The file's text, extracted by GovTribe without its formatting.
AQL
Section J - Attachment 12 Acceptable Quality Level (AQL) Matrix Template - CFS
| 21 Sept. 2022 | | Section "C" | Section "J" | Daily Readings | Weekly | Monthly Report | Quarterly Report | Annual Report | New Hire | Update upon change |
| AQL-1 | BAS Daily Log Report | C.3.21.3 | | X | | X | | | | |
| AQL-2 | RCM Airstack Closed Loop | C.3.8 | | X | | X | | | | |
| AQL-3 | Clean Spaces | C.1.21 | | | | X | | | | |
| AQL-4 | Enterprise Resource Planning System | C.1.14 | | X | | | | | | |
| AQL-5 | Critical Equipment Alarm record | | | | | X | | | | |
| AQL-6 | Critical Equipment List | | | | | X | | | | X |
| AQL-7 | Electrical System GFPE | | | | | X | | | | X |
| AQL-8 | Electrical System WO repairs | | | | | X | | | | |
| AQL-9 | Fire Alarm record | | | | | X | | | | |
| AQL-10 | Fuel Usage daily report | | | | X | | | | | |
| AQL-11a-j | Water Analysis C.3.32.6 | C.3.8 | J-13 | | | X | | | | |
| AQL-12-12a | Corrosion Coupon | C.3.32.4 | | | | | | | | |
| AQL-13 | Logs and Records | C.3.5.3 | | | X | | | | | |
| AQL-14 | Meter calibration | | | | | | | X | | |
| AQL-15 | NSF-ANSI Chemicals used | C.3 | | | X | | | | | |
| AQL-16 | One line Diagrams | | | | | | | X | | X |
| AQL-17 | Physical Security - Guard Shacks | | | | X | | | | | |
| AQL-18 | RCM - AHU - Filter & VFD daily inspection C.3.21.2 | C.1.76 | | X | | X | | | | |
| AQL-19 | RCM Electrical inspection | C.1.76 | | X | | | | | | |
| AQL-20 | RCM Plumbing daily inspections | C.1.76 | | X | | | | | | |
| AQL-21 | RCM Building Inspection Exterior | | | | X | | | | | |
| AQL-22 | RCM Building Inspection Interior | | | | X | | | | | |
| AQL-23 | RCM Make up water usage | C.1.76 | | X | | | | | | |
| AQL-24 | RCM Monthly ActivityReview | C.1.76 | | | | X | | | | |
| AQL-25 | Safety and Training | C.3 | | | | | | X | X | |
| AQL-26 | Staffing C.3.20.1c C.3.1.I | C.1.63 | | | X | | | | | |
| AQL-27 | Thermal Imaging Electrical Panels Low Voltage need to add | | | | | | | | | |
| AQL-28 | Thermal Imaging Electrical Switch Gear | | | | | | | | | |
| AQL-29 | Vibration Analysis need to add to contract | | | | | | | X | | |
| AQL-30 | Fire and Life Safety Inspection 15 FAM 813.3 | C.1.34 | | | | | | X | | |
| AQL-31 | Building Assessement of all support systems (AIS) | C.3.2.1 | | | | | | X | | |
| AQL-32 | Blank | | | | | | | | | |
| AQL-33 | Preventive Maintenance Service Contracts (PMSC) budget | | | | | | | X | | |
| AQL-34 | Workplace Hazard Identification and Assessment (OSHA) | | J-15 | | | | | X | | |
| AQL-35 | Monthly Fuel System Inspection (using Gov. Check Lit) | | J-18 | | | X | | | | |
| AQL-36 | Veeder-Root System Testing | | J-18 | | | X | | | | |
| AQL-37 | Annual Leak Monitoring and Overfill Protection Test Form | | J-18 | | | | | X | | |
| AQL-38 | Annual Walkthrough Inspection Checklist | | J-18 | | | | | X | | |
| AQL-39 | On Shelf Replacement and Expendable Parts List C.3.20.1a | C.3.7 | J-06 | | | X | | | | |
| AQL-40 | Customer Quality Assurance C.3.11 | C.3.20.10 | | | | X | | | | |
| AQL-00 | PSV valve testing | |
| Reference | Last tab is reference only: Critical equipment list by Tatitlek | |
| The Quality Assurance Surveillance Plan (QASP) is the document government personnel use to assess contractor performance. Using the Requirements Roadmap ensures that each performance objective is linked to a method of inspection incorporated in the QASP | | |
| AQL-1 | Multi-Provider, Multi-Building Mgmt | |
| AQL-01.1 | Provider-Level Management Oversight | |
| AQL: Provider Performance Monitoring: | |
| o | AQL: 100% of CFS providers receive regular performance reviews based on agreed-upon KPIs. |
| o | AQL: 95% of identified performance issues with individual CFS providers are addressed with corrective action plans within [specified timeframe]. |
| o | AQL: 100% of scheduled meetings with each CFS provider are held. |
| • | AQL: Provider Communication: |
| o | AQL: 98% of communication from the PGMO to CFS providers is documented and tracked. |
| o | AQL: 100% of CFS provider escalations are responded to within the required time frame. |
| • | AQL: Provider Compliance Tracking: |
| o | AQL: 100% of CFS providers' compliance with contract requirements, safety regulations, and environmental standards is monitored and documented. |
| AQL 2 | 2. Building-Level Management Oversight: | |
| AQL 2.1 | • | AQL: Building Inspection Coverage: |
| AQL 2.1.1 | o | AQL: 100% of buildings assigned to CFS providers receive scheduled inspections according to the established frequency. |
| AQL 2.1.2 | o | AQL: 95% of building inspections are performed according to the inspection checklist. |
| • | AQL: Building Issue Tracking: |
| o | AQL: 100% of identified building maintenance issues are tracked and resolved within the defined service level agreements (SLAs). |
| o | AQL: 90% of preventative maintenance schedules are followed for each building. |
| o | AQL: 90% of preventative maintenance schedules are followed for each building. |
| • | AQL: Building Performance Reporting: |
| o | AQL: 100% of building-level performance reports are generated and provided to the COR as required. |
| o | AQL: 100% of building specific data is entered into the ERP system. |
| • | AQL: Building SLA Compliance: |
| o | AQL: 98% of building SLA compliance is maintained. |
| AQL 3 | Provider and Building Cross-Referencing: | |
| AQL 3.1 | • | AQL: Data Correlation: |
| AQL 3.1.1 | o | AQL: 95% of data across providers and buildings is accurately correlated and analyzed to identify trends and potential issues. |
| AQL 3.1.2 | o | AQL: 100% of building to provider assignments are accurately tracked. |
| AQL 3.2 | • | AQL: Issue Escalation: |
| AQL 3.2.1 | o | AQL: 100% of issues that effect multiple buildings or providers are escalated to the COR. |
DRAFT
AQL 1 BAS Daily Log
| AQL - 1 | RCM | | BAS Daily Log Report | | | | |
| Honeywell / Tridium Niagara N4 Month: | Time inspected | Time alarm is reported | Service Company contacted / what time | Time Service Company arrived on site | Discription of Problem Software / Hardware | Discription of repair | Time system is restored |
| Inspection 1 | | | | | | | |
| Inspection 2 | | | | | | | |
| Inspection 3 | | | | | | | |
| Inspection 4 | | | | | | | |
| Inspection 5 | | | | | | | |
| Inspection 6 | | | | | | | |
| Inspection 7 | | | | | | | |
| Inspection 8 | | | | | | | |
| C.3.21.5 b. | Checking all operating equipment in the watch area every two (2) hours. |
| c. Recording operating data in appropriate logs or records every two (2) hours. | |
| Siemens Apogee 3.15 / not supported as of January 2022 | Time inspected | Time alarm is reported | Service Company contacted / what time | Time Service Company arrived on site | Discription of Problem Software / Hardware | Discription of repair | Time system is restored |
| Inspection 1 | | | | | | | |
| Inspection 2 | | | | | | | |
| Inspection 3 | | | | | | | |
| Inspection 4 | | | | | | | |
| Inspection 5 | | | | | | | |
| Inspection 6 | | | | | | | |
| Inspection 7 | | | | | | | |
| Inspection 8 | | | | | | | |
COMMENTS
AQL 2 Airstack Water Anaylsis
| AQL-2 | RCM Airstack System Daily Inspections | | | | | | | | | | | | | | | |
| Month________________ | | | | | | | | | | | | | | | | |
| Make up tank pump control panel/ power on or off | | | | | | | | | | | | | | | | |
| Glycol Make up tank tank level | | | | | | | | | | | | | | | | |
| DAY | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | |
| Make up tank pump control panel/ power on or off | | | | | | | | | | | | | | | | |
| Glycol Make up tank tank level | | | | | | | | | | | | | | | | |
| DAY | 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
| Pump P-04-230 | | | | | | | | | | | | | | | | |
| Pressure reading on system | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | |
| this is the back-up pump for | | | | | | | | | | | | | | | | |
| heat exchanger H-4A-005 | 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
| on the house side | | | | | | | | | | | | | | | | |
| this pump works on differential pressure / most of the time it will be off | | | | | | | | | | | | | | | | |
| Pump P-04-231 / pressure | | | | | | | | | | | | | | | | |
| pump On or Off | | | | | | | | | | | | | | | | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | |
| Pressure reading | | | | | | | | | | | | | | | | |
| pump On or Off | | | | | | | | | | | | | | | | |
| 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
| Pump P-04-232 / pressure | | | | | | | | | | | | | | | | |
| pump On or Off | | | | | | | | | | | | | | | | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | |
| Pressure reading | | | | | | | | | | | | | | | | |
| pump On or Off | | | | | | | | | | | | | | | | |
| 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
| Pump P-04-09 / pressure | | | | | | | | | | | | | | | | |
| pump On or Off | | | | | | | | | | | | | | | | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | |
| Pressure reading | | | | | | | | | | | | | | | | |
| pump On or Off | | | | | | | | | | | | | | | | |
| 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
| Pump P-04-010 / pressure | | | | | | | | | | | | | | | | |
| pump On or Off | | | | | | | | | | | | | | | | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | |
| Pressure reading | | | | | | | | | | | | | | | | |
| pump On or Off | | | | | | | | | | | | | | | | |
| 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
AQL 3 Clean Spaces AQL-3 Date:XX/XX/XX RCM CLEAN SPACES
| Total square footage of common area, cleaned daily 1,500,000 | Scheduled WO | Unscheduled WO | % of Unscheduled WO to Scheduled |
| Total number of Work orders requesting cleaning due to area missed | 0 | 0 | ERROR:#DIV/0! |
| Total number of Work Orders for cleaning because of a spill | Scheduled WO | Unscheduled WO | % of Unscheduled WO to Scheduled |
| 0 | 0 | ERROR:#DIV/0! |
| Total number of bathrooms, cleaned daily | Scheduled WO | Unscheduled WO | % of Unscheduled WO to Scheduled |
| Total number of Work orders requesting cleaning due to area missed. | 0 | 0 | ERROR:#DIV/0! |
| Glass doors to be cleaned | Scheduled WO | Unscheduled WO | % of Unscheduled WO to Scheduled |
| Total number of Work orders requesting cleaning per month | 0 | 0 | ERROR:#DIV/0! |
| Special Projects this Month | Scheduled WO | Unscheduled WO | % of Unscheduled WO to Scheduled |
| Total number of Work orders requesting cleaning per month | 0 | 0 | ERROR:#DIV/0! |
AQL 4 ERPS
| AQL-04 General requirements | | | | | | | | | | | | | | | |
| Maintenance Program Procedures | Date | | | | | | | | | | | | | | |
| Routine Preventative and Emergency Work Orders shall be completed and closed weekly (7days) | MAXIMO systems utilized to schedule, track and close routine and emergency work orders. | | | | | | | | | | | | | | |
| Tatitlek Work Order Report | | | | | | | | | | | | | | | |
| Plumbing | Appliance | HVAC | Janitor | Electrical | Fire | Generator | Elevator | G-Maintenance | Insulator | Water | Fuel | QAQC | Carpentry | Total |
| Scheduled | | | | | | | | | | | | | | | 0 |
| Unscheduled (Routine) | | | | | | | | | | | | | | | 0 |
| Standing | | | | | | | | | | | | | | | 0 |
| TOTAL | | | | | | | | | | | | | | | 0 |
| High Priority | 0 |
| Emergency | 0 |
| Urgent | 0 |
| On Hold | 0 |
| Canceled | 0 |
| Approved | 0 |
| Completed | 0 |
| Closed | 0 |
AQL 5 Critical Equipment Alarms
| AQL-05 General requirements, Critical Equipment Alarm Report | | | | | | | | | | | |
| Maintenance Program Procedures | Date | | | | | | | | | | |
| Routine Preventative and Emergency Work Orders shall be completed and closed weekly (7days) | Critical Equipment Alarm Report MAXIMO systems utilized to schedule, track and close routine and emergency work orders. | | | | | | | | | | |
| O&M Contractor Work Order | | | | | | | | | | | |
| Chillers | Boilers | Lift Stations | Standby Generators | Fuel Tanks | Fuel Transfer pumps | Airstack chiller | Electrical Switch Gear | Fire Pumps | Fire Alarm Systems | Total |
| Total number of Alarms for the month | | | | | | | | | | | 0 |
| Number of unscheduled work orders issued | | | | | | | | | | | 0 |
| Down time is recorded in hours | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
| Percent of down time | 0.00% | 0.00% | 0.00% | 0.00% | 0.00% | 0.00% | 0.00% | 0.00% | 0.00% | 0.00% | |
| Up time | 100.00% | 100.00% | 100.00% | 100.00% | 100.00% | 100.00% | 100.00% | 100.00% | 100.00% | 100.00% | |
| coarticulations | | | | | | | | | | | |
| Number of days x 24 hours divided by hours equipment is down = percentage | Days in Month | Hours | Total hours for the month | Up Time |
| Down time is recorded in 1/10th of an hour | 30 | 24 | 720 | 100.00% |
Comments
AQL 6 Critical Equipment List
| AQL-06 General requirements, Critical Equipment | | | | | | | | | | | |
| Maintenance Program Procedures | Month: | | | | | | | | | | |
| Routine Preventative and Emergency Work Orders shall be completed and closed weekly (7days) | Critical Equipment List Not protected by GFPE The total number of pieces of equipment in HST #_______ MAXIMO systems utilized to schedule, track and close routine and emergency work orders. | | | | | | | | | | |
| O&M Contractor Work Order Report | | | | | | | | | | | |
| Chillers | Boilers | Lift Stations | Standby Generators | Fuel Tanks | Fuel Transfer pumps | Airstack chiller | Electrical Switch Gear | Fire Pumps | Fire Alarm Systems | Total |
| Scheduled | | | | | | | | | | | 0 |
| Unscheduled (Routine) | | | | | | | | | | | 0 |
| Standing (PM's) | | | | | | | | | | | 0 |
| TOTAL | | | | | | | | | | | 0 |
| High Priority | 0 |
| Emergency | 0 |
| Urgent | 0 |
| On Hold | 0 |
| Canceled | 0 |
| Approved | 0 |
| Completed | 0 |
| Closed | 0 |
AQL 7 Electrical GFPE system
| AQL-07 General requirements, (GFPE) | | | | | | | | | | | |
| Maintenance Program Procedures | Month: | | | | | | | | | | |
| Routine Preventative and Emergency Work Orders shall be completed and closed weekly (7days) | Ground Fault Protection of Equipment (GFPE) The total number of pieces of equipment in HST #_______ MAXIMO systems utilized to schedule, track and close routine and emergency work orders. | | | | | | | | | | |
| O&M Contractor Work Order Report | | | | | | | | | | | |
| GFPE protected equipment electrical issues | Chillers | Boilers | Lift Stations | Standby Generators | Fuel Tanks | Fuel Transfer pumps | Airstack chiller | Electrical Switch Gear | Fire Pumps | Fire Alarm Systems | Total |
| Scheduled | | | | | | | | | | | 0 |
| Unscheduled (Routine) | | | | | | | | | | | 0 |
| Standing (PM's) | | | | | | | | | | | 0 |
| TOTAL | | | | | | | | | | | 0 |
| High Priority | 0 |
| Emergency | 0 |
| Urgent | 0 |
| On Hold | 0 |
| Canceled | 0 |
| Approved | 0 |
| Completed | 0 |
| Closed | 0 |
| GFPE protects equipment from damaging line-to-ground faults and is not intended for the protection of people. | |
AQL 8 Electrical WO repairs
| AQL-08 General requirements, Electrical Distribution Critical Equipment | | | | | | | |
| Maintenance Program Procedures | Date | | | | | | |
| Routine Preventative and Emergency Work Orders shall be completed and closed weekly (7days) | Electrical Distribution Critical Equipment The total number of pieces of equipment in HST #_______ MAXIMO systems utilized to schedule, track and close routine and emergency work orders. | | | | | | |
| O&M Contractor Work Order Report | | | | | | | |
| Distribution Panels | Switch Gear | Inverters | Transformers | ATS for generators | UPS gear | Total |
| Total number: | | | | | | | 0 |
| Scheduled | | | | | | | 0 |
| Unscheduled (Routine) | | | | | | | 0 |
| Standing (PM's) | | | | | | | 0 |
| TOTAL | | | | | | | 0 |
| High Priority | 0 |
| Emergency | 0 |
| Urgent | 0 |
| On Hold | 0 |
| Canceled | 0 |
| Approved | 0 |
| Completed | 0 |
| Closed | 0 |
AQL 9 Fire Alarm record
| AQL-09 Fire Alarm Report | | | | | | | | | | | |
| Maintenance Program Procedures | Month: | | | | | | | | | | |
| Routine Preventative and Emergency Work Orders shall be completed and closed weekly (7days) | Fire Alarm Report MAXIMO systems utilized to schedule, track and close routine and emergency work orders. | | | | | | | | | | |
| O&M Contractor Work Order Report | | | | | | | | | | | |
| Panel - 1 | Panel - 2 | Panel - 3 | Panel - 4 | Panel - 5 | Panel - 6 | Panel - 7 | Panel - 8 | Panel - 9 | Panel - 10 | Total |
| Total number of Alarms for the month | | | | | | | | | | | 0 |
| Number of unscheduled work orders issued | | | | | | | | | | | 0 |
| PM'S | | | | | | | | | | | 0 |
| Fire Alarm Test conducted for the month | | | | | | | | | | | 0 |
| | | | | | | | | | | 0 |
| TOTAL | | | | | | | | | | | 0 |
| Locations in HST | Parking Gurage | 1st Floor | 2nd Floor | 3rd Floor | 4th Floor | 5th Floor | 6th Floor | 7th Floor | 8th Floor |
| Device Types | | | | | | | | | |
| Ansul / Kidde Hood System | | | | | | | | | |
| Audible Circuits - CSM-4 | | | | | | | | | |
| Beam Detector | | | | | | | | | |
| Duct Detector | | | | | | | | | |
| Heat Detector | | | | | | | | | |
| Monitor Points | | | | | | | | | |
| NET 7 Cards | | | | | | | | | |
| NIM 1 Cards | | | | | | | | | |
| PSR-1 Boards | | | | | | | | | |
| Pull Stations | | | | | | | | | |
| Relays | | | | | | | | | |
| Smoke Det with Sounder Bases | | | | | | | | | |
| Smoke Detectors | | | | | | | | | |
| Spare Point on Module | | | | | | | | | |
| Tamper Switches | | | | | | | | | |
| Water Flow Switches | | | | | | | | | |
| MXL-IQ Panel | | | | | | | | | |
| MXL - MMB-3 Panel | | | | | | | | | |
| Fire Pump Rooms | | | | | | | | | |
| AA Smoke Detectors | | | | | | | | | |
| 9V Smoke Detectors | | | | | | | | | |
| Battery Main | | | | | | | | | |
| Batteries for PSR | | | | | | | | | |
| Total Devices - Siemens | | | | | | | | | |
AQL 10 Daily Fuel Report O&M Sample Fuel Report AQL-10 Daily Fuel Report: HST Building - Sample (Date) Harry S Truman Building
| TANK | Actual Cap. (USG)**** | forward from last month | 1-Aug | 2-Aug | 3-Aug | 4-Aug | 5-Aug | 6-Aug | 7-Aug | 8-Aug | 9-Aug | 10-Aug | 11-Aug | 12-Aug | 13-Aug | 14-Aug | 15-Aug | 16-Aug |
| 21 Street North Tank (gal) | 10,800 | 7,975 | 7,975 | 7,975 | 7,975 | 7,975 | 7,982 | 7,982 | 7,982 | 7,982 | 7,982 | 7,982 | 7,987 | 7,987 | 7,987 | 7,987 | 7,987 | 7,987 |
| 21 Street South Tank (gal) | 10,800 | 5,668 | 5,668 | 5,668 | 5,668 | 5,668 | 5,671 | 5,671 | 5,671 | 5,671 | 5,671 | 5,671 | 5,673 | 5,673 | 5,673 | 5,673 | 5,673 | 5,673 |
| C Street Tank (gal) | 5,449 | 4,439 | 4,439 | 4,439 | 4,439 | 4,439 | 4,438 | 4,438 | 4,438 | 4,438 | 4,438 | 4,438 | 4,435 | 4,435 | 4,435 | 4,435 | 4,435 | 4,435 |
| Total on Hand (gal) | 27,049 | 18,082 | 18,082 | 18,082 | 18,082 | 18,082 | 18,091 | 18,091 | 18,091 | 18,091 | 18,091 | 18,091 | 18,095 | 18,095 | 18,095 | 18,095 | 18,095 | 18,095 |
| Ullage* (gal) | | | 8,967 | 8,967 | 8,967 | 8,967 | 8,958 | 8,958 | 8,958 | 8,958 | 8,958 | 8,958 | 8,954 | 8,954 | 8,954 | 8,954 | 8,954 | 8,954 |
| Fuel Consumed (gal) | | | 0 | 0 | 0 | 0 | -9 | 0 | 0 | 0 | 0 | 0 | -4 | 0 | 0 | 0 | 0 | 0 |
| 21st tanks est run time (Hours)** | | | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 |
| C Street est run time (hours) | | | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 |
| Qty. Received (gal) | | | | | | | | | | | | | | | | | | |
| TANK | Actual Cap. (USG)**** | | 17-Aug | 18-Aug | 19-Aug | 20-Aug | 21-Aug | 22-Aug | 23-Aug | 24-Aug | 25-Aug | 26-Aug | 27-Aug | 28-Aug | 29-Aug | 30-Aug | 31-Aug | |
| 21 Street North Tank (gal) | | | 7,987 | 7,991 | 7,991 | 7,991 | 7,991 | 7,991 | 7,991 | 7,991 | 7,991 | 7,991 | 7,991 | 7,991 | 7,991 | 7,991 | 7,991 | |
| 21 Street South Tank (gal) | | | 5,673 | 5,501 | 5,501 | 5,501 | 5,501 | 5,501 | 5,501 | 5,501 | 5,501 | 5,501 | 5,501 | 5,501 | 5,501 | 5,501 | 5,501 | |
| C Street Tank (gal) | | | 4,435 | 4,432 | 4,432 | 4,432 | 4,432 | 4,432 | 4,432 | 4,432 | 4,432 | 4,432 | 4,432 | 4,432 | 4,432 | 4,432 | 4,432 | |
| Total on Hand (gal) | | | 18,095 | 17,924 | 17,924 | 17,924 | 17,924 | 17,924 | 17,924 | 17,924 | 17,924 | 17,924 | 17,924 | 17,924 | 17,924 | 17,924 | 17,924 | |
| Ullage* (gal) | | | 8,954 | 9,125 | 9,125 | 9,125 | 9,125 | 9,125 | 9,125 | 9,125 | 9,125 | 9,125 | 9,125 | 9,125 | 9,125 | 9,125 | 9,125 | |
| Fuel Consumed (gal) | | | 0 | 171 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
| 21st tanks est run time (Hours)** | | | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | 21 | |
| C Street est run time (hours) | | | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | 34 | |
| Qty. Received (gal) | | | | | | | | | | | | | | | | | | |
| *Total Ullage greater than or equal to 7499 will output red cell fill with red number, this indicates promt for refill order of 7500 gallons fuel. Ullage represents the gallons required to fill the empty space in the tank to 90% capacity. |
| 21st Street North and South are combined use tanks, Run time (in hours) is the total of Gallons on hand divided by the full load estimated consuption for all generators served by 21st Street North and South tanks. Based on FL consuption 658.8 per hour |
| ***C Steet tank run time (in hours) is a full load fuel consuption estimate for all the generators served by the C street fuel tank. Based on FL consumption 132.20 GPH. |
| ****Actual Capacity is 90% of tank volume. |
| *****Small increase/decrease in fuel consumed are expansion/contraction due to temperature variation. |
| ****** Planned generator test are the third Wednesday of every month. |
| ******* Veeder root readings are taken one a week and entered into this spreadsheet. |
AQL 11 Main Tower
| Co logo | AQL - 11 | RCM | Main Cooling Tower Water Analysis C.3.32.7 | | | | | |
| Month | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine 0-2 PPM | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 400 - 2000 PPM |
| Date | | 1226 | 8.7 | 120 | 0.07 | N/A | N/A | N/A |
| Date | | 1239 | 8.7 | 134 | 0.08 | N/A | N/A | N/A |
| Date | | 1289 | 8.8 | 132 | 0.08 | N/A | N/A | N/A |
| Date | | 1340 | 8.8 | 147 | 0.08 | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
| | | | | | N/A | N/A | N/A |
Note: Traxstar, is a reagent dye used to perform the test
AQL 11a Main Chilled Loop
| Co logo | AQL - 11a | RCM | Main Chill Water Loop | | | | | |
| Month | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 400 - 2000 PPM |
| Date | | 1284 | 10.3 | N/A | N/A | N/A | N/A | 400 |
| Date | | 1279 | 10.3 | N/A | N/A | N/A | N/A | 400 |
| Date | | 1250 | 10.5 | N/A | N/A | N/A | N/A | 400 |
| Date | | 1249 | 10.5 | N/A | N/A | N/A | N/A | 400 |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| The unit of measurement for conductivity is expressed in either microSiemens (uS/cm) or micromhos (umho/cm) which is the reciprocal of the unit of resistance, the ohm. The prefix "micro" means that it is measured in millionths of a mho. MicroSiemens and micromhos are equivalent units.May 28, 2020 | | | | | | | | |
Note: Traxstar, is a reagent dye used to perform the test
AQL 11b 5440 Chilled Loop
| Co logo | AQL - 11b | RCM | 5440 Chilled Water Loop Analysis | | | | | |
| Month | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 400 - 2000 PPM |
| Date | | 1256 | 10.4 | N/A | N/A | N/A | N/A | 400 |
| Date | | 1270 | 10.3 | N/A | N/A | N/A | N/A | 400 |
| Date | | 1246 | 10.5 | N/A | N/A | N/A | N/A | 400 |
| Date | | 1256 | 10.5 | N/A | N/A | N/A | N/A | 400 |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| The unit of measurement for conductivity is expressed in either microSiemens (uS/cm) or micromhos (umho/cm) which is the reciprocal of the unit of resistance, the ohm. The prefix "micro" means that it is measured in millionths of a mho. MicroSiemens and micromhos are equivalent units.May 28, 2020 | | | | | | | |
| Note: Traxstar, is a reagent dye used to perform the test | | | | | | | | |
AQL 11c 7516 Hot Loop
| Co logo | AQL - 11c | RCM | 7516 Hot Water Loop Analysis | | | | | |
| Month | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 520 - 2000 PPM |
| Date | | 930 | 10.1 | N/A | N/A | N/A | N/A | 400 |
| Date | | 930 | 10.3 | N/A | N/A | N/A | N/A | 400 |
| Date | | 937 | 10.3 | N/A | N/A | N/A | N/A | 400 |
| Date | | 929 | 10.3 | N/A | N/A | N/A | N/A | 400 |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| Note: Traxstar, is a reagent dye used to perform the test | | | | | | | | |
AQL 11d LL Steam Vault
| Co logo | AQL - 11d | RCM | LL Steam Vault Hot Water Loop Analysis | | | | | |
| Month | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 520 - 2000 PPM |
| Date | | 1500 | 10.1 | N/A | N/A | N/A | N/A | 640 |
| Date | | 1501 | 10.1 | N/A | N/A | N/A | N/A | 640 |
| Date | | 1531 | 10.2 | N/A | N/A | N/A | N/A | 640 |
| Date | | 1533 | 10.2 | N/A | N/A | N/A | N/A | 640 |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| Note: Traxstar, is a reagent dye used to perform the test | | | | | | | | |
AQL 11e 1239 UPS Hot loop
| Co logo | AQL - 11e | RCM | 1239 UPS Hot Water Loop Analysis | | | | | |
| Month | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 520 - 2000 PPM |
| Date | | 436 | 8 | N/A | N/A | N/A | 0 | N/A |
| Date | | 452 | 8.1 | N/A | N/A | N/A | 0 | N/A |
| Date | | 440 | 8.1 | N/A | N/A | N/A | 0 | N/A |
| Date | | 444 | 8.2 | N/A | N/A | N/A | 0 | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | Comments | | | | | |
Note: Traxstar, is a reagent dye used to perform the test
AQL 11f War Bldg Hot loop
| Co logo | AQL-11f | RCM | War Bldg Hot Water Loop Analysis | | | | | |
| DATE: September | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 520 - 2000 PPM |
| Date | | 1815 | 9.2 | N/A | N/A | N/A | N/A | 720 |
| Date | | 1795 | 9.2 | N/A | N/A | N/A | N/A | 720 |
| Date | | 1794 | 9.3 | N/A | N/A | N/A | N/A | 720 |
| Date | | 1801 | 9.3 | N/A | N/A | N/A | N/A | 720 |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| | | | N/A | N/A | N/A | N/A | |
| Note: Traxstar, is a reagent dye used to perform the test | | | | | | | | |
AQL 11g B2A61 Hot loop
| Co logo | AQL - 11g | RCM | B2A61 Hot Water Loop Analysis | | | | | |
| Month | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 520 - 2000 PPM |
| Date | | 2011 | 9.3 | N/A | N/A | N/A | N/A | 960 |
| Date | | 1625 | 9.3 | | | | | 800 |
| Date | | 1611 | 9.4 | | | | | 800 |
| Date | | 1612 | 9.4 | | | | | 800 |
Note: Traxstar, is a reagent dye used to perform the test
AQL 11h B266 Hot Loop
| Co logo | AQL - 11h | RCM | B266 Hot Water Loop | | | | | |
| Month | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 520 - 2000 PPM |
| Date | | 1340 | 10.1 | N/A | N/A | N/A | N/A | 400 |
| Date | | 1344 | 10.2 | | | | | 400 |
| Date | | 1308 | 10.3 | | | | | 400 |
| Date | | 1309 | 10.3 | | | | | 400 |
Note: Traxstar, is a reagent dye used to perform the test
AQL 11i Blair House
| Co logo | AQL - 11j | RCM | Blair House Chill Water Loop | | | | | |
| Month | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 400 - 2000 PPM |
| Date | | 1300 | 10 | N/A | N/A | N/A | 200 | N/A |
| Date | | 1298 | 10.1 | N/A | N/A | N/A | 200 | N/A |
| Date | | 1311 | 10.3 | N/A | N/A | N/A | 200 | N/A |
| Date | | 1307 | 10.3 | N/A | N/A | N/A | 200 | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| The unit of measurement for conductivity is expressed in either microSiemens (uS/cm) or micromhos (umho/cm) which is the reciprocal of the unit of resistance, the ohm. The prefix "micro" means that it is measured in millionths of a mho. MicroSiemens and micromhos are equivalent units.May 28, 2020 | | | | | | | | |
AQL 11j Blair Hot Loop
| Co logo | AQL - 11i | RCM | Blair House Hot Loop | | | | | |
| Month | | CONDUCTIVITY 500-7000 uohm | pH 8.5 - 11.5 PPM | Traxstar what is the chem. 100-500 PPB | Chlorine | Bromine 0-2 PPM | Molybdate 60 - 200 PPM | Nitrite 520 - 2000 PPM |
| Date | | 506 | 9 | N/A | N/A | N/A | 80 | N/A |
| Date | | 500 | 8.9 | N/A | N/A | N/A | 80 | N/A |
| Date | | 501 | 8.9 | N/A | N/A | N/A | 80 | N/A |
| Date | | 479 | 9 | N/A | N/A | N/A | 50 | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
| | | | N/A | N/A | N/A | | N/A |
AQL 12 Corrosion Coupon
| Co. logo | AQL - 12 | | RCM | Corrosion Coupon Report for Chill and Hot Water Loops | | | | | |
| DATE | | Main Tower Condenser water / open | | Main CW Loop / closed | | 5440 CW Loop / closed | | B2A61HWL | |
| | Steel | Copper | Steel | Copper | Steel | Copper | Steel | Copper |
| March | Coupon Number | 433 | 550 | 432 | 549 | 431 | 548 | 430 | 547 |
| Date | Weight Loss (g) | 0.0408 | 0.0267 | 0.0043 | 0.0051 | 0.0046 | 0.0063 | 0.0047 | 0.0088 |
| Status | Corrosion Rate (mpy) | 0.406 | 0.235 | 0.043 | 0.045 | 0.046 | 0.056 | 0.043 | 0.072 |
| June (annual) 358 | Coupon Number | F38234 | B46048 | F38233 | B46049 | F38231 | B46043 | F38232 | B46045 |
| Date | Weight Loss (g) | 0.0223 | 0.0246 | 0.0041 | 0.0108 | 0.0056 | 0.0089 | 0.0036 | 0.0124 |
| Status | Corrosion Rate (mpy) | 0.052 | 0.051 | 0.010 | 0.022 | 0.013 | 0.018 | 0.008 | 0.026 |
| June 91 days | Coupon Number | 300 | 375 | 295 | 369 | 298 | 373 | 297 | 371 |
| Date | Weight Loss (g) | 0.0338 | 0.0227 | 0.0045 | 0.0113 | 0.0062 | 0.0138 | 0.0056 | 0.0150 |
| Status | Corrosion Rate (mpy) | 0.3110 | 0.1850 | 0.0410 | 0.0920 | 0.0570 | 0.1120 | 0.0510 | 0.1220 |
| September | Coupon Number | F389249 | B46050 | F38248 | B46047 | F38247 | B46044 | F38246 | B46046 |
| Date | Weight Loss (g) | 0.0124 | 0.0174 | 0.0034 | 0.0119 | 0.0051 | 0.0102 | 0.0036 | 0.0109 |
| Status | Corrosion Rate (mpy) | 0.125 | 0.155 | 0.034 | 0.108 | 0.051 | 0.091 | 0.036 | 0.097 |
| Date | Coupon Number | F38399 | 387 | F38398 | 386 | F38397 | 385 | F38396 | 384 |
| Date | Weight Loss (g) | 0.0100 | 0.0142 | 0.0030 | 0.0113 | 0.0027 | 0.0108 | 0.0025 | 0.0103 |
| Status | Corrosion Rate (mpy) | 0.084 | 0.105 | 0.025 | 0.084 | 0.023 | 0.080 | 0.022 | 0.082 |
| | | STATUS | Open System | | Closed System | | | |
| | | | Copper | Mild Steel | Copper | Mild Steel | | |
| | | Excellent | <0.1 | <.1 | <0.1 | <.02 | | |
| | | Very Good | 0.11 - 0.25 | 1.01 - 3 | 0.11 - 0.15 | 0.21 - 0.3 | | |
| | | Good | 0.26 - 0.35 | 3.01 - 5 | 0.16 - 0.2 | 0.31 - 0.5 | | |
| | | Fair | 0.36 - 0.5 | 5.01 - 8 | 0.21 - 0.3 | 0.5 1- 0.8 | | |
| | | Poor | 0.6 - 1 | 8.01 - 10 | 0.31 - 0.5 | 0.81 - 1 | | |
| | | Severe | >1.01 | >10.01 | >0.51 | >1.01 | | |
AQL 12a Corrosion Coupon
| Co. logo | AQL - 12a | RCM | Corrosion Coupon Report for Chill and Hot Water Loops | | | | | | |
| DATE | | Old War Bldg | | UPS 1239 | | LL Steam Vault | | B266 HW loop | |
| | Steel | Copper | Steel | Copper | Steel | Copper | Steel | Copper |
| March | Coupon Number | 427 | 544 | | 545 | 429 | 546 | F38015 | B46485 |
| Date | Weight Loss (g) | 0.0033 | 0.0080 | | 0.0192 | 0.0031 | 0.0105 | 0.0023 | 0.0059 |
| Status | Corrosion Rate (mpy) | 0.0330 | 0.0710 | | 0.1560 | 0.0310 | 0.0930 | 0.0210 | 0.0480 |
| June (annual) 358 | Coupon Number | F38228 | B46037 | F38229 | B46039 | F38230 | B46041 | | |
| Date | Weight Loss (g) | 0.0062 | 0.0151 | 1.5047 | 0.0941 | 0.0055 | 0.0160 | | |
| Status | Corrosion Rate (mpy) | 0.014 | 0.031 | 3.516 | 0.195 | 0.013 | 0.033 | | |
| June 91 days | Coupon Number | 293 | 367 | | 368 | 299 | 374 | 296 | 370 |
| Date | Weight Loss (g) | 0.0053 | 0.0117 | | 0.0915 | 0.0058 | 0.0138 | 0.0046 | 0.0108 |
| Status | Corrosion Rate (mpy) | 0.049 | 0.095 | | 0.745 | 0.053 | 0.112 | 0.042 | 0.088 |
| September | Coupon Number | F38243 | B46038 | | B46040 | F38245 | B46042 | | |
| Date | Weight Loss (g) | 0.0032 | 0.0117 | | 0.0151 | 0.0032 | 0.0167 | | |
| Status | Corrosion Rate (mpy) | 0.032 | 0.104 | | 0.135 | 0.032 | 0.149 | | |
| December Year | Coupon Number | F38395 | 381 | | 382 | F38394 | 383 | | |
| Date | Weight Loss (g) | 0.0019 | 0.0094 | | 0.0129 | 0.0024 | 0.0119 | | |
| Status | Corrosion Rate (mpy) | 0.0160 | 0.070 | | 0.103 | 0.020 | 0.088 | | |
| | | STATUS | Open System | | Closed System | | | |
| | | | Copper | Mild Steel | Copper | Mild Steel | | |
| | | Excellent | <0.1 | <.1 | <0.1 | <.02 | | |
| | | Very Good | 0.11 - 0.25 | 1.01 - 3 | 0.11 - 0.15 | 0.21 - 0.3 | | |
| | | Good | 0.26 - 0.35 | 3.01 - 5 | 0.16 - 0.2 | 0.31 - 0.5 | | |
| | | Fair | 0.36 - 0.5 | 5.01 - 8 | 0.21 - 0.3 | 0.5 1- 0.8 | | |
| | | Poor | 0.6 - 1 | 8.01 - 10 | 0.31 - 0.5 | 0.81 - 1 | | |
| | | Severe | >1.01 | >10.01 | >0.51 | >1.01 | | |
AQL 13 Logs and Records
| Co logo | AQL - 13 | | RCM | Logs and Records QC/QA Verification | | |
| Daily Log Books / QCQA Weekly Review | | Date checked | BAS | Main Chiller | Boilers 8th floor | Standby Generators |
AQL 14 Meter Calibration
| Co logo | AQL - 14 | | RCM | Meter Calibration | | | | | |
| Meter Type | | Manufactory | Serial Number | New purchase Yes/No | Current calibration date | Next calibration date | Purpose | Expected Life cycle in years | Cost of meter |
AQL 15 NSF-ANSI Chemicals
| Co logo | AQL - 15 | | RCM | Chemicals used at HST in Water Treatment meet NSF and / or ANSI Standards | | | | | | | |
| Name of Chemical | | Purpose | System it is used in | Chemical storage location | SDS on File at storage location | SDA folder inspection date | Is there a Safety Shower at storage locating | Safety Shower Inspection date | Name of Personal authorized to use chemicals | Date of training on proper use of chemicals | Spill kit on site Yes/No |
NSF certification ensures that your treatment chemicals meet globally accepted public health standards. If you manufacture, sell or distribute water treatment chemicals in North America, your products are required to comply with NSF/ANSI/CAN 60: Drinking Water Treatment Chemicals - Health Effects. ANSI Standards are Voluntary For example, OSHA 1910.145, “Specifications for Accident Prevention Signs and Tags” references ANSI Z53. 1-1967. That, in effect, makes the ANSI standard a part of the OSHA standard, and OSHA can issue a citation if your workplace safety signs are not in compliance with the Z53. ( American National Standards Institute)
AQL 16 One Line Digrams
| Co logo | AQL - 16 | RCM | One Line Diagrams of Systems | | |
| Diagrams for the following areas | | Location | Process | Date updated | POC |
| Main Chiller Plant | | | | | |
| Airstack Chiller loop with pumps | | | | | |
| Main Steam in HST delivered from offsite | | | | | |
| Boilers | | | | | |
| Cooling Towers | | | | | |
| Hot Water Loop | | | | | |
| Chill water Loop | | | | | |
| Electrical Switch Gear | | | | | |
| Transformers in HST | | | | | |
| Lift Stations | | | | | |
| Fuel storage | | | | | |
| Fuel distribution Piping | | | | | |
| Hazards Chemical Lockers | | Note | | | |
| Storm Water Collection | | | | | |
| All drawing will be done in CAD, framed behind glass, install in appropriate locations | | | | | |
| Note: there maybe more than one location this information needs to be posted | | | | | |
| C.1.69 Sequence of Operations A “sequence of operations” is the control logic used to operate a system normally put into effect through a control program. | | | | | |
AQL 17 Security - Guard Post
| Co logo | AQL - 17 | RCM | Physical Security - Guard Post | | | | | |
| Location on HST Property | | Size of Guard Post Feet /Inches | Electrical service Yes / No | AC & Heat Yes / No | Water Yes / No | O&M is there a schedule PM in Maximo | Painting schedule Yes / No | Custodial schedule Yes / No |
AQL 18 RCM AHU
AQL-18 RCM Daily Inspection AHU_____________________
| Month____________________ | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 |
| VFD Display Auto | | | | | | | | | | | | | | | |
| Manual | | | | | | | | | | | | | | | |
| motor load by % | | | | | | | | | | | | | | | |
| Hz | | | | | | | | | | | | | | | |
| Amps | | | | | | | | | | | | | | | |
| Magnehelic Reading |
| HEGA |
| HEPA |
| Pre-Filters |
| 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
| VFD Display Auto | | | | | | | | | | | | | | | | |
| Manual | | | | | | | | | | | | | | | | |
| motor load by % | | | | | | | | | | | | | | | | |
| Hz | | | | | | | | | | | | | | | | |
| Amps | | | | | | | | | | | | | | | | |
| Magnehelic Reading |
| HEGA |
| HEPA |
| Pre-Filters |
Notes:
AQL 19RCM Electrical Inspection
| Co logo | AQL - 19 | RCM | Electrical Inspection - Low Voltage Distribution Panels | | | | | |
| Panel Location | | Inside of panel clean | All terminals tight | Therminal Imaging on file Yes / No | Panel Identification | Date of Inspection | Name of Qualified Technician | QC/QA Inspector |
AQL 20 RCM Plumbing inspection
| Co logo | AQL - 20 | RCM | Plumbing Inspection | |
| Daily Inspections | | Location | Operational Yes / No | Issues |
| Hot water circulation pumps | | | | |
| Lift Stations | | | | |
| Grase Traps | | | | |
| Back Flow Preventers | | | | |
| Domestic water pumps | | | | |
| Water Purefication Filters | | | | |
AQL 21 RCM Building inspection
| Co logo | AQL - 21 | RCM | | Building Exterior Inspection |
| Daily Inspections | | Issue Yes / No | WO issued | Discription |
| Doors | | | | |
| Windows | | | | |
| Façade | | | | |
| Planter Boxes | | | | |
| Land scape | | | | |
| Hand rails | | | | |
AQL 22 RCM Building Inspection
| Co logo | AQL - 22 | RCM | | Building Interior Inspection |
| Daily Inspections | | Issue Yes / No | WO issued | Discription |
| Doors | | | | |
| Windows | | | | |
| Façade | | | | |
| Planter Boxes | | | | |
| Land scape | | | | |
| Hand rails | | | | |
| Court Yards | | | | |
AQL 23 RCM Make up water
| AQL-23 | RCM | Domestic Make up Water - HST |
| Month____________________ | | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 |
| Current Reading | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| Previous reading | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| Used | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Previous reading is done for the first day of the month only
| 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
| Current Reading | 0 | 0 | | | | | | | | | | | | | | |
| Previous reading | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| Used | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
AQL 23a Make Up Water
| AQL-23a | RCM | Chill Water Loop - Make up Water - HST |
| Month____________________ | | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 |
| Current Reading | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| Previous reading | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| Used | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Previous reading is done for the first day of the month only
| 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
| Current Reading | 0 | 0 | | | | | | | | | | | | | | |
| Previous reading | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
AQL 23b Hot Water Heating
| AQL-23b | RCM | Hot Water Heating - Make up Water - HST |
| Month____________________ | | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 |
| Current Reading | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| Previous reading | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| Used | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Previous reading is done for the first day of the month only
| 16 | 17 | 18 | 19 | 20 | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 |
| Current Reading | 0 | 0 | | | | | | | | | | | | | | |
| Previous reading | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| Used | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
AQL 24 RCM Monthly Activity
| AQL-24 RCM Monthly Activity Review | |
| Month: September 2022 | Total number of equipment or material failures discovered in the course of doing daily rounds | Was a Work Order generate for the repair? Yes / No Work Order Number |
| Electrical | | |
HVAC
Plumbing
Power
Building Interior & Exterior
This information dose not include scheduled PM's or service calls to the WO desk.
Comments
AQL 25 Safety & Training
| Co logo | AQL - 25 | RCM | Safety Training | | | | | |
| Name | | Discription of Training | | Class Hours | Training Class Location | Name of Trainer | Date of Training | Certificate of training issued Yes / No |
AQL 26 Staffing
| Co Logo | AQL-26 Staffing September 2022 |
| HST - Building | |
| Labor Category | |
Department
| Planned | Filled | Subcontracted | Vacancies | % Staffed |
| Total - Headcount | 39.6 | | | | |
| Manpower Breakdown of Administration and Trades by Sites | | | | | |
| Administration- All Sites | | | | | |
| Labor Category | | | | | |
Department
| Planned | Filled | Subcontracted | Vacancies | % Staffed |
| Administration | 3 | | | | 0% |
| Tatitlek | | | | | |
| Labor Category | | | | | |
Department
| | Planned | Filled | Subcontracted | Vacancies | % Staffed | FTE | Annual hours | OT hours | (FTE) Full Time Employee |
| 1 | QC/QA / Safety | 0.6 | | | | | 0.60 | 1856 | 0 | |
| 2 | Chief Engineer | 1 | | | | | 1.00 | 1800 | 90 | |
| 3 | Lead HVAC Mechanic | 1 | | 0 | 1 | 0% | 1.00 | 1800 | 90 | |
| 4 | Mechanical Supervisor | 1 | | 0 | 1 | 0% | 1.00 | 1800 | 90 | |
| 5 | Electrical Lead | 1 | | 0 | 1 | 0% | 1.00 | 1800 | 90 | |
| 6 | Third Class Lead Engineer | 2 | | 0 | 2 | 0% | 2.00 | 1800 | 90 | |
| 7 | First Class Engineer | 2.5 | | 0 | 2.5 | 0% | 2.50 | 1800 | 90 | |
| 8 | Third Class Engineer | 4 | | 0 | 4 | 0% | 4.00 | 1800 | 90 | |
| 9 | Journeymen Pipefitter | 1 | | 0 | 1 | 0% | 1.00 | 1800 | 90 | |
| 10 | Journeymen Plumber | 3 | | 0 | 3 | 0% | 3.00 | 1800 | 90 | |
| 11 | Master Electrician | 1 | | 0 | 1 | 0% | 1.00 | 1800 | 90 | |
| 12 | Journey Electrician | 3 | | 0 | 3 | 0% | 3.00 | 1800 | 90 | |
| 13 | Pneu/Elec. Controls Tech | 3 | | 0 | 3 | 0% | 3.00 | 1800 | 90 | |
| 14 | Maintenance Mechanic | 6.5 | | 0 | 6.5 | 0% | 6.50 | 1800 | 90 | |
| 15 | Utility Maintenance Mechanic | 4 | | 0 | 4 | 0% | 4.00 | 1800 | 90 | |
| 16 | Maintenance Trades Helper | 2 | | 0 | 2 | 0% | 2.00 | 1800 | 90 | |
| | | | 0 | 0 | 0% | | 1800 | 90 | |
| | | | 0 | 0 | 0% | | | | |
| | | | 0 | 0 | 0% | | | | |
| | | | 0 | 0 | 0% | | | | |
| | | | 0 | 0 | 0% | | | | |
| | | | 0 | 0 | 0% | | | | |
| Total | 36.6 | 0 | 0 | 32 | 0% | 36.60 | | | |
AQL 27 Thermal Imaging
| Co logo | AQL - 27 | RCM | Thermal Imaging Electrical Panels - Low Voltage | | | | | | |
| Location of Panels | | Date of Inspecting | Panel Identification | Issues Yes / No | Temperature range set on Camera is 0 - 200 Fahrenheit | Manufactory of camera | Serial Number | Name of Technician | Certification Date |
Prefered Thermal Camera is: FLUKE FLK-TOX580 60HZ
AQL 28 Thermal Imaging
| Co logo | AQL - 28 | RCM | Thermal Imaging Electrical Panels - Switch Gear | | | | | | |
| Location of Panels | | Date of Inspecting | Panel Identification | Issues Yes / No | Temperature range set on Camera is 0 - 200 Fahrenheit | Manufactory of camera | Serial Number | Name of Technician | Certification Date |
Prefered Thermal Camera is: FLUKE FLK-TOX580 60HZ
AQL 29 Vibration Analysis
| Co logo | AQL - 29 | RCM | Vibration Analysis | | | | | |
| Location of Equipment | | Date of Inspecting | Identification of Equipment | Issues Yes / No (note) | Manufactory of Vibration Tester | Serial Number | Name of Technician | Certification Date |
Note: if issues are detected, a separate retesting schedule will be initiated for this piece of equipment. The O&M Operations Manager will be notified ASAP.
Preference for test is a FLUKE 810
AQL 30 Fire & Life Safety
| Co logo | | AQL - 30 | RCM | Annual Fire & Life Safety Inspection Shops and Work areas 15 FAM 813.3 | | | | | | | |
| Floor | HST Inspectors | | Date of Inspecting | Plumbing | Carpenter | HVAC | Electrical | Fire Extinguisher charged and inspected | Flammable cabinet storage | Fire-Doors & Windows | Condition of Paint by Floors |
| 1 | | | | | | | | | | | |
| 2 | | | | | | | | | | | |
| 3 | | | | | | | | | | | |
| 4 | | | | | | | | | | | |
| 5 | | | | | | | | | | | |
| 6 | | | | | | | | | | | |
| 7 | | | | | | | | | | | |
| 8 | | | | | | | | | | | |
| 1 | | | | | | | | | | | |
| 2 | | | | | | | | | | | |
| 3 | | | | | | | | | | | |
| 4 | | | | | | | | | | | |
| 5 | | | | | | | | | | | |
| 6 | | | | | | | | | | | |
| 7 | | | | | | | | | | | |
| 8 | | | | | | | | | | | |
COMMENTS
AQL 31 Building Assessment
| Co logo | | AQL - 31 | RCM | Annual Inspection Summary (AIS) Bld. Assessement | | | | | | | | |
| Floor | HST Inspectors | | Date of Inspecting | Interior Facade | Exterior Façade | Plumbing | Electrical | HVAC | BAS | Elevators | Doors & Windows | Condition of Paint by Floors |
| 1 | | | | | | | | | | | | |
| 2 | | | | | | | | | | | | |
| 3 | | | | | | | | | | | | |
| 4 | | | | | | | | | | | | |
| 5 | | | | | | | | | | | | |
| 6 | | | | | | | | | | | | |
| 7 | | | | | | | | | | | | |
| 8 | | | | | | | | | | | | |
| 9 | | | | | | | | | | | | |
| 10 | | | | | | | | | | | | |
| 11 | | | | | | | | | | | | |
| 12 | | | | | | | | | | | | |
| 13 | | | | | | | | | | | | |
| 14 | | | | | | | | | | | | |
| 15 | | | | | | | | | | | | |
| 16 | | | | | | | | | | | | |
| 17 | | | | | | | | | | | | |
| 18 | | | | | | | | | | | | |
| 19 | | | | | | | | | | | | |
| 20 | | | | | | | | | | | | |
| 21 | | | | | | | | | | | | |
| 22 | | | | | | | | | | | | |
| 23 | | | | | | | | | | | | |
| 24 | | | | | | | | | | | | |
| 25 | | | | | | | | | | | | |
| 26 | | | | | | | | | | | | |
| 27 | | | | | | | | | | | | |
| 28 | | | | | | | | | | | | |
| 29 | | | | | | | | | | | | |
| 30 | | | | | | | | | | | | |
| 31 | | | | | | | | | | | | |
| 32 | | | | | | | | | | | | |
The AIS is a list of findings resulting from the facility condition survey that must be validated annually. Posts must survey and inspect each building and its support systems and document the findings (15FAM 613). Referr to previous AIS reports, and instructions on how to validate.
AQL 32 Blank Co logo Year:_________ AQL - 32 RCM Blank
AQL 33 PMSC-post funding
| Co logo | AQL - 33 | RCM | Budget Planning (PMSC) for Capital Improvements and Services (PMSC) | | | | | | |
| PROJECTS / Services | | | | Budget planning for year ________ | Monthly cost | Cost from previous year | Annual Cost | Mark up % | Total |
| | | | | | | | | $0.00 |
TOTAL Cost $0.00
Preventive Maintenance Service Contracts (PMSC) For PMSC post funding requests: Identify and request PMSC funding needs for post requirements. For funded requests, review PMSC records status' are set to "Obligated" once funds are used to acquire services. This would include major equipment replacements due to end of life cycle.
AQL 34 Hazard Identification
| Co logo | | AQL - 34 | RCM | Workplace Hazard Identification and Assessment 15 FAM 962 | | | | | | | |
| Floor | HST Inspectors Name | | Date of Inspecting | Interior Facade | Exterior Façade | Plumbing | Electrical | HVAC | BAS | Elevators | Doors & Windows |
| 1 | | | | | | | | | | | |
| 2 | | | | | | | | | | | |
| 3 | | | | | | | | | | | |
| 4 | | | | | | | | | | | |
| 5 | | | | | | | | | | | |
| 6 | | | | | | | | | | | |
| 7 | | | | | | | | | | | |
| 8 | | | | | | | | | | | |
| 9 | | | | | | | | | | | |
| Roof | | | | | | | | | | | |
| | | COMMENTS | | | | | | | | |
AQL 35 Fuel System Inspection
| Co logo | AQL - 35 | RCM | Monthly Fuel System Inspection | | |
| DATE | HST Building | | Location | Inspector | Gov. furnished check-list |
| Underground storage tank-1 piping | | | | |
| Underground storage tank-2 piping | | | | |
| Fuel Transfer Piping | | | | |
| Pumps | | | | |
| Pumps | | | | |
| Day Tank-1 piping |
| Day Tank-2 piping |
| Day Tank-3 piping |
Note: tank inspections are annually
AQL 36 Veeder-Root testing
| Co logo | AQL - 36 | RCM | Automatic Tank Gauging System (Veeder-Root) | |
| 2024 | Test | | Veeder-Root Test Results | Inspector |
| January | Test UST's at 0.2 GPH leak rate | | | |
| February | Test UST's at 0.2 GPH leak rate | | | |
| March | Test UST's at 0.2 GPH leak rate | | | |
| April | Test UST's at 0.2 GPH leak rate | | | |
| May | Test UST's at 0.2 GPH leak rate | | | |
| June | Test UST's at 0.2 GPH leak rate | | | |
| July | Test UST's at 0.2 GPH leak rate | | | |
| August | Test UST's at 0.2 GPH leak rate | | | |
| September | Test UST's at 0.2 GPH leak rate | | | |
| October | Test UST's at 0.2 GPH leak rate | | | |
| November | Test UST's at 0.2 GPH leak rate | | | |
| December | Test UST's at 0.2 GPH leak rate | | | |
| December 31 | Test UST's at 0.1 leak rate annually | | | |
| Veeder-Root test Results will be printed out and retained for thirty six (36) continuous months. This is in addition to filling out this report. | | | | |
| December 2025 | Inspect and Test all leak sensors | | Report test results here /retain printed test results | |
AQL 37 Annual Leak & Overfill Co logo AQL - 37 RCM Annual Leak Monitoring and OverfillProtection Test Form for Underground or Aboveground Storage Tank System
AQL 38 Annual Inspection Co logo AQL - 38 RCM Annual Leak Monitoring and OverfillProtection Test Form for Underground or Aboveground Storage Tank System
AQL 39 Parts Inventory
| Co logo | | AQL - 39 | RCM | On Shelf Replacement Parts and Expendable Lists Cover 80% of repairs J-06 | | | | | | |
| Discription | Mfg. Part Number | Vendor Part Number | Vendor | Shelf Stock on hand | Minimum stock level | Stock level re-order point | Quanity ordered | Storage location | Shelf / bin number |
| 1 | | | | | | | | | | |
| 2 | | | | | | | | | | |
| 3 | | | | | | | | | | |
| 4 | | | | | | | | | | |
| 5 | | | | | | | | | | |
| 6 | | | | | | | | | | |
| 7 | | | | | | | | | | |
| 8 | | | | | | | | | | |
| 9 | | | | | | | | | | |
| 10 | | | | | | | | | | |
| 11 | | | | | | | | | | |
| 12 | | | | | | | | | | |
| 13 | | | | | | | | | | |
| 14 | | | | | | | | | | |
| 15 | | | | | | | | | | |
| 16 | | | | | | | | | | |
| 17 | | | | | | | | | | |
| 18 | | | | | | | | | | |
| 19 | | | | | | | | | | |
| 20 | | | | | | | | | | |
| 21 | | | | | | | | | | |
| 22 | | | | | | | | | | |
| 23 | | | | | | | | | | |
| 24 | | | | | | | | | | |
| 25 | | | | | | | | | | |
| 26 | | | | | | | | | | |
| 27 | | | | | | | | | | |
| 28 | | | | | | | | | | |
| 29 | | | | | | | | | | |
| 30 | | | | | | | | | | |
| 31 | | | | | | | | | | |
| 32 | | | | | | | | | | |
| 33 | | | | | | | | | | |
| 34 | | | | | | | | | | |
| 35 | | | | | | | | | | |
| 36 | | | | | | | | | | |
| 37 | | | | | | | | | | |
| 38 | | | | | | | | | | |
| 39 | | | | | | | | | | |
| 40 | | | | | | | | | | |
| 41 | | | | | | | | | | |
AQL 40 Customer QA
| Co logo | AQL - 40 | RCM | Customer Quality Assurance Sample 2% of Monthly Work Orders | | | | |
| Work Order Number | Client | Issue Date | Response Date | Date Completed | Satisfactory | Unsatisfactory | Call Back |
| C.3.20.10 Customer Quality Assurance |
| The tenant contact shall be entered into the work order in the CMMS [[[edit as necessary if CMMS exists]]] so as to generate an email notification to the customer or tenant point of contact upon the work order being placed in “complete” status. The Contractor shall create a customer satisfaction survey sheet, in electronic format if available, which must be approved by the COR in writing. Upon completion of work requests, the contractor shall provide a customer satisfaction survey to the requestor and routed from the customer directly to the COR. The Contractor shall perform re-work as necessary if the occupant is reasonably dissatisfied with the pre-vious effort. If the Contractor believes an occupant is unreasonable or requesting work outside the scope of the contract, the Contractor shall immediately notify the COR. Re-work shall be treated as a new Ser-vice Call. |
AQL 41 PSV Test
| Co logo | | Year:_________ | | AQL - 41 | RCM | Pressure Safety Relief Valve Monthly Trip Test / Annual Pressure Test | | | | | | | | |
| MAXIMO Asset Number | January | February | March | April | May | June | July | August | September | October | November | December Annual Pressure Test | Test Guage Tag # and certification Date |
| 1 | V-02-0007 | | | | | | | | | | | | | |
| 2 | V-02-0008 | | | | | | | | | | | | | |
| 3 | V-02-0009 | | | | | | | | | | | | | |
| 4 | V-02-0010 | | | | | | | | | | | | | |
| 5 | V-02-0013 | | | | | | | | | | | | | |
| 6 | V-02-0014 | | | | | | | | | | | | | |
| 7 | V-02-0015 | | | | | | | | | | | | | |
| 8 | V-02-0038 | | | | | | | | | | | | | |
| 9 | V-02-0040 | | | | | | | | | | | | | |
| 10 | V-02-0042 | | | | | | | | | | | | | |
| 11 | V-02-0043 | | | | | | | | | | | | | |
| 12 | V-02-0044 | | | | | | | | | | | | | |
| 13 | V-02-0045 | | | | | | | | | | | | | |
| 14 | V-02-0048 | | | | | | | | | | | | | |
| 15 | V-02-0049 | | | | | | | | | | | | | |
| 16 | V-02-0050 | | | | | | | | | | | | | |
| 17 | V-02-0054 | | | | | | | | | | | | | |
| 18 | V-02-0056 | | | | | | | | | | | | | |
| 19 | V-02-0057 | | | | | | | | | | | | | |
| 20 | V-02-0058 | | | | | | | | | | | | | |
| 21 | V-02-0059 | | | | | | | | | | | | | |
| 22 | V-02-0060 | | | | | | | | | | | | | |
| 23 | V-02-0061 | | | | | | | | | | | | | |
| 24 | V-02-0062 | | | | | | | | | | | | | |
| 25 | V-02-0063 | | | | | | | | | | | | | |
| 26 | V-02-0064 | | | | | | | | | | | | | |
| 27 | V-02-0065 | | | | | | | | | | | | | |
Reference: 5850/page 415 / line 24 image1.png image2.png image3.png