This document contains a request for proposal for operations and maintenance support services for a federal facility. The solicitation seeks proposals to provide operation and maintenance services for the Eastern Regional Research Center located in Wyndmoor, Pennsylvania. Interested offerors are invited to attend a pre-proposal conference on March 8, 2024 and participate in a site visit on March 11, 2024 to learn more about the requirement. Proposals are due by the date specified in the solicitation. The NAICS code for this procurement is 561210 and the small business size standard is $47 million.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PUBLIC BUILDINGS SERVICE
INSPECTION REPORT OF
BOILERS
(Make separate report for each boiler)
CITY AND STATE
Wyndmoor, PA
BUILDING
U.S. Department of Agriculture, 600 E. Mermaid Lane
REGION NUMBER
HEADQUARTERS DATE OF INSPECTION
NUMBER OF BOILERS IN BUILDING SUBJECT TO INSPECTION PLANT BOILER NUMBER
#1 Boiler – Service Building
MANUFACTURER’S NAME
Cleaver Brooks
MANUFACTURER’S NUMBER
NB 15706
TYPE OF BOILER
STEAM PACKAGE TYPE FIRE TUBE H.R.T.
HOT WATER SCOTCH FIRE TUBE FIREBOX
WATER TUBE
Flex Tube C.I. SECTIONAL OTHER (Specify type)
*TYPE OF SETTING
Steel beam to concrete
*DATE MANUFACTURED
*DATE INSTALLED THIS LOCATION
TYPE OF CONSTRUCTION (Riveted, welded, etc.)
Welded steel
MATERIAL AND GAUGE OF SHELL AND TUBES
Carbon steel
NUMBER AND SIZE OF SECTIONS FOR C.I. BOILER
*STATE SERVICE (Lighting, pumping, heating, power, etc.)
HP Steam Boiler - Heat and Process
MANUFACTURER’S RATING
CAPACITY 7650 pph (BHP, LB/HR OR MBH)
DESIGN PRESSURE 150 LBS./SQ. IN.
MAXIMUM ALLOWABLE WORKING PRESSURE 150 LBS./SQ. IN.
MAXIMUM PRESSURE UNDER WHICH BOILER IS NOW OPERATED
LBS./SQ. IN.
DATE OF LAST INSPECTION
November
NAME AND TITLE OF LAST INSPECTOR
FUEL USED
COAL OIL (Sec #6) GAS (Primary) OTHER (Specify)
GENERAL CONDITION OF BOILER AND SETTING
Satisfactory
HAS BOILER BEEN RECEIVING FEED WATER TREATMENT?
YES NO
DOES BOILER CONTAIN OIL?
YES NO
DOES BOILER CONTAIN GREASE?
YES NO
DOES BOILER CONTAIN SCALE?
YES NO
WAS EMBRITTLEMENT, GROOVING, PITTING, OR CORROSION APPARENT?
YES NO
DOES BOILER SHOW SIGNS OF BAGS OR BLISTERS?
YES NO
TO WHAT EXTENT IS FOREIGN MATTER OR DETERIORATION PRESENT?
Satisfactory
HYDROSTATIC PRESSURE OF
N/A LBS./SQ. IN. WAS APPLIED
DID BOILER SHOW DEFECTS UNDER THIS PRESSURE?
YES NO
GENERAL SERVICES ADMINISTRATION *To be reported at first inspection only GSA FORM 349 REVISED PAGE 1
SAMPLE
ERRC OPERATIONS AND MAINTENANCE CONTRACT
ATTACHMENT R.6.6.1.1 SAMPLE BOILER AND PRESSURE VESSAL REPORT
STATE CONDITION OF PRESSURE AND/OR TEMPERATURE RELIEF VALVES
2 - 1¼” - Apollo set at 150 psi - total capacity 8,480 pph – good.
GENERAL EXTERNAL CONDITION OF BOILER AND OPERATING CONTROLS
Satisfactory. Controls / cutouts – good.
CONDITION OF BOILER GAUGES AND THERMOMETERS
Satisfactory
CONDITION OF GAUGE GLASS, IF FITTED
Satisfactory
CONDITION OF BOTTOM BLOW-OFF VALVES AND PIPE CONNECTIONS
Satisfactory
HAS ADEQUATE PROVISION BEEN MADE FOR FIRE FIGHTING?
Yes
HOW DO PERSONNEL IN CHARGE OF THIS EQUIPMENT GRADE?
COMPETENT DOUBTFUL INCOMPETENT
IN YOUR OPINION IS THIS BOILER IN A SAFE CONDITION TO BE OPERATED?
YES NO
IF ANSWER TO PREVIOUS QUESTION IS NO, THE INSPECTOR WILL NOTIFY THE CUSTODIAN OR BUILDING SUPERINTENDENT, IMMEDIATELY IN WRITING, NOT TO USE SAME AND GIVE COMPLETE DETAILS TO REGIONAL OFFICE BY WIRE.
RECOMMENDATIONS AND REMARKS BY THE INSPECTOR (Include alterations, additions or repairs considered necessary)
New installation – 2015 (Replaces Kewanee NB 41091) Firesides – excellent – front cone and rear wall – good. Tubes straight and clean.
Setting / piping / fittings – all good.
Boiler is fitted with an economizer.
Note: Moderate scale noted in 2017 – new softeners and chemical treatment appear to be diminishing the scale – continue. 2021 – problems corrected. Watersides satisfactory.
External inspection conducted – conditions very good.
No pitting or corrosion noted.
ATLANTIC SERVICES, INC. 410-836-7727 #1 NB 15706
SIGNATURE OF INSPECTOR
TITLE OF INSPECTOR
Inspector for Atlantic Services Inc.
RECOMMENDATIONS AND REMARKS BY LOCAL OFFICER OR ENGINEER IN CHARGE
SIGNATURE OF OFFICER IN CHARGE
OFFICIAL TITLE OF OFFICER IN CHARGE
GENERAL SERVICES ADMINISTRATION GSA FORM 349 REVISED PAGE 2
ERRC OPERATIONS AND MAINTENANCE CONTRACT
BOILERS
(Make separate report for each boiler)
CITY AND STATE
Wyndmoor, PA
BUILDING
U.S. Department of Agriculture, 600 E. Mermaid Lane
REGION NUMBER
HEADQUARTERS DATE OF INSPECTION
NUMBER OF BOILERS IN BUILDING SUBJECT TO INSPECTION PLANT BOILER NUMBER
#2 Boiler – Service Building
MANUFACTURER’S NAME
Cleaver Brooks
MANUFACTURER’S NUMBER
NB 15733
TYPE OF BOILER
STEAM PACKAGE TYPE FIRE TUBE H.R.T.
HOT WATER SCOTCH FIRE TUBE FIREBOX
WATER TUBE
Flex Tube C.I. SECTIONAL OTHER (Specify type)
*TYPE OF SETTING
Steel beam to concrete
*DATE MANUFACTURED
*DATE INSTALLED THIS LOCATION
TYPE OF CONSTRUCTION (Riveted, welded, etc.)
Welded steel
MATERIAL AND GAUGE OF SHELL AND TUBES
Carbon steel
NUMBER AND SIZE OF SECTIONS FOR C.I. BOILER
*STATE SERVICE (Lighting, pumping, heating, power, etc.)
HP Steam Boiler - Heat and Process
MANUFACTURER’S RATING
CAPACITY 7650 pph (BHP, LB/HR OR MBH)
DESIGN PRESSURE 150 LBS./SQ. IN.
MAXIMUM ALLOWABLE WORKING PRESSURE 150 LBS./SQ. IN.
MAXIMUM PRESSURE UNDER WHICH BOILER IS NOW OPERATED
LBS./SQ. IN.
DATE OF LAST INSPECTION
November
NAME AND TITLE OF LAST INSPECTOR
FUEL USED
COAL OIL (Sec #6) GAS (Primary) OTHER (Specify)
GENERAL CONDITION OF BOILER AND SETTING
Satisfactory
HAS BOILER BEEN RECEIVING FEED WATER TREATMENT?
YES NO
DOES BOILER CONTAIN OIL?
YES NO
DOES BOILER CONTAIN GREASE?
YES NO
DOES BOILER CONTAIN SCALE?
YES NO
WAS EMBRITTLEMENT, GROOVING, PITTING, OR CORROSION APPARENT?
YES NO
DOES BOILER SHOW SIGNS OF BAGS OR BLISTERS?
YES NO
TO WHAT EXTENT IS FOREIGN MATTER OR DETERIORATION PRESENT?
Satisfactory
HYDROSTATIC PRESSURE OF
N/A LBS./SQ. IN. WAS APPLIED
DID BOILER SHOW DEFECTS UNDER THIS PRESSURE?
YES NO
GENERAL SERVICES ADMINISTRATION *To be reported at first inspection only GSA FORM 349 REVISED PAGE 1
ERRC OPERATIONS AND MAINTENANCE CONTRACT
2 - 1¼” Apollo set at 150 psi - total capacity 8,480 pph – good.
GENERAL EXTERNAL CONDITION OF BOILER AND OPERATING CONTROLS
Satisfactory. Controls / cutouts – good.
CONDITION OF BOILER GAUGES AND THERMOMETERS
Satisfactory
CONDITION OF GAUGE GLASS, IF FITTED
Satisfactory
CONDITION OF BOTTOM BLOW-OFF VALVES AND PIPE CONNECTIONS
Satisfactory
HAS ADEQUATE PROVISION BEEN MADE FOR FIRE FIGHTING?
Yes
HOW DO PERSONNEL IN CHARGE OF THIS EQUIPMENT GRADE?
COMPETENT DOUBTFUL INCOMPETENT
IN YOUR OPINION IS THIS BOILER IN A SAFE CONDITION TO BE OPERATED?
YES NO
IF ANSWER TO PREVIOUS QUESTION IS NO, THE INSPECTOR WILL NOTIFY THE CUSTODIAN OR BUILDING SUPERINTENDENT, IMMEDIATELY IN WRITING, NOT TO USE SAME AND GIVE COMPLETE DETAILS TO REGIONAL OFFICE BY WIRE.
RECOMMENDATIONS AND REMARKS BY THE INSPECTOR (Include alterations, additions or repairs considered necessary)
New installation – 2015 (Replaces Kewanee NB 41091) Firesides – excellent – front cone and rear wall – good. Tubes straight and clean.
Setting / piping / fittings – all good.
Boiler is fitted with an economizer.
Note: Moderate scale noted in 2017 – new softeners and chemical treatment appear to be diminishing the scale – continue. 2020 – unit – good. Watersides – clear.
2021 – Good overall - maintain chemical treatment and proper blowdown.
External inspection conducted – conditions very good.
No pitting or corrosion noted.
ATLANTIC SERVICES, INC. 410-836-7727 #2 NB 15733
SIGNATURE OF INSPECTOR
TITLE OF INSPECTOR
Inspector for Atlantic Services Inc.
RECOMMENDATIONS AND REMARKS BY LOCAL OFFICER OR ENGINEER IN CHARGE
SIGNATURE OF OFFICER IN CHARGE
OFFICIAL TITLE OF OFFICER IN CHARGE
GENERAL SERVICES ADMINISTRATION GSA FORM 349 REVISED PAGE 2
ERRC OPERATIONS AND MAINTENANCE CONTRACT
BOILERS
(Make separate report for each boiler)
CITY AND STATE
Wyndmoor, PA
BUILDING
U.S. Department of Agriculture, 600 E. Mermaid Lane
REGION NUMBER
HEADQUARTERS DATE OF INSPECTION
09/16/2021
NUMBER OF BOILERS IN BUILDING SUBJECT TO INSPECTION PLANT BOILER NUMBER
#3 - Service Building
MANUFACTURER’S NAME
Kewanee
MANUFACTURER’S NUMBER
SN- 1991 NB 47554
TYPE OF BOILER
STEAM PACKAGE TYPE FIRE TUBE H.R.T.
HOT WATER SCOTCH FIRE TUBE FIREBOX Wetback design
WATER TUBE C.I. SECTIONAL OTHER (Specify type)
*TYPE OF SETTING
*DATE MANUFACTURED
*DATE INSTALLED THIS LOCATION
TYPE OF CONSTRUCTION (Riveted, welded, etc.)
Welded steel
MATERIAL AND GAUGE OF SHELL AND TUBES
Carbon steel
NUMBER AND SIZE OF SECTIONS FOR C.I. BOILER
*STATE SERVICE (Lighting, pumping, heating, power, etc.)
HP Steam Boiler - Heat and Process
MANUFACTURER’S RATING
CAPACITY 13390 lb/hr (BHP, LB/HR OR MBH)
DESIGN PRESSURE 150 LBS./SQ. IN.
MAXIMUM ALLOWABLE WORKING PRESSURE 150 LBS./SQ. IN.
MAXIMUM PRESSURE UNDER WHICH BOILER IS NOW OPERATED
120 LBS./SQ. IN.
DATE OF LAST INSPECTION
September 2020
NAME AND TITLE OF LAST INSPECTOR
Richard Buck
FUEL USED
COAL OIL (Sec #6) GAS (Primary) OTHER (Specify)
GENERAL CONDITION OF BOILER AND SETTING
Satisfactory
HAS BOILER BEEN RECEIVING FEED WATER TREATMENT?
YES NO
DOES BOILER CONTAIN OIL?
YES NO
DOES BOILER CONTAIN GREASE?
** YES NO
DOES BOILER CONTAIN SCALE?
** YES NO
WAS EMBRITTLEMENT, GROOVING, PITTING, OR CORROSION APPARENT?
YES NO
DOES BOILER SHOW SIGNS OF BAGS OR BLISTERS?
YES NO
TO WHAT EXTENT IS FOREIGN MATTER OR DETERIORATION PRESENT?
See notes
HYDROSTATIC PRESSURE OF
0 LBS./SQ. IN. WAS APPLIED
DID BOILER SHOW DEFECTS UNDER THIS PRESSURE?
YES NO
GENERAL SERVICES ADMINISTRATION *To be reported at first inspection only GSA FORM 349 REVISED PAGE 1
ERRC OPERATIONS AND MAINTENANCE CONTRACT
1 - 1½” Kunkle set at 150 psi, capacity 6596 lb/hr and 1 - 2” Conbracco set at 150 psi, capacity 10,851 lb/hr.
GENERAL EXTERNAL CONDITION OF BOILER AND OPERATING CONTROLS
Satisfactory
CONDITION OF BOILER GAUGES AND THERMOMETERS
Satisfactory
CONDITION OF GAUGE GLASS, IF FITTED
Satisfactory
CONDITION OF BOTTOM BLOW-OFF VALVES AND PIPE CONNECTIONS
Satisfactory
HAS ADEQUATE PROVISION BEEN MADE FOR FIRE FIGHTING?
Yes
HOW DO PERSONNEL IN CHARGE OF THIS EQUIPMENT GRADE?
COMPETENT DOUBTFUL INCOMPETENT
IN YOUR OPINION IS THIS BOILER IN A SAFE CONDITION TO BE OPERATED?
YES NO
IF ANSWER TO PREVIOUS QUESTION IS NO, THE INSPECTOR WILL NOTIFY THE CUSTODIAN OR BUILDING SUPERINTENDENT, IMMEDIATELY IN WRITING, NOT TO USE SAME AND GIVE COMPLETE DETAILS TO REGIONAL OFFICE BY WIRE.
RECOMMENDATIONS AND REMARKS BY THE INSPECTOR (Include alterations, additions or repairs considered necessary)
Overall – good – tubes straight and clean / cone refractory – good condition.
Watersides – no evidence of pitting or corrosion.
Note – A. Low end – some scale deposits in wetback section – no change since 2015.
B. Pull low end front hand-holes and flush; some collected scale noted – to be flushed out.
C. unit has run very little in 2020.
No adverse conditions noted at time of inspection.
Internal inspection conducted – 09/2021.
ATLANTIC SERVICES, INC. 410-836-7727 #3 – NB 47554
SIGNATURE OF INSPECTOR
TITLE OF INSPECTOR
Inspector for Atlantic Services Inc.
RECOMMENDATIONS AND REMARKS BY LOCAL OFFICER OR ENGINEER IN CHARGE
SIGNATURE OF OFFICER IN CHARGE
OFFICIAL TITLE OF OFFICER IN CHARGE
GENERAL SERVICES ADMINISTRATION GSA FORM 349 REVISED PAGE 2
ERRC OPERATIONS AND MAINTENANCE CONTRACT
BOILERS
(Make separate report for each boiler)
CITY AND STATE
Wyndmoor, PA
BUILDING
U.S. Department of Agriculture, 600 E. Mermaid Lane
REGION NUMBER
HEADQUARTERS DATE OF INSPECTION
NUMBER OF BOILERS IN BUILDING SUBJECT TO INSPECTION PLANT BOILER NUMBER
#4 - Service Building
MANUFACTURER’S NAME
Cleaver Brooks
MANUFACTURER’S NUMBER
NB 17154 S/N T2062-1-1
TYPE OF BOILER
STEAM PACKAGE TYPE FIRE TUBE H.R.T.
HOT WATER SCOTCH FIRE TUBE FIREBOX Wetback design
WATER TUBE C.I. SECTIONAL OTHER (Specify type)
*TYPE OF SETTING
Steel to concrete pad
*DATE MANUFACTURED
*DATE INSTALLED THIS LOCATION
TYPE OF CONSTRUCTION (Riveted, welded, etc.)
Welded steel
MATERIAL AND GAUGE OF SHELL AND TUBES
Carbon steel
NUMBER AND SIZE OF SECTIONS FOR C.I. BOILER
*STATE SERVICE (Lighting, pumping, heating, power, etc.)
HP Steam Boiler - Heat and Process
MANUFACTURER’S RATING
CAPACITY 13800 lb/hr (BHP, LB/HR OR MBH)
DESIGN PRESSURE 150 LBS./SQ. IN.
MAXIMUM ALLOWABLE WORKING PRESSURE 150 LBS./SQ. IN.
MAXIMUM PRESSURE UNDER WHICH BOILER IS NOW OPERATED
LBS./SQ. IN.
DATE OF LAST INSPECTION
September
NAME AND TITLE OF LAST INSPECTOR
FUEL USED
COAL OIL (Sec #6) GAS (Primary) OTHER (Specify)
GENERAL CONDITION OF BOILER AND SETTING
Satisfactory
HAS BOILER BEEN RECEIVING FEED WATER TREATMENT?
YES NO
DOES BOILER CONTAIN OIL?
YES NO
DOES BOILER CONTAIN GREASE?
** YES NO
DOES BOILER CONTAIN SCALE?
** YES NO
WAS EMBRITTLEMENT, GROOVING, PITTING, OR CORROSION APPARENT?
YES NO
DOES BOILER SHOW SIGNS OF BAGS OR BLISTERS?
YES NO
TO WHAT EXTENT IS FOREIGN MATTER OR DETERIORATION PRESENT?
See notes
HYDROSTATIC PRESSURE OF
0 LBS./SQ. IN. WAS APPLIED
DID BOILER SHOW DEFECTS UNDER THIS PRESSURE?
YES NO
GENERAL SERVICES ADMINISTRATION *To be reported at first inspection only GSA FORM 349 REVISED PAGE 1
ERRC OPERATIONS AND MAINTENANCE CONTRACT
1 - 1½” - 150 psi, 10,800 PPH + 1 ½” 150 psi - 6,600 PPH
GENERAL EXTERNAL CONDITION OF BOILER AND OPERATING CONTROLS
Satisfactory
CONDITION OF BOILER GAUGES AND THERMOMETERS
Satisfactory
CONDITION OF GAUGE GLASS, IF FITTED
Satisfactory
CONDITION OF BOTTOM BLOW-OFF VALVES AND PIPE CONNECTIONS
Satisfactory
HAS ADEQUATE PROVISION BEEN MADE FOR FIRE FIGHTING?
Yes
HOW DO PERSONNEL IN CHARGE OF THIS EQUIPMENT GRADE?
COMPETENT DOUBTFUL INCOMPETENT
IN YOUR OPINION IS THIS BOILER IN A SAFE CONDITION TO BE OPERATED?
YES NO
IF ANSWER TO PREVIOUS QUESTION IS NO, THE INSPECTOR WILL NOTIFY THE CUSTODIAN OR BUILDING SUPERINTENDENT, IMMEDIATELY IN WRITING, NOT TO USE SAME AND GIVE COMPLETE DETAILS TO REGIONAL OFFICE BY WIRE.
RECOMMENDATIONS AND REMARKS BY THE INSPECTOR (Include alterations, additions or repairs considered necessary)
Economizer installed on this unit. Installation/setting/use – good.
Low – Nox burner – satisfactory. EGR Damper – good.
Firesides – excellent – tubes straight and clean.
Refractory - rear door, front door, baffle, cone and liner – good.
Watersides – good overall – no corrosion or pitting - improving from 2018.
*Note - new softeners installed 2016 - this should limit the scale formation going forward. Appears to be working well – no increased deposits noted – since 2016.
No adverse conditions noted at time of inspection. Condition of boiler – very good.
Internal inspection conducted – 09/2021.
ATLANTIC SERVICES, INC. 410-836-7727 #4 - NB 17154
SIGNATURE OF INSPECTOR
TITLE OF INSPECTOR
Inspector for Atlantic Services Inc.
RECOMMENDATIONS AND REMARKS BY LOCAL OFFICER OR ENGINEER IN CHARGE
SIGNATURE OF OFFICER IN CHARGE
OFFICIAL TITLE OF OFFICER IN CHARGE
GENERAL SERVICES ADMINISTRATION GSA FORM 349 REVISED PAGE 2
ERRC OPERATIONS AND MAINTENANCE CONTRACT
UNFIRED PRESSURE VESSEL REPORT
EXP DATE: December
DATE OF INSPECTION:
TYPE OF INSPECTION
A. INTERNAL EXTERNAL
B. PRESSURE TEST
C. OPERATIONAL TEST
1. FROM: ATLANTIC SERVICES, INC.
BEL AIR, MD 21014
410-836-7727
12. CERTIFICATE ISSUED: Yes
2. TO:
USDA c/o Akima Facility Management
600 East Mermaid Lane
Wyndmoor, PA
13. BOILER INSPECTOR:
3. MANUFACTURER:
Manchester
4. PROPERTY No:
#1 Air
5. MFG SERIAL No:
196922
14. REASON FOR NOT ISSUING A
CERTIFICATE:
6. BUILDING No:
HAZ-OP (Boiler Room)
7. YEAR BUILT:
8. NATIONAL BOARD NUMBER:
NB 196922
9. PRESSURE
DESIGN: OPER: TEST:
200 110 110
10. CAPACITY:
200 Gallons
11. UPV USE:
Service Air Tank
SAFETY VALVES
15. MANUFACTURER:
Kunkle
16. CAPACITY (CFM):
287 cfm
17. NUMBER OF VALVES:
18. SIZE:
1/2"
19. SETTING (PSI):
20. VALVE CONDITION:
Satisfactory
21. INSPECTOR’S COMMENTS:
Piping / seams / welds / joints - good.
Vessel setting and use - good.
22. ATTACHMENTS: 23. SIGNATURE:
ERRC OPERATIONS AND MAINTENANCE CONTRACT
DATE OF INSPECTION:
TYPE OF INSPECTION
A. INTERNAL EXTERNAL
B. PRESSURE TEST
C. OPERATIONAL TEST
1. FROM: ATLANTIC SERVICES, INC.
BEL AIR, MD 21014
410-836-7727
12. CERTIFICATE ISSUED: Yes
2. TO:
USDA c/o Akima Facility Management
600 East Mermaid Lane
Wyndmoor, PA
13. BOILER INSPECTOR:
3. MANUFACTURER:
Scaife
4. PROPERTY No:
#2 Air (Side room)
5. MFG SERIAL No:
14. REASON FOR NOT ISSUING A
CERTIFICATE:
6. BUILDING No:
HAZ-OP
7. YEAR BUILT:
8. NATIONAL BOARD NUMBER:
345726
9. PRESSURE
DESIGN: OPER: TEST:
200 110 110
10. CAPACITY:
200 Gallons
11. UPV USE:
Service Air Tank
SAFETY VALVES
15. MANUFACTURER:
CDI
16. CAPACITY (CFM):
97 cfm
17. NUMBER OF VALVES:
18. SIZE:
1/4"
19. SETTING (PSI):
20. VALVE CONDITION:
Satisfactory
21. INSPECTOR’S COMMENTS:
Piping / seams / welds / joints - good.
Vessel setting and use - good.
22. ATTACHMENTS: 23. SIGNATURE:
ERRC OPERATIONS AND MAINTENANCE CONTRACT
DATE OF INSPECTION:
TYPE OF INSPECTION
A. INTERNAL EXTERNAL
B. PRESSURE TEST
C. OPERATIONAL TEST
1. FROM: ATLANTIC SERVICES, INC.
BEL AIR, MD 21014
410-836-7727
12. CERTIFICATE ISSUED: Yes
2. TO:
USDA c/o Akima Facility Management
600 East Mermaid Lane
Wyndmoor, PA
13. BOILER INSPECTOR:
3. MANUFACTURER:
Silvan Tank
4. PROPERTY No:
#1
5. MFG SERIAL No:
20291
14. REASON FOR NOT ISSUING A
CERTIFICATE:
6. BUILDING No:
Service Building
7. YEAR BUILT:
8. NATIONAL BOARD NUMBER:
NB 20291
9. PRESSURE
DESIGN: OPER: TEST:
200 120 120
10. CAPACITY:
120 Gallons
11. UPV USE:
Air Tank (Gardener)
SAFETY VALVES
15. MANUFACTURER:
Kingston
16. CAPACITY (CFM):
565 cfm
17. NUMBER OF VALVES:
18. SIZE:
3/4"
19. SETTING (PSI):
150 psi
20. VALVE CONDITION:
Satisfactory
21. INSPECTOR’S COMMENTS:
Piping / seams / welds / joints - good.
Shell .187" / Head .149" - thickness data.
Vessel setting and use - good.
22. ATTACHMENTS: 23. SIGNATURE:
ERRC OPERATIONS AND MAINTENANCE CONTRACT
DATE OF INSPECTION:
TYPE OF INSPECTION
A. INTERNAL EXTERNAL
B. PRESSURE TEST
C. OPERATIONAL TEST
1. FROM: ATLANTIC SERVICES, INC.
BEL AIR, MD 21014
410-836-7727
12. CERTIFICATE ISSUED: Yes
2. TO:
USDA c/o Akima Facility Management
600 East Mermaid Lane
Wyndmoor, PA
13. BOILER INSPECTOR:
3. MANUFACTURER:
Silvan Tank
4. PROPERTY No:
#2
5. MFG SERIAL No:
20287
14. REASON FOR NOT ISSUING A
CERTIFICATE:
6. BUILDING No:
Service Building
7. YEAR BUILT:
8. NATIONAL BOARD NUMBER:
NB 20287
9. PRESSURE
DESIGN: OPER: TEST:
200 120 120
10. CAPACITY:
120 Gallons
11. UPV USE:
Air Tank (Gardener)
SAFETY VALVES
15. MANUFACTURER:
Kingston
16. CAPACITY (CFM):
565 cfm
17. NUMBER OF VALVES:
18. SIZE:
3/4"
19. SETTING (PSI):
150 psi
20. VALVE CONDITION:
Satisfactory
21. INSPECTOR’S COMMENTS:
Piping / seams / welds / joints - good.
Shell .187" / Head .149" - thickness data.
Vessel setting and use - good.
22. ATTACHMENTS: 23. SIGNATURE:
ERRC OPERATIONS AND MAINTENANCE CONTRACT
DATE OF INSPECTION:
TYPE OF INSPECTION
A. INTERNAL EXTERNAL
B. PRESSURE TEST
C. OPERATIONAL TEST
1. FROM: ATLANTIC SERVICES, INC.
BEL AIR, MD 21014
410-836-7727
12. CERTIFICATE ISSUED: Yes
2. TO:
USDA c/o Akima Facility Management
600 East Mermaid Lane
Wyndmoor, PA
13. BOILER INSPECTOR:
3. MANUFACTURER:
Quincy Tank
4. PROPERTY No:
#3
5. MFG SERIAL No:
62638
14. REASON FOR NOT ISSUING A
CERTIFICATE:
6. BUILDING No:
Service Building
7. YEAR BUILT:
8. NATIONAL BOARD NUMBER:
NB 62638
9. PRESSURE
DESIGN: OPER: TEST:
200 110 110
10. CAPACITY:
80 Gallons
11. UPV USE:
Service Air Tank
SAFETY VALVES
15. MANUFACTURER:
Kingston
16. CAPACITY (CFM):
127 cfm
17. NUMBER OF VALVES:
18. SIZE:
1/4"
19. SETTING (PSI):
200 psi
20. VALVE CONDITION:
Satisfactory
21. INSPECTOR’S COMMENTS:
Piping / seams / welds / joints - good.
Shell .187" / Head .149" - thickness data.
Vessel setting and use - good.
Drain - good.
22. ATTACHMENTS: 23. SIGNATURE:
ERRC OPERATIONS AND MAINTENANCE CONTRACT
| Boilers iNSP |
| #1 NB 15706 |
| #2 NB 15733 |
| #3 NB 47554 |
| PUBLIC BUILDINGS SERVICE |
| INSPECTION REPORT OF |
| #4 NB 17154 |
| PUBLIC BUILDINGS SERVICE |
| INSPECTION REPORT OF |