This file attachment is related to a federal contract solicitation for renovations at a Department of Veterans Affairs medical facility. The solicitation number is 36C26323R0023 and seeks proposals to renovate a private patient bed ward (3D) at a Veterans Health Administration facility located in Veterans Integrated Service Network 23. Proposals are due by responding to the solicitation for project number 618-22-102. The solicitation involves renovating an existing area to create a new private patient bed ward and appears to include revised architectural drawings as attachments. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT LEGEND
ANTE ROOM PATIENT SPACES
BARIATRIC PATIENT ROOM
STAFF SPACES
PATIENT SPACES
UTILITY SPACES
CIRCULATION
SAFER PATIENT ROOM
615 SF
CORRIDOR
C3-12
160 SF
STAIR
169 SF
STAIR
302 SF
ROOM
3C-106
307 SF
CORRIDOR
C3-28
186 SF
CORRIDOR
C3-27
245 SF
CORRIDOR
C3-26
ICE/
H2O
213 SF
PATIENT 9
3D-109
79 SF
RR 9
3D-109A
69 SF
RR 8
3D-108A
256 SF
PATIENT 8
3D-108
285 SF
PATIENT 7
3D-107
69 SF
RR 7
3D-107A
297 SF
PATIENT 6
3D-106
72 SF
RR 6
3D-106A
289 SF
PATIENT 5
3D-105
72 SF
RR 5
3D-105A
300 SF
PATIENT 4
3D-104
69 SF
RR 4
3D-104A
298 SF
PATIENT 3
3D-103
70 SF
RR 3
3D-103A
69 SF
RR 2
3D-102A
296 SF
PATIENT 2
3D-102
299 SF
BARIATRIC 1
3D-101
90 SF
RR 1
3D-101A
269 SF
PATIENT 18
3D-133
78 SF
RR 18
3D-133A
68 SF
RR 17
3D-132A
268 SF
SAFER PATIENT 17
3D-132
299 SF
STAFF WORK
3D-136
245 SF
MSA'S
3D-100
190 SF
CLEAN LINENS
3D-138
98 SF
ASST. NURSE MNGR
3D-110
93 SF
NURSE MNGR OFFICE
3D-111
127 SF
MED ROOM
3D-112
106 SF
NUTRITION
3D-135
292 SF
SAFER PATIENT 16
3D-131
67 SF
RR 16
3D-131A
67 SF
RR 15
3D-129A
252 SF
PATIENT 15
3D-129
280 SF
PATIENT 14
3D-128
71 SF
RR 14
3D-128A
71 SF
RR 13
3D-126A
102 SF
PHARM OFFICE
3D-120
108 SF
SOILED UTILITY
3D-134
49 SF
STAFF TOILET
3D-117
131 SF
SPS STORAGE
3D-114
315 SF
EQUIPMENT ROOM
3D-115 16 SF
EQUIP. ALCOVE
3D-140
245 SF
PATIENT 13
3D-126
260 SF
PATIENT 12
3D-12567 SF
RR 12
3D-125A
67 SF
RR 11
3D-123A
61 SF
HAC
3D-119
259 SF
STAFF BREAK ROOM
3D-116
238 SF
PATIENT 11
3D-123
206 SF
PATIENT 10
3D-121
74 SF
RR 10
3D-121A
54 SF
ANTE ROOM
3D-133B
74 SF
CLEAN UTILITY
3D-113
30 SF
OXYGEN STOR.
3D-118
262 SF
CIRCULATION
C3-18
55 SF
ANTE ROOM
3D-101B
19 SF
EQUIP. ALCOVE
3D-127
17 SF
CHARTING
3D-142
16 SF
EQUIP. ALCOVE
3D-140
16 SF
CHARTING
C3-19B
17 SF
CHARTING
3D-141
18 SF
CHARTING
C3-25A 17 SF
CHARTING
C3-19A
11 SF
EQUIP ALCOVE
3D-137
15 SF
CHARTING
C3-19C
49 SF
TOILET
3C-104
49 SF
TOILET
3C-105
50 SF
ANTE ROOM
3D-121B on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(520) 481-8548
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
1/8" = 1'-0"
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
B e d W in g .A
R C
H .B
.L
.r v t
/1
/2
:2
:0
A
M
09/12/2022 M.PERKINS K.MACAULAY
618-22-102
1391 - A-002
ARCHITECTURAL ROOM PROGRAM PLAN -
3D
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING100% CONSTRUCTION
DOCUMENTS
1/8" = 1'-0" F4
ARCHITECTURAL ROOM PROGRAM PLAN - 3D
ROOM PROGRAM SCHEDULE_3D
LEGEND
ROOM
PROGRAM
CODE NAME
PROGRAM
AREA
ACTUAL
AREA
AREA
DIFFERENCE
SS204 ASST. NURSE MNGR 80 SF 98 SF -18 SF
SV583 CHARTING 100 SF 18 SF 82 SF
SV583 CHARTING 100 SF 17 SF 83 SF
SV583 CHARTING 100 SF 17 SF 83 SF
SV583 CHARTING 100 SF 17 SF 83 SF
SV583 CHARTING 100 SF 16 SF 84 SF
SV583 CHARTING 100 SF 15 SF 85 SF
CIRC EQUIP ALCOVE 11 SF
SC052 EQUIP. ALCOVE 16 SF
SC052 EQUIP. ALCOVE 30 SF
IMS81 EQUIP. ALCOVE 120 SF 19 SF 101 SF
SV583 MED ROOM 100 SF 127 SF -27 SF
SC152 MSA'S 245 SF
SS204 NURSE MNGR OFFICE 80 SF 93 SF -13 SF
SV272 NUTRITION 80 SF 106 SF -26 SF
SS218 PHARM OFFICE 80 SF 102 SF -22 SF
SS262 STAFF BREAK ROOM 100 SF 259 SF -159 SF
SB191 STAFF TOILET 85 SF 49 SF 36 SF
SC231 STAFF WORK 240 SF 299 SF -59 SF
STAFF SPACES: 19 1565 SF 1552 SF 314 SF
SC471 CLEAN LINENS 60 SF 190 SF -130 SF
SB737 CLEAN UTILITY 100 SF 74 SF 26 SF
IMS81 EQUIPMENT ROOM 120 SF 315 SF -195 SF
SB244 HAC 60 SF 61 SF -1 SF
IMS83 OXYGEN STOR. 100 SF 30 SF 70 SF
SB743 SOILED UTILITY 60 SF 108 SF -48 SF
SRSP1 SPS STORAGE 60 SF 131 SF -71 SF
UTILITY SPACES: 7 560 SF 909 SF -349 SF
Grand total: 75 8330 SF 12543
SF
-3912 SF
ROOM PROGRAM SCHEDULE_3D
LEGEND
ROOM
PROGRAM
CODE NAME
PROGRAM
AREA
ACTUAL
AREA
AREA
DIFFERENCE
LEVEL 3
IMS24 ANTE ROOM 65 SF 54 SF 11 SF
IMS24 ANTE ROOM 65 SF 64 SF 1 SF
IMS24 ANTE ROOM 65 SF 50 SF 15 SF
IMS23 PATIENT 9 240 SF 213 SF 27 SF
IMS23 PATIENT 10 240 SF 206 SF 34 SF
IMS23 PATIENT 18 240 SF 269 SF -29 SF
SB147 RR 9 60 SF 79 SF -19 SF
SB147 RR 10 60 SF 74 SF -14 SF
SB147 RR 18 60 SF 78 SF -18 SF
ANTE ROOM PATIENT SPACES: 9 1095 SF 1085 SF 10 SF
IMS24 ANTE ROOM 65 SF 55 SF 10 SF
IMS27 BARIATRIC 1 280 SF 299 SF -19 SF
SB161 RR 1 85 SF 90 SF -5 SF
BARIATRIC PATIENT ROOM: 3 430 SF 444 SF -14 SF
CIRC CIRCULATION 0 SF 137 SF -137 SF
CIRC CIRCULATION 0 SF 503 SF -503 SF
CIRC CIRCULATION 0 SF 1012 SF -1012 SF
CIRC CIRCULATION 0 SF 917 SF -917 SF
CIRC CIRCULATION 0 SF 262 SF -262 SF
CIRC CORRIDOR 0 SF 615 SF -615 SF
CIRC CORRIDOR 0 SF 186 SF -186 SF
CIRC TOILET 0 SF 49 SF -49 SF
CIRC TOILET 0 SF 49 SF -49 SF
CIRCULATION: 9 0 SF 3729 SF -3729 SF
IMS21 PATIENT 2 280 SF 296 SF -16 SF
IMS21 PATIENT 3 240 SF 298 SF -58 SF
IMS21 PATIENT 4 280 SF 300 SF -20 SF
IMS21 PATIENT 5 240 SF 289 SF -49 SF
IMS21 PATIENT 6 280 SF 297 SF -17 SF
IMS21 PATIENT 7 280 SF 285 SF -5 SF
IMS21 PATIENT 8 280 SF 256 SF 24 SF
IMS21 PATIENT 11 280 SF 238 SF 42 SF
IMS21 PATIENT 12 280 SF 260 SF 20 SF
IMS21 PATIENT 13 280 SF 245 SF 35 SF
IMS21 PATIENT 14 280 SF 280 SF 0 SF
IMS21 PATIENT 15 280 SF 252 SF 28 SF
SB147 RR 2 60 SF 69 SF -9 SF
SB147 RR 3 60 SF 70 SF -10 SF
SB147 RR 4 60 SF 69 SF -9 SF
SB147 RR 5 60 SF 72 SF -12 SF
SB147 RR 6 60 SF 72 SF -12 SF
SB147 RR 7 60 SF 69 SF -9 SF
SB147 RR 8 60 SF 69 SF -9 SF
SB147 RR 11 60 SF 67 SF -7 SF
SB147 RR 12 60 SF 67 SF -7 SF
SB147 RR 13 60 SF 71 SF -11 SF
SB147 RR 14 60 SF 71 SF -11 SF
SB147 RR 15 60 SF 67 SF -7 SF
PATIENT SPACES: 24 4000 SF 4129 SF -129 SF
SB147 RR 16 60 SF 67 SF -7 SF
SB147 RR 17 60 SF 68 SF -8 SF
IMS21 SAFER PATIENT 16 280 SF 292 SF -12 SF
IMS21 SAFER PATIENT 17 280 SF 268 SF 12 SF
SAFER PATIENT ROOM: 4 680 SF 695 SF -15 SF
1 ADDENDUM 1 04/06/23
PATIENT 9
3D-109
213 SF
RR 9
3D-109A
79 SF
RR 8
3D-108A
69 SF
PATIENT 8
3D-108
256 SF
PATIENT 7
3D-107
285 SF
RR 7
3D-107A
69 SF
PATIENT 6
3D-106
297 SF
RR 6
3D-106A
72 SF
PATIENT 5
3D-105
289 SF
RR 5
3D-105A
72 SF
PATIENT 4
3D-104
300 SF
RR 4
3D-104A
69 SF
PATIENT 3
3D-103
298 SF
RR 3
3D-103A
70 SF
RR 2
3D-102A
69 SF
PATIENT 2
3D-102
296 SF
BARIATRIC
3D-101
299 SF
RR 1
3D-101A
90 SF
CIRCULATION
C3-24
503 SF
PATIENT
3D-133
269 SF
RR 18
3D-133A
78 SF
RR 17
3D-132A
68 SF
SAFER
PATIENT
3D-132
268 SF
STAFF
WORK
3D-136
299 SF
MSA'S
3D-100
245 SF
CLEAN
LINENS
3D-138
190 SF
ASST.
NURSE
MNGR
3D-110
98 SF
NURSE
MNGR
OFFICE
3D-111
93 SF
MED
ROOM
3D-112
127 SF
NUTRITION
3D-135
106 SF
EQUIP.
ALCOVE
3D-139
30 SF
SAFER
PATIENT
3D-131
292 SF
RR 16
3D-131A
67 SF
RR 15
3D-129A
67 SF
PATIENT
3D-129
252 SF
PATIENT
3D-128
280 SF
RR 14
3D-128A
71 SF
RR 13
3D-126A
71 SF
PHARM
OFFICE
3D-120
102 SF
SOILED
UTILITY
3D-134
108 SF
CIRCULATION
C3-20
137 SF
STAFF
TOILET
3D-117
49 SF
SPS
STORAGE
3D-114
131 SF
EQUIPMENT
ROOM
3D-115
315 SF
PATIENT
3D-126
245 SF
PATIENT
3D-125
260 SF
RR 12
3D-125A
67 SF
RR 11
3D-123A
67 SF
HAC
3D-119
61 SF
STAFF
BREAK
ROOM
3D-116
259 SF
PATIENT
3D-123
238 SF
PATIENT
3D-121
206 SF
RR 10
3D-121A
74 SFA-401
E8
A-401
C8
A-402
D7
F1
A-101
F1
A-101
A-403
F7
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
HJKLM
CORRIDOR
C3-12C3-12
STAIR
ROOM
3C-1063C-106
CORRIDOR
C3-27C3-27
CORRIDOR
C3-26C3-26
CORRIDOR
C3-28C3-28
STAIR
ANTE
ROOM
3D-133B
54 SF
CLEAN
UTILITY
3D-113
74 SF
OXYGEN
STOR.
3D-118
30 SF
8'-0"
CIRCULATION
C3-25
1012 SF
CIRCULATION
C3-19
917 SF
CIRCULATION
C3-18
262 SF
9A
115A 115B
3A
6A
5A
9A
8A
121 12 1A
1A
2A
6B
136A
3A
1B
8A
7A
1A
2A
4A
3A
6A
5A
109 11
121B
109B
133B 101B
EQUIP.
ALCOVE
3D-127
19 SF
CHARTING
3D-142
17 SF
EQUIP.
ALCOVE
3D-140
16 SF
CHARTING
C3-19B
16 SF
CHARTING
3D-141
17 SF
CHARTING
C3-25A
18 SF
CHARTING
C3-19A
17 SF
EQUIP
ALCOVE
3D-137
11 SF
CHARTING
C3-19C
15 SF
A
A
C
C
C
A
A
A
A
A
A
A
A
A
A
A
A
B
A-404
F7
132B
116B
Q-101
F4
TOILET
3C-1043C-104
TOILET
3C-1053C-105
55 SF
ANTE
ROOM
64 SF
ANTE
ROOM
9 SF
CHUTE
4A
38 QTY OF
LOCKERS
50 SF
ANTE
ROOM
14 QTY OF
LOCKERS
SINK
ALCOVE
3C-134B
3 SF
A-401
E6
FEC
FEC
FEC
2A
MECHANICAL
ROOM
3D-1223D-122
ARCHITECTURAL SYMBOL LEGEND
GENERAL SHEET NOTES
DEMOLISHED WALL, FIXTURE OR FURNISHING
EXISTING WALL, FIXTURE OR FURNISHING
VA/VA ITEM - VA SUPPLIED & INSTALLED
VA/CC OR VC ITEM - VA SUPPLIED & CONTRACTOR
INSTALLED
CC/CC ITEM - CONTRACTOR SUPPLIED & INSTALLED
MATCHLINE
A. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE
RATED WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA.
PROVIDE ALL PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT
WALLS SHALL BE CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY
MEANS OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL. SEE
MECHANICAL AND PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
B. C.CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND
CONDUIT PIPING WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL
SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID
CONFLICTS AND TO MAINTAIN REQUIRED EQUIPMENT ACCESS AND
SERVICEABILITY.
C. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD
VERIFICATION WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM
THOSE INDICATED. CONTRACTOR TO FIELD VERIFY IN ADVANCE THE
LOCATION AND CONDITION OF THOSE EXISTING SYSTEMS SHOWN TO BE
MODIFIED OR REMOVED. CONTRACTOR TO NOTIFY ARCHITECT SHOULD
CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY FROM CONSTRUCTION
DOCUMENTS.
D. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH
ALL TRADES PRIOR TO INSTALLATION.
E. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
F. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO
COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT
AND RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
G. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED
EXTERIOR PIPE PENETRATIONS AND SEAL COMPLETELY.
H. CONTRACTOR TO PROVIDE TEMPORARY FLOORING WHILE MODIFYING
SUBFLOORING.
I. ANY LANDSCAPE, HARDSCAPE, FIXTURE, SIGNAGE AND SYSTEMS OR
PEDESTRIAN CONTROL DEVICES WITHIN THE TEMPORARY ACCESSIBLE
PATHWAY SHALL BE PROTECTED IN PLACE OR TEMPORARILY RELOCATED
AS NECESSARY FOR CONTINUED UNINTERRUPTED OPERATION,
ACCESS, MAINTENANCE AND / OR VISIBILITY.
J. INFILL & FLOAT FLOORS AT DEMO WALL LOCATIONS, TYPICAL ALL
INTERIOR WALLS.
KEYNOTES-
UNRATED PARTITION
SMOKE PARTITION
1 HOUR RATED PARTITION
2 HOUR RATED PARTITION
EXISTING WALL TO REMAIN
EXISTING AREA NOT IN CONTRACT (NIC)
WINDOW TYPE TAG
# NEW DOOR AND TAG
## WALL TAG
LEVEL 2
INTERSTITIAL
869' - 3 1/2"
LEVEL 3
INTERSTITIAL
887' - 11 1/2"
LEVEL 2
859' - 0"
LEVEL 3
877' - 8"
LEVEL 4
896' - 4"
HJKLM
PATIENT 14
3D-128
IMS21
280 SF
PHARM
OFFICE
3D-120
SS218
102 SF
SPS
STORAGE
3D-114
SRSP1
131 SF
INTERSTITIAL
SPACE
ABOVE
INTERSTITIAL
SPACE
BELOW
RR 14
3D-128A
SB147
71 SF
2' -4
/2
6' -0
'-3
/2
2' -4
/2
6' -0
CIRCULATION
C3-25
CIRC
1012 SF
RR 5
3D-105A
SB147
72 SF
PATIENT 5
3D-105
IMS21
289 SF
CIRCULATION
C3-19
CIRC
917 SF
LEVEL 3
INTERSTITIAL
887' - 11 1/2"
LEVEL 3
877' - 8"
LEVEL 4
896' - 4"
R 5'-6"
7 5
22 22
23 23
K
K
R 6'-0" V
E R
T
IC
A L
B E
N D
5' -6
1'
-0
R 6'-0"
E1
A-101
E1
A-101 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(520) 481-8548
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
As indicated
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
B e d W in g .A
R C
H .B
.L
.r v t
/1
/2
:2
:3
A
M
09/12/2022 M.PERKINS K.MACAULAY
618-22-102
1391 - A-101
ARCHITECTURAL FLOOR PLAN - THIRD
LEVEL - 3D NEW
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING100% CONSTRUCTION
DOCUMENTS
1/8" = 1'-0" F6
ARCHITECTURAL FLOOR PLAN - THIRD LEVEL - 3D NEW
1 NO WORK IN THIS AREA.
2 FURNITURE IS NOT IN CONTRACT; SHOWN FOR REFERENCE ONLY
3 NEW LOCATION FOR PNUEMATIC TUBE SYSTEM END STATION
4 NEW MOTORIZED ROLLING SECURITY SHUTTER AT HEAD WALL.
5 NEW PNEUMATIC TUBE IN INTERSTITIAL SPACE ABOVE.
6 CONNECT NEW PNEUMATIC TUBE TO EXISTING TUBING.
7 EXISTING PNEUMATIC TUBING TO BE DEMOLISHED IN INTERSTITIAL SPACE
ABOVE - SEE AD101.
1/8" = 1'-0" F1
ARCHITECTURAL BUILDING SECTION - 3D NEW
3/16" = 1'-0" E1
PNEUMATIC TUBE SECTION
1/4" = 1'-0" C1
PNEUMATIC TUBE FLOOR PLAN
1 ADDENDUM 1 04/06/23
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
HJKLM
9A
115A 115B
123A
126A
125A
129A
128A
121 12 1A
131A
132A
6B
136A
3A
111B
108A
107A
1A
102A
104A
103A
106A
105A
1B
9B
3B
1B
213 SF
PATIENT 9
3D-109
79 SF
RR 9
3D-109A
69 SF
RR 8
3D-108A
256 SF
PATIENT 8
3D-108
285 SF
PATIENT 7
3D-107
69 SF
RR 7
3D-107A
297 SF
PATIENT 6
3D-106
72 SF
RR 6
3D-106A
289 SF
PATIENT 5
3D-105
72 SF
RR 5
3D-105A
300 SF
PATIENT 4
3D-104
69 SF
RR 4
3D-104A
298 SF
PATIENT 3
3D-103
70 SF
RR 3
3D-103A
69 SF
RR 2
3D-102A
296 SF
PATIENT 2
3D-102
299 SF
BARIATRIC 1
3D-101
90 SF
RR 1
3D-101A
269 SF
PATIENT 18
3D-133
78 SF
RR 18
3D-133A
68 SF
RR 17
3D-132A
268 SF
SAFER PATIENT 17
3D-132
299 SF
STAFF WORK
3D-136
245 SF
MSA'S
3D-100
190 SF
CLEAN LINENS
3D-138
98 SF
ASST. NURSE MNGR
3D-110
93 SF
NURSE MNGR OFFICE
3D-111
127 SF
MED ROOM
3D-112
106 SF
NUTRITION
3D-135
292 SF
SAFER PATIENT 16
3D-131
67 SF
RR 16
3D-131A
67 SF
RR 15
3D-129A
252 SF
PATIENT 15
3D-129
280 SF
PATIENT 14
3D-128
71 SF
RR 14
3D-128A
71 SF
RR 13
3D-126A
102 SF
PHARM OFFICE
3D-120
108 SF
SOILED UTILITY
3D-134
49 SF
STAFF TOILET
3D-117
131 SF
SPS STORAGE
3D-114
315 SF
EQUIPMENT ROOM
3D-115
16 SF
EQUIP. ALCOVE
3D-140
245 SF
PATIENT 13
3D-126
260 SF
PATIENT 12
3D-125
67 SF
RR 12
3D-125A
67 SF
RR 11
3D-123A
61 SF
HAC
3D-119
259 SF
STAFF BREAK ROOM
3D-116
238 SF
PATIENT 11
3D-123
206 SF
PATIENT 10
3D-121
74 SF
RR 10
3D-121A
54 SF
ANTE ROOM
3D-133B
74 SF
CLEAN UTILITY
3D-113
30 SF
OXYGEN STOR.
3D-118
262 SF
CIRCULATION
C3-18
55 SF
ANTE ROOM
3D-101B
J8
S
S6 6
± 10'-0 7/8" 2'-8 1/4" 4'-10 1/4"
U6
4'-3 1/4" 8'-1"
1'-7"
± 9'-5 1/2"
7 1/2"
S6
S 3S
S6
E
E
E3
3' -8
3'
-2
E
E
E3E3 U
S
E3
S6
S
7' -9
5'
-1
/4
2' -0
5'
-1
/4
7' -3
4'
-6
7' -5
5'
-1
/4
2' -0
5'
-1
/4
7' -4
4'
-9
7' -6
5'
-1
/4
2' -0
5'
-1
/4
7' -2
/4
5'
-0
/4
7' -8
5'
-1
/4
2' -0
5'
-1
/4
9' -7
7' -5
/8
A U
1' -0
S
" 3' -2
1' -1
3/
4" 3'
-1
A
S
S
S
1/
4"
4'-3 1/4"
6'-7 3/4"
3'-6"
1/
4"
6'-10 1/4"
1'-6"
3' -2
3'
-6
3' -2
3'
-6
S
S
U
1'-0"
S6
E3E3
E
E
S6
S
S
E
E
S
3'-6"
U
U
2"
S
S
S6
4'-0 3/4" 8'-4 1/4"
1'-0"
S 3 S6S6
S
± 11'-7 1/4"
3'-1" 4'-8"
S 6 E
E
(8 '-0
C
LE
A
R M
IN
8'
-0
/8
5' -7
'-4
/4
7' -9
/4
5'
-1
/4
2' -0
5'
-1
/4
7' -2
/2
4'
-8
/2
7' -4
5'
-1
/4
2' -0
5' -1
/4
7'
-2
/2
4' -8
/2
7'
-3
5' -1
/4
2'
-0
5' -1
/4
7'
-5
/4
5' -0
7'
-4
5' -1
/4
2'
-0
5' -7
/4
9'
-7
/4
2'
-1
3/ 8"
H W
-S H
-3 HW-1A
H W
-S
LI
-2
H W
-2 H
HW-SLI-2
HW-SLI-1
HW-SLI-1
HW-SLI-1
HW-SLI-1
HW-SLI-1
HW-SLI-1
H W
-S
LI
-2
H W
-S
LI
-2
HW-SLI-1
HW-SLI-1
HW-SLI-1
HW-SLI-1
HW-SLI-1
HW-SLI-1
HW-SLI-1
H W
-S
LI
-2
HW-SLI-3
4'-0 3/4"
1/
2"
/2
4'-0 3/4"
8'-4 1/4" ± 11'-7 1/4"
3' -2
3'
-6
3' -6
3'
-2
9"
1/ 2"
U
S
E
E
S
U
2"
1'-0" 3'-0"
3'-0"
S
1' -7
"1'-0 1/8"
1/
2"
U
U
2' -6
/2
1'-6"
S6
E
E
S3
S
E
E
S
S
CLEAR
8'-1" 8'-11" 7'-7 1/4" 6'-1" ± 10'-4"
HW-1A
HW-1A
HW-1A
HW-1A
HW-1A
HW-1A
HW-1A
HW-1A
S
U
U
1' -1
1"
3' -1
0" 1'
-7
/4
8' -0
/4
9'
-1
1/ 4"
S6
S
S 6J3S
E
S
U6
S6
6'-9" 5'-7" 1'-7"
H W
-2 H 2'
-8
4'-0 3/4"
S3
S
7'-3"
2'
-3
/4
C
LE
A R
8' -4
/8
5' -6
/8
2'
-0
'-3
8'
-3
/2
8' -3
'-1
7' -4
/4
3'
-1
C
LE
A R
6' -0
'-6
'-1
0"
'-3
5' -3
/4
1'
-9
3' -6
8'
-0
/4
(8 '-0
C
LE
A
R M
IN
8'
-1
'-3
/4
6'
-5
/2
'-0
/2
'-3
/4
(V
IF
3' -1
1/
4"
8' -4
/4
C
LE
A
R 6'
-0
1' -1
0"
'-1
1"
'-4
/4
2' -6
'-0
/8
8'-0 3/4" 1'-4" 8'-6 3/4" 3'-1 1/2" 8'-0"9'-9"
(8'-0 MIN)
8'-0 3/4"
± 22'-9 1/4"
3'-10"
2'-0" 7'-9 1/4"
1'-6"
11'-7 3/4" 11'-1 1/2"
2'-2" 14'-2 1/4" 3'-7 1/4"
2'-9 3/4"
7'-7 1/2" 6'-1 3/4"
32°
4'-1 5/8"
S
S
S6
S
S
S6
S
S
S3
S3
S
S3 S
S
S3
J3
S3
S
J3 J3
J3
S3
S3
S
S
S
S3S
S
S
S3
S3S3 S3
E
E
S
S6 S3
S3
S
S
J3
J3
S3
S
S3
S
S3
S
S3
S
S3
S3
S3
S
S6 S6
HW-1A
H W
-4 K
HW-4K
HW-3E
HW-3E
H W
-4 E
H W
-S H
-3 D
H W
-2
H W
-S H
-3
HW-SH-3
HW-3E
HW-4F HW-4F
HW-5D
HW-SH-3
H W
-S H
-3
H W
-S H
-3
2'-2 1/4" 7'-1" 5'-7 1/4"
E
E
E6
U6
S
E
E
S
1' -9
7'-0 1/2"
U
S
E
E3 E3
S6
1/
2"
2'-1"
2' -0
3'
-0
S 6S
S
S6
S
S6
E3
S
4'-6"
2'-1 1/4" 6'-7" 4'-8"
S 3 S
61' -0
/2
T
Y P
3'
-2
T Y
P
3' -6
1/
2"
E
E
S
S
S
S6
1' -1
1" U
S6
U
S
5'-3 1/4" 3'-5" 4'-8"
/2
1' -0
/4
J3
U
/4
S
S6
S
E
S 6E
E
S
S
5 1' -1
1" S
S6
S 6U
S
S
/2
2'-2" 6'-6 1/4" 4'-8"
U
J3
S
S
3' -2
3'
-6
3' -2
3/
4"
E
E
S
E3
E
E
S6 S
U
S
U6
S6
S
S
± 9'-10 3/4"
2'-2"
7'-3" 5'-6"
3' -2
3'
-1
1/ 2"
H W
-2 H
HW-1A
HW-1A
HW-1A
HW-1A
HW-1A
HW-1A
HW-1A
HW-1A
H W
-2 H
E3
S3
S3
/4
C
C
C4' -0
6"
4' -0
6"
4' -0
5'
-0
B
8"
E
E3
S
S3
U8
S3
S6
E3
E3
S
S6
S6
S3
E3E3
S6
S3
E3
S
S6
E
E3
E
S6
S
S
S3
J3
J3
J3
J3
S3
S
S3
S3
S3
E3
E
S
S
S
S
S
M
S3
J3
S
S
S6 S 3 S3
S
S3
S6
E3
S3
S
S3 E3
E
E3
S6
S3
E3
E3
E
E
S6
S6
U
S6
E3 E3
E
E3
E
E3
S6
S
A-401
E6
CORRIDOR
C3-27C3-27
TOILET
3C-1043C-104
TOILET
3C-1053C-105
A
A
A
A
A
A
A
A
A
A
A
A
E Q
E Q
S6
S
1'-4 1/4"
H W
-1 0A
2A
H W
-S H
-3
116B
132B
ARCHITECTURAL SYMBOL LEGEND
GENERAL SHEET NOTES
DEMOLISHED WALL, FIXTURE OR FURNISHING
EXISTING WALL, FIXTURE OR FURNISHING
VA/VA ITEM - VA SUPPLIED & INSTALLED
VA/CC OR VC ITEM - VA SUPPLIED & CONTRACTOR
INSTALLED
CC/CC ITEM - CONTRACTOR SUPPLIED & INSTALLED
MATCHLINE
A. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE
RATED WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA.
PROVIDE ALL PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT
WALLS SHALL BE CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY
MEANS OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL. SEE
MECHANICAL AND PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
B. C.CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND
CONDUIT PIPING WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL
SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID
CONFLICTS AND TO MAINTAIN REQUIRED EQUIPMENT ACCESS AND
SERVICEABILITY.
C. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD
VERIFICATION WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM
THOSE INDICATED. CONTRACTOR TO FIELD VERIFY IN ADVANCE THE
LOCATION AND CONDITION OF THOSE EXISTING SYSTEMS SHOWN TO BE
MODIFIED OR REMOVED. CONTRACTOR TO NOTIFY ARCHITECT SHOULD
CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY FROM CONSTRUCTION
DOCUMENTS.
D. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH
ALL TRADES PRIOR TO INSTALLATION.
E. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
F. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO
COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT
AND RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
G. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED
EXTERIOR PIPE PENETRATIONS AND SEAL COMPLETELY.
H. CONTRACTOR TO PROVIDE TEMPORARY FLOORING WHILE MODIFYING
SUBFLOORING.
I. ANY LANDSCAPE, HARDSCAPE, FIXTURE, SIGNAGE AND SYSTEMS OR
PEDESTRIAN CONTROL DEVICES WITHIN THE TEMPORARY ACCESSIBLE
PATHWAY SHALL BE PROTECTED IN PLACE OR TEMPORARILY RELOCATED
AS NECESSARY FOR CONTINUED UNINTERRUPTED OPERATION,
ACCESS, MAINTENANCE AND / OR VISIBILITY.
J. INFILL & FLOAT FLOORS AT DEMO WALL LOCATIONS, TYPICAL ALL
INTERIOR WALLS.
KEYNOTES-
UNRATED PARTITION
SMOKE PARTITION
1 HOUR RATED PARTITION
2 HOUR RATED PARTITION
EXISTING WALL TO REMAIN
EXISTING AREA NOT IN CONTRACT (NIC)
WINDOW TYPE TAG
# NEW DOOR AND TAG
## WALL TAG
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
SOUND ATTENUATION BATTS
(SAB), WHERE OCCURS
09 22 16
METAL STUDS
A-721
C6
A-721
E6
07 92 00
SEALANT BOTH SIDES
09 29 00
5/8" GWB
07 92 00
SEALANT BOTH SIDES
CEILINGCEILING
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
SOUND ATTENUATION
BATTS (SAB)
09 29 00
5/8" ACOUSTICALLY
ENHANCED GWB
(BOTH SIDES @ S3, S5, S7)
09 22 16
METAL STUDS
07 92 00
SEALANT BOTH SIDES
07 92 00
SEALANT BOTH SIDES
CEILING
A-721
C6
A-721
E6
09 29 00
5/8" GWB @ S, S4, S6
CEILING
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
5/8" ACOUSTICALLY ENHANCED
GWB, PLACE ON SOURCE SIDE
INNER LAYER
07 92 00
SEALANT BOTH SIDES
07 92 00
SEALANT BOTH SIDES
09 29 00
5/8" GWB
09 29 00
SOUND ATTENUATION
BATTS (SAB)
09 22 16
METAL STUDS
09 29 00
5/8" GWB 2 LAYERS
CEILINGCEILING
A-721
C6
A-721
E6
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 22 16
METAL STUDS
09 29 00
SOUND ATTENUATION
BATTS (SAB), WHERE
OCCURS
AT CHASE WALLS
REFER TO PLAN
1'-4" MIN AT SINGLE
1'-10" MIN AT DOUBLE,
WALL HUNG FIXTURE
CROSS BRACING GUSSETS AT
48" O.C. MAX VERTICALLY.
FABRICATED FROM 6" MTL
STUDS
A-721
C6
07 92 00
SEALANT BOTH SIDES
09 29 00
5/8" GWB PER SIDE
07 92 00
SEALANT BOTH SIDES
CEILING
A-721
E6
09 29 00
SAB RETAINER STRAP
WHERE SAB OCCURS
CEILING
LINE OF
STRUCTURE
LINE OF
STRUCTURE
09 29 00
SOUND ATTENUATION BATTS
(SAB), WHERE OCCURS
NOTE:
IF PARTITION TYPE IS USED IN A
CHASE WALL CONDITION, PROVIDE
CROSS BRACING GUSSETS AT 48"
O.C. MAX VERTICALLY. FABRICATED
FROM 6" MTL STUDS.
6”
09 29 00
5/8" GWB
09 29 00
SAB RETAINER STRAP
WHERE SAB OCCURS
CEILING
07 92 00
SEALANT
09 22 16
METAL STUDS
A-721
B6
LINE OF
STRUCTURE
LINE OF
STRUCTURE
FACE OF COLUMN,
WALL, OR OTHER
CONSTRUCTION, NEW
OR EXISTING
6”
09 29 00
5/8" GWB DIRECTLY APPLIED TO
SUPPORTING CONSTRUCTION
CEILING
07 92 00
SEALANT
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(520) 481-8548
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
As indicated
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
B e d W in g .A
R C
H .B
.L
.r v t
/1
/2
:2
:3
A
M
09/12/2022 M.PERKINS K.MACAULAY
618-22-102
1391 - A-102
ARCHITECTURAL DIMENSIONING PLAN -
THIRD FLOOR 3D
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING100% CONSTRUCTION
DOCUMENTS
1/8" = 1'-0" F5
ARCHITECTURAL FLOOR PLAN - THIRD LEVEL - DIMENSION PLAN
1 NEW PATIENT ROOM HEAD-WALL. SEE ELECTRICAL AND PLUMBING PLANS FOR
ADDITIONAL INFORMATION.
2 NEW PNEUMATIC TUBE SYSTEM END STATION - PROVIDE CONNECTION TO
EXISTING TUBE SYSTEM.
3 EXISTING COLUMN, FURRING, AND FINISH TO REMAIN. PROTECT IN PLACE,
PATCH / REPAIR / REPLACE ANY DAMAGED PORTIONS DURING CONSTRUCTION.
4 ALIGN FACE OF NEW WALL FINISH WITH FACE OF EXISTING WALL FINISH.
5 ALIGN PARTITION WITH CENTERLINE OF WINDOW MULLION.
6 FURRING - PROVIDE 1/2" GAP BETWEEN EXISTING WALL AND NEW METAL STUDS
DOOR HARDWARE LEGEND
1A Patient Bedroom - Passage (F04)
2H Patient Restroom - Occupancy (F02)
3E Staff Office - Office (F04), Keyed Lock *(Sim at SLI-3 - Sliding Door)
4K Staff Work Room - Office (F04), Keyed Lock
SH-3 Staff Break Room - Store Room (F07), Keyed Lock w/ Override
2 Staff Restroom - Privacy (F13)
SH-3D Medicine Room - Store Room (F07), Keyed Lock w/ Override
4E Nutrition Room - Store Room (F07), Keyed Lock
4F Equipment Room - Store Room (F07), Keyed Lock
SH-3 Storage Room - Store Room (F07), Keyed Lock w/ Override
SH-3 Clean Utility - Store Room (F07), Keyed Lock w/ Override, Sentronic Mag-Hold
SH-3 Soiled Utility - Store Room (F07), Keyed Lock w/ Override, Sentronic Mag-Hold
5D H.A.C. - Store Room (F07), Keyed Lock
SLI-1 Patient Restroom Slider - Barn Door, Aluminum Frame, Hardware by MFG'R
SLI-2 Three-Bay Slider - Telescoping, Sliding Aluminum and Glass Door System
8C Double-Acting Pair Corridor Door - Double-acting closers
11 Pair, Secure - Store Room (F07), Keyed Lock, Mechanical Room
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL
U465
(TYPE A) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL
U465
(TYPE S) STC PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
S3 3 5/8" 45
S6 6" 7 1/4" 45
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V484, U411
(TYPE U) HIGH STC PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
U6 6" 8 1/2" 50
U8 3 5/8" 10 1/2" 45
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED CHASE WALLS: UL
U420
(TYPE E) CHASE PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
E3 3 5/8" 4 1/4" 45
E6 6" 6 5/8" 45
(TYPE J) NON-RATED PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
J3 3 5/8" 4 1/4" -
J8 8" 8 5/8" -
(TYPE N) DIRECT APPLIED
MARK STUD WIDTH PRTN WIDTH
N 5/8"
1. PARTITIONS ARE DISTINGUISHED ON FLOOR PLANS BY SYMBOL DESIGNATION,
GRAPHIC DESIGNATION OR A COMBINATION OF BOTH DESIGNATIONS.
2. ALL WALLS NOT DESIGNATED WITH A GRAPHIC OR TAG TO BE TYPE S. IF UNCLEAR
CONTACT ARCHITECT.
3. "METAL STUDS" INDICATED ON THIS SHEET FOR INTERIOR PARTITIONS REFER TO
THOSE SPECIFIED IN SECTION 09 22 16 - NON STRUCTURAL METAL FRAMING. REFER
TO SPECIFICATIONS FOR ADDITIONAL CRITERIA SUCH AS MINIMUM STUD SPACING,
MINIMUM GAUGE AND PERMISSIBLE DEFLECTION LIMITS. SEE SECTION 05 41 04 LOAD
BEARING METAL STUD SYSTEM FOR FRAMING THAT IS OUTSIDE THE SCOPE OF 09 22
16 AND ASTM C754, SUCH AS LONG HEADERS, CANTILEVERED WALLS, TALL WALLS,
WALKABLE CEILINGS AND THEIR SUPPORTS, WALLS EXCEEDING SPAN TABLES AND
OTHER UNUSUAL FRAMING CONDITIONS.
4. SOUND TRANSMISSION CLASS (STC) IS A RATING SYSTEM THAT DESCRIBES THE
ABILITY OF AN ASSEMBLY TO REDUCE THE TRANSMISSION OF SOUND. CONFIGURE
SOUND-RATED WALL ASSEMBLIES ACCORDING TO THE MINIMUM REQUIREMENTS
STIPULATED IN THE STC TESTS LISTED. STC RATINGS LISTED ARE BASED ON
LABORATORY TESTING AND ARE NOT INDICATIVE OF RESULTS IN FIELD.
5. REFER TO SECTION 09 29 00 FOR ACOUSTIC SEALANTS.
6. SOUND ATTENUATION BATTS (SAB) ARE SPECIFIED IN SECTION 09 29 00. WHERE
SAB ARE INDICATED, THEY SHALL EXTEND CONTINUOUSLY FROM FLOOR TO
STRUCTURE ABOVE.
7. PARTITIONS ARE INDICATED WITH CONVENTIONAL GYPSUM WALLBOARD U.N.O.;
UPGRADE TO PREMIUM TYPES OF WALLBOARD (I.E., MOISTURE-RESISTANT, TILE-
BACKER BOARD, ACOUSTICALLY ENHANCED, ETC.) BASED ON THEIR LOCATION AND
ACCORDING TO REQUIREMENTS OF SECTION 09 29 00.
8. SEALANTS INDICATED MAY BE FOR FIRE RATING, SMOKE RATING, AIR PRESSURE
CONTAINMENT, ACOUSTIC RATING, VERMIN CONTROL, MOVEMENT (CRACK) CONTROL
AND/OR BIOLOGICAL CONTAINMENT. SEALANT JOINTS ARE TO BE SIZED FOR
EXPECTED MOVEMENT OF JOINT WITH EXPANSION/CONTRACTION CAPACITY OF
SEALANT MATERIAL TO MAINTAIN THE INTEGRITY OF THE SEAL FOR THESE
APPLICABLE PARAMETERS. SEE SPECIFICATION SECTION 07 92 00 FOR INTERIOR
JOINT SEALANTS.
9. REFER TO SECTION 07 84 00 FOR HEAD-OF-WALL FIRESTOPPING AND SEALING OF
THRU-WALL PENETRATIONS.
10. "LINE OF STRUCTURE" INDICATED FOR EACH PARTITION IS DIAGRAMMATIC ONLY
AND DOES NOT INDICATE EXACT CONSTRUCTION CONDITIONS OR GEOMETRY.
11. ALL DIMENSIONS ARE FROM FACE TO FACE, OR CENTERLINE TO CENTERLINE,
U.N.O. REFER TO PARTITION MATRICES FOR PARTITION WIDTH DIMENSIONS UNLESS
INDICATED TO BE SHOWN ON PLAN.
14. FIRE RESISTANT AND FIRE RESISTANT SMOKE BARRIER RATINGS ARE TO
CONTINUE THROUGH ALL OPENINGS IN RATED PARTITIONS.
15. SMOKE RESISTANT, FIRE RESISTANT, AND FIRE RESISTANT SMOKE BARRIER
PARTITIONS SHALL EXTEND AND SEAL TO INSIDE FACE OF EXTERIOR SHEATHING,
INCLUDING EXTENSIONS THROUGH SOFFITS.
16. REFER TO THE TOILET ACCESSORIES SHEET AND CASEWORK SHEET FOR
MOUNTING DETAIL INFORMATION.
17. REFER TO SHEET A-721 AND A-722 FOR ADDITIONAL PARTITION DETAILS AND
FRAMING INFORMATION.
GENERAL PARTITION NOTES:
THE TYPICAL PARTITION TAG SYMBOL DESIGNATION HAS TWO CHARACTERS.
THE FIRST CHARACTER IS A LETTER INDICATING THE PARTITION TYPE, THE
SECOND CHARACTER IS A NUMERIC INDICATION OF THE STUD OR CMU WIDTH.
IF A "≠" SYMBOL IS SHOWN AS THE FIRST CHARACTER, THIS INDICATES THE
PARTITION DOES NOT HAVE SOUND ATTENUATION. IN SOME INSTANCES, AN
ADDITIONAL CHARACTER OR "MODIFIER" MAY BE ADDED TO THE END AND/OR
THE LINE BELOW TO INDICATE ADDITIONAL CHARACTERISTICS WITHIN THE
WALL. REFER TO CHART BELOW FOR MODIFIER DEFINITIONS.
IF NO PARTITION TAG OR NUMERIC SECOND CHARACTER EXISTS, THE STUD
SIZE WILL BE 3 5/8" TYPICAL, U.N.O.
PARTITION TAGGING LEGEND:
≠ X#
SYMBOL INDICATES PARTITION TYPE
NO SOUND
ATTENUATION STUD WIDTH
CHARACTER WIDTH
3 3 5/8" 4 4" 6 6" 8 8"
4 7/8"
PH
PH
PH
PH
PH
PH
PH
PH
PH
PH
PH
PH
PH
PH
PH
PH
PH
PH
F A
C P
S S
2 2
F1
A-101
F1
A-101
A-403
F4
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
HJKLM
8' - 6"
8' - 6"
8' - 6"
8' - 0"
8' - 0"
8' - 6" 8' - 6"
8' - 6"
8' - 6"
8' - 6" 8' - 0"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
9' - 0"
9' - 0"
9' - 0"
E Q
E Q
E Q
E Q
E Q
E Q
213 SF
PATIENT 9
3D-109
79 SF
RR 9
3D-109A
69 SF
RR 8
3D-108A
256 SF
PATIENT 8
3D-108
285 SF
PATIENT 7
3D-107
69 SF
RR 7
3D-107A
297 SF
PATIENT 6
3D-106
72 SF
RR 6
3D-106A
289 SF
PATIENT 5
3D-105
72 SF
RR 5
3D-105A
300 SF
PATIENT 4
3D-104
69 SF
RR 4
3D-104A
298 SF
PATIENT 3
3D-103
70 SF
RR 3
3D-103A
69 SF
RR 2
3D-102A
296 SF
PATIENT 2
3D-102
299 SF
BARIATRIC 1
3D-101
90 SF
RR 1
3D-101A
503 SF
CIRCULATION
C3-24
269 SF
PATIENT 18
3D-133
78 SF
RR 18
3D-133A
68 SF
RR 17
3D-132A
268 SF
SAFER PATIENT 17
3D-132
299 SF
STAFF WORK
3D-136
245 SF
MSA'S
3D-100
190 SF
CLEAN LINENS
3D-138
98 SF
ASST. NURSE MNGR
3D-110
93 SF
NURSE MNGR OFFICE
3D-111
127 SF
MED ROOM
3D-112
106 SF
NUTRITION
3D-135
30 SF
EQUIP. ALCOVE
3D-139
292 SF
SAFER PATIENT 16
3D-131
67 SF
RR 16
3D-131A
67 SF
RR 15
3D-129A
252 SF
PATIENT 15
3D-129
280 SF
PATIENT 14
3D-128
71 SF
RR 14
3D-128A
71 SF
RR 13
3D-126A
102 SF
PHARM OFFICE
3D-120
108 SF
SOILED UTILITY
3D-134
137 SF
CIRCULATION
C3-20
49 SF
STAFF TOILET
3D-117
131 SF
SPS STORAGE
3D-114
315 SF
EQUIPMENT ROOM
3D-115
245 SF
PATIENT 13
3D-126
260 SF
PATIENT 12
3D-125
67 SF
RR 12
3D-125A
67 SF
RR 11
3D-123A
61 SF
HAC
3D-119
259 SF
STAFF BREAK ROOM
3D-116
238 SF
PATIENT 11
3D-123
206 SF
PATIENT 10
3D-121
74 SF
RR 10
3D-121A
54 SF
ANTE ROOM
3D-133B
74 SF
CLEAN UTILITY
3D-113
30 SF
OXYGEN STOR.
3D-118
917 SF
CIRCULATION
C3-19
262 SF
CIRCULATION
C3-18
19 SF
EQUIP. ALCOVE
3D-127
17 SF
CHARTING
3D-142
16 SF
EQUIP. ALCOVE
3D-140
16 SF
CHARTING
C3-19B
17 SF
CHARTING
3D-141
18 SF
CHARTING
C3-25A
17 SF
CHARTING
C3-19A
11 SF
EQUIP ALCOVE
3D-137
15 SF
CHARTING
C3-19C
615 SF
CORRIDOR
C3-12
8' - 0"
8' - 6"
9' - 0"
8' - 0"
8' - 0"
F6
A-551
TYP.
F6
A-551
TYP.
F6
A-551
TYP.
8' - 0"
8' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
9' - 0"
8' - 0"
9' - 0"
8' - 0"
9' - 0" 8' - 0"
8' - 6"
8' - 0"
9' - 0"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 6"
8' - 0"
8' - 0"
8' - 0"
8' - 6"
8' - 0"
9' - 0"
9' - 0"
8' - 0"
8' - 0"
9' - 0"
9' - 0"
8' - 0"
8' - 0" 9' - 0"
9' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
A-404
F5
2'-1"
1'-1"
1'-8"
8'-3 1/2"
1'-8"
8'-0"
8'-0"
1'-0"
1'-0" 1'-11"
7'-6" 1'-1"
1'-1"
7'-6"
1'-11"
1'-0"
8'-3"
1'-8"
CORRIDOR
C3-27C3-27
TOILET
3C-1043C-104
TOILET
3C-1053C-105
CORRIDOR
C3-28C3-28
CORRIDOR
C3-26C3-26
1'-11"
1'-11"
8'-3 1/2"
8'-3 1/2"
8'-3 1/2"
AC101
F2
8'-6"
ALIGN3 ALIGN
ALIGN
ALIGN
ALIGN
ALIGN
7'-6"
ALIGN
ALIGN
ALIGN
ALIGN
ALIGN
ALIGN
2' -5
AC101
D2
8' - 6"
A1200
A1200
A1200
A1200
A1200
A1200
A1200
A1200
A1203
A1203
A1200
A1200
A1200
A1200
A1200
A1200
ALIGN
7' - 6"
8' - 0"
8'
0" typical
F4
A-551
D4
A-551
D4
A-551
8' - 0"
2' -6
8' - 0"
8'-3 1/2"
8' - 0"
8'
0"
7' - 0"
KEYNOTES-
SMOKE DETECTOR
SPEAKER
HVAC RETURN DIFFUSER
EXIT LIGHT
HEAT DETECTOR
HVAC EXHAUST DIFFUSER
CEILING SURFACE MOUNTED LINEAR LED LIGHT
RECESSED ROUND DOWNLIGHT 6" - LIFE SAFETY BRANCH
RECESSED LUMINAIRE (24x48) LIFE SAFETY BRANCH
ACOUSTICAL TILE CEILING (24x24)
(AT-1)
ACOUSTICAL TILE CEILING (24x48)
(AT-2)
GYPSUM BOARD CEILING
REFLECTED CEILING SYMBOLS
ACCESS PANEL
HVAC SUPPLY DIFFUSER
SPRINKLER
EXISTING NEW
WALL SURFACE MOUNTED
OVERBED LIGHT
WALL RECESSED NIGHT LIGHT
PENDANT LIGHT
WOOD SLAT CEILING
WALL MOUNTED VANITY LIGHT
CURTAIN WITH TRACK
ACOUSTICAL TILE CEILING (24x48)
(AT-3)
RECESSED LUMINAIRE (24x48) CRITICAL BRANCH
RECESSED ROUND DOWNLIGHT 6" - CRITICAL BRANCH
SECURITY CAMERA
23 23
K
K
7' -5
2' -0
5'-6"
8'-0"
8'-0"
2'-0"
2'-5"
4'-7"
4'-7 3/4"
2'-5"
245 SF
MSA'S
3D-100
503 SF
CIRCULATION
C3-24
299 SF
STAFF WORK
3D-136
7'-0"
2'-0"
1' -9
F4
A-551
F4
A-551
D4
A-551
22 22
23 23
L
L
1'-8"
7' -6
7'
-7
7' -6
7'
-6
7' -6
5' -0
6E Q
E Q
1'-10"
8'-3 1/2"
8'-3 1/2"
8'-3 1/2"
8'-3 1/2"
8'-3 1/2"
F6
A-551
TYP.
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(520) 481-8548
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
As indicated
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
B e d W in g .A
R C
H .B
.L
.r v t
/1
/2
:2
:3
A
M
09/12/2022 M.PERKINS K.MACAULAY
618-22-102
1391 - AC101
ARCHITECTURAL REFLECTED CEILING PLAN
- THIRD FLOOR 3D
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING100% CONSTRUCTION
DOCUMENTS
1. ALL CEILING TO BE 9'-0" AFF UNLESS NOTED OTHERWISE.
2. PROVIDED GYPSUM WALL BOARD & STUD BULKHEADS WHERE CEILING OF DIFFERENT
HEIGHTS ABUT. DO NOT BUILD BULKHEADS OF ACOUSTICAL CEILING MATERIAL UNLESS
SPECIFICALLY DETAILED.
3. REFER TO MECHANICAL DRAWINGS FOR QUANTITY AND TYPE OF DIFFUSERS, RETURN AIR
GRILLES, & EXHAUST GRILLES. SCRIBE CEILING MATERIAL CAREFULLY FOR A TIGHT FIT.
4. REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND TYPES OF LIGHTS AND DEVICES.
SCRIBE CEILING MATERIAL CAREFULLY FOR TIGHT FIT.
5. REFER TO FIRE PROTECTION DRAWINGS FOR FIRE SPRINKLER HEAD LOCATIONS. CENTER
HEADS IN CEILING TILE AND SCRIBE CEILING MATERIALS FOR A TIGHT FIT.
6. REFER TO ROOM FINISH SCHEDULE FOR GRID SYSTEM, TYPE OF CEILING MATERIAL.
7. VERIFY CEILING HEIGHTS WITH STRUCTURE, MECHANICAL, PLUMBING, FIRE PROTECTION,
ELECTRICAL AND CONTRACTOR'S REQUIRED COORDINATION DRAWINGS.
8. ALL GWB SOFFITS, CEILINGS & BULKHEADS RECEIVE PAINT OR IF ALIGNING W/ ADJACENT
WALL, PAINT TO MATCH ADJACENT @ VERTICAL, PAINT @ UNDERSIDE.
REFLECTED CEILING
PLAN NOTES:
1/8" = 1'-0" F5
ARCHITECTURAL REFLECTED CEILING PLAN - THIRD FLOOR 3D
2 NEW 2'X2' ACOUSTICAL CEILING TILES
3 NEW GWB SOFFIT PAINTED P-2 ALL EXPOSED SIDES, TYP
4 NEW 2'X4' ACOUSTICAL CEILING TILES
5 NEW GWB CEILING WITH AT-4 ACOUSTICAL FELT DIRECT-GLUED PLANKS
6 NEW AT-5 WOOD PLANK CEILING
7 NEW GWB SOFFIT PAINTED P-4 ALL EXPOSED SIDES; TYP
8 MOTORIZED DUAL SHADE ROLLER SHADES AS SPECIFIED. REFER TO IN601.
9 MOTORIZED PRIVACY ROLLER SHADES AS SPECIFIED. REFER TO IN601.
10 NO WORK IN THIS AREA.
11 REFER TO A-404 FOR TYPCIAL PATIENT ROOM
12 MOUNT RECESSED LIGHT FIXTURE IN THE CENTER OF THE ROOM
13 EXISTING CEILING AND LIGHT FIXTURES TO REMAIN, PROTECT IN PLACE.
1/4" = 1'-0" F2
ARCHITECTURAL REFLECTED CEILING PLAN - THIRD FLOOR 3D - ENLARGED MSA STATION
1/4" = 1'-0" D2
ARCHITECTURAL REFLECTED CEILING PLAN - THIRD FLOOR 3D - ENLARGED CORRIDOR
69 SF
RR 7
3D-107A
70 SF
RR 3
3D-103A
503 SF
CIRCULATION
C3-24
78 SF
RR 18
3D-133A
68 SF
RR 17
3D-132A
299 SF
STAFF WORK
3D-136
245 SF
MSA'S
3D-100
190 SF
CLEAN LINENS
3D-138
98 SF
ASST. NURSE MNGR
3D-110
93 SF
NURSE MNGR OFFICE
3D-111
127 SF
MED ROOM
3D-112 106 SF
NUTRITION
3D-135
30 SF
EQUIP. ALCOVE
3D-139
67 SF
RR 16
3D-131A
67 SF
RR 15
3D-129A
71 SF
RR 14
3D-128A
71 SF
RR 13
3D-126A
102 SF
PHARM OFFICE
3D-120
108 SF
SOILED UTILITY
3D-134
137 SF
CIRCULATION
C3-20
49 SF
STAFF TOILET
3D-117
131 SF
SPS STORAGE
3D-114
315 SF
EQUIPMENT ROOM
3D-115
16 SF
EQUIP. ALCOVE
3D-140
245 SF
PATIENT 13
3D-126
67 SF
RR 12
3D-125A
67 SF
RR 11
3D-123A
61 SF
HAC
3D-119
259 SF
STAFF BREAK ROOM
3D-116
74 SF
RR 10
3D-121A
4A
A-403
F2
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
H
H
J
J
K
K
L
L
M
M
G R
A
IN
G R
A
IN
G R
A
IN
GRAIN
GRAIN
G R
A
IN
G R
A
IN
G R
A
IN
GRAIN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
GRAIN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
GRAIN
GRAIN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
GRAIN
G R
A
IN
2 2
30 SF
OXYGEN STOR.
3D-118
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
G R
A
IN
9A
115A 115B
3A
6A
5A
9A
8A
121 12 1A
1A
2A
6B
136A
3A
1B
8A
7A
1A
2A
4A
3A
6A
5A
121B
109B
133B 101B
213 SF
PATIENT 9
3D-109
256 SF
PATIENT 8
3D-108
285 SF
PATIENT 7
3D-107
297 SF
PATIENT 6
3D-106
289 SF
PATIENT 5
3D-105
300 SF
PATIENT 4
3D-104
298 SF
PATIENT 3
3D-103
296 SF
PATIENT 2
3D-102
299 SF
BARIATRIC 1
3D-101
269 SF
PATIENT 18
3D-133
268 SF
SAFER PATIENT 17
3D-132
292 SF
SAFER PATIENT 16
3D-131
252 SF
PATIENT 15
3D-129
280 SF
PATIENT 14
3D-128
245 SF
PATIENT 13
3D-126
260 SF
PATIENT 12
3D-125
238 SF
PATIENT 11
3D-123
206 SF
PATIENT 10
3D-121
69 SF
RR 4
3D-104A
72 SF
RR 5
3D-105A
72 SF
RR 6
3D-106A
69 SF
RR 2
3D-102A
90 SF
RR 1
3D-101A
69 SF
RR 8
3D-108A
79 SF
RR 9
3D-109A
17 SF
CHARTING
3D-141
18 SF
CHARTING
C3-25A
11 SF
EQUIP ALCOVE
3D-137
17 SF
CHARTING
C3-19A
16 SF
CHARTING
C3-19B
15 SF
CHARTING
C3-19C17 SF
CHARTING
3D-142
19 SF
EQUIP. ALCOVE
3D-127
1012 SF
CIRCULATION
C3-25
262 SF
CIRCULATION
C3-18
917 SF
CIRCULATION
C3-19
A-404
F1
186 SF
CORRIDOR
C3-27
49 SF
TOILET
3C-105
615 SF
CORRIDOR
C3-12
PT-2
PT-3,4
RB-1
RSF-1
RB-1
RSF-1
PT-2
PT-3,4
PT-2
PT-3,4
RB-1
RSF-1
RB-1
RSF-1
RB-1
LVT-2
PT-2
PT-3,4
PT-2
PT-3,4
RB-1
RSF-1
RB-1
RSF-1
PT-2
PT-3,4
PT-2
PT-3,4
RB-1
RSF-1
PT-2
PT-3,4
PT-2
PT-3,4
RB-1
RSF-1
RB-1
RSF-1
RB-1
LVT-1
RB-1
LVT-1
RB-1
LVT-2
RB-1
RSF-1
64 SF
ANTE ROOM
3D-109B
RB-1
LVT-1
WSF-1
WSF-1
WSF-1
WSF-1
RB-1
LVT-2
RB-1
LVT-2
RB-1
LVT-1
RB-1
LVT-1
RB-1
LVT-2
RB-1
LVT-2
RB-1
LVT-2
RB-1
LVT-2
RB-1
LVT-2
RB-1
LVT-1,2
RB-1
LVT-1
RB-1
LVT-1
RB-1
RSF-1
RB-1
RSF-1
PT-2
PT-3,4
PT-2
PT-3,4
RB-1
RSF-1
RB-1
RSF-1
PT-2
PT-3,4
PT-2
PT-3,4
RB-1
RSF-1
RB-1
RSF-1
RB-1
LVT-2
PT-2
PT-1
WSF-1
WSF-1
PT-2
PT-3,4
PT-2
PT-3,4
RB-1
RSF-1
RB-1
RSF-1
RB-1
RSF-1
PT-2
PT-3,4
PT-2
PT-3,4
RB-1
RSF-1
RB-1
RSF-1
PT-2
PT-3,4
RB-1
LVT-1
RB-1
RSF-1
55 SF
ANTE ROOM
3D-101B
RB-1
LVT-2
50 SF
ANTE ROOM
3D-121B
RB-1
LVT-2
RB-1
LVT-2
RB-1
LVT-1,2
RB-1
LVT-2
RB-1
LVT-2
49 SF
TOILET
3C-104
PT-2
PT-1
PT-2
PT-1
3 SF
SINK ALCOVE
3C-134B
G R
A
IN
16'-1 3/8"
2' - 6"
2'-6"
E3
IN501
B5
IN501
TYP.
B7
IN501
74 SF
CLEAN UTILITY
3D-113
G R
A
IN
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
A7
IN501
LVT - 1
LVT - 2
FLOOR FINISH LEGEND
PT-1
PT-4
PT-5
PT-3
RSF-1
WSF-1
PATTERN OR GRAIN DIRECTION CHANGE
MATERIAL FLOOR CHANGE
DIRECTION OF FINISH
CORNER GUARD LOCATION
CG
GRAIN
P-_ PAINT COLOR / WALL FINISHES
ROOM FINISH TAG
INTERIOR FINISH SYMBOLS
Base Finish Floor Finish
Wall Finishes
North
South
West East
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
H
H
J
J
K
K
L
L
M
M
69 SF
RR 7
3D-107A
70 SF
RR 3
3D-103A
503 SF
CIRCULATION
C3-24
78 SF
RR 18
3D-133A
68 SF
RR 17
3D-132A
299 SF
STAFF WORK
3D-136
245 SF
MSA'S
3D-100
190 SF
CLEAN LINENS
3D-138
98 SF
ASST. NURSE MNGR
3D-110
93 SF
NURSE MNGR OFFICE
3D-111
127 SF
MED ROOM
3D-112
106 SF
NUTRITION
3D-135
30 SF
EQUIP. ALCOVE
3D-139
67 SF
RR 16
3D-131A
67 SF
RR 15
3D-129A
71 SF
RR 14
3D-128A
71 SF
RR 13
3D-126A
102 SF
PHARM OFFICE
3D-120
108 SF
SOILED UTILITY
3D-134
137 SF
CIRCULATION
C3-20
49 SF
STAFF TOILET
3D-117
131 SF
SPS STORAGE
3D-114
315 SF
EQUIPMENT ROOM
3D-115
16 SF
EQUIP. ALCOVE
3D-140
67 SF
RR 12
3D-125A
67 SF
RR 11
3D-123A
61 SF
HAC
3D-119
259 SF
STAFF BREAK ROOM
3D-116
74 SF
RR 10
3D-121A
A-403
F2
74 SF
CLEAN UTILITY
3D-113
30 SF
OXYGEN STOR.
3D-118
9A
115A 115B
3A
6A
5A
9A
8A
121 12 1A
1A
2A
6B
136A
3A
1B
8A
7A
1A
2A
4A
3A
6A
5A
121B
109B
133B 101B
4A
213 SF
PATIENT 9
3D-109
256 SF
PATIENT 8
3D-108
285 SF
PATIENT 7
3D-107
297 SF
PATIENT 6
3D-106
289 SF
PATIENT 5
3D-105
300 SF
PATIENT 4
3D-104
298 SF
PATIENT 3
3D-103
296 SF
PATIENT 2
3D-102
299 SF
BARIATRIC 1
3D-101
269 SF
PATIENT 18
3D-133
268 SF
SAFER PATIENT 17
3D-132
292 SF
SAFER PATIENT 16
3D-131
252 SF
PATIENT 15
3D-129
280 SF
PATIENT 14
3D-128
245 SF
PATIENT 13
3D-126
260 SF
PATIENT 12
3D-125
238 SF
PATIENT 11
3D-123
206 SF
PATIENT 10
3D-121
69 SF
RR 4
3D-104A
72 SF
RR 5
3D-105A
72 SF
RR 6
3D-106A
69 SF
RR 2
3D-102A
90 SF
RR 1
3D-101A
69 SF
RR 8
3D-108A
79 SF
RR 9
3D-109A
17 SF
CHARTING
3D-141
18 SF
CHARTING
C3-25A
11 SF
EQUIP ALCOVE
3D-137
17 SF
CHARTING
C3-19A
16 SF
CHARTING
C3-19B
15 SF
CHARTING
C3-19C
17 SF
CHARTING
3D-142
19 SF
EQUIP. ALCOVE
3D-127
1012 SF
CIRCULATION
C3-25
262 SF
CIRCULATION
C3-18
917 SF
CIRCULATION
C3-19
W F
T -6
WFT-6
W F
T -6
W F
T -5
W F
T -5
WFT-3
WFT-6
WFT-6 WFT-6
WFT-6
W F
T -5
WFT-6
W F
T -5
W F
T -5
W F
T -5
WFT-3
W F
T -5
W F
T -5
W F
T -6
W F
T -6
WFT-6
WFT-5
WFT-6
W F
T -6
WFT-5
W F
T -5
WFT-3
WFT-6
W F
T -5
W F
T -5
W F
T -5
W F
T -5
WFT-6
W F
T -6
W F
T -5
WFT-6
W F
T -5
186 SF
CORRIDOR
C3-27
49 SF
TOILET
3C-105
615 SF
CORRIDOR
C3-12
WFT-1,2
PT-2
WFT-1,2
WFT-1,2
WFT-1,8
P-1,5
RB-1
P-1 P-1,5
P-1
P-5
RB-1
P-1,5 P-5
P-1
WFT-1,2
PT-2
WFT-1,2
WFT-1,2
WFT-1,8
WFT-1,2
PT-2
WFT-1,2
WFT-1,2
WFT-1,8
P-5
RB-1
P-1,5 P-1,5
P-1
P-1,5
RB-1
P-1 P-1,5
P-1
WFT-1,2
PT-2
WFT-1,2
WFT-1,2,8
WFT-1
WFT-1,2,8
PT-2
WFT-1,2
WFT-1,2
WFT-1
P-1,5
RB-1
P-1 P-1,5
P-1
P-1,5
RB-1
P-1 P-1,5
P-1
WFT-1,2
PT-2
WFT-1,2
WFT-1,2
WFT-1,8
WFT-1,2
PT-2
WFT-1,2
WFT-1,2
WFT-1,8
P-1,5
RB-1
P-1 P-1,5
P-1
WFT-1,2
PT-2
WFT-1,2
WFT-1,2
WFT-1,8
WFT-1,2
PT-2
WFT-1,2
WFT-1,2
WFT-1,8
P-1,5
RB-1
P-1 P-1,5
P-1
P-1,5
RB-1
P-1 P-1,5
P-1
P-1
RB-1
P-1 P-1
P-1
P-1
RB-1
P-1 P-1
P-5
P-1
RB-1
P-1 P-1
P-1
64 SF
ANTE ROOM
3D-109B
P-1
RB-1
P-1 P-1
P-1
WFT-7
WSF-1
WFT-7
WFT-7
WFT-7
P-1
WSF-1
P-1 P-1
P-1
P-1
RB-1
P-1 P-1
P-5
P-1
RB-1
P-1 P-1
P-1
P-1
RB-1
P-1 P-1
P-1
P-1
RB-1
P-1 P-1
P-5
P-1
RB-1
P-5 P-1
P-1
P-1
RB-1
P-5 P-1
P-1
P-5
RB-1
N/A P-1
P-1
P-1
RB-1
WFT-5
WFT-5,6
WFT-6
N/A
RB-1
N/A
WFT-6
WFT-6
P-1
RB-1
P-1 P-1
P-1
P-1,5
RB-1
P-1 P-1,5
P-1
P-1
RB-1
P-1 P-1
P-1
WFT-1,2
PT-2
WFT-1,8
WFT-1,2
WFT-1,2
WFT-1,2
PT-2
WFT-1,8
WFT-1,2
WFT-1,2
P-1,5
RB-1
P-1 P-1,5
P-1
P-1,5
RB-1
P-1 P-1,5
P-1
WFT-1,2
PT-2
WFT-1,8
WFT-1,2
WFT-1,2
WFT-1,2
PT-2
WFT-1,8
WFT-1,2
WFT-1,2
P-1,5
RB-1
P-1 P-1,5
P-1
P-1,5
RB-1
P-1 P-1,5
P-1
WFT-1
PT-2
WFT-1
WFT-1
WFT-1
WFT-7
WSF-1
WFT-7
WFT-7
WFT-7
WFT-1,2,8
PT-2
WFT-1
WFT-1,2
WFT-1,2
WFT-1,2
PT-2
WFT-1
WFT-1,2,8
WFT-1,2
P-1,5
RB-1
P-1 P-1,5
P-1
P-1,5
RB-1
P-1 P-1,5
P-1
P-1,5
RB-1
P-1 P-1,5
P-1
WFT-1,2
PT-2
WFT-1,8
WFT-1,2
WFT-1,2
WFT-1,2
PT-2
WFT-1,8
WFT-1,2
WFT-1,2
P-5
RB-1
P-1 P-5
P-1,5ANTE
ROOM
3D-121B3D-121B
WFT-1,2
PT-2
WFT-1,8
WFT-1,2
WFT-1,2
P-1
RB-1
P-1 P-1
P-1
P-1
RB-1
P-1 P-1
P-1
P-1
RB-1
P-1 P-1
P-1
55 SF
ANTE ROOM
3D-101B
W F
T -5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
WFT-6
WFT-6
WFT-6
WFT-6
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
W F
T -5
W F
T -5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
WFT-5
W F
T -5
WFT-6
WFT-6 WFT-6
W F
T -5
WFT-5
W F
T -5
W F
T -5
W F
T -5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5 P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-5
WFT-1
PT-2
WFT-1
WFT-1
WFT-1
49 SF
TOILET
3C-104
WFT-1
PT-2
WFT-1
WFT-1
WFT-1
WFT-4
RB-1
WFT-4
WFT-4
3 SF
SINK ALCOVE
3C-134B
ANTE
ROOM
3D-133B3D-133B
N/A
RB-1
WFT-5,6
N/A
WFT-5,6
P-1
RB-1
P-1 P-1
P-1
WFT-5,6
RB-1
WFT-5,6
WFT-6
WFT-6
W F
T -8
W F
T -8
W F
T -8
W F
T -8
WFT-8
WFT-8
W F
T -8
W F
T -8
W F
T -8
W F
T -8
W F
T -8
W F
T -8
WFT-8
WFT-8
W F
T -8
W F
T -8
W F
T -8
W F
T -8
W F
T -4
3' -0
W
F T
-3
WFT-3
WFT-4
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(520) 481-8548
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
As indicated
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
B e d W in g .A
R C
H .B
.L
.r v t
/1
/2
:2
:0
A
M
09/12/2022 M.PERKINS K.MACAULAY
618-22-102
1391 - IN101
INTERIOR FINISH PLAN - THIRD FLOOR 3D
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING100% CONSTRUCTION
DOCUMENTS
1/8" = 1'-0" F5
INTERIOR FINISH PLAN - THIRD FLOOR 3D - FLOOR FINISHES
INTERIOR SHEET NOTES
A. REFER TO IN001 FOR INTERIOR FINISH GENERAL NOTES
B. REFER TO SPECIFICATIONS FOR MATERIAL AND INSTALLATION REQUIREMENTS.
C. REFER TO IN601 FOR FINISH LEGEND AND ROOM FINISH SCHEDULE.
D. REFER TO A-400 SERIES FOR CASEWORK FINISHES.
E. REFER TO IF SERIES FOR FURNITURE; FURNITURE IS SHOWN FOR REFERENCE
ONLY, ALL FURNITURE IS NIC.
F. REFER TO AW SERIES FOR ALL SIGNAGE.
G. REFER TO Q SERIES FOR EQUIPMENT INFORMATION.
H. PAINT ALL WALLS (P-1) UNO.
I. PAINT ALL EXPOSED SIDES OF INTERIOR CEILING SOFFITS AND GYPSUM WALL
BOARD CEILINGS (P-2) UNO.
J. PAINT ALL HOLLOW METAL DOORS AND HOLLOW METAL FRAMES IN CONTRACT
BOUNDARY (P-3) UNO.
K. PLANS HAVE BEEN SCREENED BACK FOR CLARITY, REFER TO ARCHITECTURE
SERIES FOR WALL CONSTRUCTION INFORMATION
1 NO WORK IN THIS AREA.
2 FURNITURE IS NOT IN CONTRACT; SHOWN FOR REFERENCE ONLY
3 EXISTING BUILDING EXPANSION JOINT AT FLOOR TO REMAIN.
PROTECT IN PLACE.
4 REFER TO SHEET A-404 FOR FLOOR PATTERN DIMENSIONS
5 REFER TO A400S FOR ENLARGED PATIENT ROOM TYPICAL FINISH
PLANS
FINISH ABBREVIATIONS
ABBREVIATION FINISH TYPE - REFER TO IN601 FOR ADDITIONAL FINISH INFORMATION
AT ACOUSTICAL CEILING TILE
CC CUBICLE CURTAIN TRACK
CG CORNER GUARD
HR HAND RAIL
LVT LUXURY VINYL TILE
P PAINT
PL PLASTIC LAMINATE
PT PORCELAIN TILE
RB RESILIENT BASE
RSF RESILIENT SHEET VINYL
RSW ROLLER SHADES
RWC RIGID WALL COVERING
S SOLID SURFACE
TR TRIM
WD WOOD FINISH AT DOOR PANELS
WFT WALL FINISH TYPE
WSF WELDED SEAM SHEET
FLOOR MATERIAL TAKEOFF
Mark Material: Area
LVT-1 3960 SF
LVT-2 1794 SF
PT-1 98 SF
PT-3 1267 SF
PT-4 31 SF
RSF-1 5142 SF
WSF-1 303 SF
12595 SF
KEYNOTES-
1/8" = 1'-0" F1
INTERIOR FINISH PLAN - THIRD FLOOR 3D - WALL FINISHES
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR.