FA520517R0004_Atch2_Drawings_4_Architectural.pdf

PDF 9 MB Posted

Attached to
Improve Military Family Housing (IMFH) Phase III, A/C and Weatherization, Misawa Air Base, Japan
Solicitation number
FA5205-17-R-0004
Issued by

About this file

FA520517R0004_Atch2_Drawings_4_Architectural

View the file

Other files

File Type Posted
FA520517R00040005_Amendment.pdf PDF
FA520517R00040005_Atch3.pdf PDF
FA520517R00040005_Atch1.pdf PDF
FA520517R00040005_Atch4.pdf PDF
FA520517R00040005_Atch7.pdf PDF
FA520517R00040005_Atch6.pdf PDF
FA520517R00040005_Atch2.pdf PDF
FA520517R00040005_Atch5.pdf PDF
FA520517R00040004_Atch4.pdf PDF
FA520517R00040004_Amendment.pdf PDF
FA520517R00040004_Atch3-4.pdf PDF
FA520517R00040004_Atch3-3.pdf PDF
FA520517R00040004_Atch5.pdf PDF
FA520517R00040004_Atch1.pdf PDF
FA520517R00040004_Atch2.pdf PDF
FA520517R00040004_Atch3-5.pdf PDF
FA520517R00040004_Atch3-2.pdf PDF
FA520517R00040004_Atch3-1.pdf PDF
FA520517R00040003_Atch1.pdf PDF
FA520517R00040003_Atch2.pdf PDF
FA520517R00040003_Amendment.pdf PDF
FA520517R00040002_Amendment.pdf PDF
FA520517R00040002_Atch.pdf PDF
FA520517R00040001_Atch2_Revised_Specification_Section.pdf PDF
FA520517R00040001_Amendment.pdf PDF
FA520517R00040001_Atch4_Revised_Solicitation_Page.pdf PDF
FA520517R00040001_Atch1_Addendum_No._1.pdf PDF
FA520517R00040001_Atch3_Revised_Drawings.pdf PDF
FA520517R0004_PreProposal_Conference_Minutes_&_Record_of_Site_Visit.pdf PDF
FA520517R0004_Atch2_Drawings_8_Electrical.pdf PDF
FA520517R0004_Atch2_Drawings_6_Plumbing.pdf PDF
FA520517R0004_Atch10_Asbestos_Sampling_and_Analysis.pdf PDF
FA520517R0004_Atch2_Drawings_3_Structural.pdf PDF
FA520517R0004_Atch2_Drawings_2_Hazmat.pdf PDF
FA520517R0004_Atch2_Drawings_5_Mechanical.pdf PDF
FA520517R0004_Atch4_PPQ_Cvr_Ltr.pdf PDF
FA520517R0004_Solicitation.pdf PDF
FA520517R0004_Atch8_Acceptable_JPN_Product_Substitutes.pdf PDF
FA520517R0004_Atch2_Drawings_7_Controls.pdf PDF
FA520517R0004_Atch9_Mfr's_Cut_Sheet_Catalog_Info.pdf PDF
FA520517R0004_Atch2_Drawings_1_General.pdf PDF
FA520517R0004_Atch3_Other_Contract_Requirements.pdf PDF
FA520517R0004_Atch1_Specifications.pdf PDF
FA520517R0004_Atch6_Construction_Timeline.pdf PDF
FA520517R0004_Atch5_PPQ.pdf PDF
FA520517R0004_Atch7_Schedule_of_Material_Submittals.pdf PDF
Show all 46

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWING LETTER/ DETAIL NUMBER

GRID LETTER

DOOR ID

DETAIL REFERENCE DESIGNATOR

GRID/COLUMN LINES

GRID NUMBER

BATT INSULATION

EARTH/COMPACT FILL

GYPSUM WALL BOARD

ROUGH WOOD FRAMING BLOCKING/SHIM

FINISH WOOD TRIM

CMU

METAL

CONCRETE PLYWOOD

HORIZ

EXPANSION JOINTEJ

DWG

DWR

EA

DW

DS

DR

DRAWER

EACH

DISHWASHER

DOWNSPOUT

DOOR

DRAWING

MH

MIN

MTL

MECH

MFR

MC

MAX

DOUBLE ACTING

DOUBLE SASH WINDOW

CLEAN OUT TO DRAIN

DET

DBL

DIAG

DISP

DN

DIM

DIA

DIAGRAM

DOWN

DISPENSER

DIMENSION

DETAIL

DOUBLE

DIAMETER

CSK

CONTR

CTR

COTD

DBL ACT

D-SASH

CT

COUNTERSINK

CENTER

CERAMIC TILE

CONTRACTOR

LAM

LAV

J-BOX

INTR

INV

ID

INCL

INSUL

CONCRETE MASONRY UNITS

COND

CONSTR

CONN

CONC

COL

CNTR

CONT

COORD

CO

CONSTRUCTION

CONNECTION

CONTINUOUS

COORDINATE

CLEANOUT, CASED OPENING

CONDITION

CONCRETE

COLUMN

COUNTER

CMU

CLG

CEM

CER

CLR

CLO

CJ

CI

CEILING

CLEAR

CONTROL JOINT

CLOSET

CEMENT

CERAMIC

CAST IRON

HDW

HM

HB

HC

HDWD

H

GYP BD

GYP

GL

G

MANHOLE

MINIMUM

MEDICINE CABINET

METAL

MECHANICAL

MANUFACTURER

MAXIMUM

SYMM

SVCE

SYS

SYMMETRICAL

SERVICE

SYSTEM

SUSP

SURR

STRUCT

STOR

STD

SQ

SUSPENDED

SURROUND

STRUCTURAL

STORAGE

STANDARD

SQUARE

REINFORCED OR REINFORCING

REVISED, REVISION OR REVERSED

SMOKE DETECTOR; SOAP DISPENSER

LAMINATE OR LAMINATED

LAVATORY

JUNCTION BOX

INSIDE DIAMETER

INCLUSIVE, INCLUDE(D), INCLUDING

INTERIOR

INVERT

INSULATION

SLDG

SPEC

SIM

SHT

SHTHG

SPECIFICATION

SLIDING

SHEATHING

SHOWER

SIMILAR

SHEET

SHR

SECT

SD

SC

SCHED

SCRN

SECTION

SOLID CORE

SCHEDULE

SCREEN

HARDWARE

HORIZONTAL

HOLLOW METAL

HOSE BIBB

HOLLOW CORE

HARDWOOD

GYPSUM BOARD

HIGH OR HEIGHT

GYPSUM

GLASS

GROUND

RO

RND

RH

REG

RM

REV

RFG

ROUGH OPENING

ROUND

ROBE HOOK; RIGHT HAND

REGISTER

ROOM

ROOFING

RESIL

REFRIG

REQD

REINF

REC

REF

RB

REFRIGERATOR

REQUIRED

RESILIENT

RECESSED

REFERENCE

RESILIENT BASE

FLASH

FLUOR

BUILT-UP ROOFING

BRKT

CAB

BRG

BTWN

BUR

CB

BS

BED RM

CATCH BASIN

CABINET

BOTH SIDES

BEDROOM

BRACKET

BEARING

BETWEEN

ASPH

ASB

BLDG

BITUM

BOT

BM

BD

BUILDING

BEAM

BOTTOM

ASPHALT

ASBESTOS

BOARD

BITUMINOUS

GA

GALV

GB

GI

FURG

FTG

FR

FPRP

FOW

FS

FOS

FOM

FOF

FOC

ABOVE FINISHED FLOOR

NUMBER

AIR CONDITIONING

ASPHALTIC CONCRETE

AGGR

AFF

ANOD

ALT

APPROX

ARCH

ACS PNL

ALUM

ACCESS PANEL

ANODIZED

APPROXIMATE

ARCHITECTURAL

AGGREGATE

ALUMINUM

ALTERNATE

ADJ

ACST

A/C

AB

AC

ADJUSTABLE, ADJACENT

ACOUSTICAL

ANCHOR BOLT

FLDG

FIN

FLR

FIXT

FFEL

FDTN

FD

FCU

Ø

L

DIAMETER

PERPENDICULAR

PERCENT

AND

ANGLE

AT

CENTERLINE

CHANNEL

EQ

EQPT

EXP

ELEC

OUTSIDE DIAMETER, OUTSIDE DIMENSION

PLATE OR PROPERTY LINE

FURRING OR FURRED

GAUGE

GALVANIZED

GRAB BAR

GALVANIZED IRON

FOOTING

FACE OF STUD, SLAB OR STRUCTURE

FACE OF MASONRY

FACE OF CONCRETE

FULL SIZE

FRAME

FIREPROOF

FACE OF WALL

FLUORESCENT

FACE OF FINISH

PVG

R

PVC

PTN

PAVING

RISER; RADIUS

POLYVINYL CHLORIDE

PARTITION

PT

PREP

PROP

PRCST

PNL

PLYWD

PREFAB

PR

PREPARATION

PROPERTY

POINT; PAINT

PLUMBING

PREFABRICATE

PRECAST

PANEL

PLYWOOD

PAIR

FINISH FLOOR ELEVATION

FLASHING

FINISH

FOLDING

FLOOR

FIXTURE

FOUNDATION

FLOOR DRAIN

FAN COIL UNIT

PLBG

PLAS

PERIM

PL

PLAM

OPNG

OPP

PLASTIC LAMINATE

PLASTER

PERIMETER

OPPOSITE

OPENING

OGL

OD

OC

OA

NO or #

NTS

NOM

OBSCURE GLASS

ON CENTER

NOT TO SCALE

OVERALL

NOMINAL

WWF

WSCT

WP

WT

WR

WO

W/O

WH

WDW

WELDED WIRE FABRIC

WATER RESISTANT

WAINSCOT

WATERPROOFING

WALL TYPE, WEIGHT

WHERE OCCURS

WATER HEATER

WITHOUT

WINDOW

W/

WC

WD

W

VAR

VRFY

VTR

UNO

TYP

UNFIN

TV

TPH

WATER CLOSET; WALL COVERING

WASHER; WIDE; WIDTH; WEST

WITH

WOOD

VARIES

VENT THROUGH ROOF

VERIFY

UNLESS NOTED OTHERWISE

TYPICAL

UNFINISHED

TOILET PAPER HOLDER

TELEVISION

EQUAL

EQUIPMENT

EXPANSION, EXPOSED

ENCLOSURE

MTG

MATL

MUL

NIC

MTD

MOUNTING

NOT IN CONTRACT

NUMBER

MATERIAL

MULLION

MOUNTED

TO ___

THRU

THRES

THK

TMPD

TEL

TEMP

TOP OF

THICK OR THICKNESS

THROUGH

THRESHOLD

TEMPERED

TELEPHONE

TEMPORARY

ENCL

ELECTRICAL

ELEVATIONEL

MO MASONRY OPENING

MOLDING

MIRROR

MISCELLANEOUS

MLDG

MISC

MIRR

TOWEL BARTB

ASBESTOS CONTAINING MATERIALACM

PARTITION TYPE INDICATOR

BLVD BOULEVARD

BATHRM BATHROOM

MR MOISTURE RESISTANT

SEP SEPARATION

T TREAD

STL STEEL

ST STREET

PL PROPERTY LINE

AD AREA DRAIN

SHEET METAL

POLYESTER PANEL

UL UNDERWRITER'S LABORATORY

FINISH MATERIAL INDICATOR

SM

SWR SEWER

WINDOW OR LOUVER TYPE

CU CUBIC

mm MILLIMETER

WITHINW/IN

EXIST TO REMAIN

EXTR EXTERIOR

CONTRACTOR FURNISHED,CFCI

CONTRACTOR INSTALLED

INTERIOR BULK STORAGEIBS

EBS EXTERIOR BULK STORAGE

DEMOLITION

AHU AIR HANDLING UNIT

ACOUSTICAL TILEAT

CORNER GUARDCG

CAST IN PLACECIP

COPPERCU

CORRIDORCORR

CARPETCPT

COLD WATER PIPINGCW

DECK DRAINDR

EXISTINGEXIST

EASTE

ELASTOMERIC COATINGELAST

EMERGENCY

ELEVATOR

EMER

ELEV

EPS EXPANDED POLYSTYRENE BOARD

FEMALEF

FUNITURE, FIXTURE, & EQUIPMENTFF&E

FIBERGLASS REINFORCEDFRP

FIRE RETARDANT TREATEDFRT

FUTUREFUT

GFRC GLASS FIBER REINFORCED CONCRETE

GRANITEGRAN

GYPSUM SHEATHINGGS

GYPSUM SHEATHING BOARDGSB

QUARRY TILEQT

PIECEPC

OFFICEOFF

OVERFLOW DRAINOFD

NORTHN

MEMBRANEMEMB

MASTER BEDROOM

MACHINE BOLT

MBR

MB

MALE, METERM

LEFT HANDLH

LANDINGLDG

LOCATIONLOC

LINEAR METERLM

LIVING ROOM

LIGHT

LR

LT

LOUVERLVR

KNOCK DOWN

KITCHEN

KNOCKOUT

KIT

KO

KD

REINFORCING BARREBAR

ROOF DRAINRD

REFLECTEDREFL

ROOF, RESILIENT FLOORINGRF

SOUTHS

SCUPPERSCP

SEALANTSLNT

SQM SQUARE METER

SST STAINLESS STEEL

STATION

SOUND TRANSMISSION COEFFICIENT

STA

STC

SWITCHSW

TOWEL SHELFTSH

TOWEL RINGTR

TOP OF WALL

TOP OF CURB

TOP OF PAVEMENT

TOW

TOP

TOC

TRENCH DRAINTD

URINALUR

UC UNDER CUT

VENEER PLASTERVP

VOLUMEVOL

VESTIBULEVEST

VERT VERTICAL

WSP WET STANDPIPE

FIRE ALARMFA

FLAT BARFB

HAND SINKHS

UNLESS OTHERWISE NOTEDUON

DEMOLISH(ED), DEMOLITIONDEMO

OVERHANGOH

WALL-MOUNTED LIGHT FIXTURE

SUPPLY AIR DIFFUSER

RETURN AIR REGISTER

EXHAUST AIR REGISTER

W/FAN

CEILING ACCESS PANEL

CEILING FAN WITH LIGHT

SURFACE MOUNTED TRACK LIGHT

FIXTURE

ELEVATION INDICATOR

SURFACE MOUNTED

LIGHT FIXTURE

SMOKE DETECTOR

OUTDOOR HEAT PUMPOHP

OBSCURE WIRE GLASSOWGL

NEW GYPSUM BOARD CEILING

SURFACE MOUNTED LIGHT

FIXTURE

CEILING HEIGHT INDICATOR

GFCI GROUND FAULT CURRENT INTERRUPTED

NOTE: "GOVERNMENT FURNISHED,

CONTRACTOR INSTALLED" SHALL NOT

BE ABBREVIATED IN THIS DOCUMENT.

TITLE

SHEET NUMBER WHERE DRAWING

OR DETAIL IS DRAWN

SHEET NUMBER WHERE DRAWING OR

DETAIL IS CALLED OUT

DRAWING LETTER/ DETAIL NUMBER

SHEET NUMBER WHERE DRAWING

OR DETAIL IS DRAWN

SHEET NUMBER WHERE DRAWING OR

DETAIL IS CALLED OUT

DRAWING/DETAIL DESIGNATOR

SECTION REFERENCE DESIGNATOR

ELEVATION REFERENCE DESIGNATOR

INTERIOR ELEVATION REFERENCE DESIGNATOR

OVERO/

MEZZANINEMEZZ

RANGE HOOD

MST MASTER

LINENLIN

BTH BATH

DEMOLITION KEYNOTE

KEYNOTE

EXISTING WALL

TO BE DEMOLISHED

TO BE DEMOLISHED

EXISTING DOOR

TO BE DEMOLISHED

EXISTING WINDOW

EXISTING WALL TO REMAIN

NEW FURRING OVER

EXIST / CONCRETE

NEW STUD PARTITION

NEW CMU

NEW CONCRETE

EXISTING FURRING

FLOOR ACCESS PANEL

VINYL COMPOSITION TILE

DEMOLITION

CERAMIC TILE

TO BE DEMOLISHED

AE-502 AE-101

AE-502 AE-101

AE-502 AE-101

AI-401 AE-101

A

B

C

D

AIR COOLED CONDENSING UNITACCU

NEW PLASTER FINISH

NEW CONC. SIDEWALK

HOLLOW STRUCTURAL SECTION (STEEL)HSS

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

A L

I N

T E

G R

A T

E D

T

E R

P R

I S

E S

M

A Y

F A

R

O A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

C

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

T

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

S

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

Q

K K

A

M I S

A W

A

A

B

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

F

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

H Y

W

E N

D T

AE001

A R

C H

I T

E C

T U

R A

L

S

Y M

B O

L S

M

A T

E R

I A

L

L

E G

E N

D

A N

D

A

B B

R E

V I A

T I O

N S

J O

V

N

N

J D

V K

C

N A

LIGHT WEIGHT CONCRETELWC

DRYER, DEEP, DEPTHD

X2 X3 X4

Y4

Y3

Y2

Y1

Y0

LIVING / DINING

BATH

FAMILY

RM

S T

A I R

EBS

EBS

KITCHEN

LAUND.

PATIO

PORCH

PATIO

H A

L L

C L O

S T

O

EBS

EBS

EBS

EBS

NO

WORK

THIS

AREA

NO

WORK

THIS

AREA

D2

D2

D4

D3

72407240

28960

TYPICAL UNIT

D4

SIM UNIT

X2 X3 X4

Y4

Y3

Y2

Y1

Y0

BATH

S T

A I R

BEDROOM 1

HALL

CLO.

LAV

CLO.

CLO.CLO.

BEDROOM 2

BEDROOM 3

BATH

NO WORK

THIS AREA

NO WORK

THIS AREA

NO

WORK

THIS

AREA

D2

D2

D2

72407240

28960

TYPICAL UNIT

SIM UNIT

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

0 2000 4000

TYPE 4P1 - 3 BEDROOM - FIRST FLOOR

4P1-AE101

T Y

P

D

R O

O M

P L

A N

S

N

W

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

0 2000 4000

TYPE 4P1 - 3 BEDROOM - SECOND FLOOR

BUILDING LEGEND

BUILDING TYPE 4P1 CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (8 BUILDINGS):

YELLOWSTONE - 176, 177, 178, 179, 184, 186, 259, 261

GENERAL PLAN NOTES:

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

5. PRIME AND PAINT NEW AND REPAIRED INTERIOR GYP BD PAINT

FINISH TO 300mm BEYOND DISTURBANCE - COORDINATE COLOR

AND SHEEN TO MATCH BASE HOUSING STANDARD - SEE DETAIL

25/AE501

6. EXIST CONSTRUCTION CONTAINS HAZARDOUS MATERIALS

INCLUDING BUT NOT LIMITED TO GYP BD JOINT COMPOUND - REFER

TO HAZMAT DWGS AND SPECIFICATIONS

KEYED NOTES:

CEILING-MOUNTED HVAC UNIT - REPAIR DISTURBED INSULATION

ABOVE UNIT - ADD MATCHING INSULATION IF REQUIRED TO

MAINTAIN THERMAL PERFORMANCE - SEE MECH DWGS

PREFINISHED ALUM PIPE CHASE COVER - SEE DETAILS 11/AE502

AND 15/AE502

DEMOLITION NOTES:

NOT APPLICABLE TO THIS DRAWINGD1

COORDINATE DEMOLITION AND REMOVAL OF EXIST

CEILING-MOUNTED HVAC UNIT BY MECH - SEE MECH DWGS

D2

DEMOLISH AND REMOVE EXIST CEILING ACCESS PANELD3

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - PATCH AND REPAIR PER KEYNOTE 4

EXIST CEILING ACCESS PANEL TO REMAIN

PATCH AND REPAIR ABANDONED OR MODIFIED CEILING OPENINGS

AND PENETRATIONS WITH SUSPENDED GYP BD CEILING TO MATCH

EXIST - REPAIR DISTURBED INSULATION ABOVE UNIT - ADD

MATCHING INSULATION IF REQUIRED TO MAINTAIN THERMAL

PERFORMANCE - PRIME AND PAINT - SEE DETAIL 25/AE501

CEILING ACCESS PANEL - SEE DETAIL 24/AE5016

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - REMOVE GYP BD AS REQ'D - GYP BD JOINT

COMPOUND CONTAINS ASBESTOS - REMEDIATE DISTURBED ACM

D4

X0 X1 X2 X3 X4

2 2

TYPICAL UNIT

FRONT

10 TYP

15 TYP

Y4 Y3 Y2 Y1 Y0

LEFT

X0X1X2X3X4

2 2

TYPICAL UNIT

REAR

15 TYP

Y4Y3Y2Y1Y0

RIGHT

X0 X1 X2 X3 X4

TYPICAL UNIT

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

GENERAL ELEVATION NOTES:

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT. IF BUILDING

NUMBERS ARE IMPACTED OR OBSCURED BY CONSTRUCTION, THEY

SHALL BE REPAINTED IN A LOCATION APPROVED BY THE

CONTRACTING OFFICER.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

5. ALTERNATE CANOPY AND EQUIPMENT PAD MAY BE REQUIRED AT

BUILDINGS 179 AND 259 - SEE DETAIL 4/AE501.

KEYED NOTES:

HEAT PUMP UNIT TYPICAL PER MECH DWGS - SEE SITE PLANS AND

MECH DWGS FOR LOCATIONS AT EACH BUILDING - EXACT LOCATION

OF HEAT PUMP UNIT TO BE DETERMINED IN THE FIELD - SEE

MOUNTING DETAILS AE501

WALL-MOUNTED EMCS PANEL

EXIST ELECTRICAL PANEL

EXIST TV/COMM PANEL(S)

WALL-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING & CONTROL WIRING

ROOF CANOPY - WALL-MOUNTED METAL FRAME WITH METAL ROOF

- SEE DETAIL 1/AE501

ROOF CANOPY - SITE WALL-MOUNTED METAL FRAME WITH METAL

ROOF - DETAIL 2/AE501

SOFFIT-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING & CONTROL WIRING

0 2000 4000

TYPE 4P1 - 3 BEDROOM - ELEVATIONS

4P1-AE201

T Y

D

R O

O M

E L

E V

A T

I O

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

BUILDING LEGEND

BUILDING TYPE 4P1 CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (8 BUILDINGS):

YELLOWSTONE - 176, 177, 178, 179, 184, 186, 259, 261

DEMOLITION NOTES:

D1

DEMOLISH AND REMOVE EXIST EXTR FLUSH DR - REMOVE AND

STORE HARDWARE TO BE REINSTALLED ON REPLACEMENT DOOR -

PRESERVE IN PLACE FRAME, STORM DR (WO) AND SIDELITE (WO)

D2

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

EXTR ALUM FLUSH DR - FIELD VERIFY SIZE - REUSE EXIST

HARDWARE AND ACCESSORIES

TYPE 4P1 - 3 BEDRM - DEMOLITION ELEVATION

0 4000 8000

D2

TYP

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

EXTR SLIDING GLASS DR - DEMOLISH AND REPLACE SILL FLASHING

PER 10/AE502

Y3

Y2

Y1

Y0

LIVING / DINING

EBS

BATH

FAMILY

RM

S T

A I R

EBS

EBS

EBS

EBS

EBS

KIT.

LAUND.

PATIO

PORCH

PATIO

H A

L L

C L O

S T

O

D2

D2

72407240

28960

TYPICAL UNIT

NO

WORK

THIS

AREA

NO

WORK

THIS

AREA

SIM UNIT

D4

X2 X3 X4

Y4

Y3

Y2

Y1

Y0

BATH

S T

A I R

BEDROOM 1

HALL

CLO.

LAV

CLO.

CLO.CLO.

BEDROOM 2

BEDROOM 3

BATH

D2

D2

D2

ALT LOC AT

INNER UNITS

72407240

28960

TYPICAL UNIT

NO WORK

THIS AREA

NO WORK

THIS AREA

NO WORK

THIS AREA

SIM UNIT

D3

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

GENERAL PLAN NOTES:

KEYED NOTES:

CEILING-MOUNTED HVAC UNIT - REPAIR DISTURBED INSULATION

ABOVE UNIT - ADD MATCHING INSULATION IF REQUIRED TO

MAINTAIN THERMAL PERFORMANCE - SEE MECH DWGS

PREFINISHED ALUM PIPE CHASE COVER - SEE DETAILS 11/AE502

AND 15/AE502

DEMOLITION NOTES:

D1

COORDINATE DEMOLITION AND REMOVAL OF EXIST

CEILING-MOUNTED HVAC UNIT BY MECH - SEE MECH DWGS

D2

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - PATCH AND REPAIR PER KEYNOTE 4

EXIST CEILING ACCESS PANEL TO REMAIN

PATCH AND REPAIR ABANDONED OR MODIFIED CEILING OPENINGS

AND PENETRATIONS WITH SUSPENDED GYP BD CEILING TO MATCH

EXIST - REPAIR DISTURBED INSULATION ABOVE UNIT - ADD

MATCHING INSULATION IF REQUIRED TO MAINTAIN THERMAL

PERFORMANCE - PRIME AND PAINT - SEE DETAIL 25/AE501

CEILING ACCESS PANEL - SEE DETAIL 24/AE5016

0 2000 4000

TYPE 4P3 - 3 BEDROOM - FIRST FLOOR

4P3-AE101

T Y

D

R O

O M

P L

A N

S

N

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

0 2000 4000

TYPE 4P3 - 3 BEDROOM - SECOND FLOOR

BUILDING LEGEND

BUILDING TYPE 4P3 CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (9 BUILDINGS):

CAPE COD - 707, 708, 709, 710, 711, 713, 714, 720, 721

NOT APPLICABLE TO THIS DRAWING

D3

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - REMOVE GYP BD AS REQ'D - NOTE THAT GYP BD

JOINT COMPOUND MAY BE ACM - REMEDIATE DISTURBED ACM

D4

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

EXIST MECH REGISTER TO REMAIN

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

5. PRIME AND PAINT NEW AND REPAIRED INTERIOR GYP BD PAINT

FINISH TO 300 BEYOND DISTURBANCE - COORDINATE COLOR AND

SHEEN TO MATCH BASE HOUSING STANDARD - SEE DETAIL

25/AE501

6. EXIST CONSTRUCTION CONTAINS HAZARDOUS MATERIALS

INCLUDING BUT NOT LIMITED TO GYP BD JOINT COMPOUND - REFER

TO HAZMAT DWGS AND SPECIFICATIONS

2 2

TYPICAL UNIT

FRONT

15 TYP

Y4 Y3 Y2 Y1 Y0

LEFT

X0X1X2X3X4

2 2

TYPICAL UNIT

REAR

15 TYP

Y4Y3Y2Y1Y0

RIGHT

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

GENERAL ELEVATION NOTES:

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT. IF BUILDING

NUMBERS ARE IMPACTED OR OBSCURED BY CONSTRUCTION, THEY

SHALL BE REPAINTED IN A LOCATION APPROVED BY THE

CONTRACTING OFFICER.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

5. ALTERNATE CANOPY AND EQUIPMENT PAD MAY BE REQUIRED AT

BUILDINGS 708, 711, 720 AND 721 - SEE DETAIL 4/AE501.

KEYED NOTES:

HEAT PUMP UNIT TYPICAL PER MECH DWGS - SEE SITE PLANS AND

MECH DWGS FOR LOCATIONS AT EACH BUILDING - EXACT LOCATION

OF HEAT PUMP UNIT TO BE DETERMINED IN THE FIELD - SEE

MOUNTING DETAILS AE501

WALL-MOUNTED EMCS PANEL

EXIST ELECTRICAL PANEL

EXIST TV/COMM PANEL(S)

WALL-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING & CONTROL WIRING

ROOF CANOPY - WALL-MOUNTED METAL FRAME WITH METAL ROOF

- SEE DETAIL 1/AE501

ROOF CANOPY - SITE WALL-MOUNTED METAL FRAME WITH METAL

ROOF - DETAIL 2/AE501

0 2000 4000

TYPE 4P3 - 3 BEDROOM - ELEVATIONS

4P3-AE201

T Y

D

R O

O M

E L

E V

A T

I O

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

BUILDING LEGEND

BUILDING TYPE 4P3 CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (9 BUILDINGS):

CAPE COD - 707, 708, 708, 710, 711, 713, 714, 720, 721

SOFFIT-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING AND CONTROL WIRING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

EXTR SLIDING GLASS DR - DEMOLISH AND REPLACE SILL FLASHING

NOT APPLICABLE TO THIS DRAWING

Y3

Y2

Y1

Y0

LIVING / DINING

EBS

BATH

FAMILY

RM

S T

A I R

EBS

EBS

EBS

EBS

EBS

KITCHEN

L A

U N

D

H A

L L

CLO.

S T

O

A

B

4 D

75207520

30080

TYPICAL UNIT

SIM UNIT

X2 X3 X4

BEDROOM 1

BEDROOM 2

BEDROOM 3

CLO.

CLO. CLO.

C L

O

C L

O

C L

O

BATH

BATH

IBS

S T

A I R

HALL

BEDROOM 4

DD

CD

75207520

30080

TYPICAL UNIT

SIM UNIT

10 10

BEDROOM 1

BEDROOM 2

BEDROOM 3

CLO.

CLO. CLO.

C L O

C L O

C L O

BATH

BATH

IBS

S T

A I R

HALL

BEDROOM 4

D1 D1

D2

D1 D1

D2

D2D2

D4

D4

Y4

Y3

Y2

Y1

Y0

LIVING / DINING

EBS

BATH

FAMILY

RM

S T

A I R

EBS

EBS

EBS

EBS

EBS

KITCHEN

L A

U N

D

H A

L L

CLO.

S T

O

D2

D1

D2

D2

D2

D4

X0 X1 X2 X3 X4

Y4

Y3

Y2

Y1

Y0

31470

AE502

AE502

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

GENERAL PLAN NOTES:

KEYED NOTES:

DEMOLITION NOTES:

DEMOLISH AND REMOVE EXIST INTR PAIR OF SLIDING GLAZED

LEAVES @ WDW - EXIST FR TO REMAIN - SEE 6N-AE201 FOR

OPENING SCHEDULE AND AE502 FOR WDW DETAILS

D1

COORDINATE DEMOLITION AND REMOVAL OF EXIST

CEILING-MOUNTED HVAC UNIT BY MECH - SEE MECH DWGS

D2

NOT APPLICABLE TO THIS DRAWING

D3

0 2000 4000

TYPE 6N - 4 BEDROOM - FIRST FLOOR

6N-AE101

T Y

D

R O

O M

P L

A N

S

N

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

0 2000 4000

TYPE 6N - 4 BEDROOM - SECOND FLOOR

BUILDING LEGEND

BUILDING TYPE 6N CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (2 BUILDINGS):

SEQUOIA - 332, 333

TYPE 6N - 4 BEDROOM - FIRST FLOOR DEMO

0 2000 4000

TYPE 6N - 4 BEDRM - SECOND FLOOR DEMO

0 2000 4000

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - REMOVE GYP BD AS REQ'D - NOTE THAT GYP BD

JOINT COMPOUND IS ACM - REMEDIATE DISTURBED ACM

D4

TYPE 6N - 4 BEDROOM - ROOF PLAN

0 4000 8000

NEW R-20 RIGID INSULATION, MECHANICALLY FASTENED

PROTECTION BOARD AND FLUID-APPLIED URETHANE ROOFING -

SEAL ATTIC VENT OPENINGS

CEILING-MOUNTED HVAC UNIT - REPAIR DISTURBED INSULATION

ABOVE UNIT - ADD MATCHING INSULATION IF REQUIRED TO

MAINTAIN THERMAL PERFORMANCE - SEE MECH DWGS

PREFINISHED ALUM PIPE CHASE COVER - SEE DETAILS 11/AE502

AND 15/AE502

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - PATCH AND REPAIR PER KEYNOTE 4

EXIST CEILING ACCESS PANEL TO REMAIN

PATCH AND REPAIR ABANDONED OR MODIFIED CEILING OPENINGS

AND PENETRATIONS WITH SUSPENDED GYP BD CEILING TO MATCH

EXIST - REPAIR DISTURBED INSULATION ABOVE UNIT - ADD

MATCHING INSULATION IF REQUIRED TO MAINTAIN THERMAL

PERFORMANCE - PRIME AND PAINT - SEE DETAIL 25/AE501

NOT APPLICABLE TO THIS DRAWING6

LOW-EMISSIVITY FILM APPLIED TO SURFACE 3 (EXTERIOR SIDE OF

INNER SASH GLAZING) AT ALL SLIDING GLASS DRS

EXIST MECH REGISTER TO REMAIN8

EXTERIOR WDW INNER SASH REPLACEMENT - SEE DETAILS ON

AE502

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

5. PRIME AND PAINT NEW AND REPAIRED INTERIOR GYP BD PAINT

FINISH TO 300 BEYOND DISTURBANCE - COORDINATE COLOR AND

SHEEN TO MATCH BASE HOUSING STANDARD - SEE DETAIL

25/AE501

6. EXIST CONSTRUCTION CONTAINS HAZARDOUS MATERIALS

TYP

A

CE

TYP

TYPICAL UNIT

FRONT

TYP

TYP

TYP

TYP

Y4 Y3 Y2 Y1 Y0

LEFT

X0X1X2X3X4

TYP

D D

D

B

TYP

TYPICAL UNIT

REAR

TYP

TYP

TYP

Y4Y3Y2Y1Y0

RIGHT

X0 X1 X2 X3 X4

TYPICAL UNIT

Y4 Y3 Y2 Y1 Y0

X0X1X2X3X4

TYPICAL UNIT

Y4Y3Y2Y1Y0

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

GENERAL ELEVATION NOTES:

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT IF BUILDING

NUMBERS ARE IMPACTED OR OBSCURED BY CONSTRUCTION, THEY

SHALL BE REPAINTED IN A LOCATION APPROVED BY THE

CONTRACTING OFFICER.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

KEYED NOTES:

HEAT PUMP UNIT TYPICAL PER MECH DWGS - SEE SITE PLANS AND

MECH DWGS FOR LOCATIONS AT EACH BUILDING - EXACT LOCATION

OF HEAT PUMP UNIT TO BE DETERMINED IN THE FIELD - SEE

MOUNTING DETAILS AE501

WALL-MOUNTED EMCS PANEL

EXIST ELECTRICAL PANEL

EXIST TV/COMM PANEL(S)

WALL-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING & CONTROL WIRING

ROOF CANOPY - WALL-MOUNTED METAL FRAME WITH METAL ROOF

- SEE DETAIL 1/AE501

ROOF CANOPY - SITE WALL-MOUNTED METAL FRAME WITH METAL

ROOF - DETAIL 2/AE501

NOT APPLICABLE TO THIS DRAWING

ROUTE MECHANICAL PIPING THROUGH WING WALL - SEE DETAIL

16/AE501

DEMOLITION NOTES:

DEMOLISH AND REMOVE EXIST INTR PAIR OF SLIDING GLAZED

LEAVES @ WDW - EXIST FR TO REMAIN - SEE 6N-AE201 FOR

OPENING SCHEDULE AND AE502 FOR WDW DETAILS

D1

PROVIDE LOW-E WINDOW FILM AT INTERIOR SIDE OF EXTERIOR

SLIDING GLASS DOOR PANELS

NEW R-20 RIGID INSULATION, MECHANICALLY FASTENED

PROTECTION BOARD AND FLUID-APPLIED URETHANE ROOFING

0 2000 4000

TYPE 6N - 4 BEDROOM - ELEVATIONS

6N-AE201

T Y

D

R O

O M

E L

E V

A T

I O

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

BUILDING LEGEND

BUILDING TYPE 6N CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (2 BUILDINGS):

SEQUOIA - 332, 333

TYPE 6N - 4 BEDROOM - DEMOLITION ELEVATIONS

0 4000 8000

UNIT TYPE 6N - WINDOW SCHEDULE

WDW TAG QTY PER UNIT ROOM WIDTH HEIGHT NOTES

A 1 DINING AREA 1800 2100 SLIDING GLASS DRS

HORIZONTAL MULLION

B 1 LIVING RM 1700 2100 SLIDING GLASS DRS

HORIZONTAL MULLION

C 1 BEDROOM 1800 1300 HORIZONTAL MULLION

D 3 LIVING ROOM

BEDROOM 1700 1300 HORIZONTAL MULLION

E 1 BEDROOM 1300 1300 HORIZONTAL MULLION

D1

TYP

D1

TYP

DEMOLISH AND REMOVE EXIST EXTR FLUSH DR - REMOVE AND

STORE HARDWARE TO BE REINSTALLED ON REPLACEMENT DOOR -

PRESERVE IN PLACE FRAME, STORM DR (WO) AND SIDELITE (WO)

D2

EXTR ALUM FLUSH DR - FIELD VERIFY SIZE - REUSE EXIST

HARDWARE AND ACCESSORIES

EXTERIOR WDW INNER SASH REPLACEMENT - SEE DETAILS ON

AE502

D2

TYP

DEMOLISH AND REMOVE EXIST ATTIC VENT AND VENT COVER - SEE

DETAIL 8/AE502

D3

D3

TYP

D3

TYP

EXIST VENT HOOD TO REMAIN - PROTECT IN PLACE - BLOCK VENT

PER DETAIL 9/AE501

EXTR SLIDING GLASS DR - DEMOLISH AND REPLACE SILL FLASHING

PER 10/AE502

EXIST ATTIC VENTS TO BE PERMANENTLY CLOSED AND SEALED

PER 8/AE502

TYPE 6N - EXISTING BLDG

WINDOWS TO BE

REPLACED

ALUM DR PANEL

TO BE REPLACED

SLIDING GLASS DOOR

(BEYOND) TO RECEIVE

LOW-E FILM

Y5

Y4

Y3

Y2

Y0 Y1

LIVING / DINING

EBS

PWD.

RM

FAMILY

RM

S T

A I R

EBS

EBS

EBS

EBS

EBS

KITCHEN

LAUND.

PATIO

PORCH

H A

L L

CLO.

S T

O

D2 1

D2

75207520

30080

TYPICAL UNIT

SIM UNIT

D4

D4

D4

X2 X3 X4

Y5

Y4

Y3

Y2

Y0 Y1

S T

A I R

HALL

IBS

BEDROOM 1

BEDROOM 2

BEDROOM 3

C L O

C L O

C L O

CLO.

CLO.

CLO.

BATH

BATH

BEDROOM 4

D2

4D2

D2

D2

D3 D3

D3

75207520

30080

TYPICAL UNIT

SIM UNIT

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

GENERAL PLAN NOTES:

KEYED NOTES:

CEILING-MOUNTED HVAC UNIT - REPAIR DISTURBED INSULATION

ABOVE UNIT - ADD MATCHING INSULATION IF REQUIRED TO

MAINTAIN THERMAL PERFORMANCE - SEE MECH DWGS

PREFINISHED ALUM PIPE CHASE COVER - SEE DETAILS 11/AE502

AND 15/AE502

DEMOLITION NOTES:

NOT APPLICABLE TO THIS DRAWINGD1

COORDINATE DEMOLITION AND REMOVAL OF EXIST

CEILING-MOUNTED HVAC UNIT BY MECH - SEE MECH DWGS

D2

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - PATCH AND REPAIR PER KEYNOTE 4

EXIST CEILING ACCESS PANEL TO REMAIN

PATCH AND REPAIR ABANDONED OR MODIFIED CEILING OPENINGS

AND PENETRATIONS WITH SUSPENDED GYP BD CEILING TO MATCH

EXIST - REPAIR DISTURBED INSULATION ABOVE UNIT - ADD

MATCHING INSULATION IF REQUIRED TO MAINTAIN THERMAL

PERFORMANCE - PRIME AND PAINT - SEE DETAIL 25/AE501

CEILING ACCESS PANEL - SEE DETAIL 24/AE5016

0 2000 4000

TYPE 6P1 - 4 BEDROOM - FIRST FLOOR

6P1-AE101

T Y

D

R O

O M

P L

A N

S

N

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

0 2000 4000

TYPE 6P1 - 4 BEDROOM - SECOND FLOOR

BUILDING LEGEND

BUILDING TYPE 6P1 CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (23 BUILDINGS):

CAPE CANAVERAL - 187, 188, 192

SEQUOIA - 400, 403

YELLOWSTONE - 189, 190, 191, 329, 331, 335, 336, 338, 339, 340, 341, 350, 351, 352, 353, 354, 355, 356

DEMOLISH AND REMOVE EXIST CEILING ACCESS PANELD3

D4

NOT APPLICABLE TO THIS DRAWING7

EXIST MECH REGISTER TO REMAIN8

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

5. PRIME AND PAINT NEW AND REPAIRED INTERIOR GYP BD PAINT

FINISH TO 300 BEYOND DISTURBANCE - COORDINATE COLOR AND

SHEEN TO MATCH BASE HOUSING STANDARD - SEE DETAIL

25/AE501

6. EXIST CONSTRUCTION CONTAINS HAZARDOUS MATERIALS

INCLUDING BUT NOT LIMITED TO GYP BD JOINT COMPOUND - REFER

TO HAZMAT DWGS AND SPECIFICATIONS

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - REMOVE GYP BD AS REQ'D - GYP BD JOINT

TYPICAL UNIT

FRONT

TYP

TYP

Y4 Y3 Y2 Y1 Y0

7 6

LEFT

X0X1X2X3X4

TYPICAL UNIT

REAR

TYP

Y4Y3Y2Y1Y0

RIGHT

X0 X1 X2 X3 X4

TYPICAL UNIT

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

0 2000 4000

TYPE 6P1 - 4 BEDROOM - ELEVATIONS

6P1-AE201

T Y

D

R O

O M

E L

E V

A T

I O

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

BUILDING LEGEND

BUILDING TYPE 6P1 CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (2 BUILDINGS):

CAPE CANAVERAL - 187, 188, 192

SEQUOIA - 400, 403

YELLOWSTONE - 189, 190, 191, 329, 331, 335, 336, 338, 339, 340, 341, 350, 351, 352, 353, 354, 355, 356

TYPE 6P1 - 4 BEDRM - DEMOLITION ELEVATION

0 4000 8000

D2

TYP

GENERAL ELEVATION NOTES:

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT. IF

BUILDING NUMBERS ARE IMPACTED OR OBSCURED BY

CONSTRUCTION, THEY SHALL BE REPAINTED IN A LOCATION

APPROVED BY THE CONTRACTING OFFICER.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

KEYED NOTES:

HEAT PUMP UNIT TYPICAL PER MECH DWGS - SEE SITE PLANS AND

MECH DWGS FOR LOCATIONS AT EACH BUILDING - EXACT LOCATION

OF HEAT PUMP UNIT TO BE DETERMINED IN THE FIELD - SEE

MOUNTING DETAILS AE501

WALL-MOUNTED EMCS PANEL

EXIST ELECTRICAL PANEL

EXIST TV/COMM PANEL(S)

WALL-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING & CONTROL WIRING

ROOF CANOPY - WALL-MOUNTED METAL FRAME WITH METAL ROOF

- SEE DETAIL 1/AE501

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

DEMOLITION NOTES:

D1

DEMOLISH AND REMOVE EXIST EXTR FLUSH DR - REMOVE AND

STORE HARDWARE TO BE REINSTALLED ON REPLACEMENT DOOR -

PRESERVE IN PLACE FRAME, STORM DR (WO) AND SIDELITE (WO)

D2

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

EXTR ALUM FLUSH DR - FIELD VERIFY SIZE - REUSE EXIST

HARDWARE AND ACCESSORIES

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

EXTR SLIDING GLASS DR - DEMOLISH AND REPLACE SILL FLASHING

Y4

Y3

Y2

Y0

Y1

LIVING / DINING

EBS

FAMILY

RM

EBS

PORCH

S T

O

PATIO

PATIO

S T

A I R

BEDROOM 1

HALL

BEDROOM 2

C L O

BEDROOM 3 BEDROOM 4

C L O

C

L O

C

L O

C L O

C

L O

C L O

CLO.

KITCHEN

ENTRY

PORCH

ENTRY

BATH

BATH

LAUND.

D2

D2

D2 D2

D2

1 4

1 4

1 4

1 4

D2

752075207520 7520

30080

TYPICAL UNIT

1 4

SIM UNIT

D4

D4

X0 X1 X2 X3 X4

Y5

Y4

Y3

Y2

Y1

LIVING / DINING

FAMILY

RM

S T

O

S T

A I R

BEDROOM 1

HALL

BEDROOM 2

BEDROOM 3

BEDROOM 4

CLO.

KITCHEN

BATH

LAUND.

BATH

C L O

C L O

C L O

CLO.

CLO.

D2

D2D2

D2 D2 D2

1 4

4 5

752075207520 7520

30080

TYPICAL UNIT

1 4

1 42

SIM UNIT

D4D4

D4D4

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

GENERAL PLAN NOTES:

KEYED NOTES:

CEILING-MOUNTED HVAC UNIT - REPAIR DISTURBED INSULATION

ABOVE UNIT - ADD MATCHING INSULATION IF REQUIRED TO

MAINTAIN THERMAL PERFORMANCE - SEE MECH DWGS

DEMOLITION NOTES:

NOT APPLICABLE TO THIS DRAWINGD1

COORDINATE DEMOLITION AND REMOVAL OF EXIST

CEILING-MOUNTED HVAC UNIT BY MECH - SEE MECH DWGS

D2

NOT APPLICABLE TO THIS DRAWINGD3

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - PATCH AND REPAIR PER KEYNOTE 4

EXIST CEILING ACCESS PANEL TO REMAIN

NOT APPLICABLE TO THIS DRAWING6

0 2000 4000

TYPE 6A - 4 BEDROOM - FIRST FLOOR ADAPTABLE

6A-AE101

T Y

D

R O

M

C

E S

S I B

D A

P T

A B

L E

P L

A N

S

N

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

0 2000 4000

TYPE 6A - 4 BEDROOM - SECOND FLOOR STACKED

BUILDING LEGEND

BUILDING TYPE 6A CONSISTS OF THE FOLLOWING BUILDING:

BASE BID (1 BUILDING):

YELLOWSTONE - 357

PREFINISHED ALUM PIPE CHASE COVER - SEE DETAILS 11/AE502

AND 15/AE502

PATCH AND REPAIR ABANDONED OR MODIFIED CEILING OPENINGS

AND PENETRATIONS WITH SUSPENDED GYP BD CEILING TO MATCH

EXIST - REPAIR DISTURBED INSULATION ABOVE UNIT - ADD

MATCHING INSULATION IF REQUIRED TO MAINTAIN THERMAL

PERFORMANCE - PRIME AND PAINT - SEE DETAIL 25/AE501

D4

EXIST MECH REGISTER TO REMAIN8

NOT APPLICABLE TO THIS DRAWING7

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

5. PRIME AND PAINT NEW AND REPAIRED INTERIOR GYP BD PAINT

FINISH TO 300 BEYOND DISTURBANCE - COORDINATE COLOR AND

SHEEN TO MATCH BASE HOUSING STANDARD - SEE DETAIL

25/AE501

6. EXIST CONSTRUCTION CONTAINS HAZARDOUS MATERIALS

INCLUDING BUT NOT LIMITED TO GYP BD JOINT COMPOUND - REFER

TO HAZMAT DWGS AND SPECIFICATIONS

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

2 2

FRONT

TYPICAL STACKED UNIT ABOVE

TYPICAL ADAPTABLE UNIT BELOW

TYP

TYP

Y5 Y4 Y3 Y2 Y0Y1

LEFT

X0X1X2X3X4

3 3 3 3

TYPICAL STACKED UNIT ABOVE

TYPICAL ADAPTABLE UNIT BELOW

REAR

TYP

Y5Y4Y3Y2Y0 Y1

RIGHT

X0 X1 X2 X3 X4

TYPICAL STACKED UNIT ABOVE

TYPICAL ADAPTABLE UNIT BELOW

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

0 2000 4000

TYPE 6A - 4 BEDROOM - ELEVATIONS

6A-AE201

T Y

D

R O

C

E S

S I B

D A

P T

A B

L E

E L

E V

A T

I O

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

BUILDING LEGEND

BUILDING TYPE 6A CONSISTS OF THE FOLLOWING BUILDING:

BASE BID (1 BUILDING):

YELLOWSTONE - 357

GENERAL ELEVATION NOTES:

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT IF BUILDING

NUMBERS ARE IMPACTED OR OBSCURED BY CONSTRUCTION, THEY

SHALL BE REPAINTED IN A LOCATION APPROVED BY THE

CONTRACTING OFFICER.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

KEYED NOTES:

HEAT PUMP UNIT TYPICAL PER MECH DWGS - SEE SITE PLANS AND

MECH DWGS FOR LOCATIONS AT EACH BUILDING - EXACT LOCATION

OF HEAT PUMP UNIT TO BE DETERMINED IN THE FIELD - SEE

MOUNTING DETAILS AE501

WALL-MOUNTED EMCS PANEL

EXIST ELECTRICAL PANEL

EXIST TV/COMM PANEL(S)

WALL-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING & CONTROL WIRING

ROOF CANOPY - WALL-MOUNTED METAL FRAME WITH METAL ROOF

- SEE DETAIL 1/AE501

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

DEMOLITION NOTES:

D1

DEMOLISH AND REMOVE EXIST EXTR FLUSH DR - REMOVE AND

STORE HARDWARE TO BE REINSTALLED ON REPLACEMENT DOOR -

PRESERVE IN PLACE FRAME, STORM DR (WO) AND SIDELITE (WO)

D2

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

EXTR ALUM FLUSH DR - FIELD VERIFY SIZE - REUSE EXIST

HARDWARE AND ACCESSORIES

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

EXTR SLIDING GLASS DR - DEMOLISH AND REPLACE SILL FLASHING

PER 10/AE502

TYPE 6A - 4 BEDRM - DEMOLITION ELEVATION

0 4000 8000

D2

TYP

Y4

Y3

Y2

Y0 Y1

LIVING / DINING

PWD.

RM

FAMILY

RM

S T

A I R

EBS

EBS

KITCHEN

LAUND.

PATIO

VEST.

H A

L L

CLO.

S T

O

PORCH

C L O

D2 1

D2

75207520

30080

TYPICAL UNIT

SIM UNIT

D4

X2 X3 X4

Y5

Y4

Y3

Y2

Y0 Y1

S T

A I R

HALL

IBS

BEDROOM 1

BEDROOM 2

BEDROOM 3

C L O

C L O

C L O

CLO.

CLO.

CLO.

BATH

BATH

BEDROOM 4

D2

D2

D2 D2

D3

D3

75207520

30080

TYPICAL UNIT

SIM UNIT

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

GENERAL PLAN NOTES:

KEYED NOTES:

CEILING-MOUNTED HVAC UNIT - REPAIR DISTURBED INSULATION

ABOVE UNIT - ADD MATCHING INSULATION IF REQUIRED TO

MAINTAIN THERMAL PERFORMANCE - SEE MECH DWGS

PREFINISHED ALUM PIPE CHASE COVER - SEE DETAILS 11/AE502

AND 15/AE502

DEMOLITION NOTES:

NOT APPLICABLE TO THIS DRAWINGD1

COORDINATE DEMOLITION AND REMOVAL OF EXIST

CEILING-MOUNTED HVAC UNIT BY MECH - SEE MECH DWGS

D2

DEMOLISH AND REMOVE EXIST CEILING ACCESS PANELD3

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - PATCH AND REPAIR PER KEYNOTE 4

EXIST CEILING ACCESS PANEL TO REMAIN

PATCH AND REPAIR ABANDONED OR MODIFIED CEILING OPENINGS

AND PENETRATIONS WITH SUSPENDED GYP BD CEILING TO MATCH

EXIST - REPAIR DISTURBED INSULATION ABOVE UNIT - ADD

MATCHING INSULATION IF REQUIRED TO MAINTAIN THERMAL

PERFORMANCE - PRIME AND PAINT - SEE DETAIL 25/AE501

NOT APPLICABLE TO THIS DRAWING6

0 2000 4000

TYPE 7P2 - 4 BEDROOM - FIRST FLOOR

7P2-AE101

T Y

D

R O

O M

P L

A N

S

N

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

0 2000 4000

TYPE 7P2 - 4 BEDROOM - SECOND FLOOR

BUILDING LEGEND

BUILDING TYPE 7P2 CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (7 BUILDINGS):

CAPE COD - 717

YELLOWSTONE - 193, 194, 195, 196, 198, 719

D4

NOT APPLICABLE TO THIS DRAWING7

EXIST MECH REGISTER TO REMAIN8

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

5. PRIME AND PAINT NEW AND REPAIRED INTERIOR GYP BD PAINT

FINISH TO 300mm BEYOND DISTURBANCE - COORDINATE COLOR

AND SHEEN TO MATCH BASE HOUSING STANDARD - SEE DETAIL

25/AE501

6. EXIST CONSTRUCTION CONTAINS HAZARDOUS MATERIALS

INCLUDING BUT NOT LIMITED TO GYP BD JOINT COMPOUND - REFER

TO HAZMAT DWGS AND SPECIFICATIONS

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

TYP

TYPICAL UNIT

FRONT

Y4 Y3 Y2 Y1 Y0

LEFT

X0X1X2X3X4

TYP

TYPICAL UNIT

REAR

Y4Y3Y2Y1Y0

RIGHT

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

GENERAL ELEVATION NOTES:

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT IF BUILDING

NUMBERS ARE IMPACTED OR OBSCURED BY CONSTRUCTION, THEY

SHALL BE REPAINTED IN A LOCATION APPROVED BY THE

CONTRACTING OFFICER.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

KEYED NOTES:

HEAT PUMP UNIT TYPICAL PER MECH DWGS - SEE SITE PLANS AND

MECH DWGS FOR LOCATIONS AT EACH BUILDING - EXACT LOCATION

OF HEAT PUMP UNIT TO BE DETERMINED IN THE FIELD - SEE

MOUNTING DETAILS AE501

WALL-MOUNTED EMCS PANEL

EXIST ELECTRICAL PANEL

EXIST TV/COMM PANEL(S)

WALL-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING & CONTROL WIRING

ROOF CANOPY - WALL-MOUNTED METAL FRAME WITH METAL ROOF

- SEE DETAIL 1/AE501

SOFFIT-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING & CONTROL WIRING

0 2000 4000

TYPE 7P2 - 4 BEDROOM - ELEVATIONS

7P2-AE201

T Y

D

R O

O M

E L

E V

A T

I O

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

BUILDING LEGEND

BUILDING TYPE 7P2 CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (2 BUILDINGS):

CAPE COD - 717

YELLOWSTONE - 193, 194, 195, 196, 198, 719

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

EXTR SLIDING GLASS DR - DEMOLISH AND REPLACE SILL FLASHING

PER 10/AE502

Y4

Y3

Y2

Y0

Y1

LIVING / DINING

EBS

FAMILY

RM

EBS

PORCH

S T

O

PATIO

PATIO

S T

A I R

BEDROOM 1

HALL

BEDROOM 2

C L O

BEDROOM 3 BEDROOM 4

C L O

C

L O

C

L O

C L O

C

L O

C L O

CLO.

KITCHEN

ENTRY

PORCH

ENTRY

BATH

BATH

LAUND.

D2

D2

D2 D2

D2

1 4

1 4

1 4

1 4

D2

3 3

752075207520 7520

30080

TYPICAL UNIT

1 4 32

SIM UNIT

D4

D4

X0 X1 X2 X3 X4

Y5

Y4

Y3

Y2

Y1

LIVING / DINING

FAMILY

RM

S T

O

S T

A I R

BEDROOM 1

HALL

BEDROOM 2

BEDROOM 3

BEDROOM 4

CLO.

KITCHEN

BATH

LAUND.

BATH

C L O

C L O

C L O

CLO.

CLO.

D2 4

D2D2

D2 D2 D2 D4D4

D4 D4

D4

1 4

5 5

752075207520 7520

30080

TYPICAL UNIT

SIM UNIT

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

0 2000 4000

TYPE 7A - 4 BEDROOM - FIRST FLOOR ADAPTABLE

7A-AE101

T Y

D

R O

C

E S

S I B

D A

P T

A B

L E

P L

A N

S

N

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

0 2000 4000

TYPE 7A - 4 BEDROOM - SECOND FLOOR STACKED

BUILDING LEGEND

BUILDING TYPE 7A CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (1 BUILDING):

YELLOWSTONE - 197

GENERAL PLAN NOTES:

KEYED NOTES:

CEILING-MOUNTED HVAC UNIT - REPAIR DISTURBED INSULATION

ABOVE UNIT - ADD MATCHING INSULATION IF REQUIRED TO

MAINTAIN THERMAL PERFORMANCE - SEE MECH DWGS

DEMOLITION NOTES:

NOT APPLICABLE TO THIS DRAWINGD1

COORDINATE DEMOLITION AND REMOVAL OF EXIST

CEILING-MOUNTED HVAC UNIT BY MECH - SEE MECH DWGS

D2

NOT APPLICABLE TO THIS DRAWINGD3

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - PATCH AND REPAIR PER KEYNOTE 4

EXIST CEILING ACCESS PANEL TO REMAIN

PREFINISHED ALUM PIPE CHASE COVER - SEE DETAILS 11/AE502

AND 15/AE502

PATCH AND REPAIR ABANDONED OR MODIFIED CEILING OPENINGS

AND PENETRATIONS WITH SUSPENDED GYP BD CEILING TO MATCH

EXIST - REPAIR DISTURBED INSULATION ABOVE UNIT - ADD

MATCHING INSULATION IF REQUIRED TO MAINTAIN THERMAL

PERFORMANCE - PRIME AND PAINT - SEE DETAIL 25/AE501

D4

EXIST MECH REGISTER TO REMAIN8

NOT APPLICABLE TO THIS DRAWING7

NOT APPLICABLE TO THIS DRAWING

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

5. PRIME AND PAINT NEW AND REPAIRED INTERIOR GYP BD PAINT

FINISH TO 300 BEYOND DISTURBANCE - COORDINATE COLOR AND

SHEEN TO MATCH BASE HOUSING STANDARD - SEE DETAIL

25/AE501

6. EXIST CONSTRUCTION CONTAINS HAZARDOUS MATERIALS

INCLUDING BUT NOT LIMITED TO GYP BD JOINT COMPOUND - REFER

TO HAZMAT DWGS AND SPECIFICATIONS

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

TYP

TYPICAL STACKED UNIT ABOVE

TYPICAL ADAPTALBE UNIT BELOW

FRONT

X0 X1 X2 X3 X4

3 3

LEFT

Y5 Y4 Y3 Y2 Y0Y1

3 3 3 3

TYPREAR

TYPICAL STACKED UNIT ABOVE

TYPICAL ADAPTALBE UNIT BELOW

X0X1X2X3X4

RIGHT

Y5Y4Y3Y2Y0 Y1

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

0 2000 4000

TYPE 7A - 4 BEDROOM - ELEVATIONS

BUILDING LEGEND

BUILDING TYPE 7A CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (1 BUILDING):

YELLOWSTONE - 197

GENERAL ELEVATION NOTES:

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT. IF BUILDING

NUMBERS ARE IMPACTED OR OBSCURED BY CONSTRUCTION, THEY

SHALL BE REPAINTED IN A LOCATION APPROVED BY THE

CONTRACTING OFFICER.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

KEYED NOTES:

HEAT PUMP UNIT TYPICAL PER MECH DWGS - SEE SITE PLANS AND

MECH DWGS FOR LOCATIONS AT EACH BUILDING - EXACT LOCATION

OF HEAT PUMP UNIT TO BE DETERMINED IN THE FIELD - SEE

MOUNTING DETAILS AE501

WALL-MOUNTED EMCS PANEL

EXIST ELECTRICAL PANEL

EXIST TV/COMM PANEL(S)

WALL-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING & CONTROL WIRING

ROOF CANOPY - WALL-MOUNTED METAL FRAME WITH METAL ROOF

- SEE DETAIL 1/AE501

SOFFIT-MOUNTED PLASTIC DUCT FOR HVAC REFRIGERANT AND

CONDENSATE PIPING & CONTROL WIRING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

EXTR SLIDING GLASS DR - DEMOLISH AND REPLACE SILL FLASHING

PER 10/AE502

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

7A-AE201

T Y

D

R O

C

E S

S I B

D A

P T

A B

L E

E L

E V

A T

I O

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

A B

C D

W G

Y3

Y2

Y1

Y0

LIVING / DINING

EBS

BATH

FAMILY

RM

S T

A I R

EBS

EBS

EBS

EBS

EBS

KIT.

LAUND.

H A

L L

S T

O

C L

O

D2 D2

D2

72407240

28960

TYPICAL UNIT

80NO

WORK

THIS

AREA

NO

WORK

THIS

AREA

D4

SIM UNIT

X2 X3 X4

Y4

Y3

Y2

Y1

Y0

S T

A I R

HALL

BEDROOM 1

BEDROOM 2 BEDROOM 3

CLO.

CLO.

CLO.

CLO.

BATH

BATH

LAV

D2

D2

D2

72407240

28960

TYPICAL UNIT

NO WORK

THIS AREA

NO

WORK

THIS

AREA

NO WORK

THIS AREA

SIM UNIT

X0 X1 X2 X3 X4

Y4

Y3

Y2

Y1

Y0

30160

AE502

AE502

SHEET OF

SHEET

IDENTIFICATION

O N

E I D

A

T

O T

T E

G R

A T

T

E R

P R

I S

E S

M

A Y

F A

A

D

S

U I T

E

M I L

W A

U K

E E

W

I

F A

D

S O

L

B

N

U M

B

I S

O

A

D E

S I G

N E

D

B

Y

D W

N

B

Y

C K

D

B

Y

S O

L I C

I T

A T

I O

N

N

O

D A

T E

C O

N T

R A

D R

A W

I N

G

C

O D

E

I S

S U

E

D

A T

E

P L

A

L E

S U

B M

I T

T E

D

B

Y

F I L

E

N

A M

E

S I Z

E

P D

K

A

M I S

A W

A

A

S

E

A

B

C

D

1 2 3 4 5

M A

R K

D E

S C

R I P

T I O

N

D A

T E

A P

P R

SIGNED

THIS WORK WAS

PREPARED BY ME OR

UNDER MY SUPERVISION

FINAL DOCUMENTS

OF

U S

A

R

C E

C I V

G

I N

E E

R

S

Q U

A D

R O

N

A F

T I M

O T

W

E N

D T

KEY PLAN

MAIN BASE

GENERAL PLAN NOTES:

KEYED NOTES:

CEILING-MOUNTED HVAC UNIT - REPAIR DISTURBED INSULATION

ABOVE UNIT - ADD MATCHING INSULATION IF REQUIRED TO

MAINTAIN THERMAL PERFORMANCE - SEE MECH DWGS

PREFINISHED ALUM PIPE CHASE COVER - SEE DETAILS 11/AE501

AND 15/AE501

DEMOLITION NOTES:

D1

COORDINATE DEMOLITION AND REMOVAL OF EXIST

CEILING-MOUNTED HVAC UNIT BY MECH - SEE MECH DWGS

D2

DEMOLISH AND REMOVE EXIST CEILING ACCESS PANELD3

TEMPORARY CEILING OPENING FOR MECHANICAL SYSTEM

INSTALLATION - PATCH AND REPAIR PER KEYNOTE 4

EXIST CEILING ACCESS PANEL TO REMAIN

PATCH AND REPAIR ABANDONED OR MODIFIED CEILING OPENINGS

AND PENETRATIONS WITH SUSPENDED GYP BD CEILING TO MATCH

EXIST - REPAIR DISTURBED INSULATION ABOVE UNIT - ADD

MATCHING INSULATION IF REQUIRED TO MAINTAIN THERMAL

PERFORMANCE - PRIME AND PAINT - SEE DETAIL 25/AE501

0 2000 4000

TYPE 8N - 3 BEDROOM - FIRST FLOOR

8N-AE101

T Y

D

R O

O M

P L

A N

S

N

A

C

E

Q U

I P

M E

N T

J O

N

N

J D

V K

C

V A

R I E

S

0 2000 4000

TYPE 8N - 3 BEDROOM - SECOND FLOOR

BUILDING LEGEND

BUILDING TYPE 8N CONSISTS OF THE FOLLOWING BUILDINGS:

BASE BID (14 BUILDINGS):

RUSHMORE - 371, 374, 376

SEQUOIA - 201, 203, 205, 345, 346, 347, 348, 349, 360, 361, 365

EXIST MECH REGISTER TO REMAIN8

D4

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NOT APPLICABLE TO THIS DRAWING

NEW R-20 RIGID INSULATION, MECHANICALLY FASTENED

PROTECTION BOARD AND FLUID-APPLIED URETHANE ROOFING -

SEAL ATTIC VENT OPENINGS

TYPE 8N - 3 BEDROOM - ROOF PLAN

0 4000 8000

1. CONTRACTOR TO PROTECT IN PLACE EXISTING FINISHES,

MATERIALS AND AMENITIES TO REMAIN.

2. CONTRACTOR TO REPAIR ANY DAMAGE TO EXISTING TO REMAIN

ITEMS AT NO COST TO THE GOVERNMENT.

3. PROVIDE NEW FACTORY FINISH OR FINISH TO MATCH ADJACENT

CONSTRUCTION FOR ALL NEW CONSTRUCTION. REPAINT AND/OR

REFINISH EXISTING CONSTRUCTION WHICH IS PATCHED, REPAIRED

OR DISTURBED INCLUDING INTERIOR AND EXTERIOR FINISHES

EXPOSED TO VIEW AT NO COST TO THE GOVERNMENT.

4. UNIT INFORMATION, DIMENSIONS AND NOTES ARE SYMMETRICAL

ABOUT GRIDLINES AND SCOPE APPLIES TO ALL UNITS.

5. PRIME AND PAINT NEW AND REPAIRED INTERIOR GYP BD PAINT

FINISH TO 300mm BEYOND DISTURBANCE - COORDINATE COLOR

AND SHEEN TO MATCH BASE HOUSING…