This is a Section 08 71 00 Door Hardware specification document for the Phase III Groundwater Treatment System federal contract (112G08005WE24), dated 02/16 with Change 4 effective 02/22.

The specification establishes comprehensive requirements for door hardware procurement and installation, including detailed product standards referenced to ANSI/BHMA, NFPA, SDI/DOOR, ASTM, and UL standards. Required submittals include manufacturer detail drawings, verification of existing conditions, hardware schedules, keying systems, product data, installation instructions, operation and maintenance data, and key bitting charts—all subject to government approval. The hardware must comply with ABA/ADA accessibility guidelines per 36 CFR 1191 and fire-rating requirements per NFPA standards. Specific product requirements include continuous hinges (6036-T6 aluminum, extra heavy duty), heavy-duty door closers (Series C02000, Grade 1 with PT 4C and 10-year warranty), mortise locks and latches (ANSI/BHMA A156.13, Series 1000), exit devices (Grade 1), electrified hardware with solenoid actuation (12 or 24 Volts DC), electromagnetic locks with 1200-pound holding force, and weatherstripping with maximum 0.5 cubic feet per minute air leakage when tested per ASTM E283. Hardware finishes must be BHMA 630 (satin stainless steel) or BHMA 626 (satin chromium plated) as specified. The specification includes seven lockset sets with varying configurations for different door types (storeroom, classroom, privacy, exit doors), each specifying quantity, product type, description, and finish requirements. Installation must follow manufacturer instructions with specific provisions for fastening to different surfaces, and hardware protection from damage until work acceptance. A coordination meeting between the Contracting Officer, contractor, door hardware subcontractor, and facility locksmith is required prior to key shop drawing submission.

View the file

Other files

File Type Posted
Amendment 0005 - N4008526R0161.pdf PDF
Wage Determination NY20260012 5.18.2026.pdf PDF
Amendment 0004 Phase III Groundwater Treatment Plant.pdf PDF
Attachment O- 43 21 13_R1.pdf PDF
Attachment L- 43 3113.13 10.pdf PDF
Amendment 0003 Phase III Groundwater Treatment Plant.pdf PDF
Interested Vendors List N4008526R0161.docx DOCX document
Attachment P- M101-R1.pdf PDF
Attachment Q- 50 03 01 R1.pdf PDF
Attachment R- A-112G08005-WE24 Phase III- A-102.pdf PDF
Attachment M - BP Phase III Spec Mod 06102026.pdf PDF
Amendment 0002 Phase III Groundwater Treatment Plant.pdf PDF
Attachment L - Section 43 31 13.13 10.pdf PDF
Amendment 0001 Phase III Groundwater Treatment Plant.pdf PDF
Attachment K- Phase_III_Photo_Log.pdf PDF
Attachment 3-Appendix E Phase III DWGs-CUI-REDACTED-NEW.pdf PDF
Attachment J- Site Location Map.pdf PDF
Attachment 1- Basis of Design-PHASE III GWTP_BODR_Feb 26 IFB To Navy_REDACTED.pdf PDF
Attachment A - Pre Proposal Inquiry Log.xlsx XLSX spreadsheet
Attachment B - PIEE Vendor Access Instructions.pdf PDF
Attachment H- Price Proposal Form.docx DOCX document
Attachment I - Wage Determination NY20260012.pdf PDF
Solicitation - N4008526R0161.pdf PDF
Attachment D - Past Performance Questionnaire.docx DOCX document
Attachment F - SBPCD.pdf PDF
Attachment H- Price Proposal Form.pdf PDF
Attachment E - Historical SB Utilization.pdf PDF
Attachment E - Historical SB Utilization.docx DOCX document
Attachment F - SBPCD.docx DOCX document
Attachment G - Individual SB Subcontracting Plan.docx DOCX document
ATTACHMENT 2- Appendix D_Combined Specs_Signed.pdf PDF
Attachment C - Construction Experience Project Data Sheet.pdf PDF
Attachment C - Construction Experience Project Data Sheet.docx DOCX document
Attachment D - Past Performance Questionnaire.pdf PDF
Attachment G - Individual SB Subcontracting Plan.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Phase III Groundwater Treatement System 112G08005WE24

SECTION 08 71 00

DOOR HARDWARE

02/16, CHG 4: 02/22

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM E283 (2019) Standard Test Method for Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen

BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)

ANSI/BHMA A156.1 (2021) Butts and Hinges

ANSI/BHMA A156.3 (2020) Exit Devices

ANSI/BHMA A156.4 (2013) Door Controls - Closers

ANSI/BHMA A156.5 (2020) Cylinder and Input Devices for Locks

ANSI/BHMA A156.6 (2021) Architectural Door Trim

ANSI/BHMA A156.7 (2016) Template Hinge Dimensions

ANSI/BHMA A156.8 (2021) Door Controls - Overhead Stops and Holders

ANSI/BHMA A156.13 (2022) Mortise Locks & Latches Series 1000

ANSI/BHMA A156.15 (2021) Release Devices Closer Holder, Electromagnetic and Electromechanical

ANSI/BHMA A156.16 (2023) Auxiliary Hardware

ANSI/BHMA A156.18 (2020) Materials and Finishes

ANSI/BHMA A156.19 (2013) Power Assist & Low Energy Power Operated Doors

ANSI/BHMA A156.21 (2019) Thresholds

ANSI/BHMA A156.22 (2021) Gasketing

ANSI/BHMA A156.23 (2010) Electromagnetic Locks

ANSI/BHMA A156.24 (2012) Delayed Egress Locking Systems

SECTION 08 71 00 Page 1

ANSI/BHMA A156.25 (2013) Electrified Locking Devices

ANSI/BHMA A156.26 (2012) Continuous Hinges

ANSI/BHMA A156.31 (2013) Electric Strikes and Frame Mounted Actuators

ANSI/BHMA A156.36 (2010) Auxiliary Locks

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 70 (2023; ERTA 4 2023) National Electrical Code

NFPA 72 (2022; ERTA 22-1) National Fire Alarm and Signaling Code

NFPA 80 (2022) Standard for Fire Doors and Other Opening Protectives

NFPA 101 (2021; TIA 21-1) Life Safety Code

NFPA 252 (2022) Standard Methods of Fire Tests of Door Assemblies

STEEL DOOR INSTITUTE (SDI/DOOR)

SDI/DOOR A250.8 (2023) Specifications for Standard Steel Doors and Frames

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines

UNDERWRITERS LABORATORIES (UL)

UL Bld Mat Dir (updated continuously online) Building Materials Directory

1.2 SUBMITTALS

Government approval is required for submittals with a "G" classification.

Submittals not having a "G" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Manufacturer's Detail Drawings; G

Verification of Existing Conditions; G

Hardware Schedule; G

Keying System; G

SECTION 08 71 00 Page 2

SD-03 Product Data

Hardware Items; G

SD-08 Manufacturer's Instructions

Installation

SD-10 Operation and Maintenance Data

Hardware Schedule Items, Data Package 1; G

SD-11 Closeout Submittals

Key Bitting

1.3 SHOP DRAWINGS

Submit manufacturer's detail drawings indicating all hardware assembly components and interface with adjacent construction. Indicate power components and wiring coordination for electrified hardware. Base shop drawings on verified field measurements and include verification of existing conditions.

1.4 PRODUCT DATA

Indicate fire-ratings at applicable components. Provide documentation of ABA/ADA accessibility compliance of applicable components, as required by 36 CFR 1191 Appendix D - Technical.

1.5 HARDWARE SCHEDULE

Provide Hardware Item List and Hardware Schedule containing the following information, and additional information as needed to identify the complete make up of each hardware set and its application to each opening:

1.5.1 Hardware Item List:

a. Hardware Type

b. Item Number

c. Quantity

d. Size(s)

e. Reference Publication / Type Number

f. Manufacturer's Name / Catalog Number

g. Key Control Symbols

h. UL Mark (If fire rated and listed)

i. BHMA Finish(es)

j. Remarks

SECTION 08 71 00 Page 3

1.5.2 Hardware Schedule

a. Hardware Set Number

b. Opening Number(s)

c. Opening Description (single/double leaf, hand, size, door/frame material)

d. Fire Rating

e. Sound Rating

f. Hardware Items

g. Quantity

h. Size

i. BHMA Finish

j. Remarks

In addition, submit hardware schedule data package 1 in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA.

1.6 KEY BITTING CHART REQUIREMENTS

1.6.1 Requirements

Submit key bitting charts to the Contracting Officer prior to completion of the work. Include:

a. Complete listing of all keys (e.g. AA1 and AA2).

b. Complete listing of all key cuts (AA1-123456, AA2-123458).

c. Tabulation showing which key fits which door.

d. Copy of floor plan showing doors and door numbers.

e. Listing of 20 percent more key cuts than are presently required in each master system.

1.7 QUALITY ASSURANCE

1.7.1 Hardware Manufacturers and Modifications

Provide, as far as feasible, locks, hinges, and closers of one lock, hinge, or closer manufacturer's make. Modify hardware as necessary to provide features indicated or specified.

1.7.2 Key Shop Drawings Coordination Meeting

Prior to the submission of the key shop drawing, the Contracting Officer, Contractor, Door Hardware Subcontractor, using Activity and Base Locksmith must meet to discuss and coordinate key requirements for the facility.

SECTION 08 71 00 Page 4

1.8 DELIVERY, STORAGE, AND HANDLING

Deliver hardware in original individual containers, complete with necessary appurtenances including fasteners and instructions. Mark each individual container with item number as shown on hardware schedule. Deliver permanent keys and removable cores to the Contracting Officer, either directly or by certified mail. Deliver construction master keys with the locks.

PART 2 PRODUCTS

2.1 TEMPLATE HARDWARE

Hardware applied to metal or to prefinished doors must be manufactured using a template. Provide templates to door and frame manufacturers in accordance with ANSI/BHMA A156.7 for template hinges. Coordinate hardware items to prevent interference with other hardware.

2.2 HARDWARE FOR FIRE DOORS AND EXIT DOORS

Provide all hardware necessary to meet the requirements of NFPA 72 for door alarms, NFPA 80 for fire doors, NFPA 101 for exit doors, NFPA 252 for fire tests of door assemblies, ABA/ADA accessibility requirements, and all other requirements indicated, even if such hardware is not specifically mentioned in paragraph HARDWARE SCHEDULE. Provide Underwriters Laboratories, Inc. labels for such hardware in accordance with UL Bld Mat Dir or equivalent labels in accordance with another testing laboratory approved in writing by the Contracting Officer.

2.3 HARDWARE ITEMS

Clearly and permanently mark with the manufacturer's name or trademark, hinges, pivots, locks, latches, exit devices, bolts and closers where the identifying mark is visible after the item is installed. For closers with covers, the name or trademark may be beneath the cover. Coordinate electrified door hardware components with corresponding components specified in Division 28 ELECTRONIC SECURITY SYSTEMS (ESS).

2.3.1 Hinges

Provide in accordance with ANSI/BHMA A156.1. Provide hinges that are 4-1/2 by 4-1/2 inch unless otherwise indicated. Construct loose pin hinges for interior doors and reverse-bevel exterior doors so that pins are non-removable when door is closed. Other anti-friction bearing hinges may be provided in lieu of ball bearing hinges.

2.3.2 Continuous Hinges

Where continuous hinges are required, provide in accordance with

ANSI/BHMA A156.26.

2.3.3 Locks and Latches

a. At exterior locations provide locksets of full stainless steel type 302 or 304 construction including fronts, strike, escutcheons, knobs, bolts and all interior working parts. Marine Grade I, fully non-ferrous.

SECTION 08 71 00 Page 5

2.3.3.1 Mortise Locks and Latches

Provide in accordance with ANSI/BHMA A156.13, Series 1000, Operational Grade 1, Security Grade 2. Provide knobs and roses of mortise locks with screwless shanks and no exposed screws.

2.3.3.2 Auxiliary Locks

Provide in accordance with ANSI/BHMA A156.36, Grade 1.

2.3.3.3 Combination Locks

Heavy-duty, mechanical combination lockset with five push buttons, standard sized knobs, 3/4 inch deadlocking latch, 2-3/4 inch backset. Locks to operate by pressing two or more of the buttons in unison or individually in the proper sequence. Inside knob operates the latch. Provide a keyed cylinder on the interior to permit setting the combination. Provide a keyed removable core cylinder on the exterior to permit bypassing the combination.

2.3.4 Exit Devices

Provide in accordance with ANSI/BHMA A156.3, Grade 1. Provide adjustable strikes for rim type and vertical rod devices. Provide open back strikes for pairs of doors with mortise and vertical rod devices. Provide touch bars in lieu of conventional crossbars and arms.

2.3.5 Cylinders and Cores

Provide cylinders and cores for new locks, including locks provided under other sections of this specification. Provide cylinders and cores with six pin tumblers. Provide cylinders from the products of one manufacturer, and provide cores from the products of one manufacturer. Rim cylinders, mortise cylinders, and knobs of bored locksets have interchangeable cores which are removable by special control keys. Stamp each interchangeable core with a key control symbol in a concealed place on the core.

2.3.6 Push Button Mechanisms

Provide in accordance with ANSI/BHMA A156.5, Grade 1.

2.3.7 Electrified Hardware

Comply with the requirements of NFPA 70 for wiring of electrified hardware.

2.3.7.1 Electric Strikes and Frame Mounted Actuators

Provide in accordance with ANSI/BHMA A156.31, Grade 1. Provide electric strikes and actuators as required to meet operational requirements.

Provide electric strikes that remain secure during power failure. Provide a separate power supply for electric strikes, other locking devices and ancillary parts. Provide strikes and actuators with a minimum opening force of 2300 pounds.

Provide facility interface devices that use direct current (dc) power to energize the solenoids. Provide electric strikes and actuators that incorporate end-of-line resistors to facilitate line supervision by the system. If not incorporated into the electric strike or local controller, provide metal oxide resistors (MOVs) to protect the controller from reverse

SECTION 08 71 00 Page 6 current surges.

2.3.7.1.1 Solenoid

Provide actuating solenoid for strikes and actuators that are rated for continuous duty, cannot dissipate more than 12 Watts and must operate on 12 or 24 Volts dc. Inrush current cannot exceed 1 ampere and the holding current cannot be greater than 500 milliamperes. Actuating solenoid must move from fully secure to fully open positions in less than 500 milliseconds.

2.3.7.1.2 Signal Switches

Provide strikes and actuators with signal switches to indicate to the system when the bolt is not engaged or the strike mechanism is unlocked.

Signal switches must report a forced entry to the system.

2.3.7.1.3 Tamper Resistance

Provide strike guards that prevent tampering with the latch bolt of the locking hardware or the latch bolt keeper of the electric strike. Strike guards to bolt through the door using tamper resistant screws. Provide strike guards made of 1/8 inch thick brass and that are 11-1/14 inch high by 1-5/8 inch wide, with a minimum 5/32 inch wide offset.

2.3.7.1.4 Coordination

Provide electric strikes and actuators of a size, weight and profile compatible with each specified door frame. Field verify installation clearances prior to procurement.

2.3.7.1.5 Mounting Method

Provide electric strikes and actuators suitable for use with single and double doors, with mortise or rim type hardware specified, and for right or left hand mounting as specified. In double door installations, locate the lock in the active leaf and monitor the fixed leaf.

2.3.7.2 Electrified Mortise Locks

Provide in accordance with ANSI/BHMA A156.25, Grade 1. Provide electrified mortise locks that remain secure during power failure. Provide facility interface devices that use dc power to energize solenoids. Provide solenoids, resisters, and signal switches in accordance with paragraph

ELECTRIC STRIKES AND FRAME MOUNTED ACTUATORS.

2.3.7.2.1 Power Transfer Hinges

Provide power transfer hinges with each electrified lock that route power and monitoring signals from the lockset to the door frame. Coordinate power transfer hinges with door frames.

2.3.7.3 Card Readers and Keypad Access Control Hardware

Coordinate access control hardware with corresponding devices and systems specified in Division 28 ELECTRONIC SECURITY SYSTEMS (ESS).

SECTION 08 71 00 Page 7

2.3.7.4 Release Devices

In accordance with ANSI/BHMA A156.15, Grade 1.

2.3.7.4.1 Release Devices

Provide wall mounted Electromagnetic release devices connected to fire and smoke detecting devices.

2.3.7.5 Power Assist and Low Energy Power Operated Doors

Provide in accordance with ANSI/BHMA A156.19, Grade 1.

2.3.7.6 Electromagnetic Locks

Provide in accordance with ANSI/BHMA A156.23, Grade 1. Provide electromagnetic locks that do not contain any moving parts and depend solely upon electromagnetism to secure a portal by generating at least 1200 pounds of holding force. The lock must interface with the local processors without external, internal or functional alteration of the local processor. The electromagnetic lock must incorporate an end of line resistor to facilitate line supervision by the system. Provide metal-oxide resistors (MOVs) to protect controllers from reverse current surges, if not incorporated into the electromagnetic lock or local controller.

2.3.7.6.1 Armature

Provide electromagnetic locks with internal circuitry to eliminate residual magnetism and inductive kickback. Provide atuating armature that operates on 12 or 24 Volts dc and cannot dissipate more than 12 Watts. Holding current must be less than 500 milliamperes. Actuating armature must take less than 300 milliseconds to change the status of the lock from fully secure to fully open or fully open to fully secure.

2.3.7.6.2 Tamper Resistance

Provide lock mechanism encased in hardened guard barriers to deter forced entry.

2.3.7.6.3 Mounting Method

Provide electromagnetic lock suitable for use with single and double door with mortise or rim type hardware and compatible with right or left hand mounting.

2.3.7.7 Delayed Egress Locking System

Provide in accordance with ANSI/BHMA A156.24, Grade 1.

2.3.8 Keying System

Provide a grand master keying system Provide construction interchangeable cores.

2.3.9 Lock Trim

Provide cast, forged, or heavy wrought construction and commercial plain design for lock trim.

SECTION 08 71 00 Page 8

2.3.9.1 Lever Handles

Provide lever handles where indicated in the Hardware Schedule. Provide in accordance with ANSI/BHMA A156.3 for mortise locks of lever handles for exit devices. Provide lever handle locks with a breakaway feature (such as a weakened spindle or a shear key) to prevent irreparable damage to the lock when force in excess of that specified in ANSI/BHMA A156.13 is applied to the lever handle. Provide lever handles return to within 1/2 inch of the door face.

2.3.10 Keys

Furnish one file key, one duplicate key, and one working key for each key change and for each master and grand master keying system. Furnish one additional working key for each lock of each keyed-alike group. Furnish 4 great grand master keys, 12 master keys, 15 construction master keys, and 4 control keys for removable cores. Stamp each key with appropriate key control symbol and "U.S. property - do not duplicate." Do not place room number on keys.

2.3.11 Door Bolts

Provide in accordance with ANSI/BHMA A156.16. Provide dustproof strikes for bottom bolts, except at doors having metal thresholds. Provide automatic latching flush bolts in accordance with ANSI/BHMA A156.3, Type 25.

2.3.12 Closers

Provide in accordance with ANSI/BHMA A156.4, Series C02000, Grade 1, with PT 4C. Provide with brackets, arms, mounting devices, fasteners, and other features necessary for the particular application. Size closers in accordance with manufacturer's printed recommendations, or provide multi-size closers, Sizes 1 through 6, and list sizes in the Hardware Schedule. Provide manufacturer's 10 year warranty.

2.3.12.1 Identification Marking

Engrave each closer with manufacturer's name or trademark, date of manufacture, and manufacturer's size designation in locations that will be visible after installation.

2.3.13 Overhead Holders

Provide in accordance with ANSI/BHMA A156.8.

2.3.14 Door Protection Plates

Provide in accordance with ANSI/BHMA A156.6.

2.3.14.1 Sizes of Armor Mop and Kick Plates

2 inch less than door width for single doors; 1 inch less than door width for pairs of doors. Provide 10 inch kick plates for flush doors .

Provide a minimum 36 inch armor plates for flush doors and completely cover lower panels of panel doors, except UL listed armor plates on fire doors.

Provide 10 inch mop plates.

SECTION 08 71 00 Page 9

2.3.15 Door Stops and Silencers

Provide in accordance with ANSI/BHMA A156.16. Silencers Type L03011.

Provide three silencers for each single door, two for each pair.

2.3.16 Thresholds

Provide in accordance with ANSI/BHMA A156.21. Use J35100, with vinyl or silicone rubber insert in face of stop, for exterior doors opening out, unless specified otherwise.

2.3.17 Weatherstripping Gasketing

Provide in accordance with ANSI/BHMA A156.22. Provide the type and function designation where specified in paragraph HARDWARE SCHEDULE.

Provide a set to include head and jamb seals, sweep strips, and, for pairs of doors, astragals. Air leakage of weatherstripped doors not to exceed 0.5 cubic feet per minute of air per square foot of door area when tested in accordance with ASTM E283. Provide weatherstripping with one of the following: Silicone rubber, or polyurethane inserts. Provide clear anodized aluminum.

2.3.17.1 Extruded Aluminum Retainers

Extruded aluminum retainers not less than 0.050 inch wall thickness with vinyl, neoprene, silicone rubber, or polyurethane inserts. Provide clear (natural) anodized aluminum.

2.3.17.2 Interlocking Type

Zinc or bronze not less than 0.018 inch thick.

2.3.17.3 Spring Tension Type

Spring bronze or stainless steel not less than 0.008 inch thick.

2.3.18 Lightproofing and Soundproofing Gasketing

Provide in accordance with ANSI/BHMA A156.22. Provide adjustable doorstops at heads,jambs and automatic door bottoms in accordance with the hardware set, of extruded aluminum, clear (natural) anodized, surface applied, with vinyl fin seals between plunger and housing. Provide doorstops with solid neoprene tube, silicone rubber, or closed cell sponge gasket. Provide door bottoms with adjustable operating rod and silicone rubber or closed cell sponge neoprene gasket. Provide doorstops that are mitered at corners.

Provide type and function designation where specified in paragraph HARDWARE

SETS.

2.3.19 Rain Drips

Provide in accordance with ANSI/BHMA A156.22. Provide extruded aluminum rain drips, not less than 0.08 inch thick, clear anodized finish. Provide the manufacturer's full range of color choices to the Contracting Officer for color selection. Provide rain drips with a 4 inch overlap on each side of each exterior door that is not protected by an awning, roof, eave or other horizontal projection. Set drips in sealant and fasten with stainless steel screws.

SECTION 08 71 00 Page 10

2.3.19.1 Door Rain Drips

Approximately 1-1/2 inch high by 5/8 inch projection. Align bottom with bottom edge of door.

2.3.19.2 Overhead Rain Drips

Approximately 1-1/2 inch high by 2-1/2 inch projection. Align bottom with door frame rabbet.

2.3.20 Auxiliary Hardware (Other than locks)

Provide in accordance with ANSI/BHMA A156.16, Grade 1.

2.3.21 Special Tools

Provide special tools, such as spanner and socket wrenches and dogging keys, as required to service and adjust hardware items.

2.4 FASTENERS

Provide fasteners of type, quality, size, and quantity appropriate to the specific application. Fastener finish to match hardware. Provide stainless steel or nonferrous metal fasteners in locations exposed to weather. Verify metals in contact with one another are compatible and will avoid galvanic corrosion when exposed to weather.

2.5 FINISHES

Provide in accordance with ANSI/BHMA A156.18. Provide hardware in BHMA 630 finish (satin stainless steel), unless specified otherwise. Provide items not manufactured in stainless steel in BHMA 626 finish (satin chromium plated) over brass or bronze, except aluminum paint finish for surface door closers, and except BHMA 652 finish (satin chromium plated) for steel hinges. Provide hinges for exterior doors in stainless steel with BHMA 630 finish or chromium plated brass or bronze with BHMA 626 finish. Furnish exit devices in BHMA 626 finish in lieu of BHMA 630 finish except where BHMA 630 is specified under paragraph HARDWARE SETS. Match exposed parts of concealed closers to lock and door trim. Match hardware finish for aluminum doors to the doors.

2.6 KEY CABINET AND CONTROL SYSTEM

Provide in accordance with ANSI/BHMA A156.5, Type required to yield a capacity (number of hooks) 50 percent greater than the number of key changes used for door locks.

PART 3 EXECUTION

3.1 INSTALLATION

Provide hardware in accordance with manufacturers' printed installation instructions. Fasten hardware to wood surfaces with full-threaded wood screws or sheet metal screws. Provide machine screws set in expansion shields for fastening hardware to solid concrete and masonry surfaces.

Provide toggle bolts where required for fastening to hollow core construction. Provide through bolts where necessary for satisfactory installation.

SECTION 08 71 00 Page 11

3.1.1 Weatherstripping Installation

Provide full contact, weathertight seals that allow operation of doors without binding the weatherstripping.

3.1.1.1 Stop Applied Weatherstripping

Fasten in place with color matched sheet metal screws not more than 9 inch on center after doors and frames have been finish painted.

3.1.1.2 Interlocking Type Weatherstripping

Provide interlocking, self adjusting type on heads and jambs and flexible hook type at sills. Nail weatherstripping to door 1 inch on center and to heads and jambs at 4 inch on center.

3.1.1.3 Spring Tension Type Weatherstripping

Provide spring tension type on heads and jambs. Provide bronze nails with bronze. Provide stainless steel nails with stainless steel. Space nails not more than 1-1/2 inch on center.

3.1.2 Lightproofing and Soundproofing Installation

Provide as specified for stop applied weatherstripping.

3.1.3 Threshold Installation

Extend thresholds the full width of the opening and notch end for jamb stops. Set thresholds in a full bed of sealant and anchor to floor with cadmium-plated, countersunk, steel screws in expansion sleeves. For aluminum thresholds placed on top of concrete surfaces, coat the underside surfaces that are in contact with the concrete with fluid applied waterproofing as a separation measure prior to placement.

3.2 FIRE DOORS AND EXIT DOORS

Provide hardware in accordance with NFPA 72 for door alarms, NFPA 80 for fire doors, NFPA 101 for exit doors, and NFPA 252 for fire tests of door assemblies.

3.3 HARDWARE LOCATIONS

Provide in accordance with SDI/DOOR A250.8, unless indicated or specified otherwise.

a. Kick and Armor Plates: Push side of single-acting doors. Both sides of double-acting doors.

b. Mop Plates: Bottom flush with bottom of door.

3.4 KEY CABINET AND CONTROL SYSTEM

Locate where directed. Tag one set of file keys and one set of duplicate keys. Place other keys in appropriately marked envelopes, or tag each key. Provide complete instructions for setup and use of key control system. On tags and envelopes, indicate door and room numbers or master or grand master key.

SECTION 08 71 00 Page 12

3.5 FIELD QUALITY CONTROL

After installation, protect hardware from paint, stains, blemishes, and other damage until acceptance of work. Submit notice of testing 15 days before scheduled, so that testing can be witnessed by the Contracting Officer. Adjust hinges, locks, latches, bolts, holders, closers, and other items to operate properly. Demonstrate that permanent keys operate respective locks, and give keys to the Contracting Officer. Correct, repair, and finish, errors in cutting and fitting and damage to adjoining work.

3.6 HARDWARE SETS

The hardware sets represent the design intent and direction of the owner and architect. They are a guideline only and should not be considered a detailed hardware schedule. Discrepancies, conflicting hardware and missing items should be brought to the attention of the architect with corrections made prior to the bidding process. Omitted items not included in a hardware set should be scheduled with the appropriate additional hardware required for proper application and functionality

A. Basis of Design Manufacturer's Abbreviations used in schedule:

1.Cores - BE - BEST

2. BA - BEA Inc

3. DO - Dorma

4. HA - Hager

5. KA - KABA-MAS

6. ME - Medeco

7. PE - Pemko

8. RO - Rockwood

9. SU - Securitron

10. VD - Von Duprin

Hardware Sets

SECTION 08 71 00 Page 13

Phase III Groundwater Treatment System 112G008005WE24

SECTION 01 71 00 PAGE [14]

Lockset Set No.1

Quantity Product Description Finish

2 EA Continuous

Hinge Continuous 6036-T6 Aluminum geared hinge. Extra

Heavy Duty. Concealed leaf.

2 EA Closer Heavy duty closer for push-side mounting with cast iron cylinder, heavy duty hold open arm, full cover and plates as required.

2 EA Overhead Stop Concealed, shock absorbing 630

2 EA Rim Exit Device

Outside trim, grade 1 626

2 EA Cylinder

1 EA

Removeable mullion for rim style exit device

2 EA Seals

2 EA Kick Plate Push side 630 2 EA Sweeps

1 EA Drip Guard 1 1/2" X 2 1/2" projection. Full width 627

1 EA Threshold 6" wide aluminum, accessible Mill finish

Lockset Set No.2

Quantity Product Description Finish

2 EA Continuous

Hinge

1 EA Closer Heavy duty closer for push-side mounting with cast and plates as required.

2 EA Overhead Stop Concealed, shock absorbing, fixed leaf to include hold open

2 EA Flush Bolt Heavy Duty

1 EA Mechanical Lockset

Mortise Storeroom set 626

1EA Cylinder

2 EA Seals

2 EA Kick Plate Push side 630

2 EA Sweeps

1 EA Drip Guard 1 1/2" X 2 1/2" projection. Full width 627

1 EA Astragal Aluminum gasketed Mill finish

1 EA Threshold 6" wide aluminum Mill finish

Lockset Set No.3

Quantity Product Description Finish

1 EA Continuous

Hinge

SECTION 01 71 00 PAGE [15]

1 EA Closer Heavy duty closer for push-side mounting with cast iron cylinder, heavy duty hold open arm, full cover and plates as required.

1 EA Overhead Stop Concealed, shock absorbing 630

1 EA

Rim Exit Device

Outside trim, grade 1

1 EA Cylinder

2 EA Seals

2 EA Kick Plate Push side 630

2 EA Sweeps

1 EA Drip Guard 1 1/2" X 2 1/2" projection. Full width 627

1 EA Threshold 6" wide aluminum, accessible Mill finish

Lockset Set No.4

Quantity Product Description Finish

2 EA Continuous

Hinge

2 EA Overhead Stop Concealed, shock absorbing, include hold open 630

2 EA Flush Bolt Heavy Duty

1 EA Mechanical Lockset

Mortise Storeroom set 626

1EA Cylinder

2 EA Kick Plate Push side 630

1 EA Astragal steel Match door

Lockset Set No.5

Quantity Product Description Finish

1 EA Continuous

Hinge and plates as required.

1 EA Overhead Stop Concealed, shock absorbing, include hold open 630

1 EA Mechanical Lockset

Mortise Storeroom set

1EA Cylinder

1 EA Kick Plate Push side 630

1 EA Mop plate Pull side 630

Lockset Set No.6

Quantity Product Description Finish

SECTION 01 71 00 PAGE [16]

1 EA Continuous

Hinge and plates as required.

1 EA Overhead Stop Concealed, shock absorbing, include hold open

1 EA Mechanical Lockset

Mortise Classroom set 626

1EA Cylinder

1 EA Kick Plate Push side 630

1 EA Mop plate Pull side 630

Lockset Set No.7

Quantity Product Description Finish

1 EA Continuous

Hinge and plates as required.

1 EA Overhead Stop Concealed, shock absorbing, include hold open

1 EA Mechanical Lockset

Mortise Privacy set 626

1EA Cylinder

1 EA Kick Plate Push side 630

1 EA Mop plate Pull side 630

END OF SECTION

00 00 00 Phase III - Spec Cover
00 00 01 TOC (4.22.26)
01 01 00 Scope of work_Master File
01 14 00
01 30 00
01 33 00
01 35 26
01 35 29.13
01 45 00.00 20
01 45 35
01 45 35a - si_schedule
01 45 35b - Statement_of_Special_Inspections
01 57 19
01 58 00
01 78 00
01 78 23
01 78 24.00 20
01 79 00 Functional Testing
01 91 00.15 10
01 91 13 Equipment Testing and Startup-NRS
01 91 13-1 Form & Table
03 30 00
03 45 00
04 20 00
05 05 23.16
05 12 00
05 21 00
05 30 00
05 40 00
05 50 13
05 52 00
06 10 00
06 41 16.00 10
06 61 16
06 71 33
06 73 01
06 82 14
07 19 00
07 21 13
07 21 16
07 27 10
07 27 19.01
07 60 00
07 61 14.00 20
07 84 00
07 92 00
08 11 13
08 22 20
08 33 23
08 51 13
08 60 45
08 71 00
08 91 00
09 22 00
09 29 00
09 30 10
09 51 00
09 65 00
09 65 30
09 90 00
09 96 00
10 14 00.10
10 28 13
10 44 16
10 51 13
13 34 19
13 48 73
22 00 00
26 05 00.00 20
26 05 19.10 10
26 05 26.00 20
26 05 71.00 20
26 24 16.00 20
26 24 19.00 20
26 28 01.00 10
26 29 23
26 41 00
26 51 00
27 10 00
27 13 23.00 20
28 10 05
31 10 00
31 23 00.00 20
32 11 20
32 11 26
32 12 13
32 16 19
32 17 23
32 31 13
32 92 19
33 11 00
33 30 00
33 31 23.00 10
33 40 00
33 61 13.19
33 71 02
33 82 00
40 60 00 00 Control Description_021826
Part 1. General
1.1 Description
1.2 Definitions
1.3 Abbreviations:
1.4 Submittals
Part 2. Not Used
Part 3. Execution
3.1 General Operating Discription
3.2 GROUNDWATER Extraction / RECOVERY System (MI602 THRu MI604)
3.3 Equalization Tank / FILTER FEED System (MI605)
3.4 MULTI-MEDIA FILTRATION (MMF) SYSTEM (MI606)
3.5 BAG FILTER System (MI606)
3.6 advanced oxidation process (aop) SYSTEM (MI607 and mi608)
3.7 Liquid Phase Granular Activated (LGAC) FEED System (MI609)
3.8 Liquid Phase Granular Activated (LGAC) carbon System (MI610)
3.9 PLANT EFFLUENT SYSTEM (MI610, MI611 & MI612)
3.10 MMF/LGAC Backwash System (MI611)
3.11 bACKWASH wASTE / DISCHARGE SYSTEM(mi621)
3.12 Caustic Feed System (MI614)
3.13 Hypochlorite Feed System (MI613)
3.14 HYDROGEN PEROXIDE Feed System (MI615)
3.15 Air Compressor System (MI618)
3.16 Building Sump System and BUILDING CONTAINMENt SYSTEM (mi616/MI620)
3.17 Eye Wash/safety Shower System (mi619)
3.18 PROCESS TANK VENTING SYSTEM (MI617)
3.19 NON-POTABLE WATER SYSTEM (mi617)
3.20 GAS MONITORS (MI607)
3.21 BUILDING AUTOMATION SYSTEM & FIRE ALARM CONTROL PANEL (MI620)
3.22 Loss of Power Mode
3.23 Plant Restart
3.24 E-Stop Mode
3.25 Human Machine Interface Requirements
3.26 Trending, Historical Archiving requirements:
3.27 Reports
3.28 Web Interface Requirements
3.29 Alarming Software and Configuration Requirements
3.30 Loss of Communication
40 60 00 2.4.4.1 Magnetic Flowmeter and Transmitter_021426
40 60 00 2.4.5.1 Ultrasonic Gap Level Switch_021226
40 60 00 2.4.5.3 Ultrasonic Level Transmitter_021226
40 60 00 2.4.5.5 Float Level Switch_021226
40 60 00 2.4.5.6 Hydrostatic Level Transmitter_021326
40 60 00 2.4.6 Pressure Gauge__021226
40 60 00 2.4.6.1 Pressure Transmitter__021226
40 60 00 2.4.6.2 Pressure Switch__021226
40 60 00 2.4.7.1 pH & ORP Measurement_021226
40 60 00 2.4.8.1 Bldg Temp Sensor_021226
40 60 00_2-20-2026
40 60 00_Control Description_021826
Part 1. General
1.1 Description
1.2 Definitions
1.3 Abbreviations:
1.4 Submittals
Part 2. Not Used
Part 3. Execution
3.1 General Operating Discription
3.2 GROUNDWATER Extraction / RECOVERY System (MI602 THRu MI604)
3.3 Equalization Tank / FILTER FEED System (MI605)
3.4 MULTI-MEDIA FILTRATION (MMF) SYSTEM (MI606)
3.5 BAG FILTER System (MI606)
3.6 advanced oxidation process (aop) SYSTEM (MI607 and mi608)
3.7 Liquid Phase Granular Activated (LGAC) FEED System (MI609)
3.8 Liquid Phase Granular Activated (LGAC) carbon System (MI610)
3.9 PLANT EFFLUENT SYSTEM (MI610, MI611 & MI612)
3.10 MMF/LGAC Backwash System (MI611)
3.11 bACKWASH wASTE / DISCHARGE SYSTEM(mi621)
3.12 Caustic Feed System (MI614)
3.13 Hypochlorite Feed System (MI613)
3.14 HYDROGEN PEROXIDE Feed System (MI615)
3.15 Air Compressor System (MI618)
3.16 Building Sump System and BUILDING CONTAINMENt SYSTEM (mi616/MI620)
3.17 Eye Wash/safety Shower System (mi619)
3.18 PROCESS TANK VENTING SYSTEM (MI617)
3.19 NON-POTABLE WATER SYSTEM (mi617)
3.20 GAS MONITORS (MI607)
3.21 BUILDING AUTOMATION SYSTEM & FIRE ALARM CONTROL PANEL (MI620)
3.22 Loss of Power Mode
3.23 Plant Restart
3.24 E-Stop Mode
3.25 Human Machine Interface Requirements
3.26 Trending, Historical Archiving requirements:
3.27 Reports
3.28 Web Interface Requirements
3.29 Alarming Software and Configuration Requirements
3.30 Loss of Communication
40 60 00_IO List_021826
Worksheets
SUMMARY
41 10 02 Process Piping
PART 1 - GENERAL
1.1 SCOPE OF WORK
1.1.1 Furnish all labor, materials, equipment and incidentals required to install all Process Piping and Appurtenances as shown on the drawings and specified herein. This specification covers the requirements for above and below grade groundwater and ...
1.1.2 All the process water piping as shown on drawings shall be PVC, except small bore piping (1” and below) for connecting to pressure gauges, instruments, sample ports, pipe drains, and pipe vents, which shall be as shown on drawings.
1.1.3 Piping shall include:
1.1.3.1 Water process piping from extraction vault and manholes to GWTP shall be PVC and HDPE piping as shown on contract drawings. HDPE piping shall be PE4710 SDR 11.
1.1.3.2 Water process piping from recovery well pumps to casing shall be stainless steel and piping inside extraction vaults shall be Schedule 80 PVC as shown on contract drawings.
1.1.3.3 Water process piping inside manholes shall be Schedule 80 PVC as shown on contract drawings.
1.2 RELATED SECTIONS
1.2.1 Sections Include:
1.2.1.1 Section 01 33 00 Submittals Procedures
1.2.1.2 Section 22 11 13 Facility Water Distribution Piping
1.2.1.3 Section 22 13 16 Sanitary Waste and Vent Piping
1.2.1.4 Section 22 42 13 Plumbing Fixtures
1.2.1.5 Section 31 00 00 Excavation, Backfill & Compaction
1.2.1.6 Section 46 30 00 Water and Wastewater Chemical Feed Systems
1.3 REFERENCES
1.3.1 The publications listed below form a part of this specification to the extent referenced.
1.3.1.1 American Society of Mechanical Engineers International (ASME)
1.3.1.1.1 B1.1: Unified Inch Screw Threads (UN and UNR Thread Form)
1.3.1.1.2 B1.20.1: Pipe Threads, General Purpose (Inch)
1.3.1.1.3 B1.20.7: Standard for Hose Coupling Screw Threads (Inch)
1.3.1.1.4 B16.11: Forged Fittings, Socket-Welding and Threaded
1.3.1.1.5 B16.21: Nonmetallic Flat Gaskets for Pipe Flanges
1.3.1.1.6 B16.3: Malleable Iron Threaded Fittings, Classes 150 and 300
1.3.1.1.7 B16.39: Standard for Malleable Iron Threaded Pipe Unions; Classes 150, 250, and 300
1.3.1.1.8 B16.5: Pipe Flanges and Flanged Fittings: NPS 1/2 through NPS 24 Metric/Inch Standard
1.3.1.1.9 B16.9: Standard for Factory-Made Wrought Steel Butt-welding Fittings
1.3.1.1.10 B18.2.1: Square and Hex Bolts and Screws (Inch Series)
1.3.1.1.11 B18.2.2: Standard for Square and Hex Nuts
1.3.1.1.12 B31.3: Process Piping
1.3.1.1.13 B36.19M: Stainless Steel Pipe
1.3.1.1.14 BPVC SEC VIII D1: BPVC Section VIII-Rules for Construction of Pressure Vessels Division 1
1.3.1.2 American Society for Testing and Materials (ASTM)
1.3.1.2.1 A181/A181M: Standard Specification for Carbon Steel Forgings, for General-Purpose Piping
1.3.1.2.2 D1784: Standard Specification for Rigid Poly (Vinyl Chloride) (PVC) Compounds
1.3.1.2.3 D1785: Standard Specification for Poly (Vinyl Chloride) (PVC), Plastic Pipe, Schedules 40, 80, and 120
1.3.1.2.4 D2104: Standard Specification for Polyethylene (PE) Plastic Pipe, Schedule 40
1.3.1.2.5 D2105: Standard Test for Longitudinal Tensile Properties of Reinforced Thermosetting Plastic Pipe and Tube
1.3.1.2.6 D2122: Standard Test Method for Determining Dimensions of Thermoplastic Pipe and Fittings
1.3.1.2.7 D 2241: Standard Specification for Poly (Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)
1.3.1.2.8 D2412: Standard Test for External Loading Properties of Plastic Pipe by Parallel-Plate Loading
1.3.1.2.9 D2447: Standard Specification for Polyethylene (PE) Plastic Pipe, Schedules 40 and 80, Based on Outside Diameter
1.3.1.2.10 D2464: Standard Specification for Threaded Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80
1.3.1.2.11 D2466: Standard Specification for Poly(Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40
1.3.1.2.12 D2467: Standard Specification for Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80
1.3.1.2.13 D2564: Standard Specification for Solvent Cements for Poly (Vinyl Chloride) (PVC) Plastic Piping Systems
1.3.1.2.14 D2609: Standard Specification for Plastic Insert Fittings for Polyethylene (PE) Plastic Pipe
1.3.1.2.15 D2737: Polyethylene (PE) Plastic Tubing ASTM D2774 (2012) Underground Installation of Thermoplastic Pressure Piping
1.3.1.2.16 D2855: Standard Practice for Making Solvent-Cemented Joints with Poly (Vinyl Chloride) (PVC) Pipe and Fittings
1.3.1.2.17 F2164: Standard Practice for Field Leak Testing of Polyethylene (PE) Pressure Piping Systems Using Hydrostatic Pressure
1.3.1.2.18 F2620: Standard Practice for Heat Fusion Joining of Polyethylene Pipe and Fittings
1.3.1.2.19 D3261: Standard Specification for Butt Heat Fusion Polyethylene (PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing
1.3.1.2.20 F477: Standard Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe
1.3.1.2.21 F593: Standard Specification for Stainless Steel Bolts, Hex Cap Screws, and Studs
1.3.1.2.22 F656: Primers for Use in Solvent Cement Joints of Poly(Vinyl Chloride) (PVC) Plastic Pipe and Fittings
1.3.1.2.23 F714: Polyethylene (PE) Plastic Pipe (SDR-PR) Based on Outside Diameter
1.3.1.3 American Welding Society (AWS):
1.3.1.3.1 B3.0: Welding Procedure and Performance Qualification
1.3.1.3.2 A5.11/A5.11M: Specification for Nickel and Nickel Alloy Welding Electrodes for Shielded Metal Arc Welding
1.3.1.3.3 A5.14/A5.14M: Specification for Nickel and Nickel Alloy Bare Welding Electrodes and Rods
1.3.1.3.4 D1.1/D1.1M: Structural Welding Code – Steel
1.3.1.4 American Water Works Association (AWWA)
1.3.1.4.1 C901: Polyethylene (PE) Pressure Pipe, Tubing and Fittings, 1/2" through 3" for Water
1.3.1.4.2 C906: Polyethylene (PE) Pressure Pipe and Fittings, 4" through 63", For Water Distribution
1.3.1.5 Manufacturers Standardization Society (MSS)
1.3.1.5.1 SP-25: Standard Marking System for Valves, Fittings, Flanges and Unions
1.3.1.5.2 SP-58: Standard for Pipe Hangers and Supports - Materials, Design and Manufacture
1.3.1.5.3 SP-69: Standard for Pipe Hangers and Supports - Selection and Application
1.3.1.5.4 SP-80: Bronze Gate, Globe, Angle, and Check Valves
1.3.1.5.5 SP-89: Pipe Hangers and Supports - Fabrication and Installation Practices
1.3.1.6 Plastics Pipe Institute (PPI)
1.3.1.6.1 TR-21: Thermal Expansion and Contraction in Plastic Piping Systems
1.3.1.7 Rubber Manufacturers Association (RMA)
1.3.1.7.1 IP-2: Hose Handbook
1.4 SUBMITTALS
1.4.1 The following shall be submitted in accordance with Section 01 33 00 Submittal Procedures:
1.4.1.1 Shop Drawings: Shop drawings and support system detail drawings showing piping and appurtenances including mechanical joints, valves, hangers, and pipe supports. Include a complete list of equipment and materials on the drawings.
1.4.1.2 Product Data: Manufacturer's descriptive and technical literature for each piping system, including design recommendations; pressure and temperature ratings; dimensions, type, grade and strength of pipe and fittings and chemical resistance.
1.4.1.3 Material safety data sheet in conformance with 29 CFR 1910 Section 1200(g) for each chemical (solvents, solvent cements, and glues) delivered for use in pipe installation.
1.4.1.4 Pipe Schedule: Provide a list of piping systems, pressure ratings and source of supply for each piping system broken out by material, size and application as indicated on the Contract Drawings. Provide a list of any special tools necessary for...
1.4.1.5 Valve and Valve Operator Schedule: Provide a list of valve materials, pressure ratings, and valve operator materials and reference identification as indicated in the Contract Drawings. Provide a list of any special tools necessary for each val...
1.4.1.6 Test Reports: Submit Pipe Leakage Tests, Hydrostatic Tests, Valve Testing; copies of all field test reports including Pipe Leakage Tests and Hydrostatic Tests.
1.4.1.7 As-built drawings: Show pipe anchors and guides, and layout of piping systems relative to other parts of the work including clearances for maintenance and operation. Submit as-built piping and instrumentation diagrams (P&IDs) identifying and ...
1.4.1.8 Instruction Manuals: Submit sufficient detail in the Operation Manuals to demonstrate the step-by-step procedures required for startup, operation and shutdown of piping systems, and include the manufacturer's name, model number, parts list and...
1.5 DELIVERY, STORAGE, AND HANDLING
1.5.1 Materials delivered and placed in storage shall be stored with protection from the weather, excessive humidity variation, excessive temperature variation, dirt, dust and/or other contaminants. Proper protection and care of material before, duri...
1.6 BUILDING PIPING SYSTEMS
1.6.1 Buried piping systems shall be suitable for design conditions, considering the piping both with and without internal pressure. Consideration shall be given to all operating and service conditions including forces both internal and external to th...
1.7 ABOVE GRADE PIPING SYSTEMS (WITHIN GWTP)
1.7.1 Above ground piping systems shall be suitable for design conditions, considering the piping both with and without internal pressure, and installation factors such as insulation, support spans, and ambient temperatures. Consideration shall be giv...
1.8 SEQUENCING AND SCHEDULING
1.8.1 For slab, floor, wall, and roof penetrations, keep on site pertinent wall pipes and sleeves before they are required for placement in concrete forms. Verify and coordinate the size and location of building pipe penetrations before forming and pl...
1.9 MAINTENANCE
1.9.1 Service
1.9.1.1 A manufacturer’s representative who is experienced in the installation, adjustment and operation of the valves specified shall provide inspection services for automatic valve systems. The representative shall inspect the installation, and sup...
1.9.2 Extra Materials
1.9.2.1 Contractor shall provide the manufacturer’s recommended spare parts that are expected to be replaced within the first 3 years of service of the piping system.
PART 2 - PRODUCTS
2.1 MATERIALS AND EQUIPMENT
2.1.1 Provide piping materials and appurtenances as specified and as shown on the Drawings. Piping materials, valves, and appurtenances supplied as part of this contract shall be of equal material and ratings as the connecting pipe, new and unused ex...
2.1.2 Piping systems shall be rated for at least 1.5 times the deadhead pressure of the pump feeding the piping.
2.1.3 Standard Products: Provide material which are the standard products of a manufacturer regularly engaged in the manufacturing of the products and that essentially duplicate items that have been in satisfactory use for at least 10 years prior to b...
2.1.4 Identification and Tagging: Each piece of pipe shall bear the ASTM designation and all other markings required for that designation. The service, valve identification number shown on the Contract Drawings, the manufacturer's name, and the valve...
2.1.5 Pipe Supports: Pipe shall be provided with supports spaced not farther than the manufacturer’s recommended spacing for 70 F service. For PVC pipe 2” or smaller, supports shall be every 5’ or less; for 3” pipe every 6’; for 4” pipe every 8’, and ...
2.1.6 The Contractor shall provide slip-type PVC expansion joints with joint material as recommended by the manufacturer for the type of service. Joints shall be installed not more than 100 feet apart only on all straight runs of pipe that exceed 100 ...
2.2 PLASTIC, DUCTILE IRON, AND CARBON STEEL PIPING AND FITTING FOR WATER PROCESS SERVICE
2.2.1 PVC Pipe: PVC pipe shall be Schedule 80, seamless, unplasticized polyvinyl chloride normal impact type, conforming to ASTM D-1784, Class 12454-B and D-1785, PVC 1120, for Type I, Grade 1. PVC pipe system shall be as manufactured by CertainTeed ...
2.2.2 PVC Joints: The piping system shall be joined by flanged or mechanical connections except where connecting to unions, valves, and equipment with threaded connections that may require future disassembly. Connections at those points shall be thre...
2.2.3 PVC Fittings: The schedule rating for the fittings shall not be less than that for the associated pipe. All pipe and fittings shall conform to ASTM D2467 and joints shall be solvent socket welded where threaded or flanged fittings are not used.
2.2.4 Flanged Fittings: Flanges shall be used at all valves, pumps, equipment, tanks, and vessels. Flanges will be of the same material as the piping. Flanges shall be the Van-Stone type complete with gaskets, bolts, and nuts. Flanges will be flat f...
2.2.5 PVC Solvent Cement: Joints shall be assembled using approved solvent cement in accordance with the manufacturer’s recommendations and ASTM D2564 and ASTM D2855. No cementing shall be done in the rain or when the air temperature is below 40 F or ...
2.2.6 The Contractor is cautioned to exercise care in handling, loading, unloading, and storing plastic pipe, valves, and fittings. All plastic pipe, valves, and fittings shall be stored under cover before using and shall be transported in a vehicle w...
2.2.7 All PVC piping, fittings, and valves shall not be painted.
2.2.8 Ductile Iron Pipe for pump discharge: Ductile iron piping shall meet requirements of ANSI/AWWA C151/A21.51 and ANSI/AWWA C150/A21.50. The pipes shall be flanged of Pressure Class 350 with nominal pipe thickness of 0.25 inches. Ductile iron pipe ...
2.2.9 Condensate Pipe: Piping for condensate shall be 316L stainless steel pipe meeting ASTM A312/AS312M standards.
2.2.10 Carbon Steel Pipe for recovery well and extraction vaults: Carbon steel piping shall meet requirements of A252 Grade and A500 Grade Carbon Steel pipe, ASTM A181/A181M for forged fittings, general process piping application and ASTM/ASME A106/SA...
2.3 PLASTIC PIPING AND FITTINGS FOR TANK VENTS
2.3.1 Plastic vent piping shall be Schedule 40 PVC pipe, seamless, unplasticized polyvinyl chloride normal impact type, conforming to ASTM D-1784, Class 12454-B and D-1785, PVC 1120, for Type I, Grade 1. PVC vent pipe system shall be as manufactured...
2.3.2 Vent piping shall be 8-inch diameter unless shown otherwise on the drawings. Standards: ASTM D 2665 and NSF approved for DWV; ASTM D 3034 for SDR.
2.3.3 Fittings: PVC material, solvent weld, Type 1, ASTM D 2466 for Schedule 40, and ASTM 2665 for DWV; ASTM D 3212 for SDR.
2.3.4 Joint material: Use solvent cement in accordance with industry standards and manufacturer's recommendations.
2.3.5 All vent pipe discharging outside shall have a rain guard and bird screen that is compatible.
2.4 VALVES AND SPECIALTIES (PVC PROCESS SERVICE)
2.4.1 General. The Contractor shall furnish and install all valves and specialties as specified herein and shown on the Drawings. In addition, valve-operator and other accessories shall be furnished and installed by the Contractor where specified for...
2.4.2 Check valves 2 inches and smaller for liquid service shall be Schedule 80 double-union ball check as manufactured by Nibco, Hayward, Chemline, or approved equal. Check valves shall be capable of operating in either the horizontal or the vertical...
2.4.3 Ball Valves (General Purpose). Ball valves upto 4 inch, shall be Schedule 80 PVC double-union ball valves with handle as manufactured by Nibco, Hayward, Chemline, or approved equal.
2.4.3.1 All sampling valves and drain a valves shall be 316 SS, provided with a spring return handle with a locking device similar to manufactured J Flow Controls LLC or equal.
2.4.4 Butterfly Valves. Butterfly valves, 3 inch and larger, shall be Schedule 80 PVC with lugs for flanged service. Butterfly valves shall have hand wheel or chain wheel operators. Butterfly valves shall be as manufactured by Nibco, Hayward, Cheml...
2.4.5 Pressure/Vacuum Relief Valve: Two pressure/vacuum pressure/vacuum breather valves shall be provided (one of which will be a backup). The valves shall be of stainless steel construction and shall be rated for atmospheric pressure (14.7 psi) and ...
2.4.6 Air/Vacuum release valves(vent valves)
2.4.6.1 Air/Vacuum release valves up to 3 inches, shall be combination air/vacuum release automatic PVC valves and provided as shown on the drawings. The valves shall have flanged ends and manufactured by Nibco, Hayward, Chemline or approved equal. Th...
2.4.7 Solenoid Valves
Solenoid valves shall be ASCO General Service Solenoid Valves with brass bodies and manufactured by Emerson or Approved Equal. Provide and install solenoid valves where shown on drawings.
Valve Actuation: Solenoid
Body Material: Brass
Seals and Discs: PTFE
Core Tube: 305 Stainless Steel
Core and Plugnut: 430F Stainless Steel
Spring: 302 Stainless Steel
Shading Coil: Copper
Media: Air, Inert Gas, Water, Light Oil
Pipe Size: 2”
Orifice Size: 1 ¾”
Port Type: NPTF
Function: 2 way-2/2 Normally Closed
Flow: 43 Cv
Voltage: 24 AC, 110AC, 115 AC, 12 DC, 12 to 24 DC
Voltage Ranging, 120 AC, 120 DC
Max Differential / Max Operating Pressure: Up to 150 psi
Operating Environment: Indoor, Outdoor
UL listed and CSA certified
2.6.7 Electric Actuators
Electric Actuators: Series 70 manufactured by Bray International Inc. or approved equal
Motor Service: 120 VAC, 1 phase, 60 Hz
Enclosure: Designed to meet NEMA Type 4X and IP65 specification
Certification: UL, CSA and CE approved
Torque output range: For 6” to 12” Butterfly valves from 1200 lb-in to 5000 lb-in with a safety factor of 1.3
OPEN/CLOSED limit switches
Manual Override: The actuator shall be equipped with a manual override handwheel to rotate the valve without electrical power. The manual override system shall ensure efficient manual operation without the use of extra tools or levers. A motor power c...
2.5 DRAINS AND VENT VALVES
2.5.1 All drain and vent valves may not be shown on the detailed drawings for individual pipelines; their absence will not relieve the Contractor of the responsibility for providing and installing them to complete the piping system for the use intende...