Drawings 589A4-20-158 VOL 1- 90 pages.pdf
PDF 18 MB Posted
- Solicitation number
- 36C25521R0075
About this file
This solicitation package outlines requirements for a renovation project to upgrade an existing warehouse facility for pandemic preparedness purposes. The scope of work involves raising approximately 6,000 square feet of roof, adding 3,800 square feet of mezzanine storage space, and renovating interior spaces. Architectural, structural, fire protection, mechanical, plumbing, electrical, and technology upgrades are specified. The estimated price range for the project is $2,000,000 to $5,000,000. Pursuant to applicable public law, this project will be solicited as a total small business set-aside for Service-Disabled Veteran-Owned Small Businesses. Interested offerors should monitor the System for Award Management for solicitation release on or about April 2, 2021, with proposals due on or about May 7, 2021. An organized site visit will be scheduled upon solicitation issuance.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Incandescence Life Safety, Inc.
3575 Ringsby Court, #408, Denver, CO, 80216
Phone:(720) 722-3010
589A4-20-158
IMEG Corp.
15 Sunnen Drive, Suite 104
St. Louis, MO 63143
Phone:(314) 951-2534
BID SET RENOVATE WAREHOUSE FOR
PANDEMIC PREPAREDNESS
HARRY S. TRUMAN MEM. VETERANS HOSPITAL
800 HOSPITAL DR., COLUMBIA MO 65201
BID SET 03/24/2021
Dwg. # of 94
C
L H
D C
\H o m e
\t fi e s e lm a n \R e v it M o d e ls \R
-2
-2
A
-2
-1
R e n o v a te W a re h o u s e tf ie s e lm a n A
G
Y .r v t
/2
/2
:4
:0
A
M
G-001
COVER SHEET
AHT TJF03/24/2021
VA Project No. 589A4-20-158
Harry S. Truman Memorial Veterans' Hospital
R E
N O
V A
T E
W A
R E
H O
U S
E F
O R
P A
N D
E M
IC
P
R E
P A
R E
D N
E S
S
C
D S
U B
M
IT
T A
L (R
E V
IS
E
D
3/
/2
RENOVATE WAREHOUSE FOR PANDEMIC PREPAREDNESS
800 Hospital Drive Columbia, MO 65201
BLDG. 14 -
WAREHOUSE
LOCATION MAP/PHOTO
NOT TO SCALE
INTEGRATED PROJECT TEAM APPROVAL SIGNATURES
Director Date
Assistant Director
Date
Associate Director Date
Chief of Staff
Date
Associate Director of Patient Services Date
Executive of High Reliability Date
Chief of Logistics Date
Infection Control Date
Safety Officer Date
BLDG. 1 -
HOSPITAL
PARKING
GARAGE 'A'
OR - SPS ADDITION
BLDG. 23 -
CHILLER
PLANT
STAFF/
CONTR
ENTRANCE
HOSPITAL
EAST
ENTRANCE
SOUTH STAFF PARKING
LOT 'D'
ACCESSIBLE PARKING
LOT 'B'
NORTH WEST PARKING
LOT 'C'
ACA BUILDING
ACA BLDG PORTE COCHERE
ORIGINAL HOSPITAL
BLDG. 22 -
FACILITIES
MANAGEMENT
PARKING GARAGE ADD'N
NORTH EMERGENCY
ROOM ENTRANCE
EMERGENCY
ROOM
PATIENT
EDUCATION
CENTER
HOSPITAL NORTH ENTRANCE
BLDG. 16 -
GENERAL
STORAGE
HOSPITAL MAIN ENTRACE
WEST
EMERGENCY
ROOM
ENTRANCE
BLDG. 24 -
UPS
WAREHOUSE
BLDG. 14 -
WAREHOUSE
LOADING DOCK
UNIV OF MISSOURI MEDICAL CENTER CAMPUS
UNIV OF MISSOURI
CAMPUS
E. STADIUM DRIVE
HOSPITAL DRIVE
M O
N K
D R
IV
E
T
IG
E R
A V
E N
U E
D E
A N
S ' D
R
IV
E
Chief Facilities Management Date
1Revisions: Date:
ABBREVIATIONS
DET, DTL
DIAMETER
DIMENSION
DAMPER
DOWN
DISTRIBUTION PANEL
DOWNSPOUT, STORM DRAINAGE
STRUCTURE
DOMESTIC WATER
DRAWING
EACH
EACH FACE, EXHAUST FAN
EXHAUST GRILLE
ELEVATION
ELECTRIC, ELECTRICAL CLOSET
EMER
EQ
EQUIP
EACH WAY
ELECTRIC WATER COOLER
EXH
EXIST
EXP
EXPANSION JOINT
EXPANSION JOINT
HEIGHT, HUMIDIFIER
HB
HANDICAPPED
HDW
HORIZ
HR
NA
NEC
NEUT
NIC
NOM
NTS
OA
OC
OD
OPNG
OPP
OH, OVHD
FRAME
FTG
T
T&B
TEL
TEMP
TERM
3/C
3/P
3 WAY
TO
TRANS
TS
TV
TW
TYP
WA
UH
V
VA
VAC
VCT
VENT
VERT
VEST
VS
VTR
VWC
W
W
W/
W/O
WC
WD
WP
WS
WT
WWF
SG
SAN
SCH
SD
SECT
SH
1 PH
SL
SP
SPDT
SPEC
SPST
SQ
SR
SS
ST
STA
STD
STL
SUP
SUSP
SV
SW
SWBD
SWGR
SIM
M
MAS
MATL
MAX
MECH
MET/MTL
MH
MIN
MISC
MM
MTD
MTG
MWP
MULL
KO
KVA
KW
L
LT
LAV
INT
INSUL
INV
JB
JC
JCT
JT
FXTR
GA
GALV
GFI, GFCI
GL
GWB
GYP
C
C
CAPACITY
CENTER TO CENTER
CEILING DIFFUSER
CEM
CAST IRON, COURTYARD INLET
CHILLER
CAST IRON PIPE
CIRCULATING
CONTROL JOINT
CIRCUIT
CENTERLINE
CEILING
CLEAR
CORRUGATED METAL PIPE
CORRUGATED METAL PIPE ARCH
CONCRETE MASONRY UNITS
CONDENSATE
CLEANOUT
COLUMN
COMMUNICATION
CONCRETE
CONDUCTOR
CONNECTION
CONSTRUCTION
CONTINUOUS
CONVERTER
NONREINFORCED CONCRETE PIPE
CONDUIT
CERAMIC TILE, CURRENT TRANSFORMER,
COOLING TOWER
CENTER, COOLING TOWER RETURN
COOLING TOWER SUPPLY
COLD WATER
CARPET
CONCRETE SEALER/SURFACE
BOARD
BUILDING
BLK
BEAM
BOTTOM
BEARING
BASEMENT
ACOUSTIC
ADJUSTABLE
ABOVE FINISHED FLOOR
ALTERNATE
AIR HANDLING UNIT
ANCHOR BOLT, AUGER BORING
AL
APPROXIMATE
ARCH
AUTOMATIC TRANSFER SWITCH
FA
FLOOR DRAIN, FIRE DAMPER
FOUNDATION
FEEDER
FIRE EXTINGUISHER
FINISHED FLOOR ELEVATION
FIG
FIN
FLOOR, FLASHING, FLOW LINE
FLUOR
P
PB
PIV
PL
PLYWD
PNL
PNT
CHAIR OR CRASH RAIL
CORNER GUARD
FIRE EXTINGUISHER CABINET
OF
WG
ALC
CUBICAL CURTAIN TRACK
CLEAN
ACOUSTIC TILE
L
EPDM ROOF MEMBRANE
HSKP
NEG
STRUC
R
RA
RAD
RB
RES
RECP
REINF
REG
REQD
REV
RF
RHC
RM
RPM
RWC
PRELIM
PRIM
PT
PTN
PVMT
PVC
PVC
AB
ACT
ACST
ADJ
AFF
AHU
ALT
ALUMINUM
ALCOVE
APPROX
ARCHITECTURAL
ATS
BD
BLDG
BLOCK
BM
BOT
BRG
BSMT
CELSIUS
CAP
CC
CD
CCT
CEMENT
CG
CH
CI
CIP
CIR
CJ
CKT
CLN
CLG
CLR
CMP
CMPA
CMU
CND,C
CNDS
CO
COL
COMM
CONC
COND
CONN
CONST
CONT
CONV
CP
CR
CS
CT
CT
CTR
CTS
CW
CPT
DETAIL
DIA
DIM
DMPR
DN
DP
DS
DW
DWG
EA
EF
EG
EJ
ELEV
ELEC
EMERGENCY
EPDM
EQUAL
EQUIPMENT
EW
EWC
EXHAUST
EXISTING
EXPANSION, EXPOSED
EXP JT
FIRE ALARM
FD
FDN
FDR
FE
FEC
FFE
FIGURE
FINISH
FL
FLUORESCENT
FRAME
FOOTING
FIXTURE
GAGE
GALVANIZED
GROUND FAULT INTERRUPT
GLASS
GYPSUM WALL BOARD
GYPSUM
HGT, H
HOSE BIBB
HC
HARDWARE
HORIZONTAL
HOUR, HAND RAIL
HOUSEKEEPING
INTERIOR
INSULATION, INSULATED
INVERT
JUNCTION BOX
JANITOR CLOSET
JUNCTION
JOINT
KNOCK OUT
KILOVOLT-AMPERE
KILOWATT
LOUVER, LENGTH, LENGTH OF CURVE
LIGHT
LAVATORY VERTICAL
METER, MEGA
MASONRY
MATERIAL
MAXIMUM
MECHANICAL
METAL
MANHOLE
MINIMUM, MINUTE
MISCELLANEOUS
MILLIMETER
MOUNTED
MOUNTING
MEMBRANE WATERPROOFING
MULLION
NOT APPLICABLE
NATIONAL ELECTRIC CODE
NEGATIVE
NEUTRAL
NOT IN CONTRACT
NOMINAL
NOT TO SCALE
OUTSIDE AIR
ON CENTER
OUTSIDE DIAMETER
OVERFLOW DRAIN
OPENING
OPPOSITE
PIPE, POLE
OVERHEAD
PULL BOX
POST INDICATOR VALVE
PLATE
PLYWOOD
PANEL
PAINT
PRELIMINARY
PRIMARY
POINT, POINT OF TANGENT
PARTITION
POINT OF VERTICAL CURVE
POLY VINYL CHLORIDE
PAVEMENT
RADIUS, RISER, RUBBER SHEATH
RETURN AIR
RADIUS
RESILIENT/RUBBER BASE
RCP
RECEPTACLE
REINFORCEMENT
REGULATOR, REGISTER
REQUIRED
REVISION
ROOF, RETURN FAN
REHEAT COIL
ROOM
REVOLUTIONS PER MINUTE
RESILIENT WALL COVERING
SANITARY SEWER
SCHEDULE
SPLITTER DAMPER, STORM DRAIN
SECTION
SUPPLY GRILLE
SHEET
SIMILAR
SINGLE PHASE
SLOPE
STATIC PRESSURE, SINGLE POLE
SINGLE POLE, DOUBLE THROW
SPECIFICATION
SINGLE POLE, SINGLE THROW
SQUARE
SUPPLY REGISTER
SANITARY SEWER
STEAM, SINGLE THROW, STREET, STAFF
STATION
STANDARD
STEEL
STRUCTURAL
SUPPORT
SUSPENDED
SHEET VINYL
SWITCH, SIDEWALK
SWITCHBOARD
SWITCHGEAR
TILE,TOP,TANGENT
TOP AND BOTTOM
TELEPHONE
TEMPERATURE, TEMPORARY
TERMINAL
THREE CONDUCTOR
THREE POLE
THREE WAY
TOP OF
TRANSITION
TOP OF STEEL, TOP OF STONE, TOP OF SLAB
TELEVISION
TOP OF WALL
TYPICAL
UNIT HEATER
VENT,VOLT,VALVE
VOLT AMPRE
VACUUM
VINYL COMPOSITION TILE
VENTILATING
VERTICAL
VESTIBULE
VENT STACK
VENT THRU ROOF
VINYL WALL COVERING
WIDTH,WASTE,WATER,WATT,WEST, WIRE,
WATER LINE STRUCTURE
WATT
WITH
WITHOUT
WATER CLOSET, WHEEL CHAIR
WIDTH, WINDOW DIMENSION
WALL GUARD
WATERPROOF, WEATHERPROOF
WASTE STACK, WATER SURFACE, WATERSTOP
WEIGHT
WELDED WIRE FABRIC
TA TOILET ACCESSORIES
WDW WINDOW
IR IMPACT RESISTANT, INFRARED
PEMB PRE-ENGINEERED METAL BUILDING
RESINOUS EPOXY SYSTEM
RIGID CONCRETE PIPE
IRWC IMPACT RESISTANT WALL COVERING
LVT LUXURY VINYL TILE
WRB WEATHER RESISTANT BARRIER
SC SEALED CONCRETE
ARCHITECTURAL
SYMBOLS
A101
DETAIL NUMBER
COLUMN NUMBER /
GRID LINE
SHEET NUMBER
ARCHITECTURAL
SECTION
WINDOW TYPE
1 Ref
R e f
1 Ref
R e f
ARCHITECTURAL
ELEVATION
X
X-XXX
DETAIL NUMBER
SHEET NUMBER
CENTER LINE
DIMENSION LINE
DOOR NUMBER
SYMBOL
x'- x"
EXISTING TO REMAIN
NEW CONSTRUCTION
EXISTING TO BE
REMOVED
EXISTING TO REMAIN
1i
KEYNOTE - RENOVATION
PLAN (U.N.O.)
WALL / PARTITION TYPE
KEYNOTE - DEMOLITION
PLAN
X
X
X
NOTE: NOT ALL SYMBOLS USED
ROOM NAME
W01
ROOM NAME
ROOM NUMBER
XX
X-XXX
SHEET DETAIL IS
DRAWN ON
DETAIL NUMBER
XX
X-XXX ARCHITECTURAL
ELEVATION - EXTERIOR
XX SP XX SP DESIGN SF
PROGRAM SF
ACT-X
X'-X" AFF
CEILING CODE
CEILING HEIGHT,
ABOVE FINISH FLOOR
X
NEW EXISTING
KEYNOTE - PHASING
PLAN
X
MATERIAL SYMBOLS
EARTH
CAST-IN-PLACE CONCRETE /
PRECAST CONCRETE
CONCRETE MASONRY
STEEL
CONTINUOUS WOOD
FRAMING
WOOD BLOCKING
FIBROUS INSULATION
GYPSUM BOARD
BRICK MASONRY
RIGID INSULATION
ROOF INSULATION
ALUMINUM
1. CONTRACTOR SHALL COMPLY WITH THE MOST-
CURRENT VERSION OF OSHA'S PUBLICATION
3142-12R "LEAD IN CONSTRUCTION" (29 CFR
1926.62) FOR CONSTRUCTION ACTIVITIES THAT
DISTURB LEAD-BASED PAINTED SURFACES, PAINT
CONTAINING DETECTABLE LEVELS OF LEAD OR
OTHER MATERIALS CONTAINING LEAD..
2. CONTACT THE COR TO OBTAIN MOST-CURRENT
COPIES OF ASBESTOS AND LEAD BASED PAINT
(LBP) REPORTS.
3. HAZARDOUS MATERIALS DISCLOSED IN THE ACM
AND LBP REPORTS MAY NOT BE A FULL
ACCOUNTING OF SUCH MATERIALS IN THE AREA
OF THE FACILITY IN QUESTION. REFER TO THE
VA'S ABATEMENT SPECIFICATIONS FOR HANDLING
OF MATERIALS THAT WERE NOT DIRECTLY
OBSERVED, BUT SHOULD BE EXPECTED BY THE
ABATEMENT CONTRACTOR.
4. CONTRACTOR TO VERIFY THE ABSENCE OF
ASBESTOS CONTAINING MATERIALS (ACM) PRIOR
TO ANY DEMOLITION.
5. IF THE CONTRACTOR ENCOUNTERS MATERIAL
THAT COULD BE HAZARDOUS, THE CONTRACTOR
SHALL STOP WORK AND NOTIFY THE GOVT.
IMMEDIATELY FOR DIRECTION.
6. ALL CONTRACTORS' PERSONNEL IN AREAS NEAR
DISTURBANCE OR ABATEMENT OF HAZARDOUS
MATERIALS MUST BE NOTIFIED OF ACTIVITIES.
7. ASBESTOS AND LEAD-BASED PAINT ABATEMENT,
IF REQUIRED, SHALL BE CONDUCTED IN
ACCORDANCE WITH VA SPECIFICATIONS AND ALL
APPLICABLE REGULATIONS.
8. ABATEMENT CONTRACTORS SHALL SCHEDULE
WORK IN GENERAL ACCORDANCE WITH THE
PROJECT'S PHASING STRATEGY.
1. MAINTAIN FIRE RATED CONSTRUCTION AT WALL
PENETRATIONS - CONSTRUCTION IS TO
CONFORM TO MANUFACTURER'S FIRE RATED /
TEST ASSEMBLIES.
2. FIRE CAULK ALL SLEEVES AND PENETRATIONS
AT FIRE WALLS / PARTITIONS AND FLOORS.
CONFORM WITH THE TESTED / SUBMITTED FIRE
RATED ASSEMBLY. USE RED FIRE CAULK AND
LABEL WALL WITH U.L. DESIGN NUMBER. FIRE
RATED WALLS SHOWN ON PLAN.
3. PATCH AND REPAIR ALL EXISTING FIREPROOFING
ON EXISTING STRUCTURAL MEMBERS,
INCLUDING THAT WHICH IS UNCOVERED
NEEDING REPAIR AND THAT WHICH IS
DISTURBED DURING CONSTRUCTION.
4. PATCH AND REPAIR ALL EXISTING FIRE CAULKING
AT EXISTING RATED WALLS WHICH IS
UNCOVERED NEEDING REPAIR AND THAT WHICH
IS DISTURBED DURING CONSTRUCTION. RE-
LABEL EXISTING WALL IF NECESSARY.
HAZARDOUS MAT'LS:
FIRE PROOFING
GENERAL NOTES:
ARCHITECTURAL GENERAL NOTES:
1. ALL NEW CONSTRUCTION IS INDICATED BOLD OR FULL TONE.
2. ALL EXISTING CONSTRUCTION, CABINETWORK, EQUIPMENT, ETC. TO
REMAIN IS INDICATED LIGHT OR HALF TONE.
3. ALL INTERIOR WALLS WILL BE TYPE "A" CONSTRUCTION UNLESS
OTHERWISE INDICATED. REFER TO SHEET G-003 FOR WALL TYPES.
4. ALL METAL STUD AND GYPSUM WALLBOARD PARTITIONS ARE
DIMENSIONED TO THE OUTSIDE FACE AND TO COLUMN GRID
UNLESS OTHERWISE NOTED.
5. WHEN WALL PARTITIONS OF DIFFERENT FIRE RATING INTERSECT,
THE HIGHEST RATED PARTITION TAKES PRECEDENT. MAINTAIN
RATING BEHIND FIRE EXTINGUISHER CABINETS, ETC.
6. REFER TO SHEET AF501 FOR FIRE EXTINGUISHER CABINET DETAILS.
7. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS
PRIOR TO CONSTRUCTION.
8. ALL FURNITURE SHOWN HALF TONE WILL BE OWNER FURNISHED
AND OWNER INSTALLED.
9. REFER TO SHEET AE401 FOR LARGE SCALE PLANS AND TOILET
ACCESSORIES. (TA) ALSO, REFER TO SPECIFICATION SECTION
102800 FOR ADDITIONAL TA LOCATIONS AND MOUNTING HEIGHTS.
10. REFER TO SHEET G-003 FOR TYPICAL BACKING DETAIL WITHIN
FRAMED INTERIOR WALL PARTITIONS FOR WALL-MOUNTED ITEMS
SUCH AS HANDRAILS, CORNER GUARDS ETC.
11. ALL EXISTING TO REMAIN CEILING AND WALL GRILLES, DIFFUSERS
AND LIGHTS ETC. TO BE CLEANED.
12. VERIFY THAT THE EXISTING WALLS REQUIRING FIRE RATING ARE
MAINTAINED, REPAIRED AND EXTENDED TO STRUCTURE.
13. ALL CORRIDOR WALLS ARE REQUIRED TO BE SMOKE TIGHT,
WHETHER THEY ARE FIRE RATED OR NOT. REPAIR AND EXTEND AT
LEAST THE CORRIDOR SIDE OF NON-FIRE RATED CORRIDOR WALLS
TO STRUCTURE, UNLESS NOTED OTHERWISE NOTED. SEE WALL
TYPES SHEET.
14. REFER TO LIFE SAFETY PLANS FOR LOCATION OF REQUIRED FIRE
WALLS.
15. REFER TO SHEET G-003, ALONG WITH SPECIFICATION SECTIONS
092216 & 092900 FOR GYPSUM BOARD CONTROL/EXPANSION JOINT
ASSEMBLIES. PROVIDE FIRE RATED EXPANSION JOINTS IN RATED
FIRE RATED WALLS, REFER TO LIFE SAFETY (LS-) SERIES SHEETS
FOR FIRE RATINGS.
16. REFER TO 'TEMPORARY CONSTRUCTION BARRIERS AND
ENCLOSURE NOTES' FOR INFORMATION RELATED TO EXTERIOR
ENCLOSURE AND PROTECTION OF EXISTING AND NEW
CONSTRUCTION.
ARCHITECTURAL
GENERAL NOTES:
BID ITEMS & DEDUCT ALTS:
REFER TO SECTION 01 00 00 FOR STATEMENT OF BID ITEMS
A. BID ITEM #1, GENERAL CONSTRUCTION: BASE BID: Renovate Warehouse for Pandemic Preparedness: Includes all scope communicated in the drawings and specifications.
1. Work includes general construction, alterations, walks, grading, drainage, necessary removal of existing structures and construction of certain other items.
B. BID ITEM #2, Renovate Warehouse for Pandemic Preparedness:
Includes all scope described in Bid Item #1 – excluding Bid Deduct #1 described below:
1. Work associated with new Material Lift WE01.
2. Work associated with construction and finishes for new
Rooms W08 and W09 (Demolition of existing Rooms W07, W08 and W09, including plumbing, fixtures and finishes in Room W08 will be retained in Base Bid);
3. Work associated with installation of new ceilings and f inishes in Rooms W04, W05A and W06;
4. Demolition and renovation of work counters at Rooms W10A and W10C.
BID ITEMS & DEDUCT
ALTERNATES:
TEMP BARRIERS-ENCLOSURE NOTES:
1. SEE SPECIFICATION SECTION 01 56 00 "TEMPORARY BARRIERS &
ENCLOSURES" FOR REQUIREMENTS RELATED TO ENCLOSURE OF
CONSTRUCTION IN PROGRESS.
2. SEE PH-SERIES SHEETS / PHASING PLANS FOR NOTES AND
INFORMATION RELATED TO TEMPORARY INTERIOR
CONSTRUCTION PARTITIONS AND OVERHEAD PROTECTION
DURING CONSTRUCTION.
3. SEE RA-SERIES SHEETS FOR EXISTING CONDITIONS DRAWINGS
AND PHOTOS.
4. ALL ENCLOSURES AND PENETRATIONS THROUGH EXISTING
STRUCTURE ARE TO BE MAINTAINED BY THE CONTRACTOR
DURING DEMOLITION AND NEW CONSTRUCTION TO PREVENT THE
INFILTRATION OF WATER INTO THE BUILDING DURING THE
COURSE OF THE PROJECT.
5. EXTERIOR WALL ENCLOSURES SHALL BE ERECTED PRIOR TO THE
START OF DEMOLITION OF THE EXISTING ROOF. ENCLOSURES
SHALL BE REMOVED AS NEEDED TO ALLOW FOR ROOFING
DEMOLITION AND REPLACED BEFORE THE END OF EACH WORK
DAY.
6. EXISTING CONSTRUCTION TO REMAIN SHALL BE PROTECTED
FROM DEMOLITION AND NEW CONSTRUCTION ACTIVITY.
PROTECTION METHODS SHALL BE APPROVED BY THE COR AT
LEAST ONE WEEK PRIOR TO INITIAL INSTALLATION.
7. ALL ENCLOSURES MUST BE INSPECTED AND APPROVED BY THE
COR BEFORE THE END OF EACH WORK DAY. UNSATISFACTORY
ENCLOSURE WORK SHALL BE CORRECTED BY THE CONTRACTOR
AND APPROVED BY THE COR BEFORE CESSATION OF THE DAY'S
WORK ACTIVITY.
TEMPORARY
BARRIERS &
ENCLOSURES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Incandescence Life Safety, Inc.
3575 Ringsby Court, #408, Denver, CO, 80216
Phone:(720) 722-3010
589A4-20-158
IMEG Corp.
15 Sunnen Drive, Suite 104
St. Louis, MO 63143
Phone:(314) 951-2534
BID SET RENOVATE WAREHOUSE FOR
PANDEMIC PREPAREDNESS
HARRY S. TRUMAN MEM. VETERANS HOSPITAL
800 HOSPITAL DR., COLUMBIA MO 65201
BID SET 03/24/2021
Dwg. # of 94
C
L H
D C
\H o m e
\t fi e s e lm a n \R e v it M o d e ls \R
-2
-2
A
-2
-1
R e n o v a te W a re h o u s e tf ie s e lm a n A
G
Y .r v t
/2
/2
:4
:0
A
M
G-002
ABBREVIATIONS, SYMBOLS, GENERAL
NOTES & INDEX OF DRAWING
AHT TJF03/24/2021
Index of Drawings - Architectural
SHEET
NO. SHEET NAME
AS101 ARCHITECTURAL SITE PLAN
AD101 FLOOR PLAN - DEMOLITION
AD102 ROOF PLAN - DEMOLITION
AE101 FLOOR PLAN - RENOVATION
AE102 MEZZANINE LEVEL PLAN - RENOVATION
AE103 ROOF PLAN - RENOVATION
AE201 EXTERIOR ELEVATIONS
AE301 BUILDING SECTIONS
AE302 BUILDING SECTIONS
AE303 BUILDING SECTIONS
AE310 WALL SECTIONS
AE311 WALL SECTIONS
AE401 LARGE SCALE PLANS & DETAILS
AE501 EXTERIOR DETAILS
AE502 INTERIOR STAIR & MATERIAL LIFT PLANS, SECTIONS & DETAILS
AE503 EXTERIOR STAIR PLANS, SECTIONS & DETAILS
AE504 MATERIAL LIFT ELEVATIONS, SECTIONS & DETAILS
AE601 ROOM FINISH SCHEDULE & COLOR SCHEDULE
AE701 DOOR & WINDOW SCHEDULE & DETAILS
AE901 INTERIOR ELEVATIONS
AE902 INTERIOR ELEVATIONS
AE903 INTERIOR ELEVATIONS
AE904 INTERIOR ELEVATIONS
AE905 INTERIOR ELEVATIONS
AC101 FIRST FLOOR REFLECTED CEILING PLAN
AC102 RCP & MEZZ CEILING DETAILS
AF101 FIRST FLOOR FINISH & SIGNAGE PLAN
AF102 MEZZANINE FINISH & SIGNAGE PLAN
AF501 INTERIOR FINISH DETAILS
AF502 SIGNAGE SCHEDULE & DETAILS
Index of Drawings - General
SHEET
NO. SHEET NAME
G-001 COVER SHEET
G-002 ABBREVIATIONS, SYMBOLS, GENERAL NOTES & INDEX OF DRAWING
G-003 WALL TYPES & DETAILS
G-004 ACCESSIBILITY CLEARANCES
V-100 EXISTING SITE SURVEY
LS001 BUILDING AND LIFE SAFETY CODE ANALYSIS
PH101 PHASING PLAN - PHASE 1
PH102 PHASING PLAN - PHASE 2
PH103 PHASING PLAN - PHASE 3
Index of Drawings - Resource
SHEET
NO. SHEET NAME
RA101 EXISTING CONDITIONS PLAN & EXTERIOR PHOTOS
RA102 EXISTING CONDITIONS PLAN & INT. PHOTOS - WEST WAREHOUSE
RA103 EXISTING CONDITIONS PLAN & INT. PHOTOS - NORTH-EAST ROOMS
RA104 EXISTING CONDITIONS PLAN, EXT. & INT. PHOTOS - CORRS. & OPEN
AREA
Index of Drawings - Structural
SHEET
NO. SHEET NAME
S-001 GENERAL NOTES - STRUCTURAL
S-002 GENERAL NOTES, ABBREVIATIONS - STRUCTURAL
S-101 FOUNDATION PLAN
S-201 SECOND FLOOR FRAMING PLAN
S-202 ROOF FRAMING PLAN
S-301 FOUNDATION SECTIONS AND DETAILS
S-302 FOUNDATION SECTIONS AND DETAILS
S-501 FRAMING SECTIONS AND DETAILS
S-502 FRAMING SECTIONS AND DETAILS
S-503 FRAMING SECTIONS AND DETAILS
Index of Drawings - Plumbing
SHEET
NO. SHEET NAME
P-000 PLUMBING COVERSHEET
PD101 FIRST FLOOR PLAN - PLUMBING DEMOLITION
P-100 UNDER FLOOR PLAN - PLUMBING
P-101 FIRST FLOOR PLAN - PLUMBING
P-102 MEZZANINE FLOOR PLAN - PLUMBING
P-300 PLUMBING DETAILS
Index of Drawings - Mechanical
SHEET
NO. SHEET NAME
M-000 MECHANICAL COVERSHEET
MD101 FIRST FLOOR PLAN - MECHANICAL DEMOLITION
MD102 ROOF PLAN - MECHANICAL DEMOLITION
M-100 BASEMENT PLAN - MECHANICAL
M-101 FIRST FLOOR PLAN - MECHANICAL
M-102 MEZZANINE FLOOR PLAN - MECHANICAL
M-300 MECHANICAL DETAILS
M-301 MECHANICAL DETAILS
M-302 MECHANICAL DETAILS
M-400 MECHANICAL DIAGRAMS
M-401 MECHANICAL DIAGRAMS
M-402 MECHANICAL DIAGRAMS
M-500 MECHANICAL SCHEDULES
M-501 MECHANICAL SCHEDULES
Index of Drawings - Electrical
SHEET
NO. SHEET NAME
E-000 ELECTRICAL COVERSHEET
E-110 CHILLER PLANT PLAN - ELECTRICAL
E-111 BASEMENT BUILDING 1 PLAN - ELECTRICAL
ED101 FIRST FLOOR PLAN - ELECTRICAL DEMOLITION
EL101 FIRST FLOOR PLAN - ELECTRICAL LIGHTING
EL102 MEZZANINE FLOOR PLAN - ELECTRICAL LIGHTING
EP101 FIRST FLOOR PLAN - ELECTRICAL POWER
EP102 MEZZANINE FLOOR PLAN - ELECTRICAL POWER
E-300 ELECTRICAL DETAILS
E-400 ELECTRICAL DIAGRAMS AND SCHEDULES
E-500 ELECTRICAL SCHEDULES
Index of Drawings - Technology
SHEET
NO. SHEET NAME
T-000 TECHNOLOGY COVERSHEET
TD101 FIRST FLOOR PLAN - TECHNOLOGY DEMOLITION
T-101 FIRST FLOOR PLAN - TECHNOLOGY
T-102 MEZZANINE FLOOR PLAN - TECHNOLOGY
T-300 TECHNOLOGY DETAILS
T-400 TECHNOLOGY DIAGRAMS
T-500 TECHNOLOGY SCHEDULES
Index of Drawings - Fire Protection
SHEET
NO. SHEET NAME
FA101 FIRE ALARM SYSTEM PLAN
FX101 FIRE SUPPRESSION SYSTEM PLAN
2Revisions: Date:
A
STRUCTURE ABOVE
FIRE RATED SEALANT,
EA. SIDE, T&B
HEAD SLIP
CONNECTOR
FINISHED CEILING
ACOUSTIC BATTS
3 5/8" METAL STUDS
@ (16" O.C.)
1 LAYER 5/8" GWB
EA. SIDE
PAF (.145)
@ (32" O.C.)
TRACK - T&B
F2A
STRUCTURE
ABOVE
1 LAYER IMPACT-
RESISTANT 5/8"
GWB
F
STRUCTURE ABOVE
HEAD SLIP
CONNECTOR
FINISHED CEILING
(WHERE SCHEDULED)
ACOUSTIC BATTS
3 5/8" METAL STUDS
@ (16" O.C.)
1 LAYER
5/8" GWB
PAF (.145)
@ (32" O.C.)
TRACK - T&B
F1
STRUCTURE
ABOVE
FINISHED CEILING
(WHERE SCHEDULED)
1 LAYER
5/8" GWB
B
STRUCTURE ABOVE
FIRE RATED SEALANT,
EA. SIDE, T&B
HEAD SLIP
CONNECTOR
FINISHED CEILING
ACOUSTIC BATTS
6" METAL STUDS
@ (16" O.C.)
1 LAYER 5/8" GWB
EA. SIDE
PAF (.145) @ (32" O.C.)
TRACK - T&B
A1
STRUCTURE ABOVE
FIRE RATED SEALANT,
EA. SIDE, T&B
HEAD SLIP
CONNECTOR
FINISHED CEILING
ACOUSTIC BATTS
3 5/8" METAL STUDS
@ (16" O.C.)
1 LAYER 5/8" IMPACT-
RESISTANT
GWB, EA. SIDE
PAF (.145) @ (32" O.C.)
TRACK - T&B
9 GA. EXP. METAL MESH
(WAREHOUSE SIDE)
M6
STRUCTURE ABOVE
FIRE
RATED
SEALANT,
EA. SIDE,
T&B
FINISHED
CEILING
6" CMU
M6A
6" CMU
+8'-0"
AFF
6" CONC CEILING
OVER TOP OF CMU w/
LT. GA. JOIST
6" LT. GA. JOIST
@ 16" O.C.
5/8" GWB
4" CMU
M4
TRACK
TRACK
1 5/8" METAL STUDS
@ (16" O.C.)
2 1/2" METAL STUDS
@ (16" O.C.)
PAF (.145)
@ (32" O.C.)
PAF (.145)
@ (32" O.C.)
+9'-4"
F3
STRUCTURE
ABOVE
FINISHED CEILING
(WHERE SCHEDULED)
SPRAY-APPLIED
FOAM INSUL
R-9.5 (MIN.)
1 1/2" METAL
WALL LINER PANEL
TRACK
2 1/2" METAL STUDS
@ (16" O.C.)
PAF (.145)
@ (32" O.C.)
F.O. EXIST
EXTERIOR WALL
SPRAY-APPLIED
FOAM INSUL
R-9.5 (MIN.)
F.O. EXIST EXT. WALL
FINISHED CEILING
(WHERE SCHEDULED)
F.V.
2 15/16"
1 LAYER RWC
TO +4'-0" AFF
HEAD SLIP
CONNECTOR
HEAD SLIP
CONNECTOR
HEAD SLIP
CONNECTOR
F3A
STRUCTURE
ABOVE
FINISHED CEILING
(WHERE SCHEDULED)
SPRAY-APPLIED
FOAM INSUL
R-9.5 (MIN.)
1 1/2" METAL
WALL LINER PANEL
TRACK
2 1/2" METAL STUDS
@ (16" O.C.)
PAF (.145)
@ (32" O.C.)
F.O. EXIST
EXTERIOR WALL
HEAD SLIP
CONNECTOR
1'-2 1/8"
STRUCTURE ABOVE
FIRE
RATED
SEALANT,
EA. SIDE,
T&B
FINISHED
CEILING
HOLLOW
METAL FRAME
(AS
APPLICABLE)
HIGHER
PRIORITY
WALL
ONE HOUR
CONSTRUCTION
TWO HOUR FIRE AND /
OR SMOKE PARTITION
CONSTRUCTION
METAL STUDS
RATED WALL AND /
OR SMOKE
PARTITION
NON-RATED WALL
HIGHER
PRIORITY
WALL
ONE LAYER
AT ONE
HOUR
SMOKE
PARTITION
WALL PRIORITY LEGEND
TWO HOUR FIRE AND / OR
SMOKE WALL
PRIORITY 1 (HIGHEST)
TWO HOUR FIRE WALL
TWO HOUR SHAFT WALL
PRIORITY 2
ONE HOUR FIRE AND /
OR SMOKE WALL
PRIORITY 3
ONE HOUR FIRE WALL PRIORITY 4
NON-RATED WALL PRIORITY 5 (LOWEST)
NOTE: ALL PARTITION TYPES INDICATED, MAY NOT BE USED.
REFER TO PLANS FOR MORE INFORMATION.
RATED WALL AND / OR
SMOKE PARTITION
NON-RATED WALL
EXISTING MASONRY WALL
THERMAL INSULATION
FILL FIRST CAVITY
M
IN
1"
STRUCTURE ABOVE
FIRESTOP
5/8" GYP. BD.
5/8" CORE BD.
ACOUSTIC BATTS
PAF (.145) @ (32" O.C.)
TRACK - T&B
CUT HORIZONTAL FASTENER
FROM METAL STUDS
FASTEN AT BOTH ENDS WITH
MINIMUM 4 SELF-TAPPING
SCREWS
METAL STUDS AT 16" O. C.
ISOMETRIC PLAN VIEW
NOTES:
1. CONTRACTOR SHALL COORDINATE LOCATIONS OF
HORIZONTAL FASTENERS
2. WALL BACKING SHALL BE USED AT ALL GRAB BARS, WALL
CABINETS, BUMPER/CRASH RAILS, ETC. U.N.O.
3. MINIMUIM GAGE FOR WALL BACKING TO BE 16 GA. U.N.O.
WALL PARTITION GENERAL NOTES:
A. ALL PARTITION FRAMING SHALL EXTEND FROM
FLOOR TO FLOOR/ROOF STRUCTURE ABOVE
UNLESS NOTED OTHERWISE.
B. REFER TO INDIVIDUAL PARTITION TYPES FOR
EXTENT OF GYPSUM WALLBOARD AND
ACOUSTICAL TREATMENT.
C. ALL BULKHEAD FRAMING SHALL EXTEND TO
UNDERSIDE OF STRUCTURE ABOVE WITH
DIAGONAL METAL STUD BRACING AT 4'-0" ON
CENTER MAXIMUM. PROVIDE MINIMUM TWO
BRACES PER BULKHEAD.
D. WHEN A PARTITION IS REQUIRED TO MEET A
SPECIFIC FIRE RATED TEST NUMBER OR STC
TEST NUMBER THE SPECIFIC REQUIREMENTS OF
THAT TEST NUMBER SHALL SUPERSEDE ANY
CONFLICTING NOTATION ON THAT PARTICULAR
DETAIL OR PARTITION TYPE.
E. ALL PARTITIONS WITH ACOUSTICAL BATT
INSULATION SHALL BE CONSIDERED "SOUND"
PARTITIONS. ALL PENETRATIONS SHALL BE
SEALED WITH ACOUSTICAL SEALANT.
WALL PARTITION
GENERAL NOTES:
NOTES:
1. THIS DETAIL IS APPLICABLE TO ALL PARTITIONS WITH
ACOUSTICAL BATT INSULATION (SOUND PARTITION).
2. REFER TO PARTITION TYPES FOR ADDITIONAL INFORMATION.
3. REFER TO HEAD OF PARTITION DETAILS FOR DEFLECTION
CONSIDERATIONS.
ACOUSTIC BATT
INSULATION
(WHERE INDICATED ON
PARTITION TYPE)
WALL FINISH
AS SCHEDULED
WALL BASE
AS SCHEDULED
CONTINUOUS ACOUSTIC
SEALANT UNDERNEATH
RUNNER
AND BOTH SIDES OF WALL;
JAMB LOCATIONS ALSO
FLOOR FINISH
AS SCHEDULED
FLOOR LINE5
/8
GWB CONTROL JOINT,
(TYP)
WALL FRAMING AS SCH.
NOTE:
SIMILAR ON FURRED WALLS
1/2"
MAX. 10" DIA. NOMINAL STEEL PIPE
SCHEDULE 10 OR GREATER (SEE NOTE
3 FOR OTHER OPTIONS)
MIN. 1/2" DEPTH INTUMESCENT
FIRESTOP SEALANT
MIN. 3" MINERAL WOOL TIGHTLY PACKED
(MAX. 12" DIAMETER OPENING)
MIN. 1/2" FIRESTOP SEALANT BEAD AT ALL
POINTS OF CONTACT (BOTH SIDES OF WALL
ASSEMBLY)NOTE:
1. 2HR FIRE-RATED CONCRETE FLOOR SHOWN
2. MAX. DIAMETER OF OPENING = 12"
3. PIPE OPTION MAX. DIA. PIPE OPTIONS MAX. DIA.
CAST IRON 10" STEEL CONDUIT 4"
COPPER PIPE OR TUBING 4" EMT 4"
MIN. 4 1/2" CONCRETE FLOOR OR
UL CONCRETE BLOCK WALL
UL C-AJ-1149
MAX. 4" NOMINAL STEEL PIPE
SCHEDULE 10 OR GREATER
(MAX. 4" DIAMETER COPPER PIPE)
3/4" FLEXIBLE FOAM
PIPE INSULATION
MIN. 1/2" DEPTH
INTUMESCENT
FIRESTOP SEALANT
(REQUIRED BOTH SIDES
OF WALL ASSEMBLY)
MIN. 2 1/2" CONCRETE FLOOR
(MIN. 3" CONCRETE WALL
MIN. 2" MINERAL WOOL
TIGHTLY PACKED
MIN. 1/2" FIRESTOP SEALANT
BEAD AT ALL POINTS OF
CONTACT
NOTE:
1. 2HR FIRE-RATED CONCRETE FLOOR SHOWN
2. MAX. DIAMETER OF OPENING = 7"
UL C-AJ-5198
MAX. 2" STEEL PIPE SCHEDULE,
40 OR GREATER
MAX. 1" GLASS FIBER PIPE
INSULATION
MIN. 1/2" DEPTH INTUMESCENT FIRESTOP SEALANT
(REQUIRED BOTH SIDES OF WALL)
@ ALL POINTS OF CONTACT
MIN. 4 1/2" CONCRETE FLOOR
(MIN. 5" CONCRETE WALL
MIN. 4" MINERAL WOOL TIGHTLY PACKED
(ANNULAR SPACE = MIN. 11/16" MAX. 3 1/16")
NOTE:
1. 2HR FIRE-RATING FLOOR SHOWN
2. MAX. DIAMETER OF OPENING = 8"
UL C-AJ-5048
GYPSUM WALL ASSEMBLY, FIRE-RATIING
AS SCHEDULED
METAL STUD FRAMING MIN, 2 1/2" WIDE
ON ALL SIDES OF OPENING
MIN. 1/4" ANNULAR COMPRESSES GLASS
FIBER INSULATION (1" MAX.)
MIN. 24 GA. RECTANGULAR SHEET METAL
DUCT (24" x 12" DUCT MAX.)
MIN. 1 1/4" DEPTH INTUMESCENT FIRESTOP
SEALANT
(MIN. 5/8" FOR 1 HR FIRE-RATED) @ ALL
POINTS OF CONTACT
NOTE:
2 HR FIRE-RATING SHOWN
w/ MINIMUM REQUIREMENTS
GYPSUM WALL ASSEMBLY,
FIRE-RATIING AS SCHEDULED
METAL STUD FRAMING
MIN, 3 1/2" WIDE ON ALL
SIDES OF OPENING
MIN. 5" MINERAL WOOL
INTO OPENING (MIN. 3 3/4"
FOR 1 HR FIRE-RATING)
MIN. 1/2" DEPTH
INTUMESCENT
FIRESTOP SEALANT
MIN. 24 GA.
RECTANGULAR SHEET
METAL DUCT
(24"x24" DUCT MAX.)
MIN. 1/4" FIRESTOP SEALANT
BEAD AT POINT OF CONTACT
(2 HR FIRE-RATING ONLY MAY
HAVE 0" ANNULAR SPACE
AT BOTTOM OF THE DUCT)
METAL STUD TRACK
SCREW ATTACH TRACK TO
BOTH JAMB STUDS
(2) 20 GA. METAL STUDS
INTERIOR HOLLOW METAL
DOOR OR WINDOW FRAME
1/2" CONTROL JOINT SPACING
INSTALL SUITABLE BACKING
AT RATED WALLS
STOP
EXTRA METAL STUD
1/2"
SCREW ATTACH TRACK TO
BOTH JAMB STUDS
NOTE:
PROVIDE ONE AT EACH CORNER OF ALL DOORS BOTH SIDES OF WALL,
PROVIDE ONE EVERY 30 FEET AND AS INDICATED ON THE RCP.
STRUCTURAL DECK
FIRESTOP
METAL STUD RUNNER:
SECURE STUD RUNNER TO
STRUCTURE WITH TWO 1/4"
DRILLED ANCHORS @ 24" O.C.
NOTE:
DO NOT SCREW STUDS OF GYP TO
RUNNER, PROVIDE HORIZONTAL
BRACING WITHIN STUD SPACE TO
BRACE STUDS WITHIN 1'-0" FROM
TO OF WALL
TYPE S SCREWS
GYPSUM WALL BOARD
NOTE:
FIRESTOPPING AND SEALANT IS REQUIRED ONLY AT RATED WALLS
REFER TO A6-SERIES FOR LOCATIONS
FOR WALL TYPES
SEE FLOOR PLAN
1/
2"
5/ 8"
3/ 4"
UL W-L-5028
METAL STUD FRAMING MIN 2 1/2"
WIDE ON ALL SIDES OF OPENING
MIN. 5/8" DEPTH INTUMESCENT
FIRESTOP SEALANT
3/4" FLEXIBLE FOAM PIPE
INSULATION
MAX. 4" NOMINAL STEEL PIPE
SCHEDULE 40 OR GREATER
(MAX. 2" DIAMETER COPPER
PIPE OR TUBING)
MIN. 1/2" FIRESTOP SEALANT
BEAD AT ALL JOINTS OF CONTACT
GYPSUM WALL ASSEMBLY, FIRE-
RATING AS SCHEDULED
NOTE:
1. 2 HR FIRE-RATING SHOWN
2. MAX. DIAMETER OF
OPENING = 7 1/2"
STRUCTURE ABOVE
1/2" T FIRE STOP SEALANT, EACH
SIDE (ACOUSTIC SEALANT AT
SOUND PARTITION)
J-CASING BEAD, EACH SIDE
CONTINUOUS 16 GA. DEEP LEG TRACK
1" DEFLECTION SPACE TO RUNNER CHANNEL
5/8" FIRE RATED GYPSUM BOARD, EACH SIDE
GYPSUM BOARD PARTITION,
SEE FLOOR PLAN FOR TYPE
NOTES:
1. DETAIL FOR SMOKE RESISTANT, 1-HR RATED,
OR SOUND PARTITION ASSEMBLIES.
2. ATTACH GYPSUM BOARD TO METAL STUDS ONLY,
DO NOT TO DEEP LEG TRACK.
WALL TYPE NOTES:
1. NOT ALL WALL TYPES SHOWN IN THIS SCHEDULE
MAY BE USED IN THE PROJECT. REFER TO FLOOR
PLANS FOR WALL TYPES USED.
2. ALL NEW INTERIOR GWB SHALL BE 5/8" TYPE X
MOISTURE AND MOLD RESISTANT GWB UNLESS
OTHERWISE NOTED.
3. PROVIDE ABUSE-RESISTANT GWB UP TO THE
CEILING AT ROOMS WITH CEILINGS, INCLUDING
EXTERIOR WALLS. AT ROOMS WITH NO CEILINGS,
EXTEND ABUSE-RESISTANT GWB UP TO BOTTOM
OF STRUCTURE.
4. ALL GWB TO BE SMOOTH FINISH THROUGHOUT,
LEVEL 4 FINISH, UNLESS NOTED OTHERWISE.
5. FIELD VERIFY DETAILED WALL CONSTRUCTION &
REVIEW PLAN LAYOUT WITH EXISTING
CONDITIONS IN THE FIELD. WHERE FIELD
CONDITIONS CONFLICT WITH WALL
CONSTRUCTION DETAILS, MODIFY WALL
CONSTRUCTION AS PER ARCHITECTS DIRECTIVE
AT NO ADDITIONAL COST TO THE OWNER.
6. ALL WALL TYPES TO HAVE ACOUSTICAL SEALANT
AT TOP AND BOTTOM, BOTH SIDES AND ALL
OTHER CUTOUTS TO PREVENT SOUND LEAKAGE.
7. CONSTRUCT ALL WALLS TO CONFORM TO THE
DETAILED REQUIREMENTS OF THE MOST-
CURRENT EDITION OF UNDERWRITERS
LABORATORIES INC.'S "FIRE RESISTANCE
DIRECTORY" AND THE GYPSUM ASSOCIATION'S
"FIRE RESISTIVE DESIGN MANUAL" GA-600,
CURRENT EDITION. APPLY GWB PER LISTED
ASSEMBLY TO MEET UL DESIGN NUMBER.
8. WHERE WALLS ARE INDICATED TO BE FIRE
RESISTIVE CONSTRUCTION, TAPE ALL JOINTS,
INCLUDING THOSE JOINTS ABOVE CEILINGS.
9. ALL RATED WALLS TO BE CONTINUOUS WHEN
INTERSECTED BY WALLS OF LESSER OR NO
RATING.
10. PROVIDE "MUD ON" CASING, TEAR AWAY, "L", OR
"J" BEA.D AT FRAMES, CEILINGS AND OTHER
OPENINGS AND TRANSITIONS AS REQUIRED. ALL
BEAD SHALL BE "MUD ON" TYPE UNLESS
INDICATED OTHERWISE.
11. ACOUSTIC INSULATION AT 3-5/8" STUDS SHALL BE
3-1/2" THICK BATTS MINIMUM. ACOUSTIC
INSULATION AT 6" STUDS SHALL BE 6" THICK
BATTS.
12. PROVIDE TILE BACKER BOARD AND
WATERPROOF MEMBRANE AT ALL CERAMIC TILE-
FACED WALLS.
13. DIMENSIONS ARE TO FACE OF GWB UNLESS
OTHERWISE NOTED.
14. SEE INTERIOR ELEVATIONS AND FINISH PLANS
FOR EXTENTS OF CERAMIC TILE.
15. PROVIDE MTL STUD WALL BACKING CENTERED
AT 3'-0" AFF & WHERE REQ'D FOR ANCHORAGE
OF WALL-MOUNTED ITEMS.
WALL TYPES
GENERAL NOTES:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Incandescence Life Safety, Inc.
3575 Ringsby Court, #408, Denver, CO, 80216
Phone:(720) 722-3010
589A4-20-158
IMEG Corp.
15 Sunnen Drive, Suite 104
St. Louis, MO 63143
Phone:(314) 951-2534
BID SET RENOVATE WAREHOUSE FOR
PANDEMIC PREPAREDNESS
HARRY S. TRUMAN MEM. VETERANS HOSPITAL
800 HOSPITAL DR., COLUMBIA MO 65201
BID SET 03/24/2021
Dwg. # of 94
C
L H
D C
\H o m e
\t fi e s e lm a n \R e v it M o d e ls \R
-2
-2
A
-2
-1
R e n o v a te W a re h o u s e tf ie s e lm a n A
G
Y .r v t
/2
/2
:4
:0
A
M
G-003
WALL TYPES & DETAILS
AHT TJF03/24/2021
1 1/2" = 1'-0"B1
WALL TYPES
1 1/2" = 1'-0"D1
WALL PRIORITY
NOT TO SCALED4
TEMPORARY PARTITION DETAIL
NOT TO SCALEF1
WALL BACKING
NOT TO SCALEF3
PARTITION BASE DETAIL
3" = 1'-0"C4
WALL GWB EXP. JOINT
NOT TO SCALEF8
FIRE RATED PIPE THRU SLAB
NOT TO SCALEF6
FIRE RATED INSULATED PIPE THRU SLAB
NOT TO SCALED8
WALL-INSULATED DUCT PENETRATION
NOT TO SCALED6
WALL-DUCT PENETRATION
NOT TO SCALEE5
WALL - TYPICAL CONTROL JOINT
NOT TO SCALEF5
WALL HEAD DETAIL
NOT TO SCALEE8
FIRE RATED INSULATED PIPE THRU PARTITION
NOT TO SCALEE3
PARTITION HEAD DETAIL
3Revisions: Date:
LC
LC
T his Drawing Produc ed by the U.S. Acc ess Board
LC
T his Dra wing Pro duced b y the U. S. Acces s Board
T his Drawing Produc ed by the U.S. Acc ess Board
T his Drawing P roduc ed by the U.S. Acc ess B oard
This Dr awing Pr oduced by t he U.S. Access Boar d
T his D rawing Produ ced by the U.S. A ccess Board Figure 104 Graphic Convention for Figures
This Dr awing Pr oduced by t he U.S. Access Boar d
T his Drawing Produced by the U.S. A ccess Board
T his Drawing Pro duced by the U. S. Access Board
T his Dr aw in g Pr od uc ed b y t he U .S . Ac ce ss B oa rd
T his Dra wing Pro duced b y the U. S. Acces s Board
This Dr awing Pr oduced by t he U.S. Access Boar d
This Dr awing Pr oduced by t he U.S. Access Boar d
T his Dra wing Pro duced b y the U. S. Acces s Board
T his Drawing Produced by the U.S. Access Board
30 min
48 min m in m in
(a) forward
(b) parallel
36 min
X
12 min
24 min
36 min
11 min m in
8 min
9 min min max dimension showing English units (in inches unless otherwise specified) above the line and SI units (in millimeters unless otherwise specified) below the line dimension for small measurements direction of travel or approach boundary of clear floor space or maneuvering clearance centerline minimum maximum a permitted element or its extension a wall, floor, ceiling or other element cut in section or plan a highlighted element in elevation or plan
Convention Description location zone of element, control or feature greater than>
< less than
33-36 840-915 dimension showing a range with minimum - maximum less than or equal to greater than or equal to>
BEVELED CHANGE IN LEVEL
UNOBSTRUCTED FORWARD REACHCLEAR FLOOR SPACE OBSTRUCTED HIGH FORWARD REACH UNOBSTRUCTED SIDE REACHALCOVE CLEARANCE LIMITS OF PROTRUDING OBJECTS
TOE CLEARANCE KNEE CLEARANCE SPOUT LOCATION
CLEARANCE AT WATER CLOSETS SIDE WALL GRAB BAR AT WATER CLOSETS REAR WALL GRAB BAR AT WATER CLOSETS T. P. DISPENSER OUTLET LOCATION m in m a x m a x m a x
>20-25 max 510-635
20 max
(a) (b) 10 max m a x m in
4 max
X
X
60 min m in
12 max
42 min
54 min m in
7-9 180-230 m a x
5 max 15 min 380125
17-25
430-635
6 max m in
(a) elevation
(b) plan
6.4
¼
¼ 6.4
½
TURNING RADIUS
66 min
DRINKING FOUNTAINDRINKING FOUNTAIN DRINKING FOUNTAIN
TRANSFER SIDE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Incandescence Life Safety, Inc.
3575 Ringsby Court, #408, Denver, CO, 80216
Phone:(720) 722-3010
589A4-20-158
IMEG Corp.
15 Sunnen Drive, Suite 104
St. Louis, MO 63143
Phone:(314) 951-2534
BID SET RENOVATE WAREHOUSE FOR
PANDEMIC PREPAREDNESS
HARRY S. TRUMAN MEM. VETERANS HOSPITAL
800 HOSPITAL DR., COLUMBIA MO 65201
BID SET 03/24/2021
Dwg. # of 94
C
L H
D C
\H o m e
\t fi e s e lm a n \R e v it M o d e ls \R
-2
-2
A
-2
-1
R e n o v a te W a re h o u s e tf ie s e lm a n A
G
Y .r v t
/2
/2
:4
:0
A
M
G-004
ACCESSIBILITY CLEARANCES
AHT TJF03/24/2021
4Revisions: Date:
T
GENERAL NOTES:
1. SURVEY IS PROVIDED BY THE VA FOR REFERENCE ONLY OF
EXISTING CONDITIONS AND UNDERGROUND IMPROVEMENTS..
2. SEE ARCHITECTURAL SITE PLAN SHEET AS101 FOR
INFORMATION RELATED TO CONTRACTOR'S USE OF SITE,
CONSTRUCTION LIMITS, FENCING AND BARRIERS, SITE
IMPROVEMENTS AND ACCESS.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD
VERIFICATION OF EXISTING CONDITIONS AND CHANGES MADE
TO THE SITE SINCE THE PUBLISHED DATE OF THE SURVEY.
4. THE CONTRACTOR SHALL RETAIN THE SERVICES OF AN
UNDERGROUND UTILITY LOCATE SERVICE PRIOR TO START OF
WORK ON SITE THAT INCLUDES EXCAVATION, DEMOLITION OF
EXISTING PAVEMENT OR OTHER WORK THAT MAY DISTURB
BELOW-GRADE UTILITIES AND IMPROVEMENTS.
5. CONTRACTOR SHALL PROTECT ALL SITE INFRASTRUCTURE
UNLESS DIRECTED OTHERWISE BY COR.
6. COORDINATE ACCESS TO CHILLER PLANT AND ADJACENT
ELECTRICAL VAULT W/ COR.
SURVEY
GENERAL NOTES:
BLDG 14 -
WAREHOUSE
KEY PLAN
AREA 'G'
AREA 'C' AREA 'D'
AREA 'B' AREA 'A'
AREA 'E'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Incandescence Life Safety, Inc.
3575 Ringsby Court, #408, Denver, CO, 80216
Phone:(720) 722-3010
589A4-20-158
IMEG Corp.
15 Sunnen Drive, Suite 104
St. Louis, MO 63143
Phone:(314) 951-2534
BID SET RENOVATE WAREHOUSE FOR
PANDEMIC PREPAREDNESS
HARRY S. TRUMAN MEM. VETERANS HOSPITAL
800 HOSPITAL DR., COLUMBIA MO 65201
BID SET 03/24/2021
Dwg. # of 94
C
L H
D C
\H o m e \a ta s t\ R
-2
-2
A -2
-1
R e n o v a te
W a re h o u s e a ta s t.
rv t
/2
/2
:1
:3
A
M
V-100
EXISTING SITE SURVEY
AHT TJF03/24/2021
N O R
HT
1" = 20'-0"1
EXISTING SURVEY
5Revisions: Date:
atast Rectangle
BUILDING AND LIFE SAFETY CODE ANALYSIS SUMMARY:
THE FOLLOWING IS A SUMMARY OF THE BASIS OF DESIGN NARRATIVE THAT IS INTENDED TO DEMONSTRATE COMPLIANCE WITH APPLICABLE CODES AND STANDARDS. MORE DETAILED CODE ANALYSIS INFORMATION IS PROVIDED ON SUBSEQUENT DRAWING SHEETS AND WITHIN THE FIRE PROTECTION AND LIFE
SAFETY SECTION OF THE DESIGN NARRATIVE.
APPLICABLE CODES:
THE FOLLOWING PRIMARY CODES AND STANDARDS ARE USED AS THE BASIS FOR THE DESIGN
• VA FIRE PROTECTION DESIGN MANUAL (VAFPDM; 7TH EDITION DECEMBER 2015)
• NATIONAL FIRE PROTECTION ASSOCIATION FIRE CODE (NFPA 1; 2018 EDITION)
• NATIONAL FIRE PROTECTION ASSOCIATION STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS (NFPA 13; 2019 EDITION)
• NATIONAL FIRE PROTECTION ASSOCIATION NATIONAL FIRE ALARM AND SIGNALING CODE (NFPA 72, 2019 EDITION)
• NATIONAL FIRE PROTECTION ASSOCIATION LIFE SAFETY CODE (NFPA 101; 2018 EDITION)
• INTERNATIONAL BUILDING CODE (IBC; 2018 EDITION) *NOTE: AS ENFORCED BY VAFPDM §1.3.
BUILDING RENOVATION & RECONSTRUCTION
THE RENOVATION OF THE EXISTING WAREHOUSE BUILDING CONSISTS OF THE MODIFICATION OF MORE THAN 50% OF THE AREA OF THE BUILDING AND THEREFORE IS CLASSIFIED AS A RECONSTRUCTION IN ACCORDANCE WITH NFPA 101 §43.5.2.3. THE RECONSTRUCTION OF THE WAREHOUSE IS SUBJECT TO THE REQUIREMENTS OF NFPA 101 §43.6 AND GENERALLY MUST COMPLY WITH BUILDING REQUIREMENTS RELATED TO NEW CONSTRUCTION, EXCEPT WHERE NOTED.
SITE FIRE PROTECTION DESIGN
NONE OF THE ASPECTS OF THE SITE FIRE DEPARTMENT / EMERGENCY VEHICLE ACCESS ARE BEING MODIFIED AS PART OF THIS RENOVATION SCOPE OF WORK AND
ARE TO REMAIN AS IS.
REQUIRED FIRE FLOW FOR THE FACILITY IS PROVIDED IN ACCORDANCE WITH NFPA 1 BASED ON THE CONSTRUCTION TYPE AND FIRE FLOW CALCULATION AREAS.
BASED ON TYPE II (000) CONSTRUCTION, A FIRE AREA OF APPROXIMATELY 16,600 FT2 AND A 75% REDUCTION DUE TO THE PRESENCE OF AUTOMATIC SPRINKLERS, NFPA 1 TABLE 18.4.5.2.1 REQUIRES A FIRE FLOW OF 1000 GPM AT 20 PSI FOR 2 HOURS (NFPA 1 §18.4.5.3.2). PRELIMINARY HYDRANT FLOW TEST DATA PROVIDED BY COLUMBIA WATER AND LIGHT HAS BEEN PROVIDED NEAR THE PROJECT SITE AND INDICATES THAT THE AVAILABLE FIRE FLOW WILL BE IN EXCESS OF 5,000 GPM AT 20 PSI AND THEREFORE THE EXISTING WATER SUPPLY IS CAPABLE OF MEETING THE REQUIRE FIRE FLOW DEMAND.
SINCE THE FIRE FLOW REMAINS UNCHANGED AND THE FOOTPRINT OF THE EXISTING BUILDING REMAINS UNCHANGED AS PART OF THIS SCOPE OF WORK, NO
ADDITIONAL HYDRANTS ARE REQUIRED PER NFPA 1 AND THE VAFPDM.
OCCUPANCY CLASSIFICATION:
OCCUPANCY CLASSIFICATION IS DETERMINED IN ACCORDANCE WITH NFPA 101 AS REQUIRED BY THE VAFPDM. THE ENTIRE WAREHOUSE IS CLASSIFIED AS AN
ORDINARY HAZARD STORAGE OCCUPANCY IN ACCORDANCE WITH NFPA 101 CHAPTER 42.
OCCUPANCY SEPARATIONS:
THE ENTIRE BUILDING IS CLASSIFIED AS A SINGLE OCCUPANCY CONSISTING OF ORDINARY HAZARD STORAGE, AND THEREFORE NO OCCUPANCY SEPARATIONS ARE
PROVIDED.
BUILDING SEPARATION:
IN ACCORDANCE WITH §2.2.A OF THE VAFPDM, THERE ARE NO REQUIREMENTS FOR SEPARATION OR OPENINGS BETWEEN VA BUILDINGS WITH ALL BUILDINGS ARE FULLY SPRINKLER PROTECTED. AN EXISTING CHILLER PLANT IS LOCATED TO THE WEST AND A HOSPITAL BUILDING IS LOCATED TO THE NORTH; BOTH OF WHICH ARE PHYSICALLY SEPARATED AND SPRINKLERED THROUGHOUT. THE LARGER HOSPITAL BUILDING (BUILDING 1) LOCATED TO THE NORTH AND EAST IS PHYSICALLY CONNECTED TO THE WAREHOUSE BY A CONNECTING CORRIDOR THAT HAS AN EXISTING 2-HOUR BUILDING SEPARATION ALONG THE NORTH SIDE OF THE CONNECTING CORRIDOR TO SEPARATE THE WAREHOUSE FROM THE HOSPITAL BUILDING (BUILDING 1).
BUILDING CONSTRUCTION TYPE:
THE EXISTING WAREHOUSE BUILDING IS CONSTRUCTED OF EXTERIOR BLOCK WALLS WITH UNPROTECTED STEEL SUPPORTS AND ROOF ASSEMBLIES AND NONCOMBUSTIBLE BUILDING ELEMENTS. THEREFORE THE EXISTING BUILDING APPEARS TO MATCH TYPE II (000) CONSTRUCTION PER NFPA 220 AND TYPE II-B PER THE IBC. THE WAREHOUSE RENOVATIONS INCLUDED IN THIS SCOPE OF WORK WILL BE DONE IN A MANNER WHICH MAINTAINS THE EXISTING CONSTRUCTION TYPE AND THEREFORE, NO MODIFICATIONS TO THE EXISTING CONSTRUCTION TYPE WILL BE INCORPORATED AS PART OF THIS SCOPE OF WORK.
ALLOWABLE HEIGHT & AREA ANALYSIS (NFPA 101 §42.1.6 & IBC TABLES 504.3, 504.4 & 506.2) NFPA 101 DOES NOT INCLUDE CONSTRUCTION TYPE REQUIREMENTS FOR STORAGE OCCUPANCIES AND THEREFORE §2.1-B OF THE VAFPDM REQUIRES THAT THE HEIGHT AND AREA LIMITATIONS BE IN ACCORDANCE WITH THE IBC. THE FOLLOWING SUMMARIZES THE ACTUAL AND ALLOWABLE HEIGHT, STORY, AND AREA FOR THE WAREHOUSE BUILDING IN ACCORDANCE WITH THE IBC CHAPTER 5 FOR A FULLY SPRINKLERED BUILDING OF TYPE II-B CONSTRUCTION THAT CONTAINS A GROUP
S-2 OCCUPANCY.
HEIGHT (IBC TABLE 504.3)
• ALLOWABLE: 75 FT
• ACTUAL: 31 FT
# OF STORIES (IBC TABLE 504.4):
• ALLOWABLE: 4
• ACTUAL: 2
AREA (IBC TABLE 506.2):
• ALLOWABLE PER STORY: 78,000 FT2
• ACTUAL PER STORY:
• FIRST: 11,742 FT2
• UPPER: 3,822 FT2
MEZZANINES AND VERTICAL OPENINGS:
THE AREA OF THE UPPER FLOOR IS GREATER THAN 1/3 OF THE TOTAL AREA OF THE ROOMS ON THE GROUND FLOOR WHICH IT IS OPEN TO AND THEREFORE CANNOT BE CONSIDERED A MEZZANINE PER NFPA 101 §8.6.10.2.1. THEREFORE, THE UPPER FLOOR IS CONSIDERED A BUILDING STORY AND VERTICAL OPENINGS ARE PROTECTED ACCORDINGLY. IT IS IMPORTANT TO NOTE THAT THESE PLANS REFER TO THIS UPPER FLOOR AS A 'MEZZANINE' AT THE REQUEST OF THE CLIENT;
HOWEVER, THIS AREA HAS BEEN DESIGNED AND ANALYZED AS A BUILDING STORY PER THE REQUIREMENtS OF NFPA 101. AS PERMITTED BY NFPA 101 §42.3.1, CONVENIENCE OPENINGS IN ACCORDANCE WITH §8.6.9.1 ARE PERMITTED WITHIN STORAGE OCCUPANCIES. AN OPEN CONVENIENCE STAIR IS PROVIDED TO CONNECT THE UPPER FLOOR WITH THE GROUND FLOOR; THE VERTICAL OPENING IS CONFIGURED AS A CONVENIENCE OPENING IN ACCORDANCE WITH NFPA 101 §
8.6.9.1. THIS PERMITS UNPROTECTED VERTICAL OPENINGS BETWEEN THE TWO STORIES, AND THEREFORE NO SHAFTS ARE REQUIRED AS LONG AS THEY ARE
WITHIN THE CONVENIENCE OPENING.
HAZARDOUS AREA SEPARATION:
ALL AREAS WITHIN THE WAREHOUSE ARE THE SAME RELATIVE LEVEL OF HAZARD AND NO HAZARDOUS MATERIALS ARE ANTICIPATED TO BE STORED WITHIN THE BUILDING IN QUANTITIES THAT WOULD BE DEEMED HAZARDOUS; THEREFORE, NO HAZARDOUS AREA SEPARATIONS ARE REQUIRED IN ACCORDANCE WITH NFPA 101
§8.7 AND §42.3.2.
EGRESS DESIGN:
ALL EGRESS PROVISIONS ARE PROVIDED IN ACCORDANCE WITH NFPA 101 AND THE VAFPDM.
• OCCUPANT LOAD CALCULATIONS ARE BASED ON THE FACTORS IN NFPA 101 TABLE 7.3.1.2
• NUMBER OF EXITS AND CONFIGURATION IS PROVIDED IN ACCORDANCE WITH NFPA 101 SECTIONS 7.4 AND 7.5. AS PERMITTED BY NFPA 101 §
• EXIT ACCESS AND TRAVEL DISTANCE REQUIREMENTS (TRAVEL DISTANCE LIMITATIONS, COMMON PATH LIMITATIONS, AND DEAD-END CORRIDORS) ARE IN
ACCORDANCE WITH NFPA 101 §42.2.5 AND §42.2.6.
• EXITS MEET THE REQUIREMENTS OF NFPA 101 SECTION 7.1.3.2 AND EGRESS COMPONENTS CONFORM TO THE TYPES AND REQUIREMENTS IN NFPA 101
SECTION 7.2.
• EGRESS WIDTH AND CAPACITY IS PROVIDED BASED ON OCCUPANT LOAD, CALCULATED IN ACCORDANCE WITH NFPA 101 SECTION 7.3.3.
• EXIT DISCHARGE IS PROVIDED IN ACCORDANCE WITH NFPA 101 SECTION 7.7.
• ROOF ACCESS IS NOT REQUIRED FOR THE BUILDING ADDITION AS IT IS LESS THAN FOUR STORIES ABOVE GRADE PLANE.
FIRE SUPPRESSION SYSTEMS:
THE EXISTING WAREHOUSE IS PROTECTED BY AN AUTOMATIC WET-PIPE SPRINKLER PROTECTION IN ACCORDANCE WITH NFPA 13 AS REQUIRED BY THE VAFPDM.
THE EXISTING 4" SPRINKLER STANDPIPE RISER IS LOCATED IN THE SOUTHWEST CORNER OF THE BUILDING AND INCLUDES A BACKFLOW PREVENTER, A FLOW SWITCH, AND FIRE DEPARTMENT CONNECTION. THE EXISTING RISER ASSEMBLY AND SPRINKLER PIPING IS TO BE REUSED TO THE GREATEST EXTENT POSSIBLE AS PART OF THIS SCOPE OF WORK. MODIFICATIONS TO EXISTING PIPING WILL BE REQUIRED TO PROVIDE SPRINKLER PROTECTION ABOVE AND BELOW THE UPPER FLOOR LEVEL, IN ADDITION TO RECONFIGURATION OF THE EXISTING SPRINKLER HEADS TO ACCOMMODATE THE MODIFIED STORAGE CONFIGURATION WITHIN THE BUILDING. VA HAS PROVIDED AN INVENTORY OF ANTICIPATED STORAGE MATERIALS AND STORAGE CONFIGURATIONS THROUGHOUT THE BUILDING TO ENSURE THAT SPRINKLER PROTECTION IS APPROPRIATELY DESIGNED IN ACCORDANCE WITH NFPA 13. USER WILL UTILIZE OPEN RACK, PALLETIZED, AND BIN BOX STORAGE CONFIGURATIONS OF CLASS IV COMMODITIES WITH MAXIMUM STORAGE HEIGHTS OF 12'; MORE DETAILS OF STORAGE CONFIGURATIONS ARE INDICATED ON FIRE SUPPRESSION PLAN. HYDRANT FLOW TEST DATA HAS BEEN PROVIDED BY THE CITY OF COLUMBIA MISSOURI UTILITIES DEPARTMENT FOR VERIFICATION THAT
EXISTING WATER SUPPLY IS ADEQUATE TO SUPPORT THE PROPOSED SYSTEM MODIFICATIONS..
THE EXISTING FIRE SUPPRESSION SYSTEM IS MONITORED BY THE BUILDING 1 FIRE ALARM SYSTEM TO TRANSMIT FIRE ALARM, SUPERVISORY, AND TROUBLE SIGNALS TO THE RESPONDING FIRE DEPARTMENT VIA THE HEAD-END FIRE ALARM RECEIVING EQUIPMENT LOCATED IN BUILDING 1. IT IS NOT ANTICIPATED THAT ANY
MODIFICATIONS WILL BE REQUIRED FOR THE EXISTING FIRE ALARM MONITORING.
FIRE EXTINGUISHERS ARE PROVIDED THROUGHOUT THE WAREHOUSE IN ACCORDANCE WITH NFPA 10. EXTINGUISHERS HAVE BEEN SPACED BASED ON 10-LB MULTIPURPOSE DRY CHEMICAL TYPE EXTINGUISHERS WITH A MAXIMUM TRAVEL DISTANCE FROM ANY POINT ON THE FLOOR TO AN EXTINGUISHER OF 75'.
FIRE ALARM SYSTEM:
THE EXISTING WAREHOUSE BUILDING 14 ADDRESSABLE FIRE ALARM SYSTEM WILL BE MAINTAINED TO THE GREATEST EXTENT POSSIBLE AND MODIFIED AS REQUIRED TO SUPPORT THE RENOVATIONS INCLUDED IN THIS SCOPE. BASED ON SITE INVESTIGATIONS AND AS-BUILT DOCUMENTATION, NO FIRE ALARM CONTROL UNITS ARE PRESENT WITHIN THE WAREHOUSE AND THAT THE SLC AND NAC CIRCUITS THAT SUPPORT BUILDING 14 ORIGINATE WITHIN THE HOSPITAL. AN EXISTING FACP IS LOCATED IN THE CHILLER PLANT IF THE EXISTING CIRCUITS FROM THE BUILDING 1 PANELS ARE NOT CAPABLE OF SUPPORTING THE ADDED/RELOCATED DEVICES WITHIN THE WAREHOUSE. ALL EXISTING DEVICES WITHIN THE BUILDING ARE TO BE REPLACED WITH NEW DEVICES, AND ADDITIONAL DEVICES ARE ADDED AS NECESSARY TO SUPPORT THE BUILDING RECONFIGURATION AS INDICATED ON THE FIRE ALARM SYSTEM SHEETS. NEW DEVICES ARE TO BE TIED INTO THE THE
EXISTING NAC AND SLC CIRCUITS THAT CURRENTLY SUPPORT BUILDING 14.
FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING
ELEMENTS: NFPA 220 TYPE II (000) & IBC TYPE II-B
RATING (HOURS)
(NOTE 4)
BUILDING ELEMENT
0SUPPORTING ONE FLOOR OR ROOF ONLY
0SUPPORTING MORE THAN ONE FLOOR,
COLUMN OR OTHER BEARING WALLS
INTERIOR BEARING
WALL, COLUMNS,
BEAMS, GRIDERS,
TRUSSES, AND ARCHES
0INTERIOR - SUPPORTING MORE THAN ONE
FLOOR, COLUMN, OR OTHER BEARING WALL
NOTES:
1. FIRE-RESISTANCE RATINGS ARE BASED OFF OF IBC TABLES 601 AND 602. SEE LIFE
SAFETY PLANS FOR LOCATIONS OF RATED PARTITIONS FOR ACCOMMODATION OF
LIFE SAFETY CODE REQUIREMENTS.
2. ACCORDING TO EXISTING DESIGN DRAWINGS DATED SEPTEMBER 22,2015, BLDG 26
IS OF TYPE 1-A CONSTRUCTION. THERFORE, THE RATINGS IN THIS TABLE REFLECT
THE FIRE RESISTANCE RATING OF TYPE I(332) CONTRUCTION FROM NFPA 220.
STRUCTURAL FRAME
EXTERIOR; SEE NOTE 1
INTERIOR - SUPPORTING ONE FLOOR OR
ROOF ONLY
INTERIOR NONBEARING WALLS
EXTERIOR BEARING
FLOOR/CEILING ASSEMBLIES
ROOF/CEILING ASSEMBLIES 0
EXTERIOR NONBEARING WALLS; SEE NOTE 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Incandescence Life Safety, Inc.
3575 Ringsby Court, #408, Denver, CO, 80216
Phone:(720) 722-3010
589A4-20-158
IMEG Corp.
15 Sunnen Drive, Suite 104
St. Louis, MO 63143
Phone:(314) 951-2534
BID SET RENOVATE WAREHOUSE FOR
PANDEMIC PREPAREDNESS
HARRY S. TRUMAN MEM. VETERANS HOSPITAL
800 HOSPITAL DR., COLUMBIA MO 65201
BID SET 03/24/2021
Dwg. # of 94
B
IM
/0
-0
C
L H
V A
T ru m a n
R e n o v a te
W a re h o u s e
/0
-0
C L
H V
A R e n o v a te W a re h o u s e
F P
L S
R
.r v t
/2
/2
:4
:0
A
M
LS001
BUILDING AND LIFE SAFETY CODE
ANALYSIS
TGD APS03/24/2021
Applicable Codes & Standards
Code/Standard Code/Standard Authority Code/Standard Name Code/Standard Year
INTERNATIONAL CODE COUNCIL
IBC INTERNATIONAL CODE COUNCIL INTERNATIONAL BUILDING CODE 2018
NATIONAL FIRE PROTECTION ASSOCIATION
NFPA 1 NATIONAL FIRE PROTECTION ASSOCIATION FIRE CODE 2018
NFPA 10 NATIONAL FIRE PROTECTION ASSOCIATION STANDARD FOR PORTABLE FIRE EXTINGUISHERS 2018
NFPA 13 NATIONAL FIRE PROTECTION ASSOCIATION STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2019
NFPA 24 NATIONAL FIRE PROTECTION ASSOCIATION STANDARD FOR THE INSTALLATION OF PRIVATE FIRE SERVICE
MAINS AND THEIR APPURTENANCES
NFPA 70 NATIONAL FIRE PROTECTION ASSOCIATION NATIONAL ELECTRICAL CODE 2020
NFPA 72 NATIONAL FIRE PROTECTION ASSOCIATION NATIONAL FIRE ALARM AND SIGNALING CODE 2019
NFPA 80 NATIONAL FIRE PROTECTION ASSOCIATION STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES 2019
NFPA 90A NATIONAL FIRE PROTECTION ASSOCIATION STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING AND
VENTILATION SYSTEMS
NFPA 101 NATIONAL FIRE PROTECTION ASSOCIATION LIFE SAFETY CODE 2018
NFPA 110 NATIONAL FIRE PROTECTION ASSOCIATION STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS 2019
NFPA 220 NATIONAL FIRE PROTECTION ASSOCIATION STANDARD ON TYPES OF BUILDING CONSTRUCTION 2018
U.S. DEPARTMENT OF VETERANS AFFAIRS
VAFPDM U.S. DEPARTMENT OF VETERANS AFFAIRS FIRE PROTECTION DESIGN MANUAL 7TH EDITION, DECEMBER 2015
VAPSDM U.S. DEPARTMENT OF VETERANS AFFAIRS PHSYICAL SECURITY DESIGN MANUAL FOR VA MISSION CRITICAL
FACILITIES
JANUARY 2015
NOTE: THE FOLLOWING LEGEND IS PROVIDED FOR REFERENCE ONLY; NO NEW FIRE RESISTANCE RATED BARRIERS
ARE PROVIDED AS PART OF THIS SCOPE OF WORK.
Revisions: Date: 5
FD
C P
-0
C P
-0
T D
-0
TD-01
TD-02
T D
-0
T D
-0
FE
F E
F E
FE
FE
FE
CP-02
C P
-0
FE
F E
A
B
C
D
F
E
1 2 3 4 5 6 72.11.1 2.9 3.9
C.6
B.4
VETERANS
CANTEEN
SERVICE
(VCS)
STORAGE
W01
CORRIDOR
WC01A
RECEIVING
DOCK
W02
RECEIVING
BREAKOUT
INSPECTION
(NEW)
W06
OIT
CLOSET
W05B
EQUIPMENT
PREP/
STAGING
(NEW)
W07
SUPERVISOR
OFFICE
(NEW)
W09
STAFF
TOILET
(NEW)
W08
CORRIDOR
WC03
STERILE
CONSUMABLES
(SOFT
GOODS)
STORAGE
W05
PROSTHETICS
STORAGE
W04
DRUG
CACHE-STORAGE
W03A
BULK
ITEMS
STORAGE
W03B
RECEIVING/ISSUE
W10C
RECEIVING/ISSUE
W10A
RECEIVING/ISSUE
W10B
BULK
ITEMS
STORAGE
W03
EXISTING BUILDING SEPARATION TO
REMAIN - OUTSIDE OF SCOPE OF WORK
AREA
AREAS OUTSIDE
OF SCOPE OF
WORK
NARCOTICS
STORAGE
CAGE
W03A1
CORRIDOR
WC04
STAFF
LOUNGE
(NEW)
EW04A
LOGICAL
UNIT
OF
MEASURE
(LUM)
STAGING
ROOM
(NEW)
EW05A
120 / 2
2.1"
36"
340 / 1
1.4"
68"
EXIT SIGNAGE LOCATION
(SEE ELECTRICAL LIGHTING PLANS FOR
EMERGENCY LIGHTING AND EXIT SIGNS)
A
B
C
D
F
E
1 2 32.11.1 2.9 3.9
C.6
B.4
PANDEMIC
STORAGE
W11
CONVENIENCE STAIR AND VERTICAL
OPENING PERMITTED BY NFPA 101 §
42.3.1 & §8.6.9.1
SINGLE MEANS OF EGRESS PERMITTED
FROM UPPER LEVEL BY NFPA 101 §
42.2.4.1(2)
120 / 3
0.3"
36"
SYMBOLS
FOR EXIT LIGHTS AND EMERGENCY LIGHTING, SEE ELECTRICAL DRAWINGS.
FOR FIRE ALARM SYSTEM, SEE FIRE ALARM DRAWINGS; FOR FIRE
SUPPRESSION SYSTEM, SEE FIRE SUPPRESSION DRAWINGS.
THIS BUILDING SHALL BE FULLY SPRINKLERED, SEE FIRE SUPPRESSION
SHEETS FOR DETAILS.
AT FIRE RATED DOOR LOCATIONS FRAMES AND DOORS SHALL BE LABELED
FOR THE INTENDED USE OR EQUIVALENT.
NON-RATED SMOKE PARTITIONS SHALL BE CONSTRUCTED TO LIMIT THE
TRANSFER OF SMOKE. PARTITIONS SHALL EXTEND FROM FLOOR SLAB TO
UNDERSIDE THE FIRE RESISTANCE RATED HORIZONTAL ASSEMBLY ABOVE
(WHERE APPLICABLE). THE SPACE ADJACENT TO THE DECK AND OTHER
SURFACES, AND THE SPACES AROUND PENETRATING ITEMS SHALL BE
CAULKED TO LIMIT THE FREE PASSAGE OF SMOKE.
ASSEMBLY USE - LESS CONCENTRATED WITHOUT FIXED SEATING
TRAVEL PATH TYPE (TD =
TRAVEL DISTANCE, CP =
COMMON PATH, DE = DEAD END)
TD-XX
DISTANCE IDENTIFIER
(SEE SCHEDULE FOR
ACTUAL / ALLOWABLE
TRAVEL DISTANCES)
NO. OF OCC. EXITING
STORAGE USE - IN STORAGE OCCUPANCIES
BUSINESS USE - GENERAL
BUILDING SEPARATION:
2-HOUR FIRE BARRIER (EXISTING)
FE
FIRE EXTINGUISHER LOCATION (10 LB.
MULTI-PURPOSE DRY CHEMICAL)
NOTE: SEE ARCHITECTURAL PLANS FOR
MOUNTING REQUIREMENTS
B / C
D
E
REQ'D. EXIT WIDTH
ACTUAL EXIT WIDTH
NO. OF OCC. /
NO. OF EXIT
STARTING
LOCATION
NOTES
OCCUPANT LOAD USES
OCCUPANCY…