This is a room requirements specification document for a women's restroom (Room G209) in the P-909 SDVT-2 Operations Support Facility at JEB Little Creek-Fort Story in Norfolk, Virginia. The document details the technical requirements for constructing a second-floor women's restroom facility that requires special RF shielding and STC 55 minimum sound rating for floors, roof, and interior partitions.

The specifications include detailed requirements for floor construction (4" concrete on 2" steel deck), interior finishes (porcelain tile floors and walls), fixtures (floor-mounted water closets, wall-hung urinals, solid surface counters with integral sinks), and comprehensive bathroom accessories. The room requires a 9'-0" minimum ceiling height, moisture-resistant gypsum wallboard with epoxy paint, dedicated HVAC and exhaust systems, wet pipe sprinklers, emergency lighting, and a public address system. Special attention is given to RF shielding requirements throughout the floor and roof assemblies, along with specific requirements for door hardware, lighting controls per UFC 3-530-01 standards, and emergency power connectivity for mission-critical circuits.

View the file

Other files

File Type Posted
Attachment D - P909 Price Proposal Form R3.docx DOCX document
24R2862 Amendment 0014.docx DOCX document
Attachment D - P909 Price Proposal Form R2.docx DOCX document
P909 Amendments Index.pdf PDF
24R2862 Amendment 0013.pdf PDF
Attachment B Wage Determination.pdf PDF
Attachment X - Lithium Battery Current Quantities.pdf PDF
24R2862 Amendment 0012.pdf PDF
Section 01 14 00 R0824.pdf PDF
24R2862 Amendment 0011.pdf PDF
W_LIttle Creek Oneline.pdf PDF
V_Secured Area Second Floor.pdf PDF
24R2862 Amendment 0010.pdf PDF
24R2862 Amendment 0009.pdf PDF
24R2862 Amendment 0008.pdf PDF
1704761-CS101.pdf PDF
DOD_Anti-ram_Vehicle_Barriers_September_2024.pdf PDF
6_ESR_A20.pdf PDF
24R2862 Amendment 0007.pdf PDF
Part 2 General Requirements.pdf PDF
5_RR_D105_MAINTENANCE RM-O2 SAFE.pdf PDF
5_RR_D106_MAINTENANCE RM.pdf PDF
5_RR_D109_COMPRESSOR ROOM.pdf PDF
3_site_analysis.pdf PDF
5_RR_D104_BATTERY STORAGE.pdf PDF
NAVFAC High Performance and Sustainable Building Checklist GOALS.pdf PDF
5_RR_G111_MENS TOILET.pdf PDF
6_ESR_D20.pdf PDF
---5_RR_G207 MENS TOILET.pdf PDF
6_ESR_D30.pdf PDF
5_RR G108 WOMENS TOILET AND SHOWER.pdf PDF
Part 3 Chapter 1 changes.pdf PDF
5.0_Room.Requirements_Amendment.0006.pdf PDF
SPACE TABULATION.23Oct2024xlsx.pdf PDF
U_Telecommunication_Point_Of_Connection.pdf PDF
Spec.ESR_Amendment.0006.pdf PDF
24R2862 Amendment 0006.pdf PDF
24R2862 Amendment 0005.pdf PDF
24R2862 Amendment 0004.pdf PDF
24R2862 Amendment 0003 Site Visit Log.pdf PDF
24R2862 Amendment 0002.pdf PDF
Attachment J - PTS_SECTION_Z10.pdf PDF
Attachment I - 1704761 CONTINUATION SHEET Ammendement 0002.pdf PDF
ATTACHMENT G - SECNAV FORM 5512.pdf PDF
ATTACHMENT H - ONE DAY PASS FORM.xls XLS spreadsheet
24R2862 Amendment 0001.pdf PDF
Attachment A- R18_P909_RFP Plans_23.12.11 SITE PLAN.pdf PDF
24R2862 SOF General Requirements.pdf PDF
Attachment C-Pre-Proposal Inquiry Form.xlsx XLSX spreadsheet
Attachment F - JA ML-22-02 Class FRCS Standardization.pdf PDF
Show 40 more

Latest 50 of 52 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761 JEB Little Creek-Fort Story, Norfolk, Virginia

5.0 ROOM REQUIREMENTS

G209 – WOMEN’S TOILET

Space Characteristics

FUNCTION: Women’s restroom. Provide adequate fixture counts per Plumbing UFC and associated Occupant loads.

ADJACENCIES: Locate centrally to second floor office suites.

SPATIAL REQUIREMENTS:

Ideal Plan Dimensions: See Floor Plans.

Minimum Ceiling Height: 9’-0” Ceiling

ACOUSTICAL REQUIREMENTS: Unless Otherwise Noted:

EXTERIOR: Provide STC 55 (min) rated floor, roof and exterior envelope and window assemblies for entire second level.

INTERIOR: Provide STC 55 (min) rated interior partitions for entire second level.

NUMBER OF OCCUPANTS: 0 PN

SPECIAL REQUIREMENTS:

UNIFORMAT DESCRIPTION QTY SIZE SPECIFIC REQUIREMENTS

B1010 FLOOR CONSTRUCTION – STC 55 (MIN) AR AR

4" (min) normal weight concrete on 2” (min) deep, 20ga (min) composite steel deck & a minimum total slab thickness of 6”. Reinforce with 6x6-W2.9xW2.9 WWR.

STC 55 (min) lab-tested rating.

B1010 FLOOR – RF SHIELDING AR AR

Provide RF Shielding and required RF mitigations within entire second floor assembly.

B301090 OTHER ROOFING – STC 55 (MIN) AR AR

All second floor roof assemblies shall provide an STC 55 (min) lab-tested rating.

B301090 OTHER ROOFING – RF SHIELDING AR AR

Provide RF Shielding & required RF mitigations within all second floor roof assemblies.

C101001 FIXED PARTITIONS

Impact Resistant gypsum board on cold-formed steel studs continuous to underside of structural deck above.

Provide STC 55 (min) lab-tested assembly

C102001 STANDARD INTERIOR DOORS (1) 3’ x 7’ Solid-Core, flush door panel with natural wood veneer finish hosted in Hollow Metal frame. Factory Primed. Field- Painted.

C102007 INTERIOR DOOR HARDWARE Hinge, Rim Cylinder, Closer, Kick plate and Silencer.

C103001

COMPARTMENTS, CUBICLES & TOILET

PARTITIONS

AR AR

HDPE floor-supported, over-head braced partitions at each water closet/urinal

C103002 TOILET AND BATH ACCESSORIES AR

Double toilet tissue dispensers – jumbo roll size, sanitary napkin disposal, wall mirrors (match width of counter top -minimum 36” high), full height mirror, semi-recessed paper towel dispenser/disposal, wall mounted soap dispensers at each sink, grab bars, high efficiency electric hand dryer, coat hook on back of toilet compartment doors.

C103004 IDENTIFYING DEVICES

1 per door

Signage on exterior side of room entry door(s). Indicate permanent room name(s) and number

P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761 JEB Little Creek-Fort Story, Norfolk, Virginia

UNIFORMAT DESCRIPTION QTY SIZE SPECIFIC REQUIREMENTS

C103008 COUNTERS

2’-0”d x

8’-0”l

½” thick solid surface counter with 4” high backsplash and side splashes as required; include integral solid surface sink(s) – SEE D20 Section. Provide high pressure laminate apron on stainless steel brackets underneath counter to conceal exposed plumbing.

C301004 TILE WALL FINISHES SF

12” X

12” min

Porcelain tile on all walls; full height to ceiling, with accent tile band. Provide grouted in stainless steel edge protection strips at all inside and outside corners and where wall tile meets the floor tile. Install with epoxy grout. Provide cementitious backer board at all locations to receive wall tile.

C302001 TILE FLOOR FINISHES SF

12” X

12” min

Porcelain floor tile. Provide grouted in stainless steel edge protection strips at all inside and outside corners, where the floor tile meets the wall tile and transitions strips or marble thresholds at doorways. Install with epoxy grout.

C303003

GYPSUM WALLBOARD CEILING

FINISHES

AR AR Moisture resistant gypsum wallboard. Epoxy paint.

C304001 INTERIOR COATINGS / FINISHES AR AR

Paint suitable in accordance with Master Painter Institute (MPI) standards for the interior architectural surface being finished.

D201001 WATER CLOSEST AR Provide floor mounted fixtures.

D201002 URINALS AR Provide wall-hung fixtures.

D201003 LAVATORIES Provide lavatory faucet for integral countertop lavatory.

D203003 FLOOR DRAINS (1) Provide floor drain. Slope floor tile to drain AR.

D30 HVAC Provide air conditioning & heating for temperature control.

D304007 EXHAUST SYSTEMS

Provide dedicated, ducted exhaust from bathroom per IBC/ UFC requirements.

D4010 FIRE ALARM / DETECTION SYSTEMS See RFP Part 3; ESR D4010

D4040 SPRINKLER SYSTEMS

Provide wet pipe automatic sprinkler protection providing complete coverage throughout facility. See Part 3; ESR D4040.

D502002 RECEPTACLE OUTLETS Provide cleaning and basin counter receptacles

D502001 LIGHTING EQUIPMENT UFC 3-530-01 3-3.6 Restrooms Type A and B Luminaires

D502002 LIGHTING CONTROLS Per UFC 3-530-01 3-3.6 Restrooms

D503002 PUBLIC ADDRESS SYSTEMS

Provide Public Address system with flush ceiling mounted speakers.

D509002 EMERGENCY LIGHTING AND POWER AR

All mission critical power circuits shall connect to emergency panel and back up by emergency generator.