This is a room requirements document detailing specifications for Room D106 (Dive Gear Maintenance Room) as part of the P-909 SDVT-2 Operations Support Facility project at JEB Little Creek-Fort Story in Norfolk, Virginia.

The document specifies requirements for a maintenance and instruction space where dive rigs and gear are maintained, requiring a minimum 10' ceiling height and ample clear space around 4'x8' work tables (8' ideal, 6' minimum). Key features include stainless steel work benches with VIDMAR storage, regulator lockers, dive quality compressed air service (5000 psi), shop-quality air service (120 psi), and specialized ventilation for oxygen tank storage. The room includes extensive shelving requirements for rig storage and O2 bottle storage racks, stainless steel sinks, and specific electrical requirements including NIPR/SIPR drops. Construction specifications detail CMU walls, heavy-duty steel doors with electronic access control, resinous flooring, and LED lighting systems. The space must accommodate specialized equipment including 6 stainless steel work bench units, test benches, and storage systems, with all FF&E and AV equipment to be funded separately as a modification to the construction contract.

View the file

Other files

File Type Posted
Attachment D - P909 Price Proposal Form R3.docx DOCX document
24R2862 Amendment 0014.docx DOCX document
Attachment D - P909 Price Proposal Form R2.docx DOCX document
P909 Amendments Index.pdf PDF
24R2862 Amendment 0013.pdf PDF
Attachment B Wage Determination.pdf PDF
Attachment X - Lithium Battery Current Quantities.pdf PDF
24R2862 Amendment 0012.pdf PDF
Section 01 14 00 R0824.pdf PDF
24R2862 Amendment 0011.pdf PDF
W_LIttle Creek Oneline.pdf PDF
V_Secured Area Second Floor.pdf PDF
24R2862 Amendment 0010.pdf PDF
24R2862 Amendment 0009.pdf PDF
24R2862 Amendment 0008.pdf PDF
1704761-CS101.pdf PDF
DOD_Anti-ram_Vehicle_Barriers_September_2024.pdf PDF
6_ESR_A20.pdf PDF
---5_RR_G209 WOMENS TOILET.pdf PDF
24R2862 Amendment 0007.pdf PDF
Part 2 General Requirements.pdf PDF
5_RR_D105_MAINTENANCE RM-O2 SAFE.pdf PDF
5_RR_D109_COMPRESSOR ROOM.pdf PDF
3_site_analysis.pdf PDF
5_RR_D104_BATTERY STORAGE.pdf PDF
NAVFAC High Performance and Sustainable Building Checklist GOALS.pdf PDF
5_RR_G111_MENS TOILET.pdf PDF
6_ESR_D20.pdf PDF
---5_RR_G207 MENS TOILET.pdf PDF
6_ESR_D30.pdf PDF
5_RR G108 WOMENS TOILET AND SHOWER.pdf PDF
Part 3 Chapter 1 changes.pdf PDF
5.0_Room.Requirements_Amendment.0006.pdf PDF
SPACE TABULATION.23Oct2024xlsx.pdf PDF
U_Telecommunication_Point_Of_Connection.pdf PDF
Spec.ESR_Amendment.0006.pdf PDF
24R2862 Amendment 0006.pdf PDF
24R2862 Amendment 0005.pdf PDF
24R2862 Amendment 0004.pdf PDF
24R2862 Amendment 0003 Site Visit Log.pdf PDF
24R2862 Amendment 0002.pdf PDF
Attachment J - PTS_SECTION_Z10.pdf PDF
Attachment I - 1704761 CONTINUATION SHEET Ammendement 0002.pdf PDF
ATTACHMENT G - SECNAV FORM 5512.pdf PDF
ATTACHMENT H - ONE DAY PASS FORM.xls XLS spreadsheet
24R2862 Amendment 0001.pdf PDF
Attachment A- R18_P909_RFP Plans_23.12.11 SITE PLAN.pdf PDF
24R2862 SOF General Requirements.pdf PDF
Attachment C-Pre-Proposal Inquiry Form.xlsx XLSX spreadsheet
Attachment F - JA ML-22-02 Class FRCS Standardization.pdf PDF
Show 40 more

Latest 50 of 52 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761 JEB Little Creek-Fort Story, Norfolk, Virginia

5.0 ROOM REQUIREMENTS

D106 – DIVE GEAR MAINTENANCE ROOM

Space Characteristics

FUNCTION: Maintenance and Instruction space where dive rigs and gear is worked on and maintained. Master Diver’s use this space as an instruction space as well as work is being done.

ADJACENCIES: Adjacent to Consolidated Rig Storage. Close proximity to Dive Maintenance rooms and Dive Systems Office Suite.

SPATIAL REQUIREMENTS:

Ideal Plan Dimensions: See Floor Plans. Provide ample clear space around 4’ x 8’ work tables. 8’-0”+ is ideal (6’-0” MIN).

Minimum Ceiling Height: 10’ minimum clear

ACOUSTICAL REQUIREMENTS:

ACCESS REQUIREMENTS:

NUMBER OF OCCUPANTS: 0 PN

OTHER / SPECIAL REQUIREMENTS:

F&E INFORMATION FOR COORDINATION:

FF&E and AV Equipment will be funded separately as a modification to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor’s Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design workshop (CDW). Space will accommodate, at a minimum, the following:

FF&E: (1) fire extinguisher, (6) 8’ x 4’ stainless steel work bench unit w/ below-counter VIDMAR storage and utility rack stanchions above, (1) 2’ x 2’ stainless steel locker for regulators, (1) 4’-0” x 2’-0” test bench, (1) stool, (2) trash cans, (1) recycling receptacle

UNIFORMAT DESCRIPTION QTY SIZE SPECIFIC REQUIREMENTS

A1030 GROUND FLOOR SLABS -- Structurally Reinforced Concrete Slab.

B203001 EXTERIOR SOLID DOORS (1) 6’ x 8’

Pair of Insulated Heavy-Duty, Hot-Dipped Galvanized Steel doors and frames. Factory Primed with Zinc Rich MPI compliant primer.

Provide compatible epoxy-based intermediate & top-coat.

B203008 EXTERIOR DOOR HARDWARE

EGRESS ONLY: Heavy-Duty pinned security hinges, Exit Device, Closer, Kick Plate, Threshold, Weather-seal, and sweep. Provide Door Position Switch and contact connected to security system and CCTV.

C101001 FIXED PARTITIONS

Concrete Masonry Unit (CMU) walls continuous to underside of structural deck above. Provide with bullnose corners and edges.

C102001 STANDARD INTERIOR DOORS (1) 3’ x 8’ Heavy-Duty steel doors and frames. Factory Primed. Field-Painted

C102007 INTERIOR DOOR HARDWARE

Electronic Key Pad/ Proximity Card Reader, Mortis power transfer from the hinge side and balanced magnetic door sensor. Heavy-Duty hinges, door closure device, Kick Plate and Silencer.

C103003 MARKER BOARDS & TACK BOARDS (2)

36”h x 60”w

Magnetic, Glass White Board. Wall mount.

Centerline of board @ ±5’-6” AFF.

P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761

C103004 IDENTIFYING DEVICES

1 per door

Provide signage on exterior side of room entry door(s). Indicate permanent room name(s) and number

C103006 SHELVING (1)

2’d x 13’l x 8’h

Provide drying rack shelving adjacent to sinks

C103006 SHELVING (1)

1’-6”d x 12’-0”l

Provide 18”d stainless steel shelf 3’-0” above sinks

C103006 SHELVING (3)

4’d x 9’l x 8’h

Shelving for rig storage

C103006 SHELVING (2)

2’d x 8’l x 6’h

Provide O2 Bottle Storage Racks

C103007 FIRE EXTINGUISHER CABINETS Provide Extinguisher.

C301003 WALL FINISHES AR AR Provide painted CMU

C302007 WALL BASE FINISHES AR 4”h Integral 1” radius, resinous flooring cove base with a stainless steel top cap

C302009 RESINOUS FLOOR COATING SYSTEM SF

3/16” thick standard troweled mortar/quartz broadcast resinous floor coating system

C30309009 CEILING FINISHES AR AR Exposed structure, painted epoxy

C304001 INTERIOR COATINGS / FINISHES

Epoxy wall paint. Paint suitable in accordance with Master Painter Institute (MPI) standards for the interior architectural surface being finished.

D201004 SINKS (2)

6’ x 4’ x 30”d

Provide Stainless Steel sink units

D203003 FLOOR DRAINS Provide Floor Drain.

D209001 SPECIAL PIPING SYSTEMS

Provide Dive Quality Compressed Air Service (5000 psi). Provide drops on self-retracting reels.

See Plans for locations.

D209005

COMPRESSED AIR SYSTEMS (NON-

BREATHING)

Provide Dive Quality Compressed Air Service (5000 psi). Provide drops on self-retracting reels.

Provide Shop-Quality Air Service (120 psi).

Provide drops on self-retracting reels.. See Plans for locations. Provide Dial-Down Regulator to convert air pressure as required.

D30 HVAC

Provide air conditioning and heating for temperature control. HVAC system selection based on results of LCCA performed by KTR.

D3040 OTHER HVAC

Ventilation? Exhaust?Provide minimum required ventilation. This room shall be exhausted as there will be oxygen tanks in this room.

D4010 FIRE ALARM / DETECTION SYSTEMS See RFP Part 3; ESR D4010

P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761

D4040 SPRINKLER SYSTEMS

Provide wet pipe automatic sprinkler protection providing complete coverage throughout facility.

See Part 3; ESR D4040.

D502001 BRANCH WIRING Provide a minimum of (8) 125V 20amp outlets.

D502001 BRANCH WIRING (1)

Provide 125 volt, 20 amp, duplex receptacle @ ±66” on wall to receive wall-mounted TV/ monitor.

D502002 LIGHTING EQUIPMENT (2) 6’ L

ABOVE TABLES: Provide Suspended linear industrial LED luminaires with 5%-10% up-light component and wire guard. UFC 3-530-01;

Section 3-3.5 Mechanical Rooms.

D502002 LIGHTING EQUIPMENT AR 2’ x 4’

REST OF ROOM: Provide Recessed direct / indirect LED luminaires per UFC 3-530-01;

Section 3-4.4 “Open Offices” (Alternate Scheme).

See Part 6 Attachment - Lighting Plate NL-1.

D503001 LIGHTING CONTROLS

Per UFC 3-530-01; Section 3-4.4 “Open Offices” (Alternate Scheme).

D503001 TELECOMMUNICATIONS SYSTEMS

Provide (2) NIPR and (2) SIPR Drops. Customer to identify desired locations.

D503001 DATA / TELEPHONE (1)

Provide designated data drop(s) and CATV connection @ ±66” on wall to receive wall-mounted TV/ monitor.

D503002 PUBLIC ADDRESS SYSTEMS

Provide Public Address system with flush ceiling mounted speakers.

D503004 TELEVISION SYSTEMS (1) Provide wall-mounted TV