This document provides details for a federal contract solicitation from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23. The solicitation number is 36C26323R0023 and is for project Z1DA--618-22-102 to renovate a private patient bed ward (3D) at facility 36C263. The solicitation involves renovating an existing facility to create a private patient bed ward and includes seven drawings as an attachment to the solicitation document. Responses to the solicitation are due on an unspecified date. The award date is also unspecified. The solicitation is for renovating and upgrading an existing inpatient facility to improve patient privacy and accommodate more single occupancy rooms.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL ABBREVIATIONS
J J
J
M
V
SP
R
GB
VFD
LCP
LRP
AFB
FBX
ET
M
M
C
DTDT
A-1
PH
D
P
K a
L
OS
R
B
CB
MD
MD
SP
VP
TV
XX
DC
C
DM
R/D
DGP
RX
ELM
DO
CR
K
AC
E
K
ATS
TBB
T
TMH
EMH
EHH
X
PSD
EMU
FB
UG
GB
G
PB
6-30R
UPS
CT
DOOR CONTACT SWITCH
ACCESS FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)
FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)
CONTACTOR
VARIABLE FREQUENCY DRIVE/VARIABLE FREQUENCY MOTOR CONTROLLER
MANUAL MOTOR STARTER WITH PILOT LIGHT AS INDICATED.
PUSHBUTTON STATION
CCTV SURVEILLANCE CAMERA OUTLET - WALL MTD, UON
DOOR MONITOR SWITCH
RECEIVER/DRIVER UNIT
GLASS BREAK DETECTOR
LIGHTING FIXTURE TYPE DESIGNATION - "XX" INDICATES SPECIFIC TYPE
EXIT LIGHT - WALL/CEILING MOUNTED - DIRECTIONAL ARROWS
AS INDICATED SHADING INDICATES ILLUMINATED FACE
LIGHTING TRACK - "X" DENOTES TYPE
UTILITY LIGHTING FIXTURE - TYPE AS INDICATED
WALL MOUNTED LIGHTING FIXTURE- TYPE AS INDICATED
SITE LIGHTING FIXTURE TYPE AS INDICATED
LIGHTING FIXTURE - TYPE AS INDICATED (SUBSCRIPT INDICATES SWITCH CONTROL)
JUNCTION BOX - CEILING OR WALL MOUNTED - INDICATED IN POWER, LIGHTING & FIRE
ALARM SYSTEMS PLANS.
DIRECT CONNECTION TO EQUIPMENT
SINGLE POLE SWITCH (SUBSCRIPT INDICATES FIXTURES CONTROLLED)
DIMMER SWITCH
SINGLE OR DOUBLE, REMOTE EMERGENCY LIGHTING FIXTURE
THREE-WAY SWITCH (S3P-THREE-WAY SWITCH WITH PILOT LIGHT)
KEY OPERATED SWITCH
SINGLE POLE SWITCH WITH PILOT LIGHT
FOUR - WAY SWITCH
FUSED SWITCH
DELTA CONNECTION
CPT
PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING)
ELECTRIC INTERLOCK SYSTEM
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
PHOTO CELL
KEY INTERLOCKING SYSTEM
WYE CONNECTION - SOLID GROUND
SWITCH - SINGLE THROW
TELECOMMUNICATIONS BACKBOARD
MOTOR CONTROL CENTER
TELEPHONE MANHOLE
ELECTRIC MANHOLE
FUSE
BUS DUCT PLUG-IN UNIT
GROUND
AUTOMATIC TRANSFER SWITCH
DRAWOUT TYPE, CIRCUIT BREAKER
STATIONARY CIRCUIT BREAKER
DISCONNECT SWITCH, FUSED.
PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY,
UON
GROUND ROD
DISCONNECT SWITCH, NON-FUSED
PROVIDE SWITCH AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON
TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, FLOOR MTD SERVICE FITTING,
SURFACE TYPE ("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)
TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, WALL MTD.
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
TRANSFORMER - TYPE AND RATING AS INDICATED
COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH.
PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER
AMPACITY, UON
PANELBOARD - (FLUSH/SURFACE)
DISTRIBUTION PANELBOARD
ELECTRIC HANDHOLE
LIGHTING CONTROL PANEL, SURFACE MTD. UON.
LOW VOLTAGE LIGHTING RELAY PANEL, SURFACE MTD. UON
UNINTERRUPTIBLE POWER SUPPLY
SHADING INDICATES FIXTURE [CONNECTED TO CRITICAL BRANCH]
[CONNECTED TO GENERATOR CIRCUIT (SWITCHED)]
[W/FLUORESCENT BATTERY/INVERTER UNIT (SWITCHED)]
SHADING INDICATES FIXTURE [CONNECTED TO LIFE SAFETY BRANCH
(UNSWITCHED)] [W/FLUORESCENT BATTERY/INVERTER UNIT (UNSWITCHED)]
a
LOW VOLTAGE SWITCH
JUNCTION BOX - FLOOR MOUNTED
TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, CEILING MTD SERVICE
FITTING,
SURFACE TYPE ("F" DENOTES FLUSH TYPE)
MOTOR AND CONNECTION
EMERGENCY POWER OFF
REQUEST-FOR-EXIT SENSOR
ELECTRIC LOCKING/LATCHING AND MONITORING HARDWARE
ACCESS CONTROL STATION - KEYPAD TYPE
ACCESS CONTROL STATION - CARD TYPE
DOOR OPERATING EQUIPMENT
DATA GATHERING PANEL
CODE BLUE WITH RED PHONE, WALL MTD, MOUNTED 48" AFF
CODE BLUE WITH BLUE LIGHT, WALL MTD, MOUNTED 48" AFF
MOTION DETECTOR - CEILING MTD
MOTION DETECTOR - WALL MTD
POWER SUPPLY FOR DOOR(S) WITH ELECTRICAL HARDWARE
CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SHADING INDICATES
EMERGENCY RECEPTACLE)
SPECIAL PURPOSE RECEPTACLE. TYPE AS INDICATED ON DRAWINGS.
COORDINATE RECEPTACLE TYPE WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION.
SWITCHED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.
FLOOR MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,
2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON
FACEPLATE.
FLOOR MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES
WITH A COMMON FACEPLATE. (SHADING INDICATES EMERGENCY RECEPTACLE)
FLOOR MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. PROVIDE CORE DRILL PACKAGE TO MAINTAIN FIRE RATING OF FLOOR. EXTEND CONDUIT AND WIRING IN CEILING SPACE OF FLOOR
BELOW TO ELECTRICAL CLOSET OR PANELBOARD. (SHADING INDICATES EMERGENCY
RECEPTACLE)
FLOOR MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,
2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.
FLOOR MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
CEILING MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.
SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH
INDICATES MOUNTING ABOVE FINISH COUNTER)
QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V, 2P, 3W,
DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON
FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.
(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER;
SHADING INDICATES EMERGENCY RECEPTACLE)
SINGLE RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
RECEPTACLES MOUNTED ABOVE THE CEILING.
QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES WITH A
COMMON FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER;
SHADING INDICATES EMERGENCY RECEPTACLE)
CEILING MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES
WITH A COMMON FACEPLATE. (SHADING INDICATES EMERGENCY RECEPTACLE)
GFI, DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)
ELECTRONIC METERING UNIT
GROUND BUS
GROUND CABLE, SIZE AS INDICATED
PLUG-IN BUSWAY
FEEDER BUSWAY
UNDERGROUND CONDUIT/DUCTBANK
CABLE TRAY
CONDUIT TURNED DOWN
CONDUIT TURNED UP
CONDUIT CAST IN CONCRETE OR BELOW SLAB
CONDUIT RUN CONCEALED IN FINISHED AREAS, EXPOSED IN UNFINISHED
AREAS OR BELOW ACCESS FLOORS
HOMERUN TO PANEL WITH CIRCUIT NUMBER(S) AS INDICATED
TELECOMMUNICATIONS DATA OUTLET ABOVE CEILING
COMBINATION TV OUTLET AND DUPLEX RECEPTACLE ON SINGLE
FACEPLATE
SPEAKER - WALL MTD
PA VOLUME CONTROL
MICROPHONE OUTLET - CEILING MTD
MICROPHONE OUTLET - WALL MTD
MICROPHONE OUTLET - FLOOR MTD
SPEAKER - CEILING MTD
RECORDING OUTLET
COMBINATION VIDEO PROJECTOR OUTLET AND DUPLEX RECEPTACLE
CLOCK OUTLET, W/RECPT AND HANGER
CLOCK OUTLET, MASTER CLOCK
CLOCK OUTLET, ELAPSED TIME
GENERATORG
SURFACE RACEWAY ("X" DENOTES TYPE AS SPECIFIED)
WALLWASH LIGHT FIXTURE,
DEMOLITION WORK
OCCUPANCY SENSOR WALL SWITCH
M
HC ADA PUSH BUTTON.
ELECTRICAL LIGHTING SYMBOLS ELECTRICAL POWER SYMBOLS GENERAL NOTES
A INTERCOMMUNICATION SYSTEM ( AI PHONE)
A B C A B C
P P
PD PD
D D
POWER SERVICE FITTING (FLOOR/WALL) MOUNTED FOR CONNECTION TO FURNITURE
SYSTEM AS SPECIFIED.
COMBINATION POWER AND TELECOMMUNICATIONS FLOOR OR WALL MOUNTED BOX FOR
POWER AND DATA CONNECTION - INDICATED IN POWER & SPECIAL SYSTEMS PLANS.
JUNCTION BOX FLOOR OR WALL MOUNTED FOR CONNECTION TO FURNITURE SYSTEM
MOUNTING HEIGHT NOTES:
1. ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.
2. REFER TO EQUIPMENT ELEVATION DRAWINGS FOR COORDINATION WITH
CASEWORK.
3. MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.
4. REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL ELECTRICAL DEVICE
MOUNTING HEIGHTS AND DEVICE ALIGNMENT RULES.
WALL SWITCHES
RECEPTACLES
TELECOMMUNICATIONS OUTLETS
TELECOMMUNICATIONS OUTLETS - WALL PHONE
CLOCK OUTLETS
TV OUTLETS
PUSHBUTTONS
VOLUME CONTROLS
NURSE CALL STATIONS
NURSE CALL DOME LIGHTS
DIMMERS
ACCESS CONTROL DEVICES
VANITY LIGHT IN TOILET
INTERCOM
FIREMAN'S PHONE
FIRE ALARM - PULL STATIONS
FIRE ALARM DEVICES HORN/SPEAKERS/STROBES
(MOUNTING HEIGHT AT THE TOP OF THE FIRE ALARM DEVICE OR
6" BELOW CEILING WHICH IS LOWER)
4'-0" AFF
1'-6" AFF
1'-6" AFF
4'-0" AFF
7'-0" AFF
1'-6" AFF
4'-0" AFF
4'-0" AFF
4'-0" AFF
7'-6" AFF
4'-0" AFF
4'-0" AFF
6" ABOVE THE MIRROR, UON
4'-0" AFF
4'-0" AFF
4'-0" AFF
7'-2" AFF TO TOP
PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF
THREE CIRCUITS PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.
PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.
COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL
DRAWINGS PRIOR TO ROUGH-IN.
PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR
SLABS, WALLS AND CEILINGS TO MAINTAIN FIRE RATING.
INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL
CODE AND LOCAL BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE
MANNER.
LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE
DERATING FACTOR FOR ROOF-MOUNTED CONDUITS.
REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING
MOUNTED DEVICES AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.
WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL
PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS
AND A COMMON FACEPLATE.
WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING
HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS
FOUR INCHES BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.
WHERE UPDATE TO TECHNOLOGY (LOW VOLTAGE/SIGNAL) ARE LOCATED IN THE
SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.
WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE
EXIT SIGN BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP
OF DOOR FRAME AND CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM
OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED
EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT. COORDINATE WITH
ARCHITECTURAL DETAILS.
EXIT SIGNS ARE TO BE TYPE "X1", UON.
PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.
PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR
GREATER THAN THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.
FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL
LOCATION OF ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND
FINAL FURNITURE PLANS PRIOR TO INSTALLATION.
MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE
DRAWINGS AND IN MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.
THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC.
PROVIDE ALL COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL
SYSTEMS.
WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY
CONNECT RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.
A.
B.
C.
D.
E.
F.
G.
H.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
ELTD EMERGENCY LIGHTING TRANSFER DEVICE
SECURITY SYSTEM SYMBOLS
TELECOMMUNICATION SYMBOLS
NURSE CALL SYSTEM SYMBOLS
MOUNTING HEIGHTS
ELECTRICAL EQUIPMENT SYMBOLS
ELECTRICAL WIRING SYMBOLS
DISTRIBUTION AND DIAGRAM SYMBOLS
REFERENCE SYMBOLS
SECTION NUMBER
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
E1-1.0
KEY NOTE
1 DEMO KEY NOTE
SPECIAL SYSTEM OUTLET SYMBOLS
CB
E1-1.0
DISCONNECT SWITCHES
MOTOR STARTERS
PANELBOARDS & CABINETS
INDIVIDUAL CIRCUIT BREAKERS
5'-6" AFF
5'-6" AFF
6'-0" AFF TO TOP
5'-6" AFF
x
WAP WIRELESS ACCESS POINT, CEILING MOUNTED
NOTE: NOT ALL ABBREVIATIONS AND
SYMBOLS APPLY TO THIS PROJECT.
SPST
SWBD
SYM
STD
SW
SPEC(S)
SPDT
SPKR
SF
SEC
SINGLE POLE SINGLE THROW
SINGLE POLE DOUBLE THROW
SYMMETRICAL
SWITCHBOARD
STANDARD
SWITCH
SECONDARY
SQUARE FOOT
SPECIFICATION(S)
SPEAKER
PRI
RCLP
RM
SCH, SCHED
RP
REF
RCPT
RSC
RLA
RF
R, RE
QTY
PWR
PT
PVC
PA
PH, ∅
PF
PNL
PE
PB
P
OPP
OHE/T
OH
OFOI
OFCI
NO., NUM, #
OC
NTS
AMERICAN WIRE GAUGE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AUTOMATIC TRANSFER SWITCH
AMPERE INTERRUPTING CAPACITY
ALTERNATING CURRENT
ABOVE FINISHED COUNTER
AWG
BLDG
BRKR, BKR
BUILDING
BREAKER
AUTO
AUX
ARCH
AT
ATS
ALT
AFG
AIC
AFC
AFF
AC
AF
AUXILIARY
ALTERNATE
ARCHITECT
AUTOMATIC
AMPERES TRIP
AMPERE FRAME (BREAKER RATING)
MTG
NC
NEMA
NO
NIC
NEC
N
MV
MH
MOCP
MTD
MLO
MIN
MISC
MECH
MCC
MFR
MCA
MCB
RIGID STEEL CONDUIT
RATED (RUNNING) LOAD AMPS
RECEPTACLE PANELBOARD
ROOM
SCHEDULE
RADIO FREQUENCY
RECEPTACLE
REFRIGERATOR
RELOCATE AS SHOWN
POTENTIAL TRANSFORMER
POLYVINYL CHLORIDE
REMOTE CONTROL LIGHTING PANEL
QUANTITY
POWER
PUBLIC ADDRESS
PANEL
PRIMARY
PULL BOX
POWER FACTOR
PHOTO ELECTRIC
PHASE
POLE
OPPOSITE
OWNER FURNISHED, CONTRACTOR INSTALLED
OWNER FURNISHED, OWNER INSTALLED
OVERHEAD ELECTRIC/TELEPHONE
OVERHEAD
ON CENTER
NOT TO SCALE
NUMBER
MOUNTING
NATIONAL ELECTRICAL CODE
MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)
NORMALLY CLOSED
NORMALLY OPEN
NOT IN CONTRACT
NEUTRAL
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAXIMUM OVERCURRENT PROTECTION
MOUNTED
MISCELLANEOUS
MAIN LUGS ONLY
MINIMUM
MANHOLE
MANUFACTURER
MECHANICAL
SWGR SWITCHGEAR
AIR HANDLING UNITAHU
MTS MANUAL TRANSFER SWITCH
PDP POWER DISTRIBUTION PANEL
AMPERESAMP
OCPD OVERCURRENT PROTECTION DEVICE
A M
B N
O
P
Q
R
S
T
SPD SURGE PROTECTIVE DEVICE
OD OUTLET DESIGNATOR
LOW VOLTAGE (BELOW 50 VOLTS)
L-L
L-N
LTG
LV
LIGHTING
LINE TO LINE
LINE TO NEUTRAL
1000 CIRCULAR mils
KILOVOLTS (THOUSAND VOLTS)
KILOWATTS (THOUSAND WATTS)
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)
ISOLATED GROUND
KWH
LAN
LA
KW
KVA
Kcmil
KV
KILOWATT-HOURS
INCAND
KEY INTERLOCK
JUNCTION BOX
INCH/INCHES (")
INCANDESCENT
GROUND FAULT INTERRUPTER
HAND-OFF-AUTOMATIC
HIGH PRESSURE SODIUM
HEATING VENTILATION AND AIR CONDITIONING
HERTZ
HVAC
HZ
HTR
HR
HT
HPS
HOA
HP
HEATER
HEIGHT
HORSEPOWER
HOUR
GFI
G, GND, GRD
GEN
FLUOR
FL, FLR
GROUND
GENERATOR
FOOT/FEET (')
FLUORESCENT
FLOOR
CATV
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FIRE ALARM ANNUNCIATOR PANEL
ELECTRIC, ELECTRICAL
ELECTRIC METALLIC CONDUIT
EQUIPMENT GROUND
EWC
FAAP
FLA
FDR
EWH
FA
FULL LOAD AMPS
FEEDER
FIRE ALARM
FUSE
ELEC
EQ, EQUIP
EM, EMERG
EMT
ELEV
ENCL
EG
EQUIPMENT
ELEVATOR
EMERGENCY
ENCLOSURE
DISTRIBUTION PANEL
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
DPDT
DWG
DPST
DIST
DISC
DC
DP
DN
DRAWING
DISTRIBUTION
DIRECT CURRENT
DISCONNECT
DOWN
CPT
CU
CT
COM, COMM
CKT
CLG
COPPER
COMMUNICATIONS
CIRCUIT
CEILING
CABLE TELEVISION
CB CIRCUIT BREAKER
CONDUIT
FIRE ALARM CONTROL PANELFACP
FIRE ALARM EXTENDER PANELFAEP
CCTV CLOSED CIRCUIT TELEVISION
CP CONTROL PANEL
FLEX FLEXIBLE
HAND HOLEHH
LIGHTING CONTROL PANELLC, LCP
LIGHTING PANEL
L-G LINE TO GROUND
C
F
EXISTINGE, EX, EXIST
FT
IN
IG
JB, JBOX
K
LP
FOOT CANDLEFC
DIV DIVISION
C
D
E
F
G
H
I
J
K
L
HORIZONTAL MOUNTINGH
COR CONTRACTING OFFICER'S REPRESENTATIVE
X
XFMR
WP
WHM
W/
W/O
W
VFD
VA
V
UPS
UL
UON
UG
UGS
UGT
UGP
TYP
TV
TP
TEL,TELE
TELECOM
TC
TRANSFORMER
REMOVE DEVICE
WATT HOUR METER
WEATHERPROOF
VOLTS
VARIABLE FREQUENCY DRIVE/
VARIABLE FREQUENCY MOTOR
CONTROLLER
WITHOUT
WITH
WIRE
VOLT-AMPERES
UNDERGROUND PRIMARY
UNDERGROUND SECONDARY
UNDERGROUND TELEPHONE
UNDERWRITER'S LABORATORY
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
UNDERGROUND
TELECOMMUNICATIONS
TYPICAL
TELEVISION
TAMPERPROOF
TIME CLOCK
TELEPHONE
TB TERMINAL BLOCK
TBB TELEPHONE BACKBOARD
U
V
W
X
Z
TPST TRIPLE POLE SINGLE THROW
FDS FORWARD DEPLOYED SERVICES
JOINT SECURITY ARCHITECTUREJSA
PIV PERSONAL IDENTITY VERIFICATION
(WALL MOUNTED DEVICES MOUNTED 60" AFF TO TOP, UON.)
PATIENT BED STATION, SINGLE BED
PATIENT BED STATION, DOUBLE BED
PATIENT BED RECEPTACLE, 20" AFF
EMERGENCY CALL:
TOILETS: W/PULL CORD.
36" AFF AT TOILETS.
EMERGENCY CALL:
SHOWERS: W/PULL CORD.
84" AFF IN SHOWERS.
CODE BLUE
DUTY STATION
PATIENT BED STATION, SINGLE BED, PILLOW SPEAKER
CABLE TV INTERFACE
DOME LIGHT, CEILING OR WALL +80" AFF FLOOR OR 6" BELOW CEILING.
ZONE LIGHT, CEILING OR WALL +80" AFF FLOOR OR 6" BELOW CEILING.
NURSE CALL MASTER
NURSE CALL ANNUNCIATOR
NURSE CALL TERMINAL CABINET
HEAD-END EQUIPMENT
LOW-VOLTAGE LIGHT CONTROLLERS
SINGLE ENHANCED PATIENT STATION
BED CONTROL MODULE
N
N
N
N
N
N
N
N
N
NCM
ANN
NCT
B
T
S
C
D
P
TV
N
Z
PENDANT LIGHTING FIXTURE- TYPE AS INDICATED
NIGHTLIGHT FIXTURE- TYPE AS INDICATED
ES DOOR ELECTRIC STRIKE
HEC
LITE
EPS
N
M on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
A/E:
TRIPLE C - The A/E Group
(520) 481-8548
Mat Perkins
1 : 1
B
IM
/6
-2
-1
R e n o va te
D B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
.B e d .W in g .M
E P
.G e n e ra l.
S h e e ts
.r v t
/1
/2
:0 :3
P
M
09/12/2022 K. Luke N. Wicklund
618-22-102
1391 - E-001
ELECTRICAL ABBREVIATIONS AND SYMBOLS
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING100% CONSTRUCTION
DOCUMENTS12/17/2021
AREA NOT IN PROJECT SCOPE.
LIGHTING IS EXISTING TO REMAIN.
/F6 EDL103 /F6 EDL103
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
EXAM
3D-119B
EXAM
3D-119C
EXAM
3D-120
EXAM
3D-121
CORRIDOR
C3-17
BREAK
3D-123A
BREAK ROOM
3D-123
CORRIDOR
C3-18
PATIENT
3D-124
TLT
3D-124A
PATIENT
3D-126
TLT
3D-126A
PATIENT
3D-128C
ANTE
3D-128
PATIENT
3D-128B
TLT
3D-128A
PATIENT
3D-129
STORAGE
3D-134B
WORK ROOM
3D-134A
CHECK-IN
3D-134
EXAM
3D-135
EXAM
3D-136
TLT
3D-135A
CORRIDOR
C3-24
CORRIDOR
C3-22
CORRIDOR
C3-23
TLT
3D-101A
EXAM
3D-101
ANTE ROOM
3D-102A
PATIENT
3D-102
TLT
3D-102B
TLT
3D-103B
PATIENT
3D-103
ANTE
3D-103A
ANTE
3D-104A
PATIENT
3D-104
TLT
3D-104B
PATIENT
3D-107
TLT
3D-107B
ANTE
3D-107A
PATIENT
3D-108
TLT
3D-108A
TLT
3D-114A
PATIENT
3D-114B
ANTE
3D-114
PATIENT
3D-114C
PATIENT
3D-116B
TLT
3D-116A
ANTE
3D-116
PATIENT
3D-116C
TREATMENT
3D-119
EXAM
3D-119A
EXAM
3D-118
OFFICE
3D-125
EXAM
3D-127
STOR
3D-127A
EXAM
3D-117
EXAM
3D-112WORK ROOM
3D-115
OFFICE
3D-109
HAC
3D-110 TLT
3D-111
STORAGE
3D-130
NURSING RM
3D-109A
CORRIDOR
C3-19
CORRIDOR
C3-19
OFFICE
3D-131 3D-105
3D-105
OFFICE
3D-106
CORRIDOR
C3-12
TOILET
TOILET
3C-105
CORRIDOR
C3-27
CORRIDOR
C3-28
CORRIDOR
C3-26
STAIR
CORRIDOR
C3-25
CORRIDOR
C3-20
OFFICE
3C-103
AREA NOT IN PROJECT SCOPE.
LIGHTING IS EXISTING TO REMAIN.
/F3 EDL103 /F3 EDL103
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(612) 355-1251
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
GENERAL NOTES
KEYNOTES
1/8" = 1'-0"
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
.B e d .W in g .M
E P
.B .L
.r v t
/1
/2
:3
:5
A
M
09/12/2022 K. Luke N. Wicklund
618-22-102
1391 -
EDL103
ELECTRICAL LIGHTING CEILING PLANS -
THIRD LEVEL 3D - DEMO
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING
100% CONSTRUCTION
DOCUMENTS
1. REMOVE ALL EXISTING LIGHT FIXTURES AND CONTROLS .
2. REMOVE ALL EXISTING ELECTRICAL OUTLETS AND FEEDERS BACK TO THE
SOURCE PANEL. PROVIDE NEW ELECTRICAL DEVICES FOR THE RENOVATION.
3. PROVIDE NEW LIGHT FIXTURE, SEE LUMINARE SCHEDULE ON SHEET E-701 FOR
ADDITIONAL INFORMATION.
4. PROVIDE NEW LIGHT SWITCH, SEE E-900 SERIES FOR ADDITIONAL
INFORMATION.
5. PROVIDE NEW ELECTRICAL OUTLETS.
6. SEE SHEET E-601 FOR ADDITIONAL ONE-LINE INFORMATION.
7. REMOVE FEEDERS SERVING MECHANICAL EQUIPMENT TO BE REPLACED WITH
THIS PROJECT. PROVIDE NEW FEEDERS. AIR HANDLING UNIT, EXHAUST AND
RETURN FANS SHALL BE SERVED FROM AN EMERGENCY POWER SOURCE.
8. PROVIDE A CODE SIZED RECESSED JBOX WITH A 1-1/4" CONDUIT STUBBED
ABOVE CEILING FOR NURSE CALL DEVICE.
9. PROVIDE 120V CIRCUIT TO SERVE ROLLER BLINDS, SEE ARCH PLANS FOR
DETAILS.
10. PROVIDE 120V CIRCUIT TO SERVE NEW PLUMBING FIXTURES. SEE 22 40 00 FOR
DETAILS.
11. DEMOLISH EXISTING PANELBOARD, REPLACE WITH NEW PANELBOARD, SIZE AS
INDICATED ON ELECTRICAL PANEL SCHEDULES AND ELECTRICAL ONE-LINES.
REPLACE CIRCUIT BREAKER, SOURCE FEEDER AND REPLACE ALL EXISTING
CIRCUITS TO NEW PANELBOARD AS INDICATED. SEE E-600 AND E-700 SERIES
SHEETS FOR ADDITIONAL INFORMATION.
12. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO
ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL
DEVICE/CIRCUITS NOT ASSOICATED WITH THE LOCAL DEMOLITION SHALL BE
PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE PER CONDITONS
PRIOR TO DEMOLTION. ALL DEMOLITION / PHASING SHALL BE COORDINATED
WITH THE VA COR.
13. EXISTING LIGHTING/RECEPTACLES TO REMAIN, PROTECT IN PLACE
14. PROVIDE 120V CIRCUIT TO SERVE NEW ACCESS CONTROLS. SEE
ARCHITECUTRAL DOOR SCHEDULE FOR ADDITIONAL INFORMATION.
15. PROVIDE 120V CONNECTION TO 24V TRANSFORMER FURNISHED WITH
RESPECTIVE MONITORS AND PRESSURE SENSORS. COORDINATE EXACT
LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.
16. EXISTING ELECTRICAL PANEL TO REMAIN, PROTECT IN PLACE.
17. NEW PANELBOARD, SIZE AS INDICATED ON ELECTRICAL PANEL SCHEUDLES AND
ELECTRICAL ONE-LINES. SEE E-600 AND E-700 SERIES FOR ADDITIONAL
INFORMATION.
18. EXISTING ELECTRICAL EQUIPMENT TO REMAIN, PROTECT IN PLACE.
19. PROVIDE NEW 30kW TRANSFORMER IN LOCATION INDICATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS. SEE E-600 AND E-700
SERIES FOR ADDITIONAL INFORMATION.
20. DEMOLISH EXISTING TRANSFORMER, REPLACE WITH NEW TRANSFORMER, SIZE
AS INDICATED ON ELECTRICAL PANEL SCHEDULES AND ELECTRICAL ONE-LINES.
SEE E-600 AND E-700 SERIES SHEETS FOR ADDITIONAL INFORMATION.
21. DEMOLISH EXISTING DISCONNECT FOR PANELS BEING REPLACED, REPLACE
WITH NEW DISCONNECT, SIZE AS INDICATED ON ELECTRICAL PANEL
SCHEDULES AND ELECTRICAL ONE-LINES. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION.
22. PROVIDE NEW ELECTRICAL DISCONNECT FOR PANELBOARD, SIZE AS
INDICATED.
23. PROVIDE NEW CEILING MOUNTED PHOTOCELL, SEE E-900 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
24. PROVIDE 120V CONNECTION TO SERVE PLUMBING FIXTURE POWER SUPPLY.
25. COORDINATE RECEPTACLE WITH FOOTWALL FOR TV.
26. (NOT USED)
27. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACUTURERS
RECOMMENDATIONS.
28. PROVIDE EMERGENCY POWER FOR PATIENT MONITORING STATION ABOVE
COUNTER.
29. PROVIDE EMERGENCY POWER AT 72" AFF FOR BMS DSIPLAY
30. PROVIDE J-BOX, CONDUIT, AND FEEDERS FOR PNEUMATIC TUBE SYSTEM
POWER.
31. PROVIDE J-BOX, CONDUIT, AND FEEDERS FOR MED GAS PANEL ALARM.
32. PROVIDE PRE-WIRED WITH DUPLEX RECEPTACLES SPACED 1' - 6" ON CENTER.
CABLE ENTRY (POWER) SHALL BE HIDDEN, INSTALLED FROM BACK OF
WIREWAY. WIREMOLD #ALDS4000 SERIES OR APPROVED EQUAL. PROVIDE WIRE
MOLD AND J-BOX AT EACH LEVEL (4) EACH SHELF. COORDINATE SPACING AND
HEIGHTS WITH FURNISHING VENDOR.
33. PROVIDE TWO DUPLEX RECEPTACLES INSIDE CABINET. ONE AT A HEIGHT OF
+36" AFF AND THE OTHER AT A HEIGHT OF +18" AFF.
34. PROVIDE 120V SERVICE TO NEW HVAC CONTROLS ENCLOSURES. COORDINATE
WITH HVAC CONTROLS CONTRACTOR
35. PROVIDE NEW VFD TO SF-27 (SUPPLY FAN).
36. PROVIDE NEW VFD TO EF-34 (EXHAUST FAN).
37. PROVIDE NEW VFD TO RF-18 (RETURN FAN).
38. NEW DOMESTIC WATER MONITORING SYSTEM CONTROL PANEL. REFER TO
DIAGRAM ON SHEET P-501.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
SCALE: 1/8" = 1'-0"
F3
ELECTRICAL LIGHTING CEILING
PLANS - THIRD LEVEL 3D - DEMO
SCALE: 1/8" = 1'-0"
F6
ELECTRICAL LIGHTING CEILING
PLANS - THIRD LEVEL 3D - DEMO
12/17/2021
J
CR
CR
CL3A1-2
CL3A1-1
NH3A1-1
NL3A1-1B
NL3A1-1A
NT3A1-1
(E) CL3A2-2
(E) CL3A2-1
(E) PP3A2-1
(E) EH3A2-1
(E) NL3A2-2
(E) NL3A2-1B
(E) NL3A2-1A
NT3A2-1
(E) NH3A2-1
ELECTRICAL ROOM
3U-137
ELECTRICAL ROOM
3D-122A
CORRIDOR
C3-12
AREA NOT IN PROJECT SCOPE
ELECTRICAL ITEMS ARE EXISTING TO REMAIN
EP400
F4
/F6 EDP103 /F6 EDP103
(E) NL3A2-2
(E) NL3A2-1B
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
CORRIDOR
C3-26
TOILET
3C-104
TOILET
3C-105
CORRIDOR
C3-27 CORRIDOR
C3-28
ROOM
3C-106
STAIR
CORRIDOR
C3-12
AREA NOT IN PROJECT SCOPE.
ELECTRICAL ITEMS ARE EXISTING TO REMAIN.
TYP.
TYP.
/F3 EDP103 /F3 EDP103
EXAM
3D-119B
EXAM
3D-119C
EXAM
3D-120
EXAM
3D-121
EXAM
3D-119A
TREATMENT
3D-119
PATIENT
3D-116C
ANTE
3D-116
PATIENT
3D-116B
TLT
3D-116A
PATIENT
3D-114C
ANTE
3D-114
PATIENT
3D-114B
TLT
3D-114A
TLT
3D-108APATIENT
3D-108
PATIENT
3D-107
ANTE
3D-107A
TLT
3D-107B
TLT
3D-104B
ANTE
3D-104A
PATIENT
3D-104
PATIENT
3D-103
TLT
3D-103B
ANTE
3D-103A
TLT
3D-102BPATIENT
3D-102
ANTE ROOM
3D-102A
EXAM
3D-101
TLT
3D-101A
CORRIDOR
C3-22
CORRIDOR
C3-24
CORRIDOR
C3-23
CORRIDOR
C3-19
EXAM
3D-135
EXAM
3D-136
TLT
3D-135A
CHECK-IN
3D-134
WORK ROOM
3D-134A
STORAGE
3D-134B
PATIENT
3D-129
HAC
3D-110
TLT
3D-111
OFFICE
3D-109
NURSING RM
3D-109A
OFFICE
3D-106
STORAGE
3D-130
OFFICE
3D-131
3D-105
3D-105
PATIENT
3D-128B
TLT
3D-128A
ANTE
3D-128
PATIENT
3D-128C
EXAM
3D-112
WORK ROOM
3D-115
EXAM
3D-127
STOR
3D-127A
EXAM
3D-117
EXAM
3D-118
OFFICE
3D-125
CORRIDOR
C3-18
CORRIDOR
C3-19
TLT
3D-126A
PATIENT
3D-126
TLT
3D-124A
PATIENT
3D-124
BREAK ROOM
3D-123
BREAK
3D-123A
CORRIDOR
C3-17
CORRIDOR
C3-18
OFFICE
3C-103
LINEN CHUTE
3D-112A on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(612) 355-1251
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
GENERAL NOTES
KEYNOTES
1/8" = 1'-0"
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
.B e d .W in g .M
E P
.B .L
.r v t
/1
/2
:3
:0
A
M
09/12/2022 K. Luke N. Wicklund
618-22-102
1391 -
EDP103
ELECTRICAL POWER PLANS - THIRD LEVEL
3D - DEMO
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING
100% CONSTRUCTION
DOCUMENTS
1. REMOVE ALL EXISTING LIGHT FIXTURES AND CONTROLS .
2. REMOVE ALL EXISTING ELECTRICAL OUTLETS AND FEEDERS BACK TO THE
SOURCE PANEL. PROVIDE NEW ELECTRICAL DEVICES FOR THE RENOVATION.
3. PROVIDE NEW LIGHT FIXTURE, SEE LUMINARE SCHEDULE ON SHEET E-701 FOR
ADDITIONAL INFORMATION.
4. PROVIDE NEW LIGHT SWITCH, SEE E-900 SERIES FOR ADDITIONAL
INFORMATION.
5. PROVIDE NEW ELECTRICAL OUTLETS.
6. SEE SHEET E-601 FOR ADDITIONAL ONE-LINE INFORMATION.
7. REMOVE FEEDERS SERVING MECHANICAL EQUIPMENT TO BE REPLACED WITH
THIS PROJECT. PROVIDE NEW FEEDERS. AIR HANDLING UNIT, EXHAUST AND
RETURN FANS SHALL BE SERVED FROM AN EMERGENCY POWER SOURCE.
8. PROVIDE A CODE SIZED RECESSED JBOX WITH A 1-1/4" CONDUIT STUBBED
ABOVE CEILING FOR NURSE CALL DEVICE.
9. PROVIDE 120V CIRCUIT TO SERVE ROLLER BLINDS, SEE ARCH PLANS FOR
DETAILS.
10. PROVIDE 120V CIRCUIT TO SERVE NEW PLUMBING FIXTURES. SEE 22 40 00 FOR
DETAILS.
11. DEMOLISH EXISTING PANELBOARD, REPLACE WITH NEW PANELBOARD, SIZE AS
INDICATED ON ELECTRICAL PANEL SCHEDULES AND ELECTRICAL ONE-LINES.
REPLACE CIRCUIT BREAKER, SOURCE FEEDER AND REPLACE ALL EXISTING
CIRCUITS TO NEW PANELBOARD AS INDICATED. SEE E-600 AND E-700 SERIES
SHEETS FOR ADDITIONAL INFORMATION.
12. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO
ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL
DEVICE/CIRCUITS NOT ASSOICATED WITH THE LOCAL DEMOLITION SHALL BE
PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE PER CONDITONS
PRIOR TO DEMOLTION. ALL DEMOLITION / PHASING SHALL BE COORDINATED
WITH THE VA COR.
13. EXISTING LIGHTING/RECEPTACLES TO REMAIN, PROTECT IN PLACE
14. PROVIDE 120V CIRCUIT TO SERVE NEW ACCESS CONTROLS. SEE
ARCHITECUTRAL DOOR SCHEDULE FOR ADDITIONAL INFORMATION.
15. PROVIDE 120V CONNECTION TO 24V TRANSFORMER FURNISHED WITH
RESPECTIVE MONITORS AND PRESSURE SENSORS. COORDINATE EXACT
LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.
16. EXISTING ELECTRICAL PANEL TO REMAIN, PROTECT IN PLACE.
17. NEW PANELBOARD, SIZE AS INDICATED ON ELECTRICAL PANEL SCHEUDLES AND
ELECTRICAL ONE-LINES. SEE E-600 AND E-700 SERIES FOR ADDITIONAL
INFORMATION.
18. EXISTING ELECTRICAL EQUIPMENT TO REMAIN, PROTECT IN PLACE.
19. PROVIDE NEW 30kW TRANSFORMER IN LOCATION INDICATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS. SEE E-600 AND E-700
SERIES FOR ADDITIONAL INFORMATION.
20. DEMOLISH EXISTING TRANSFORMER, REPLACE WITH NEW TRANSFORMER, SIZE
AS INDICATED ON ELECTRICAL PANEL SCHEDULES AND ELECTRICAL ONE-LINES.
SEE E-600 AND E-700 SERIES SHEETS FOR ADDITIONAL INFORMATION.
21. DEMOLISH EXISTING DISCONNECT FOR PANELS BEING REPLACED, REPLACE
WITH NEW DISCONNECT, SIZE AS INDICATED ON ELECTRICAL PANEL
SCHEDULES AND ELECTRICAL ONE-LINES. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION.
22. PROVIDE NEW ELECTRICAL DISCONNECT FOR PANELBOARD, SIZE AS
INDICATED.
23. PROVIDE NEW CEILING MOUNTED PHOTOCELL, SEE E-900 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
24. PROVIDE 120V CONNECTION TO SERVE PLUMBING FIXTURE POWER SUPPLY.
25. COORDINATE RECEPTACLE WITH FOOTWALL FOR TV.
26. (NOT USED)
27. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACUTURERS
RECOMMENDATIONS.
28. PROVIDE EMERGENCY POWER FOR PATIENT MONITORING STATION ABOVE
COUNTER.
29. PROVIDE EMERGENCY POWER AT 72" AFF FOR BMS DSIPLAY
30. PROVIDE J-BOX, CONDUIT, AND FEEDERS FOR PNEUMATIC TUBE SYSTEM
POWER.
31. PROVIDE J-BOX, CONDUIT, AND FEEDERS FOR MED GAS PANEL ALARM.
32. PROVIDE PRE-WIRED WITH DUPLEX RECEPTACLES SPACED 1' - 6" ON CENTER.
CABLE ENTRY (POWER) SHALL BE HIDDEN, INSTALLED FROM BACK OF
WIREWAY. WIREMOLD #ALDS4000 SERIES OR APPROVED EQUAL. PROVIDE WIRE
MOLD AND J-BOX AT EACH LEVEL (4) EACH SHELF. COORDINATE SPACING AND
HEIGHTS WITH FURNISHING VENDOR.
33. PROVIDE TWO DUPLEX RECEPTACLES INSIDE CABINET. ONE AT A HEIGHT OF
+36" AFF AND THE OTHER AT A HEIGHT OF +18" AFF.
34. PROVIDE 120V SERVICE TO NEW HVAC CONTROLS ENCLOSURES. COORDINATE
WITH HVAC CONTROLS CONTRACTOR
35. PROVIDE NEW VFD TO SF-27 (SUPPLY FAN).
36. PROVIDE NEW VFD TO EF-34 (EXHAUST FAN).
37. PROVIDE NEW VFD TO RF-18 (RETURN FAN).
38. NEW DOMESTIC WATER MONITORING SYSTEM CONTROL PANEL. REFER TO
DIAGRAM ON SHEET P-501.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
SCALE: 1/8" = 1'-0"
F3
ELECTRICAL POWER PLANS - THIRD
LEVEL 3D - DEMO
SCALE: 1/8" = 1'-0"
F6
ELECTRICAL POWER PLANS - THIRD
LEVEL 3D - DEMO
TYP.
TYP.
TYP.
AREA NOT IN PROJECT SCOPE.
EXISTING TO REMAIN.
POE
ACC
/F2 EDP103i /F2 EDP103i
TYP.
TYP.
AREA NOT IN PROJECT SCOPE.
EXISTING TO REMAIN.
/F6 EDP103i /F6 EDP103i on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(612) 355-1251
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
GENERAL NOTES
KEYNOTES
1/8" = 1'-0"
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
.B e d .W in g .M
E P
.B .L
.r v t
/1
/2
:3
:0
A
M
09/12/2022 K. Luke K.Hutchinson
618-22-102
1391 - EDP103i
ELECTRICAL POWER PLAN - THIRD LEVEL
INTERSTITIAL
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING
100% CONSTRUCTION
DOCUMENTS
NTS
F6
ELECTRICAL INTERSTITIAL SOUTH - DEMO
NTS
F2
ELECTRICAL INTERSTITIAL NORTH - DEMO
1. EXISTING DUCTBANK ELECTRICAL RACEWAY, SEE E-603 FOR ADDITIONAL
INFORMATION.
2. DUCTBANK ELECTRICAL RACEWAY DROP TO ELECTRICAL ROOM, SEE E-603 FOR
ADDITIONAL INFORMATION.
3. WALLS SHOWN ON PLAN ARE FROM THIRD LEVEL BELOW FOR REFERENCE
ONLY. SEE A-103 FOR ADDITIONAL INFORMATION.
4. ELECTRICAL JUNCTION BOX TO BE DEMOLISHED. INFILL OR CLOSE
PENETRATION WITH MATERIALS THAT MEET REQUIRED FIRE RATING OF
EXISTING CONCRETE SLAB.
5. WIRE NEW SECURITY DEVICES TO HEAD-END EQUIPMENT.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
PH
D D
PH
D
DD
D3 D3
D
D
D D3D3D3
D
PH
PH
PH
PH
D3
D D
PH
PH
PH
D3D3 D3D3D
DD
DD
D
D
D
D3D3
D
D
D
D3D3
D
D
D
D
D
D
DD
DD
D
D
DD
DD
D
D
D
DD
DD
D
DD
D
D
D
D D
D
D
D
D D
D
DD
D
DD
DD
D
D
PH
D3D3
D
D
D3D3
D
D
D3D3
D
D
PH
PH
PH
PH
PH
PH
PH
PH
PH
PH
D
D3D3 D
D3D3
D
D
D3 D3
D3 D3
D3 D3 D3 D3
D3 D3
D
D
D
D
D3 D3
D
D 3 D3 D3
D3D3
D
D
D3 D3
D
D
D
D
D3 D3
D3 D3
D
D
D D
D
D D
D
D D
DD
D D
D
D 3 D
D3
D
D
D
DD
D3
D3 D3
D3
D3DD3
D
D3
D
D
PATIENT 9
3D-109
RR 9
3D-109A
RR 10
3D-121A
CIRCULATION
C3-18
E
E
E
(E) LL3A2-1- 4
(E) LL3A2-1- 4 (E) LL3A2-1- 4
CORRIDOR
C3-12
NL3A2-1B- 5
NL3A2-1B- 5E
E
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
E E E
C
D E
B
CL3A2-1- 5
CL3A2-1- 5
CL3A2-1- 5CL3A2-1- 5
AA
C
D
AA
CL3A2-1- 5 CL3A2-1- 5
AA
Z (E) LL3A2-1- 4
Z
(E) LL3A2-1- 4
ELECTRICAL ROOM
3D-122A
IT CLOSET
3D-122B
EP400
F7
MECHANICAL ROOM
3D-122
TYP.
AREA NOT IN PROJECT SCOPE.
LIGHTING IS EXISTING TO REMAIN.
EP401
C2
EP401
C5
EP401
C7
D1
D2
D3
PATIENT 9
3D-109
PATIENT 8
3D-108
PATIENT 7
3D-107
PATIENT 6
3D-106
PATIENT 5
3D-105
PATIENT 4
3D-104
PATIENT 3
3D-103
PATIENT 2
3D-102
BARIATRIC 1
3D-101
RR 9
3D-109A
ANTE ROOM
3D-109B
RR 8
3D-108A
RR 7
3D-107A
RR 6
3D-106A
RR 5
3D-105A
RR 4
3D-104A
RR 3
3D-103A
RR 2
3D-102A
RR 1
3D-101A
ANTE ROOM
3D-101B
CIRCULATION
C3-24
CIRCULATION
C3-25
CIRCULATION
C3-20
CIRCULATION
C3-19
MSA'S
3D-100
ASST. NURSE MNGR
3D-110
STAFF WORK
3D-136
NURSE MNGR OFFICE
3D-111
NUTRITION
3D-135
MED ROOM
3D-112
SOILED UTILITY
3D-134
SPS STORAGE
3D-114
PHARM OFFICE
3D-120
EQUIPMENT ROOM
3D-115
STAFF BREAK ROOM
3D-116
HAC
3D-119
OXYGEN STOR.
3D-118
RR 10
3D-121A
ANTE ROOM
3D-121B
PATIENT 10
3D-121
PATIENT 11
3D-123
RR 11
3D-123A
RR 12
3D-125A
PATIENT 12
3D-125
PATIENT 13
3D-126
PATIENT 14
3D-128
RR 13
3D-126A
RR 14
3D-128A
PATIENT 15
3D-129
RR 15
3D-129A
RR 16
3D-131A
SAFER PATIENT 16
3D-131
SAFER PATIENT 17
3D-132
RR 17
3D-132A
PATIENT 18
3D-133
RR 18
3D-133A
ANTE ROOM
3D-133B
CLEAN LINENS
3D-138
EQUIP. ALCOVE
3D-140
EQUIP. ALCOVE
3D-127
SINK ALCOVE
3C-134B
EQUIP. ALCOVE
3D-139
EQUIP ALCOVE
3D-137
CHARTING
C3-19A
CHARTING
C3-19B
CHARTING
C3-19C
CHARTING
3D-142
CHARTING
3D-141
CHARTING
C3-25A
CIRCULATION
C3-18
CHUTE
3C-134A
CL3A2-1- 14
A A A
CL3A2-1- 14 CL3A2-1- 14
E
B
A A
A
D
CL3A2-1- 14
CL3A2-1- 14
CL3A2-1- 14
CL3A2-1- 14 CL3A2-1- 14
CL3A2-1- 14 CL3A2-1- 14
CL3A2-1- 14 CL3A2-1- 14
NL3A2-1B- 25
NL3A2-1B- 25
C
NL3A2-1B- 25
NL3A2-1B- 25
CL3A2-1- 10 CL3A2-1- 10
CL3A2-1- 10CL3A2-1- 10
CL3A2-1- 10CL3A2-1- 10
CL3A2-1- 10 CL3A2-1- 10
CL3A2-1- 10 CL3A2-1- 10
CL3A2-1- 10CL3A2-1- 10
CL3A2-1- 10
A A A
A AAA
A A A A
AA
AA
A A
A A
AA
AA
A A
CL3A2-1- 6 CL3A2-1- 6
CL3A2-1- 6
CL3A2-1- 6
CL3A2-1- 6 CL3A2-1- 6
CL3A2-1- 6 CL3A2-1- 6
CL3A2-1- 6 CL3A2-1- 6
CL3A2-1- 6 CL3A2-1- 6
AA
A A
AA
A A
A
AA
A
CL3A2-1- 8 CL3A2-1- 8
CL3A2-1- 8CL3A2-1- 8
CL3A2-1- 8 CL3A2-1- 8
CL3A2-1- 8
CL3A2-1- 8
CL3A2-1- 8CL3A2-1- 8
CL3A2-1- 8 CL3A2-1- 8
A A
A A
A A
A A
A A
A A
CL3A2-1- 9 CL3A2-1- 9
CL3A2-1- 9 CL3A2-1- 9
CL3A2-1- 9
CL3A2-1- 9
CL3A2-1- 9
CL3A2-1- 9
CL3A2-1- 9CL3A2-1- 9
CL3A2-1- 9CL3A2-1- 9
(E) LL3A2-1- 4
E
E
E
E
E
E
E
E
E
E
E
(E) LL3A2-1- 4
(E) LL3A2-1- 4 (E) LL3A2-1- 4
(E) LL3A2-1- 4
(E) LL3A2-1- 4
(E) LL3A2-1- 4
(E) LL3A2-1- 4
(E) LL3A2-1- 4
(E) LL3A2-1- 4
(E) LL3A2-1- 4
CORRIDOR
C3-12
NL3A2-1B- 23
E
B NL3A2-1B- 23
NL3A2-1B- 23D
E
B NL3A2-1B- 23
NL3A2-1B- 23
NL3A2-1B- 23D
C
NL3A2-1B- 23
NL3A2-1B- 23
C
DNL3A2-1B- 23
NL3A2-1B- 23
C
E
B
NL3A2-1B- 23
NL3A2-1B- 23
NL3A2-1B- 23D
E
NL3A2-1B- 23
B
NL3A2-1B- 23
NL3A2-1B- 23
C
NL3A2-1B- 23
B
E
NL3A2-1B- 23NL3A2-1B- 23 D
C
N L3
A 2-
1B
N
L3 A
2- 1B
C
DNL3A2-1B- 23
NL3A2-1B- 23
E
B
NL3A2-1B- 23
NL3A2-1B- 23
B
E NL3A2-1B- 23
NL3A2-1B- 23
C
NL3A2-1B- 23 D
E
B
D
C
NL3A2-1B- 23
NL3A2-1B- 23
NL3A2-1B- 23
NL3A2-1B- 23
CL3A2-1- 1
CL3A2-1- 1
E
E
CL3A2-1- 1
E
CL3A2-1- 1
(E) LL3A2-1- 4
A
E
CL3A2-1- 1
CL3A2-1- 1
E
E
CL3A2-1- 1
E
CL3A2-1- 1
CL3A2-1- 1
E
E
CL3A2-1- 1
CL3A2-1- 1
E E
CL3A2-1- 1
E
(E) LL3A2-1- 4 A
A
(E) LL3A2-1- 4
(E) LL3A2-1- 4A
A CL3A2-1- 2
CL3A2-1- 2CL3A2-1- 2 CL3A2-1- 2
A AA
NL3A2-1B- 5
E
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1B- 5
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
NL3A2-1B- 5
NL3A2-1B- 5
E
NL3A2-1B- 5
E
E
NL3A2-1B- 5
NL3A2-1B- 5
E
NL3A2-1B- 5
E
NL3A2-1B- 5
E
NL3A2-1B- 5
E
C
NL3A2-1B- 5
NL3A2-1B- 5E
E
NL3A2-1B- 5
NL3A2-1B- 5
F
F
F
NL3A2-1B- 5
NL3A2-1B- 5
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
N L3
A 2-
A
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
N L3
A 2-
A
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
CL3A2-1- 5 CL3A2-1- 5
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9 NL3A2-1A- 9
NL3A2-1A- 9NL3A2-1A- 9NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
NL3A2-1A- 9
E E
EEE
E
E E
E E E
C
D E
B
CL3A2-1- 11
CL3A2-1- 5
CL3A2-1- 5
CL3A2-1- 5CL3A2-1- 5
A
AA
C
D
AA
E
B
A
CL3A2-1- 11
C
D E
B
CL3A2-1- 11 CL3A2-1- 11
CL3A2-1- 11 CL3A2-1- 11
CL3A2-1- 11CL3A2-1- 11
CL3A2-1- 11 CL3A2-1- 11
CL3A2-1- 11 CL3A2-1- 11
AA
AA
A A
A A A A
AA
C
D
E
B
CL3A2-1- 5 CL3A2-1- 5
CL3A2-1- 5
CL3A2-1- 5 CL3A2-1- 5
AA
A A A
CL3A2-1- 16 CL3A2-1- 16
CL3A2-1- 16 CL3A2-1- 16
CL3A2-1- 16
CL3A2-1- 16
CL3A2-1- 16
CL3A2-1- 16
CL3A2-1- 16CL3A2-1- 16
CL3A2-1- 16
CL3A2-1- 16
E
B
A A
AA
D
C
A A
A A
C
D
AA
E
A
A
B
CL3A2-1- 10
CL3A2-1- 2
CL3A2-1- 2
CL3A2-1- 11
CL3A2-1- 16
CL3A2-1- 8
CL3A2-1- 9
CL3A2-1- 4
CL3A2-1- 4 CL3A2-1- 4
CL3A2-1- 4CL3A2-1- 4
CL3A2-1- 4
CL3A2-1- 4
CL3A2-1- 4CL3A2-1- 4
CL3A2-1- 4CL3A2-1- 4
CL3A2-1- 4 CL3A2-1- 4
CL3A2-1- 10
NL3A2-1B- 23
NL3A2-1B- 23
NL3A2-1B- 25
NL3A2-1B- 25
NL3A2-1B- 25
NL3A2-1B- 25
NL3A2-1B- 25
NL3A2-1B- 25
NL3A2-1B- 25
NL3A2-1B- 25
E
B
A A
A
C
D
AA
A
G
B
E
A A
A A
D
C
A A
A A
AA
E
B
A A
G
D
C
G
A
A
G
G
G
E
E
E
Z(E) LL3A2-1- 4
(E) LL3A2-1- 4
Z
Z
(E) LL3A2-1- 4
Z
(E) LL3A2-1- 4
Z (E) LL3A2-1- 4
Z
(E) LL3A2-1- 4
Z
(E) LL3A2-1- 4
(E) LL3A2-1- 4
Z
CORRIDOR
C3-26
TOILET
3C-104
TOILET
3C-105
CORRIDOR
C3-27 CORRIDOR
C3-28
ROOM
3C-106
STAIR
TYP.
24 TYP.
TYP.
TYP.
TYP.
TYP.
AREA NOT IN PROJECT SCOPE.
ELECTRICAL ITEMS ARE EXISTING TO REMAIN.
CLEAN UTILITY
3D-113
A
CL3A2-1- 2
A
CL3A2-1- 2
STAFF TOILET
3D-117
NL3A2-1B- 5
E on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(612) 355-1251
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
GENERAL NOTES
KEYNOTES
1/8" = 1'-0"
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
.B e d .W in g .M
E P
.B .L
.r v t
/1
/2
:3
:1
A
M
09/12/2022 K. Luke N. Wicklund
618-22-102
1391 - EL103
ELECTRICAL LIGHTING CEILING PLANS
-THIRD LEVEL 3D - NEW
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING
100% CONSTRUCTION
DOCUMENTS
SCALE: 1/8" = 1'-0"
F3
ELECTRICAL LIGHTING CEILING PLAN
-THIRD LEVEL 3D - NEW
DEDUCTIVE ALTERNATES
D1
DEDUCTIVE ALTERNATE #1: PROVIDE STORAGE ROOM IN
LIEU OF PATIENT ROOMS 10 AND 11 (3D-310/A & 3D-311/A).
REMOVE SCOPE OF WORK ASSOCIATED WITH NEW
HEADWALL, PLUMBING, SPECIALTY EQUIPMENT.
D2
D3
DEDUCTIVE ALTERNATE #2: PROVIDE STORAGE ROOM IN
LIEU OF PATIENT ROOMS 12 AND 13 (3D-312/A & 3D-313/A).
REMOVE SCOPE OF WORK ASSOCIATED WITH NEW
HEADWALL, PLUMBING, SPECIALTY EQUIPMENT.
DEDUCTIVE ALTERNATE #3: PROVIDE STORAGE ROOM IN
LIEU OF PATIENT ROOMS 14, 15, 16, AND 17 (3D-314/A,
3D-315/A, 3D-316/A & 3D-317/A). REMOVE SCOPE OF WORK
ASSOCIATED WITH NEW HEADWALL, PLUMBING, SPECIALTY
EQUIPMENT.
NOTE: DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE TAKEN IN
SEQUENTIAL ORDER.
SCALE: 1/8" = 1'-0"
F6
ELECTRICAL LIGHTING CEILING PLAN
-THIRD LEVEL 3D - NEW
1. REMOVE ALL EXISTING LIGHT FIXTURES AND CONTROLS .
2. REMOVE ALL EXISTING ELECTRICAL OUTLETS AND FEEDERS BACK TO THE
SOURCE PANEL. PROVIDE NEW ELECTRICAL DEVICES FOR THE RENOVATION.
3. PROVIDE NEW LIGHT FIXTURE, SEE LUMINAIRE SCHEDULE ON SHEET E-701 FOR
ADDITIONAL INFORMATION.
4. PROVIDE NEW LIGHT SWITCH, SEE E-900 SERIES FOR ADDITIONAL
INFORMATION.
5. PROVIDE NEW ELECTRICAL OUTLETS.
6. SEE SHEET E-601 FOR ADDITIONAL ONE-LINE INFORMATION.
7. REMOVE FEEDERS SERVING MECHANICAL EQUIPMENT TO BE REPLACED WITH
THIS PROJECT. PROVIDE NEW FEEDERS. AIR HANDLING UNIT, EXHAUST AND
RETURN FANS SHALL BE SERVED FROM AN EMERGENCY POWER SOURCE.
8. PROVIDE A CODE SIZED RECESSED JBOX WITH A 1-1/4" CONDUIT STUBBED
ABOVE CEILING FOR NURSE CALL DEVICE.
9. PROVIDE 120V CIRCUIT TO SERVE ROLLER BLINDS, SEE ARCH PLANS FOR
DETAILS.
10. PROVIDE 120V CIRCUIT TO SERVE NEW PLUMBING FIXTURES.