This document provides details for a federal contract opportunity to renovate a warehouse for pandemic preparedness. The scope of work involves raising approximately 6,000 square feet of roof and adding 3,800 square feet of mezzanine storage space. Renovations include upgrading the building envelope, HVAC system, electrical distribution, lighting, and data cabling. A controlled-access room will also be rebuilt. The estimated price range is $2-5 million. Pursuant to applicable laws, this will be solicited as a total set-aside for Service-Disabled Veteran-Owned Small Businesses. The North American Industry Classification Code is 236220. The performance period is up to 330 calendar days. Proposals are due on or about May 7, 2021. Interested offerors should attend the scheduled site visit and monitor the System for Award Management for any amendments.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
m m
M A
X
SIDE VIEW TRAPEZE HANGER FOR UP TO
453KG [1000 LB.] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGERTYPE
1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGERTYPE
43 - SEE SPECIFICATIONS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
PIPE HANGERS
mm [IN] mm
[FT]
mm
[FT]
THRU 20
[THRU 3/4]
[7]
[5]
[1]
[7]
[6]
[1 1/4]
[7]
[7]
[1 1/2]
[9]
[8]
[2]
[10]
[8]
[2 1/2]
[11]
[9]
[3]
[12]
[10]
[4]
[14]
[12]
[5]
[16]
[13]
[6]
[17]
[14]
[8]
[19]
[16]
[10]
[22]
[12]
[23]
[14]
[25]
[16]
[27]
[18]
[28]
[20]
[30]
[24]
[32]
EXPANSION LOOP
LOOP NO.
100-ELI
W H
PIPING CONNECTIONS
COIL
TEST PLUG (TYP.)
REDUCER, IF REQUIRED
WATER RETURN
MANUAL AIR VENT
UNION
CONNECTIONS
(TYP.)
WATER SUPPLY
TERMINAL UNIT WATER COILS -
SHUT OFF VALVE
DRAIN WITH HOSE
CONNECTION
MV
MODULATION CONTROL VALVE
AHU WATER COILS - PIPING CONNECTIONS
SINGLE COIL
WATER COIL
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
DRAIN WHEN
COIL IS NOT SELF-
DRAINING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL REDUCER, IF REQUIRED
DRAIN
FEMV
MV
MV
TI
TEMPERATURE
INDICATION TO ECC SEE
CONTROL DIAGRAM
PREHEAT COIL (HOT WATER) - PIPING CONNECTIONS
NOTE:
SIZE AND SELECT COIL FOR PARALLEL FLOW AND
MINIMUM TUBE WATER VELOCITY OF .91 M/S
[3.0 FPS]
MODULATING
CONTROL
VALVE
HWS
HWR
INLINE PUMP
AV
AUTO. AIR VENT TO DRAIN, TYP
AV
SHUTOFF VALVE
FULL SIZE
CONNECTIONS
TO ALL COIL HEADER
TAPPINGS
BALANCING
DEVICE
PREHEAT
COIL
AIR
MANUAL BYPASS VALVE
PROVIDE
INSULATION
SHIELD
& INSERT FOR ALL
PIPING
(200mm [8"] MIN.)
BAND
43mm [1-5/8"] 12 GAUGE
CHANNEL OR
50x50x6.4mm
[2"X2"X1/4"] ANGLE
15mm [1/2"] DIA.
HANGER RODS
WITH
900mm [36"] MAX.
SPACING ON
EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
NOTES:
1. CHILLED WATER COIL CONTROL VALVE SHALL BE PRESSURE INDEPENDANT TYPE (PICV).
/4
"C W
3/4"CW
E
E
3/4"CW
E
S
REMOVABLE
PIPE SECTION
HUMIDIFIER SUPPLY VALVE
PROVIDED WITH HUMIDIFIER.
HUMIDIFIER DRAIN
VALVE PROVIDED
WITH HUMIDIFIER.
TRAP DEPTH PER
MANUFACTURERS
RECOMMENDATIONS.
TO MAKEUP WATER
FOR HEAT EXCHANGER
FLOOR DRAIN
WITH FUNNEL.
ROUTE TO
FLOOR
DRAIN.
TRAP DEPTH PER
MANUFACTURERS
RECOMMENDATIONS.
INTERLOCK HUMIDIFIER DRAIN
VALVE AND CW VALVE TO
OPERATE IN UNISON. BALANCE
CW TO RESULT IN A MIXED WATER
TEMPERATURE BELOW 140°F.
ROUTE TO
FLOOR DRAIN.
BFP
REMOVABLE LID
STEAM TO STEAM HUMIDIFIER.
HUMIDIFIER
MANIFOLD
SUMMER SHUTOFF
VALVE BY
CONTROLS
CONTRACTOR.
SLOPE BACK TO
STEAM RISER
HUMIDIFIER STEAM CONTROL
VALVE PROVIDED WITH
HUMIDIFIER.
INSTALL STRAINER IN
HORIZONTAL POSITION TO
PREVENT CONDENSATE
FROM POOLING. (TYP.)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
Calvin rchitects, P.C.L 3705 North 200th Street
Elkhorn, Nebraska 68022
Phone: 402.291.6941 Fax: 402.291.9193
AH. INZ
Incandescence Life Safety, Inc.
3575 Ringsby Court, #408, Denver, CO, 80216
Phone:(720) 722-3010
589A4-20-158
IMEG Corp.
15 Sunnen Drive, Suite 104
St. Louis, MO 63143
Phone:(314) 951-2534
BID SET RENOVATE WAREHOUSE FOR
PANDEMIC PREPAREDNESS
HARRY S. TRUMAN MEM. VETERANS HOSPITAL
800 HOSPITAL DR., COLUMBIA MO 65201
Dwg. # of 94
C R e v it L o c a l F ile s \M
E P
T
.1
V A
T ru m a n W a re h o u s e
C
R u s s e ll.
J .A rn e s o n
.r v t
/2
/2
:0
:5
P
M
M-301
MECHANICAL DETAILS
JASSNE ANUSHA03/24/2021
NO SCALE
HUMIDIFIER (STEAM TO STEAM) DETAIL
Revisions: Date:
BID SET 03/24/2021
ADDENDUM NO. 1 4/29/2021
atast Text Box
AMENDMENT #3
atast Text Box 05/07/2021 atast Snapshot