This is a room requirements specification document for Room D105 (O2 Safe - Dive Gear Maintenance Room) within the P-909 SDVT-2 Operations Support Facility project at JEB Little Creek-Fort Story in Norfolk, Virginia.
The room is designed as a maintenance and instruction space for dive rigs and gear, requiring a minimum 10' ceiling height and ample clear space around 4' x 8' work tables (8' ideal, 6' minimum). Key features include CMU walls with bullnose corners, heavy-duty steel doors with electronic keypad/card reader access, specialized storage systems including O2 bottle racks and drying racks, and stainless steel work benches with VIDMAR storage. The space includes comprehensive utility systems with dive quality compressed air service (5000 psi), shop-quality air service (120 psi), HVAC with special ventilation for oxygen tanks, and both NIPR and SIPR data connections. The room features industrial LED lighting, resinous floor coating, stainless steel sinks, and requires specific safety elements including fire suppression systems and extinguishers. FF&E and AV equipment will be funded separately as a modification to the construction contract.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761 JEB Little Creek-Fort Story, Norfolk, Virginia
5.0 ROOM REQUIREMENTS
D105 – O2 SAFE - DIVE GEAR MAINTENANCE ROOM
Space Characteristics
FUNCTION: Maintenance and Instruction space where dive rigs and gear is worked on and maintained. Master Diver’s use this space as an instruction space as well as work is being done.
ADJACENCIES: Adjacent to Consolidated Rig Storage. Close proximity to Dive Maintenance rooms and Dive Systems Office Suite.
SPATIAL REQUIREMENTS:
Ideal Plan Dimensions: See Floor Plans. Provide ample clear space around 4’ x 8’ work tables. 8’-0”+ is ideal (6’-0” MIN).
Minimum Ceiling Height: 10’ minimum clear
ACOUSTICAL REQUIREMENTS:
ACCESS REQUIREMENTS:
NUMBER OF OCCUPANTS: 0 PN
OTHER / SPECIAL REQUIREMENTS:
FF&E INFORMATION FOR COORDINATION:
FF&E and AV Equipment will be funded separately as a modification to the construction contract. Infrastructure to support all FF&E and AV must be included in the construction contract. Contractor’s Interior Designer must validate and determine FF&E requirements based on in-depth interviews with Activity at Concept Design workshop (CDW). Space will accommodate, at a minimum, the following:
FF&E: (1) fire extinguisher, (6) 8’ x 4’ stainless steel work bench unit w/ below-counter VIDMAR storage and utility rack stanchions above, (1) 2’ x 2’ stainless steel locker for regulators, (1) 4’-0” x 2’-0” test bench, (1) stool, (2) trash cans, (1) recycling receptacle
UNIFORMAT DESCRIPTION QTY SIZE SPECIFIC REQUIREMENTS
A1030 GROUND FLOOR SLABS -- Structurally Reinforced Concrete Slab.
C101001 FIXED PARTITIONS
Concrete Masonry Unit (CMU) walls continuous to underside of structural deck above. Provide with bullnose corners and edges.
C102001 STANDARD INTERIOR DOORS (1) 3’ x 8’ Heavy-Duty steel doors and frames. Factory Primed. Field-Painted
C102007 INTERIOR DOOR HARDWARE
Electronic Key Pad/ Proximity Card Reader, Mortis power transfer from the hinge side and balanced magnetic door sensor. Heavy-Duty hinges, door closure device, Kick Plate and Silencer.
C103003 MARKER BOARDS & TACK BOARDS (2)
36”h x 60”w
Magnetic, Glass White Board. Wall mount.
Centerline of board @ ± 5’-6” AFF.
C103004 IDENTIFYING DEVICES
1 per door
Provide signage on exterior side of room entry door(s). Indicate permanent room name(s) and number
C103006 SHELVING (1)
2’d x 13’l x 8’h
Provide drying rack shelving
C103006 SHELVING (1)
1’-6”d x 12’-0”l
Provide 18”d stainless steel shelf 3’-0” above sinks
P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761
C103006 SHELVING (3)
4’d x 9’l x 8’h
Shelving for rig storage
C103006 SHELVING (2)
2’d x 8’l x 6’h
Provide O2 Bottle Storage Racks
C103007 FIRE EXTINGUISHER CABINETS Provide Extinguisher.
C301003 WALL FINISHES AR AR Provide painted CMU
C302007 WALL BASE FINISHES AR 4”h Integral 1” radius, resinous flooring cove base with a stainless steel top cap
C302009 RESINOUS FLOOR COATING SYSTEM SF
3/16” thick standard troweled mortar/quartz broadcast resinous floor coating system
C30309009 CEILING FINISHES AR AR Exposed structure, painted epoxy
C304001 INTERIOR COATINGS / FINISHES
Epoxy wall paint. Paint suitable in accordance with Master Painter Institute (MPI) standards for the interior architectural surface being finished.
D201004 SINKS (2)
6’ x 4’ x 30”d
Provide Stainless Steel sink units
D203003 FLOOR DRAINS Provide Floor Drain.
D209001 SPECIAL PIPING SYSTEMS
Provide Dive Quality Compressed Air Service (5000 psi). Provide drops on self-retracting reels.
See Plans for locations.
D209005
COMPRESSED AIR SYSTEMS (NON-
BREATHING)
Provide Dive Quality Compressed Air Service (5000 psi). Provide drops on self-retracting reels.
Provide Shop-Quality Air Service (120 psi).
Provide drops on self-retracting reels. See Plans for locations. Provide Dial-Down Regulator to convert air pressure as required.
D30 HVAC
Provide air conditioning and heating for temperature control. HVAC system selection based on results of LCCA performed by KTR.
D3040 OTHER HVAC
Ventilation? Exhaust?Provide minimum required ventilation. This room shall be exhausted as there will be oxygen tanks in the room.
D4010 FIRE ALARM / DETECTION SYSTEMS See RFP Part 3; ESR D4010
D4040 SPRINKLER SYSTEMS
Provide wet pipe automatic sprinkler protection providing complete coverage throughout facility.
See Part 3; ESR D4040.
D502001 BRANCH WIRING Provide a minimum of (8) 125V 20amp outlets.
D502001 BRANCH WIRING (1)
Provide 125 volt, 20 amp, duplex receptacle @ ±66” on wall to receive wall-mounted TV/ monitor.
D502002 LIGHTING EQUIPMENT (2) 6’ L
ABOVE TABLES: Provide Suspended linear industrial LED luminaires with 5%-10% up-light
P-909 SDVT-2 OPERATIONS SUPPORT FACILITY Work Order Number: 1704761 component and wire guard. UFC 3-530-01;
Section 3-3.5 Mechanical Rooms.
D502002 LIGHTING EQUIPMENT AR 2’ x 4’
REST OF ROOM: Provide Recessed direct / indirect LED luminaires per UFC 3-530-01;
Section 3-4.4 “Open Offices” (Alternate Scheme).
See Part 6 Attachment - Lighting Plate NL-1.
D503001 LIGHTING CONTROLS
Per UFC 3-530-01; Section 3-4.4 “Open Offices” (Alternate Scheme).
D503001 TELECOMMUNICATIONS SYSTEMS
Provide (2) NIPR and (2) SIPR Drops. Customer to identify desired locations.
D503001 DATA / TELEPHONE (1)
Provide designated NIPR/SIPR data drop(s) and CATV connection @ ±66” on wall to receive wall-mounted TV/ monitor.
D503002 PUBLIC ADDRESS SYSTEMS
Provide Public Address system with flush ceiling mounted speakers.
D503004
TELEVISION SYSTEMS
(1) Provide wall-mounted TV