ED101 Amendment 3.pdf
PDF 336 KB Posted
- Solicitation number
- 36C25521R0075
About this file
This document contains details for a federal contract opportunity to renovate a warehouse for pandemic preparedness at the Harry S. Truman Memorial Veterans Hospital in Columbia, Missouri. The renovation work includes raising approximately 6,000 square feet of roof and adding 3,800 square feet of mezzanine storage space. The project will be completed in three phases to allow continued warehouse operations during construction. Architectural, structural, fire protection, mechanical, plumbing, electrical, and technology scopes of work are outlined. The estimated price range for the project is $2,000,000 to $5,000,000. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and utilize the Best Value Lowest Price Technical Acceptable source selection process. The North American Industry Classification Code is 236220 and the small business size standard is $39.5 million. The performance period is up to 330 calendar days from notice to proceed. Interested offerors should monitor the System for Award Management for amendment releases and ensure registration in both SAM and VetBiz VIP databases under the applicable NAICS code. The solicitation package will be available for download on or about April 2, 2021 with a proposal due date of May 7, 2021.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
J
E
E E
E
E
E
E
E E
E
EE
E
E
E
E E
E
E
E
E
E
EEE
A
B
C
D
F
G
E
1 2 3 4 5 6 72.11.1 2.9 3.9
C.6
B.4
12.5
13.4 13.5
11.5
FEED AND COMMUNICATIONS BACK TO THE PARALLELING GEAR
FOR THE "AUTOMATIC TRANSFER SWITCH". CONTRACTOR
SHALL FIELD VERIFY AND COORDINATE THE OPERATIONAL
NEEDS DURING CONSTRUCTION WITH THE OWNER.
+48"
UNIT HEATER
UNIT HEATER
UNIT HEATER
UNIT HEATER
UNIT HEATER
+84"
EWC
DUCTWORK CONNECTION
AT ROOF LIFE
HP-E
WIREMOLD
WIREMOLD
TWO 4" CONDUITS
FOR LOW VOLTAGE.
ONE (1) IS EMPTY
FIREWALL
UNIT HEATER
UNIT HEATER
FED FROM
H13-480-VNR
277/1P, 5KW
(TYP.)
UNIDENTIFIABLE
RECEPTACLE FED
FROM DISCONNECT
SURGE SUPRESSION
SURGE SUPRESSION
DISCONNECT TAPPED ON
SECONDARY OF TRANFORMER FOR
TEMPORARY CONSTRUCTION POWER
(NOT IN USE), APPROX. +120" AFF
LOCATED NEAR
ROOF LINE
a b
EXISTING TR-30 W01
HP-E CONDENSING
UNIT. COORDINATE
WITH MECHANICAL.
UNIT HEATER
EXHAUST FAN
AIR HANDLING UNIT
PRESUMED TO BE FED FROM CHILLER
PLANT PANEL LP1-B1-277VN. E.C. TO
FIELD VERIFY.
5 (TYP.)
EXHAUST FAN
MATERIAL
LIFT
SECURITY PANEL
HP-E
+90"
FORKLIFT
CHARGING
EXISTING LPB-WH-277VE
EXISTING PPB-WH-120VE
UPS WAREHOUSE
BRANCH CIRCUITS
FROM CHILLER PLANT
PANELS TO BE
DEMOLISHED
DOOR DOOR DOOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Incandescence Life Safety, Inc.
3575 Ringsby Court, #408, Denver, CO, 80216
Phone:(720) 722-3010
589A4-20-158
IMEG Corp.
15 Sunnen Drive, Suite 104
St. Louis, MO 63143
Phone:(314) 951-2534
BID SET RENOVATE WAREHOUSE FOR
PANDEMIC PREPAREDNESS
HARRY S. TRUMAN MEM. VETERANS HOSPITAL
800 HOSPITAL DR., COLUMBIA MO 65201
Dwg. # of 94
C R e v it L o c a l F ile s \M
E P
T
.1
V
A T ru m a n W a re h o u s e
C
M a s o n
.J .R y a n .r v t
/2
/2
:1
:2
P
M
ED101
FIRST FLOOR PLAN - ELECTRICAL
DEMOLITION
MARHAR MASRYA03/24/2021
N O R
HT
1/8" = 1'-0"
FIRST FLOOR PLAN - ELECTRICAL DEMOLITION
KEYNOTES:
1. EXISTING OVERHEAD CMU IN CORRIDOR WITH
ELECTRICAL CONDUITS PENETRATING IT,
INCLUDING FEEDS TO WAREHOUSE UNIT
HEATERS AND LPB-14-277VE. FEEDS TO
WAREHOUSE UNIT HEATERS AND A/C
ORIGINATE IN BUILDING 1 ROOM D020, MOTOR
CONTROL CENTER H13-480-VNR. CONDUIT TO
BE MADE SAFE FOR REUSE AND SECTIONS
WITHIN H13-480-VNR FOR WAREHOUSE UNIT
HEATERS AND A/C TO BE MADE SPARES.
2. THE FOLLOWING CIRCUITS IN THE EXISTING
DRUG CACHE ARE FED FROM PANELS IN THE
CHILLER PLANT: PP1-B1-240VE #16,18 FOR "UPS
WAREHOUSE", PP1-B1-240VE #6 FOR
"PHARMACY ALARM-WHS", PP1-B1-120VN #34
FOR "PHARMACY REFR.-WHSE", AND LP1-
B1-277VN #38,40,42 FOR "PHARMACY A/C IN
WAREHOUSE". THESE CIRCUITS ARE TO BE
DEMOLISHED AND THE BREAKERS MADE
SPARE. THESE LOADS WILL BE REFED OUT OF
WAREHOUSE PANELS IN NEW WORK.
3. ALL EXISTING BRANCH CIRCUITRY IN THE
EXISTING DRUG CACHE SHALL BE
DEMOLISHED.
4. DEMOLISH EXISTING LUMINAIRE IN THIS ROOM
AND SALVAGE FOR REUSE DURING NEW
CONSTRUCTION. REFER TO NEW WORK SHEET
EL101 FOR LOCATION.
5. EXISTING SUSPENDED INDUSTRIAL LINEAR
FIXTURES SHOWN AS DEMO SHALL BE
PREPARED FOR REUSE.
6. PHARMACY ALARM-WHS, PRESUMED TO BE
FED FROM CHILLER PLANT PANEL PP1-
B1-240VE. E.C. TO FIELD VERIFY.
7. APPROXIMATE LOCATION OF UPS
WAREHOUSE, PRESUMED TO BE FED FROM
CHILLER PLANT PANEL PP1-B1-240VE. E.C. TO
FIELD VERIFY.
8. CONNECTION TO EXISTING EXHAUST FAN ON
ROOF ABOVE TO BE DEMOLISHED.
COORDINATE WITH M.C.
9. REFER TO V-100 FOR EXISTING "UE" LINE
RUNNING DIAGONALLY BELOW THE BUILDING.
THIS ELECTRIC LINE IS FROM THE ORIGINAL
CONSTRUCTION OF THE CHILLER PLANT. THE
LINE SHALL BE CUT AND CAP JUST WEST OF
THE WAREHOUSE IN APPROXIMATELY THIS
LOCATION.
10. E.C. TO FIELD VERIFY THIS CONNECTION AND
ASSOCIATED DISCONNECT AND COORDINATE
DEMOLITION WITH CONTRACTING OFFICER.
11. EXISTING LIGHT FIXTURES WILL REMAIN IN
ROOMS W04, W05A, AND W06 UNDER BID ITEM
#2. REFER TO ARCHITECTURAL DOCUMENTS
FOR MORE INFORMATION.
SHEET NOTES:
1. COORDINATE PHASING WITH ARCHITECTURAL
PLANS AND OTHER DISCIPLINES.
Revisions: Date:
BID SET 03/24/2021
ADDENDUM NO. 1 4/29/2021
atast Text Box
AMENDMENT #3
atast Text Box 05/07/2021 atast Snapshot
File details come from the government source that posted it. Updated .