adequate UPS module that can be forklift handled and lifted. Provide the UPS module cabinet with hinged and key lockable doors on the front only and with assemblies and components accessible from the front. Provide dead-front construction behind the door for those UPS module cabinets that are not
SECTION 26 33 53 Page 10 lockable. Operating controls are to be located outside the locked doors.
Install input, output, and battery cables through the top or bottom of the cabinet.
2.3.6.1 Factory Applied Finish
Provide electrical equipment with a factory-applied painting systems which, as a minimum, meets the requirements of NEMA 250 corrosion-resistance test.
2.3.6.2 Drawout Assemblies
Provide a means of lifting, either and overhead device or a hoisting device for drawout assemblies weighing 50 lbs or more. Device can either be part of the UPS or a separate portable device that can be used to perform the lifting.
2.3.7 Manufacturer's Nameplates
Provide a nameplate for each item of equipment bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
2.3.8 Field Fabricated Nameplates
ASTM D709. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified or as indicated on the drawings. Provide an inscription on each nameplate that identifies the name of the item, calculated short circuit rating with date, and source of power e.g. 'Panel A in Electrical Room 103'. Provide nameplates that are made of melamine plastic, 0.125 inch thick, white with black center core.
Provide the nameplate with a surface that is matte finished and that has square corners.. Accurately align lettering and engrave into the core.
Provide nameplates that are at least 1.0 by 2.5 inches with a minimum lettering size of 0.25 inch high normal block style.
2.3.9 Safety
Provide UPS with instruction plates including warnings and cautions, suitably located, and describing any special or important procedures to be followed in operating and servicing the equipment. Provide control panel displays, which also provide warning messages prior to performing a critical function.
2.3.9.1 Maintenance Isolation
All energized terminals, both AC and DC, and control voltage exposed points are to be insulated or enclosed to ensure the safety of maintenance personnel. Provide the system with the ability to isolate the static switch to enable repair when the UPS is bypassed.
2.3.9.2 Remote Emergency Power Off (REPO) Switch
Provide a remote emergency power off switch that is separate from the UPS. Provide a red, pushbutton with a cover with a label indicating "UPS Emergency Power Off". The switch disconnects all breakers or contactors including battery, input, output, and bypass breakers when activated.
SECTION 26 33 53 Page 11
2.4 TECHNICAL REQUIREMENTS UPS SYSTEM RATINGS
Unless stated otherwise, the parameters listed are under full output load over the range of0.9 lagging power factor to 0.9 leading power factor, with batteries fully charged and floating on the dc bus and with nominal input voltage.
2.4.1 UPS SYSTEM LOAD PROFILE
Provide an UPS system that is compatible with the load characteristics defined in the LOAD PROFILE below and load configuration. Refer to the panel schedules for a more detailed load profile. The UPS system is to provide compensation for UPS/load interaction problems resulting from nonlinear loads or transformer and motor inrush.
LOAD PROFILE
Type of load:
Data processing equipment. Size of load: 474.4kW, 480kW Electric Discharge Lighting. Size of load: 9.2kVa, 480VAC Variable Frequency Drive(s). Size of load: (4)30hp,480VAC. Miscellaneous Loads. Size of load: 505kVA, 480VAC.
Load switching pattern: unswitched Steady-state characteristics: power factor.
Special factors: harmonic characteristics - Total Harmonic Distortion 5 percent
2.4.2 System Requirements
The UPS is to support and maintain full battery charging under the following conditions: indicated environmental conditions, a.c input voltage range, air filters blocked up to 50% and a single failed fan. The UPS size and configuration is indicated below.
Single UPS(redundant). Provide one UPS sized for 1500 kVA and 1500 kW.
2.4.3 Battery Capacity
Discharge time to end voltage: 15 minutes, at 77 degrees F. Provide a battery that is capable of delivering 125 percent of full rated UPS kW load at 0.9 power factor at initial start-up.
2.4.4 Static Switch
Sized per manufacturer requirements.
2.4.5 Short Circuit Withstand Rating
Braced for at least 100,000 amperes symmetrical interrupting capacity.
2.4.6 AC Input
a. Voltage volts line-to-line.
b. Number of phases: Three-phase + ground configuration..
c. Voltage Range: Plus 10 percent, minus 15 percent nominal (no battery
SECTION 26 33 53 Page 12 discharge), without affecting battery float voltage or output voltage.
d. Frequency: 60 Hz, plus or minus 5 percent.
e. Power walk-in: 20 percent to 100 percent input current over 10 to 15 seconds.
f. Total harmonic current distortion (THD) reflected into the primary line: 5 percent maximum at full load.
g. Sub-cycle magnetizing inrush: 2 to 3 times full load current for modules without an isolation transformer.
h. Input surge protection: per IEEE C62.41.1 and IEEE C62.41.2 , meeting IEEE C62.41 requirement of Category B3 6kV, 100k Hz ring wave and 6kV, combined wave.
i. Input power factor: Lagging from 1-100 percent load.
2.4.7 AC Output
a. Voltage 480 volts line-to-line.
b. Number of phases: Three-phase + ground configuration.
c. Voltage regulation:
(1) Balanced load: Plus or minus 1.0 percent.
(2) 50 percent load imbalance, phase-to-phase: Plus or minus 2 percent.
(3) 100 percent load imbalance, phase-to-phase Plus or minus 3 percent.
(4) Voltage drift: Plus or minus 1 percent over any 30 day interval (or length of test) at stated ambient conditions found in paragraph Environmental Conditions.
d. Voltage adjustment: Plus or minus 5 percent.
e. Frequency: 60 Hz.
f. Frequency regulation: Plus or minus 0.1 percent, when on internal oscillator. Internal oscillator is to be temperature compensated.
g. Frequency drift: Plus or minus 0.1 percent over any 24 hour interval (or length of test) at stated ambient conditions when on internal oscillator.
h. Harmonic content (RMS voltage): Provide a system that meets the following voltage THD levels: maximum of 4% RMS total,2 percent total with 100 percent on any single harmonic (linear load) and 5 percent RMS total for up to 100 percent nonlinear load.
i. Load power factor operating range (without derating): 0.9 leading to
0.9 lagging.
j. Phase angle displacement/imbalance:
(1) Balanced load: 120 degrees plus or minus 1 degree of bypass input.
SECTION 26 33 53 Page 13
(2) 50 percent load imbalance phase-to-phase: 120 degrees plus or minus 3 degrees of input.
k. Inverter overload capability (at full voltage with plus or minus 2 percent regulation) (excluding battery):
(1) 125 percent load for 10 minutes.
(2) 150 percent load for 60 seconds.
(3) Fault clearing. Provide an UPS that is able to maintain output current during a fault condition for 20 cycles if bypass is unavailable or 1 cycle with bypass available. If the fault is not cleared and a bypass is available, the UPS is to transfer to bypass without interruption to clear the fault.
l. Load sharing of parallel modules: Plus or minus 5 percent at full rated system load.
m. Bypass Overload Capability.
150 percent load for 15 seconds.
2.4.8 Transient Response
2.4.8.1 Voltage Transients
a. 100 percent load step: Plus or minus 5 percent.
b. Loss or return of ac input: Plus or minus 5 percent.
c. Automatic transfer of load from UPS to bypass: Plus or minus 1 percent.
d. Manual retransfer of load from bypass to UPS: Plus or minus 5 percent.
e. Response time: Recovery to 1 percent of nominal within 20 milliseconds where there was a maximum deviation from nominal system output of volts plus or minus 5 percent.
2.4.8.2 Frequency
a. Transients: Plus or minus 0.6 Hz maximum.
b. Slew Rate: under all conditions of operation, 0.25 to 0.8 Hz per second.
2.4.9 Efficiency
a. Minimum Single-Module Efficiency: 97 percent at full load kW and 92 percent at 50 percent load.
b. Minimum System Efficiency: 93 percent at full system load kW.
c. Provide Energy Star labeled battery charging systems and AC-DC/AC-AC power supplies. Provide proof of Energy Star label for battery charging systems and AC-DC/AC-AC power supply products.
SECTION 26 33 53 Page 14
2.4.10 Energy Saving Mode
Provide the UPS with an energy saving mode that operates by having the inverter charged and batteries on at all times, while the main power to the output is through the static bypass switch. When a power problem is sensed, the system is to operate in double-conversion mode and revert to energy saving mode after a pre-set period of time. Maximum transition time is 2 miliseconds.
2.5 UPS MODULE
2.5.1 General Description
UPS module consists of a rectifier/charger unit and a 3-phase inverter unit with their associated transformers, synchronizing equipment, protective devices, surge suppression, and accessories as required for operation.
2.5.1.1 Interchangeability
The subassemblies in one UPS module are to be interchangeable with the corresponding modules within the same UPS, and from one UPS system to another of identical systems.
2.5.1.2 Rectifier/Charger Unit
Provide a solid state rectifier/charger unit that converts alternating current to direct current, and provides regulated direct current to the dc bus, supplying power to the inverter and charging the battery plant.
2.5.1.2.1 Input Protective Device
Provide the rectifier/charger unit with an input protective device. Size the protective device to accept simultaneously the full-rated load and the battery recharge current. Provide a protective device that is capable of shunt tripping and has an amperes symmetrical interrupting rating of 65000 Amps. Provide the protective device with an under-voltage release to open automatically when the control voltage is lost.
2.5.1.2.2 Power Walk-In
Protect the rectifier/charger unit with a power walk-in feature such that when ac power is returned to the ac input bus, the total initial power requirement will not exceed 20 percent of the rated full load current.
This demand is to gradually increase to 100 percent of the rated full load current plus the battery charging current over the specified time interval.
2.5.1.2.3 Sizing
Size the rectifier/charger unit for the following two simultaneous operating conditions:
a. Supplying the full rated load current to the inverter.
b. Recharging a fully-discharged battery to 90 percent of rated ampere-hour capacity within ten times the discharge time after normal ac power is restored.
2.5.1.2.4 AC Input Current Limiting
Provide a circuit on the rectifier/charger to limit AC input current to an
SECTION 26 33 53 Page 15 adjustable level of 100 percent to 125 percent with a factory setting at 100 percent.
Second step current limiting: Provide the rectifier/charger unit with a second-step input current limit. Provide a separately adjustable second-step current limit that is adjustable from 85 percent to 125 percent of the maximum discharge current with initial setting at 100 percent. Activate the second-step current-limit circuit by a dry contact signal from the generator.
2.5.1.2.5 Battery Charging Current
a. Primary current limiting: Battery-charging current is to be voltage regulated and current limited. Provide a separately adjustable battery-charging current limit that is adjustable from 1 percent to 20 percent of the maximum discharge current. Set the limit at the factory to 10 percent. After the battery is recharged, the rectifier/charger unit maintains the battery at full float charge until the next operation under input power failure. Battery charger is capable of providing equalizing charge to the battery.
b. Second step current limiting: The rectifier/charger unit is also to have a second-step battery current limit. Provide a separately adjustable second-step current limit that is adjustable from 0 percent to 20 percent of the maximum discharge current with initial setting at 1 percent. The second-step current-limit circuit is activated by a dry contact signal from the generator set controls and it will prevent normal rate battery recharging until utility power is restored.
2.5.1.2.6 DC Ripple (Output Filter)
Rectifier/charger unit is to minimize ripple current and voltage supplied to the battery; the ripple voltage into the battery is not to exceed 1 percent RMS of the float voltage. Ensure the AC ripple voltage of the rectifier DC output does not exceed 0.5 percent of the float voltage.
2.5.1.2.7 DC Voltage Adjustment
Provide a manual means at the rectifier/charger unit that allows for adjusting the dc voltage for battery equalization in order to provide voltage within plus 10 percent of nominal float voltage.
2.5.1.2.8 Battery Isolation Protective Device
Provide the module or external battery system with a dc protective device to isolate the module from the battery system. The protective device size and interrupting rating are as required by system capacity and is to incorporate the trip required by circuit design. Provide the protective device with a provision for locking in the "off" position.
2.5.1.2.9 Battery Equalize Charge
Equalize charge timer is to provide an equalizing charge automatically to the battery after a 30 second or longer utility outage. The equalize charging time is to be adjustable form 0-72 hours. Provide a manual override for the automatic equalize circuit.
SECTION 26 33 53 Page 16
2.5.2 Inverter Unit
Provide a solid-state inverter with sinusoidal output deriving its power from the dc bus (rectifier or battery source) and providing ac power within specified limits to the critical load. Inverter is to utilize microprocessor controlled solid state Pulse Width Modulation (PWM) controlled insulated gate bipolar transistor (IGBT) power transistor technology to shape the ac output. Include a bypass phase synchronization window adjustment to optimize compatibility with local engine-generator-set power source.
2.5.2.1 Output Overload
Provide an inverter that is able to sustain an overload as specified across its output terminals. The inverter is to remain on and continue to operate within rated parameters, with inverse-time overload shutdown protection. If the overload condition persists beyond the rated parameters of the inverter, the load is to be transferred to the bypass source where the inverter disconnects automatically from the critical load bus. If the bypass source is not available and the overload/fault condition continues, the inverter is to current limit for the time as determined by the manufacturer and then shut down to protect the internal components.
2.5.2.2 Output Protective Device
Provide an output protective device that is capable of opening on an applied control signal and has the proper frame size and trip rating to supply overload current as specified. Provide the external output protective device with provision for locking in the "off" position. The inverter output protective device works in conjunction with the bypass protective device for both manual and automatic load transfers to and from bypass power.
2.5.3 External Protection
Provide the UPS module with built-in self-protection against undervoltage, overvoltage, overcurrent and surges introduced on the ac input source and/or the bypass source. Provide the UPS with built-in self-protection against overvoltage and voltage surges introduced at the output terminals by paralleled sources, load switching, or circuit breaker operation in the critical load distribution system.
2.5.4 Internal Protection
Provide the UPS module with the ability to be self-protected against overcurrent, sudden changes in output load and short circuits at the output terminals. Provide the UPS module with output reverse power detection which causes the module to be disconnected from the critical load bus when output reverse power is present. Provide the UPS module with built-in protection against permanent damage to itself and the connected load for predictable types of failure within itself and the connected load. At the end of battery discharge limit, the module shuts down without damage to internal components.
2.5.5 Battery Protection
Provide the inverter with monitoring and controls circuits to protect the battery system from damage due to excessive discharge. Inverter shutdown
SECTION 26 33 53 Page 17 is be initiated when the battery has reached the end of discharge voltage. Manufacturer is to calculate the end-of-discharge voltage and automatically adjusted for partial load conditions to allow extended operation without damaging the battery. Automatic shutdown based on discharge time is not acceptable.
2.5.6 Modular Inverter Isolation
Provide each inverter in the UPS system with fault sensing and static isolation as well as an output protective device, to remove a faulted module from the system without affecting the critical load bus beyond the stated limits.
2.5.7 Parallel Operation
For parallel operation, ensure the protection system has control logic capable of isolating only the faulted module, and does not shut down the entire UPS system upon a fault in one module. Open protective devices are to be indicated by an alarm and indicator light.
2.6 STATIC BYPASS TRANSFER CIRCUIT
Provide the control logic with an automatic transfer circuit that senses the status of the inverter logic signals and alarm conditions and provides an uninterrupted transfer of the load to the static bypass ac power source, without exceeding the transient limits specified herein, during times when maintenance is required, when a malfunction occurs in the UPS or when an external overload condition occurs. The power section of the static bypass transfer circuit consists of a plug-in type assembly to facilitate maintenance. The static bypass transfer circuit is to be used to connect the input bypass ac power source to the critical load when required. Provide the static bypass transfer circuit with the following features:
2.6.1 Construction
Provide a static with a continuous duty rating of at least 100 percent of the UPS output rating. Provide a static bypass transfer circuit as an integral part of the UPS that consists of a static switch, made up of two reverse-paralleled SCRs (silicon-controlled rectifiers) per phase conductor, and a bypass protective device, made up of a circuit breaker and fuses. The bypass protective device is to be in series with the static switch. The inverter output protective device disconnects and isolates the inverter from the bypass transfer circuit.
2.6.2 Automatic Uninterrupted Transfer
The static bypass transfer switch automatically causes the bypass ac power source to assume the critical load without interruption when the bypass control logic senses one of the following conditions and the UPS inverter output is synchronized to the bypass ac power source:
a. Inverter overload exceeds unit's rating.
b. Battery protection period is expired and bypass is available.
c. System failure.
d. Inverter output undervoltage or overvoltage.
SECTION 26 33 53 Page 18
2.6.3 Interrupted Transfer
If an overload occurs and the UPS inverter output is not synchronized to the bypass ac power source, the UPS inverter output current-limits for 200 milliseconds minimum. The inverter then turns off and an interrupted transfer to the bypass ac power source is made.
If the bypass ac power source is beyond the conditions stated below, an interrupted transfer is made upon detection of a fault condition:
a. Bypass voltage greater than plus or minus 10 percent from the UPS rated output voltage.
b. Bypass frequency greater than plus or minus 0.5 Hz from the UPS rated output frequency.
c. Phase differential of ac bypass voltage to UPS output voltage greater than plus or minus 3 degrees.
2.6.4 Manual Load Transfer
It must be possible to make a manually-initiated static transfer from the system status and control panel by turning the UPS inverter off or by initiating it through the UPS display interface. The transfer is to make-before-break utilizing the UPS output and system bypass circuit breakers. Do not use the static switch for manual transfer unless there isn't a parallel by-pass circuit breaker or contactor.
2.6.5 Automatic Uninterrupted Forward Transfer
Automatic transfer of the load back to the inverter is to take place when the transfer was caused by an overload and only after the load has returned to a level within the inverter souse. Provide the ability to allow 1 to 3 transfers within any one-hour period to prevent cyclical transfers caused by overloads.
2.6.6 Forced Transfer
Provide control logic circuitry with the means of making a forced or reverse transfer of the static bypass transfer circuit on an interrupted basis. Minimum interruption is 200 milliseconds when the UPS inverter is not synchronized to the bypass ac power source.
2.6.7 Overload Ratings
The static bypass transfer switch is to withstand the following overload conditions:
a. 1000 percent of UPS output rating for one cycle.
b. 125 percent of UPS output rating for 1 minute.
2.6.8 System Protection
Incorporate into the static bypass circuit back-feed protection per UL 1778 .
To achieve back-feed protection, provide a back-feed protection breaker/mechanical contactor upstream and in series with the bypass switch that is controlled by the UPS/static switch, to open immediately upon
SECTION 26 33 53 Page 19 sensing a condition where back-feeding of the static switch by any source connected to the critical output bus of the system is occurring.
2.6.9 Static Bypass Switch Disconnect
Incorporate a static switch disconnect that can be used to isolate the static bypass transfer switch assembly so it can be removed for servicing.
Equip the device with auxiliary contacts and provisions for padlocking in either the "on" or "off" position.
2.7 MAINTENANCE BYPASS CIRCUIT
2.7.1 Interlock
Electrically and mechanically interlock the switch(es) to prevent interrupting power to the load when switching to bypass mode. Key interlock requires unlocking bypass/isolating switch before switching from normal position with key that is released only when the UPS is bypassed by the static bypass transfer switch. Lock is designed specifically for mechanical and electrical component interlocking.
2.7.2 Load Transfer
The maintenance bypass switch provides the capability of transferring the critical load from the UPS static bypass transfer switch to maintenance bypass and then back to the UPS static bypass transfer switch with no interruption to the critical load.
2.8 DISPLAY,CONTROLS AND ALARMS
Provide the UPS module with a microprocessor-controlled display unit located on the hinged door on the front of the system. Provide a LCD color alphanumeric display that operated by touchscreen to access the various information. Controls, meters, alarms and indicators for operation of the UPS module are to be on this panel. Provide a menu driven graphical user interface for browsing the screens. All three-phases of three-phase parameters are to be displayed simultaneously.
2.8.1 Module Meters
2.8.1.1 Monitored Functions
Display the actual value along with the ability to show the peak, average and low values over various periods of time. Monitor and display the following functions:
a. Input voltage, phase-to-phase (all three phases).
b. Input current, all three phases.
c. Input frequency.
d. Bypass voltage, phase-to-phase and phase-to-neutral (all three phases).
e. Bypass frequency.
f. Battery voltage.
g. Battery current (charge/discharge).
SECTION 26 33 53 Page 20
h. Output voltage, phase-to-phase and phase-to-neutral (all three phases).
i. Output current, all three phases.
j. Output frequency.
k. Input power factor.
l. Maintenance bypass voltage, phase-to-phase and phase-to-ground (all three phases)
m. Bypass voltage, phase-to-phase (all three phases).
2.8.1.2 Meter Construction
Display alphanumeric parameters based on true RMS metering with 2 percent accuracy at full scale(minimum 4 significant digits) at the display panel.
2.8.2 Module Controls
Provide a module or equivalent features via touchscreen with the following controls:
a. Silence audible alarm..
b. Display or set the date and time.
c. Adjust setpoints on various alarms.
d. Alarm test/reset pushbutton.
e. Battery protective device trip pushbutton, with guard.
f. Emergency off pushbutton, with guard. Provide a hard-wired pushbutton even if touchscreen system is provided.
g. DC voltage adjustment potentiometer, with locking guard or AC output voltage adjustment potentiometer. Provide potentiometer that is accessible only by authorized personnel.
h. Control power off switch.
i. Transfer load to and from static bypass circuit.
j. Display control pushbuttons: up, down, select.
l. Module input protective device trip pushbutton.
m. Module output protective device trip pushbutton.
2.8.3 Module or System Alarm Indicators
Provide the module with indicators for the following alarm items. Any one of these conditions is to turn on an audible alarm and the appropriate summary indicator. The system is to register each new alarm without affecting any previous alarm. Provide a processor that time-date stamps each event.
SECTION 26 33 53 Page 21
a. Input ac power source failure.
b. Input protective device open.
c. Input power out of tolerance.
d. Overload.
e. Overload shutdown.
f. DC overvoltage/shutdown.
g. DC ground fault.
h. Low battery.
i. Battery discharged.
j. Battery protective device open.
k. Blower fan failure or overtemperature.
l. Overtemperature shutdown.
m. Hardware shutdown.
n. Equipment overtemperature.
o. Fuse blown with annunciation..
p. Control power failure.
q. Charger off/problem.
r. Inverter fault/off.
s. Emergency power off.
t. External shutdown (Remote Emergency Power Off) activated.
u. Output protective device open.
v. Operating on internal oscillator
w. UPS on battery
x. Critical load on static bypass.
y. Static bypass transfer switch disabled/failure.
z. Inverter output overvoltage.
aa. Inverter output undervoltage.
bb. Inverter output overfrequency.
cc. Inverter output underfrequency.
dd. Bypass source overvoltage.
SECTION 26 33 53 Page 22
ee. Bypass source undervoltage.
ff. Bypass source overfrequency.
gg. Bypass source underfrequency.
hh. Bypass source to inverter out of synchronization.
2.8.4 Module Emergency OFF Button
Provide an emergency off pushbutton with a protective cover. Pressing the emergency off button causes the module input, output, and battery circuit breakers or contactors to open, completely isolating the UPS system from sources of power and transfer of the load to bypass.
System Mimic Panel
Provide a mimic panel in the format of a single-line diagram that graphically depicts whether the load is supplied from the inverter, bypass, or battery. Provide on status on the following:
a. Module on-line, one per UPS module.
b. UPS output protective device status, one for closed (red), one for open (green), and one for withdrawn (amber).
c. Static bypass protective device status, one for closed (red), one for open (green), and one for withdrawn (amber).
d. Static switch status, one for connected (red), and one for disconnected (green).
e. Status on the AC input circuit breaker, battery circuit breaker, and inverter circuit breaker. Connected (red) and disconnected (green).
2.9 REMOTE MONITORING PANEL
2.9.1 Indicators
Provide indicators for the following (minimum):
a. Load on UPS.
b. Battery discharging.
c. Load on bypass.
d. Low battery.
e. Overload.
e. summary alarm.
f. New alarm (to alert the operator that a second summary alarm condition has occurred).
SECTION 26 33 53 Page 23
2.9.2 Audible Alarm
Any single indicator turns on the audible alarm. An audible alarm test/reset button and lamp test/reset button is to be included.