The specifications require dual function flush valve water closets, manually operated metering faucets for lavatories, emergency eyewash and shower facilities in battery storage areas, and natural gas water heaters for domestic water. The document mandates copper tubing for above-ground piping, PVC for below-ground waste piping, and cast iron for vent systems. Specific requirements include backflow preventers, master thermostatic mixing valves, floor drains with trap primers in mechanical rooms and restrooms, and a compressed air system meeting ISO 8573.1 class 2.4.4 standards. The facility must also include small commercial ice machines in laundry rooms, breathing quality air compressors, and tank fill stations. All installations must comply with International Plumbing Code (IPC) and UFC 3-420-01 standards.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P‐909 SOF SDVT2 Operations Support Facility Work Order Number: 1704761
JEB Little Creek, VA
PART 3 - CHAPTER 6 / ESR D20 - Page 1
6. ENGINEERING SYSTEMS REQUIREMENTS
D20 PLUMBING
Refer to Part 4 Section D20 for performance requirements of the building elements included in the plumbing system.
SYSTEM DESCRIPTION
The plumbing system consists of all fixtures, potable cold and hot water piping and equipment, piping insulation, water heating equipment, sanitary waste and vent piping systems, and other specialty piping and equipment within 5 feet (1.5 meters) of the building. Refer to Building Requirements, Space Tabulations Section, of the Project Program for building occupancy levels.
GENERAL SYSTEM REQUIREMENTS
Provide working space around all equipment. Provide concrete pads under all floor-level equipment.
Provide all required fittings, connections and accessories required for a complete and usable system.
Install all equipment in accordance with the criteria of PTS section D20 and the manufacturer’s recommendations. Design and install in accordance with International Plumbing Code (IPC) and UFC 3-420-01, Plumbing Systems. Where the word "should" is used in the manufacturer’s recommendations, substitute the word "must."
Do not route piping above electrical equipment rooms, to ensure that electrical equipment is protected from fluid falling off piping in the future.
D2010 PLUMBING FIXTURES
Provide quantity and type of plumbing fixtures required for the occupancy, use, and functions described for this facility. Refer to Room Requirements Section for additional specific requirements for spaces with plumbing fixtures. Provide handicapped fixtures in accordance with the referenced criteria in the Project Program.
D201001 WATER CLOSETS
Refer to Room Requirement Section for the number and type of water closets required.
Provide floor mounted dual function flush valve water closets in all public restroom spaces.
D201002 URINALS
Refer to Room Requirement Section for the number and type of urinals required.
Provide flush valve urinals in all public restroom spaces.
D201003 LAVATORIES
Refer to Room Requirement Section for the number and type of lavatories required.
Provide countertop lavatories with manually operated (i.e. not automatically controlled) metering faucet in each restroom space.
PART 3 - CHAPTER 6 / ESR D20 - Page 2
D201004 SINKS
Refer to Room Requirement Section for the number and type of sinks required.
D201005 SHOWERS/TUBS
Refer to Room Requirement Section for the number of showers required.
D201006 DRINKING FOUNTAINS AND COOLERS
Refer to Room Requirement Section for the number and type of drinking fountains required.
D201090 EMERGENCY FIXTURES
Provide emergency eyewash and shower in the battery storage space.
Provide tepid water (90F to 100F) with water tempering valve assembly.
Provide alarms and appurtenances for service within NEMA type 3 or 4 enclosures.
D2020 DOMESTIC WATER DISTRIBUTION
Perform a flow test to determine system requirements.
D202001 PIPES AND FITTINGS
Provide Copper tubing and fittings for above ground piping.
D202002 VALVES & HYDRANTS
Provide isolation valves at supply to each floor. Provide hose bibbs in mechanical rooms. Provide hose bibbs along the building exterior such that all points along the perimeter can be reached with a 50 foot long hose. Provide hose bibbs on each roof such that all roof-mounted mechanical equipment can be reached with a 50 foot long hose.
D202003 DOMESTIC WATER EQUIPMENT
Provide backflow preventers of types and at points within domestic water systems as specified by IPC. Locate building backflow preventer inside a mechanical room on service entrance lines where not provided exterior to the building. Provide reduced pressure principle type backflow preventer at all make-up water lines inside each mechanical room and at all make-up water lines to systems containing chemical treatment.
Refer to ESR G30 for water meter requirements.
Provide natural gas water heater for heating of domestic water.
Provide master thermostatic mixing valve.
Provide domestic hot water recirculation system with high efficiency recirculation pump and
PART 3 - CHAPTER 6 / ESR D20 - Page 3 recirculation loop with all associated fixtures, equipment, and appurtenances.
D202004 INSULATION & IDENTIFICATION
Provide mineral fiber insulation with vapor barrier on domestic hot water supply and recirculation piping. Provide flexible cellular-elastomeric thermal insulation for domestic cold water supply piping.
Provide identification for piping and equipment.
D202005 SPECIALTIES
Provide small commercial ice machine in each laundry room. Provide recessed connector wall box, fabricated of PVC plastic, with bronze shut-off valve. Provide floor sink for ice machine drain.
D202090 OTHER DOMESTIC WATER SUPPLY
Provide piping supports in accordance with the IPC. Provide inspections, disinfection, and testing in accordance with the IPC.
D2030 SANITARY WASTE
D203001 WASTE PIPE & FITTINGS
Provide PVC pipe and fittings, for below ground installation.
D203002 VENT PIPE & FITTINGS
Provide cast iron hub and spigot pipe and fittings, rubber compression gasket joints.
D203003 FLOOR DRAINS
Provide floor drains in mechanical rooms, restrooms, and plumbing chase areas.
Provide a water supply trap primer to each floor drain unless an exception is permitted by the Government. Locate each trap primer in the overhead area with easy access (e.g. removable acoustical ceiling tile or ceiling access door) for maintenance and replacement. Do not locate trap primers in walls.
D203004 SANITARY & VENT EQUIPMENT
Not Used.
D2040 RAIN WATER DRAINAGE
Provide Cast iron hub and spigot pipe and fittings above ground.
D204002 ROOF DRAINS
Provide roof drains that are compatible with the roofing system.
D204004 INSULATION & IDENTIFICATION
PART 3 - CHAPTER 6 / ESR D20 - Page 4
Provide the same as domestic water piping.
D204090 OTHER RAIN WATER DRAINAGE SYSTEM
Not Used.
D2090 OTHER PLUMBING SYSTEMS
D209001 SPECIAL PIPING SYSTEMS
Provide breathing quality air compressors and tank fill stations.
D209002 ACID WASTE SYSTEMS
D209003 INTERCEPTORS
Not used.
D209005 COMPRESSED AIR SYSTEM (NON-BREATHING)
Refer to Room Requirement Section for the number and type of compressed air systems. Provide air compressor, and receiver. Provide piping and compressed air drops with quick disconnects throughout the work areas to allow connection of equipment such as pneumatic tools and air guns. Air quality of ISO 8573.1 class 2.4.4 is acceptable.
D209090 OTHER SPECIAL PLUMBING SYSTEMS
Not used.
--End of Section--