This document outlines requirements for a design-build request for proposal for hurricane recovery training and storage facilities at Marine Corps Base Camp Lejeune in North Carolina. Package 3 consists of replacing three facilities: the MCCSSS Log Ops School, the II MEF Simulation/Training Center, and the LOGCOM CSP Warehouse. The solicitation seeks firms to design and construct the new facilities to include warehouse pallet racks, shelving, dock levelers, kitchen equipment, and the rough-in and connection of government furnished equipment such as mask leak testers and hazardous storage cabinets. Proposals are due by April 27, 2020 and the selected firm will contract with the Naval Facilities Engineering Command.
View the file
Other files
Show 40 more
Latest 50 of 97 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Design-Build Request for Proposal RTA Hurricane Florence Recovery Training and Storage Facilities 3 March 2020 27 April 2020 Marine Corps Base Camp Lejeune, North Carolina Rev 02
PART 3 - CHAPTER 6/ESR E10 - P1527F LOGCOM CSP WAREHOUSE REPLACEMENT - Page 1
E10 EQUIPMENT – P1527F LOGCOM CSP WAREHOUSE
REPLACEMENT
GENERAL SYSTEMS REQUIREMENTS
E1010 COMMERCIAL EQUIPMENT
Obtain the services of equipment specialists to specify audiovisual equipment, as indicated in E102009. Equipment specialists shall not have any affiliation with the product specified.
All specialty equipment will be installed by qualified installers regularly engaged in installing the specialty equipment.
Provide energy using equipment per criteria listed in UFGS 01 33 29.05 20 Sustainability Requirements for Design Build.
E101003 VENDING EQUIPMENT
Government to provide and install vending equipment (four units) under separate contract.
Users to provide requirements of electrical and plumbing devices to be provided by Contractor to properly support the complete functional operation of the vending equipment. Design the break rooms to provide space, utilities, and cooling to accommodate the vending equipment.
E101005 SECURITY AND VAULT EQUIPMENT
NOT USED
E1020 INSTITUTIONAL EQUIPMENT
E102003 LABORATORY EQUIPMENT
NOT USED
E102009 AUDIOVISUAL EQUIPMENT
Coordinate design requirements with the end user/Command IT personnel, and provide equipment specifications, and procurement and installation of the Audiovisual (AV) equipment.
Obtain the services of an audiovisual equipment specialist with CTS-D certification to design and specify the audiovisual equipment.
AV Equipment including electronics potentially connected to data/IT, must be coordinated with design and construction but planned for and funded by the user or Budget Submitting Office sponsoring the user. AV equipment must include, but is not limited to, intercom/sound systems, smartboards, flat screens, projectors, video teleconferencing, interactive wall systems and CCTVs.
AV equipment is funded separately. The AV Equipment is identified on the AV Cost Estimate Worksheet. Refer to E20 for the Best Value Determination process for AV systems.
E1030 WAREHOUSE AND VEHICULAR EQUIPMENT
Provide warehouse pallet racks complying with UFC 4-440-01, Change 1 and Rack Manufacturers Institute MH16.1 Specification for the Design, Testing and Utilization of Industrial Steel Storage Racks:
Marine Corps Base Camp Lejeune, North Carolina Rev 01
PART 3 - CHAPTER 6/ESR E10 - P1527F LOGCOM CSP WAREHOUSE REPLACEMENT - Page 2
a. Load beam length: 9 ft. (108 in.)
b. Load beam capacity: 2 loads, 3,000 lb. each per pair of beams
c. 4-levels high with load beam elevations at 1’-0”, 6’-4”, 11’-8”, and 17’-0”’
d. Double deep design with 96” depth for two pallets.
e. 12” minimum back-to-back flue space between rows of double deep rack
f. 6” minimum clearance between racks and building columns
g. 14 ft. wide aisles between racks faces
h. 16 ft. minimum wide cross aisles and end aisles
i. Overall capacity of 1,536 pallet positions minimum.
Provide pallet rack with capacity for 48 pallets minimum in JEFS storage area. This may be either single deep or double deep as fits building arrangement. Beam length, beam capacity, beam elevations, aisle widths, and clearance shall be the same as warehouse pallet racks.
Provide new shelving for Test Equipment Storage similar to existing shelving including 120 volt power strips for some sections.
Loading dock shall be pProvided witha dock levelers and truck-trailer restraining devices at each dock door. Refer to the Architectural Block Diagram.
Minimum performance characteristics for the dock lift shall be based on the following:
a. Service Period:
(1) Number of shift operations of 1.
(2) Maximum number of trucks per shift opening of 8.
(3) Maximum number of days per week of 6.
b. Fork Lift Loads:
(1) Design lift s to accommodate 4-wheel fork trucks with rated capacity of at least 6,000 lbs.
(2) Design lifts to handle 15,000 lb. gross dynamic load.
(3) Base lift design on number of cycles per loading/unloading operation per truck of 18.
c. Dock lift design:
(1) Dock lift must be surface mount type. Pits are not acceptable.
(2) Dock lift must be end design with approach ramp, straight across travel.
E1040 GOVERNMENT FURNISHED EQUIPMENT
Rough-in and provide connections for Government-furnished equipment such that equipment will operate as intended, including providing miscellaneous items such as plugs, receptacles, wire, cable, conduit, flexible conduit and outlet boxes or fittings. Contractor shall pick up equipment at Building 1601 and transfer to site when ready for installation and relocation is approved by Contracting Officer. Equipment shall remain in control of the Government until such time as the Contractor is ready to install. Contractor shall provide 30 days advance notice of expected installation date and pick up equipment and transfer to site for installation. Testing
Marine Corps Base Camp Lejeune, North Carolina Rev 01
PART 3 - CHAPTER 6/ESR E10 - P1527F LOGCOM CSP WAREHOUSE REPLACEMENT - Page 3 requirements of Government Furnished equipment shall be the responsibility of the Contractor and shall follow the same guidelines as though the Contractor had provided the equipment. The following items will be furnished by the Government and shall be relocated, installed and tested by the Contractor:
• JSMLT (Joint Service Mask Leak Tester) equipment in warehouse.
• JSMLT equipment, 4 units, in JEFS.
• Hazardous Storage Cabinets, 3 units in JEFS.
• 50 pallets of JEFS equipment, not to exceed 500 pounds and 48” x 48” x 48” each.
E1090 OTHER EQUIPMENT
E109002 FOOD SERVICE EQUIPMENT
Provide light commercial kitchen equipment design to meet the needs of the end user. All light commercial electric kitchen equipment to be coordinated to provide a functional facility. Project includes the preparation of specific detailed information for each selected item. Each submittal must demonstrate thorough interaction with the end user requirements and complete coordination with the facility design. Equipment must include, but is not limited to, refrigerator, microwave, coffee maker, and ice maker.