This document provides details for a federal contract opportunity with the Department of Veterans Affairs to renovate a private patient bed ward. The solicitation number is 36C26323R0023 and seeks to award a contract for project Z1DA--618-22-102 to renovate a private patient bed ward (3D) at Veterans Integrated Service Network 23. The description specifies that the opportunity involves renovating a private patient bed ward. No further information is included regarding response dates, award dates, pricing terms, set asides, or incumbent contractors. The attached file appears to contain technical drawings related to the renovation project requirements.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TYPE D
A. IMPLEMENT INFECTION CONTROL RISK ASSESSMENT (ICRA)
PROCEDURES AS PER THE ICRA PLAN AND AS DIRECTED BY THE
CONTRACTING OFFICER REPRESENTATIVE (COR).
B. COORDINATE ALL DEMOLITION/ CONSTRUCTION DEBRIS PATH OF
TRAVEL AND INTERIM LIFE SAFETY MEASURES (ILSM) WITH THE COR.
ALL INTERIOR DOORS THAT LEAD TO THE CONSTRUCTION SITE
SHALL BE POSTED AS PER THE ISLM PLAN.
C. OBTAIN INFECTION CONTROL PERMIT PRIOR TO BEGINNING WORK.
D. THE ONE HOUR FIRE RATED CONSTRUCTION BARRIERS SHALL BE
CONSTRUCTED PRIOR TO BEGINNING OTHER WORK.
E. CONSTRUCT ANTEROOM AT ENTRANCES TO CONSTRUCTION AREAS
AND REQUIRE ALL CONSTRUCTION PERSONNEL TO PASS THROUGH
THIS ROOM TO BE VACUUMED WITH HEPA VACUUM CLEANER PRIOR
TO LEAVING THE SITE.
F. FIRE PROTECTION SYSTEMS SHALL REMAIN FUNCTIONAL FOR
OCCUPIED AREAS ON THE FLOOR.
G. PROVIDE FIRE EXTINGUISHERS IN CONSTRUCTION AREAS; REVIEW
WITH COR AND VA SAFETY GROUP.
H. MAINTAIN EXIT LIGHTS IN CONSTRUCTION AREA.
I. MAINTAIN NEGATIVE AIR PRESSURE IN CONSTRUCTION AREA AT ALL
TIMES (24/7). WHETHER OCCUPIED OR NOT, THROUGHOUT
DURATION OF PROJECT USING HEPA EQUIPPED AIR FILTRATION
UNITS.
J. CONSTRUCTION AREA SHALL REMAIN ISOLATED FROM THE OTHER
AREAS OF THE MEDICAL CENTER; NO RETURN AIR OR EXHAUST
SHALL PASS INTO THE AREAS OUTSIDE THE CONSTRUCTION AREA.
ISOLATE HVAC SYSTEM WITHIN CONSTRUCTION AREA TO PREVENT
CONTAMINATION OF EXISTING DUCT SYSTEM.
K. PROVIDE SIGNS ON DOORS INTO THE CONSTRUCTION AREA THAT
READS: "CONSTRUCTION AREA-DO NOT ENTER".
L. TACKY MATS SHALL BE PLACED AT ALL DOORS INTO THE
CONSTRUCTION AREA AND SHALL BE MONITORED TO MAKE SURE
THEY REMAIN EFFECTIVE.
M. MAINTAIN A CLEAN AND ORDERLY CONSTRUCTION AREA. ALL
DEBRIS REMOVAL SHALL BE IN COVERED CARTS AND/OR
CONTAINERS.
N. SEAL ALL HOLES, PUNCTURES, AND PENETRATIONS FROM PIPES AND
CONDUITS APPROPRIATELY AND IMMEDIATELY TO MAINTAIN DUST
PROTECTION AND NEGATIVE AIR PRESSURE.
O. AFTER COMPLETION OF WORK: VACUUM CONSTRUCTION AREA WITH
HEPA FILTERED VACUUMS, WET MOP WITH DISINFECTANT, REMOVE
CONSTRUCTION BARRIERS (UPON APPROVAL). PATCH OR REPAIR
ANY DAMAGE FROM CONSTRUCTION BARRIER REMOVAL AND
REMOVE ISOLATION OF HVAC SYSTEM.
P. CONSTRUCTION BARRIERS SHALL NOT BE REMOVE UNTIL PROJECT
IS COMPLETED AND INSPECTED BY VA SAFETY PERSONNEL,
INFECTION CONTROL GROUP, AND COR.
ICRA NOTES:
INFECTION CONTROL RISK
ASSESSMENT:
STEP 1: TYPE D
IDENTIFY THE TYPE OF CONSTRUCTION PROJECT
ACTIVITY (TYPE A–D)
TYPE A: INSPECTION AND NONINVASIVE ACTIVITIES.
TYPE B: SMALL-SCALE, SHORT-DURATION ACTIVITIES
THAT CREATE MINIMAL DUST.
TYPE C: WORK THAT GENERATES A MODERATE TO
HIGH LEVEL OF DUST OR REQUIRES DEMOLITION OR
REMOVAL OF ANY FIXED BUILDING COMPONENTS OR
ASSEMBLIES.
TYPE D: MAJOR DEMOLITION AND CONSTRUCTION
PROJECTS.
STEP 2: HIGH RISK
IDENTIFY THE PATIENT RISK GROUPS THAT WILL BE
AFFECTED.
IF MORE THAN ONE RISK GROUP WILL BE AFFECTED,
SELECT THE HIGHER RISK GROUP.
STEP 3: CLASS IV
MATCH THE PATIENT RISK GROUP (LOW, MEDIUM,
HIGH, HIGHEST) WITH THE PLANNED CONSTRUCTION
PROJECT TYPE (A, B, C, D) ON THE FOLLOWING MATRIX,
TO FIND THE CLASS OF PRECAUTIONS (I, II, III OR IV) OR
LEVEL OF INFECTION CONTROL ACTIVITIES REQUIRED.
STEP 4: IDENTIFY THE AREAS SURROUNDING THE PROJECT
AREA, ASSESSING POTENTIAL IMPACT.
BELOW ABOVE NORTH SOUTH EAST WEST
_______________________RISK GROUP_____________________
LOW LOW N/A N/A N/A N/A
STEP 5:
IDENTIFY SPECIFIC SITE OF ACTIVITY, FOR EXAMPLE, PATIENT
ROOMS, MEDICATION ROOM, AND SO ON.
STEP 6:
IDENTIFY ISSUES RELATED TO: VENTILATION, PLUMBING, AND
ELECTRICAL IN TERMS OF THE OCCURRENCE OF PROBABLE
OUTAGES.
STEP 7.
IDENTIFY CONTAINMENT MEASURES, USING PRIOR
ASSESSMENT. WHAT TYPES OF BARRIERS (FOR EXAMPLE,
SOLIDS WALLS)? WILL HEPA FILTRATION BE REQUIRED?
STEP 8.
CONSIDER POTENTIAL RISK OF WATER DAMAGE. IS THERE A
RISK DUE TO COMPROMISING STRUCTURAL INTEGRITY (FOR
EXAMPLE, WALL, CEILING, ROOF)?
NOTE: RENOVATION/CONSTRUCTION AREA SHALL BE
ISOLATED FROM THE OCCUPIED AREAS DURING
CONSTRUCTION AND SHALL BE NEGATIVE WITH RESPECT TO
SURROUNDING AREAS.
STEP 9.
WORK HOURS: CAN OR WILL THE WORK BE DONE DURING
NON-PATIENT-CARE HOURS?
STEP 10.
DO PLANS ALLOW FOR ADEQUATE NUMBER OF
ISOLATION/NEGATIVE AIRFLOW ROOMS?
STEP 11.
DO THE PLANS ALLOW FOR THE REQUIRED NUMBER AND TYPE
OF HAND-WASHING SINKS?
STEP 12.
DOES THE INFECTION PREVENTION AND CONTROL STAFF
AGREE WITH THE MINIMUM NUMBER OF SINKS FOR THIS
PROJECT? (VERIFY AGAINST FACILITY GUIDELINES INSTITUTE
(FGI) DESIGN AND CONSTRUCTION GUIDELINES FOR TYPES
AND AREA.)
STEP 13.
DOES THE INFECTION PREVENTION AND CONTROL STAFF
AGREE WITH THE PLANS RELATIVE TO CLEAN AND SOILED
UTILITY ROOMS?
STEP 14.
PLAN TO DISCUSS THE FOLLOWING CONTAINMENT ISSUES
WITH THE PROJECT TEAM, FOR EXAMPLE, TRAFFIC FLOW,
HOUSEKEEPING, DEBRIS REMOVAL (HOW AND WHEN).
C
LA
S S
IV
DURING CONSTRUCTION
PROJECT
UPON COMPLETION OF
PROJECT
1. Remove or isolate HVAC system in area where work is being done, to prevent contamination of duct system.
2. Complete all critical barriers— i.e., drywall, plywood, plastic—to seal area from non-work area before construction begins. Or, implement control cube method with HEPA-fiItered vacuum for vacuuming prior to exit.
3. Maintain negative air pressure within worksite utilizing HEPA-equipped air filtration units.
4. Contain construction waste in tightly covered containers before transport.
5. Cover transport receptacles or carts. Tape down covering unless cart has a solid lid.
1. Do not remove barriers from work area until completed project is inspected by the owner’s Safety Department and Infection Control Department and thoroughly cleaned by the owner’s Environmental Services Department.
2. Remove barrier materials carefully to minimize spreading of dirt and debris associated with construction.
3. Vacuum work area with HEPA-filtered vacuum.
4. Wet mop area with disinfectant.
5. Upon completion, restore HVAC system where work was performed.
Construction Project Type
Patient Risk Group
LOW Risk Group MEDIUM Risk Group
HIGH Risk Group
HIGHEST Risk Group
I II II III/IV
I II III IV
I II III/IV IV
II III/IV III/IV IV
TYPE A TYPE B TYPE C TYPE D
WEEKLY CHANGED OR MORE
AS NEEDED PRE-FILTER
FLEX DUCT
MONTHLY CHANGED HEPA FILTER
HEPA NEGATIVE AIR UNIT
PROVIDE STICKY MATS (CHANGED END OF
EVERY SHIFT OR MORE IF NECESSARY TO
MAINTAIN CLEANLINESS).
STATIC PRESSURE WATER GAUGE INDICATOR
SHALL -0.03" W.G. MINIMUM TO MAINTAIN NEGATIVE
PRESSURE IN CONSTRUCTION AREA (VERIFY DAILY). IF
NOT VERIFY ALL OPENING SUCH AS DOOR ARE CLOSED
AND/OR CHANGE NEGATIVE AIR PRE-FILTER.
SUPPLY DUCTS EITHER
KEEP RUNNING OR
COVER WHEN NOT
RUNNING TO KEEP
DUST OUT.
A
V
O
TAPE ALL WALL, FLOOR, AND CEILING
SERVICES, TO PROTECT AGAINST
CONTAMINATION
E
FIRE EXTINGUISHER ON
PORTABLE FLOOR BRACKET
(SHALL REQUIRE MORE THAN
ONE.)
E4
GI201
PUBLIC AREA
CONSTRUCTION AREA
ANTE
ROOM
4' -0
M
IN
IM
U M
S E
E
F L O
O R
P
L A
N
TEMPORARY WALL
FLOOR LINE
CEILING SYSTEM AS
SCHEDULED
EXISTING STRUCTURE
FIRE RATED PLASTIC TO
PREVENT DUST INSTALL
PRIOR TO CONSTRUCTION
F
IN
IS
H E
D F
LO
O
R T
O U
N D
E R
S
ID
E O
F S
T R
U C
T U
R E
V E
R
IF
Y F
LO
O
R T
O F
LO
O
R H
E
IG
H T
RENOVATED SPRINKLER
SYSTEM
HJKLM
PROVIDE ICRA BARRIERS TO
CREATE ANTE-ROOM OUTSIDE OF
CONSTRUCTION ENTRY
PROVIDE ICRA BARRIERS TO
CREATE ANTE-ROOM OUTSIDE OF
CONSTRUCTION ENTRY - THIS SIDE
FOR EMERGENCY EGRESS ONLY
D1
D2
D3
PATH OF TRAVEL FOR MATERIAL /
WASTE TRANSPORTATION -
VERIFY WITH COR - SEE
CONSTRUCTION MATERIALS PLAN
THIS SHEET
5' -8
213 SF
PATIENT 9
3D-109
79 SF
RR 9
3D-109A
69 SF
RR 8
3D-108A
256 SF
PATIENT 8
3D-108
285 SF
PATIENT 7
3D-107
69 SF
RR 7
3D-107A
297 SF
PATIENT 6
3D-106
72 SF
RR 6
3D-106A
289 SF
PATIENT 5
3D-105
72 SF
RR 5
3D-105A
300 SF
PATIENT 4
3D-104
69 SF
RR 4
3D-104A
298 SF
PATIENT 3
3D-103
70 SF
RR 3
3D-103A
69 SF
RR 2
3D-102A
296 SF
PATIENT 2
3D-102
299 SF
BARIATRIC 1
3D-101
90 SF
RR 1
3D-101A
269 SF
PATIENT 18
3D-133
78 SF
RR 18
3D-133A
68 SF
RR 17
3D-132A
268 SF
SAFER PATIENT 17
3D-132
299 SF
STAFF WORK
3D-136
245 SF
MSA'S
3D-100
190 SF
CLEAN LINENS
3D-138
98 SF
ASST. NURSE MNGR
3D-110
93 SF
NURSE MNGR OFFICE
3D-111
127 SF
MED ROOM
3D-112
106 SF
NUTRITION
3D-135
292 SF
SAFER PATIENT 16
3D-131
67 SF
RR 16
3D-131A
67 SF
RR 15
3D-129A
252 SF
PATIENT 15
3D-129
280 SF
PATIENT 14
3D-128
71 SF
RR 14
3D-128A
71 SF
RR 13
3D-126A
102 SF
PHARM OFFICE
3D-120
108 SF
SOILED UTILITY
3D-134
49 SF
STAFF TOILET
3D-117
131 SF
SPS STORAGE
3D-114
315 SF
EQUIPMENT ROOM
3D-115 16 SF
EQUIP. ALCOVE
3D-140
245 SF
PATIENT 13
3D-126
260 SF
PATIENT 12
3D-12567 SF
RR 12
3D-125A
67 SF
RR 11
3D-123A
61 SF
HAC
3D-119
259 SF
STAFF BREAK ROOM
3D-116
238 SF
PATIENT 11
3D-123
206 SF
PATIENT 10
3D-121
74 SF
RR 10
3D-121A
54 SF
ANTE ROOM
3D-133B
74 SF
CLEAN UTILITY
3D-113
30 SF
OXYGEN STOR.
3D-118
262 SF
CIRCULATION
C3-18
55 SF
ANTE ROOM
3D-101B
186 SF
CORRIDOR
C3-27
49 SF
TOILET
3C-104
49 SF
TOILET
3C-105
RE-FINISH ONLY, NO
DESTRUCTIVE DEMOLITION
TAKING PLACE
CONSTRUCT NEW
CORRIDOR WALLS
AS ICRA BARRIERS
PRIOR TO COMMENCEMENT
OF REST OF CONSTRUCTION.
CONSTRUCT NEW
CORRIDOR WALLS
AS ICRA BARRIERS
PRIOR TO COMMENCEMENT
OF REST OF CONSTRUCTION.
4' -0
PROVIDE ANTE-ROOM FOR
MECHANICAL ROOM AND TELECOM
ROOM SCOPE OF WORK
ELEVATORS
ELE
VA
TO
R S
FREIGHT
ELEVATOR
ELEVATORS
ELEVATORS
ELEVATORS
PATH OF TRAVEL FOR MATERIAL / WASTE
TRANSPORTATION - VERIFY WITH COR
PROJECT SCOPE AREA
on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(520) 481-8548
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
As indicated
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
B e d W in g .A
R C
H .B
.L
.r v t
/1
/2
:5 :4
P
M
09/12/2022 M.PERKINS C.LOWERY
618-22-102
1391 - GI201
INFECTION CONTROL PLAN & INTERIM LIFE
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING100% CONSTRUCTION
DOCUMENTS
1/4" = 1'-0" F4
TYPICAL CONSTRUCTION LAYOUT- CLASS IV
1/2" = 1'-0" E4
CROSS SECTION A'-A'- CLASS IV
NTS
F1
TYPICAL ICRA PRODUCTS
1/8" = 1'-0"
F6
ICRA PLAN
1" = 60'-0" C3
CONSTRUCTION MATERIALS PLAN
DEDUCTIVE ALTERNATES
D1
DEDUCTIVE ALTERNATE #1: PROVIDE STORAGE ROOM IN LIEU OF PATIENT
ROOMS 10 AND 11 (3D-321/A & 3D-323/A). REMOVE SCOPE OF WORK
ASSOCIATED WITH NEW HEADWALL, PLUMBING, SPECIALTY EQUIPMENT.
D2
D3
DEDUCTIVE ALTERNATE #2: PROVIDE STORAGE ROOM IN LIEU OF PATIENT
ROOMS 12 AND 13 (3D-325/A & 3D-326/A). REMOVE SCOPE OF WORK
ASSOCIATED WITH NEW HEADWALL, PLUMBING, SPECIALTY EQUIPMENT.
DEDUCTIVE ALTERNATE #3: PROVIDE STORAGE ROOM IN LIEU OF PATIENT
ROOMS 14, 15, 16, AND 17 (3D-328/A, 3D-329/A, 3D-331/A & 3D-332/A).
REMOVE SCOPE OF WORK ASSOCIATED WITH NEW HEADWALL, PLUMBING,
SPECIALTY EQUIPMENT.
NOTE: DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE TAKEN IN
SEQUENTIAL ORDER.
NOTE: PROJECT WING WILL NOT
BE OCCUPIED DURING CONSTRUCTION.
CONTRACTOR TO UTILIZE SPACE IN
WING FOR TEMPORARY MATERIAL
STORAGE AS NEEDED DURING
CONSTRUCTION
S S
ARCHITECTURAL SYMBOLS
SHEET NUMBER
A-100 Sheet Number
Discipline Code
A-1 1/8" = 1'-0"
View Name
VIEW TITLE
Drawing Scale
Drawing Number
1/8" = 1'-0"
View NameA-1 A101R101
VIEW TITLE WITH REFERENCES
Drawing Scale
Sheet Number
Drawing Number
Reference Sheet Number
EXTERIOR ELEVATIONS
INTERIOR ELEVATIONS
A-200
A1 Position on Sheet
Sheet Number
Position on Sheet
Sheet Number
A1
A2B2
B1
A-350
MATCH LINES
MATCHLINE
SEE: A1/A-101B
Sheet Number
Position on Sheet
AREA REFERENCE
A
SEE: (X/X-XXX)
Reference to Area
View Reference for Additional Information
BUILDING SECTION
Position on Sheet
Sheet Number
SIM
X
X-XXX
SIM
X
X-XXX
WALL SECTION
Position on Sheet
Sheet Number
X
X-XXX
SIM
DETAIL - SECTION
SIM
X
X-XXX
Position on Sheet
Sheet Number
DETAIL - PLAN/RCP
SIM
X
X-XXX
Position on Sheet
Sheet Number
DRAWING REVISIONS
Revision Number
NORTH ARROW
True North
PLAN
NORTH Plan North
0 4'-0" 8'-0" 16'-0"
IF THIS IS NOT A 42"x30" SHEET IT IS A
REDUCED SIZE PLOT, USE GRAPHIC
SCALE ACCORDINGLY.
GRAPHIC SCALE
COLUMN GRID LINES
Column Grid Line (New)
Column Grid Line (Existing)
1 2
A
B
LEVEL DATUM
LEVEL XX
0' - 0"
Level Name
Level Elevation
SPOT ELEVATION
0'-0"
Spot Elevation
ROOM TAG
ROOM
NAME
ABC123
150 SF
Room Name
Room Number
CEILING TAG
CEILING HEIGHT
1' - 0"
Ceiling Type
Ceiling Height
DOOR NUMBER TAG
New Door Door Number Tag
1A
Existing Door Door Number Tag
1A101
WINDOW TAG
Interior Window Tag
X X
X X
Exterior Window Tag
CURTAIN WALL TAG
XX
Interior Curtain Wall Tag
Exterior Curtain Wall Tag
XX
AD100
Room Code Room Area Or Volume
1T
CURTAIN PANEL TAG
Interior Curtain Wall Tag
WALL TYPE TAG
≠ A# B
C
V V Item - VA Supplied & Installed
V C ITEM -
VA Supplied & Contractor Installed
C C Item - Contractor Supplied & Installed
FFE Tag (By JSN)A1000
TM FFE Tag Furnished By VA Equipment Vendor
? KEYNOTE
1"
R 0"
90°
DIMENSION TO FACE OF
FINISH, FACE OF CONCRETE,
COLUMN CENTERLINE, OR AS
NOTED.
DIMENSIONS
1"
Symbol Indicates No Sound
Attenuation
Partition Type
CMU/Stud Width
Partition Modifier Partition Modifier II
KEYNOTE TAG
SEE A-720 STANDARD PARTITION TYPES
Contract Limit line Style
Not In Contract Area
CONTRACT LIMIT GRAPHIC
LINE STYLES
Centerline
Demolished
Temporary
Hidden
Overhead
Beyond
FURNITURE, FIXTURE, & EQUIPMENT
8'-6"1
Name
Room Name Room Number
Existing Finish Key
Ceiling Height
TM Toilet Accessory Tag. See A-730
Matchline
Deduct Alternate
RECESSED LUMINAIRE (24x24)
SMOKE DETECTOR
SPEAKER
EXISTING HVAC SUPPLY DIFFUSER
HVAC RETURN DIFFUSER
EXIT LIGHT
HEAT DETECTOR
HVAC EXHAUST DIFFUSER
LINEAR UPLIGHT LUMINAIRE, WALL
MOUNTED
RECESSED ROUND DOWNLIGHT
LUMINAIRE
RECESSED LUMINAIRE (24x48)
ACOUSTICAL TILE CEILING (24x24)
ACOUSTICAL TILE CEILING (24x48)
GYPSUM BOARD CEILING
REFLECTED CEILING SYMBOLS
ACCESS PANEL
HVAC SUPPLY DIFFUSER
EXISTING HVAC RETURN DIFFUSER
SPRINKLER
UNDERCABINET TASK LIGHT
EXISTING DEMO
MATERIALS LEGEND
CONCRETE (SECTION)
GRANULAR FILL
CONCRETE MASONRY UNITS
BRICK
RIGID INSULATION (SECTION)
ACOUSTIC/THERMAL INSULATION (SECTION)
STEEL (SECTION)
ALUMINUM (SECTION)
WOOD FINISH (SECTION)
LUMBER FINISH (SECTION)
EARTHWORK (SECTION)
STUD WALL (PLAN & SECTION)
EXISTING WALL TO REMAIN (PLAN & SECTION)
DEMOLISHED WALL (PLAN &
SECTION)
EXISTING TO REMAIN
EXISTING TO BE REMOVED
EXISTING TO REMAIN
NEW CONSTRUCTION
DOOR NUMBER
SYMBOL AND MINIMUM
CLEARANCES
18" MIN.
12" MIN.
6" MIN.
1A
WALL LEGEND
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(520) 481-8548
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
As indicated
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
B e d W in g .A
R C
H .B
.L
.r v t
/1
/2
:0 :4
P
M
09/12/2022 M. Perkins K.MACAULAY
618-22-102
1391 - A-001
SYMBOLS, & GENERAL NOTES
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING100% CONSTRUCTION
DOCUMENTS
ABBREVIATIONS
° DEGREE
± PLUS/MINUS
⌀ DIAMETER
≈ ALMOST EQUAL
∠ ANGLE
℄ CENTER LINE
Δ DELTA, DEFLECTION
ϕ ELECTRICAL PHASE
≠ NOT EQUAL
Ω OHM, OMEGA
BOUNDARY LINE
FLOW LINE
≡ IDENTITY
INITIAL LENGTH
MOMENT LINE
PROPERTY LINE, PLATE
½ ONE HALF FRACTION
¼ ONE QUARTER FRACTION
¾ THREE QUARTERS FRACTION
> GREATER THAN
≥ GREATER THAN OR EQUAL TO
< LESS THAN
≤ LESS THAN OR EQUAL TO
ABCDEFGHIJKMNOPQRSTUVWXYZ 1234567890
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAMA AMERICAN ARCHITECTURAL
MANUFACTURERS ASSOCIATION
AB ANCHOR BOLT, AUGER BORING
ABA ARCHITECTURAL BARRIERS ACT
ABC AGGREGATE BASE COURSE
ABS AIR BREAK SWITCH
AC ASBESTOS CEMENT OR ASPHALTIC
CONCRETE
ACB AIR CIRCUIT BREAKER
ACI AMERICAN CONCRETE INSTITUTE
ACS DR ACCESS DOOR
ACS FLR ACCESS FLOOR
ACS PNL ACCESS PANEL
ACSR ALUMINUM CONDUCTOR STEEL
REINFORCED
ACST ACOUSTIC
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADC AUTOMATIC DOOR CLOSER
ADDL ADDITIONAL
ADDN ADDITION
ADH ADHESIVE
ADJ ADJACENT, ADJOINING, OR
ADJUSTABLE
ADMIN ADMINISTRATION
ADB AUTOMATIC DOOR BOTTOM
ADO AUTOMATIC DOOR OPERATOR
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGA AMERICAN GAS ASSOCIATION
AGC ASSOCIATED GENERAL CONTRACTORS
AGGR AGGREGATE
AHJ AUTHORITY HAVING JURISDICTION
AHR ANCHOR
AHU AIR HANDLING UNIT
AIA AMERICAN INSTITUTE OF ARCHITECTS
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
AL ALUMINUM
ALT ALTERNATE
ALT NO ALTERNATE NUMBER
ALUM ALUMINUM
AM ACOUSTIC MATERIAL
AMP AMPERE
AMT AMOUNT
ANOD ANODIZE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
ANT ANTENNA
AP ACCESS PANEL, APPROX.,
APPROXIMATE
APA AMERICAN PLYWOOD ASSOCIATION
APPD APPROVED
APPROX APPROXIMATE
APT APARTMENT
AR AS REQUIRED
ARR ARRESTOR
ARCH ARCHITECT, ARCHITECTURAL
ASB ASBESTOS
ASI ARCHITECT'S SUPPLEMENTAL
INSTRUCTION
ASKLR AUTOMATIC SPRINKLER
ASPH ASPHALT
ASSN ASSOCIATION
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
ATCH ATTACHMENT
ATM AUTOMATIC TELLER MACHINE
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AVE AVENUE
AVG AVERAGE
AW ACID WASTE
AWI ARCHITECTURAL WOODWORKING
INSTITUTE
AWPA AMERICAN WOOD PRESERVERS'
ASSOCIATION
AWS AMERICAN WELDING SOCIETY
AWT ACOUSTICAL WALL TREATMENT
B BASELINE, BOTTOM
B LABEL CLASS B DOOR
B PL BASE PLATE
BALC BALCONY
BAT BATTEN
BB BULLETIN BOARD
BD BOARD
BD FT BOARD FEET (FOOT)
BEJ BRICK EXPANSION JOINT
BEV BEVEL
BHMA BUILDER'S HARDWARE
MANUFACTURER'S ASSOCIATION
BI FLD DR BIFOLDING DOORS
BITUM BITUMINOUS
BKG BACKING
BLD BUILD
BLDG BUILDING
BLKT BLANKET
BLVD BOULEVARD
BM BEAM OR BENCHMARK
BO BOARD
BOT BOTTOM
BR BEDROOM, BOTTOM REGISTER
BRCG BRACING
BRDG BRIDGING
BRDG JST BRIDGING JOIST
BRG BEARING
BRG PL BEARING PLATE
BRKT BRACKET
BRZ BRONZE
BSMT BASEMENT
BTWN BETWEEN
BU BUSHEL
BUR BUILT-UP ROOFING
C CELSIUS, CHANNEL
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
C TO C CENTER TO CENTER
CAB CABINET
CAC CEILING ATTENUATION CLASS
CB CATCH BASIN, CORNER BEAD, CIRCUIT
BREAKER
CBB CEMENTITIOUS (BACKER) BOARD
CC CUBIC CENTIMETER, CONTRACTOR
SUPPLIED & INSTALLED
CCTV CLOSED CIRCUIT TELEVISION
CCW COUNTERCLOCKWISE
CD CONSTRUCTION DOCUMENTS,
CONTRACT DOCUMENTS, CEILING
DIFFUSER
CEM CEMENT
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED /
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER
INSTALLED
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CENTER OF GRAVITY, CORNER GUARD
C&G CURB AND GUTTER
CGSFU CERAMIC GLAZED STRUCTURAL
FACING UNITS
CH CHILLER
CH BD CHALKBOARD
CHEM CHEMICAL
CHFR CHAMFER
CHK CHECK
CI CAST IRON
CIP CAST-IN-PLACE
CIR CIRCLE
CIRC CIRCULAR
CJ CONSTRUCTION JOINT OR CONTROL
JOINT
CL CENTER LINE
CLDG CLADDING
CLG CEILING
CLG HT CEILING HEIGHT
CLR CLEAR
CM² SQUARE CENTIMETER
CM³ CUBIC CENTIMETER
CM CONSTRUCTION MANAGEMENT
CMP CORRUGATED METAL PIPE
CMPA CORRUGATED METAL PIPE ARCH
CMU CONCRETE MASONRY UNIT
CND CONDUIT
CNDS CONDENSATE
CNR CORNER
CNTR COUNTER
CO CARBON MONOXIDE, CERTIFICATE OF
OCCUPANCY, CLEANOUT, OR COMPANY
CO2 CARBON DIOXIDE
CODP CLEANOUT W/ DECK PLUG
COL COLUMN
COM COMMON
COMB COMBINATION, COMBINED
COMM COMMUNICATION
COMP COMPONENT
CONC CONCRETE
CONC FLR CONCRETE FLOOR
COND CONDENSER OR CONDITION
CONF CONFERENCE
CONN CONNECT, CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUE
CONTR CONTRACTOR, CONTRACTION
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CORR CORRIDOR
CP NON-REINFORCED CONCRETE PIPE
CPM CRITICAL PATH METHOD
CPRS COMPRESSIBLE
CPT CARPET
CR CHAIR, CRASH RAIL
CRS COLD ROLLED STEEL
CRSI CONCRETE REINFORCING STEEL
INSTITUTE
CS CONCRETE SEALER/SURFACE
CSB CONCRETE SPLASH BLOCK
CSG CASING
CSI CONSTRUCTION SPECIFICATIONS
INSTITUTE
CSK COUNTER SUNK
CSMT CASEMENT
CSWK CASEWORK
CT CERAMIC TILE, CURRENT
TRANSFORMER, COOLING TOWER
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTG COATING
CTR CENTER, CONTOUR, COOLING TOWER
RETURN
CTRL CONTROL
CTV CABLE TELEVISION
CU COPPER C
CUH CABINET UNIT HEATER
CU FT CUBIC FEET
CU IN CUBIC INCH
CU YD CUBIC YARD
CURT CURTAIN
CW COLD WATER
CWB CAPILLARY WATER BARRIER
CWR COLD WATER RETURN
CYL CYLINDER
CYL L CYLINDER LOCK
D DEPTH OR PENNY (NAIL)
D LABEL CLASS D DOOR
DAT DATUM
DB DECIBEL, DRY BUILT, DIRECT BURIAL
DBL DOUBLE
DBL GLZ DOUBLE GLAZE
DC DIRECT CURRENT
DD DIVERSION DIKE
DEG, ° DEGREE
DEL DELETE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DI DUCTILE IRON
DIA, DIAMETER
DIAG DIAGONAL DIAGRAM
DIAG DIAGRAM DIAGONAL
DIFF DIFFERENCE OR DIFFUSER
DIM DIMENSION
DIR DIRECTION
DISP DISPENSER
DIST DISTANCE
DIV DIVIDE OR DIVISION
DL DEAD LOAD
DMPR DAMPER
DN DOWN
DP DISTRIBUTION
DOC DOCUMENT
DOUG FIR DOUGLAS FIR
DOZ DOZEN
DR DOOR, DRAIN, DRESSING ROOM, OR
DRIVE
DR CL DOOR CLOSER
DR FR DOOR FRAME
DR OPNG DOOR OPENING
DS DOWNSPOUT, STORM DRAINAGE
STRUCTURE
DSGN DESIGN
DW DISHWASHER, DOMESTIC WATER
DWD DRINKING WATER DISPENSER
DWG DRAWING
DWTR DUMBWAITER
E EAST
E LABEL CLASS E DOOR
EA EACH
EAM EXCEPT AS NOTED
EAT ENTERING AIR TEMPERATURE
EF EACH FACE, EXHAUST FAN
EFF EFFICIENCY
EFS EXTERIOR FINISH SYSTEM
EG EXHAUST GRILLE
EIFS EXTERIOR INSULATION AND FINISH
SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELAST ELASTOMERIC
ELEC ELECTRIC
ELEC DR OP ELECTRIC DOOR OPENER
ELEV ELEVATOR
EMER EMERGENCY
EMER SHR EMERGENCY SHOWER
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
ENGR ENGINEER
ENVIR ENVIRONMENT
E/P EDGE OF PAVEMEMNT
EPA ENVIRONMENTAL PROTECTION
AGENCY
EPDM ETHYLENE PROPYLENE DIENE
MONOMER
EPO EMERGENCY POWER OFF
EPS EXPANDED POLYSTYRENE BOARD
(INSULATION)
EQ EQUAL
EQL SP EQUALLY SPACED
EQUIP EQUIPMENT
EQUIV EQUIVALENT
ER EXHAUST REGISTER
ERD EXISTING ROOF DRAIN
ESC ESCAPE OR ESCUTCHEON
ESCAL ESCALATOR
ESMT EASEMENT
ESP ESPECIALLY
EST ESTIMATE
ETC AND SO FORTH OR ET CETERA
EVAP EVAPORATIVE
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWS EYE WASH STATION
EXH EXHAUST
EXIST EXISTING
EXP EXPANSION OR EXPOSED
EXP BT EXPANSION BOLT
EXP JT EXPANSION JOINT
EXST GR EXISTING GRADE
EXT EXTERIOR, EXTERNAL, OR
EXTINGUISHER
EXT GR EXTERIOR GRADE
F FAHRENHEIT, FEMALE, FIRE, FUSE,
FILTER
FA FIRE ALARM
FAB FABRIC
FABX FIRE ALARM BOX
FAC FACTOR
FACIL FACILITY
FAS FASCIA
FAS BD FASCIA BOARD
FCO FLOOR CLEANOUT
FCTY FACTORY
FD FLOOR DRAIN, FIRE DAMPER
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF&E, FFE FURNITURE, FIXTURE, AND EQUIPMENT
FH FLAT HEAD, FLAT HEAD SCREWS, FIRE
HYDRANT
FHC FIRE HOSE CABINET
FHMS FLAT HEAD MACHINE SCREW
FHP FULL HEIGHT PARTITION
FHWS FLAT HEAD WOOD SCREW
FIG FIGURE
FIL FILLET
FIN FINISH
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIN WD FINISH WOOD
FIXT FIXTURE
FJ FELT JOINT
FL FLOORLINE, FLOOR, FLASHING, FLOW
LINE
FLASH FLASHING
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLR FLOOR
FLR FIN FLOOR FINISH
FLR SK FLOOR SINK
FLUOR FLUORESCENT
FLUOR FIX FLUORESCENT FIXTURE
FM FACTORY MUTUAL
FM-G FACTORY MUTUAL GLOBAL
FO FINISHED OPENING
FOC FACE OF CONCRETE OR FACE OF CURB
FOF FACE OF FINISH
FOM FACE OF MASONRY
4 WAY FOUR WAY
FOS FACE OF SLAB OR FACE OF STUD
FOUNT FOUNTAIN
FOW FACE OF WALL
FP FIRE PROTECTION OR FIREPROOF
FPH FROST PROOF HYDRANT
FPM FEET PER MINUTE
FPS FEET PER SECOND
FR FIRE RATING, FIRE RESISTANT, OR
FRAME
FR SNK FLUSHING RIM SINK
FREQ FREQUENCY
FRMG FRAMING
FRP FIBER REINFORCED POLYESTER OR
FIBERGLASS REINFORCED PLASTIC
FRZ FREEZER
FS FEDERAL SPECIFICATION, FULL SIZE
FSTNR FASTENER
FT FEET OR FOOT
FTG FOOTING
FURG FURRING
FURN FURNISH OR FURNITURE
FUT FUTURE
FW FIRE WATER
FWC FABRIC WALLCOVERING
G GROUND, GAS LINE, GRAM
GA GAGE OR GYPSUM ASSOCIATION
GAL GALLON, GALVANIZED
GALV GALVANIC OR GALVANIZED
GALV STL GALVANIZED STEEL
GB GRAB BAR
GC GENERAL CONTRACTOR, GLAZED
COATING
GD GUARD
GDR GUARD RAIL
GEN GENERAL OR GENERATOR
GFI GROUND FAULT INTERRUPT
GFMU GROUND FACE MASONRY UNIT
GFRC GLASS-FIBER-REINFORCED CONCRETE
GFRG GLASS-FIBER-REINFORCED GYPSUM
GFRP GLASS-FIBER-REINFORCED PLASTIC
GI GALVANIZED IRON
GL GLASS
GLZ-C GLAZED BLOCK-CMU
GLZ-T GLAZED BLOCK-CLAY TILE
GL BLK GLASS BLOCK
GLU LAM GLUED LAMINATED WOOD
GR GRADE
GR FL GROUND FLOOR
GRAN GRANITE
GRTG GRATING
GSB GYPSUM SHEATHING BOARD
GSM GALVANIZED SHEET METAL
GSU GLAZED STRUCTURAL UNIT
GT GROUT
GUAR GUARANTEE
GUT GUTTER
GW GROUND WATER
GWB GYPUSM WALL BOARD
GYP GYPSUM
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H HIGH, HEIGHT, HUMIDIFIER
H PLAM HIGH PRESSURE PLASTIC LAMINATE
HAC HOUSEKEEPING AIDS CLOSET
HAZ MAT HAZARDOUS MATERIALS
HB HOSE BIBB
HC HOLLOW CORE, HANDICAPPED
HCWD HOLLOW CORE WOOD DOOR
HD HARD DRAWN
HDBD HARDBOARD
HDNR HARDENER
HDO HIGH DENSITY OVERLAY
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE AIR
(FILTER)
HEX HEXAGON
HF HIGH FREQUENCY
HGR HANGER
HGSW HORN GAP SWITCH
HID HIGH INTENSITY DISCHARGE
HM HECTOMETER
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMDF HOLLOW METAL DOOR AND FRAME
HMF HOLLOW METAL FRAME
HNDRL HANDRAIL
HO HOLD OPEN
HORIZ HORIZONTAL
HOSP HOSPITAL
HP HIGH PRESSURE, HIGH POINT,
HORSEPOWER
HPS HIGH PRESSURE SODIUM
HQ HEADQUARTERS
HR HOUR
HS HEAT-STRENGTHENED (GLASS) OR
HIGH STRENGTH
HSE HOUSE
HSKPG HOUSEKEEPING
HST HOIST
HT HEIGHT
HVAC HEATING, VENTILATING, AND AIR
CONDITIONING
HVY HEAVY
HW HOT WATER, HEAD WALL
HYD HYDRANT
HYDR HYDRAULIC
HZ HERTZ
I INTERSTATE (HIGHWAY) OR MOMENT
OF INERTIA
IAQ INDOOR AIR QUALITY
IBC INTERNATIONAL BUILDING CODE
ID IDENTIFICATION, INSIDE DIAMETER, OR
INTERIOR DESIGN
ID NO IDENTIFICATION NUMBER
IE INVERT ELEVATION
ILLUM ILLUMINATION
IMC INTERMEDIATE METAL CONDUIT
INCL INCLUDED
IND INDEPENDENT OR INDUSTRIAL
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
INTERCOM INTERCOMMUNICATION
INTL INTERNATIONAL
INV INVERT
IP INLET PROTECTION
IRBF INDUSTRIAL RESIN BASE FLOORING
IRMA INVERTED ROOF MEMBRANE ASSEMBLY
IWH INSTANTANEOUS WATER HEATER
JAN JANITOR
J-BOX, JB JUNCTION BOX
JC JANITOR CLOSET
JCT JUNCTION
JT JOINT
JST JOIST
K KILO
KCP KEENE'S CEMENT PLASTER
KD KILN DRIED OR KNOCKED DOWN
KG KILOGRAM
KN KILONEWTON
KIT KITCHEN
KO KNOCKOUT
KPL KICKPLATE
KV KILOVOLT
KVA KILOVOLT-AMPERE
KW KILOWATT
L ANGLE, LOUVER, LENGTH, LENGTH OF
CURVE
LA LIGHTING ARRESTOR
LAB LABORATORY
LAD LADDER
LAM LAMINATE
LAM GL LAMINATED GLASS
LAU LAUNDRY
LAV LAVATORY
LBR LUMBER
LBS POUND
LC LEAD COVERED
LD BRG LOAD-BEARING
LDR LEADER
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LH LEFT HAND
LHR LEFT HAND REVERSE
LHR LEFT HAND REVERSE, LATENT HEAT
RATIO
LIB LIBRARY
LIN LINEAR
LINO LINOLEUM
LIQ LIQUID
LKR LOCKER
LKR RM LOCKER ROOM
LKWASH LOCKWASHER
LL LEAD LINED, LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LMST LIMESTONE
LNDSCP LANDSCAPE
LR LIVING ROOM
LRG LARGE
LRV LOUVERED ROOF VENT
LS LUMP SUM
L/S LITERS PER SECOND
LT LIGHT
LT GA LIGHT GAGE
LT WT LIGHTWEIGHT
LTG LIGHTING
LTNG LIGHTNING
LVC LENGTH OF VERTICAL CURVE
LVD LOUVERED
LVR LOUVER
LWC LIGHTWEIGHT CONCRETE
LWIC LIGHTWEIGHT INSULATING CONCRETE
LYR LAYER
M METER, MEGA
MACH MACHINE
MACH RM MACHINE ROOM
MAINT MAINTENANCE
MAN MANUAL
MAS MASONRY
MATL MATERIAL
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MB MACHINE BOLT
MCB METAL CORNER BEAD
MD METAL DECK
ME MECHANICAL ENGINEER
MEAS MEASURE
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MED MEDICAL, MEDIUM
MEK METHYL ETHYL KETONE
MEL MELAMINE
MEMB MEMBRANE
MEMO MEMORANDUM
MEZZ MEZZANINE
MF MILL FINISH
MFD MANUFACTURED
MFG MANUFACTURING
MFR MANUFACTURER
MFR REC MANUFACTURER'S RECOMMENDATION
MGT MANAGEMENT
MH MANHOLE
MIC MICROPHONE
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM MINUTE
MIN MINUTE MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MIT MITER
MKR MARKER
ML METAL LATH
MLDG MOLDING (MOULDING)
MLO MAIN LUG ONLY
MLWK MILLWORK
mm MILLIMETER
MMP MEMBRANE WATERPROOFING
MO MASONRY OPENING OR MOTOR
OPERATED
MOD MODEL, MODIFY OR MODULE
MOD BIT MODIFIED BITUMEN
MON MONITOR
MOPR MOP RACK
MP MEDIUM PRESSURE
MR MOISTURE RESISTANT
MS MACHINE SCREW OR MOP SINK
M/S METERS PER SECOND
MTD MOUNTED
MTG MOUNTING
MTL METAL
MULL MULLION
MW MICROWAVE
MWP MEMBRANE WATERPROOFING
N NORTH
NA NOT APPLICABLE
NAAMM NATIONAL ASSOCIATION OF
ARCHITECTURAL METAL
MANUFACTURERS
NAT NATURAL
NATL NATIONAL
NC NOISE CRITERIA, NON-CORROSIVE
NCOMBL NONCOMBUSTIBLE
NDC NOSE DOWN CURB
NE NORTHEAST
NEC NATIONAL ELECTRICAL CODE
NEG NEGATIVE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NEUT NEUTRAL
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NPS NOMINAL PIPE SIZE
NR NOISE REDUCTION
NRC NOISE REDUCTION COEFFICIENT
NRCA NATIONAL ROOFING CONTRACTORS
ASSOCIATION
NRP NON-REMOVABLE
NS NARROW STILE
NTS NOT TO SCALE
NUM NUMERAL
NW NORTHWEST
O/O OUT TO OUT
O OXYGEN
OA OUTSIDE AIR OR OVERALL
OC ON CENTER
OCB OIL CIRCUIT BREAKER
OCC OCCUPY
OCT OCTAGON
OD OUTSIDE DIAMETER OUTSIDE
DIMENSION
OD OUTSIDE DIMENSION OUTSIDE
DIAMETER
OF/CI OWNER FURNISHED/CONTRACTOR
INSTALLED
OFD OVERFLOW DRAIN
OFF OFFICE
OF/OI OWNER FURNISHED/OWNER INSTALLED
OH OVERHANG, OVERHEAD
OH DR OVERHEAD (COILING) DOOR
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPR OPERABLE
OPT OPTIONAL
OR OPERATING ROOM, OUTSIDE RADIUS
ORD ORDNANCE OR OVERFLOW ROOF
DRAIN
ORG ORGANIC
ORIG ORIGINAL
ORN ORNAMENTAL
OSD OPEN SITE DRAIN
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
OVHD OVERHEAD
OUT OUTLET
OZ OUNCE
P PIPE, POLE
Pa PASCALES
PA PUBLIC ADDRESS
PAR PARALLEL OR PARAPET
PARA PARAGRAPH
PART PARTIAL
PAT PATTERN
PB PUSHBUTTON, PULL BOX
PBD PARTICLEBOARD
PC PIECE, POLYCARBONATE, PORTLAND
CEMENT, PRECAST
PCA PORTLAND CEMENT ASSOCIATION
PCC PRECAST CONCRETE
PCCP CONCRETE PAVEMENT
PCD PAPER CUP DISPENSER
PCF POUNDS PER CUBIC FOOT
PCP PORTLAND CEMENT PLASTER
PED PEDESTAL
PEN PENETRATE
PEND PENDANT
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PGBD PEGBOARD
PHAR PHARMACY
PHOTO PHOTOGRAPH
PHS PHILLIPS HEAD SCREW
PI POINT OF INTERSECTION
PIV POST INDICATOR VALVE
PJF PREFORMED JOINT FILLER
PKG PACKAGE
PL PROPERTY LINE, PLATE
PL GL PLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER OR PLASTIC
PLAS CMU PLASTER COVERED CMU
PLBG PLUMBING
PLYWD PLYWOOD
PMTL PAINTED METAL
PNEU PNEUMATIC
PNL PANEL
PNT PAINT
PO POST OFFICE, PURCHASE ORDER
PO PURCHASE ORDER POST OFFICE
POLY POLYETHYLENE (PLASTIC)
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATE
PREFIN PREFINISH
PRELIM PRELIMINARY
PREP PREPARATION
PRESS PRESSURE
PREV PREVIOUS
PRIM PRIMARY
PRKG PARKING
PRMLD PREMOLDED
PROJ PROJECT
PROP PROPERTY
PRV PRESSURE RELIEF VALVE
PS PULL SWITCH
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT, PNEUMATIC TUBE, PRESSURE
TREATED, POINT OF TANGENT
PTD PAPER TOWEL DISPENSER
PTN PARTITION
PVC POLYVINYL CHLORIDE (PLASTIC), POINT
OF VERTICAL CURVE
PVG PAVING
PVI POINT OF VERTICAL INTERSECTION
PVT POINT OF VERTICAL TANGENT
PVMT PAVEMENT
PWR POWER
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QRY QUARRY
QT QUARRY TILE
QTB QUARRY TILE BASE
QTF QUARRY TILE FLOOR
QTR QUARTER
QTY QUANTITY
QUAD QUADRANT
QUAL QUALITY
R RADIUS, RISER, RUBBER, RETURN
RA RETURN AIR
RAD RADIATOR, RADIUS
RB RESILIENT BASE OR RUBBER BASE
RB HK ROBE HOOK
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REMOTE CONTROL
RCP REFLECTED CEILING PLAN,
REINFORCED CONCRETE PIPE
RCVR RECEIVER
RD ROAD OR ROOF DRAIN
REC RECESSED
RECD RECEIVED
RECPT RECEPTACLE
RECT RECTANGLE
RED REDUCING
REF REFERENCE OR REFRIGERATOR
REFR REFRACTORY, REFRIGERATION
REG REGISTER, REGULATOR
REINF REINFORCE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
RESIL T RESILIENT TILE
RET RETURN
REV REVISION
RF RADIO FREQUENCY, ROOF, RETURN
FAN
RFG ROOFING
RFI REQUEST FOR INFORMATION
RFP REQUEST FOR PROPOSAL
RGS RIGID GALVANIZED STEEL
RH RIGHT HAND
RHC REHEAT COIL
RHMS ROUND HEAD MACHINE SCREW
RHR RIGHT HAND REVERSE
RHWS ROUND HEAD WOOD SCREW
RI RUBBER INSULATED
RL ROOF LEADER
RLG RAILING
RM ROOM
RND ROUND
RO ROUGH OPENING
ROW RIGHT OF WAY
RPM REVOLUTIONS PER MINUTE
RS ROUGH SAWN
RT RIGHT
RV ROOF VENT
RVS REVERSE
RVT RESILIENT VINYL TILE
RWD REDWOOD
RWL RAIN WATER LEADER
S SECOND, SOUTH, SANITARY, SEWER,
STRUCTURE
SA SUPPLY AIR
SALV SALVAGE
SAMP SAMPLE
SAN SANITARY SEWER
SAT SUSPENDED ACOUSTICAL TILE
SATC SUSPENDED ACOUSTICAL TILE CEILING
SB SPLASH BLOCK
SBS STYRENE BUTADIEN STYRENE
SBSTR SUBSTRATE
SC SHADING COEFFICIENT OR SOLID CORE
SCH SCHOOL, SCHEDULE
SCHED SCHEDULE
SCHEM SCHEMATIC
SCP SCUPPER
SCRN SCREEN
SCT STRUCTURAL CLAY TILE
SCWD SOLID CORE WOOD DOOR
SD SHOP DRAWINGS, SMOKE DETECTOR,
OR SOAP DISPENSER;
SDG SIDING
SE SOUTHEAST
SECT SECTION
SEG SEGMENT
SEL SELECT
SEP SEPARATE
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SG SUPPLY GRILLE
SGD SLIDING GLASS DOOR
1PH SINGLE PHASE
SGL SINGLE
SH SHEET
SHR SHOWER
SHR HD SHOWER HEAD
SHRD SHOWER DRAIN
SHT SHEET
SHT MTL FL SHEET METAL (FLASHING)
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SJI STEEL JOIST INSTITUTE
SK SKETCH
SKCP SUSPENDED KEENE'S CEMENT
PLASTER
SKLT SKYLIGHT
SL SLOPE
SLD WDW HORIZONTAL SLIDING WINDOW
SLDG SLIDING
SLNT SEALANT
SM SHEET METAL
SMH SANITARY MODULE
SMK SMOKE
SND SANITARY NAPKIN DISPENSER
SND INS SOUND INSULATION
SNDU SANITARY NAPKIN DISPOSAL UNIT
SP STATIC PRESSURE, SINGLE POLE
SPC SUSPENDED PLASTER CEILING
SPDT SINGLE POLE DOUBLE THROW
SPEC SPECIFICATION
SPKLR SPRINKLER
SPKR SPEAKER
SPST SINGLE POLE SINGLE THROW
SPLY SUPPLY
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SR SUPPLY REGISTER
SS SANITARY SEWER OR SERVICE SINK
SST STAINLESS STEEL
ST STAIRS, STREET, SINGLE THROW
STA STATION
STC SOUND TRANSMISSION CLASS
STD STANDARD
STIF STIFFENER
STL STEEL
STL JST STEEL JOIST
STL LNTL STEEL LINTEL
STL PL STEEL PLATE
STL RF DK STEEL ROOF DECK
STL TB STEEL TUBE
STL TR STEEL TRUSS
STNLS STAINLESS
STOR STORAGE
STR STRINGERS
STRUCT STRUCTURAL
STRUCT STL STRUCTURAL STEEL
SUB SUBSTITUTE
SURF SURFACE
SUP SUPPORT
SUSP SUSPEND
SUSP CLG SUSPENDED CEILING
SV SHEET VINYL
SV B SHEET VINYL BASE
SW SWITCH, SIDE WALK
SWBD SWITCHBOARD
SWDR SWING DOOR
SWGR SWITCH GEAR
SYM SYMBOL
SYNTH SYNTHETIC
SYS SYSTEM
T TREAD, TILE, TOP, TANGENT
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
T&M TIME AND MATERIALS
TB THROUGH BOLT OR TOWEL BAR
TC TOP OF CURB
TCA TILE COUNCIL OF AMERICA
TCP TELEPHONE CONTROL PANEL
TEMPERATURE CONTROL PANEL;
TRAFFIC CONTROL PLAN
TD TOWEL DISPENSER
TECH TECHNICAL
TEL TELEPHONE
TEMP TEMPERATURE OR TEMPORARY
TER TERRAZZO
TERM TERMINAL
TH TOTAL HEAD (PUMPS)
THD THREAD
THERM THERMAL
THK THICKNESS
THRES THRESHOLD
THRSLD THRESHOLD
THRU THROUGH
THRUOUT THROUGHOUT
TK BD TACKBOARD
TMPD TEMPERED
TMPD GL TEMPERED GLASS
TN TRUE NORTH
TO TOP OF ___
TO FDN TOP OF FOUNDATION
TOB TOP OF BEAM
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOS TOP OF STEEL
TOW TOP OF WALL
TPD TOILET PAPER DISPENSER
TPH TOILET PAPER HOLDER
TR TOWEL RACK, TOP REGISTER
TRANS TRANSOM, TRANSITION
TRANS WD FIN TRANSPARENT WOOD FINISH
TRTD TREATED
TS TENSILE STRENGTH, TUBE STEEL, TOP
OF STEEL, TOP OF STONE, TOP OF
SLAB
TSTAT THERMOSTAT
TV TELEVISION
TYP TYPICAL
U HEAT TRANSFER COEFFICIENT
UC UNDERCUT
UCD UNDERCUT DOOR
UCF UNDER COUNTER FREEZER
UCR UNDER COUNTER REFRIGERATOR
UGE UNDERGROUND ELECTRIC
UGND UNDERGROUND
UGT UNDERGROUND TELEPHONE
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
ULT ULTIMATE
UNFIN UNFINISH
UNO UNLESS NOTED OTHER WISE
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UR URINAL
UTIL UTILITY
UV ULTRAVIOLET
V VOLT, VENT, VALVE
VA VOLT AMPRE
VAC VACUUM
VAR VARIES
VB VINYL BASE
VC VARNISH CAMBRIC, VITRIFIED CLAY, VA
SUPPLIED & CONTRACTOR INSTALLED
VCT VINYL COMPOSITION TILE, VITRIFIED
CLAY TILE
VEH VEHICLE
VENT VENTILATION
VERT VERTICAL
VEST VESTIBULE
VFAT VINYL FACED ACOUSTICAL TILE
VIC VICINITY
VID VIDEO
VIF VERIFY IN FIELD
VNR VENEER
VOC VOLATILE ORGANIC COMPOUND
VOL VOLUME
VOLT VOLTAGE
VP VENEER PLASTER
VPI VERTICAL POINT OF INTERSECTION
VPOC VERTICAL POINT OF CURVE
VPOT VERTICAL POINT OF TANGENT
VR VAPOR RETARDER
VS VENT STACK
VTR VENT THROUGH ROOF
VV VA SUPPLIED & INSTALLED
VWC VINYL WALL COVERING
VWF VINYL WALL FABRIC
W WIDE, WEST, WIDTH, WASTE, WATER,
WATT, WIRE
W/ WITH
W/O WITHOUT
WA WATT
WARR WARRANTY
WB WET BULB
WBL WOOD BLOCKING
WC WALL COVERING OR WATER CLOSET
WC WL HNG WATER CLOSET, WALL HUNG
WCHR WATER CHILLER
WCL WL MTD WATER COOLER, WALL HUNG
WD WOOD, WINDOW DIMENSION
WDW WINDOW
WF WIDE FLANGE
WFAB WALL FABRIC
WFR WOOD FRAME
WFS WOOD FURRING STRIPS
WH WATER HEATER
WHSE WAREHOUSE
WL WATER LEVEL
WLD WELDED
WM WIRE MESH
WOM WALK OFF MATT
WP WATERPROOFING, WEATHERPROOF
WPD WATER PRESSURE DROP
WPM WATERPROOF MEMBRANE
WR WEATHER RESISTANT
WS WEATHERSTRIP, WASTE STACK, WATER
SURFACE, WATERSTOP
WSCT WAINSCOT
WT WEIGHT
WTB WALL TILE BASE
WTL WALL TILE
WWF WELDED WIRE FABRIC
X BRACE CROSS BRACE
XFMR TRANSFORMER
XPS EXTRUDED POLYSTYRENE BOARD
(INSULATION)
X-STR EXISTING STRUCTURE
YD YARD
YR YEAR
1. ACCESS TO EXISTING FIRE EXIT SHALL REMAIN
OPERATIONAL DURING ALL PHASES OF CONSTRUCTION.
ENSURE ADEQUATE EGRESS CLEARANCES ARE
MAINTAINED AND NOT IMPEDED DURING PHASED
CONSTRUCTION.
2. GENERAL NOTES APPLY TO ALL DRAWING SETS.
3. SUBCONTRACTORS FOR EACH TRADE ARE ADVISED THAT
INFORMATION PERTINENT TO THEIR WORK MAY OCCUR IN
OTHER PORTIONS OF THE CONTRACT DOCUMENTS. ALL
NOTES ARE TO BE REVIEWED AND APPLIED TO RELATED
BUILDING DOCUMENTS.
4. FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS.
IF INCONSISTENCIES, CONTRADICTIONS OR OMISSIONS
ARE DISCOVERED FOLLOW PROCEDURES LISTED IN
SECTION 01 26 13 REQUESTS FOR INFORMATION (RFI)
BEFORE AND/OR DURING CONSTRUCTION.
5. CROSS REFERENCES SHOWN ON DRAWINGS DO NOT
NECESSARILY INDICATE ALL LIKE CONDITIONS AND DO NOT
LIMIT APPLICATION OF ANY DRAWING OR DETAIL. WHERE
SPECIFIC DIMENSIONS, DETAILS, OR DESIGN INTENT
CANNOT BE DETERMINED, FOLLOW PROCEDURES LISTED
IN SECTION 01 26 13 REQUESTS FOR INFORMATION (RFI)
PRIOR TO PROCEEDING WITH WORK.
6. REVIEW SPECIFICATIONS FOR INSTRUCTIONS NOT SHOWN
ON DRAWINGS. INFORMATION COMMON TO SEVERAL
DRAWINGS MAY BE NOTED ON ONLY ONCE.
CONTRACTORS ARE RESPONSIBLE FOR ENTIRE SET OF
DOCUMENTS.
7. PATCH ALL HOLES IN EXISTING SURFACES AND WHERE
EQUIPMENT HAS BEEN REMOVED OR DEMOLITION HAS
OCCURRED AND PREPARE WALL SURFACES (PATCH, SKIM
COAT, PAINT AND FINISH TO MATCH ADJACENT SURFACES)
AS REQUIRED IN PREPARATION FOR NEW FINISHES
SCHEDULED. PATCH TO MATCH ADJACENT SURFACES IF
NOT SCHEDULED.
8. DIMENSIONS ARE TO STRUCTURAL GRIDLINE OR FACE OF
FINISHED WALL UNLESS NOTED OTHERWISE.
9. PROVIDE METAL BACKING AND/OR METAL BLOCKING IN
WALLS AS REQUIRED AT ALL WALL-MOUNTED ITEMS.
VERIFY HEIGHT AND LENGTH WITH ACTUAL EQUIPMENT.
REFER TO METAL BACKING AND BLOCKING DETAILS ON
SHEET A-722. AT EXISTING WALLS, REMOVE WALL
MATERIAL TO INSTALL METAL BACKING/BLOCKING FOR
NEW WALL-MOUNTED ITEMS.
10. ALL EXISTING FLOOR AND WALL OPENINGS AND
DEPRESSIONS NOT USED IN THE NEW WORK SHALL BE
FILLED OR CLOSED WITH MATERIALS TO MEET REQUIRED
FIRE RATING AND MATCH ADJACENT FINISHES.
11. DRAWINGS ARE NOT TO BE SCALED. CONTRACTOR TO
VERIFY ALL DIMENSIONS AND FIELD CONDITIONS PRIOR TO
COMMENCING THE WORK.
12. COORDINATE WITH INTERIORS SHEETS FOR CORNER
GUARD AND WALL PROTECTION LOCATIONS AND DETAILS.
13. RADIUS EXPOSED COUNTERTOP CORNERS 2" RADIUS,
TYPICALLY. (2" WHERE 3MM EDGE BANDING, 1" RADIUS AT
PLAM EDGES.) SEE CASEWORK DETAILS.
14. CAULK ALL COUNTERTOPS, BACKSPLASHES AND CABINETS
AT LOCATIONS WHERE THEY MEET WALLS. SEAL ALL CUT-
OUTS IN COUNTERTOPS.
15. ALL CUTTING AND PATCHING REQUIRED FOR NEW
MECHANICAL AND ELECTRICAL WORK IN ALL EXISTING
SPACES SHALL BE BY THE RESPECTIVE CONTRACTORS.
16. MATCH ALL FINISHED WALL THICKNESS WHERE NEW
WALLS OCCUR IN LINE WITH EXISTING WALLS.
17. CONTRACTOR TO PROVIDE FIRE, SMOKE, DIRT, DUST &
NOISE CONTAINMENT BARRIERS BETWEEN THE WORK
AREA & THE ADJACENT OCCUPIED SPACES.
18. ALL PIPING, CONDUITS, AND RELATED MECHANICAL AND
ELECTRICAL ITEMS SHALL BE CONCEALED WITHIN
DRYWALL AND/OR PLASTER FURRING AS REQUIRED IN
FINISHED AREAS WHETHER SHOWN ON DRAWINGS OR NOT
UNLESS OTHERWISE NOTED.
19. SEAL AROUND ALL MECHANICAL AND ELECTRICAL
EQUIPMENT PENETRATIONS AT RATED WALLS, ABOVE AND
BELOW CEILINGS, WITH A UL APPROVED FIRE-STOPPING
MATERIAL.
20. ALL INTERIOR WALLS WILL BE TYPE 'S' CONSTRUCTION
UNLESS OTHERWISE INDICATED. ALL FRAMING AROUND
COLUMNS WILL BE TYPE 'L2' CONSTRUCTION UNLESS
OTHERWISE INDICATED. REFER TO REGULATORY PLAN
SHEETS GI001 FOR WALL RATINGS.
21. WHEN WALL PARTITIONS OF DIFFERENT FIRE RATING
INTERSECT, THE HIGHEST RATED PARTITION TAKES
PRECEDENT.
22. ALL EXISTING TO REMAIN CEILING AND WALL GRILLES,
DIFFUSERS AND LIGHTS, SPRINKLER HEADS, OCCUPANCY
AND FIRE ALARM DETECTORS TO BE CLEANED IN AREAS
OF CONSTRUCTION.
23. VERIFY THAT THE EXISTING WALLS REQUIRING FIRE
RATING ARE MAINTAINED, REPAIRED AND EXTENDED TO
STRUCTURE.
24. REFER TO LIFE SAFETY PLANS AND FLOOR PLANS FOR
LOCATION OF REQUIRED WALL RATINGS.
25. ALL THERMOSTAT LOCATIONS TO BE COORDINATED WITH
COR PRIOR TO INSTALLATION.
GENERAL SHEET NOTES:
DEPARTMENT LEGEND
ANTE ROOM PATIENT SPACES
BARIATRIC PATIENT ROOM
STAFF SPACES
PATIENT SPACES
UTILITY SPACES
CIRCULATION
SAFER PATIENT ROOM
615 SF
CORRIDOR
C3-12
160 SF
STAIR
169 SF
STAIR
302 SF
ROOM
3C-106
307 SF
CORRIDOR
C3-28
186 SF
CORRIDOR
C3-27
245 SF
CORRIDOR
C3-26
D1
D2
D3ICE/
H2O
213 SF
PATIENT 9
3D-109
79 SF
RR 9
3D-109A
69 SF
RR 8
3D-108A
256 SF
PATIENT 8
3D-108
285 SF
PATIENT 7
3D-107
69 SF
RR 7
3D-107A
297 SF
PATIENT 6
3D-106
72 SF
RR 6
3D-106A
289 SF
PATIENT 5
3D-105
72 SF
RR 5
3D-105A
300 SF
PATIENT 4
3D-104
69 SF
RR 4
3D-104A
298 SF
PATIENT 3
3D-103
70 SF
RR 3
3D-103A
69 SF
RR 2
3D-102A
296 SF
PATIENT 2
3D-102
299 SF
BARIATRIC 1
3D-101
90 SF
RR 1
3D-101A
269 SF
PATIENT 18
3D-133
78 SF
RR 18
3D-133A
68 SF
RR 17
3D-132A
268 SF
SAFER PATIENT 17
3D-132
299 SF
STAFF WORK
3D-136
245 SF
MSA'S
3D-100
190 SF
CLEAN LINENS
3D-138
98 SF
ASST. NURSE MNGR
3D-110
93 SF
NURSE MNGR OFFICE
3D-111
127 SF
MED ROOM
3D-112
106 SF
NUTRITION
3D-135
292 SF
SAFER PATIENT 16
3D-131
67 SF
RR 16
3D-131A
67 SF
RR 15
3D-129A
252 SF
PATIENT 15
3D-129
280 SF
PATIENT 14
3D-128
71 SF
RR 14
3D-128A
71 SF
RR 13
3D-126A
102 SF
PHARM OFFICE
3D-120
108 SF
SOILED UTILITY
3D-134
49 SF
STAFF TOILET
3D-117
131 SF
SPS STORAGE
3D-114
315 SF
EQUIPMENT ROOM
3D-115 16 SF
EQUIP. ALCOVE
3D-140
245 SF
PATIENT 13
3D-126
260 SF
PATIENT 12
3D-12567 SF
RR 12
3D-125A
67 SF
RR 11
3D-123A
61 SF
HAC
3D-119
259 SF
STAFF BREAK ROOM
3D-116
238 SF
PATIENT 11
3D-123
206 SF
PATIENT 10
3D-121
74 SF
RR 10
3D-121A
54 SF
ANTE ROOM
3D-133B
74 SF
CLEAN UTILITY
3D-113
30 SF
OXYGEN STOR.
3D-118
262 SF
CIRCULATION
C3-18
55 SF
ANTE ROOM
3D-101B
19 SF
EQUIP. ALCOVE
3D-127
17 SF
CHARTING
3D-142
16 SF
EQUIP. ALCOVE
3D-140
16 SF
CHARTING
C3-19B
17 SF
CHARTING
3D-141
18 SF
CHARTING
C3-25A 17 SF
CHARTING
C3-19A
11 SF
EQUIP ALCOVE
3D-137
15 SF
CHARTING
C3-19C
49 SF
TOILET
3C-104
49 SF
TOILET
3C-105
50 SF
ANTE ROOM
3D-121B on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
TRUE NORTH
PLAN NORTH
KEYPLAN
A/E:
TRIPLE C - The A/E Group
(520) 481-8548
Mat Perkins
A
B D
EF
G
H
J
K
L
M
C
1/8" = 1'-0"
B
IM
/6
-2
-1
R e n o v a te
D
B e d W in g -B
-M
P L S
V A
M C
/6 -2
-7
.M
P L S
.3 D
B e d W in g .A
R C
H .B
.L
.r v t
/1
/2
:0 :0
P
M
09/12/2022 M.PERKINS K.MACAULAY
618-22-102
1391 - A-002
ARCHITECTURAL ROOM PROGRAM PLAN -
3D
1 Veterans Drive, Minneapolis, MN 55417
B70
RENOVATION OF BUILDING 70 3D
BED WING100% CONSTRUCTION
DOCUMENTS
1/8" = 1'-0" F4
ARCHITECTURAL ROOM PROGRAM PLAN - 3D
ROOM PROGRAM SCHEDULE_3D
LEGEND
ROOM
PROGRAM
CODE NAME
PROGRAM
AREA
ACTUAL
AREA
AREA
DIFFERENCE
SS204 ASST. NURSE MNGR 80 SF 98 SF -18 SF
SV583 CHARTING 100 SF 18 SF 82 SF
SV583 CHARTING 100 SF 17 SF 83 SF
SV583 CHARTING 100 SF 17 SF 83 SF
SV583 CHARTING 100 SF 17 SF 83 SF
SV583 CHARTING 100 SF 16 SF 84 SF
SV583 CHARTING 100 SF 15 SF 85 SF
CIRC EQUIP ALCOVE 11 SF
SC052 EQUIP. ALCOVE 16 SF
SC052 EQUIP. ALCOVE 30 SF
IMS81 EQUIP. ALCOVE 120 SF 19 SF 101 SF
SV583 MED ROOM 100 SF 127 SF -27 SF
SC152 MSA'S 245 SF
SS204 NURSE MNGR OFFICE 80 SF 93 SF -13 SF
SV272 NUTRITION 80 SF 106 SF -26 SF
SS218 PHARM OFFICE 80 SF 102 SF -22 SF
SS262 STAFF BREAK ROOM 100 SF 259 SF -159 SF
SB191 STAFF TOILET 85 SF 49 SF 36 SF
SC231 STAFF WORK 240 SF 299 SF -59 SF
STAFF SPACES: 19 1565 SF 1552 SF 314 SF
SC471 CLEAN LINENS 60 SF 190 SF -130 SF
SB737 CLEAN UTILITY 100 SF 74 SF 26 SF
IMS81 EQUIPMENT ROOM 120 SF 315 SF -195 SF
SB244 HAC 60 SF 61 SF -1 SF
IMS83 OXYGEN STOR. 100 SF 30 SF 70 SF
SB743 SOILED UTILITY 60 SF 108 SF -48 SF
SRSP1 SPS STORAGE 60 SF 131 SF -71 SF
UTILITY SPACES: 7 560 SF 909 SF -349 SF
Grand total: 75 8330 SF 12543
SF
-3912 SF
ROOM PROGRAM SCHEDULE_3D
LEGEND
ROOM
PROGRAM
CODE NAME
PROGRAM
AREA
ACTUAL
AREA
AREA
DIFFERENCE
LEVEL 3
IMS24 ANTE ROOM 65 SF 54 SF 11 SF
IMS24 ANTE ROOM 65 SF 64 SF 1 SF
IMS24 ANTE ROOM 65 SF 50 SF 15 SF
IMS23 PATIENT 9 240 SF 213 SF 27 SF
IMS23 PATIENT 10 240 SF 206 SF 34 SF
IMS23 PATIENT 18 240 SF 269 SF -29 SF
SB147 RR 9 60 SF 79 SF -19 SF
SB147 RR 10 60 SF 74 SF -14 SF
SB147 RR 18 60 SF 78 SF -18 SF
ANTE ROOM PATIENT SPACES: 9 1095 SF 1085 SF 10 SF
IMS24 ANTE ROOM 65 SF 55 SF 10 SF
IMS27 BARIATRIC 1 280 SF 299 SF -19 SF
SB161 RR 1 85 SF 90 SF -5 SF
BARIATRIC PATIENT ROOM: 3 430 SF 444 SF -14 SF
CIRC CIRCULATION 0 SF 137 SF -137 SF
CIRC CIRCULATION 0 SF 503 SF -503 SF
CIRC CIRCULATION 0 SF 1012 SF -1012 SF
CIRC CIRCULATION 0 SF 917 SF -917 SF
CIRC CIRCULATION 0 SF 262 SF -262 SF
CIRC CORRIDOR 0 SF 615 SF -615 SF
CIRC CORRIDOR 0 SF 186 SF -186 SF
CIRC TOILET 0 SF 49 SF -49 SF
CIRC TOILET 0 SF 49 SF -49 SF
CIRCULATION: 9 0 SF 3729 SF -3729 SF
IMS21 PATIENT 2 280 SF 296 SF -16 SF
IMS21 PATIENT 3 240 SF 298 SF -58 SF
IMS21 PATIENT 4 280 SF 300 SF -20 SF
IMS21 PATIENT 5 240 SF 289 SF -49 SF
IMS21 PATIENT 6 280 SF 297 SF -17 SF
IMS21 PATIENT 7 280 SF 285 SF -5 SF
IMS21 PATIENT 8 280 SF 256 SF 24 SF
IMS21 PATIENT 11 280 SF 238 SF 42 SF
IMS21 PATIENT 12 280 SF 260 SF 20 SF
IMS21 PATIENT 13 280 SF 245 SF 35 SF
IMS21 PATIENT 14 280 SF 280 SF 0 SF
IMS21 PATIENT 15 280 SF 252 SF 28 SF
SB147 RR 2 60 SF 69 SF -9 SF
SB147 RR 3 60 SF 70 SF -10 SF
SB147 RR 4 60 SF 69 SF -9 SF
SB147 RR 5 60 SF 72 SF -12 SF
SB147 RR 6 60 SF 72 SF -12 SF
SB147 RR 7 60 SF 69 SF -9 SF
SB147 RR 8 60 SF 69 SF -9 SF
SB147 RR 11 60 SF 67 SF -7 SF
SB147 RR 12 60 SF 67 SF -7 SF
SB147 RR 13 60 SF 71 SF -11 SF
SB147 RR 14 60 SF 71 SF -11 SF
SB147 RR 15 60 SF 67 SF -7 SF
PATIENT SPACES: 24 4000 SF 4129 SF -129 SF
SB147 RR 16 60 SF 67 SF -7 SF
SB147 RR 17 60 SF 68 SF -8 SF
IMS21 SAFER PATIENT 16 280 SF 292 SF -12 SF
IMS21 SAFER PATIENT 17 280 SF 268 SF 12 SF
SAFER PATIENT ROOM: 4 680 SF 695 SF -15 SF
DEDUCTIVE ALTERNATES
D1
DEDUCTIVE ALTERNATE #1: PROVIDE STORAGE ROOM IN LIEU OF PATIENT
ROOMS 10 AND 11 (3D-321/A & 3D-323/A). REMOVE SCOPE OF WORK
ASSOCIATED WITH NEW HEADWALL, PLUMBING, SPECIALTY EQUIPMENT.
D2
D3
DEDUCTIVE ALTERNATE #2: PROVIDE STORAGE ROOM IN LIEU OF PATIENT
ROOMS 12 AND 13 (3D-325/A & 3D-326/A). REMOVE SCOPE OF WORK
ASSOCIATED WITH NEW HEADWALL, PLUMBING, SPECIALTY EQUIPMENT.
DEDUCTIVE ALTERNATE #3: PROVIDE STORAGE ROOM IN LIEU OF PATIENT
ROOMS 14, 15, 16, AND 17 (3D-328/A, 3D-329/A, 3D-331/A & 3D-332/A).
REMOVE SCOPE OF WORK ASSOCIATED WITH NEW HEADWALL, PLUMBING,
SPECIALTY EQUIPMENT.
NOTE: DEDUCTIVE ALTERNATES ARE CASCADING AND MUST BE TAKEN IN
SEQUENTIAL ORDER.
S S
1 1 1 1 1
21 21
22 22
23 23
24 24
25 25
26 26
27 27
28 28
29 29
HJKLM
11 11 11
7 13
2 2 2
2 14
1 2 3
1 2 3
LIMIT OF FLOORING
REMOVAL TO ALIGN
WITH WALL
LIMIT OF FLOORING
REMOVAL TO ALIGN
WITH WALL
186 SF
CORRIDOR
C3-27
49 SF
TOILET
3C-105
49 SF
TOILET
3C-104
307 SF
CORRIDOR
C3-28
245 SF
CORRIDOR
C3-26
FEC
FEC
A-401
ARCHITECTURAL SYMBOL LEGEND
GENERAL DEMOLITION SHEET NOTES
KEYNOTES
A. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE
RATED WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA.
PROVIDE ALL PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT
WALLS SHALL BE CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY
MEANS OF U.L. APPROVED FIRE PROOF CAULKING MATERIAL. SEE
MECHANICAL AND PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.
B. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND CONDUIT
PIPING WITH STRUCTURAL, MECHANICAL, AND…