S-501 Amendment 3.pdf
PDF 487 KB Posted
- Solicitation number
- 36C25521R0075
About this file
This document provides details for a federal construction contract solicitation to renovate a warehouse for pandemic preparedness. The scope of work involves raising approximately 6,000 square feet of roof and adding 3,800 square feet of mezzanine storage space. It also includes interior renovations, upgrading building systems to current energy codes and installing new data cabling, electrical distribution, and lighting. The estimated price range for the work is $2 million to $5 million. The solicitation number is 36C25521R0075 and will be set aside for Service-Disabled Veteran-Owned Small Businesses. The project completion period is up to 330 calendar days from notice to proceed. The solicitation package and drawings will be available on April 2, 2021 and proposals will be due on or around May 7, 2021. Interested offerors are encouraged to attend the scheduled site visit.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTES:
1. NO CONDUITS ALLOWED IN SLAB.
2. FOR TYPICAL CONSTRUCTION JOINT DETAIL, SEE 1/S-104.
3. SEE GENERAL NOTES FOR ADDITIONAL DECK INFORMATION.
SEE PLAN
"EOD"
VARIES
C L R
LAP PER TYP
EDGE OF DECK
2' - 6"
ADD #4 ( ) @
18" OC WHEN "D"
EXCEEDS 10" IN
DECK PARALLEL TO BEAM
S-501
S-501
12' - 0" MAX
STEEL BEAM
SEE PLAN, TYP
SLAB ON STEEL DECK
SEE PLAN
DECK PERPENDICULAR TO SUPPORTS
TYP
U N
O
/2
S-501
SINGLE STUD PER ROW
NOTES:
1. IF NUMBER OF STUDS IS NOT SHOWN ON PLANS, PROVIDE A SINGLE
ROW OF STUDS SPACED @ 1' - 0" OC. EXCEPT AT W8 & W10 BEAMS,
PROVIDE @ 2' - 0" OC CENTERED OVER BEAM WEB.
2. WHERE BEAM FLANGE THICKNESS IS LESS THAN 0.30", STUD ANCHOR
MUST BE PLACED AT CENTER LINE OF BEAM.
[8]
SLAB ON
STEEL DECK
SEE PLAN &
TYP
DECK PERPENDICULAR TO BEAM
STEEL BEAM
STUD ANCHOR LEGEND
STEEL BEAM
SEE PLAN
3/4"Ø x 4" LONG HEADED STUD @ 4 1/2" OC MIN
AND 24" OC MAX - SEE PLANS AND NOTE 1.
WHERE 1 1/2" SLAB DEPRESSION OCCURS OVER
BEAM OR AT 4 3/4" THICK SLAB, USE 3/4"Ø x 3 1/2".
AT 5 3/4" THICK SLAB, USE 3/4"Ø x 4"
INDICATES NUMBER OF EQUALLY SPACED STUD ANCHORS ON BEAM
(SEE FRAMING PLANS). WHERE NO SYMBOL IS SHOWN, SEE NOTE 1.
ONE SYMBOL INDICATES NUMBER OF STUD ANCHORS EQUALLY
SPACED ALONG FULL LENGTH OF BEAM.
C O
V E
R T
Y P
M
IN
C O
N C
R E
T E
S-501
JOINT
1ST POUR 2ND POUR 1ST POUR 2ND POUR
SEE
BEAM/GIRDER
#4 BAR x 6' - 0" LONG @
12" OC CENTERED OVER
BEAMS/GIRDERS
FRAMING BETWEEN
COLUMNS
DETAIL PARALLEL
TO DECK SPAN
DETAIL PERPENDICULAR
TO DECK SPAN
NOTE:
1. LOCATE JOINT MIN 6" TO
MAX 1' - 6" AWAY FROM
GIRDER CENTERLINE.
NOTE:
1. LOCATE JOINT AT DECK
MIDSPAN BETWEEN BEAMS.
PLAN
1' - 0" MIN LAP LENGTH
OF MESH, TYP
MESH AND REINFORCING
BARS (IF PRESENT) TO
BE CONTINUOUS
THROUGH JOINT, TYP
/4
C
L
S-501
PARALLEL TO DECK DETAIL
PERPENDICULAR TO DECK DETAILS
1/2
DECK TO CLOSURE
PLATE AT EACH
FLUTE
1/8 1@18
1/8 1@18
1/4" BENT PLATE
6" MAX
2" MIN
TYP
2" MIN
SLAB ON STEEL
DECK - SEE
PLAN AND
PROVIDE DECK
CLOSURE, TYP
TYP
6" MAX
2" MIN 3"
1' - 6" MAX
> 6" MIN
S-501
ADDITIONAL
#5 BAR AT
PERIMETER
AT OPEN EDGE OF SLAB, USE A
5/16" EDGE PLATE AND EXTEND
4" TOE-KICK ABOVE SLAB
CONC SLAB ON COMPOSITE
STEEL DECK - SEE PLAN
STEEL BEAM - SEE PLAN
EL (SEE PLAN)
T.O. SLAB
(E) 12" SPLIT-FACE CMU
BLOCK WALL, TO REMAIN
EL (VIF)
T.O. (E) CMU
AT REINFORCED CELLS,
EXTEND SOLID GROUT
TO A MINIMUM DEPTH OF
32" BELOW TOP OF
ORIGINAL WALL
EXTEND CMU WALL WITH
BLOCKS THAT MATCH (E)
TO ELEVATION SHOWN,
REINF WITH #5 @ 24" OC,
INSERTED INTO (E) CMU,
GROUT SOLID ALL CELLS
WITH REINFORCEMENT
CFSF STUD WALL - SEE ARCH
EXTERIOR PANEL
SEE ARCHITECT
(V
IF
#4 BAR x 4'-0" @ 12" OC WITH
180° STANDARD HOOK
3/16 2@12
3/8" BENT PLATE x CONT
1"
EL ( 737' - 8", VWA )
T.O. MASONRY
EOD - SEE PLAN
S-501
BOND BEAM WITH (2) #5
BARS AT TOP COURSE
NOTES:
1. TURN NUT FINGER TIGHT, THEN BACK OFF ONE
QUARTER TURN AND MAR THREADS.
2. SEE 6/S-501 FOR ADDITIONAL INFORMATION.
PL3/8" x 4" x "A" @ 48" OC, LOCATED
AT A SOLID-GROUTED CMU CELL
#5 x CONT
P L A
N
S E
E
M
IN2
E Q
E Q
1/2"Ø x 6" LONG HEADED STUDS @ 12" OC
5/8"Ø EXPANSION ANCHOR WITH
OVERSIZED WASHER IN VERTICAL
LONG-SLOTTED HOLE (SEE NOTE 1)
3/16 2@18
STEEL BEAM - SEE PLAN
EL (VIF)
T.O. (E) CMU
AT REINFORCED CELLS,
EXTEND SOLID GROUT
TO A MINIMUM DEPTH OF
32" BELOW TOP OF
ORIGINAL WALL
EXTEND CMU WALL WITH
BLOCKS THAT MATCH (E)
TO ELEVATION SHOWN,
REINF WITH #5 @ 24" OC,
INSERTED INTO (E) CMU,
GROUT SOLID ALL CELLS
WITH REINFORCEMENT
CFSF STUD WALL - SEE ARCH
EXTERIOR PANEL
SEE ARCHITECT
(V
IF
EL ( 737' - 8", VWA )
T.O. MASONRY
3/16 4 MIN
L6x6x5/16 x 0' - 6" WITH 5/8"Ø EXPANSION
ANCHOR WITH OVERSIZED WASHER, 4"
EMBED, IN VERTICAL LONG-SLOTTED
HOLE @ 48" OC, TYP ABOVE AND BELOW
BEAM (SEE NOTES)
NOTES:
1. TURN NUT FINGER TIGHT, THEN BACK OFF ONE QUARTER TURN AND MAR THREADS.
2. LOCATE ANGLE AND ANCHOR AT A SOLID GROUTED CMU CELL.
3. PLACE THE UPPER ANGLE FIRST, THEN ERECT THE STEEL BEAM AND PLACE THE
LOWER ANGLE LAST.
BOND BEAM WITH (2) #5
BARS AT TOP COURSE
3/16 4 MIN
5/16
NOTE 1
GUSSET
PL3/8"
5/16
NOTE 1
SEE TYPICAL SHEAR
CONNECTION DETAILS
1/4 9
EA SIDE OF
PLATE, NOTE 1
(2) 3/4"Ø ERECTION
BOLTS
STEEL BEAM
SEE PLAN
COLUMN
SEE PLAN
BEAM WHERE
OCCURS - SEE
PLAN
HSS BRACE
SEE ELEVATION
CL BEAM
CL BRACE
T Y
P
M A
X
NOTE:
1. WHERE THE GUSSET PLATE OCCURS AT THE MEZZANINE
LEVEL NEAR THE TOP OF THE EXISTING CMU WALL,
SELECTIVELY REMOVE EXTERIOR CMU BLOCKS AS
REQUIRED TO PERFORM WELDING ON THE BACK SIDE OF
THE CONNECTION. AFTER STEEL IS INSTALLED, REBUILD
THE MASONRY WALL TO THE HEIGHT REQUIRED BY DETAIL
5/S-501.
(2) 3/4"Ø
ERECTION BOLTS
HSS BRACE
SEE ELEVATION
SEE TYP SHEAR
CONNECTION DETAILS
1/4
AT COLUMN
1/4 9
EA SIDE OF
PLATE, NOTE 1
5/16
NOTE 1
STEEL COLUMN
SEE PLAN
STEEL BEAM
SEE PLAN
GUSSET
PL3/8"
5/16
TYP, NOTE 1
STIFFENER PL1/2", TYP
CL
BRACE
CL BEAM
TY
P
1"
M A
X
NOTE:
1. WHERE THE GUSSET PLATE OCCURS AT THE MEZZANINE LEVEL NEAR
THE TOP OF THE EXISTING CMU WALL, SELECTIVELY REMOVE EXTERIOR
CMU BLOCKS AS REQUIRED TO PERFORM WELDING ON THE BACK SIDE
OF THE CONNECTION. AFTER STEEL IS INSTALLED, REBUILD THE
MASONRY WALL TO THE HEIGHT REQUIRED BY DETAIL 5/S-501.
3/4"Ø ERECTION
BOLT
HSS BRACE
SEE ELEVATION
1/4
1/4
STEEL COLUMN
SEE PLAN
GUSSET
PL3/8"
C
L BR
AC
E
8"
BASE PLATE AND
ANCHOR BOLTS -
SEE S-301
2"
TYP1"
1/4 8
3/4"Ø ERECTION
BOLT
HSS BRACE
SEE ELEVATION
1/4
1/4
STEEL COLUMN
SEE PLAN
GUSSET
PL3/8"
C
L BR
AC
E
8"
BASE PLATE AND
ANCHOR BOLTS -
SEE S-301
TYP1" 2"
1/4 8
CONC SLAB ON DECK
SEE PLAN
EQ EQ
/4
10' - 0"
#4 @ 16" OC
STEEL BEAM -
SEE PLAN, TYP
STEEL GIRDER
SEE PLAN
SEE TYP SHEAR
CONNECTION DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Incandescence Life Safety, Inc.
3575 Ringsby Court, #408, Denver, CO, 80216
Phone:(720) 722-3010
589A4-20-158
IMEG Corp.
15 Sunnen Drive, Suite 104
St. Louis, MO 63143
Phone:(314) 951-2534
BID SET RENOVATE WAREHOUSE FOR
PANDEMIC PREPAREDNESS
HARRY S. TRUMAN MEM. VETERANS HOSPITAL
800 HOSPITAL DR., COLUMBIA MO 65201
Dwg. # of 94
C R e v it L o c a l F ile s \S
.1
V
A T ru m a n
W a re h o u s e
C s u jit k u m a r.
n
.p a d h a n
.r v t
-A p r-
:2
:2
P
M
S-501
FRAMING SECTIONS AND DETAILS
MICALB WALLEW03/24/2021
3/4" = 1'-0"
TYPICAL CONCRETE SLAB
ON STEEL DECK DETAILS
1 3/4" = 1'-0"
SHEAR STUD LAYOUT DETAILS
33/4" = 1'-0"
SLAB ON DECK
CONSTRUCTION JOINT DETAILS
2 3/4" = 1'-0"
TYPICAL INTERIOR SLAB EDGE DETAILS
3/4" = 1'-0"
REINFORCED INTERIOR
SLAB EDGE DETAIL
5 1 1/2" = 1'-0"
EDGE OF SLAB DETAIL
6 3/4" = 1'-0"
WALL/BEAM CONNECTION DETAIL
7 3/4" = 1'-0"
BRACE CONNECTION
TO COLUMN FLANGE
3/4" = 1'-0"
BRACE CONNECTION
TO COLUMN WEB
3/4" = 1'-0"
BRACE CONNECTION TO
BASE PLATE/COLUMN WEB
10 3/4" = 1'-0"
BRACE CONNECTION TO
BASE PLATE/COLUMN FLANGE
11 3/4" = 1'-0"
SLAB REINFORCEMENT AT GIRDERS
Revisions: Date:
BID SET 03/24/2021
ADDENDUM NO. 1 04/29/2021
atast Text Box
AMENDMENT #3
atast Text Box 05/07/2021 atast Snapshot