5_RR_D104_BATTERY STORAGE.pdf
PDF 120 KB Posted
- Solicitation number
- N4008524R2862
About this file
This is a room requirements specification document for Room D104 (Battery Storage Room) in the P-909 SDVT-2 Operations Support Facility project at JEB Little Creek-Fort Story in Norfolk, Virginia. The document details the technical requirements for a specialized room designed to store and charge lithium ion battery packs used in dive gear self-propulsion devices.
The room specifications include a 20-foot minimum ceiling height, 2-3 hour fire rated separation from adjacent spaces, and both interior access and exterior egress-only doors (6'x8' heavy-duty galvanized steel). Key infrastructure requirements include a reinforced concrete slab with drainage, battery spill control features, CMU walls to the deck, electronic keypad/proximity card access, 80 linear feet of heavy-duty galvanized shelving, dedicated HVAC with 100% outside air makeup, emergency shower/eyewash station, floor drain with acid waste collection, LED lighting (50fc at floor), and multiple electrical services including 125V 20amp outlets and two 208V single-phase 60hz 50amp circuits. The space requires specialized finishes including resinous flooring, epoxy wall paint, and exposed painted structure ceiling.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761 JEB Little Creek-Fort Story, Norfolk, Virginia
5.0 ROOM REQUIREMENTS
D104 – BATTERY STORAGE ROOM
Space Characteristics
FUNCTION: Space for storing and charging small lithium ion battery packs used in dive gear self-propulsion devices.
ADJACENCIES: Locate in close proximity with Dive Maintenance rooms, Dive Staging & Setup bay and Consolidated Rig Storage.
SPATIAL REQUIREMENTS:
Ideal Plan Dimensions: See Floor Plans.
Minimum Ceiling Height: 20’ clear to underside of structure
ACOUSTICAL REQUIREMENTS:
ACCESS REQUIREMENTS: SDVT-2 Personnel. Provide access from the interior and egress only, double door exit to the exterior.
NUMBER OF OCCUPANTS: 0 PN
OTHER / SPECIAL REQUIREMENTS: Space Requires a 2-3 hour fire rated separation from all other spaces. DOR to confirm requirement based on user provided information related to size of battery units and quantity intended to be stored within.
FF&E INFORMATION FOR COORDINATION:
FF&E and AV Equipment will be funded separately as a modification to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor’s Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design workshop (CDW). Space will accommodate, at a minimum, the following:
FF&E: fire extinguisher
UNIFORMAT DESCRIPTION QTY SIZE SPECIFIC REQUIREMENTS
A1030 GROUND FLOOR SLABS -- Structurally Reinforced Concrete Slab. Slope to drain.
A202002 BATTERY ROOM PIT/SUMP
Provide battery spill control per UFC 3-520-05 paragraph 2-2.4 Spill Control
B203001 EXTERIOR SOLID DOORS (1) 6’ x 8’
Pair of Insulated Heavy-Duty, Hot-Dipped Galvanized Steel doors and frames. Factory Primed with Zinc Rich MPI compliant primer. Provide compatible epoxy-based intermediate & top-coat.
B203008 EXTERIOR DOOR HARDWARE
EGRESS ONLY: Heavy-Duty pinned security hinges, Exit Device, Closer, Kick Plate, Threshold, Weather-seal, and sweep. Provide Door Position Switch and contact connected to security system and CCTV. Provide active/ inactive leaf.
C101001 FIXED PARTITIONS
Concrete Masonry Unit (CMU) walls continuous to underside of structural deck above. Provide with bullnose corners and edges.
C102001 STANDARD INTERIOR DOORS (1) 6’ x 8’ Heavy-Duty steel doors and frames. Factory Primed.
Field-Painted. Provide active/ inactive leaf.
C102003 FIRE DOORS
C102007 INTERIOR DOOR HARDWARE
Electronic Key Pad/ Proximity Card Reader, Mortis power transfer from the hinge side and balanced magnetic door sensor. Heavy-Duty hinges, door closure, Exit device, Kick Plate and Silencer.
P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761 JEB Little Creek-Fort Story, Norfolk, Virginia
Provide SS flush-bolts and associated connections at top and bottom of inactive leaf to secure into concrete slab and metal frame.
C103004 IDENTIFYING DEVICES AR AR
.Signage on exterior side of room entry door(s).
Indicate permanent room name(s) and number
C103006 SHELVING
LF
22” d Heavy Duty Hot-Dipped Galvanized or Stainless Steel Shelving
C301003 WALL FINISHES AR AR Provide painted CMU
C302007 WALL BASE FINISHES AR 4”h Integral 1” radius, resinous flooring cove base with a stainless steel top cap
C302009 RESINOUS FLOOR COATING SYSTEM SF
3/16” thick standard troweled mortar/quartz broadcast resinous floor coating system
C303009 CEILING FINISHES AR AR .Exposed structure, painted epoxy
C304001 INTERIOR COATINGS / FINISHES
Epoxy wall paint. Paint suitable in accordance with Master Painter Institute (MPI) standards for the interior architectural surface being finished.
D201090 EMERGENCY FIXTURES
Provide emergency combination shower/ eyewash station with tepid water. Locate within battery storage room or just outside. (Shown on plans outside battery room in adjacent D103 HALL)
D203003 FLOOR DRAINS (1)
Provide floor trench/ pit drain with steel grated floor cover with appropriate acid/ waste collection capabilities.
D30 HVAC
Provide air conditioning and heating for temperature control for equipment protection.
D3040 OTHER HVAC
Dedicated exhaust and dedicated 100% outside air make-up in D309090 OTHER SPECIAL MECHANICAL SYSTEMS apply to this room.
D4010 FIRE ALARM / DETECTION SYSTEMS See RFP Part 3; ESR D4010
D502001 BRANCH WIRING
Multiple 4 gang 125V 20amp outlets and Qty 2 208V single phase 60hz at 50amp service
D502002 LIGHTING EQUIPMENT
LED Lighting 50fc at floor. Installed per UFC 3-530-01. Provide battery backup emergency fixtures as required.
D503001 LIGHTING CONTROLS No dimming required.
D503001 TELECOMMUNICATIONS SYSTEMS TBD
D503002 PUBLIC ADDRESS SYSTEMS
Provide Public Address system with flush ceiling mounted speakers.