This is a specification document (Section 26 56 00) for exterior lighting systems to be installed at a federal facility (P-1112 Desal project 50140980), dated August 2021.
The specification mandates LED-based lighting systems with comprehensive performance and quality requirements. All luminaires must be UL-listed, complete with integrated LED drivers and light sources, constructed of non-corrosive materials with factory-applied finishes capable of surviving 2500 hours of ASTM B117 salt spray testing. Minimum requirements include L70 lumen maintenance of 50,000 hours per ANSI/IES standards, luminaire efficacy of 80 LPW for linear accent fixtures, 50 LPW for wall sconces, and 30 LPW for steplights, with Color Rendering Index of 70 minimum and Correlated Color Temperature of 4000 Kelvin or greater. LED drivers must be UL Class 1 or 2 constant-current type, operating at 120 volts 50/60 Hz, with power factor ≥0.90, Total Harmonic Distortion ≤20 percent, and integral thermal and surge protection meeting IEEE C62.41.2 elevated requirements. The lighting control system shall utilize passive photosensor control exclusively, with photosensors rated for 100 watts minimum at 120 volts per UL 773/773A standards, designed for 20-year service with zero-cross technology and metal oxide varistor surge protection.
Submittals require government approval for shop drawings, product data, photometric plans, ANSI/IES LM-79, LM-80, and TM-21 test reports from NVLAP-accredited laboratories, along with five-year luminaire and controls warranties covering materials, finish, and workmanship. Installation must comply with manufacturer specifications, followed by 72-hour operational testing and commissioning verification. The contractor must provide comprehensive operation and maintenance manuals, maintenance staff training, and end-user training per specified plans submitted 30 days prior to training sessions.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-1112 Desal 50140980
SECTION 26 56 00
EXTERIOR LIGHTING
08/21
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B117 (2019) Standard Practice for Operating Salt Spray (Fog) Apparatus
EUROPEAN UNION (EU)
Directive 2011/65/EU (2011) Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment
ILLUMINATING ENGINEERING SOCIETY (IES)
ANSI/IES LM-79 (2019) Approved Method: Electrical and Photometric Measurements of Solid State Lighting Products
ANSI/IES LM-80 (2020) Approved Method: Measuring Luminous Flux and Color Maintenance of LED Packages, Arrays and Modules
ANSI/IES LS-1 (2020) Lighting Science: Nomenclature and Definitions for Illuminating Engineering
ANSI/IES RP-8 (2018; Addenda 1 2020; Errata 1-2 2021) Recommended Practice for Design and Maintenance of Roadway and Parking Facility Lighting
ANSI/IES TM-15 (2020) Technical Memorandum: Luminaire Classification System for Outdoor Luminaires
ANSI/IES TM-21 (2021) Technical Memorandum: Projecting Long-TermLuminous, Photon, and Radiant Flux Maintenance of LED Light Sources
IES Lighting Library IES Lighting Library
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE C62.41.2 (2002) Recommended Practice on
SECTION 26 56 00 Page 1
Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA ANSLG C78.377 (2017) Electric Lamps— Specifications for the Chromaticity of Solid State Lighting Products
NEMA C82.77-10 (2020) Harmonic Emission Limits - Related Power Quality Requirements
NEMA C136.10 (2023) American National Standard for Roadway and Area Lighting Equipment-Locking-Type Photocontrol Devices and Mating Receptacles--Physical and Electrical Interchangeability and Testing
NEMA C136.31 (2023) Roadway and Area Lighting Equipment
- Luminaire Vibration
NEMA IEC 60529 (2004) Degrees of Protection Provided by Enclosures (IP Code)
NEMA SSL 1 (2016) Electronic Drivers for LED Devices, Arrays, or Systems
NEMA SSL 3 (2011) High-Power White LED Binning for General Illumination
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 4 2023) National Electrical Code
UNDERWRITERS LABORATORIES (UL)
UL 773 (2016; Reprint Jul 2020) UL Standard for Safety Plug-In, Locking Type Photocontrols for Use with Area Lighting
UL 773A (2016; Reprint Jun 2020) UL Standard for Safety Nonindustrial Photoelectric Switches for Lighting Control
UL 1310 (2018; Reprint Jun 2022) UL Standard for Safety Class 2 Power Units
UL 1598 (2021; Reprint Jun 2021) Luminaires
UL 8750 (2015; Reprint Sep 2021) UL Standard for Safety Light Emitting Diode (LED) Equipment for Use in Lighting Products
SECTION 26 56 00 Page 2
1.2 RELATED REQUIREMENTS
Luminaires and accessories installed in interior of buildings or attached to the exterior of a building are specified in Section 26 51 00 INTERIOR LIGHTING. Commissioning requirements are specified in Section 01 91 00.15
TOTAL BUILDING COMMISSIONING.
1.3 DEFINITIONS
a. Unless otherwise specified or indicated, electrical and electronics terms used in these specifications and on the drawings must be as defined in IEEE 100 and ANSI/IES LS-1 .
b. For LED luminaire light sources, "Useful Life" is the operating hours before reaching 70 percent of the initial rated lumen output (L70) with no catastrophic failures under normal operating conditions. This is also known as 70 percent "Rated Lumen Maintenance Life" as defined in ANSI/IES LM-80 .
c. For LED luminaires, "Luminaire Efficacy" (LE) is the appropriate measure of energy efficiency, measured in lumens/watt. This is gathered from LM-79 data for the luminaire, in which absolute photometry is used to measure the lumen output of the luminaire as one entity, not the source separately and then the source and housing together.
d. Total Harmonic Distortion (THD) is the Root Mean Square (RMS) of all the harmonic components divided by the total fundamental current.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Luminaire Drawings ; G
Sequence of Operation for Exterior Lighting Control System ; G
SD-03 Product Data
Luminaires ; G
Light Sources ; G
LED Drivers ; G
Luminaire Warranty ; G
Lighting Controls Warranty ; G
SECTION 26 56 00 Page 3
Motion Sensors ; G
Photosensors ; G
Lighting Contactor ; G
Brackets
Obstruction Marker Luminaires ; G
SD-05 Design Data
Luminaire Design Data ; G
Photometric Plan ; G
SD-06 Test Reports
ANSI/IES LM-79 Test Report ; G
ANSI/IES LM-80 Test Report ; G
ANSI/IES TM-21 Test Report ; G
SD-10 Operation and Maintenance Data
Lighting System , Data Package 5; G
Exterior Lighting Control System , Data Package 5; G
Maintenance Staff Training Plan ; G
End-User Training Plan ; G
1.5 QUALITY ASSURANCE
Data, drawings, and reports must employ the terminology, classifications and methods prescribed by the IES Lighting Library as applicable, for the lighting system specified.
1.5.1 Drawing Requirements
1.5.1.1 Luminaire Drawings
Include dimensions, effective projected area (EPA), weight, accessories, and installation and construction details. Photometric data, including CRI, CCT, TM-15-11 BUG rating, LED driver type, zonal lumen data, and candlepower distribution data per LM-79 must accompany shop drawings.
SECTION 26 56 00 Page 4
1.5.2 Luminaire Design Data
a. Provide distribution data according to IES classification type as defined in IES Lighting Library and ANSI/IES RP-8 .
b. B.U.G. rating for the installed position as defined by ANSI/IES TM-15 and shielding as defined by ANSI/IES RP-8 .
c. Provide safety certification and file number for the luminaire family. Include listing, labeling and identification in accordance with NFPA 70 (NEC). Applicable testing bodies are determined by the US Occupational Safety Health Administration (OSHA) as Nationally Recognized Testing Laboratories (NRTL) and include: CSA (Canadian Standards Association), ETL (Edison Testing Laboratory), and UL (Underwriters Laboratories).
d. Provide long term lumen maintenance projections for each LED luminaire in accordance with ANSI/IES TM-21 . Data used for projections must be obtained from testing in accordance with ANSI/IES LM-80 .
1.5.3 ANSI/IES LM-79 Test Report
Submit test report on manufacturer's standard production model of specified luminaire. Testing must be performed at the same operating drive current as specified luminaire. Include all applicable and required data as outlined under "14.0 Test Report" in ANSI/IES LM-79 .
1.5.4 ANSI/IES LM-80 Test Report
Submit report on manufacturer's standard production LED light source (package, array, or module) of specified luminaire. Testing must be performed at the same operating drive current as specified luminaire.
Include all applicable and required data as outlined under "8.0 Test Report" in ANSI/IES LM-80 .
1.5.5 ANSI/IES TM-21 Test Report
Submit test report on manufacturer's standard production LED light source (package, array or module) of specified luminaire. Testing must be performed at the same operating drive current as specified luminaire.
Include all applicable and required data, as well as required interpolation information as outlined under "7.0 Report" in ANSI/IES TM-21 .
1.5.6 Test Laboratories
Test laboratories for the ANSI/IES LM-79 and ANSI/IES LM-80 test reports must be one of the following:
a. National Voluntary Laboratory Accreditation Program (NVLAP) accredited for solid-state lighting testing as part of the Energy-Efficient Lighting Products laboratory accreditation program.
b. One of the qualified labs listed on the Department of Energy - Energy Efficiency & Renewable Energy, Solid-State Lighting web site.
c. One of the EPA-Recognized Laboratories listed at for LM-80 testing.
SECTION 26 56 00 Page 5
1.5.7 Regulatory Requirements
Equipment, materials, installation, and workmanship must be in accordance with the mandatory provisions of NFPA 70 unless more stringent requirements are specified or indicated. Provide luminaires and assembled components that are approved by and bear the label of UL for the applicable location and conditions unless otherwise specified.
1.5.8 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship. Products must have been in satisfactory commercial or industrial use for six months prior to bid opening. The six-month period must include applications of equipment and materials under similar circumstances and of similar size. The product must have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the six-month period. Where two or more items of the same class of equipment are required, these items must be products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.5.8.1 Alternative Qualifications
Products having less than a six-month field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.5.8.2 Material and Equipment Manufacturing Date
Do not use products manufactured more than six months prior to date of delivery to site, unless specified otherwise.
1.6 WARRANTY
Support all equipment items by service organizations which are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
1.6.1 Luminaire Warranty
Provide and transfer to the government the original LED luminaire manufacturers standard commercial warranty for each different luminaire manufacturer used in the project.
a. Provide a written five year minimum replacement warranty for material, luminaire finish, and workmanship. Provide written warranty document that contains all warranty processing information needed, including customer service point of contact, whether or not a return authorization number is required, return shipping information, and closest return location to the luminaire location.
(1) Finish warranty must include failure and substantial deterioration such as blistering, cracking, peeling, chalking, or fading.
(2) Material warranty must include:
SECTION 26 56 00 Page 6
(a) All LED drivers and integral control equipment.
(b) Replacement when more than 15 percent of LED sources in any lightbar or subassembly(s) are defective, non-starting, or operating below 70 percent of specified lumen output.
b. Warranty period must begin in accordance with the manufacturer's standard warranty starting date.
c. Provide replacements that are promptly shipped, without charge, to the using Government facility point of contact and that are identical to or an improvement upon the original equipment. All replacements must include testing of new components and installation.
1.6.2 Lighting Controls Warranty
Provide and transfer to the government the original lighting controls manufacturers standard commercial warranty for each different lighting controls manufacturer used in the project. Warranty coverage must begin from date of final system commissioning or three months from date of delivery, whichever is the earliest. Warranty service must be performed by a factory-trained engineer or technician.
a. Unless otherwise noted, provide a written five year minimum warranty on the complete system for all systems with factory commissioning.
Provide warranty that covers 100 percent of the cost of any replacement parts and services required over the five years which are directly attributable to the product failure. Failures include, but are not limited to, the following:
(1) Software: Failure of input/output to execute switching or dimming commands.
(2) Damage of electronic components due to transient voltage surges.
(3) Failure of control devices, including but not limited to photosensors and motion sensors.
b. Provide a written five year minimum warranty on all input devices against defect in workmanship or materials provided by device manufacturer.
c. Provide a written five year minimum warranty on all control components attached to luminaires against defect in workmanship or materials.
1.7 OPERATION AND MAINTENANCE MANUALS
1.7.1 Lighting System
Provide operation and maintenance manuals for the lighting system in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA that provide basic data relating to the design, operation, and maintenance of the lighting system. Additional requirements for the Navy are provided in Section 01 78 24 22 FACILITY ELECTRONIC OPERATION AND MAINTENANCE SUPPORT INFORMATION (eOMSI) . Include the following:
a. Manufacturers' operating and maintenance manuals.
SECTION 26 56 00 Page 7
b. Luminaire shop drawings for modified and custom luminaires.
c. Luminaire Manufacturers' standard commercial warranty information as specified in paragraph LUMINAIRE WARRANTY.
1.7.2 Exterior Lighting Control System
Provide operation and maintenance manuals for the exterior lighting control system in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA that provide basic data relating to the design, operation, and maintenance of the exterior lighting control system.
Include the following:
a. Control System One-Line Diagram
b. Product data for all devices, including installation and programming instructions.
c. Training materials, such as videos or in-depth manuals, that cover basic operation of the lighting control system and instructions on modifying the control system. Training materials must include calibration, adjustment, troubleshooting, maintenance, repair, and replacement.
PART 2 PRODUCTS
2.1 PRODUCT COORDINATION
2.2 LUMINAIRES
UL 1598 , NEMA C82.77-10 . Provide luminaires as indicated in the luminaire schedule and XL plates or details on project plans, complete with light source, wattage, and lumen output indicated. All luminaires of the same type must be provided by the same manufacturer. Luminaires must be specifically designed for use with the LED driver and light source provided.
2.2.1 Luminaires
UL 8750 , ANSI/IES LM-79 , ANSI/IES LM-80 . For all luminaires, provide:
a. Complete system with LED drivers and light sources.
b. Housing constructed of non-corrosive materials. All new aluminum housings must be anodized or powder-coated. All new steel housings must be treated to be corrosion resistant.
c. ANSI/IES TM-21 , ANSI/IES LM-80 . Minimum L70 lumen maintenance value of 50,000 hours unless otherwise indicated in the luminaire schedule.
Luminaire drive current value must be identical to that provided by test data for luminaire in question.
d. Minimum efficacy as specified in the luminaire schedule. Theoretical models of initial lamp lumens per watt are not acceptable. If efficacy values are not listed in the luminaire schedule, provide luminaires that meet the following minimum values:
SECTION 26 56 00 Page 8
Luminaire Style Minimum Luminaire Efficacy
Linear Accent (facade, wallwash) 80 LPW
Exterior Wall Sconce 50 LPW
Steplight 30 LPW
e. Product rated for operation within an ambient temperature range of minus 22 degrees F to 104 degrees F .
f. UL listed for wet locations. Optical compartment for LED luminaires must be sealed and rated a minimum of IP65 per NEMA IEC 60529 .
g. IES Lighting Library . Light distribution and NEMA field angle classifications as indicated in luminaire schedule on project plans.
h. Housing finish that is baked-on enamel, anodized, or baked-on powder coat paint. Finish must be capable of surviving ASTM B117 salt fog environment testing for 2500 hours minimum without blistering or peeling.
i. LED driver and light source package, array, or module are accessible for service or replacement without removal or destruction of luminaire.
j. ANSI/IES TM-15 . Does not exceed the BUG ratings as listed in the luminaire schedule. If BUG ratings are not listed in the luminaire schedule, provide luminaires that meet the following minimum values for each application and mounting conditions:
Lighting Application Mounting Conditions BUG Rating
Pedestrian Post-Top All B2-U1-G1
Exterior Wall Sconce Above 4 feet AFF B1-U0-G2
Exterior Wall Sconce Below or at 4 feet AFF B4-U0-G4
Steplight Above 4 feet AFF B1-U1-G2
Steplight Below or at 4 feet AFF B4-U1-G4
Lighting Application Mounting Conditions BUG Rating
k. Fully assembled and electrically tested prior to shipment from factory.
l. Finish color is as indicated in the luminaire schedule or detail on the project plans.
m. Lenses constructed of clear tempered glass or UV-resistant acrylic.
n. All factory electrical connections are made using crimp, locking, or latching style connectors. Twist-style wire nuts are not acceptable.
o. NEMA C136.31 . Comply with 3G vibration testing.
p. Luminaire arm bolts constructed from 304 stainless steel or zinc-plated steel.
SECTION 26 56 00 Page 9
q. Incorporate modular electrical connections, and construct luminaires to allow replacement of all or any part of the optics, heat sinks, LED drivers, surge suppressors and other electrical components using only a simple tool, such as a manual or cordless electric screwdriver.
2.2.2 Obstruction Marker Luminaires
Provide obstruction marker luminaires for facilities as required by the FAA.
2.3 LIGHT SOURCES
NEMA ANSLG C78.377 , NEMA SSL 3. Provide type, lumen rating, and wattage as indicated in luminaire schedule on project plans.
2.3.1 LED Light Sources
Provide LED light sources that meet the following requirements:
a. NEMA ANSLG C78.377 . Emit white light and have a nominal Correlated Color Temperature (CCT) of 4000 Kelvin or greater.
b. Minimum Color Rendering Index (CRI) of 70.
c. Directive 2011/65/EU . Restriction of Hazardous Substances (RoHS) compliant.
d. Light source color consistency by utilizing a binning tolerance within a 4-step McAdam ellipse.
2.4 LED DRIVERS
NEMA SSL 1, UL 1310 . Provide LED Drivers that are electronic, UL Class 1 or Class 2, constant-current type and meet the following requirements:
a. The combined LED driver and LED light source system is greater than or equal to the minimum luminaire efficacy values as listed in the luminaire schedule provided.
b. Operate at a voltage of 120 volts at 50/60 hertz, with input voltage fluctuations of plus or minus 10 percent.
c. Power Factor (PF) greater than or equal to 0.90 at full input power and across specified dimming range.
d. Maximum Total Harmonic Distortion (THD) less than or equal to 20 percent at full input power and across specified dimming range.
e. Operates for at least 50,000 hours at maximum case temperature and 90 percent non-condensing relative humidity.
f. Meets the "Elevated" (10kV/10kA) requirements per IEEE C62.41.2 -2002. Manufacturer must indicate whether failure of the electrical immunity system can possibly result in disconnect of power to luminaire. Provide surge protection that is integral to the LED driver.
g. Contains integral thermal protection that reduces the output power to protect the driver and light source from damage if the case
SECTION 26 56 00 Page 10 temperature approaches or exceeds the driver's maximum operating temperature.
h. Complies with the requirements of the Federal Communications Commission (FCC) rules and regulations, Title 47 CFR part 15, Non-Consumer (Class A) for EMI/RFI (conducted and radiated).
i. Class A sound rating for all drivers mounted under a covered structure, such as a canopy, or where otherwise appropriate.
j. Directive 2011/65/EU . Restriction of Hazardous Substances (RoHS) compliant.
k. UL listed for wet locations typical of exterior installations.
l. Non-dimmable.
m. Rated to operate between ambient temperatures of minus 22 degrees F and 104 degrees F .
2.5 LIGHTING CONTROLS
Provide a passive control system with exclusively photosensor control methods.
2.5.1 Devices 2.5.1.1 Photosensors
UL 773 , UL 773A . Provide Photosensors that meet the following requirements:
a. Hermetically sealed, silicon diode light sensor type, rated at 100 watts minimum , 120 volts, 50/60 Hz with single-pole, double-throw contacts.
b. Turns ON at 1 to 3 footcandles and turns OFF at 3 to 15 footcandles .
c. Designed to fail to the ON position.
d. Housing is constructed of UV stabilized polypropylene, rated to operate within a temperature range of minus 40 to 158 degrees F .
e. Time delay that prevents accidental switching from transient light sources.
g. Designed for 20-year service to match life expectancy of long-life LED fixtures and exceed 15,000 operations at full load. Provide photosensors with zero-cross technology to withstand severe in-rush current and extend relay life.
i. NEMA C136.10 . Twist-lock receptacle type. Provide with solid brass prongs and voltage markings and color coding on exterior of housing.
j. Provide photosensors with metal oxide varistor (MOV) type surge protection.
SECTION 26 56 00 Page 11
2.6 EQUIPMENT IDENTIFICATION
2.6.1 Manufacturer's Nameplate
Each item of equipment must have a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
2.6.2 Labels
UL 1598 . Luminaires must be clearly marked for operation of specific light sources and drivers according to proper light source type. Note the following luminaire characteristics in the format "Use Only _____":
a. Correlated color temperature (CCT) and color rendering index (CRI) for all luminaires.
b. Driver and dimming protocol.
Markings related to light source type must be clear and located to be readily visible to service personnel, but unseen from normal viewing angles when light sources are in place. LED drivers must have clear markings indicating dimming type and indicate proper terminals for the various outputs.
2.7 FACTORY APPLIED FINISH
NEMA 250. Provide all luminaires and lighting equipment with factory-applied painting system that as a minimum meets requirements of corrosion-resistance testing.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Luminaires
Install all luminaires in accordance with the luminaire manufacturer's written instructions. Install all luminaires at locations and heights as indicated on the project plans. Level all luminaires in accordance to manufacturer's written instructions.
3.1.2 LED Drivers
Provide LED drivers integral to luminaire as constructed by the manufacturer.
3.1.3 Lighting Controls
3.1.3.1 Photosensors
Aim photosensor according to manufacturer's recommendations. Mount sensor on or beside each luminaire when switch is provided in cast weatherproof aluminum housing with swivel arm. Set adjustable window slide for 1-10 footcandles photosensor turn-on.
SECTION 26 56 00 Page 12
3.1.4 Grounding
Ground noncurrent-carrying parts of equipment including luminaires, mounting arms, brackets, and metallic enclosures. Where copper grounding conductor is connected to a metal other than copper, provide specially treated or lined connectors suitable for this purpose.
3.2 FIELD QUALITY CONTROL
3.2.1 Tests
Upon completion of installation, verify that equipment is properly installed, connected, and adjusted. Perform initial operational test, consisting of the entire system energized for 72 consecutive hours without any failures of any kind occurring in the system. All circuits must test clear of faults, grounds, and open circuits.
3.2.1.1 Lighting Control Verification Test
Verify lighting control system and devices operate according to approved sequence of operations. Verification tests are to be completed after commissioning.
3.3 CLOSEOUT ACTIVITIES
3.3.1 Training
Provide on-site training to the Owner's personnel in the operation and maintenance of lighting and lighting control system. Provide training that includes calibration, adjustment, troubleshooting, maintenance, repair, and replacement.
3.3.1.1 Maintenance Staff Training
Submit a Maintenance Staff Training Plan at least 30 calendar days prior to training session that describes training procedures for Owner's personnel in the operation and maintenance of lighting and lighting control system. Provide on-site training which demonstrate full system functionality, assigning schedules, calibration adjustments for light levels and sensor sensitivity, integration procedures for connecting to third-party devices, and manual override including information on appropriate use. Provide protocols for troubleshooting, maintenance, repair, and replacement, and literature on available system updates and process for implementing updates.
3.3.1.2 End-User Training
Submit a End-User Training Plan at least 30 calendar days prior to training session that describes training procedures for end-users on the lighting control system. Provide demonstration for each type of user interface. Provide users with the curfew schedule as currently commissioned, including conditional programming based on astronomic time clock functionality. Provide users with the correct contact information for maintenance personnel who will be available to address any lighting control issues.
-- End of Section --