This solicitation is for an infrastructure upgrade construction project at the St. Cloud Veterans Affairs Health Care System campus in Minnesota. The contractor shall provide all labor, materials, tools and equipment to perform electrical, HVAC, telecommunications, and data center infrastructure upgrades and renovations. Work includes upgrading electrical systems, installing UPS and building management interfaces, enhancing physical and network security, assessing and improving HVAC, expanding fiber infrastructure within and between buildings, and hazardous materials abatement. The solicitation is issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas.
View the file
Other files for this federal contract opportunity
Show all 50
Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING FIBER - INSIDE
VFY EXIST
EXISTING FIBER - OUTSIDE
VFY EXIST
FIBER ROUTE - INSIDE
SEE TELECOM
FIBER ROUTE - OUTSIDE
SEE CIVIL
BUILDING OUTLINE
VFY EXIST
CORRIDOR OUTLINE
VFY EXIST
LEGEND
TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST
44TH AVE.
TRAIL 1
TRAIL 2
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2)
15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
GRAVEL
GRAVEL
GRAVEL
EXISTING
ROAD
CHAIN LINK FENCE
CHAIN LINK FENCE
16' GATE
GRAVEL
ELECTRICAL
SUBSTATION
G E N E R A T O R
FUEL LINES
CONDU ITS TO TU NNEL
M V
D U
C T
B A
N K
1 1 2 W
PHARMACY ADDITION
11 2 E
G E N E R A T O R
B
CORRIDOR LINK
A
C T
TR
A
IL
ER
174 s .f.
256 s .f.
185 s .f.
149 s ..f.
155 s .f.
104 s .f.
70 s. .f .
72 s .f.
110 s .f.
276 s .f.
112 s .f.
99 s .f.
57 s .f.
146 s .f.
434 s .f.
R A
MP
U P
1:
M A X
R A
MP
U P
1:
M A X
RA
M P
UP
1:2 0 M
AX
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2) 15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
.3
TRANSFORMER
BUILD ING
#91
5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN
O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW
C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D
P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S
R EC O M M EN D ATIO N S
N EW G AS SU P P LY M AIN
IN TO B U ILD IN G
SP AR E
P H O N E LIN E
EXTEN D S TO
E XISTIN G
P H O N E IN
B O ILER R O O M
P ER P LAN .
SP AR E
P H O N E
LIN E TO
M ETER
TU N N EL
E XTEN D S
A D D ITIO N AL
2'- 0" U N D ER
B U ILD IN G
FUEL LINE
VENT LINE
1,000 GAL.
UNDERGROUND
DIESEL FUEL
TANK
1,000/5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
S 1
LIG H T
N EW G AS SU P P LY
(C O O R D IN ATE W ITH SU P P LIER )
12"D
10"D
"D
TP TP
EXIST. BUILDING
EXIST.
BUS STOP
CC
L O
O P
16"
20"
12"
3"
8"
DN
BIRDCAGE
B
IR
D C
A G
E
NSP ELECTRICAL
FOR HWY DEPT
T101
I.T.
CHILLER
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
VESTIBULE
DN
DN
DN
FD
DN
F B
F
B
F B
F
B
F B
F
B
SOUTH
VESTIBULE
PASS
THROUGH
LINK TO
BUILDI NG 51
6 3. 32 56
1 13 5. 35 78
PARKING
NO
PARKING
93 49
37 6
109 5
1A
S M
O K
E B
L D
G
SMOKE
BLDG
SMOKE
BLDG
S M
O K
E B
L D
G
SMOKE
BLDG
M.H.
STOR.
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
STOR.
BIO-
HAZ.
SAUK RIVER
GP
HOLDING POND
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
OWNER AND
CONSULTANTS:
CONTACT:
ADDRESS:
MIKE ENGMARK
ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
NAME:
ADDRESS:
CONTACT:
ADVANCED STRUCTURAL TECHNOLOGIES
7301 OHMS LANE; SUITE 215
EDINA, MN 55439
ZACHARY CRAIG
PHONE:
NAME:
ADDRESS:
CONTACT:
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
PHONE: 402-991-5520
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
IAN WEBER
763-412-4000
ARCHITECT:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
EDWARD MARKFORT
763-412-4000
952-854-9302
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
402-991-5520
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
COVER
DATE:
APPROVED: APPROVED: PROJECTS SECTION MANAGER
APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:
APPROVED: SAFETY MANAGER
APPROVED: CHIEF OF POLICE
APPROVED: PATIENT SAFETY
DATE:
DATE:
DATE: APPROVED: EMS MANAGER
APPROVED: M/O MANAGER
DATE:
DATE:
DATE:DATE:
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: PROJECT COR DATE:
APPROVED: INFECTION CONTROL NURSE DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: GEMS COORDINATOR DATE:
DATE:
APPROVED: NURSE EXECUTIVE
APPROVED: CHIEF OF STAFF DATE:
APPROVED: DIRECTOR FMS
APPROVED: ASSOCIATE DIRECTOR
DATE:
DATE:
DATE:
DATE:APPROVED: DATE:
APPROVED: DATE:
APPROVED: DATE:
Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System
N
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
VICINITY MAP:
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHONE: 320-252-1670
CIVIL ENGINEER:
VA COR:
TELECOMMUNICATIONS ENGINEER:
CONTACT:
ADDRESS:
JONATHAN WEST
ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
PHONE: 504-250-2699
PROGRAM MANAGER:
EMAIL: Jonathan.West@vciint.com
STRUCTURAL ENGINEER:
MECH/ELEC/PLUMB/FIRE ENGINEER:
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:0 :1
P
M
118-GI000
BUILDING 118 COVER SHEET &
SHEET INDEX
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM, BMW
16305
BUILDING 118 - EHRM INFRASTRUCTURE UPGRADES
03/30/2022
0APPROX 150' 300'75'
SHEET INDEX - BUILDING 118
SHEET NO. SHEET TITLE
118-GI000 BUILDING 118 COVER SHEET & SHEET INDEX
118-GI101 BASEMENT FLOOR - INFECTION CONTROL & PHASING PLAN
118-GI111 FIRST FLOOR - INFECTION CONTROL & PHASING PLAN
118-AS100 BASEMENT FLOOR PLANS
118-AS110 FIRST FLOOR PLANS
118-TD110 FIRST FLOOR PLAN - ELECTRICAL DEMOLITION
118-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS
118-TN210 FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE
118-TN400 ENLARGED PLANS - TELECOMMUNICATIONS
118-TN401 ENLARGED PLANS - TELECOMMUNICATIONS
118-E201 FIRST FLOOR - ELECTRICAL
118-E300 ELECTRICAL ENLARGED PLANS
118-M101 FIRST FLOOR DEMOLITION - MECHANICAL
118-M201 FIRST FLOOR - MECHANICAL
SEE CAMPUS SHEETS FOR ADDITIONAL INFORMATION
ROOM SCHEDULE
NO. NAME C
A
B
LI
N G
P A
T C
H P
A N
E L
F
IB
E R
P O
W E
R
B O
N D
IN
G
U P
S
D E
D
IC
A T
E D
C O
O
LI
N G
T E
M P
E R
A T
U R
E
H U
M
ID
IT
Y
R A
C K
S E
N S
O R
S P
A C
E
AREA
WIDTH
(FT)
LENGTH
(FT)
HT TO
CLG
STRUCT REMARKS
BASEMENT
005 TELECOM ROOM X X X X X X X X X X 86 SF 8.0 10.7 12.08 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM ROOM
STANDARDS. SEE TELECOM DRAWINGS
FIRST FLOOR
115 TELECOM ROOM X X X X X X X 65 SF 8.0 8.0 12.08 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM ROOM
STANDARDS. SEE TELECOM DRAWINGS
OPENING SCHEDULE
VA Building Number
ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION
H D
W G
R O
U P
F
IR
E L
A B
E L
(M
IN
G A
S K
E T
E
LE
C T
R
IC
A L
S L
A B
E L
COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT
PANEL
TYPE
2ND
PANEL
TYPE
PANEL
GLAZING FRAME TYPE
FRAME
GLAZING
118 TELECOM ROOM 005 3'-0" 7'-0" HM-F NONE HMM-1 NONE HW-3.2 45 Y Y Y
118 TELECOM ROOM 115 3'-0" 7'-0" HM-F NONE HMM-1 NONE HW-3.2 45 Y Y Y
HAZARDOUS MATERIAL SCHEDULE
LEVEL ROOM NO. ROOM NAME QUESTIONABLE HAZARDOUS ELEMENT POSSIBLE ABATEMENT ACTION
BASEMENT 005 TELECOM ROOM NONE NONE
FIRST FLOOR 115 TELECOM ROOM NONE NONE
HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT
DISTURB QUESTIONABLE HAZARDOUS MATERIAL.
LEAK PREVENTION / DIVERTER SCHEDULE
LEVEL
ROOM
NO. ROOM NAME OVERHEAD LEAK DIVERTER AND DRAIN PIPING LEAK PREVENTION BARRIER WATERPROOFING
BASEMENT 005 TELECOM ROOM
FIRST FLOOR 115 TELECOM ROOM
SEE GENERAL NOTES SHEET FOR DETAIL. MWP = MEMBRANE WATERPROOFING. MASONRY = FLUID-APPLIED WATERPROOFING. INT = INTERIOR. EXT = EXTERIOR
ICRA PHASE CONSTRUCTION ROOM SCHEDULE
LEVEL
ROOM
NO. ROOM NAME
CAI BLDG NAME /
FUNCTION
CONSTRUCTION
PROJECT ACTIVITY
INFECTION CONTROL
RISK GROUP
CONTROL
PROCEDURE CLASS SECTION
CONSTRUCTION ZONE /
OCCUPIED CONSTR
DAY /
NIGHT
BASEMENT 005 TELECOM ROOM NUTRITION / FOODS
SERVICE KITCHEN
TYPE C GROUP 1 CLASS II EAST OCCUPIED CONSTRUCTION NIGHT
FIRST FLOOR 115 TELECOM ROOM NUTRITION / FOODS
SERVICE KITCHEN
TYPE C GROUP 1 CLASS II EAST OCCUPIED CONSTRUCTION NIGHT
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
T
T
T -S
ROOM
MECHANICAL
ROOM
LOCKER
ROOM
LOCKER
BREAKROOM
EMPLOYEE
ROOM
STORAGE
ROOM
STORAGE
ELECT.
LOW VOLTAGE
ROOM
ELECTRICAL
CORRIDOR
CORRIDOR
EQUIP
ELEVATOR
ST-0B
STAIRWELL
T -S
T -S
UPUPUP
TELECOM
ROOM
INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND
LIMITS OF CONSTRUCTION
1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER
LOCATION, AND DOOR, WHERE SHOWN
TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER
LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.
UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\b w e a v e r\
D o c u m e n ts \1
-1
-R b w e a v e rR
M
Q M
.r v t
/2
/2
:2 :1
A
M
118-GI101
BASEMENT FLOOR -
INFECTION CONTROL &
PHASING PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM BMW
16305
03/30/2022
1/8" = 1'-0"1
BASEMENT FLOOR - CONST BARRIER PLAN
ROOM ICRA SCHEDULE
YAMA
ROOM
NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS
BASEMENT 005 TELECOM ROOM NUTRITION / FOODS SERVICE
KITCHEN
TYPE C GROUP 1 CLASS II
FIRST FLOOR 115 TELECOM ROOM NUTRITION / FOODS SERVICE
KITCHEN
TYPE C GROUP 1 CLASS II
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
N
0 8' 16'4'
65 222
162199
L E
D L
T
L E
D L
T
L E
D L
T
L E
D L
T
L E
D L
T
L E
D L
T
LED LT.LED LT.
LED LT.LED LT.LED LT.
LED LT. LED LT.
LED LT. LED LT.
(+35 F)
DINING
ROOM
ENTRY
HAC
HAC
UNISEX
TOILET
ISSUE
FREEZER
FOOD BANK
RETHERM
MEAT
TEMPERING
ISSUE COOK
REFRIDGE.
MEAT
PREP
DISHROOM
DIET AID
OFFICE
CART
WASH
FREEZER
NFS
STORAGE
PAPER
STORAGE
HAC
ISSUE
REFRIDGE
125 DAIRY
REFRIDGE
PHONE
ELECT.
SOILED
LINEN
WOMENS
MENS
DOCK
OFFICE
ALCOVE
HOT FOOD
PROD
COLD FOOD
PROD
COLD FOOD
PLATING
RECEIVING
RETURNABLES
F
DN
DN
UP DN
DN
DN
D R
D R
42" DR
42" DR
42" DR 42" DR
" D
R
42" DR
D R
" D
R
COLD FOOD
PRODUCTION
& PLATING
QUEUE
LINE
J U N C T
IO
N
B O X
H W
D A
C R
C W
J U N C T
IO
N
B O X
C W
C R
A D
H W
D
OUT
H
H
IN
D
OUT
H
H
IN
LED LT.LED LT.LED LT.LED LT.
SERVING
LINE
TRAY RETURN
DIAMOND
TREAD WALL
PANEL
DESSERTS
SALAD
BAR
FLATWARE &
CONDIMENTS
CHECK
IN
TRAYS
INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND
LIMITS OF CONSTRUCTION
1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER
LOCATION, AND DOOR, WHERE SHOWN
TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER
LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.
UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA
TELECOM
ROOM
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\b w e a v e r\
D o c u m e n ts \1
-1
-R b w e a v e rR
M
Q M
.r v t
/2
/2
:2 :1
A
M
118-GI111
FIRST FLOOR - INFECTION
CONTROL & PHASING PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM, BMW
16305
03/30/2022
ROOM ICRA SCHEDULE
YAMA
ROOM
NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS
BASEMENT 005 TELECOM ROOM NUTRITION / FOODS SERVICE
KITCHEN
TYPE C GROUP 1 CLASS II
FIRST FLOOR 115 TELECOM ROOM NUTRITION / FOODS SERVICE
KITCHEN
TYPE C GROUP 1 CLASS II
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
1/8" = 1'-0"
FIRST FLOOR - CONST BARRIER PLAN
N
0 8' 16'4'
T
T -S
ROOM
MECHANICAL
ROOM
LOCKER
ROOM
LOCKER
BREAKROOM
EMPLOYEE
ROOM
STORAGE
ROOM
STORAGE
ELECT.
LOW VOLTAGE
ROOM
ELECTRICAL
CORRIDOR
CORRIDOR
EQUIP
ELEVATOR
ST-0B
STAIRWELL
T -S
T -S
UPUPUP
TELECOM
ROOM
8'-0 1/2"
'-8
118-AS100
TELECOM
ROOM
3' -1
1" 2'
-6
4' -3
IN-03.01
5'-5 3/8"
TELECOM
ROOM
TELECOM
ROOM
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\b w e a v e r\
D o c u m e n ts \1
-1
-R b w e a v e rR
M
Q M
.r v t
/2
/2
:2 :1
A
M
118-AS100
BASEMENT FLOOR PLANS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
03/30/2022
N
0 8' 16'4'1/8" = 1'-0"1
BASEMENT FLOOR -OVERALL PLAN
1/4" = 1'-0"
ENLARGED FLOOR PLAN
1/4" = 1'-0"
DEMOLITION PLAN
1/4" = 1'-0"
REFLECTED CEILING PLAN
DE1
DE2
FL2
RC1 RC2
_DEMOLITION PLAN KEYED NOTES
DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM
REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS
DE2 REMOVE AND SALVAGE DOOR. PREPARE OPENING FOR DOOR WITH
IMPROVED SECURITY. SEE FLOOR PLAN AND DOOR SCHEDULE
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_FLOOR PLAN KEYED NOTES
FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”
TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH
HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT
OVER FIRE RATING STAMP.
FL2 DOOR, SIZE AS SCHEDULED, FIRE RESISTANT AS SCHEDULED
FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE
TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST
THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS
WITH FIRE CAULK.
FL4 PATCH TO MATCH FINISHES DISTURBED BY CONSTRUCTION TO MATCH
EXISTING; FLOOR AND WALL. CONTRACTOR TO PROVIDE LABOR AND
MATERIAL
FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_REFLECTED CEILING PLAN KEYED NOTES
RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET
ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE
VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION.
RC2 OPEN TO STRUCTURAL FLOOR ABOVE
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
N
0 4' 8'2'
N
0 4' 8'2'
N
0 4' 8'2'
FL1
DE1
DE1
FL20
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
DEMOLITION AND CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS
DETERMINED BY THE VA) WITH WALL MOUNT BRACKET AND CODE
REQUIRED SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN
TELECOM ROOMS.
FL3
FL3
FL3
FL3
F
DN
DN
UP DN
DN
DN
D R
D R
42" DR
42" DR
42" DR 42" DR
" D
R
42" DR
D R
" D
R
COLD FOOD
PRODUCTION
& PLATING
QUEUE
LINE
J U N C T
IO
N
B O X
H W
D A
C R
C W
J U N C T
IO
N
B O X
C W
C R
A D
H W
D
OUT
H
H
IN
D
OUT
H
H
IN
LED LT.LED LT.LED LT.LED LT.
SERVING
LINE
TRAY RETURN
DIAMOND
TREAD WALL
PANEL
DESSERTS
SALAD
BAR
FLATWARE &
CONDIMENTS
CHECK
IN
TRAYS
TELECOM
ROOM
8'-0 1/2"
8' -0
/2
118-AS110
TELECOM
ROOM
8'-0 1/2"
TELECOM
ROOM
TELECOM
ROOM
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\b w e a v e r\
D o c u m e n ts \1
-1
-R b w e a v e rR
M
Q M
.r v t
/2
/2
:2 :2
A
M
118-AS110
FIRST FLOOR PLANS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
03/30/2022
1/8" = 1'-0"
FIRST FLOOR - OVERALL PLAN
N
0 8' 16'4'
1/4" = 1'-0"
ENLARGED FLOOR PLAN
1/4" = 1'-0"
DEMOLITION PLAN
1/4" = 1'-0"4
REFLECTED CEILING PLAN
RC1 RC2
_DEMOLITION PLAN KEYED NOTES
DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM
REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS
DE2 REMOVE AND SALVAGE DOOR. PREPARE OPENING FOR DOOR WITH
IMPROVED SECURITY. SEE FLOOR PLAN AND DOOR SCHEDULE
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_FLOOR PLAN KEYED NOTES
FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”
TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH
HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT
OVER FIRE RATING STAMP.
FL2 DOOR, SIZE AS SCHEDULED, FIRE RESISTANT AS SCHEDULED
FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE
TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST
THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS
WITH FIRE CAULK.
FL4 PATCH TO MATCH FINISHES DISTURBED BY CONSTRUCTION TO MATCH
EXISTING; FLOOR AND WALL. CONTRACTOR TO PROVIDE LABOR AND
MATERIAL
FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_REFLECTED CEILING PLAN KEYED NOTES
RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET
ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE
VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION.
RC2 OPEN TO STRUCTURAL FLOOR ABOVE
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
N
0 4' 8'2'
N
0 4' 8'2'
N
0 4' 8'2'
FL1
FL1
FL1
FL2
DE1
DE1
DE1
DE2
FL20
FL4
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
DEMOLITION AND CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS
DETERMINED BY THE VA) WITH WALL MOUNT BRACKET AND CODE
REQUIRED SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN
TELECOM ROOMS.
T
T -S
ST-0B
AW1
S-1
T -N
T1-S T2-S
T3
017 018
ROOM
MECHANICAL
ROOM
LOCKER
ROOM
LOCKER
BREAKROOM
EMPLOYEE
ROOM
STORAGE
ROOM
STORAGE
ELECT.
LOW VOLTAGE
ROOM
ELECTRICAL
CORRIDOR
CORRIDOR
EQUIP
ELEVATOR
ST-0B
STAIRWELL
T -S
T -S
018017
T3
T2-ST1-S
T -N
S-1
AW1
ST-0B
018017
T3
T2-ST1-S
T -N
S-1
AW1
ST-0B
UPUPUP LOW VOLTAGE
118-TD110
E
E
E
8" x2
8"x2"
8" x2
8" x2
E
DC
D
DATA RACK
E
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/2
/2
:1
:3
A
M
118-TD100
BASEMENT FLOOR PLAN -
ELECTRICAL DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
SHEET NOTES:
1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION.
EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK PLANS FOR SERVING
COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.
N
0 8' 16'4'1/8" = 1'-0"1
BASEMENT FLOOR PLAN - TELECOM - DEMOLITION
1/4" = 1'-0"
ENLARGED PLAN - EXIST TR 005 - TELECOM - DEMO
N
0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE
RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE
PROJECT.
1. ROOM 005
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 8
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
L E
D L
T
L E
D L
T
L E
D L
T
L E
D L
T
L E
D L
T
L E
D L
T
LED LT.LED LT.
LED LT.LED LT.LED LT.
LED LT. LED LT.
LED LT. LED LT.
F x
R
(-10 F)
(+35 F)
(+28 F)
(+35 F)
B/C
W x
F
R
(-10 F) x x x x x x x
B/C
FR R
W x
F
UNLOAD
" x 6
CLEAN
" x 4
" x 4
" x 4
" x 4 x x x
" x 5
HOLDING
CART
PARKING
ALTERNATE
LOCATION FOR
SECOND
TOASTER
" x 6
" x 6
" x 6
" x 6
" x 6
" x 4
" x 4
" x 4
" x 4 x x x
" x 6 x x x x
" x 6
" x 4
" x 4
" x 4
" x 6
" x 6 x x x
" x 4 x
" x 5 x x x x x x x
" x 6
" x 6
" 2
" x 6 x x x x x x
JUICE
x x x x x
RETHERM
HOT FOOD
PRODUCTION
BAKING
COLD FOOD
HOT FOOD
ROUGH PREP
TRAY
ASSEMBLY
x x x x
ADVANCED
PREP
x
" x 4 x x x x x x x x
ALTERNATE
LOCATION FOR
SECOND
TOASTER
CONDIMENTS
VEG.
ENTREE
MILK
CEREAL
HOT BEV.
COLD BEV.
RECEIVING/
RETURNABLES
ROOM
DINING
ENTRY
HAC
HAC
TOILET
UNISEX
FREEZER
ISSUE
RETHERM
FOOD BANK
TEMPERING
MEAT
REFRIDGE.
ISSUE COOK
PREP
MEAT
DISHROOM
OFFICE
DIET AID
WASH
CART
FREEZER
STORAGE
NFS
STORAGE
PAPER
HAC
REFRIDGE
ISSUE
REFRIDGE.
DAIRY
PHONE
ELECT.
LINEN
SOILED
WOMENS
MENS
DOCK
OFFICE
ALCOVE
RETURN
TRAY
LINE
SERVING
PROD.
HOT FOOD
PROD.
COLD FOOD
PLATING
COLD FOOD
RETURNABLES
RECEIVING
DN
DN
UP DN
DN
DN
D R
D R
42" DR
42" DR
42" DR 42" DR
" D
R
42" DR
D R
" D
R
C
118-TD110
E
E
WAP
WAP
LIMITS OF DATA CABLING DEMOLITION
E
E E
8"x2"
8" x2
8"x2"
8" x2
DATA RACK
E
D
D
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/2
/2
:1
:3
A
M
118-TD110
FIRST FLOOR PLAN -
ELECTRICAL DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 8' 16'4' 1/8" = 1'-0"
FIRST FLOOR PLAN - TELECOM - DEMOLITION
1/4" = 1'-0"2
ENLARGED PLAN - EXIST TR 115 - TELECOM - DEMO
N
0 4' 8'2'
SHEET NOTES:
1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION.
EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK PLANS FOR SERVING
COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE
RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE
PROJECT.
1. ROOM 115
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 40
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
T
T -S
ROOM
MECHANICAL
ROOM
LOCKER
ROOM
LOCKER
BREAKROOM
EMPLOYEE
ROOM
STORAGE
ROOM
STORAGE
ELECT.
LOW VOLTAGE
ROOM
ELECTRICAL
CORRIDOR
CORRIDOR
EQUIP
ELEVATOR
ST-0B
STAIRWELL
T -S
T -S
UPUPUP
T
T
T
T -S
ROOM
MECHANICAL
ROOM
LOCKER
ROOM
LOCKER
BREAKROOM
EMPLOYEE
ROOM
STORAGE
ROOM
STORAGE
ELECT.
LOW VOLTAGE
ROOM
ELECTRICAL
CORRIDOR
CORRIDOR
EQUIP
ELEVATOR
ST-0B
STAIRWELL
T -S
T -S
UPUPUP
TELECOM ROOM
118-TN400
2"
2"
2"
2"
4"
2"E
E
E
E
8" x2
8"x2"
8"x2"
2"
UP
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/2
/2
:1
:3
A
M
118-TN100
BASEMENT FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 8' 16'4'1/8" = 1'-0"
BASEMENT FLOOR PLAN - TELECOMMUNICATIONS
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
SHEET NOTES:
1. PROVIDE JUNCTION BOX TO CONNECT FIBER CONDUIT ENTRY TO EXTEND CONDUIT PATHWAY TO THE NEW
TELECOM ROOM.
ROOM
DINING
ENTRY
HAC
HAC
TOILET
UNISEX
FREEZER
ISSUE
RETHERM
FOOD BANK
TEMPERING
MEAT
REFRIDGE.
ISSUE COOK
PREP
MEAT
DISHROOM
OFFICE
DIET AID
WASH
CART
FREEZER
STORAGE
NFS
STORAGE
PAPER
HAC
REFRIDGE
ISSUE
REFRIDGE.
DAIRY
PHONE
ELECT.
LINEN
SOILED
WOMENS
MENS
DOCK
OFFICE
ALCOVE
RETURN
TRAY
LINE
SERVING
PROD.
HOT FOOD
PROD.
COLD FOOD
PLATING
COLD FOOD
RETURNABLES
RECEIVING
DN
DN
UP DN
DN
DN
D R
D R
42" DR
42" DR
42" DR 42" DR
" D
R
42" DR
D R
" D
R
COLD FOOD
PRODUCTION
& PLATING
QUEUE
LINE
J U N C T
IO
N
B O X
H W
D A
C R
C W
J U N C T
IO
N
B O X
C W
C R
A D
H W
D
OUT H
HIN
D
OUTH
H IN
LED LT.LED LT.LED LT.LED LT.
SERVING
LINE
TRAY RETURN
DIAMOND
TREAD WALL
PANEL
DESSERTS
SALAD
BAR
FLATWARE &
CONDIMENTS
CHECK
IN
TRAYS
F
ROOM
DINING
ENTRY
HAC
HAC
TOILET
UNISEX
FREEZER
ISSUE
RETHERM
FOOD BANK
TEMPERING
MEAT
REFRIDGE.
ISSUE COOK
PREP
MEAT
DISHROOM
OFFICE
DIET AID
WASH
CART
FREEZER
STORAGE
NFS
STORAGE
PAPER
HAC
REFRIDGE
ISSUE
REFRIDGE.
DAIRY
PHONE
ELECT.
LINEN
SOILED
WOMENS
MENS
DOCK
OFFICE
ALCOVE
RETURN
TRAY
LINE
SERVING
PROD.
HOT FOOD
PROD.
COLD FOOD
PLATING
COLD FOOD
RETURNABLES
RECEIVING
DN
DN
UP DN
DN
DN
D R
D R
42" DR
42" DR
42" DR 42" DR
" D
R
42" DR
D R
" D
R
COLD FOOD
PRODUCTION
& PLATING
QUEUE
LINE
J U N C T
IO
N
B O X
H W
D A
C R
C W
J U N C T
IO
N
B O X
C W
C R
A D
H W
D
OUT H
HIN
D
OUTH
H IN
LED LT.LED LT.LED LT.LED LT.
SERVING
LINE
TRAY RETURN
DIAMOND
TREAD WALL
PANEL
DESSERTS
SALAD
BAR
FLATWARE &
CONDIMENTS
CHECK
IN
TRAYS
TELECOM ROOM
118-TN401
E
E
WAP
WAP
LIMITS OF DATA CABLING REPLACEMENT
FROM ROOM 005
C2 126"
2"
2"
2"
2"
2" DOWN
EE
E
8" x2
8"x2"
8" x2
8"x2"
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/2
/2
:1
:3
A
M
118-TN110
FIRST FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 8' 16'4' 1/8" = 1'-0"1
FIRST FLOOR PLAN - TELECOMMUNICATIONS
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
T
T -S
ROOM
MECHANICAL
ROOM
LOCKER
ROOM
LOCKER
BREAKROOM
EMPLOYEE
ROOM
STORAGE
ROOM
STORAGE
ELECT.
LOW VOLTAGE
ROOM
ELECTRICAL
CORRIDOR
CORRIDOR
EQUIP
ELEVATOR
ST-0B
STAIRWELL
T -S
T -S
UPUPUP
T
T
T
T -S
ROOM
MECHANICAL
ROOM
LOCKER
ROOM
LOCKER
BREAKROOM
EMPLOYEE
ROOM
STORAGE
ROOM
STORAGE
ELECT.
LOW VOLTAGE
ROOM
ELECTRICAL
CORRIDOR
CORRIDOR
EQUIP
ELEVATOR
ST-0B
STAIRWELL
T -S
T -S
UPUPUP
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/2
/2
:1
:4
A
M
118-TN200
BASEMENT FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 30' 60'15'
N
0 30' 60'15' 1" = 30'-0"
BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE
ROOM
DINING
ENTRY
HAC
HAC
TOILET
UNISEX
FREEZER
ISSUE
RETHERM
FOOD BANK
TEMPERING
MEAT
REFRIDGE.
ISSUE COOK
PREP
MEAT
DISHROOM
OFFICE
DIET AID
WASH
CART
FREEZER
STORAGE
NFS
STORAGE
PAPER
HAC
REFRIDGE
ISSUE
REFRIDGE.
DAIRY
PHONE
ELECT.
LINEN
SOILED
WOMENS
MENS
DOCK
OFFICE
ALCOVE
RETURN
TRAY
LINE
SERVING
PROD.
HOT FOOD
PROD.
COLD FOOD
PLATING
COLD FOOD
RETURNABLES
RECEIVING
DN
DN
UP DN
DN
DN
D
R
D
R
42" DR
42" DR
42" DR 42" DR
" D R
42" DR
D
R
" D R
COLD FOOD
PRODUCTION
& PLATING
QUEUE
LINE
J U N C T
IO
N
B O X
H W
D A
C R
C W
J U N C T
IO
N
B O X
C W
C R
A D
H W
D
OUT H
HIN
D
OUTH
H IN
LED LT.LED LT.LED LT.LED LT.
SERVING
LINE
TRAY RETURN
DIAMOND
TREAD WALL
PANEL
DESSERTS
SALAD
BAR
FLATWARE &
CONDIMENTS
CHECK
IN
TRAYS
F
ROOM
DINING
ENTRY
HAC
HAC
TOILET
UNISEX
FREEZER
ISSUE
RETHERM
FOOD BANK
TEMPERING
MEAT
REFRIDGE.
ISSUE COOK
PREP
MEAT
DISHROOM
OFFICE
DIET AID
WASH
CART
FREEZER
STORAGE
NFS
STORAGE
PAPER
HAC
REFRIDGE
ISSUE
REFRIDGE.
DAIRY
PHONE
ELECT.
LINEN
SOILED
WOMENS
MENS
DOCK
OFFICE
ALCOVE
RETURN
TRAY
LINE
SERVING
PROD.
HOT FOOD
PROD.
COLD FOOD
PLATING
COLD FOOD
RETURNABLES
RECEIVING
DN
DN
UP DN
DN
DN
D
R
D
R
42" DR
42" DR
42" DR 42" DR
" D R
42" DR
D
R
" D R
COLD FOOD
PRODUCTION
& PLATING
QUEUE
LINE
J U N C T
IO
N
B O X
H W
D A
C R
C W
J U N C T
IO
N
B O X
C W
C R
A D
H W
D
OUT H
HIN
D
OUTH
H IN
LED LT.LED LT.LED LT.LED LT.
SERVING
LINE
TRAY RETURN
DIAMOND
TREAD WALL
PANEL
DESSERTS
SALAD
BAR
FLATWARE &
CONDIMENTS
CHECK
IN
TRAYS
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/2
/2
:1
:4
A
M
118-TN210
FIRST FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 30' 60'15' 1" = 30'-0"
FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE
LOW VOLTAGELOW VOLTAGE
AC
CR
C
TELECOM ROOM
118-TN400
1 - a b
1 - c d
12"x2"
12"x2"
"x
2"
"x
2"
12"x2"
C1 126"
DATA
RACK
CABLE
TRAY
E
KEYPAD
W
2"
2"
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U 48 PORT CAT5E BACKBONE/ANALOG PATCH PANEL
1U CABLE MANAGEMENT
2U CABLE MANAGEMENT
1U 48 PORT CAT6A DATA PATCH PANEL
1U RACK BONDING BUSBAR
2U RACK MOUNT UPS
2U CABLE MANAGEMENT
13U SPACE FOR OIT PROVIDED
EQUIPMENT. PROVIDE BLANKING
PANELS FOR UNUSED SPACES
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. CONTRACTOR TO PROVIDE PATCH PANELS AND HORIZONTAL CABLE MANAGEMENT TO SUPPORT THE DATA COUNT ON
THE WORK PLAN + 1 ADDITIONAL SPARE PATCH PANEL. (NOT TO EXCEED 288 PORTS PER RACK)
5. SPARE RACKS WITH NO HARDWARE CONFIGURED IN THEM MUST HAVE THE STANDARD UPS INSTALLED UNLESS THE
ROOM HAS A CENTRAL UPS SOURCE.
6. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
7. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER
ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
8. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
1U 48 PORT VA PROVIDED SWITCH
1U CABLE MANAGEMENT
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/2
/2
:1
:4
A
M
118-TN400
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 2' 4'1'
0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM 005
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 8
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6A): 8
DATA (CAT6): 0
1/2" = 1'-0"
ENLARGED PLAN - EXIST TR 005 - TELECOM - CABLE TRAY AND DATA
1/4" = 1'-0"
1 - a 1/4" = 1'-0"
1 - b
1/4" = 1'-0"
1 - c 1/4" = 1'-0"
1 - d
NOT TO SCALE6
COMMUNICATIONS - TYPICAL WALL CABINET (TE) ELEVATION - TR005
116116
A C
C R
C
TELECOM ROOM
118-TN401
2 - a b
2 - c d
DATA RACK
E
C2 126"
KEYPAD
W
CABLE
TRAY
12"x2"
12"x2"
12"x2"
12"x2"
12"x2"
2"
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U 48 PORT CAT5E BACKBONE/ANALOG PATCH PANEL
1U CABLE MANAGEMENT
2U CABLE MANAGEMENT
1U 48 PORT CAT6A DATA PATCH PANEL
1U RACK BONDING BUSBAR
2U RACK MOUNT UPS
2U CABLE MANAGEMENT
13U SPACE FOR OIT PROVIDED
EQUIPMENT. PROVIDE BLANKING
PANELS FOR UNUSED SPACES
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. CONTRACTOR TO PROVIDE PATCH PANELS AND HORIZONTAL CABLE MANAGEMENT TO SUPPORT THE DATA COUNT ON
THE WORK PLAN + 1 ADDITIONAL SPARE PATCH PANEL. (NOT TO EXCEED 288 PORTS PER RACK)
5. SPARE RACKS WITH NO HARDWARE CONFIGURED IN THEM MUST HAVE THE STANDARD UPS INSTALLED UNLESS THE
ROOM HAS A CENTRAL UPS SOURCE.
6. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
7. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER
ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
8. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
1U 48 PORT VA PROVIDED SWITCH
1U CABLE MANAGEMENT
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/2
/2
:1
:4
A
M
118-TN401
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 2' 4'1'
0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
1/2" = 1'-0"
ENLARGED PLAN - EXIST TR 115 - TELECOM - CABLE TRAY AND DATA
1/4" = 1'-0"
2 - b 1/4" = 1'-0"
2 - c
1/4" = 1'-0"
2 - a 1/4" = 1'-0"
2 - d
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM 115
EXISTING CABLE COUNT
DATA (CAT6): 40
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 40
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6A): 0
DATA (CAT6): 40
NOT TO SCALE6
COMMUNICATIONS - TYPICAL WALL CABINET (TE) ELEVATION - TR115
T
T -S
ST-0B
AW1
S-1
T -N
T1-S T2-S
T3
017 018
MECHANICAL
ROOM
LOCKER
ROOM
LOCKER
ROOM
EMPLOYEE
BREAKROOM
STORAGE
ROOM
STORAGE
ROOM
LOW VOLTAGE
ELECT.
ELECTRICAL
ROOM
CORRIDOR
CORRIDOR
ELEVATOR
EQUIP
STAIRWELL
ST-0B
T -S
T -S
018017
T3
T2-ST1-S
T -N
S-1
AW1
ST-0B
018017
T3
T2-ST1-S
T -N
S-1
AW1
ST-0B
UPUPUP
118-E300
118-E300
118-E300
118-E300
TELECOM ROOM
TELECOM
ROOM
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/2
/2
:5
:5
P
M
118-E200
BASEMENT - ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
IMEG IMEG
16305
1/8" = 1'-0"
BASEMENT - ELECTRICAL
KEYNOTES:
1. .
2. .
3. .
SHEET NOTES:
1. .
2. .
3. .
0 8' 16'4'
N
100% CD 03/30
53095
(+35 F)
DINING
ROOM
ENTRY
HAC
HAC
UNISEX
TOILET
ISSUE
FREEZER
FOOD BANK
RETHERM
MEAT
TEMPERING
ISSUE COOK
REFRIDGE.
MEAT
PREP
DISHROOM
DIET AID
OFFICE
CART
WASH
FREEZER
NFS
STORAGE
PAPER
STORAGE
HAC
ISSUE
REFRIDGE
125 DAIRY
REFRIDGE
PHONE
ELECT.
SOILED
LINEN
WOMENS
MENS
DOCK
OFFICE
ALCOVE
HOT FOOD
PROD
COLD FOOD
PROD
COLD FOOD
PLATING
RECEIVING
RETURNABLES
F
DN
DN
UP DN
DN
DN
D R
D R
42" DR
42" DR
42" DR 42" DR
" D
R
42" DR
D R
" D
R
COLD FOOD
PRODUCTION
& PLATING
QUEUE
LINE
J U N C T
IO
N
B O X
H W
D A
C R
C W
J U N C T
IO
N
B O X
C W
C R
A D
H W
D
OUT
H
H
IN
D
OUT
H
H
IN
LED LT.LED LT.LED LT.LED LT.
SERVING
LINE
TRAY RETURN
DIAMOND
TREAD WALL
PANEL
DESSERTS
SALAD
BAR
FLATWARE &
CONDIMENTS
CHECK
IN
TRAYS
118-E300
CU-118-2
CU-118-1
B118IT-CR-7,9
B118IT-CR-4,6
TELECOM ROOM
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/2
/2
:5
:5
P
M
118-E201
FIRST FLOOR - ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
IMEG IMEG
16305
1/8" = 1'-0"
FIRST FLOOR - ELECTRICAL
KEYNOTES:
1. PROVIDE ELECTRICAL CONNECTION TO
CONDENSING UNIT CU-118-1 & CU-118-2, AS
REQUIRED. COORDINATE FINAL LOCATION AND
CONNECTION REQUIREMENTS WITH
MECHANICAL.
0 8' 16'4'
N
ELECTRICAL
ROOM
G B
E
PHONE
ELECT.
DN
E
SD
LOW VOLTAGE
ELECT.
LOW VOLTAGE
ELECT.
LOW VOLTAGE
ELECT.
PANEL
118EQB-2
118EQB-1
118 ES-1
118-LB-1
118EQDP-2
118EQDP-1
118 MDP
XFMR
XFMR
XFMR118-ATS-ES
118-ATS-EQ
O
AC-118-2
B118IT-CR-8,10,12
B118IT-4,6,8
TELECOM ROOM
AC-118-1
B118IT
B118IT-2
42"
B118IT-CR-2
42"
B118IT-2
42"
B118IT-2
42"
B118IT-CR-2
42"
B118IT-2
42"
B118IT-CR-1,3,5
B118IT-1,3,5
B118IT-CR
TELECOM ROOM
LOW VOLTAGE
ELECT.
TELECOM ROOM
TELECOM
ROOM
A
B118IT
A
B118IT-CR
TELECOM ROOM
LOW VOLTAGE
ELECT.
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/2
/2
:5
:5
P
M
118-E300
ELECTRICAL ENLARGED
PLANS
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
IMEG IMEG
16305
1/4" = 1'-0"
BASEMENT ENLARGED - ELEC RM
002 - ELECTRICAL
21/4" = 1'-0"
FIRST FLOOR ENLARGED - ELEC
118/115/116 - ELECTRICAL
3 1/4" = 1'-0"
BASEMENT ENLARGED - TR 005 -
POWER AND SYSTEM - EXIST TR
KEYNOTES:
1. DISCONNECT AND REMOVE LIGHTS AND
RECEPTACLES IN AREA OF NEW IT ROOM.
MAINTAIN CIRCUIT CONTINUITY TO ADJOINING
SPACES.
2. INDOOR UNIT TO BE POWERED BY OUTDOOR
UNIT. COORDINATE EXACT LOCATION WITH
M.C.
3. CONNECT SMOKE DETECTOR TO NEAREST
EXISTING SLC.
4. COORDINATE FINAL LOCATION OF
RECEPTACLE L21-20R WITH TELECOM
CONTRACTOR. PROVIDE 3/4"C-4#10, 1#12 GND
TO PANEL FOR EACH RECEPTACLE.
5. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-
PHASE, 4-WIRE RACK MOUNTED UPS FOR
EACH RACK TOWER.
6. PROVIDE APC#AP8861 RPDU RACK PDU 2G
WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,
ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R
OUTLETS. PROVIDE TWO PER RACK, MOUNTED
PER MANUFACTURER'S REQUIREMENTS.
SHEET NOTES:
1. REFER TO TECHNOLOGY PLANS FOR IT ROOM
LAYOUT AND RACK LAYOUT/DETAILS.
2. REFER TO SHEET 0-GE400 DETAIL LAYOUT &
ONE-LINE OF RACK
4 5
N N N
0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
1/4" = 1'-0"
BASEMENT - TR 005 - ELECTRICAL DEMO
4 1/4" = 1'-0"
BASEMENT - TR 005 - LIGHTING
BASEMENT
FIRST FLOOR
B118IT-1
100Y
118-EQDP-2
B118IT-1-CR
100Y
118-LB1
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/2
/2
:5
:5
P
M
118-E400
ELECTRICAL ONE-LINE
DIAGRAMS
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
IMEG IMEG
16305
N O R
HT
12" = 1'-0"
PARTIAL POWER RISER
KEYNOTES:
1. PROVIDE NEW 100A/3P CIRCUIT BREAKERS IN
EXISTING PANEL TO MATCH EXISTING TYPE
AND AIC RATING.
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/2
/2
:5
:5
P
M
118-E500
ELECTRICAL SCHEDULES
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
IMEG IMEG
16305
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 29.8 A
TOTAL CONNECTED AMPS: 29.85 A
Receptacles 0.72 kVA 100.00% 0.72 kVA TOTAL ESTIMATED DEMAND LOAD: 10.753 kVA
Power 10 kVA 100.00% 10 kVA TOTAL CONNECTED LOAD: 10.75 kVA
Lighting 0.033 kVA 100.00% 0.033 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 34.06 27.78 27.78
Total Load: 4.09 kVA 3.33 kVA 3.33 kVA
-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --
-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --
-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --
-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --
-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --
-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --
-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --
-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --
-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --
-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --
-- 9 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 10 --
7 Lighting 20 A 1 0.03 1.67 -- -- -- -- -- -- 8 --
-- 5 -- -- -- -- -- -- 1.67 1.67 -- -- -- -- -- -- 6 --
-- 3 -- -- -- -- -- -- 1.67 1.67 3 20 A L21-20R 4
1 L21-20R 20 A 3 1.67 0.72 1 20 A TELECOM ROOM REC. 2
K E Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
A B C
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K E Y
NOTES:
ISC UNKNOWN 0.00 kA
SCCR: 65 kA
LOCATION: WIRE: 4
FED FROM: 0 A/0P @ GROUND BUS PHASE: 3
ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE MAIN: 100 A MCB
PANEL B118IT
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 40 A
TOTAL CONNECTED AMPS: 39.95 A
Receptacles 0.36 kVA 100.00% 0.36 kVA TOTAL ESTIMATED DEMAND LOAD: 14.393 kVA
Power 14 kVA 100.00% 14 kVA TOTAL CONNECTED LOAD: 14.39 kVA
Lighting 0.033 kVA 100.00% 0.033 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 39.53 44.86 36.39
Total Load: 4.69 kVA 5.33 kVA 4.37 kVA
-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --
-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --
-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --
-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --
-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --
-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --
-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --
-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --
-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --
11 Lighting 20 A 1 0.03 1.67 -- -- -- -- -- -- 12 --
-- 9 -- -- -- -- -- -- 1 1.67 -- -- -- -- -- -- 10 --
7 CU-118-1 20 A 2 1 1.67 3 20 A L21-20R 8
-- 5 -- -- -- -- -- -- 1.67 1 -- -- -- -- -- -- 6 --
-- 3 -- -- -- -- -- -- 1.67 1 2 20 A CU-118-2 4
1 L21-20R 20 A 3 1.67 0.36 1 20 A TELECOM ROOM REC. 2
K E Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
A B C
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K E Y
NOTES:
ISC UNKNOWN 0.00 kA
SCCR: 65 kA
LOCATION: WIRE: 4
FED FROM: 0 A/0P @ GROUND BUS PHASE: 3
ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE MAIN: 100 A MCB
PANEL B118IT-CR
LOW VOLTAGE
ELECT.
CORRIDOR
019019
EXISTING 1 1/2" SPRINKLER
EXISTING 1" SPRINKLER
EXISTING SA DIFFUSER
EXISTING 2 1/2" CAST
IRON PIPE
EXISTING 4" CAST
IRON SANITARY
EXISTING T'STAT
VAV-003
TELECOM ROOM
TELECOM
ROOM
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES AND COR PRIOR TO INSTALLATION TO
PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE,
AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE COR AND THE ARCHITECT/ENGINEER BEFORE
PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS. FINAL LOCATIONS TO BE ACCURATELY DESCRIBED IN AS-BUILTS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST, TIME OR
EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
7. REFER TO CONTRACT DOCUMENTS, TO INCLUDE BUT NOT LIMITED TO, THE
ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND
OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES,
OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO THE SATISFACTION OF THE COR TO MATCH ORIGINAL
CONSTRUCTION, FIRE RATING, AND FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE
COR FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE
PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE COR OF THE REQUIRED ACCESS
PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING,
AND DUCTS PENETRATE, BOTH NEW AND EXISTING. PENETRATIONS THROUGH EXTERIOR
WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS
RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES, BOTH NEW AND EXISTING. THIS IS ESSENTIAL
TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE
DESIRED NC LEVELS WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.
15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.
16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.
17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE
CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
18. CONTRACTOR TO COORDINATE SCHEDULE OF ANY NOISE-PRODUCING WORK SCOPE WITH
COR NOT LESS THAN 10 DAYS PRIOR TO COMMENCING WORK.
19. ALL CARTS, EQUIPMENT, MATERIAL AND TOOLS AS WELL AS ALL TOOL BAGS/BOXES AND
LADDERS ARE TO BE LABELED, CLEARLY IDENTIFYING THE CONTRACTOR/SUBCONTRACTOR
NAME AND PROJECT.
20. STORAGE OF TOOLS, EQUIPMENT AND MATERIALS IS ONLY AUTHORIZED IN APPROVED
LOCATIONS.
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.M
R
.r v t
/2
/2
:4
:2
P
M
118-M100
BASEMENT DEMOLITION -
MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
RDL JCL
16305
1/2" = 1'-0"
BASEMENT DEMOLITION - MECHANICAL - TELECOM ROOM 005
FIELD VERIFICATION NOTES:
1. THE HVAC CONTRACTOR SHOULD VISIT THE SITE PRIOR TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT
THEIR BID. THE FOLLOWING ITEMS SHALL BE FIELD VERIFIED:
A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER…