About this file

This document contains a request for proposal for operations and maintenance support services for a federal facility. The solicitation seeks proposals to provide operation and maintenance services for the Eastern Regional Research Center located in Wyndmoor, Pennsylvania. Interested offerors are invited to attend a pre-proposal conference on March 8, 2024 and participate in a site visit on March 11, 2024 to learn more about the requirement. Proposals are due by the date specified in the solicitation. The NAICS code for this procurement is 561210 and the small business size standard is $47 million.

View the file

Other files

File Type Posted
12305B24R00140004.pdf PDF
Schedule B - Rev. 3 - 21MAR2024.xlsx XLSX spreadsheet
Exhibit E.7 – Past Performance Questionnaire.docx DOCX document
Schedule B - Rev. 2 - 19MAR2024.xlsx XLSX spreadsheet
12305B24R00140003.pdf PDF
Pre-Proposal Conference - Recording - 12305B24R0014 ERRC OandM.mp4 MP4 file
Pre-Proposal Conference Slides - 12305B24R0014 ERRC OandM.pptx PPTX presentation
Pre-Proposal Conference Minutes - 12305B24R0014 ERRC OandM.pdf PDF
12305B24R00140002.pdf PDF
12305B24R00140001.pdf PDF
Attachment A.1.0 – Maps and Floor Plans for the ERRC.PDF PDF
Schedule B.xlsx XLSX spreadsheet
Attachment A.6.6.9 – Special Environmental Rooms.pdf PDF
Attachment R.7.3.2 - Sample Report.pdf PDF
Attachment A.2.4 – Historical Pricing Data.pdf PDF
Attachment A.1.3 – Available Government Property and Materials.pdf PDF
Attachment R.S - Report and Submittal Summary.pdf PDF
Attachment A.3.2.2.b – Declaration for Federal Employment OF 306.pdf PDF
Attachment S - Submittal Registry.pdf PDF
Attachment A.6.4 – List of Elevators and Hoisting Devices.pdf PDF
Exhibit E.6 - Collective Bargaining Agreement Wage Determination.pdf PDF
Attachment A.6.3.1.2 - Door Security and Intrusion Detection System Equipment.pdf PDF
Attachment A.1.4.1 – Government Furnished Services via Contracts.pdf PDF
Attachment A.2.2.2 – Preventive Maintenance Schedule.pdf PDF
Exhibit E.2 - QASP Attachment A – Functional Assessment Plan.pdf PDF
Attachment A.2.2.1 – Historically Maintained Equipment.pdf PDF
Attachment R.4.3 - Sample Report.pdf PDF
Attachment A.7.1 – Key Request Form.pdf PDF
Attachment R.3.1.2 - Sample Report.pdf PDF
Exhibit E.1 - Quality Assurance Surveillance Plan.pdf PDF
Attachment R.2.0 - Sample Report - Combined.pdf PDF
Attachment A.3.2.2.a – REE NEIS PII Sheet.pdf PDF
Attachment A.7.3.4 – Housekeeping Matrix.pdf PDF
Attachment A.2.1 – Work Order History.pdf PDF
Exhibit E.5 - Collective Bargaining Agreement.pdf PDF
Exhibit E.3 - Construction Wage Rate Requirements Statute.pdf PDF
Attachment A.1.1 – Listing of Applicable Codes, Regulations and Documents.pdf PDF
Attachment R.4.1.4 - Sample Report.pdf PDF
Attachment A.1.2 – Listing of Known Confined Spaces.pdf PDF
Attachment A.6.6.4 – List of Pressure Vessels.pdf PDF
12305B24R0014.pdf PDF
Attachment A.4.1 – Historically Subcontracted Work - Contractor-Subcontracted.pdf PDF
Exhibit E.4 - Service Contract Labor Standards Wage Determination.pdf PDF
Attachment A.7.3.4.2 – Schedule of Flooring Surfaces.pdf PDF
Attachment A.7.3.1 – ARS 45 Annual Vehicle Inspection Checklist.pdf PDF
Attachment R.6.4 - Sample Report.pdf PDF
Attachment A.3.3 – Inventory of Government Owned Vehicles.pdf PDF
Attachment 1 - Performance Work Statement ERRC OM - 08JAN24.pdf PDF
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PUBLIC BUILDINGS SERVICE

INSPECTION REPORT OF

BOILERS

(Make separate report for each boiler)

CITY AND STATE

Wyndmoor, PA

BUILDING

U.S. Department of Agriculture, 600 E. Mermaid Lane

REGION NUMBER

HEADQUARTERS DATE OF INSPECTION

NUMBER OF BOILERS IN BUILDING SUBJECT TO INSPECTION PLANT BOILER NUMBER

#1 Boiler – Service Building

MANUFACTURER’S NAME

Cleaver Brooks

MANUFACTURER’S NUMBER

NB 15706

TYPE OF BOILER

STEAM PACKAGE TYPE FIRE TUBE H.R.T.

HOT WATER SCOTCH FIRE TUBE FIREBOX

WATER TUBE

Flex Tube C.I. SECTIONAL OTHER (Specify type)

*TYPE OF SETTING

Steel beam to concrete

*DATE MANUFACTURED

*DATE INSTALLED THIS LOCATION

TYPE OF CONSTRUCTION (Riveted, welded, etc.)

Welded steel

MATERIAL AND GAUGE OF SHELL AND TUBES

Carbon steel

NUMBER AND SIZE OF SECTIONS FOR C.I. BOILER

*STATE SERVICE (Lighting, pumping, heating, power, etc.)

HP Steam Boiler - Heat and Process

MANUFACTURER’S RATING

CAPACITY 7650 pph (BHP, LB/HR OR MBH)

DESIGN PRESSURE 150 LBS./SQ. IN.

MAXIMUM ALLOWABLE WORKING PRESSURE 150 LBS./SQ. IN.

MAXIMUM PRESSURE UNDER WHICH BOILER IS NOW OPERATED

LBS./SQ. IN.

DATE OF LAST INSPECTION

November

NAME AND TITLE OF LAST INSPECTOR

FUEL USED

COAL OIL (Sec #6) GAS (Primary) OTHER (Specify)

GENERAL CONDITION OF BOILER AND SETTING

Satisfactory

HAS BOILER BEEN RECEIVING FEED WATER TREATMENT?

YES NO

DOES BOILER CONTAIN OIL?

YES NO

DOES BOILER CONTAIN GREASE?

YES NO

DOES BOILER CONTAIN SCALE?

YES NO

WAS EMBRITTLEMENT, GROOVING, PITTING, OR CORROSION APPARENT?

YES NO

DOES BOILER SHOW SIGNS OF BAGS OR BLISTERS?

YES NO

TO WHAT EXTENT IS FOREIGN MATTER OR DETERIORATION PRESENT?

Satisfactory

HYDROSTATIC PRESSURE OF

N/A LBS./SQ. IN. WAS APPLIED

DID BOILER SHOW DEFECTS UNDER THIS PRESSURE?

YES NO

GENERAL SERVICES ADMINISTRATION *To be reported at first inspection only GSA FORM 349 REVISED PAGE 1

SAMPLE

ERRC OPERATIONS AND MAINTENANCE CONTRACT

ATTACHMENT R.6.6.1.1 SAMPLE BOILER AND PRESSURE VESSAL REPORT

STATE CONDITION OF PRESSURE AND/OR TEMPERATURE RELIEF VALVES

2 - 1¼” - Apollo set at 150 psi - total capacity 8,480 pph – good.

GENERAL EXTERNAL CONDITION OF BOILER AND OPERATING CONTROLS

Satisfactory. Controls / cutouts – good.

CONDITION OF BOILER GAUGES AND THERMOMETERS

Satisfactory

CONDITION OF GAUGE GLASS, IF FITTED

Satisfactory

CONDITION OF BOTTOM BLOW-OFF VALVES AND PIPE CONNECTIONS

Satisfactory

HAS ADEQUATE PROVISION BEEN MADE FOR FIRE FIGHTING?

Yes

HOW DO PERSONNEL IN CHARGE OF THIS EQUIPMENT GRADE?

COMPETENT DOUBTFUL INCOMPETENT

IN YOUR OPINION IS THIS BOILER IN A SAFE CONDITION TO BE OPERATED?

YES NO

IF ANSWER TO PREVIOUS QUESTION IS NO, THE INSPECTOR WILL NOTIFY THE CUSTODIAN OR BUILDING SUPERINTENDENT, IMMEDIATELY IN WRITING, NOT TO USE SAME AND GIVE COMPLETE DETAILS TO REGIONAL OFFICE BY WIRE.

RECOMMENDATIONS AND REMARKS BY THE INSPECTOR (Include alterations, additions or repairs considered necessary)

New installation – 2015 (Replaces Kewanee NB 41091) Firesides – excellent – front cone and rear wall – good. Tubes straight and clean.

Setting / piping / fittings – all good.

Boiler is fitted with an economizer.

Note: Moderate scale noted in 2017 – new softeners and chemical treatment appear to be diminishing the scale – continue. 2021 – problems corrected. Watersides satisfactory.

External inspection conducted – conditions very good.

No pitting or corrosion noted.

ATLANTIC SERVICES, INC. 410-836-7727 #1 NB 15706

SIGNATURE OF INSPECTOR

TITLE OF INSPECTOR

Inspector for Atlantic Services Inc.

RECOMMENDATIONS AND REMARKS BY LOCAL OFFICER OR ENGINEER IN CHARGE

SIGNATURE OF OFFICER IN CHARGE

OFFICIAL TITLE OF OFFICER IN CHARGE

GENERAL SERVICES ADMINISTRATION GSA FORM 349 REVISED PAGE 2

ERRC OPERATIONS AND MAINTENANCE CONTRACT

BOILERS

(Make separate report for each boiler)

CITY AND STATE

Wyndmoor, PA

BUILDING

U.S. Department of Agriculture, 600 E. Mermaid Lane

REGION NUMBER

HEADQUARTERS DATE OF INSPECTION

NUMBER OF BOILERS IN BUILDING SUBJECT TO INSPECTION PLANT BOILER NUMBER

#2 Boiler – Service Building

MANUFACTURER’S NAME

Cleaver Brooks

MANUFACTURER’S NUMBER

NB 15733

TYPE OF BOILER

STEAM PACKAGE TYPE FIRE TUBE H.R.T.

HOT WATER SCOTCH FIRE TUBE FIREBOX

WATER TUBE

Flex Tube C.I. SECTIONAL OTHER (Specify type)

*TYPE OF SETTING

Steel beam to concrete

*DATE MANUFACTURED

*DATE INSTALLED THIS LOCATION

TYPE OF CONSTRUCTION (Riveted, welded, etc.)

Welded steel

MATERIAL AND GAUGE OF SHELL AND TUBES

Carbon steel

NUMBER AND SIZE OF SECTIONS FOR C.I. BOILER

*STATE SERVICE (Lighting, pumping, heating, power, etc.)

HP Steam Boiler - Heat and Process

MANUFACTURER’S RATING

CAPACITY 7650 pph (BHP, LB/HR OR MBH)

DESIGN PRESSURE 150 LBS./SQ. IN.

MAXIMUM ALLOWABLE WORKING PRESSURE 150 LBS./SQ. IN.

MAXIMUM PRESSURE UNDER WHICH BOILER IS NOW OPERATED

LBS./SQ. IN.

DATE OF LAST INSPECTION

November

NAME AND TITLE OF LAST INSPECTOR

FUEL USED

COAL OIL (Sec #6) GAS (Primary) OTHER (Specify)

GENERAL CONDITION OF BOILER AND SETTING

Satisfactory

HAS BOILER BEEN RECEIVING FEED WATER TREATMENT?

YES NO

DOES BOILER CONTAIN OIL?

YES NO

DOES BOILER CONTAIN GREASE?

YES NO

DOES BOILER CONTAIN SCALE?

YES NO

WAS EMBRITTLEMENT, GROOVING, PITTING, OR CORROSION APPARENT?

YES NO

DOES BOILER SHOW SIGNS OF BAGS OR BLISTERS?

YES NO

TO WHAT EXTENT IS FOREIGN MATTER OR DETERIORATION PRESENT?

Satisfactory

HYDROSTATIC PRESSURE OF

N/A LBS./SQ. IN. WAS APPLIED

DID BOILER SHOW DEFECTS UNDER THIS PRESSURE?

YES NO

GENERAL SERVICES ADMINISTRATION *To be reported at first inspection only GSA FORM 349 REVISED PAGE 1

ERRC OPERATIONS AND MAINTENANCE CONTRACT

2 - 1¼” Apollo set at 150 psi - total capacity 8,480 pph – good.

GENERAL EXTERNAL CONDITION OF BOILER AND OPERATING CONTROLS

Satisfactory. Controls / cutouts – good.

CONDITION OF BOILER GAUGES AND THERMOMETERS

Satisfactory

CONDITION OF GAUGE GLASS, IF FITTED

Satisfactory

CONDITION OF BOTTOM BLOW-OFF VALVES AND PIPE CONNECTIONS

Satisfactory

HAS ADEQUATE PROVISION BEEN MADE FOR FIRE FIGHTING?

Yes

HOW DO PERSONNEL IN CHARGE OF THIS EQUIPMENT GRADE?

COMPETENT DOUBTFUL INCOMPETENT

IN YOUR OPINION IS THIS BOILER IN A SAFE CONDITION TO BE OPERATED?

YES NO

IF ANSWER TO PREVIOUS QUESTION IS NO, THE INSPECTOR WILL NOTIFY THE CUSTODIAN OR BUILDING SUPERINTENDENT, IMMEDIATELY IN WRITING, NOT TO USE SAME AND GIVE COMPLETE DETAILS TO REGIONAL OFFICE BY WIRE.

RECOMMENDATIONS AND REMARKS BY THE INSPECTOR (Include alterations, additions or repairs considered necessary)

New installation – 2015 (Replaces Kewanee NB 41091) Firesides – excellent – front cone and rear wall – good. Tubes straight and clean.

Setting / piping / fittings – all good.

Boiler is fitted with an economizer.

Note: Moderate scale noted in 2017 – new softeners and chemical treatment appear to be diminishing the scale – continue. 2020 – unit – good. Watersides – clear.

2021 – Good overall - maintain chemical treatment and proper blowdown.

External inspection conducted – conditions very good.

No pitting or corrosion noted.

ATLANTIC SERVICES, INC. 410-836-7727 #2 NB 15733

SIGNATURE OF INSPECTOR

TITLE OF INSPECTOR

Inspector for Atlantic Services Inc.

RECOMMENDATIONS AND REMARKS BY LOCAL OFFICER OR ENGINEER IN CHARGE

SIGNATURE OF OFFICER IN CHARGE

OFFICIAL TITLE OF OFFICER IN CHARGE

GENERAL SERVICES ADMINISTRATION GSA FORM 349 REVISED PAGE 2

ERRC OPERATIONS AND MAINTENANCE CONTRACT

BOILERS

(Make separate report for each boiler)

CITY AND STATE

Wyndmoor, PA

BUILDING

U.S. Department of Agriculture, 600 E. Mermaid Lane

REGION NUMBER

HEADQUARTERS DATE OF INSPECTION

09/16/2021

NUMBER OF BOILERS IN BUILDING SUBJECT TO INSPECTION PLANT BOILER NUMBER

#3 - Service Building

MANUFACTURER’S NAME

Kewanee

MANUFACTURER’S NUMBER

SN- 1991 NB 47554

TYPE OF BOILER

STEAM PACKAGE TYPE FIRE TUBE H.R.T.

HOT WATER SCOTCH FIRE TUBE FIREBOX Wetback design

WATER TUBE C.I. SECTIONAL OTHER (Specify type)

*TYPE OF SETTING

*DATE MANUFACTURED

*DATE INSTALLED THIS LOCATION

TYPE OF CONSTRUCTION (Riveted, welded, etc.)

Welded steel

MATERIAL AND GAUGE OF SHELL AND TUBES

Carbon steel

NUMBER AND SIZE OF SECTIONS FOR C.I. BOILER

*STATE SERVICE (Lighting, pumping, heating, power, etc.)

HP Steam Boiler - Heat and Process

MANUFACTURER’S RATING

CAPACITY 13390 lb/hr (BHP, LB/HR OR MBH)

DESIGN PRESSURE 150 LBS./SQ. IN.

MAXIMUM ALLOWABLE WORKING PRESSURE 150 LBS./SQ. IN.

MAXIMUM PRESSURE UNDER WHICH BOILER IS NOW OPERATED

120 LBS./SQ. IN.

DATE OF LAST INSPECTION

September 2020

NAME AND TITLE OF LAST INSPECTOR

Richard Buck

FUEL USED

COAL OIL (Sec #6) GAS (Primary) OTHER (Specify)

GENERAL CONDITION OF BOILER AND SETTING

Satisfactory

HAS BOILER BEEN RECEIVING FEED WATER TREATMENT?

YES NO

DOES BOILER CONTAIN OIL?

YES NO

DOES BOILER CONTAIN GREASE?

** YES NO

DOES BOILER CONTAIN SCALE?

** YES NO

WAS EMBRITTLEMENT, GROOVING, PITTING, OR CORROSION APPARENT?

YES NO

DOES BOILER SHOW SIGNS OF BAGS OR BLISTERS?

YES NO

TO WHAT EXTENT IS FOREIGN MATTER OR DETERIORATION PRESENT?

See notes

HYDROSTATIC PRESSURE OF

0 LBS./SQ. IN. WAS APPLIED

DID BOILER SHOW DEFECTS UNDER THIS PRESSURE?

YES NO

GENERAL SERVICES ADMINISTRATION *To be reported at first inspection only GSA FORM 349 REVISED PAGE 1

ERRC OPERATIONS AND MAINTENANCE CONTRACT

1 - 1½” Kunkle set at 150 psi, capacity 6596 lb/hr and 1 - 2” Conbracco set at 150 psi, capacity 10,851 lb/hr.

GENERAL EXTERNAL CONDITION OF BOILER AND OPERATING CONTROLS

Satisfactory

CONDITION OF BOILER GAUGES AND THERMOMETERS

Satisfactory

CONDITION OF GAUGE GLASS, IF FITTED

Satisfactory

CONDITION OF BOTTOM BLOW-OFF VALVES AND PIPE CONNECTIONS

Satisfactory

HAS ADEQUATE PROVISION BEEN MADE FOR FIRE FIGHTING?

Yes

HOW DO PERSONNEL IN CHARGE OF THIS EQUIPMENT GRADE?

COMPETENT DOUBTFUL INCOMPETENT

IN YOUR OPINION IS THIS BOILER IN A SAFE CONDITION TO BE OPERATED?

YES NO

IF ANSWER TO PREVIOUS QUESTION IS NO, THE INSPECTOR WILL NOTIFY THE CUSTODIAN OR BUILDING SUPERINTENDENT, IMMEDIATELY IN WRITING, NOT TO USE SAME AND GIVE COMPLETE DETAILS TO REGIONAL OFFICE BY WIRE.

RECOMMENDATIONS AND REMARKS BY THE INSPECTOR (Include alterations, additions or repairs considered necessary)

Overall – good – tubes straight and clean / cone refractory – good condition.

Watersides – no evidence of pitting or corrosion.

Note – A. Low end – some scale deposits in wetback section – no change since 2015.

B. Pull low end front hand-holes and flush; some collected scale noted – to be flushed out.

C. unit has run very little in 2020.

No adverse conditions noted at time of inspection.

Internal inspection conducted – 09/2021.

ATLANTIC SERVICES, INC. 410-836-7727 #3 – NB 47554

SIGNATURE OF INSPECTOR

TITLE OF INSPECTOR

Inspector for Atlantic Services Inc.

RECOMMENDATIONS AND REMARKS BY LOCAL OFFICER OR ENGINEER IN CHARGE

SIGNATURE OF OFFICER IN CHARGE

OFFICIAL TITLE OF OFFICER IN CHARGE

GENERAL SERVICES ADMINISTRATION GSA FORM 349 REVISED PAGE 2

ERRC OPERATIONS AND MAINTENANCE CONTRACT

BOILERS

(Make separate report for each boiler)

CITY AND STATE

Wyndmoor, PA

BUILDING

U.S. Department of Agriculture, 600 E. Mermaid Lane

REGION NUMBER

HEADQUARTERS DATE OF INSPECTION

NUMBER OF BOILERS IN BUILDING SUBJECT TO INSPECTION PLANT BOILER NUMBER

#4 - Service Building

MANUFACTURER’S NAME

Cleaver Brooks

MANUFACTURER’S NUMBER

NB 17154 S/N T2062-1-1

TYPE OF BOILER

STEAM PACKAGE TYPE FIRE TUBE H.R.T.

HOT WATER SCOTCH FIRE TUBE FIREBOX Wetback design

WATER TUBE C.I. SECTIONAL OTHER (Specify type)

*TYPE OF SETTING

Steel to concrete pad

*DATE MANUFACTURED

*DATE INSTALLED THIS LOCATION

TYPE OF CONSTRUCTION (Riveted, welded, etc.)

Welded steel

MATERIAL AND GAUGE OF SHELL AND TUBES

Carbon steel

NUMBER AND SIZE OF SECTIONS FOR C.I. BOILER

*STATE SERVICE (Lighting, pumping, heating, power, etc.)

HP Steam Boiler - Heat and Process

MANUFACTURER’S RATING

CAPACITY 13800 lb/hr (BHP, LB/HR OR MBH)

DESIGN PRESSURE 150 LBS./SQ. IN.

MAXIMUM ALLOWABLE WORKING PRESSURE 150 LBS./SQ. IN.

MAXIMUM PRESSURE UNDER WHICH BOILER IS NOW OPERATED

LBS./SQ. IN.

DATE OF LAST INSPECTION

September

NAME AND TITLE OF LAST INSPECTOR

FUEL USED

COAL OIL (Sec #6) GAS (Primary) OTHER (Specify)

GENERAL CONDITION OF BOILER AND SETTING

Satisfactory

HAS BOILER BEEN RECEIVING FEED WATER TREATMENT?

YES NO

DOES BOILER CONTAIN OIL?

YES NO

DOES BOILER CONTAIN GREASE?

** YES NO

DOES BOILER CONTAIN SCALE?

** YES NO

WAS EMBRITTLEMENT, GROOVING, PITTING, OR CORROSION APPARENT?

YES NO

DOES BOILER SHOW SIGNS OF BAGS OR BLISTERS?

YES NO

TO WHAT EXTENT IS FOREIGN MATTER OR DETERIORATION PRESENT?

See notes

HYDROSTATIC PRESSURE OF

0 LBS./SQ. IN. WAS APPLIED

DID BOILER SHOW DEFECTS UNDER THIS PRESSURE?

YES NO

GENERAL SERVICES ADMINISTRATION *To be reported at first inspection only GSA FORM 349 REVISED PAGE 1

ERRC OPERATIONS AND MAINTENANCE CONTRACT

1 - 1½” - 150 psi, 10,800 PPH + 1 ½” 150 psi - 6,600 PPH

GENERAL EXTERNAL CONDITION OF BOILER AND OPERATING CONTROLS

Satisfactory

CONDITION OF BOILER GAUGES AND THERMOMETERS

Satisfactory

CONDITION OF GAUGE GLASS, IF FITTED

Satisfactory

CONDITION OF BOTTOM BLOW-OFF VALVES AND PIPE CONNECTIONS

Satisfactory

HAS ADEQUATE PROVISION BEEN MADE FOR FIRE FIGHTING?

Yes

HOW DO PERSONNEL IN CHARGE OF THIS EQUIPMENT GRADE?

COMPETENT DOUBTFUL INCOMPETENT

IN YOUR OPINION IS THIS BOILER IN A SAFE CONDITION TO BE OPERATED?

YES NO

IF ANSWER TO PREVIOUS QUESTION IS NO, THE INSPECTOR WILL NOTIFY THE CUSTODIAN OR BUILDING SUPERINTENDENT, IMMEDIATELY IN WRITING, NOT TO USE SAME AND GIVE COMPLETE DETAILS TO REGIONAL OFFICE BY WIRE.

RECOMMENDATIONS AND REMARKS BY THE INSPECTOR (Include alterations, additions or repairs considered necessary)

Economizer installed on this unit. Installation/setting/use – good.

Low – Nox burner – satisfactory. EGR Damper – good.

Firesides – excellent – tubes straight and clean.

Refractory - rear door, front door, baffle, cone and liner – good.

Watersides – good overall – no corrosion or pitting - improving from 2018.

*Note - new softeners installed 2016 - this should limit the scale formation going forward. Appears to be working well – no increased deposits noted – since 2016.

No adverse conditions noted at time of inspection. Condition of boiler – very good.

Internal inspection conducted – 09/2021.

ATLANTIC SERVICES, INC. 410-836-7727 #4 - NB 17154

SIGNATURE OF INSPECTOR

TITLE OF INSPECTOR

Inspector for Atlantic Services Inc.

RECOMMENDATIONS AND REMARKS BY LOCAL OFFICER OR ENGINEER IN CHARGE

SIGNATURE OF OFFICER IN CHARGE

OFFICIAL TITLE OF OFFICER IN CHARGE

GENERAL SERVICES ADMINISTRATION GSA FORM 349 REVISED PAGE 2

ERRC OPERATIONS AND MAINTENANCE CONTRACT

UNFIRED PRESSURE VESSEL REPORT

EXP DATE: December

DATE OF INSPECTION:

TYPE OF INSPECTION

A. INTERNAL EXTERNAL

B. PRESSURE TEST

C. OPERATIONAL TEST

1. FROM: ATLANTIC SERVICES, INC.

BEL AIR, MD 21014

410-836-7727

12. CERTIFICATE ISSUED: Yes

2. TO:

USDA c/o Akima Facility Management

600 East Mermaid Lane

Wyndmoor, PA

13. BOILER INSPECTOR:

3. MANUFACTURER:

Manchester

4. PROPERTY No:

#1 Air

5. MFG SERIAL No:

196922

14. REASON FOR NOT ISSUING A

CERTIFICATE:

6. BUILDING No:

HAZ-OP (Boiler Room)

7. YEAR BUILT:

8. NATIONAL BOARD NUMBER:

NB 196922

9. PRESSURE

DESIGN: OPER: TEST:

200 110 110

10. CAPACITY:

200 Gallons

11. UPV USE:

Service Air Tank

SAFETY VALVES

15. MANUFACTURER:

Kunkle

16. CAPACITY (CFM):

287 cfm

17. NUMBER OF VALVES:

18. SIZE:

1/2"

19. SETTING (PSI):

20. VALVE CONDITION:

Satisfactory

21. INSPECTOR’S COMMENTS:

Piping / seams / welds / joints - good.

Vessel setting and use - good.

22. ATTACHMENTS: 23. SIGNATURE:

ERRC OPERATIONS AND MAINTENANCE CONTRACT

DATE OF INSPECTION:

TYPE OF INSPECTION

A. INTERNAL EXTERNAL

B. PRESSURE TEST

C. OPERATIONAL TEST

1. FROM: ATLANTIC SERVICES, INC.

BEL AIR, MD 21014

410-836-7727

12. CERTIFICATE ISSUED: Yes

2. TO:

USDA c/o Akima Facility Management

600 East Mermaid Lane

Wyndmoor, PA

13. BOILER INSPECTOR:

3. MANUFACTURER:

Scaife

4. PROPERTY No:

#2 Air (Side room)

5. MFG SERIAL No:

14. REASON FOR NOT ISSUING A

CERTIFICATE:

6. BUILDING No:

HAZ-OP

7. YEAR BUILT:

8. NATIONAL BOARD NUMBER:

345726

9. PRESSURE

DESIGN: OPER: TEST:

200 110 110

10. CAPACITY:

200 Gallons

11. UPV USE:

Service Air Tank

SAFETY VALVES

15. MANUFACTURER:

CDI

16. CAPACITY (CFM):

97 cfm

17. NUMBER OF VALVES:

18. SIZE:

1/4"

19. SETTING (PSI):

20. VALVE CONDITION:

Satisfactory

21. INSPECTOR’S COMMENTS:

Piping / seams / welds / joints - good.

Vessel setting and use - good.

22. ATTACHMENTS: 23. SIGNATURE:

ERRC OPERATIONS AND MAINTENANCE CONTRACT

DATE OF INSPECTION:

TYPE OF INSPECTION

A. INTERNAL EXTERNAL

B. PRESSURE TEST

C. OPERATIONAL TEST

1. FROM: ATLANTIC SERVICES, INC.

BEL AIR, MD 21014

410-836-7727

12. CERTIFICATE ISSUED: Yes

2. TO:

USDA c/o Akima Facility Management

600 East Mermaid Lane

Wyndmoor, PA

13. BOILER INSPECTOR:

3. MANUFACTURER:

Silvan Tank

4. PROPERTY No:

#1

5. MFG SERIAL No:

20291

14. REASON FOR NOT ISSUING A

CERTIFICATE:

6. BUILDING No:

Service Building

7. YEAR BUILT:

8. NATIONAL BOARD NUMBER:

NB 20291

9. PRESSURE

DESIGN: OPER: TEST:

200 120 120

10. CAPACITY:

120 Gallons

11. UPV USE:

Air Tank (Gardener)

SAFETY VALVES

15. MANUFACTURER:

Kingston

16. CAPACITY (CFM):

565 cfm

17. NUMBER OF VALVES:

18. SIZE:

3/4"

19. SETTING (PSI):

150 psi

20. VALVE CONDITION:

Satisfactory

21. INSPECTOR’S COMMENTS:

Piping / seams / welds / joints - good.

Shell .187" / Head .149" - thickness data.

Vessel setting and use - good.

22. ATTACHMENTS: 23. SIGNATURE:

ERRC OPERATIONS AND MAINTENANCE CONTRACT

DATE OF INSPECTION:

TYPE OF INSPECTION

A. INTERNAL EXTERNAL

B. PRESSURE TEST

C. OPERATIONAL TEST

1. FROM: ATLANTIC SERVICES, INC.

BEL AIR, MD 21014

410-836-7727

12. CERTIFICATE ISSUED: Yes

2. TO:

USDA c/o Akima Facility Management

600 East Mermaid Lane

Wyndmoor, PA

13. BOILER INSPECTOR:

3. MANUFACTURER:

Silvan Tank

4. PROPERTY No:

#2

5. MFG SERIAL No:

20287

14. REASON FOR NOT ISSUING A

CERTIFICATE:

6. BUILDING No:

Service Building

7. YEAR BUILT:

8. NATIONAL BOARD NUMBER:

NB 20287

9. PRESSURE

DESIGN: OPER: TEST:

200 120 120

10. CAPACITY:

120 Gallons

11. UPV USE:

Air Tank (Gardener)

SAFETY VALVES

15. MANUFACTURER:

Kingston

16. CAPACITY (CFM):

565 cfm

17. NUMBER OF VALVES:

18. SIZE:

3/4"

19. SETTING (PSI):

150 psi

20. VALVE CONDITION:

Satisfactory

21. INSPECTOR’S COMMENTS:

Piping / seams / welds / joints - good.

Shell .187" / Head .149" - thickness data.

Vessel setting and use - good.

22. ATTACHMENTS: 23. SIGNATURE:

ERRC OPERATIONS AND MAINTENANCE CONTRACT

DATE OF INSPECTION:

TYPE OF INSPECTION

A. INTERNAL EXTERNAL

B. PRESSURE TEST

C. OPERATIONAL TEST

1. FROM: ATLANTIC SERVICES, INC.

BEL AIR, MD 21014

410-836-7727

12. CERTIFICATE ISSUED: Yes

2. TO:

USDA c/o Akima Facility Management

600 East Mermaid Lane

Wyndmoor, PA

13. BOILER INSPECTOR:

3. MANUFACTURER:

Quincy Tank

4. PROPERTY No:

#3

5. MFG SERIAL No:

62638

14. REASON FOR NOT ISSUING A

CERTIFICATE:

6. BUILDING No:

Service Building

7. YEAR BUILT:

8. NATIONAL BOARD NUMBER:

NB 62638

9. PRESSURE

DESIGN: OPER: TEST:

200 110 110

10. CAPACITY:

80 Gallons

11. UPV USE:

Service Air Tank

SAFETY VALVES

15. MANUFACTURER:

Kingston

16. CAPACITY (CFM):

127 cfm

17. NUMBER OF VALVES:

18. SIZE:

1/4"

19. SETTING (PSI):

200 psi

20. VALVE CONDITION:

Satisfactory

21. INSPECTOR’S COMMENTS:

Piping / seams / welds / joints - good.

Shell .187" / Head .149" - thickness data.

Vessel setting and use - good.

Drain - good.

22. ATTACHMENTS: 23. SIGNATURE:

ERRC OPERATIONS AND MAINTENANCE CONTRACT

Boilers iNSP
#1 NB 15706
#2 NB 15733
#3 NB 47554
PUBLIC BUILDINGS SERVICE
INSPECTION REPORT OF
#4 NB 17154
PUBLIC BUILDINGS SERVICE
INSPECTION REPORT OF

UPVRPT