Attachment D.7 Drawings 7 of 7 - 37 pages.pdf

PDF 19 MB Posted

Attached to
Z1DA--618-22-102, Renovate for a Private Patient Bed Ward (3D) 36C263-23-AP-0055
Solicitation number
36C26323R0023
Issued by

About this file

This document provides details for a federal contract solicitation from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23. The solicitation number is 36C26323R0023 and is for project Z1DA--618-22-102 to renovate a private patient bed ward (3D) at facility 36C263. The solicitation involves renovating an existing facility to create a private patient bed ward and includes seven drawings as an attachment to the solicitation document. Responses to the solicitation are due on an unspecified date. The award date is also unspecified. The solicitation is for renovating and upgrading an existing inpatient facility to improve patient privacy and accommodate more single occupancy rooms.

View the file

Other files

File Type Posted
S06 Q_A Atch 1 - Revised Atch C.1 Specifications Vol 1.2 - 609 pages.pdf PDF
S06 36C26323R0023 Amendment 0005.docx DOCX document
S06 Revised Drawings - 12 pages.pdf PDF
S06 Q_A Atch 2 - Revised Atch C.1 Specifications Vol 1.1 - 291 pages.pdf PDF
S06 Late Questions - Solicitation 36C26323R0023 - 1 page.pdf PDF
S06 Addendum Number 2 - 2 pages.pdf PDF
36C26323R0023 0004.docx DOCX document
S06 36C26323R0023 Amendment 0003.docx DOCX document
S06 Q_A Atch 3 - Revised Drawing A-601 - 1 page.pdf PDF
S06 Revised Atch F Wage Determination MN20230117 4-14-23 - 9 pages.pdf PDF
S06 Q_A Atch 5 - Lidar Scans - 1 page.pdf PDF
S06 Q_A Atch 4 - Revised Drawing Q-601 - 1 page.pdf PDF
S06 Q_A Atch 1.2 - Revised Atch C.1 Specifications Vol 1.2 - 634 pages.pdf PDF
S06 Revised Drawings MP103i M-501 and M-502 - 3 pages.pdf PDF
S06 36C26323R0023 Amendment 0002.docx DOCX document
S06 Q_A Atch 1.1 - Revised Atch C.1 Specifications Vol 1.1 - 291 pages.pdf PDF
S06 Q_A Atch 7 - Revised Drawing GI201 - 1 page.pdf PDF
S06 Revised Drawings M-702 M-802 and M-804 - 3 pages.pdf PDF
S06 Questions - Solicitation 36C26323R0023.pdf PDF
S06 Q_A Atch 6 - Revised Drawings GI000 and GI101 - 2 pages.pdf PDF
S06 Q_A Atch 2 - Revised Drawings - 15 pages.pdf PDF
S06 Q_A Atch 8 - Revised Atch E Brand Name J and A - 30 pages.pdf PDF
S06 Revised Drawings M-503 M-504 and M-601 - 3 pages.pdf PDF
S06 Addendum Number 1 - 3 pages.pdf PDF
S06 Attachment 1 - Pre-Bid Sign-In Sheet - 2 pages.pdf PDF
S06 36C26323R0023 Amendment 0001.docx DOCX document
S06 Attachment 2 - Pre-Bid Site Visit Agenda - 2 pages.pdf PDF
36C26323R0023.docx DOCX document
Attachment I Questions Request Form - 1 page.doc DOC document
Attachment D.6 Drawings 6 of 7 - 13 pages.pdf PDF
Attachment A SOW - 3 pages.pdf PDF
Attachment B Price Schedule Breakdown Sheet - 1 page.xlsx XLSX spreadsheet
Attachment J VAAR 852.219-75 Limitations on Subcontracting Cert of Compliance - 2 pages.pdf PDF
Attachment C.3 Specifications Volume 3 - 410 pages.pdf PDF
Attachment F Wage Determination MN20230117 1-6-23 - 7 pages.pdf PDF
Attachment D.1 Drawings 1 of 7 - 3 pages.pdf PDF
Attachment D.4 Drawings 4 of 7 - 24 pages.pdf PDF
Attachment G VA6500 Appendix C 1-2-3a-6a-7a-7d-9 and Appendix D - 6 pages.pdf PDF
Attachment C.2 Specifications Volume 2 - 14 pages.pdf PDF
Attachment D.3 Drawings 3 of 7 - 24 pages.pdf PDF
Attachment H Past Performance Questionnaire - 3 Pages.docx DOCX document
Attachment D.2 Drawings 2 of 7 - 8 pages.pdf PDF
Attachment D.5 Drawings 5 of 7 - 23 pages.pdf PDF
Attachment E Brand Name Justification and Approvals _Redacted - 27 pages.pdf PDF
Attachment C.1 Specifications Volume 1 - 930 pages.pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL ABBREVIATIONS

J J

J

M

V

SP

R

GB

VFD

LCP

LRP

AFB

FBX

ET

M

M

C

DTDT

A-1

PH

D

P

K a

L

OS

R

B

CB

MD

MD

SP

VP

TV

XX

DC

C

DM

R/D

DGP

RX

ELM

DO

CR

K

AC

E

K

ATS

TBB

T

TMH

EMH

EHH

X

PSD

EMU

FB

UG

GB

G

PB

6-30R

UPS

CT

DOOR CONTACT SWITCH

ACCESS FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)

FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)

CONTACTOR

VARIABLE FREQUENCY DRIVE/VARIABLE FREQUENCY MOTOR CONTROLLER

MANUAL MOTOR STARTER WITH PILOT LIGHT AS INDICATED.

PUSHBUTTON STATION

CCTV SURVEILLANCE CAMERA OUTLET - WALL MTD, UON

DOOR MONITOR SWITCH

RECEIVER/DRIVER UNIT

GLASS BREAK DETECTOR

LIGHTING FIXTURE TYPE DESIGNATION - "XX" INDICATES SPECIFIC TYPE

EXIT LIGHT - WALL/CEILING MOUNTED - DIRECTIONAL ARROWS

AS INDICATED SHADING INDICATES ILLUMINATED FACE

LIGHTING TRACK - "X" DENOTES TYPE

UTILITY LIGHTING FIXTURE - TYPE AS INDICATED

WALL MOUNTED LIGHTING FIXTURE- TYPE AS INDICATED

SITE LIGHTING FIXTURE TYPE AS INDICATED

LIGHTING FIXTURE - TYPE AS INDICATED (SUBSCRIPT INDICATES SWITCH CONTROL)

JUNCTION BOX - CEILING OR WALL MOUNTED - INDICATED IN POWER, LIGHTING & FIRE

ALARM SYSTEMS PLANS.

DIRECT CONNECTION TO EQUIPMENT

SINGLE POLE SWITCH (SUBSCRIPT INDICATES FIXTURES CONTROLLED)

DIMMER SWITCH

SINGLE OR DOUBLE, REMOTE EMERGENCY LIGHTING FIXTURE

THREE-WAY SWITCH (S3P-THREE-WAY SWITCH WITH PILOT LIGHT)

KEY OPERATED SWITCH

SINGLE POLE SWITCH WITH PILOT LIGHT

FOUR - WAY SWITCH

FUSED SWITCH

DELTA CONNECTION

CPT

PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING)

ELECTRIC INTERLOCK SYSTEM

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

PHOTO CELL

KEY INTERLOCKING SYSTEM

WYE CONNECTION - SOLID GROUND

SWITCH - SINGLE THROW

TELECOMMUNICATIONS BACKBOARD

MOTOR CONTROL CENTER

TELEPHONE MANHOLE

ELECTRIC MANHOLE

FUSE

BUS DUCT PLUG-IN UNIT

GROUND

AUTOMATIC TRANSFER SWITCH

DRAWOUT TYPE, CIRCUIT BREAKER

STATIONARY CIRCUIT BREAKER

DISCONNECT SWITCH, FUSED.

PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY,

UON

GROUND ROD

DISCONNECT SWITCH, NON-FUSED

PROVIDE SWITCH AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, FLOOR MTD SERVICE FITTING,

SURFACE TYPE ("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, WALL MTD.

(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

TRANSFORMER - TYPE AND RATING AS INDICATED

COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH.

PROVIDE SWITCH AND FUSE AMACITY EQUAL TO OR GREATER THAN FEEDER

AMPACITY, UON

PANELBOARD - (FLUSH/SURFACE)

DISTRIBUTION PANELBOARD

ELECTRIC HANDHOLE

LIGHTING CONTROL PANEL, SURFACE MTD. UON.

LOW VOLTAGE LIGHTING RELAY PANEL, SURFACE MTD. UON

UNINTERRUPTIBLE POWER SUPPLY

SHADING INDICATES FIXTURE [CONNECTED TO CRITICAL BRANCH]

[CONNECTED TO GENERATOR CIRCUIT (SWITCHED)]

[W/FLUORESCENT BATTERY/INVERTER UNIT (SWITCHED)]

SHADING INDICATES FIXTURE [CONNECTED TO LIFE SAFETY BRANCH

(UNSWITCHED)] [W/FLUORESCENT BATTERY/INVERTER UNIT (UNSWITCHED)]

a

LOW VOLTAGE SWITCH

JUNCTION BOX - FLOOR MOUNTED

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, CEILING MTD SERVICE

FITTING,

SURFACE TYPE ("F" DENOTES FLUSH TYPE)

MOTOR AND CONNECTION

EMERGENCY POWER OFF

REQUEST-FOR-EXIT SENSOR

ELECTRIC LOCKING/LATCHING AND MONITORING HARDWARE

ACCESS CONTROL STATION - KEYPAD TYPE

ACCESS CONTROL STATION - CARD TYPE

DOOR OPERATING EQUIPMENT

DATA GATHERING PANEL

CODE BLUE WITH RED PHONE, WALL MTD, MOUNTED 48" AFF

CODE BLUE WITH BLUE LIGHT, WALL MTD, MOUNTED 48" AFF

MOTION DETECTOR - CEILING MTD

MOTION DETECTOR - WALL MTD

POWER SUPPLY FOR DOOR(S) WITH ELECTRICAL HARDWARE

CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SHADING INDICATES

EMERGENCY RECEPTACLE)

SPECIAL PURPOSE RECEPTACLE. TYPE AS INDICATED ON DRAWINGS.

COORDINATE RECEPTACLE TYPE WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION.

SWITCHED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.

FLOOR MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,

2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON

FACEPLATE.

FLOOR MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES

WITH A COMMON FACEPLATE. (SHADING INDICATES EMERGENCY RECEPTACLE)

FLOOR MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. PROVIDE CORE DRILL PACKAGE TO MAINTAIN FIRE RATING OF FLOOR. EXTEND CONDUIT AND WIRING IN CEILING SPACE OF FLOOR

BELOW TO ELECTRICAL CLOSET OR PANELBOARD. (SHADING INDICATES EMERGENCY

RECEPTACLE)

FLOOR MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,

2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.

FLOOR MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.

SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH

INDICATES MOUNTING ABOVE FINISH COUNTER)

QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V, 2P, 3W,

DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON

FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER;

SHADING INDICATES EMERGENCY RECEPTACLE)

SINGLE RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

RECEPTACLES MOUNTED ABOVE THE CEILING.

QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES WITH A

COMMON FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER;

SHADING INDICATES EMERGENCY RECEPTACLE)

CEILING MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES

WITH A COMMON FACEPLATE. (SHADING INDICATES EMERGENCY RECEPTACLE)

GFI, DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

ELECTRONIC METERING UNIT

GROUND BUS

GROUND CABLE, SIZE AS INDICATED

PLUG-IN BUSWAY

FEEDER BUSWAY

UNDERGROUND CONDUIT/DUCTBANK

CABLE TRAY

CONDUIT TURNED DOWN

CONDUIT TURNED UP

CONDUIT CAST IN CONCRETE OR BELOW SLAB

CONDUIT RUN CONCEALED IN FINISHED AREAS, EXPOSED IN UNFINISHED

AREAS OR BELOW ACCESS FLOORS

HOMERUN TO PANEL WITH CIRCUIT NUMBER(S) AS INDICATED

TELECOMMUNICATIONS DATA OUTLET ABOVE CEILING

COMBINATION TV OUTLET AND DUPLEX RECEPTACLE ON SINGLE

FACEPLATE

SPEAKER - WALL MTD

PA VOLUME CONTROL

MICROPHONE OUTLET - CEILING MTD

MICROPHONE OUTLET - WALL MTD

MICROPHONE OUTLET - FLOOR MTD

SPEAKER - CEILING MTD

RECORDING OUTLET

COMBINATION VIDEO PROJECTOR OUTLET AND DUPLEX RECEPTACLE

CLOCK OUTLET, W/RECPT AND HANGER

CLOCK OUTLET, MASTER CLOCK

CLOCK OUTLET, ELAPSED TIME

GENERATORG

SURFACE RACEWAY ("X" DENOTES TYPE AS SPECIFIED)

WALLWASH LIGHT FIXTURE,

DEMOLITION WORK

OCCUPANCY SENSOR WALL SWITCH

M

HC ADA PUSH BUTTON.

ELECTRICAL LIGHTING SYMBOLS ELECTRICAL POWER SYMBOLS GENERAL NOTES

A INTERCOMMUNICATION SYSTEM ( AI PHONE)

A B C A B C

P P

PD PD

D D

POWER SERVICE FITTING (FLOOR/WALL) MOUNTED FOR CONNECTION TO FURNITURE

SYSTEM AS SPECIFIED.

COMBINATION POWER AND TELECOMMUNICATIONS FLOOR OR WALL MOUNTED BOX FOR

POWER AND DATA CONNECTION - INDICATED IN POWER & SPECIAL SYSTEMS PLANS.

JUNCTION BOX FLOOR OR WALL MOUNTED FOR CONNECTION TO FURNITURE SYSTEM

MOUNTING HEIGHT NOTES:

1. ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.

2. REFER TO EQUIPMENT ELEVATION DRAWINGS FOR COORDINATION WITH

CASEWORK.

3. MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.

4. REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL ELECTRICAL DEVICE

MOUNTING HEIGHTS AND DEVICE ALIGNMENT RULES.

WALL SWITCHES

RECEPTACLES

TELECOMMUNICATIONS OUTLETS

TELECOMMUNICATIONS OUTLETS - WALL PHONE

CLOCK OUTLETS

TV OUTLETS

PUSHBUTTONS

VOLUME CONTROLS

NURSE CALL STATIONS

NURSE CALL DOME LIGHTS

DIMMERS

ACCESS CONTROL DEVICES

VANITY LIGHT IN TOILET

INTERCOM

FIREMAN'S PHONE

FIRE ALARM - PULL STATIONS

FIRE ALARM DEVICES HORN/SPEAKERS/STROBES

(MOUNTING HEIGHT AT THE TOP OF THE FIRE ALARM DEVICE OR

6" BELOW CEILING WHICH IS LOWER)

4'-0" AFF

1'-6" AFF

1'-6" AFF

4'-0" AFF

7'-0" AFF

1'-6" AFF

4'-0" AFF

4'-0" AFF

4'-0" AFF

7'-6" AFF

4'-0" AFF

4'-0" AFF

6" ABOVE THE MIRROR, UON

4'-0" AFF

4'-0" AFF

4'-0" AFF

7'-2" AFF TO TOP

PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF

THREE CIRCUITS PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.

COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL

DRAWINGS PRIOR TO ROUGH-IN.

PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR

SLABS, WALLS AND CEILINGS TO MAINTAIN FIRE RATING.

INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL

CODE AND LOCAL BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE

MANNER.

LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE

DERATING FACTOR FOR ROOF-MOUNTED CONDUITS.

REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING

MOUNTED DEVICES AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL

PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS

AND A COMMON FACEPLATE.

WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING

HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS

FOUR INCHES BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

WHERE UPDATE TO TECHNOLOGY (LOW VOLTAGE/SIGNAL) ARE LOCATED IN THE

SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.

WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE

EXIT SIGN BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP

OF DOOR FRAME AND CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM

OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED

EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT. COORDINATE WITH

ARCHITECTURAL DETAILS.

EXIT SIGNS ARE TO BE TYPE "X1", UON.

PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR

GREATER THAN THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL

LOCATION OF ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND

FINAL FURNITURE PLANS PRIOR TO INSTALLATION.

MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE

DRAWINGS AND IN MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC.

PROVIDE ALL COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL

SYSTEMS.

WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY

CONNECT RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

A.

B.

C.

D.

E.

F.

G.

H.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

ELTD EMERGENCY LIGHTING TRANSFER DEVICE

SECURITY SYSTEM SYMBOLS

TELECOMMUNICATION SYMBOLS

NURSE CALL SYSTEM SYMBOLS

MOUNTING HEIGHTS

ELECTRICAL EQUIPMENT SYMBOLS

ELECTRICAL WIRING SYMBOLS

DISTRIBUTION AND DIAGRAM SYMBOLS

REFERENCE SYMBOLS

SECTION NUMBER

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING NUMBER WHERE DRAWN

E1-1.0

KEY NOTE

1 DEMO KEY NOTE

SPECIAL SYSTEM OUTLET SYMBOLS

CB

E1-1.0

DISCONNECT SWITCHES

MOTOR STARTERS

PANELBOARDS & CABINETS

INDIVIDUAL CIRCUIT BREAKERS

5'-6" AFF

5'-6" AFF

6'-0" AFF TO TOP

5'-6" AFF

x

WAP WIRELESS ACCESS POINT, CEILING MOUNTED

NOTE: NOT ALL ABBREVIATIONS AND

SYMBOLS APPLY TO THIS PROJECT.

SPST

SWBD

SYM

STD

SW

SPEC(S)

SPDT

SPKR

SF

SEC

SINGLE POLE SINGLE THROW

SINGLE POLE DOUBLE THROW

SYMMETRICAL

SWITCHBOARD

STANDARD

SWITCH

SECONDARY

SQUARE FOOT

SPECIFICATION(S)

SPEAKER

PRI

RCLP

RM

SCH, SCHED

RP

REF

RCPT

RSC

RLA

RF

R, RE

QTY

PWR

PT

PVC

PA

PH, ∅

PF

PNL

PE

PB

P

OPP

OHE/T

OH

OFOI

OFCI

NO., NUM, #

OC

NTS

AMERICAN WIRE GAUGE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTOMATIC TRANSFER SWITCH

AMPERE INTERRUPTING CAPACITY

ALTERNATING CURRENT

ABOVE FINISHED COUNTER

AWG

BLDG

BRKR, BKR

BUILDING

BREAKER

AUTO

AUX

ARCH

AT

ATS

ALT

AFG

AIC

AFC

AFF

AC

AF

AUXILIARY

ALTERNATE

ARCHITECT

AUTOMATIC

AMPERES TRIP

AMPERE FRAME (BREAKER RATING)

MTG

NC

NEMA

NO

NIC

NEC

N

MV

MH

MOCP

MTD

MLO

MIN

MISC

MECH

MCC

MFR

MCA

MCB

RIGID STEEL CONDUIT

RATED (RUNNING) LOAD AMPS

RECEPTACLE PANELBOARD

ROOM

SCHEDULE

RADIO FREQUENCY

RECEPTACLE

REFRIGERATOR

RELOCATE AS SHOWN

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

REMOTE CONTROL LIGHTING PANEL

QUANTITY

POWER

PUBLIC ADDRESS

PANEL

PRIMARY

PULL BOX

POWER FACTOR

PHOTO ELECTRIC

PHASE

POLE

OPPOSITE

OWNER FURNISHED, CONTRACTOR INSTALLED

OWNER FURNISHED, OWNER INSTALLED

OVERHEAD ELECTRIC/TELEPHONE

OVERHEAD

ON CENTER

NOT TO SCALE

NUMBER

MOUNTING

NATIONAL ELECTRICAL CODE

MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)

NORMALLY CLOSED

NORMALLY OPEN

NOT IN CONTRACT

NEUTRAL

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAXIMUM OVERCURRENT PROTECTION

MOUNTED

MISCELLANEOUS

MAIN LUGS ONLY

MINIMUM

MANHOLE

MANUFACTURER

MECHANICAL

SWGR SWITCHGEAR

AIR HANDLING UNITAHU

MTS MANUAL TRANSFER SWITCH

PDP POWER DISTRIBUTION PANEL

AMPERESAMP

OCPD OVERCURRENT PROTECTION DEVICE

A M

B N

O

P

Q

R

S

T

SPD SURGE PROTECTIVE DEVICE

OD OUTLET DESIGNATOR

LOW VOLTAGE (BELOW 50 VOLTS)

L-L

L-N

LTG

LV

LIGHTING

LINE TO LINE

LINE TO NEUTRAL

1000 CIRCULAR mils

KILOVOLTS (THOUSAND VOLTS)

KILOWATTS (THOUSAND WATTS)

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)

ISOLATED GROUND

KWH

LAN

LA

KW

KVA

Kcmil

KV

KILOWATT-HOURS

INCAND

KEY INTERLOCK

JUNCTION BOX

INCH/INCHES (")

INCANDESCENT

GROUND FAULT INTERRUPTER

HAND-OFF-AUTOMATIC

HIGH PRESSURE SODIUM

HEATING VENTILATION AND AIR CONDITIONING

HERTZ

HVAC

HZ

HTR

HR

HT

HPS

HOA

HP

HEATER

HEIGHT

HORSEPOWER

HOUR

GFI

G, GND, GRD

GEN

FLUOR

FL, FLR

GROUND

GENERATOR

FOOT/FEET (')

FLUORESCENT

FLOOR

CATV

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FIRE ALARM ANNUNCIATOR PANEL

ELECTRIC, ELECTRICAL

ELECTRIC METALLIC CONDUIT

EQUIPMENT GROUND

EWC

FAAP

FLA

FDR

EWH

FA

FULL LOAD AMPS

FEEDER

FIRE ALARM

FUSE

ELEC

EQ, EQUIP

EM, EMERG

EMT

ELEV

ENCL

EG

EQUIPMENT

ELEVATOR

EMERGENCY

ENCLOSURE

DISTRIBUTION PANEL

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

DPDT

DWG

DPST

DIST

DISC

DC

DP

DN

DRAWING

DISTRIBUTION

DIRECT CURRENT

DISCONNECT

DOWN

CPT

CU

CT

COM, COMM

CKT

CLG

COPPER

COMMUNICATIONS

CIRCUIT

CEILING

CABLE TELEVISION

CB CIRCUIT BREAKER

CONDUIT

FIRE ALARM CONTROL PANELFACP

FIRE ALARM EXTENDER PANELFAEP

CCTV CLOSED CIRCUIT TELEVISION

CP CONTROL PANEL

FLEX FLEXIBLE

HAND HOLEHH

LIGHTING CONTROL PANELLC, LCP

LIGHTING PANEL

L-G LINE TO GROUND

C

F

EXISTINGE, EX, EXIST

FT

IN

IG

JB, JBOX

K

LP

FOOT CANDLEFC

DIV DIVISION

C

D

E

F

G

H

I

J

K

L

HORIZONTAL MOUNTINGH

COR CONTRACTING OFFICER'S REPRESENTATIVE

X

XFMR

WP

WHM

W/

W/O

W

VFD

VA

V

UPS

UL

UON

UG

UGS

UGT

UGP

TYP

TV

TP

TEL,TELE

TELECOM

TC

TRANSFORMER

REMOVE DEVICE

WATT HOUR METER

WEATHERPROOF

VOLTS

VARIABLE FREQUENCY DRIVE/

VARIABLE FREQUENCY MOTOR

CONTROLLER

WITHOUT

WITH

WIRE

VOLT-AMPERES

UNDERGROUND PRIMARY

UNDERGROUND SECONDARY

UNDERGROUND TELEPHONE

UNDERWRITER'S LABORATORY

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

UNDERGROUND

TELECOMMUNICATIONS

TYPICAL

TELEVISION

TAMPERPROOF

TIME CLOCK

TELEPHONE

TB TERMINAL BLOCK

TBB TELEPHONE BACKBOARD

U

V

W

X

Z

TPST TRIPLE POLE SINGLE THROW

FDS FORWARD DEPLOYED SERVICES

JOINT SECURITY ARCHITECTUREJSA

PIV PERSONAL IDENTITY VERIFICATION

(WALL MOUNTED DEVICES MOUNTED 60" AFF TO TOP, UON.)

PATIENT BED STATION, SINGLE BED

PATIENT BED STATION, DOUBLE BED

PATIENT BED RECEPTACLE, 20" AFF

EMERGENCY CALL:

TOILETS: W/PULL CORD.

36" AFF AT TOILETS.

EMERGENCY CALL:

SHOWERS: W/PULL CORD.

84" AFF IN SHOWERS.

CODE BLUE

DUTY STATION

PATIENT BED STATION, SINGLE BED, PILLOW SPEAKER

CABLE TV INTERFACE

DOME LIGHT, CEILING OR WALL +80" AFF FLOOR OR 6" BELOW CEILING.

ZONE LIGHT, CEILING OR WALL +80" AFF FLOOR OR 6" BELOW CEILING.

NURSE CALL MASTER

NURSE CALL ANNUNCIATOR

NURSE CALL TERMINAL CABINET

HEAD-END EQUIPMENT

LOW-VOLTAGE LIGHT CONTROLLERS

SINGLE ENHANCED PATIENT STATION

BED CONTROL MODULE

N

N

N

N

N

N

N

N

N

NCM

ANN

NCT

B

T

S

C

D

P

TV

N

Z

PENDANT LIGHTING FIXTURE- TYPE AS INDICATED

NIGHTLIGHT FIXTURE- TYPE AS INDICATED

ES DOOR ELECTRIC STRIKE

HEC

LITE

EPS

N

M on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

A/E:

TRIPLE C - The A/E Group

(520) 481-8548

Mat Perkins

1 : 1

B

IM

/6

-2

-1

R e n o va te

D B e d W in g -B

-M

P L S

V A

M C

/6 -2

-7

.M

P L S

.3 D

.B e d .W in g .M

E P

.G e n e ra l.

S h e e ts

.r v t

/1

/2

:0 :3

P

M

09/12/2022 K. Luke N. Wicklund

618-22-102

1391 - E-001

ELECTRICAL ABBREVIATIONS AND SYMBOLS

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATION OF BUILDING 70 3D

BED WING100% CONSTRUCTION

DOCUMENTS12/17/2021

AREA NOT IN PROJECT SCOPE.

LIGHTING IS EXISTING TO REMAIN.

/F6 EDL103 /F6 EDL103

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

EXAM

3D-119B

EXAM

3D-119C

EXAM

3D-120

EXAM

3D-121

CORRIDOR

C3-17

BREAK

3D-123A

BREAK ROOM

3D-123

CORRIDOR

C3-18

PATIENT

3D-124

TLT

3D-124A

PATIENT

3D-126

TLT

3D-126A

PATIENT

3D-128C

ANTE

3D-128

PATIENT

3D-128B

TLT

3D-128A

PATIENT

3D-129

STORAGE

3D-134B

WORK ROOM

3D-134A

CHECK-IN

3D-134

EXAM

3D-135

EXAM

3D-136

TLT

3D-135A

CORRIDOR

C3-24

CORRIDOR

C3-22

CORRIDOR

C3-23

TLT

3D-101A

EXAM

3D-101

ANTE ROOM

3D-102A

PATIENT

3D-102

TLT

3D-102B

TLT

3D-103B

PATIENT

3D-103

ANTE

3D-103A

ANTE

3D-104A

PATIENT

3D-104

TLT

3D-104B

PATIENT

3D-107

TLT

3D-107B

ANTE

3D-107A

PATIENT

3D-108

TLT

3D-108A

TLT

3D-114A

PATIENT

3D-114B

ANTE

3D-114

PATIENT

3D-114C

PATIENT

3D-116B

TLT

3D-116A

ANTE

3D-116

PATIENT

3D-116C

TREATMENT

3D-119

EXAM

3D-119A

EXAM

3D-118

OFFICE

3D-125

EXAM

3D-127

STOR

3D-127A

EXAM

3D-117

EXAM

3D-112WORK ROOM

3D-115

OFFICE

3D-109

HAC

3D-110 TLT

3D-111

STORAGE

3D-130

NURSING RM

3D-109A

CORRIDOR

C3-19

CORRIDOR

C3-19

OFFICE

3D-131 3D-105

3D-105

OFFICE

3D-106

CORRIDOR

C3-12

TOILET

TOILET

3C-105

CORRIDOR

C3-27

CORRIDOR

C3-28

CORRIDOR

C3-26

STAIR

CORRIDOR

C3-25

CORRIDOR

C3-20

OFFICE

3C-103

AREA NOT IN PROJECT SCOPE.

LIGHTING IS EXISTING TO REMAIN.

/F3 EDL103 /F3 EDL103

on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

(612) 355-1251

Mat Perkins

A

B D

EF

G

H

J

K

L

M

C

GENERAL NOTES

KEYNOTES

1/8" = 1'-0"

B

IM

/6

-2

-1

R e n o v a te

D

B e d W in g -B

-M

P L S

V A

M C

/6 -2

-7

.M

P L S

.3 D

.B e d .W in g .M

E P

.B .L

.r v t

/1

/2

:3

:5

A

M

09/12/2022 K. Luke N. Wicklund

618-22-102

1391 -

EDL103

ELECTRICAL LIGHTING CEILING PLANS -

THIRD LEVEL 3D - DEMO

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATION OF BUILDING 70 3D

BED WING

100% CONSTRUCTION

DOCUMENTS

1. REMOVE ALL EXISTING LIGHT FIXTURES AND CONTROLS .

2. REMOVE ALL EXISTING ELECTRICAL OUTLETS AND FEEDERS BACK TO THE

SOURCE PANEL. PROVIDE NEW ELECTRICAL DEVICES FOR THE RENOVATION.

3. PROVIDE NEW LIGHT FIXTURE, SEE LUMINARE SCHEDULE ON SHEET E-701 FOR

ADDITIONAL INFORMATION.

4. PROVIDE NEW LIGHT SWITCH, SEE E-900 SERIES FOR ADDITIONAL

INFORMATION.

5. PROVIDE NEW ELECTRICAL OUTLETS.

6. SEE SHEET E-601 FOR ADDITIONAL ONE-LINE INFORMATION.

7. REMOVE FEEDERS SERVING MECHANICAL EQUIPMENT TO BE REPLACED WITH

THIS PROJECT. PROVIDE NEW FEEDERS. AIR HANDLING UNIT, EXHAUST AND

RETURN FANS SHALL BE SERVED FROM AN EMERGENCY POWER SOURCE.

8. PROVIDE A CODE SIZED RECESSED JBOX WITH A 1-1/4" CONDUIT STUBBED

ABOVE CEILING FOR NURSE CALL DEVICE.

9. PROVIDE 120V CIRCUIT TO SERVE ROLLER BLINDS, SEE ARCH PLANS FOR

DETAILS.

10. PROVIDE 120V CIRCUIT TO SERVE NEW PLUMBING FIXTURES. SEE 22 40 00 FOR

DETAILS.

11. DEMOLISH EXISTING PANELBOARD, REPLACE WITH NEW PANELBOARD, SIZE AS

INDICATED ON ELECTRICAL PANEL SCHEDULES AND ELECTRICAL ONE-LINES.

REPLACE CIRCUIT BREAKER, SOURCE FEEDER AND REPLACE ALL EXISTING

CIRCUITS TO NEW PANELBOARD AS INDICATED. SEE E-600 AND E-700 SERIES

SHEETS FOR ADDITIONAL INFORMATION.

12. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICE/CIRCUITS NOT ASSOICATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE PER CONDITONS

PRIOR TO DEMOLTION. ALL DEMOLITION / PHASING SHALL BE COORDINATED

WITH THE VA COR.

13. EXISTING LIGHTING/RECEPTACLES TO REMAIN, PROTECT IN PLACE

14. PROVIDE 120V CIRCUIT TO SERVE NEW ACCESS CONTROLS. SEE

ARCHITECUTRAL DOOR SCHEDULE FOR ADDITIONAL INFORMATION.

15. PROVIDE 120V CONNECTION TO 24V TRANSFORMER FURNISHED WITH

RESPECTIVE MONITORS AND PRESSURE SENSORS. COORDINATE EXACT

LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.

16. EXISTING ELECTRICAL PANEL TO REMAIN, PROTECT IN PLACE.

17. NEW PANELBOARD, SIZE AS INDICATED ON ELECTRICAL PANEL SCHEUDLES AND

ELECTRICAL ONE-LINES. SEE E-600 AND E-700 SERIES FOR ADDITIONAL

INFORMATION.

18. EXISTING ELECTRICAL EQUIPMENT TO REMAIN, PROTECT IN PLACE.

19. PROVIDE NEW 30kW TRANSFORMER IN LOCATION INDICATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS. SEE E-600 AND E-700

SERIES FOR ADDITIONAL INFORMATION.

20. DEMOLISH EXISTING TRANSFORMER, REPLACE WITH NEW TRANSFORMER, SIZE

AS INDICATED ON ELECTRICAL PANEL SCHEDULES AND ELECTRICAL ONE-LINES.

SEE E-600 AND E-700 SERIES SHEETS FOR ADDITIONAL INFORMATION.

21. DEMOLISH EXISTING DISCONNECT FOR PANELS BEING REPLACED, REPLACE

WITH NEW DISCONNECT, SIZE AS INDICATED ON ELECTRICAL PANEL

SCHEDULES AND ELECTRICAL ONE-LINES. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

22. PROVIDE NEW ELECTRICAL DISCONNECT FOR PANELBOARD, SIZE AS

INDICATED.

23. PROVIDE NEW CEILING MOUNTED PHOTOCELL, SEE E-900 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

24. PROVIDE 120V CONNECTION TO SERVE PLUMBING FIXTURE POWER SUPPLY.

25. COORDINATE RECEPTACLE WITH FOOTWALL FOR TV.

26. (NOT USED)

27. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACUTURERS

RECOMMENDATIONS.

28. PROVIDE EMERGENCY POWER FOR PATIENT MONITORING STATION ABOVE

COUNTER.

29. PROVIDE EMERGENCY POWER AT 72" AFF FOR BMS DSIPLAY

30. PROVIDE J-BOX, CONDUIT, AND FEEDERS FOR PNEUMATIC TUBE SYSTEM

POWER.

31. PROVIDE J-BOX, CONDUIT, AND FEEDERS FOR MED GAS PANEL ALARM.

32. PROVIDE PRE-WIRED WITH DUPLEX RECEPTACLES SPACED 1' - 6" ON CENTER.

CABLE ENTRY (POWER) SHALL BE HIDDEN, INSTALLED FROM BACK OF

WIREWAY. WIREMOLD #ALDS4000 SERIES OR APPROVED EQUAL. PROVIDE WIRE

MOLD AND J-BOX AT EACH LEVEL (4) EACH SHELF. COORDINATE SPACING AND

HEIGHTS WITH FURNISHING VENDOR.

33. PROVIDE TWO DUPLEX RECEPTACLES INSIDE CABINET. ONE AT A HEIGHT OF

+36" AFF AND THE OTHER AT A HEIGHT OF +18" AFF.

34. PROVIDE 120V SERVICE TO NEW HVAC CONTROLS ENCLOSURES. COORDINATE

WITH HVAC CONTROLS CONTRACTOR

35. PROVIDE NEW VFD TO SF-27 (SUPPLY FAN).

36. PROVIDE NEW VFD TO EF-34 (EXHAUST FAN).

37. PROVIDE NEW VFD TO RF-18 (RETURN FAN).

38. NEW DOMESTIC WATER MONITORING SYSTEM CONTROL PANEL. REFER TO

DIAGRAM ON SHEET P-501.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1/8" = 1'-0"

F3

ELECTRICAL LIGHTING CEILING

PLANS - THIRD LEVEL 3D - DEMO

SCALE: 1/8" = 1'-0"

F6

ELECTRICAL LIGHTING CEILING

PLANS - THIRD LEVEL 3D - DEMO

12/17/2021

J

CR

CR

CL3A1-2

CL3A1-1

NH3A1-1

NL3A1-1B

NL3A1-1A

NT3A1-1

(E) CL3A2-2

(E) CL3A2-1

(E) PP3A2-1

(E) EH3A2-1

(E) NL3A2-2

(E) NL3A2-1B

(E) NL3A2-1A

NT3A2-1

(E) NH3A2-1

ELECTRICAL ROOM

3U-137

ELECTRICAL ROOM

3D-122A

CORRIDOR

C3-12

AREA NOT IN PROJECT SCOPE

ELECTRICAL ITEMS ARE EXISTING TO REMAIN

EP400

F4

/F6 EDP103 /F6 EDP103

(E) NL3A2-2

(E) NL3A2-1B

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

CORRIDOR

C3-26

TOILET

3C-104

TOILET

3C-105

CORRIDOR

C3-27 CORRIDOR

C3-28

ROOM

3C-106

STAIR

CORRIDOR

C3-12

AREA NOT IN PROJECT SCOPE.

ELECTRICAL ITEMS ARE EXISTING TO REMAIN.

TYP.

TYP.

/F3 EDP103 /F3 EDP103

EXAM

3D-119B

EXAM

3D-119C

EXAM

3D-120

EXAM

3D-121

EXAM

3D-119A

TREATMENT

3D-119

PATIENT

3D-116C

ANTE

3D-116

PATIENT

3D-116B

TLT

3D-116A

PATIENT

3D-114C

ANTE

3D-114

PATIENT

3D-114B

TLT

3D-114A

TLT

3D-108APATIENT

3D-108

PATIENT

3D-107

ANTE

3D-107A

TLT

3D-107B

TLT

3D-104B

ANTE

3D-104A

PATIENT

3D-104

PATIENT

3D-103

TLT

3D-103B

ANTE

3D-103A

TLT

3D-102BPATIENT

3D-102

ANTE ROOM

3D-102A

EXAM

3D-101

TLT

3D-101A

CORRIDOR

C3-22

CORRIDOR

C3-24

CORRIDOR

C3-23

CORRIDOR

C3-19

EXAM

3D-135

EXAM

3D-136

TLT

3D-135A

CHECK-IN

3D-134

WORK ROOM

3D-134A

STORAGE

3D-134B

PATIENT

3D-129

HAC

3D-110

TLT

3D-111

OFFICE

3D-109

NURSING RM

3D-109A

OFFICE

3D-106

STORAGE

3D-130

OFFICE

3D-131

3D-105

3D-105

PATIENT

3D-128B

TLT

3D-128A

ANTE

3D-128

PATIENT

3D-128C

EXAM

3D-112

WORK ROOM

3D-115

EXAM

3D-127

STOR

3D-127A

EXAM

3D-117

EXAM

3D-118

OFFICE

3D-125

CORRIDOR

C3-18

CORRIDOR

C3-19

TLT

3D-126A

PATIENT

3D-126

TLT

3D-124A

PATIENT

3D-124

BREAK ROOM

3D-123

BREAK

3D-123A

CORRIDOR

C3-17

CORRIDOR

C3-18

OFFICE

3C-103

LINEN CHUTE

3D-112A on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

(612) 355-1251

Mat Perkins

A

B D

EF

G

H

J

K

L

M

C

GENERAL NOTES

KEYNOTES

1/8" = 1'-0"

B

IM

/6

-2

-1

R e n o v a te

D

B e d W in g -B

-M

P L S

V A

M C

/6 -2

-7

.M

P L S

.3 D

.B e d .W in g .M

E P

.B .L

.r v t

/1

/2

:3

:0

A

M

09/12/2022 K. Luke N. Wicklund

618-22-102

1391 -

EDP103

ELECTRICAL POWER PLANS - THIRD LEVEL

3D - DEMO

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATION OF BUILDING 70 3D

BED WING

100% CONSTRUCTION

DOCUMENTS

1. REMOVE ALL EXISTING LIGHT FIXTURES AND CONTROLS .

2. REMOVE ALL EXISTING ELECTRICAL OUTLETS AND FEEDERS BACK TO THE

SOURCE PANEL. PROVIDE NEW ELECTRICAL DEVICES FOR THE RENOVATION.

3. PROVIDE NEW LIGHT FIXTURE, SEE LUMINARE SCHEDULE ON SHEET E-701 FOR

ADDITIONAL INFORMATION.

4. PROVIDE NEW LIGHT SWITCH, SEE E-900 SERIES FOR ADDITIONAL

INFORMATION.

5. PROVIDE NEW ELECTRICAL OUTLETS.

6. SEE SHEET E-601 FOR ADDITIONAL ONE-LINE INFORMATION.

7. REMOVE FEEDERS SERVING MECHANICAL EQUIPMENT TO BE REPLACED WITH

THIS PROJECT. PROVIDE NEW FEEDERS. AIR HANDLING UNIT, EXHAUST AND

RETURN FANS SHALL BE SERVED FROM AN EMERGENCY POWER SOURCE.

8. PROVIDE A CODE SIZED RECESSED JBOX WITH A 1-1/4" CONDUIT STUBBED

ABOVE CEILING FOR NURSE CALL DEVICE.

9. PROVIDE 120V CIRCUIT TO SERVE ROLLER BLINDS, SEE ARCH PLANS FOR

DETAILS.

10. PROVIDE 120V CIRCUIT TO SERVE NEW PLUMBING FIXTURES. SEE 22 40 00 FOR

DETAILS.

11. DEMOLISH EXISTING PANELBOARD, REPLACE WITH NEW PANELBOARD, SIZE AS

INDICATED ON ELECTRICAL PANEL SCHEDULES AND ELECTRICAL ONE-LINES.

REPLACE CIRCUIT BREAKER, SOURCE FEEDER AND REPLACE ALL EXISTING

CIRCUITS TO NEW PANELBOARD AS INDICATED. SEE E-600 AND E-700 SERIES

SHEETS FOR ADDITIONAL INFORMATION.

12. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICE/CIRCUITS NOT ASSOICATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE PER CONDITONS

PRIOR TO DEMOLTION. ALL DEMOLITION / PHASING SHALL BE COORDINATED

WITH THE VA COR.

13. EXISTING LIGHTING/RECEPTACLES TO REMAIN, PROTECT IN PLACE

14. PROVIDE 120V CIRCUIT TO SERVE NEW ACCESS CONTROLS. SEE

ARCHITECUTRAL DOOR SCHEDULE FOR ADDITIONAL INFORMATION.

15. PROVIDE 120V CONNECTION TO 24V TRANSFORMER FURNISHED WITH

RESPECTIVE MONITORS AND PRESSURE SENSORS. COORDINATE EXACT

LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.

16. EXISTING ELECTRICAL PANEL TO REMAIN, PROTECT IN PLACE.

17. NEW PANELBOARD, SIZE AS INDICATED ON ELECTRICAL PANEL SCHEUDLES AND

ELECTRICAL ONE-LINES. SEE E-600 AND E-700 SERIES FOR ADDITIONAL

INFORMATION.

18. EXISTING ELECTRICAL EQUIPMENT TO REMAIN, PROTECT IN PLACE.

19. PROVIDE NEW 30kW TRANSFORMER IN LOCATION INDICATED ON PLAN, COORDINATE WITH NEW AND EXISTING CONDITIONS. SEE E-600 AND E-700

SERIES FOR ADDITIONAL INFORMATION.

20. DEMOLISH EXISTING TRANSFORMER, REPLACE WITH NEW TRANSFORMER, SIZE

AS INDICATED ON ELECTRICAL PANEL SCHEDULES AND ELECTRICAL ONE-LINES.

SEE E-600 AND E-700 SERIES SHEETS FOR ADDITIONAL INFORMATION.

21. DEMOLISH EXISTING DISCONNECT FOR PANELS BEING REPLACED, REPLACE

WITH NEW DISCONNECT, SIZE AS INDICATED ON ELECTRICAL PANEL

SCHEDULES AND ELECTRICAL ONE-LINES. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

22. PROVIDE NEW ELECTRICAL DISCONNECT FOR PANELBOARD, SIZE AS

INDICATED.

23. PROVIDE NEW CEILING MOUNTED PHOTOCELL, SEE E-900 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

24. PROVIDE 120V CONNECTION TO SERVE PLUMBING FIXTURE POWER SUPPLY.

25. COORDINATE RECEPTACLE WITH FOOTWALL FOR TV.

26. (NOT USED)

27. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACUTURERS

RECOMMENDATIONS.

28. PROVIDE EMERGENCY POWER FOR PATIENT MONITORING STATION ABOVE

COUNTER.

29. PROVIDE EMERGENCY POWER AT 72" AFF FOR BMS DSIPLAY

30. PROVIDE J-BOX, CONDUIT, AND FEEDERS FOR PNEUMATIC TUBE SYSTEM

POWER.

31. PROVIDE J-BOX, CONDUIT, AND FEEDERS FOR MED GAS PANEL ALARM.

32. PROVIDE PRE-WIRED WITH DUPLEX RECEPTACLES SPACED 1' - 6" ON CENTER.

CABLE ENTRY (POWER) SHALL BE HIDDEN, INSTALLED FROM BACK OF

WIREWAY. WIREMOLD #ALDS4000 SERIES OR APPROVED EQUAL. PROVIDE WIRE

MOLD AND J-BOX AT EACH LEVEL (4) EACH SHELF. COORDINATE SPACING AND

HEIGHTS WITH FURNISHING VENDOR.

33. PROVIDE TWO DUPLEX RECEPTACLES INSIDE CABINET. ONE AT A HEIGHT OF

+36" AFF AND THE OTHER AT A HEIGHT OF +18" AFF.

34. PROVIDE 120V SERVICE TO NEW HVAC CONTROLS ENCLOSURES. COORDINATE

WITH HVAC CONTROLS CONTRACTOR

35. PROVIDE NEW VFD TO SF-27 (SUPPLY FAN).

36. PROVIDE NEW VFD TO EF-34 (EXHAUST FAN).

37. PROVIDE NEW VFD TO RF-18 (RETURN FAN).

38. NEW DOMESTIC WATER MONITORING SYSTEM CONTROL PANEL. REFER TO

DIAGRAM ON SHEET P-501.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1/8" = 1'-0"

F3

ELECTRICAL POWER PLANS - THIRD

LEVEL 3D - DEMO

SCALE: 1/8" = 1'-0"

F6

ELECTRICAL POWER PLANS - THIRD

LEVEL 3D - DEMO

TYP.

TYP.

TYP.

AREA NOT IN PROJECT SCOPE.

EXISTING TO REMAIN.

POE

ACC

/F2 EDP103i /F2 EDP103i

TYP.

TYP.

AREA NOT IN PROJECT SCOPE.

EXISTING TO REMAIN.

/F6 EDP103i /F6 EDP103i on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

(612) 355-1251

Mat Perkins

A

B D

EF

G

H

J

K

L

M

C

GENERAL NOTES

KEYNOTES

1/8" = 1'-0"

B

IM

/6

-2

-1

R e n o v a te

D

B e d W in g -B

-M

P L S

V A

M C

/6 -2

-7

.M

P L S

.3 D

.B e d .W in g .M

E P

.B .L

.r v t

/1

/2

:3

:0

A

M

09/12/2022 K. Luke K.Hutchinson

618-22-102

1391 - EDP103i

ELECTRICAL POWER PLAN - THIRD LEVEL

INTERSTITIAL

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATION OF BUILDING 70 3D

BED WING

100% CONSTRUCTION

DOCUMENTS

NTS

F6

ELECTRICAL INTERSTITIAL SOUTH - DEMO

NTS

F2

ELECTRICAL INTERSTITIAL NORTH - DEMO

1. EXISTING DUCTBANK ELECTRICAL RACEWAY, SEE E-603 FOR ADDITIONAL

INFORMATION.

2. DUCTBANK ELECTRICAL RACEWAY DROP TO ELECTRICAL ROOM, SEE E-603 FOR

ADDITIONAL INFORMATION.

3. WALLS SHOWN ON PLAN ARE FROM THIRD LEVEL BELOW FOR REFERENCE

ONLY. SEE A-103 FOR ADDITIONAL INFORMATION.

4. ELECTRICAL JUNCTION BOX TO BE DEMOLISHED. INFILL OR CLOSE

PENETRATION WITH MATERIALS THAT MEET REQUIRED FIRE RATING OF

EXISTING CONCRETE SLAB.

5. WIRE NEW SECURITY DEVICES TO HEAD-END EQUIPMENT.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-701.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.87 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

PH

D D

PH

D

DD

D3 D3

D

D

D D3D3D3

D

PH

PH

PH

PH

D3

D D

PH

PH

PH

D3D3 D3D3D

DD

DD

D

D

D

D3D3

D

D

D

D3D3

D

D

D

D

D

D

DD

DD

D

D

DD

DD

D

D

D

DD

DD

D

DD

D

D

D

D D

D

D

D

D D

D

DD

D

DD

DD

D

D

PH

D3D3

D

D

D3D3

D

D

D3D3

D

D

PH

PH

PH

PH

PH

PH

PH

PH

PH

PH

D

D3D3 D

D3D3

D

D

D3 D3

D3 D3

D3 D3 D3 D3

D3 D3

D

D

D

D

D3 D3

D

D 3 D3 D3

D3D3

D

D

D3 D3

D

D

D

D

D3 D3

D3 D3

D

D

D D

D

D D

D

D D

DD

D D

D

D 3 D

D3

D

D

D

DD

D3

D3 D3

D3

D3DD3

D

D3

D

D

PATIENT 9

3D-109

RR 9

3D-109A

RR 10

3D-121A

CIRCULATION

C3-18

E

E

E

(E) LL3A2-1- 4

(E) LL3A2-1- 4 (E) LL3A2-1- 4

CORRIDOR

C3-12

NL3A2-1B- 5

NL3A2-1B- 5E

E

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

E E E

C

D E

B

CL3A2-1- 5

CL3A2-1- 5

CL3A2-1- 5CL3A2-1- 5

AA

C

D

AA

CL3A2-1- 5 CL3A2-1- 5

AA

Z (E) LL3A2-1- 4

Z

(E) LL3A2-1- 4

ELECTRICAL ROOM

3D-122A

IT CLOSET

3D-122B

EP400

F7

MECHANICAL ROOM

3D-122

TYP.

AREA NOT IN PROJECT SCOPE.

LIGHTING IS EXISTING TO REMAIN.

EP401

C2

EP401

C5

EP401

C7

D1

D2

D3

PATIENT 9

3D-109

PATIENT 8

3D-108

PATIENT 7

3D-107

PATIENT 6

3D-106

PATIENT 5

3D-105

PATIENT 4

3D-104

PATIENT 3

3D-103

PATIENT 2

3D-102

BARIATRIC 1

3D-101

RR 9

3D-109A

ANTE ROOM

3D-109B

RR 8

3D-108A

RR 7

3D-107A

RR 6

3D-106A

RR 5

3D-105A

RR 4

3D-104A

RR 3

3D-103A

RR 2

3D-102A

RR 1

3D-101A

ANTE ROOM

3D-101B

CIRCULATION

C3-24

CIRCULATION

C3-25

CIRCULATION

C3-20

CIRCULATION

C3-19

MSA'S

3D-100

ASST. NURSE MNGR

3D-110

STAFF WORK

3D-136

NURSE MNGR OFFICE

3D-111

NUTRITION

3D-135

MED ROOM

3D-112

SOILED UTILITY

3D-134

SPS STORAGE

3D-114

PHARM OFFICE

3D-120

EQUIPMENT ROOM

3D-115

STAFF BREAK ROOM

3D-116

HAC

3D-119

OXYGEN STOR.

3D-118

RR 10

3D-121A

ANTE ROOM

3D-121B

PATIENT 10

3D-121

PATIENT 11

3D-123

RR 11

3D-123A

RR 12

3D-125A

PATIENT 12

3D-125

PATIENT 13

3D-126

PATIENT 14

3D-128

RR 13

3D-126A

RR 14

3D-128A

PATIENT 15

3D-129

RR 15

3D-129A

RR 16

3D-131A

SAFER PATIENT 16

3D-131

SAFER PATIENT 17

3D-132

RR 17

3D-132A

PATIENT 18

3D-133

RR 18

3D-133A

ANTE ROOM

3D-133B

CLEAN LINENS

3D-138

EQUIP. ALCOVE

3D-140

EQUIP. ALCOVE

3D-127

SINK ALCOVE

3C-134B

EQUIP. ALCOVE

3D-139

EQUIP ALCOVE

3D-137

CHARTING

C3-19A

CHARTING

C3-19B

CHARTING

C3-19C

CHARTING

3D-142

CHARTING

3D-141

CHARTING

C3-25A

CIRCULATION

C3-18

CHUTE

3C-134A

CL3A2-1- 14

A A A

CL3A2-1- 14 CL3A2-1- 14

E

B

A A

A

D

CL3A2-1- 14

CL3A2-1- 14

CL3A2-1- 14

CL3A2-1- 14 CL3A2-1- 14

CL3A2-1- 14 CL3A2-1- 14

CL3A2-1- 14 CL3A2-1- 14

NL3A2-1B- 25

NL3A2-1B- 25

C

NL3A2-1B- 25

NL3A2-1B- 25

CL3A2-1- 10 CL3A2-1- 10

CL3A2-1- 10CL3A2-1- 10

CL3A2-1- 10CL3A2-1- 10

CL3A2-1- 10 CL3A2-1- 10

CL3A2-1- 10 CL3A2-1- 10

CL3A2-1- 10CL3A2-1- 10

CL3A2-1- 10

A A A

A AAA

A A A A

AA

AA

A A

A A

AA

AA

A A

CL3A2-1- 6 CL3A2-1- 6

CL3A2-1- 6

CL3A2-1- 6

CL3A2-1- 6 CL3A2-1- 6

CL3A2-1- 6 CL3A2-1- 6

CL3A2-1- 6 CL3A2-1- 6

CL3A2-1- 6 CL3A2-1- 6

AA

A A

AA

A A

A

AA

A

CL3A2-1- 8 CL3A2-1- 8

CL3A2-1- 8CL3A2-1- 8

CL3A2-1- 8 CL3A2-1- 8

CL3A2-1- 8

CL3A2-1- 8

CL3A2-1- 8CL3A2-1- 8

CL3A2-1- 8 CL3A2-1- 8

A A

A A

A A

A A

A A

A A

CL3A2-1- 9 CL3A2-1- 9

CL3A2-1- 9 CL3A2-1- 9

CL3A2-1- 9

CL3A2-1- 9

CL3A2-1- 9

CL3A2-1- 9

CL3A2-1- 9CL3A2-1- 9

CL3A2-1- 9CL3A2-1- 9

(E) LL3A2-1- 4

E

E

E

E

E

E

E

E

E

E

E

(E) LL3A2-1- 4

(E) LL3A2-1- 4 (E) LL3A2-1- 4

(E) LL3A2-1- 4

(E) LL3A2-1- 4

(E) LL3A2-1- 4

(E) LL3A2-1- 4

(E) LL3A2-1- 4

(E) LL3A2-1- 4

(E) LL3A2-1- 4

CORRIDOR

C3-12

NL3A2-1B- 23

E

B NL3A2-1B- 23

NL3A2-1B- 23D

E

B NL3A2-1B- 23

NL3A2-1B- 23

NL3A2-1B- 23D

C

NL3A2-1B- 23

NL3A2-1B- 23

C

DNL3A2-1B- 23

NL3A2-1B- 23

C

E

B

NL3A2-1B- 23

NL3A2-1B- 23

NL3A2-1B- 23D

E

NL3A2-1B- 23

B

NL3A2-1B- 23

NL3A2-1B- 23

C

NL3A2-1B- 23

B

E

NL3A2-1B- 23NL3A2-1B- 23 D

C

N L3

A 2-

1B

N

L3 A

2- 1B

C

DNL3A2-1B- 23

NL3A2-1B- 23

E

B

NL3A2-1B- 23

NL3A2-1B- 23

B

E NL3A2-1B- 23

NL3A2-1B- 23

C

NL3A2-1B- 23 D

E

B

D

C

NL3A2-1B- 23

NL3A2-1B- 23

NL3A2-1B- 23

NL3A2-1B- 23

CL3A2-1- 1

CL3A2-1- 1

E

E

CL3A2-1- 1

E

CL3A2-1- 1

(E) LL3A2-1- 4

A

E

CL3A2-1- 1

CL3A2-1- 1

E

E

CL3A2-1- 1

E

CL3A2-1- 1

CL3A2-1- 1

E

E

CL3A2-1- 1

CL3A2-1- 1

E E

CL3A2-1- 1

E

(E) LL3A2-1- 4 A

A

(E) LL3A2-1- 4

(E) LL3A2-1- 4A

A CL3A2-1- 2

CL3A2-1- 2CL3A2-1- 2 CL3A2-1- 2

A AA

NL3A2-1B- 5

E

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1B- 5

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

NL3A2-1B- 5

NL3A2-1B- 5

E

NL3A2-1B- 5

E

E

NL3A2-1B- 5

NL3A2-1B- 5

E

NL3A2-1B- 5

E

NL3A2-1B- 5

E

NL3A2-1B- 5

E

C

NL3A2-1B- 5

NL3A2-1B- 5E

E

NL3A2-1B- 5

NL3A2-1B- 5

F

F

F

NL3A2-1B- 5

NL3A2-1B- 5

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

N L3

A 2-

A

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

N L3

A 2-

A

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

CL3A2-1- 5 CL3A2-1- 5

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9 NL3A2-1A- 9

NL3A2-1A- 9NL3A2-1A- 9NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

NL3A2-1A- 9

E E

EEE

E

E E

E E E

C

D E

B

CL3A2-1- 11

CL3A2-1- 5

CL3A2-1- 5

CL3A2-1- 5CL3A2-1- 5

A

AA

C

D

AA

E

B

A

CL3A2-1- 11

C

D E

B

CL3A2-1- 11 CL3A2-1- 11

CL3A2-1- 11 CL3A2-1- 11

CL3A2-1- 11CL3A2-1- 11

CL3A2-1- 11 CL3A2-1- 11

CL3A2-1- 11 CL3A2-1- 11

AA

AA

A A

A A A A

AA

C

D

E

B

CL3A2-1- 5 CL3A2-1- 5

CL3A2-1- 5

CL3A2-1- 5 CL3A2-1- 5

AA

A A A

CL3A2-1- 16 CL3A2-1- 16

CL3A2-1- 16 CL3A2-1- 16

CL3A2-1- 16

CL3A2-1- 16

CL3A2-1- 16

CL3A2-1- 16

CL3A2-1- 16CL3A2-1- 16

CL3A2-1- 16

CL3A2-1- 16

E

B

A A

AA

D

C

A A

A A

C

D

AA

E

A

A

B

CL3A2-1- 10

CL3A2-1- 2

CL3A2-1- 2

CL3A2-1- 11

CL3A2-1- 16

CL3A2-1- 8

CL3A2-1- 9

CL3A2-1- 4

CL3A2-1- 4 CL3A2-1- 4

CL3A2-1- 4CL3A2-1- 4

CL3A2-1- 4

CL3A2-1- 4

CL3A2-1- 4CL3A2-1- 4

CL3A2-1- 4CL3A2-1- 4

CL3A2-1- 4 CL3A2-1- 4

CL3A2-1- 10

NL3A2-1B- 23

NL3A2-1B- 23

NL3A2-1B- 25

NL3A2-1B- 25

NL3A2-1B- 25

NL3A2-1B- 25

NL3A2-1B- 25

NL3A2-1B- 25

NL3A2-1B- 25

NL3A2-1B- 25

E

B

A A

A

C

D

AA

A

G

B

E

A A

A A

D

C

A A

A A

AA

E

B

A A

G

D

C

G

A

A

G

G

G

E

E

E

Z(E) LL3A2-1- 4

(E) LL3A2-1- 4

Z

Z

(E) LL3A2-1- 4

Z

(E) LL3A2-1- 4

Z (E) LL3A2-1- 4

Z

(E) LL3A2-1- 4

Z

(E) LL3A2-1- 4

(E) LL3A2-1- 4

Z

CORRIDOR

C3-26

TOILET

3C-104

TOILET

3C-105

CORRIDOR

C3-27 CORRIDOR

C3-28

ROOM

3C-106

STAIR

TYP.

24 TYP.

TYP.

TYP.

TYP.

TYP.

AREA NOT IN PROJECT SCOPE.

ELECTRICAL ITEMS ARE EXISTING TO REMAIN.

CLEAN UTILITY

3D-113

A

CL3A2-1- 2

A

CL3A2-1- 2

STAFF TOILET

3D-117

NL3A2-1B- 5

E on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

TRUE NORTH

PLAN NORTH

KEYPLAN

A/E:

TRIPLE C - The A/E Group

(612) 355-1251

Mat Perkins

A

B D

EF

G

H

J

K

L

M

C

GENERAL NOTES

KEYNOTES

1/8" = 1'-0"

B

IM

/6

-2

-1

R e n o v a te

D

B e d W in g -B

-M

P L S

V A

M C

/6 -2

-7

.M

P L S

.3 D

.B e d .W in g .M

E P

.B .L

.r v t

/1

/2

:3

:1

A

M

09/12/2022 K. Luke N. Wicklund

618-22-102

1391 - EL103

ELECTRICAL LIGHTING CEILING PLANS

-THIRD LEVEL 3D - NEW

1 Veterans Drive, Minneapolis, MN 55417

B70

RENOVATION OF BUILDING 70 3D

BED WING

100% CONSTRUCTION

DOCUMENTS

SCALE: 1/8" = 1'-0"

F3

ELECTRICAL LIGHTING CEILING PLAN

-THIRD LEVEL 3D - NEW

DEDUCTIVE ALTERNATES

D1

DEDUCTIVE ALTERNATE #1: PROVIDE STORAGE ROOM IN

LIEU OF PATIENT ROOMS 10 AND 11 (3D-310/A & 3D-311/A).

REMOVE SCOPE OF WORK ASSOCIATED WITH NEW

HEADWALL, PLUMBING, SPECIALTY EQUIPMENT.

D2

D3

DEDUCTIVE ALTERNATE #2: PROVIDE STORAGE ROOM IN

LIEU OF PATIENT ROOMS 12 AND 13 (3D-312/A & 3D-313/A).

REMOVE SCOPE OF WORK ASSOCIATED WITH NEW

HEADWALL, PLUMBING, SPECIALTY EQUIPMENT.

DEDUCTIVE ALTERNATE #3: PROVIDE STORAGE ROOM IN

LIEU OF PATIENT ROOMS 14, 15, 16, AND 17 (3D-314/A,

3D-315/A, 3D-316/A & 3D-317/A). REMOVE SCOPE OF WORK

ASSOCIATED WITH NEW HEADWALL, PLUMBING, SPECIALTY

EQUIPMENT.

NOTE: DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE TAKEN IN

SEQUENTIAL ORDER.

SCALE: 1/8" = 1'-0"

F6

ELECTRICAL LIGHTING CEILING PLAN

-THIRD LEVEL 3D - NEW

1. REMOVE ALL EXISTING LIGHT FIXTURES AND CONTROLS .

2. REMOVE ALL EXISTING ELECTRICAL OUTLETS AND FEEDERS BACK TO THE

SOURCE PANEL. PROVIDE NEW ELECTRICAL DEVICES FOR THE RENOVATION.

3. PROVIDE NEW LIGHT FIXTURE, SEE LUMINAIRE SCHEDULE ON SHEET E-701 FOR

ADDITIONAL INFORMATION.

4. PROVIDE NEW LIGHT SWITCH, SEE E-900 SERIES FOR ADDITIONAL

INFORMATION.

5. PROVIDE NEW ELECTRICAL OUTLETS.

6. SEE SHEET E-601 FOR ADDITIONAL ONE-LINE INFORMATION.

7. REMOVE FEEDERS SERVING MECHANICAL EQUIPMENT TO BE REPLACED WITH

THIS PROJECT. PROVIDE NEW FEEDERS. AIR HANDLING UNIT, EXHAUST AND

RETURN FANS SHALL BE SERVED FROM AN EMERGENCY POWER SOURCE.

8. PROVIDE A CODE SIZED RECESSED JBOX WITH A 1-1/4" CONDUIT STUBBED

ABOVE CEILING FOR NURSE CALL DEVICE.

9. PROVIDE 120V CIRCUIT TO SERVE ROLLER BLINDS, SEE ARCH PLANS FOR

DETAILS.

10. PROVIDE 120V CIRCUIT TO SERVE NEW PLUMBING FIXTURES.

This is the start of the file's text. The full file is on GovTribe.