The specification details extensive requirements for a second-floor men's restroom including STC 55 minimum rated floor, roof and exterior assemblies, RF shielding requirements for a fully protected 6-sided box, and specific construction requirements like 4" minimum normal weight concrete flooring. The room must have a 9'-0" minimum ceiling height and includes detailed specifications for fixtures and finishes including porcelain tile floors and walls, solid surface counters with integral sinks, HDPE toilet partitions, and various accessories like electric hand dryers and paper towel dispensers. Technical systems requirements include dedicated exhaust, HVAC, fire alarm/sprinkler systems, lighting per UFC 3-530-01 standards, and emergency power backup. The space must be centrally located to second floor office suites and meet plumbing fixture counts per UFC requirements.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761 JEB Little Creek-Fort Story, Norfolk, Virginia
5.0 ROOM REQUIREMENTS
G207 – MEN’S TOILET
Space Characteristics
FUNCTION: Men’s restroom. Provide adequate fixture counts per Plumbing UFC and associated Occupant loads.
ADJACENCIES: Locate centrally to second floor office suites.
SPATIAL REQUIREMENTS:
Ideal Plan Dimensions: See Floor Plans.
Minimum Ceiling Height: 9’-0” Ceiling
ACOUSTICAL REQUIREMENTS: Unless Otherwise Noted:
EXTERIOR: Provide STC 55 (min) rated floor, roof and exterior envelope and window assemblies for entire second level.
INTERIOR: Provide STC 55 (min) rated interior partitions for entire second level.
NUMBER OF OCCUPANTS: 0 PN
SPECIAL REQUIREMENTS: Provide RF Shielding and required RF mitigations for floor, roof, exterior envelope and window assemblies for entire second level. For the second floor, provide fully protected (6) sided box.
UNIFORMAT DESCRIPTION QTY SIZE SPECIFIC REQUIREMENTS
B1010 FLOOR CONSTRUCTION – STC 55 (MIN) AR AR
4" (min) normal weight concrete on 2” (min) deep, 20ga (min) composite steel deck & a minimum total slab thickness of 6”. Reinforce with 6x6-W2.9xW2.9 WWR.
STC 55 (min) lab-tested rating.
B1010 FLOOR – RF SHIELDING AR AR
Provide RF Shielding and required RF mitigations within entire second floor assembly.
B301090 OTHER ROOFING – STC 55 (MIN) AR AR
All second floor roof assemblies shall provide an STC 55 (min) lab-tested rating.
B301090 OTHER ROOFING – RF SHIELDING AR AR
Provide RF Shielding & required RF mitigations within all second floor roof assemblies.
C101001 FIXED PARTITIONS
Impact Resistant gypsum board on cold-formed steel studs continuous to underside of structural deck above.
Provide STC 55 (min) lab-tested assembly
C102001 STANDARD INTERIOR DOORS (1) 3’ x 7’ Solid-Core, flush door panel with natural wood veneer finish hosted in Hollow Metal frame. Factory Primed. Field- Painted.
C102007 INTERIOR DOOR HARDWARE Hinge, Rim Cylinder, Closer, Kick plate and Silencer.
C103001
COMPARTMENTS, CUBICLES & TOILET
PARTITIONS
AR AR
HDPE floor-supported, over-head braced partitions at each water closet/urinal
C103002 TOILET AND BATH ACCESSORIES AR
Double toilet tissue dispensers – jumbo roll size, wall mirrors (match width of counter top - minimum 36” high), full height mirror, semi-recessed paper towel dispenser/disposal, wall mounted soap dispensers at each sink, grab bars, high efficiency electric hand dryer, coat hook on back of toilet compartment doors.
P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761
UNIFORMAT DESCRIPTION QTY SIZE SPECIFIC REQUIREMENTS
C103004 IDENTIFYING DEVICES
1 per door
Signage on exterior side of room entry door(s). Indicate permanent room name(s) and number
C103008 COUNTERS
2’-0”d x
7’-6”l
½” thick solid surface counter with 4” high backsplash and side splashes as required; include integral solid surface sink(s) – SEE D20 Section. Provide high pressure laminate apron on stainless steel brackets underneath counter to conceal exposed plumbing.
C301004 TILE WALL FINISHES SF
12” X
12” min
Porcelain tile on all walls; full height to ceiling, with accent tile band. Provide grouted in stainless steel edge protection strips at all inside and outside corners and where wall tile meets the floor tile. Install with epoxy grout. Provide cementitious backer board at all locations to receive wall tile.
C302001 TILE FLOOR FINISHES SF
12” X
12” min
Porcelain floor tile. Provide grouted in stainless steel edge protection strips at all inside and outside corners, where the floor tile meets the wall tile and transitions strips or marble thresholds at doorways. Install with epoxy grout.
C303003
GYPSUM WALLBOARD CEILING
FINISHES
AR AR Moisture resistant gypsum wallboard. Epoxy paint.
C304001 INTERIOR COATINGS / FINISHES AR AR
Paint suitable in accordance with Master Painter Institute (MPI) standards for the interior architectural surface being finished.
D201001 WATER CLOSEST AR Provide floor mounted fixtures.
D201002 URINALS AR Provide wall-hung fixtures.
D201003 LAVATORIES Provide lavatory faucet for integral countertop lavatory.
D203003 FLOOR DRAINS (1) Provide floor drain. Slope floor tile to drain AR.
D30 HVAC Provide air conditioning & heating for temperature control.
D304007 EXHAUST SYSTEMS
Provide dedicated, ducted exhaust from bathroom per IBC/ UFC requirements.
D4010 FIRE ALARM / DETECTION SYSTEMS See RFP Part 3; ESR D4010
D4040 SPRINKLER SYSTEMS
Provide wet pipe automatic sprinkler protection providing complete coverage throughout facility. See Part 3; ESR D4040.
D502002 RECEPTACLE OUTLETS Provide cleaning and basin counter receptacles
D502001 LIGHTING EQUIPMENT UFC 3-530-01 3-3.6 Restrooms Type A and B Luminaires
D502002 LIGHTING CONTROLS Per UFC 3-530-01 3-3.6 Restrooms
D503002 PUBLIC ADDRESS SYSTEMS
Provide Public Address system with flush ceiling mounted speakers.
P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761
UNIFORMAT DESCRIPTION QTY SIZE SPECIFIC REQUIREMENTS
D509002 EMERGENCY LIGHTING AND POWER AR
All mission critical power circuits shall connect to emergency panel and back up by emergency generator.