Improve Military Family Housing (IMFH) Phase III, A/C and Weatherization, Misawa Air Base, Japan
Solicitation number
FA5205-17-R-0004
Issued by

About this file

FA520517R00040004_Atch1

View the file

Other files

File Type Posted
FA520517R00040005_Amendment.pdf PDF
FA520517R00040005_Atch3.pdf PDF
FA520517R00040005_Atch1.pdf PDF
FA520517R00040005_Atch4.pdf PDF
FA520517R00040005_Atch7.pdf PDF
FA520517R00040005_Atch6.pdf PDF
FA520517R00040005_Atch2.pdf PDF
FA520517R00040005_Atch5.pdf PDF
FA520517R00040004_Atch4.pdf PDF
FA520517R00040004_Amendment.pdf PDF
FA520517R00040004_Atch3-4.pdf PDF
FA520517R00040004_Atch3-3.pdf PDF
FA520517R00040004_Atch5.pdf PDF
FA520517R00040004_Atch2.pdf PDF
FA520517R00040004_Atch3-5.pdf PDF
FA520517R00040004_Atch3-2.pdf PDF
FA520517R00040004_Atch3-1.pdf PDF
FA520517R00040003_Atch1.pdf PDF
FA520517R00040003_Atch2.pdf PDF
FA520517R00040003_Amendment.pdf PDF
FA520517R00040002_Amendment.pdf PDF
FA520517R00040002_Atch.pdf PDF
FA520517R00040001_Atch2_Revised_Specification_Section.pdf PDF
FA520517R00040001_Amendment.pdf PDF
FA520517R00040001_Atch4_Revised_Solicitation_Page.pdf PDF
FA520517R00040001_Atch1_Addendum_No._1.pdf PDF
FA520517R00040001_Atch3_Revised_Drawings.pdf PDF
FA520517R0004_PreProposal_Conference_Minutes_&_Record_of_Site_Visit.pdf PDF
FA520517R0004_Atch2_Drawings_8_Electrical.pdf PDF
FA520517R0004_Atch2_Drawings_6_Plumbing.pdf PDF
FA520517R0004_Atch10_Asbestos_Sampling_and_Analysis.pdf PDF
FA520517R0004_Atch2_Drawings_3_Structural.pdf PDF
FA520517R0004_Atch2_Drawings_2_Hazmat.pdf PDF
FA520517R0004_Atch2_Drawings_5_Mechanical.pdf PDF
FA520517R0004_Atch4_PPQ_Cvr_Ltr.pdf PDF
FA520517R0004_Solicitation.pdf PDF
FA520517R0004_Atch8_Acceptable_JPN_Product_Substitutes.pdf PDF
FA520517R0004_Atch2_Drawings_7_Controls.pdf PDF
FA520517R0004_Atch2_Drawings_4_Architectural.pdf PDF
FA520517R0004_Atch9_Mfr's_Cut_Sheet_Catalog_Info.pdf PDF
FA520517R0004_Atch2_Drawings_1_General.pdf PDF
FA520517R0004_Atch3_Other_Contract_Requirements.pdf PDF
FA520517R0004_Atch1_Specifications.pdf PDF
FA520517R0004_Atch6_Construction_Timeline.pdf PDF
FA520517R0004_Atch5_PPQ.pdf PDF
FA520517R0004_Atch7_Schedule_of_Material_Submittals.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ADDENDUM 2

FOR

PROJECT NO. QKKA 15-4008

IMFH Phase 3, A/C & Weatherization

MISAWA AB, JAPAN

31 May 2017

1. The following specifications have been revised for the change of information as provided:

SPECIFICATION

Section Number Paragraph Description

1 00 01 15 1.2 Revised list of drawings to incorporate added and deleted drawings and changed sheet titles by this addendum.

2 01 11 00 1.1.1 Removed portion titled “INSTALL WATER METERS”. Removed column 12 “WATER METER” in table.

3 01 11 00 1.1.1 Updated Table to clarify existing ACM conditions.

4 01 33 00 Submittal Register Deleted Product Data Submittals associated with Section 25 10 10

5 08 11 16 2.1 Delete the text “and frames” in the first sentence. Replace the text “complete with frames, framing members, and accessories” with “complete with accessories. Doors should be sized and configured to hang in existing frames.”

6 23 09 23.13 20 1.3-b Removed text “Water meter pulse aggregator and’’

7 23 09 23.13 20 1.3-c Removed text “water and”

8 23 09 23.13 20 1.3-d Changed paragraphs labels so they are numbered in sequence (1,2,2,3,4) to (1,2,3,4,5).

9 23 09 23.13 20 1.3-d.4 Removed text ”and Water Metering”

10 25 10 10 1.1 Replaced “natural gas distribution, steam, chilled water, heating water, domestic water, recovered water and makeup water systems” with “power systems”

11 25 10 10 1.1-3 Replaced “Volumetric flowmeters, temperature sensors and pressure transducers” with “Electric Meters”

12 25 10 10 1.1-4 Deleted “4. Mass flowmeters”

13 25 10 10 1.6-B Deleted item B regarding Reporting Accuracy of water meters.

Atch. 1 to

FA520517R00040004

SPECIFICATION

Section Number Paragraph Description

14 25 10 10 1.8 Deleted SD-03 Product Data Submittal requirements.

15 25 10 10 2.1.4 Deleted subpart “2.1.4 Water Meter Criteria”

16 25 10 10 2.5 Deleted subpart “2.5 WATER, GAS METER

DEVICES”

17 25 10 10 3.1.1 Deleted subpart “3.1.1 Water and Gas Meters”

2. The following drawings have been revised for the change of information as provided:

DRAWING

Sheet Identification Number

Description

G-011 Revised list to incorporate added and deleted drawings by this addendum. See revised sheet.

G-011 Corrected Sheet Title for Sheet AE502 from “Window Details” to “Door Types, Window Types and Details”. See revised sheet.

G-011 Corrected Sheet Title for Sheet EI106 from “Cabe Cod Drive and Yoseeite Drive” to “Cape Cod Drive and Yosemite Drive”. See revised sheet.

G-021 Corrected the Sheet Title in the Titleblock from “Scope of Work” to “General Project Information”. See revised sheet.

G-021 Add Note 18 – Contractor shall close the Outside Air Vents by temporary seals to prevent damage to water lines when temperatures are below freezing during construction. See revised sheet.

G-024 Updated Disposition of Housing Units Table to clarify existing ACM conditions.

See revised sheet.

AE502 Updated Details 4 and 7 to remove requirement for replacement of termination bar. Updated Detail 14 to clarify glazing type. See revised sheet.

12N-MH102 Buildings applicable to this elevation has changed as a result of addition of rear patio awnings. See Building legend in revised sheet

12N-MH103 Buildings applicable to this elevation has changed as a result of addition of rear patio awnings. See Building legend in revised sheet.

12N-MH104 Buildings applicable to this elevation has changed as a result of addition of rear patio awnings. See Building Legend in revised sheet.

12N-MH105 Slim-duct routing was revised to accommodate addition of rear patio awnings.

Buildings applicable to this elevation has changed as a result of addition of rear patio awnings. This sheet was added.

12N-MH106 Slim-duct routing was revised to accommodate addition of rear patio awnings.

Buildings applicable to this elevation has changed as a result of addition of rear patio awnings. This sheet was added.

Identification Number

Description

15N-MH102 Slim-duct routing was revised to accommodate addition of rear patio awnings.

See revised sheet.

16ND-MH102 Slim-duct routing was revised to accommodate addition of rear patio awnings.

See revised sheet.

16N-MH102 Buildings applicable to this elevation has changed as a result of addition of rear patio awnings. See revised sheet.

16N-MH103 Slim-duct routing was revised to accommodate addition of rear patio awnings.

Buildings applicable to this elevation has changed as a result of addition of rear patio awnings. See revised sheet.

16N-MH104 Slim-duct routing was revised to accommodate addition of rear patio awnings.

Buildings applicable to this elevation has changed as a result of addition of rear patio awnings. This sheet was added.

M-501 Detail 5 - Condensate drain routing was modified at wing walls to accommodate splash block at end of patio. See revised sheet.

M-501 Detail 5 - Condensate pipe stainless steel cover was added for falling icicle protection. See revised sheet.

M-501 Detail 1 - Dimension of heat pump bracket was modified to accommodate the potential of a slightly longer vertical bracket member. See revised sheet.

M-503 Detail 5 - Condensate drain piping ant barrier mesh was added to drawings. See revised sheet.

M-503 Detail 6 - A detail was added to drawing showing refrigerant line-set, electrical and control wiring routed underground where it is not feasible to mount slim-duct on existing wall. See revised sheet.

EM002 Remove water meters from the project. See revised sheet.

EM004 Remove water meters from the project. See revised sheet.

4P1-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

4P3-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

6N-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

6P1-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

6A-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

7P2-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

7A-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

8N-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

10N-EM102 Reroute M-Net cable for Multi-Purpose room. See revised sheet.

15N-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

Identification Number

Description

12N-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

16N-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

16ND-EM101 Delete Note 3 (Detail 1), Detail 4, and Line types and symbols referencing water meters. See revised sheet.

EM103 Change Details 1 thru 9 to indicate correct conduit size at 28mm. See revised sheet.

EM104 Change Details 1, 2, and 3 to indicate correct conduit size at 28mm. See revised sheet.

EM104 Change Detail 4 to indicate correct conduit sizes at 100mm in lieu of 400mm. See revised sheet.

EM104 Change Detail 5 to indicate correct ground rod size at 3.05m or 10 Feet. See revised sheet.

EM501 Change Sheet Note 9 to indicate correct source panelboard First Floor Lighting Panel M-1A. See revised sheet.

EM501 Change Sheet Note 12 to indicate correct conduit size at 42mm. See revised sheet.

EM503 Change Sheet Note 9 to indicate correct source panelboard Floor Panel M. See revised sheet.

EM504 Remove water meters from the project. See revised sheet.

EM505 Remove water meters from the project. See revised sheet.

EM506 Change Sheet Note 22 to “Not Applicable”, and change Detail 1 to remove references to water meters. See revised sheet.

EM506 Change Sheet Note 11 to indicate correct conduit size at 28mm. See revised sheet.

EM507 Delete Detail 2. See revised sheet.

EM508 Change Sheet Note 2 to indicate correct handhole dimension to 600mm x 600mm x 690mm. Change Detail 1 to remove water meters. See revised sheet.

EM509 Change Detail 1 to remove water meters from the project. See revised sheet.

E-001 Change General Plan Note 5. See revised sheet.

4P1-EP101 Change Sheet Note 2 to indicate correct conduit at FEP 65mm. See revised sheet.

4P1-EP101 Add Sheet Note 13 and water service entrance locations. Changed Detail 2. See revised sheet.

4P1-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

4P1-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet 4P1-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet 4P3-ED101 Change Sheet Note 1 to indicate building panel to be removed. See revised sheet.

4P3-EP101 Change Sheet Note 4 to indicate building panel to be new. See revised sheet 4P3-EP101 Change Sheet Note 2 to indicate correct conduit at FEP 65mm. See revised

Identification Number

Description sheet.

4P3-EP101 Add Sheet Note 11 and water service entrance locations. Changed Detail 2. See

4P3-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

4P3-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

4P3-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

6N-EP101 Change Sheet Note 2 to indicate correct conduit size at 65mm. See revised sheet.

6N-EP101 Add Sheet Note 11 and water service entrance locations. Changed Detail 2. See revised sheet.

6N-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

6N-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

6N-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

6P1-EP101 Change Sheet Note 2 to indicate correct conduit at FEP 65mm. See revised sheet.

6P1-EP101 Add Sheet Note 13 and water service entrance locations. Changed Detail 2. See revised sheet.

6P1-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

6P1-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

6P1-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

6A-EP101 Change Sheet Note 2 to indicate correct conduit size at FEP 65mm. See revised sheet.

6A-EP101 Add Sheet Note 13 and water service entrance locations. Changed Detail 2. See revised sheet.

6A-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

6A-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

6A-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

7P2-ED101 Change Sheet Note 1 to indicate building panel to be demolished See revised sheet.

7P2-EP101 Change Sheet Note 4 to indicate building panel to be new. See revised sheet.

7P2-EP101 Change Sheet Note 2 to indicate correct conduit size at FEP 65mm. See revised sheet.

7P2-EP101 Add Sheet Note 11 and water service entrance locations. Changed Detail 2. See revised sheet.

7P2-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

7P2-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

7P2-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

Identification Number

Description

7A-EP101 Change Sheet Note 2 to indicate correct conduit size at FEP 65mm. See revised sheet.

7A-EP101 Add Sheet Note 12 and water service entrance locations. Changed Detail 2. See revised sheet.

7A-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

7A-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

7A-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

8N-EP101 Change Sheet Note 2 to indicate correct conduit size at FEP 65mm. See revised sheet.

8N-EP101 Add Sheet Note 11 and water service entrance locations. Changed Detail 2. See revised sheet.

8N-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

8N-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

8N-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

10N-EP101 Change Detail 1 to show location of existing electrical panels and new panel M-

1A. See revised sheet.

10N-EP101 Change Detail 2, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

10N-EP101 Change Sheet Note 7 to add GFCI receptacle. See revised sheet.

10N-EP102 Add Detail 3 to indicate work associated with Main Lighting Panel M-1 and new panel M-1A. See revised sheet.

10N-EP103 Change Detail 1 to indicate corrected demand load for 10N-MDP and updated circuit breaker sizes. See revised sheet.

10N-EP103 Change Detail 2 to indicate corrected circuit breaker sizes. See revised sheet.

10N-EP103 Change Detail 3 to indicate Unit Panel and modify heat pump circuit breaker from a 3-pole to a 2-pole. See revised sheet.

10N-EP103 Change Detail 4 to indicate correct panel calculations and circuit compliments.

See revised sheet.

10N-EP103 Change Detail 5 to indicate modified demand calculations. See revised sheet.

10N-EP104 Add panel schedule for new panel M-1A See revised sheet.

15N-EP101 Change Sheet Note 2 to indicate correct conduit size at FEP 65mm. See revised sheet.

15N-EP101 Add Sheet Note 13 and water service entrance locations. Changed Detail 2. See revised sheet.

15N-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

15N-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

15N-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

12N-EP101 Change Sheet Note 2 to indicate correct conduit size at FEP 65mm. See revised sheet.

12N-EP101 Add Sheet Note 13 and water service entrance locations. Changed Detail 2. See

Identification Number

Description

12N-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

12N-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

12N-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

16N-ED101 Change Sheet Note 4 to indicate telecommunication cabinet to remain as is See revised sheet.

16N-EP101 Change Details 2 & 4 to indicate new location of heat pump and disconnect switch. Change Sheet Notes 6, 9, & 10 as shown. Telecommunication cabinet to remain in original location. See revised sheet.

16N-EP101 Add Sheet Note 16 and water service entrance locations. Changed Detail 2. See

16N-EP101 Add Detail 4/16N-EP101 General Note. See revised sheet. .

16N-EP102 Change Detail 1, panel schedule as shown on drawings. See revised sheet. sheet 16N-EP102 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

16N-EP102 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

16ND-EP103 Add Sheet Note 10 and water service entrance locations. Changed Detail 2. See revised sheet.

16ND-EP104 Change Detail 1, panel schedule as shown on drawings. See revised sheet.

16ND-EP104 Change Detail 2, one line diagram as shown on drawings. See revised sheet.

16ND-EP104 Change Detail 4, heat pump disconnect switch to indicate IP44 rating in lieu of

NEMA-4X and a 2-pole circuit breaker in lieu of a 3-pole. See revised sheet.

E-601 E-602 E-603 E-604

Updated Equipment Connection Schedule. See revised sheets.

P-001 Remove this sheet from project 15N-P-101 Remove this sheet from project 16N-P-101 Remove this sheet from project 16ND-P-101 Remove this sheet from project 4P1-P-101 Remove this sheet from project 4P3-P-101 Remove this sheet from project 6A-P-101 Remove this sheet from project 6N-P-101 Remove this sheet from project 6P1-P-101 Remove this sheet from project 7A-P-101 Remove this sheet from project 7P2-P-101 Remove this sheet from project 8N-P-101 Remove this sheet from project 12N-P-101 Remove this sheet from project