This is an Engineering Systems Requirements document (ESR D20) for plumbing systems at the P-909 SOF SDVT2 Operations Support Facility at JEB Little Creek, VA. The document details comprehensive plumbing requirements including fixtures, water distribution, and specialty systems.

The specifications require dual function flush valve water closets, manually operated metering faucets for lavatories, emergency eyewash and shower facilities in battery storage areas, and natural gas water heaters for domestic water. The document mandates copper tubing for above-ground piping, PVC for below-ground waste piping, and cast iron for vent systems. Specific requirements include backflow preventers, master thermostatic mixing valves, floor drains with trap primers in mechanical rooms and restrooms, and a compressed air system meeting ISO 8573.1 class 2.4.4 standards. The facility must also include small commercial ice machines in laundry rooms, breathing quality air compressors, and tank fill stations. All installations must comply with International Plumbing Code (IPC) and UFC 3-420-01 standards.

View the file

Other files

File Type Posted
Attachment D - P909 Price Proposal Form R3.docx DOCX document
24R2862 Amendment 0014.docx DOCX document
Attachment D - P909 Price Proposal Form R2.docx DOCX document
P909 Amendments Index.pdf PDF
24R2862 Amendment 0013.pdf PDF
Attachment B Wage Determination.pdf PDF
Attachment X - Lithium Battery Current Quantities.pdf PDF
24R2862 Amendment 0012.pdf PDF
Section 01 14 00 R0824.pdf PDF
24R2862 Amendment 0011.pdf PDF
W_LIttle Creek Oneline.pdf PDF
V_Secured Area Second Floor.pdf PDF
24R2862 Amendment 0010.pdf PDF
24R2862 Amendment 0009.pdf PDF
24R2862 Amendment 0008.pdf PDF
1704761-CS101.pdf PDF
DOD_Anti-ram_Vehicle_Barriers_September_2024.pdf PDF
6_ESR_A20.pdf PDF
---5_RR_G209 WOMENS TOILET.pdf PDF
24R2862 Amendment 0007.pdf PDF
Part 2 General Requirements.pdf PDF
5_RR_D105_MAINTENANCE RM-O2 SAFE.pdf PDF
5_RR_D106_MAINTENANCE RM.pdf PDF
5_RR_D109_COMPRESSOR ROOM.pdf PDF
3_site_analysis.pdf PDF
5_RR_D104_BATTERY STORAGE.pdf PDF
NAVFAC High Performance and Sustainable Building Checklist GOALS.pdf PDF
5_RR_G111_MENS TOILET.pdf PDF
---5_RR_G207 MENS TOILET.pdf PDF
6_ESR_D30.pdf PDF
5_RR G108 WOMENS TOILET AND SHOWER.pdf PDF
Part 3 Chapter 1 changes.pdf PDF
5.0_Room.Requirements_Amendment.0006.pdf PDF
SPACE TABULATION.23Oct2024xlsx.pdf PDF
U_Telecommunication_Point_Of_Connection.pdf PDF
Spec.ESR_Amendment.0006.pdf PDF
24R2862 Amendment 0006.pdf PDF
24R2862 Amendment 0005.pdf PDF
24R2862 Amendment 0004.pdf PDF
24R2862 Amendment 0003 Site Visit Log.pdf PDF
24R2862 Amendment 0002.pdf PDF
Attachment J - PTS_SECTION_Z10.pdf PDF
Attachment I - 1704761 CONTINUATION SHEET Ammendement 0002.pdf PDF
ATTACHMENT G - SECNAV FORM 5512.pdf PDF
ATTACHMENT H - ONE DAY PASS FORM.xls XLS spreadsheet
24R2862 Amendment 0001.pdf PDF
Attachment A- R18_P909_RFP Plans_23.12.11 SITE PLAN.pdf PDF
24R2862 SOF General Requirements.pdf PDF
Attachment C-Pre-Proposal Inquiry Form.xlsx XLSX spreadsheet
Attachment F - JA ML-22-02 Class FRCS Standardization.pdf PDF
Show 40 more

Latest 50 of 52 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P‐909 SOF SDVT2 Operations Support Facility Work Order Number: 1704761

JEB Little Creek, VA

PART 3 - CHAPTER 6 / ESR D20 - Page 1

6. ENGINEERING SYSTEMS REQUIREMENTS

D20 PLUMBING

Refer to Part 4 Section D20 for performance requirements of the building elements included in the plumbing system.

SYSTEM DESCRIPTION

The plumbing system consists of all fixtures, potable cold and hot water piping and equipment, piping insulation, water heating equipment, sanitary waste and vent piping systems, and other specialty piping and equipment within 5 feet (1.5 meters) of the building. Refer to Building Requirements, Space Tabulations Section, of the Project Program for building occupancy levels.

GENERAL SYSTEM REQUIREMENTS

Provide working space around all equipment. Provide concrete pads under all floor-level equipment.

Provide all required fittings, connections and accessories required for a complete and usable system.

Install all equipment in accordance with the criteria of PTS section D20 and the manufacturer’s recommendations. Design and install in accordance with International Plumbing Code (IPC) and UFC 3-420-01, Plumbing Systems. Where the word "should" is used in the manufacturer’s recommendations, substitute the word "must."

Do not route piping above electrical equipment rooms, to ensure that electrical equipment is protected from fluid falling off piping in the future.

D2010 PLUMBING FIXTURES

Provide quantity and type of plumbing fixtures required for the occupancy, use, and functions described for this facility. Refer to Room Requirements Section for additional specific requirements for spaces with plumbing fixtures. Provide handicapped fixtures in accordance with the referenced criteria in the Project Program.

D201001 WATER CLOSETS

Refer to Room Requirement Section for the number and type of water closets required.

Provide floor mounted dual function flush valve water closets in all public restroom spaces.

D201002 URINALS

Refer to Room Requirement Section for the number and type of urinals required.

Provide flush valve urinals in all public restroom spaces.

D201003 LAVATORIES

Refer to Room Requirement Section for the number and type of lavatories required.

Provide countertop lavatories with manually operated (i.e. not automatically controlled) metering faucet in each restroom space.

PART 3 - CHAPTER 6 / ESR D20 - Page 2

D201004 SINKS

Refer to Room Requirement Section for the number and type of sinks required.

D201005 SHOWERS/TUBS

Refer to Room Requirement Section for the number of showers required.

D201006 DRINKING FOUNTAINS AND COOLERS

Refer to Room Requirement Section for the number and type of drinking fountains required.

D201090 EMERGENCY FIXTURES

Provide emergency eyewash and shower in the battery storage space.

Provide tepid water (90F to 100F) with water tempering valve assembly.

Provide alarms and appurtenances for service within NEMA type 3 or 4 enclosures.

D2020 DOMESTIC WATER DISTRIBUTION

Perform a flow test to determine system requirements.

D202001 PIPES AND FITTINGS

Provide Copper tubing and fittings for above ground piping.

D202002 VALVES & HYDRANTS

Provide isolation valves at supply to each floor. Provide hose bibbs in mechanical rooms. Provide hose bibbs along the building exterior such that all points along the perimeter can be reached with a 50 foot long hose. Provide hose bibbs on each roof such that all roof-mounted mechanical equipment can be reached with a 50 foot long hose.

D202003 DOMESTIC WATER EQUIPMENT

Provide backflow preventers of types and at points within domestic water systems as specified by IPC. Locate building backflow preventer inside a mechanical room on service entrance lines where not provided exterior to the building. Provide reduced pressure principle type backflow preventer at all make-up water lines inside each mechanical room and at all make-up water lines to systems containing chemical treatment.

Refer to ESR G30 for water meter requirements.

Provide natural gas water heater for heating of domestic water.

Provide master thermostatic mixing valve.

Provide domestic hot water recirculation system with high efficiency recirculation pump and

PART 3 - CHAPTER 6 / ESR D20 - Page 3 recirculation loop with all associated fixtures, equipment, and appurtenances.

D202004 INSULATION & IDENTIFICATION

Provide mineral fiber insulation with vapor barrier on domestic hot water supply and recirculation piping. Provide flexible cellular-elastomeric thermal insulation for domestic cold water supply piping.

Provide identification for piping and equipment.

D202005 SPECIALTIES

Provide small commercial ice machine in each laundry room. Provide recessed connector wall box, fabricated of PVC plastic, with bronze shut-off valve. Provide floor sink for ice machine drain.

D202090 OTHER DOMESTIC WATER SUPPLY

Provide piping supports in accordance with the IPC. Provide inspections, disinfection, and testing in accordance with the IPC.

D2030 SANITARY WASTE

D203001 WASTE PIPE & FITTINGS

Provide PVC pipe and fittings, for below ground installation.

D203002 VENT PIPE & FITTINGS

Provide cast iron hub and spigot pipe and fittings, rubber compression gasket joints.

D203003 FLOOR DRAINS

Provide floor drains in mechanical rooms, restrooms, and plumbing chase areas.

Provide a water supply trap primer to each floor drain unless an exception is permitted by the Government. Locate each trap primer in the overhead area with easy access (e.g. removable acoustical ceiling tile or ceiling access door) for maintenance and replacement. Do not locate trap primers in walls.

D203004 SANITARY & VENT EQUIPMENT

Not Used.

D2040 RAIN WATER DRAINAGE

Provide Cast iron hub and spigot pipe and fittings above ground.

D204002 ROOF DRAINS

Provide roof drains that are compatible with the roofing system.

D204004 INSULATION & IDENTIFICATION

PART 3 - CHAPTER 6 / ESR D20 - Page 4

Provide the same as domestic water piping.

D204090 OTHER RAIN WATER DRAINAGE SYSTEM

Not Used.

D2090 OTHER PLUMBING SYSTEMS

D209001 SPECIAL PIPING SYSTEMS

Provide breathing quality air compressors and tank fill stations.

D209002 ACID WASTE SYSTEMS

D209003 INTERCEPTORS

Not used.

D209005 COMPRESSED AIR SYSTEM (NON-BREATHING)

Refer to Room Requirement Section for the number and type of compressed air systems. Provide air compressor, and receiver. Provide piping and compressed air drops with quick disconnects throughout the work areas to allow connection of equipment such as pneumatic tools and air guns. Air quality of ISO 8573.1 class 2.4.4 is acceptable.

D209090 OTHER SPECIAL PLUMBING SYSTEMS

Not used.

--End of Section--