M-301 Amendment 3.pdf

PDF 233 KB Posted

Attached to
Z2DA--Renovate Warehouse for Pandemic Preparedness PN: 589A4-20-158
Solicitation number
36C25521R0075
Issued by

About this file

This document provides details for a federal contract opportunity to renovate a warehouse for pandemic preparedness. The scope of work involves raising approximately 6,000 square feet of roof and adding 3,800 square feet of mezzanine storage space. Renovations include upgrading the building envelope, HVAC system, electrical distribution, lighting, and data cabling. A controlled-access room will also be rebuilt. The estimated price range is $2-5 million. Pursuant to applicable laws, this will be solicited as a total set-aside for Service-Disabled Veteran-Owned Small Businesses. The North American Industry Classification Code is 236220. The performance period is up to 330 calendar days. Proposals are due on or about May 7, 2021. Interested offerors should attend the scheduled site visit and monitor the System for Award Management for any amendments.

View the file

Other files

File Type Posted
AD102 Amendment 3.pdf PDF
MD101 Amendment 3.pdf PDF
EL101 Amendment 3.pdf PDF
EP101 Amendment 3.pdf PDF
S-501 Amendment 3.pdf PDF
AF101 Amendment 3.pdf PDF
PD101 Amendment 3.pdf PDF
M-102 Amendment 3.pdf PDF
M-101 Amendment 3.pdf PDF
AE101 Amendment 3.pdf PDF
AE401 Amendment 3.pdf PDF
M-500 Amendment 3.pdf PDF
P-101 Amendment 3.pdf PDF
S-301 Amendment 3.pdf PDF
PH101 Amendment 3.pdf PDF
AF502 Amendment 3.pdf PDF
ED101 Amendment 3.pdf PDF
11 00 00 Beam Scale Cut Sheet - Amendment 3.pdf PDF
AC102 Amendment 3.pdf PDF
31 62 00 Driven or Drilled Micropiles - Amendment 3.pdf PDF
36C25521R0075 0003.docx DOCX document
01 35 26 pgs 12-13 - Amendment 3.pdf PDF
AD101 Amendment 3.pdf PDF
PH103 Amendment 3.pdf PDF
S-001 Amendment 3.pdf PDF
00 01 10 pg 4 - Amendment 3.pdf PDF
ATTENDANCE ROSTER.pdf PDF
36C25521R0075 0002.docx DOCX document
589A4-20-158 GeoTech Report.pdf PDF
36C25521R0075 0001.docx DOCX document
Drawings 589A4-20-158 VOL 3- 1 page.pdf PDF
36C25521R0075_1.docx DOCX document
Drawings -589A4-20-158 VOL 2- 2 pages.pdf PDF
Drawings-589A4-20-158 VOL 4-1 page.pdf PDF
S02-Specifications 589A4-20-158- Volume 1 -630 pages.pdf PDF
S02-Specifications 589A4-20-158 - Volume 2 Divs 21-48- 848 pages.pdf PDF
Drawings 589A4-20-158 VOL 1- 90 pages.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

m m

M A

X

SIDE VIEW TRAPEZE HANGER FOR UP TO

453KG [1000 LB.] UNIFORM LOAD

ADJUSTABLE CLEVIS HANGERTYPE

1 - SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGERTYPE

43 - SEE SPECIFICATIONS

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

PIPE HANGERS

mm [IN] mm

[FT]

mm

[FT]

THRU 20

[THRU 3/4]

[7]

[5]

[1]

[7]

[6]

[1 1/4]

[7]

[7]

[1 1/2]

[9]

[8]

[2]

[10]

[8]

[2 1/2]

[11]

[9]

[3]

[12]

[10]

[4]

[14]

[12]

[5]

[16]

[13]

[6]

[17]

[14]

[8]

[19]

[16]

[10]

[22]

[12]

[23]

[14]

[25]

[16]

[27]

[18]

[28]

[20]

[30]

[24]

[32]

EXPANSION LOOP

LOOP NO.

100-ELI

W H

PIPING CONNECTIONS

COIL

TEST PLUG (TYP.)

REDUCER, IF REQUIRED

WATER RETURN

MANUAL AIR VENT

UNION

CONNECTIONS

(TYP.)

WATER SUPPLY

TERMINAL UNIT WATER COILS -

SHUT OFF VALVE

DRAIN WITH HOSE

CONNECTION

MV

MODULATION CONTROL VALVE

AHU WATER COILS - PIPING CONNECTIONS

SINGLE COIL

WATER COIL

AIR VENT

WHEN COIL

IS NOT

SELF-VENTING

DRAIN WHEN

COIL IS NOT SELF-

DRAINING

TEST PLUG

(TYP.)

PIPE HANGER SHALL SUPPORT

PIPING INDEPENDENT OF COIL REDUCER, IF REQUIRED

DRAIN

FEMV

MV

MV

TI

TEMPERATURE

INDICATION TO ECC SEE

CONTROL DIAGRAM

PREHEAT COIL (HOT WATER) - PIPING CONNECTIONS

NOTE:

SIZE AND SELECT COIL FOR PARALLEL FLOW AND

MINIMUM TUBE WATER VELOCITY OF .91 M/S

[3.0 FPS]

MODULATING

CONTROL

VALVE

HWS

HWR

INLINE PUMP

AV

AUTO. AIR VENT TO DRAIN, TYP

AV

SHUTOFF VALVE

FULL SIZE

CONNECTIONS

TO ALL COIL HEADER

TAPPINGS

BALANCING

DEVICE

PREHEAT

COIL

AIR

MANUAL BYPASS VALVE

PROVIDE

INSULATION

SHIELD

& INSERT FOR ALL

PIPING

(200mm [8"] MIN.)

BAND

43mm [1-5/8"] 12 GAUGE

CHANNEL OR

50x50x6.4mm

[2"X2"X1/4"] ANGLE

15mm [1/2"] DIA.

HANGER RODS

WITH

900mm [36"] MAX.

SPACING ON

EACH

CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9 PSF

MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

NOTES:

1. CHILLED WATER COIL CONTROL VALVE SHALL BE PRESSURE INDEPENDANT TYPE (PICV).

/4

"C W

3/4"CW

E

E

3/4"CW

E

S

REMOVABLE

PIPE SECTION

HUMIDIFIER SUPPLY VALVE

PROVIDED WITH HUMIDIFIER.

HUMIDIFIER DRAIN

VALVE PROVIDED

WITH HUMIDIFIER.

TRAP DEPTH PER

MANUFACTURERS

RECOMMENDATIONS.

TO MAKEUP WATER

FOR HEAT EXCHANGER

FLOOR DRAIN

WITH FUNNEL.

ROUTE TO

FLOOR

DRAIN.

TRAP DEPTH PER

MANUFACTURERS

RECOMMENDATIONS.

INTERLOCK HUMIDIFIER DRAIN

VALVE AND CW VALVE TO

OPERATE IN UNISON. BALANCE

CW TO RESULT IN A MIXED WATER

TEMPERATURE BELOW 140°F.

ROUTE TO

FLOOR DRAIN.

BFP

REMOVABLE LID

STEAM TO STEAM HUMIDIFIER.

HUMIDIFIER

MANIFOLD

SUMMER SHUTOFF

VALVE BY

CONTROLS

CONTRACTOR.

SLOPE BACK TO

STEAM RISER

HUMIDIFIER STEAM CONTROL

VALVE PROVIDED WITH

HUMIDIFIER.

INSTALL STRAINER IN

HORIZONTAL POSITION TO

PREVENT CONDENSATE

FROM POOLING. (TYP.)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

Calvin rchitects, P.C.L 3705 North 200th Street

Elkhorn, Nebraska 68022

Phone: 402.291.6941 Fax: 402.291.9193

AH. INZ

Incandescence Life Safety, Inc.

3575 Ringsby Court, #408, Denver, CO, 80216

Phone:(720) 722-3010

589A4-20-158

IMEG Corp.

15 Sunnen Drive, Suite 104

St. Louis, MO 63143

Phone:(314) 951-2534

BID SET RENOVATE WAREHOUSE FOR

PANDEMIC PREPAREDNESS

HARRY S. TRUMAN MEM. VETERANS HOSPITAL

800 HOSPITAL DR., COLUMBIA MO 65201

Dwg. # of 94

C R e v it L o c a l F ile s \M

E P

T

.1

V A

T ru m a n W a re h o u s e

C

R u s s e ll.

J .A rn e s o n

.r v t

/2

/2

:0

:5

P

M

M-301

MECHANICAL DETAILS

JASSNE ANUSHA03/24/2021

NO SCALE

HUMIDIFIER (STEAM TO STEAM) DETAIL

Revisions: Date:

BID SET 03/24/2021

ADDENDUM NO. 1 4/29/2021

atast Text Box

AMENDMENT #3

atast Text Box 05/07/2021 atast Snapshot

File details come from the government source that posted it. Updated .