Atch 24 - BLDG 51 addendum.pdf

PDF 9 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud Federal contract opportunity
Solicitation number
36C77622B0035
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation requests proposals for infrastructure upgrade construction services at the St. Cloud Veterans Affairs Health Care System campus. The contractor shall provide all labor, materials, tools and equipment to complete electrical, telecommunications, data center, HVAC and hazardous materials abatement projects. Work includes installing new and upgrading existing electrical systems, building management system interfaces, access security, fiber optic backbone, data center physical security and diversified WAN pathways. The solicitation is issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud, newest first.
File Type Posted
Atch 41 - Construction Wage Rates - Stearns 7-29-22.pdf PDF
Technical Questions - LATE - St. Cloud 8-10-22.pdf PDF
01-M204 - ROOF REMODEL -MECHANICAL.pdf PDF
Atch 3 - Specifications Volume 3 - Asbestos addendum.pdf PDF
Atch 4 - General 1 of 2 addendum.pdf PDF
Atch 6 - BLDG 1 - 1 of 2 addendum.pdf PDF
Atch 8 - BLDG 2 addendum.pdf PDF
Atch 9 - BLDG 3 addendum.pdf PDF
Atch 12 - BLDG 6 addendum.pdf PDF
Atch 13 - BLDG 7 and 13 addendum.pdf PDF
Atch 27 - BLDG 96 addendum.pdf PDF
Atch 30 - BLDG 111 addendum.pdf PDF
Atch 31 - BLDG 112 addendum.pdf PDF
Specifications Addendum Information.pdf PDF
Drawings Addendum Information.pdf PDF
Atch 1 - Specifications Volume 1 addendum.pdf PDF
Atch 11 - BLDG 5 addendum.pdf PDF
Atch 17 - BLDG 11 addendum.pdf PDF
Atch 18 - BLDG 14 addendum.pdf PDF
Atch 28 - BLDG 108 addendum.pdf PDF
Atch 33 - BLDG 116 addendum.pdf PDF
Site Visit Sign-in Sheets - 6-28-22 - 6-30-22.pdf PDF
36C77622B0035 - 6-9-22.pdf PDF
Atch 6 - BLDG 1 - 1 of 2.pdf PDF
Atch 16 - BLDG 10.pdf PDF
Atch 19 - BLDG 28.pdf PDF
Atch 22 - BLDG 49.pdf PDF
Atch 35 - ADHC.pdf PDF
Atch 4 - General 1 of 2.pdf PDF
Atch 5 - General 2 of 2.pdf PDF
Atch 8 - BLDG 2.pdf PDF
Atch 23 - BLDG 50.pdf PDF
Atch 24 - BLDG 51.pdf PDF
Atch 27 - BLDG 96.pdf PDF
Atch 31 - BLDG 112.pdf PDF
Atch 10 - BLDG 4.pdf PDF
Atch 34 - BLDG 118.pdf PDF
Atch 1 - Specifications Volume 1.pdf PDF
Atch 7 - BLDG 1 - 2 of 2.pdf PDF
Atch 12 - BLDG 6.pdf PDF
Atch 15 - BLDG 9.pdf PDF
Atch 18 - BLDG 14.pdf PDF
Atch 21 - BLDG 48.pdf PDF
Atch 25 - BLDG 54 and 69.pdf PDF
Atch 26 - BLDG 95 and 88.pdf PDF
Atch 28 - BLDG 108.pdf PDF
Atch 30 - BLDG 111.pdf PDF
Atch 32 - BLDG 115.pdf PDF
Atch 36 - Parking Structure.pdf PDF
Atch 40 - Limitations on Subcontracting - Construction.docx DOCX document
Show all 50

Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LEGEND

CORRIDOR OUTLINE

VFY EXIST

BUILDING OUTLINE

VFY EXIST

TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST

44TH AVE.

TRAIL 1

TRAIL 2

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2)

15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

GRAVEL

GRAVEL

GRAVEL

EXISTING

ROAD

CHAIN LINK FENCE

CHAIN LINK FENCE

16' GATE

GRAVEL

ELECTRICAL

SUBSTATION

G E N E R A T O R

FUEL LINES

CONDU ITS TO TU NNEL

M V

D U

C T

B A

N K

1 1 2 W

PHARMACY ADDITION

11 2 E

G E N E R A T O R

B

CORRIDOR LINK

A

C T

TR

A

IL

ER

174 s .f.

256 s .f.

185 s .f.

149 s ..f.

155 s .f.

104 s .f.

70 s. .f .

72 s .f.

110 s .f.

276 s .f.

112 s .f.

99 s .f.

57 s .f.

146 s .f.

434 s .f.

R A

MP

U P

1:

M A X

R A

MP

U P

1:

M A X

RA

M P

UP

1:2 0 M

AX

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2) 15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

.3

TRANSFORMER

BUILD ING

#91

5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN

O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW

C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D

P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S

R EC O M M EN D ATIO N S

N EW G AS SU P P LY M AIN

IN TO B U ILD IN G

SP AR E

P H O N E LIN E

EXTEN D S TO

E XISTIN G

P H O N E IN

B O ILER R O O M

P ER P LAN .

SP AR E

P H O N E

LIN E TO

M ETER

TU N N EL

E XTEN D S

A D D ITIO N AL

2'- 0" U N D ER

B U ILD IN G

FUEL LINE

VENT LINE

1,000 GAL.

UNDERGROUND

DIESEL FUEL

TANK

1,000/5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

S 1

LIG H T

N EW G AS SU P P LY

(C O O R D IN ATE W ITH SU P P LIER )

12"D

10"D

"D

TP TP

EXIST. BUILDING

EXIST.

BUS STOP

CC

L O

O P

L O

O P

16"

20"

12"

3"

8"

DN

0.

0’

BIRDCAGE

B

IR

D C

A G

E

NSP ELECTRICAL

FOR HWY DEPT

T101

I.T.

CHILLER

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

VESTIBULE

DN

DN

DN

FD

DN

F B

F

B

F B

F

B

F B

F

B

SOUTH

VESTIBULE

PASS

THROUGH

LINK TO

BUILDI NG 51

6 3. 32 56

1 13 5. 35 78

PARKING

NO

PARKING

93 49

37 6

109 5

1A

S M

O K

E B

L D

G

SMOKE

BLDG

SMOKE

BLDG

S M

O K

E B

L D

G

SMOKE

BLDG

M.H.

STOR.

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

STOR.

BIO-

HAZ.

GP

HOLDING POND

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

OWNER AND

CONSULTANTS:

CONTACT:

ADDRESS:

MIKE ENGMARK

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

NAME:

ADDRESS:

CONTACT:

ADVANCED STRUCTURAL TECHNOLOGIES

7301 OHMS LANE; SUITE 215

EDINA, MN 55439

ZACHARY CRAIG

PHONE:

NAME:

ADDRESS:

CONTACT:

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

PHONE: 402-991-5520

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

IAN WEBER

763-412-4000

ARCHITECT:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

EDWARD MARKFORT

763-412-4000

952-854-9302

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

402-991-5520

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

COVER

DATE:

APPROVED: APPROVED: PROJECTS SECTION MANAGER

APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:

APPROVED: SAFETY MANAGER

APPROVED: CHIEF OF POLICE

APPROVED: PATIENT SAFETY

DATE:

DATE:

DATE: APPROVED: EMS MANAGER

APPROVED: M/O MANAGER

DATE:

DATE:

DATE:DATE:

APPROVED: MEDICAL CENTER DIRECTOR

APPROVED: PROJECT COR DATE:

APPROVED: INFECTION CONTROL NURSE DATE:

APPROVED: SERVICE LINE DIRECTOR

APPROVED: GEMS COORDINATOR DATE:

DATE:

APPROVED: NURSE EXECUTIVE

APPROVED: CHIEF OF STAFF DATE:

APPROVED: DIRECTOR FMS

APPROVED: ASSOCIATE DIRECTOR

DATE:

DATE:

DATE:

DATE:APPROVED: DATE:

APPROVED: DATE:

APPROVED: DATE:

Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System

N

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

VICINITY MAP:

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHONE: 320-252-1670

CIVIL ENGINEER:

VA COR:

TELECOMMUNICATIONS ENGINEER:

CONTACT:

ADDRESS:

JONATHAN WEST

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

PHONE: 504-250-2699

PROGRAM MANAGER:

EMAIL: Jonathan.West@vciint.com

STRUCTURAL ENGINEER:

MECH/ELEC/PLUMB/FIRE ENGINEER:

C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/2

/2

:3

:2

P

M

51-GI000

BUILDING 51 COVER SHEET &

SHEET INDEX

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

BUILDING 51 - EHRM INFRASTRUCTURE UPGRADES

03/30/2022

0APPROX 150' 300'75'

SHEET INDEX - BUILDING 51

SHEET NO. SHEET TITLE

51-GI000 BUILDING 51 COVER SHEET & SHEET INDEX

51-GI101 BASEMENT FLOOR - INFECTION CONTROL & PHASING PLAN

51-GI111 FIRST FLOOR - INFECTION CONTROL & PHASING PLAN

51-HA-1A REFERENCE - SUBBASEMENT FLOOR ASBESTOS RE-SURVEY

51-HA-2A REFERENCE - BASEMENT FLOOR ASBESTOS RE-SURVEY

51-HA-3A REFERENCE - FIRST FLOOR ASBESTOS RE-SURVEY

51-HA-4A REFERENCE - SECOND FLOOR ASBESTOS RE-SURVEY

51-AS100 BASEMENT PLANS

51-AS110 FIRST FLOOR - OVERALL PLAN

51-AS120 SECOND FLOOR - OVERALL PLAN

51-TD100 BASEMENT FLOOR PLAN - ELECTRICAL DEMOLITION

51-TD110 FIRST FLOOR PLAN - ELECTRICAL DEMOLITION

51-TD120 SECOND FLOOR PLAN - ELECTRICAL DEMOLITION

51-TN100 BASEMENT FLOOR PLAN - TELECOMMUNICATIONS

51-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS

51-TN120 SECOND FLOOR PLAN - TELECOMMUNICATIONS

51-TN200 BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE

51-TN400 ENLARGED PLANS - TELECOMMUNICATIONS

51-E100 BASEMENT FLOOR PLAN - ELECTRICAL

51-E101 FIRST FLOOR PLAN - ELECTRICAL

51-E300 ENLARGED PLANS - ELECTRICAL

51-E500 ELECTRICAL DIAGRAMS

51-E600 ELECTRICAL SCHEDULES

51-M100 BASEMENT DEMOLITION PLAN - MECHANICAL

51-M200 BASEMENT FLOOR PLAN - MECHANICAL

SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION

ROOM SCHEDULE

NO. NAME C

A

B

LI

N G

P A

T C

H P

A N

E L

F

IB

E R

P O

W E

R

B O

N D

IN

G

U P

S

D E

D

IC

A T

E D

C O

O

LI

N G

T E

M P

E R

A T

U R

E

H U

M

ID

IT

Y

R A

C K

S E

N S

O R

S P

A C

E

AREA

WIDTH

(FT)

LENGTH

(FT)

HT TO

CLG

STRUCT REMARKS

BASEMENT

001 TELECOM ROOM X X X X X X X X X X X 147 SF 8.2 18.2 CONSTRUCT TO EHRM TELECOM ROOM STANDARDS. SEE

TELECOM DRAWINGS

FIRST FLOOR

103A EXIST RM 23 SF 7.3 6.2 11.50 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM

DRAWINGS RELOCATE FUNCTIONS TO ROOM 001

OPENING SCHEDULE

VA Building Number

ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION

H D

W G

R O

U P

F

IR

E L

A B

E L

(M

IN

G A

S K

E T

E

LE

C T

R

IC

A L

S L

A B

E L

COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT

PANEL

TYPE

2ND

PANEL

TYPE

PANEL

GLAZING FRAME TYPE

FRAME

GLAZING

51 TELECOM ROOM 001 3'-6" 7'-0" WD-F NONE HMS-1 NONE HW-3.2B 45 Y Y Y

HAZARDOUS MATERIAL SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

QUESTIONABLE HAZARDOUS

ELEMENT POSSIBLE ABATEMENT ACTION

BASEMENT 001 TELECOM ROOM ASBESTOS CONTAINING MASTIC

UNDER TILE. SEE 51-HA-2A

REMOVE HAZARDOUS MATERIAL UNDER FULL CONTAINMENT

FIRST FLOOR 103A EXIST RM NONE. SEE 51-HA-3A NONE.ACM TO REMAIN UNDISTURBED

HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT DISTURB

QUESTIONABLE HAZARDOUS MATERIAL.

ICRA PHASE CONSTRUCTION ROOM SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

CAI BLDG NAME /

FUNCTION

CONSTRUCTION

PROJECT ACTIVITY

INFECTION CONTROL

RISK GROUP

CONTROL

PROCEDURE CLASS SECTION

CONSTRUCTION ZONE /

OCCUPIED CONSTR

DAY /

NIGHT

BASEMENT 001 TELECOM ROOM EXTENDED CARE TYPE C GROUP 1 CLASS II WEST ZONE51 DAY

FIRST FLOOR 103A EXIST RM EXTENDED CARE TYPE B GROUP 1 CLASS II WEST OCCUPIED CONSTRUCTION DAY

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

1 UPDATE TO BID DOCUMENTS 06/29/22

P

WHEELCHAIR

STORAGE

4C

WHEELCHAIR

WASHER

4D

WHEELCHAIR

CLINIC OFFICE

4E

EMPLOYEE

LOUNGE

6 WHEELCHAIR

CLINIC

OFFICE

4B

H.A.C.

TOILET

4A

FEMALE

LOCKER

BATHROOM

2A

SOILED

UTILITY

1A

PROSTHETICS

OFFICE

PROSTHETICS

STORAGE

OFFICE

9A

[PROSTHETICS

STAIR

HALL

UPPER

SERVICE ROOM

10A

OFFICE

PIPE

CHASE

19A

EXAM

23C

PHONE

CLOSET

1B

CORRIDOR

C0C

INTAKE

23C

WAITING

OCCUPATIONAL

THERAPY

KITCHEN

21B

STORAGE

BATHROOM

21C

SPEECH

THERAPY

21A

FEMALE

TOILET

MALE

TOILET

SOILED

LINEN

STORAGE

ACTIVITIES

HAC

HALL

12A

STAIR

12B

REHAB

OFFICE

17B

SPEECH

OFFICE

17A

MECHANICAL

STAIR

HALL

CORRIDOR

STAFF

17M

TREATMENT 4

17D

TREATMENT 3

17C

TREATMENT 1

17L

ENTRY

12C

ELEV

EQUIP

12D

EQUIP.

STORAGE

17G

TOUCHDOWN

ROOM

17H

STAIR

STAIR

SCI CLINIC

17F

TREATMENT 5

17E

TREATMENT 2

17K

STOR.

17J

INTAKE

17I

RECEPTION

OFFICE

PASSAGE

COCA

STOR.

17J

TELECOM

ROOM

ZONE 51

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/2

/2

:3 :1

P

M

51-GI101

BASEMENT FLOOR -

INFECTION CONTROL &

PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

1/8" = 1'-0"

BASEMENT FLOOR - CONST BARRIER PLAN

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

BASEMENT 001 TELECOM ROOM EXTENDED CARE TYPE C GROUP 1 CLASS II

FIRST FLOOR 103A EXIST RM EXTENDED CARE TYPE B GROUP 1 CLASS II

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

N 0 8' 16'4'

LIG

H

T

LI

G

H T

LI

G

H T

LIGHTLIGHT

LIG

H

T

LIGHTLIGHT

LIG

H

T

LIGHT

LIGHT

LIG

H

T

LIGHT

LI

G

H T

LIGHT

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

ENTRY

ELECT.

ROOM

STORAGE

116A

RECREATION

CLOSET

TOILET

111A

2 BED

2 BED

2 BED

CLOSET

TOILET

112A

1 BED

NURSES

SUBSTATION

MULTI.

ROOM

1 BED

TOILET

108A

OFFICE

CONF

CLASS

LINEN

CHUTE

DINING

SOILED

UTILITY

STAIR 1

1 BED

CLEAN

UTIL/LINEN

BATHING

CONGREGATE

HAC

1 BED

TOILET

121A

TOILET

126A

2 BED

STAFF

TOILET

NURSE

STATION

MED

TOILET

123A

STAIR

2 BED

2 BED

EQ STOR

VISITATION WARD

SUPPLY

CLEAN

UTIL/LINEN

TOILET

150A

2 BED

PUBLIC

TOILET

OFFICE

ADMIN.

ASSIST

ALCOVE

ELEV

BATH

163A

NURSE

PRACTIONER

CLOSET

2 BED

2 BED

TOILET

156A

2 BED

155CORR

TOILET

157A

1 BED

SOILED

UTILITY

1 BED

TOILET

153A

CLOSET

2 BED

HAC

141STAIR

134B

STORAGE

STOR

135A

TOILET

136A

2 BED

DINING

VESTIBULE

134A

STAIR

2 BED

2 BED

2 BED

TOILET

138A

2 BED

TOILET

147A

CLOSET

CLOSET

2 BED

LOUNGE

142 STORAGE

CONGREGATE BATH

PATIENT LAUNDRY

STAIR

CORRIDOR

C1C

CORRIDOR

C1NE

CORRIDOR

C1SE

CORRIDOR

C1W

VESTIBULE

102A

103A

EXIST RM

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/2

/2

:3 :0

P

M

51-GI111

FIRST FLOOR - INFECTION

CONTROL & PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

1/8" = 1'-0"

FIRST FLOOR - CONST BARRIER PLAN

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

BASEMENT 001 TELECOM ROOM EXTENDED CARE TYPE C GROUP 1 CLASS II

FIRST FLOOR 103A EXIST RM EXTENDED CARE TYPE B GROUP 1 CLASS II

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

0 8' 16'4'

-ASBESTOS-CONTAMINATED SOIL

CASTLE HILL ASSOCIATES, LLC.

N

S

W

E

BUILDING #51 - SUB-BASEMENT FLOOR PLAN

LEGEND

-POSITIVE SAMPLE LOCATION

-SAMPLE LOCATION

-ASBESTOS-CONTAINING FIRE DOOR

-ASBESTOS-CONTAINING PIPE INSULATION (VERTICAL RISERS)

-ASBESTOS-CONTAINING MASTIC UNDER FLOOR TILE AND CARPET

-ASBESTOS-CONTAINING WHITE PAPER IN ELECTRICAL BOX

-ASBESTOS-CONTAINING PIPE INSULATION (HORIZONTAL RUNS)

-ASBESTOS-CONTAINING MASTIC UNDER 12"X12" FLOOR TILE

-ASBESTOS-CONTAINING TRANSITE INSIDE CONVECTOR

CASTLE HILL ASSOCIATES, LLC.

N

S

WE

BUILDING #51 - BASEMENT FLOOR PLAN

-ASBESTOS-CONTAINING EXTERIOR WALL CAULK

-ASBESTOS-CONTAINING PIPE INSULATION (VERTICAL RISERS)

-ASBESTOS-CONTAINING TRANSITE INSIDE CONVECTOR

-ASBESTOS-CONTAINING CEILING TILE MASTIC

-ASBESTOS-CONTAINING FIRE DOOR

CASTLE HILL ASSOCIATES, LLC.

N

S

WE

BUILDING #51 - FIRST FLOOR PLAN

-ASBESTOS-CONTAINING TRANSITE INSIDE CONVECTOR

-ASBESTOS-CONTAINING CEILING TILE MASTIC

-ASBESTOS-CONTAINING FIRE DOOR

CASTLE HILL ASSOCIATES, LLC.

N

S

WE

BUILDING #51 - SECOND FLOOR PLAN

STORAGE

4C

WHEELCHAIR

WASHER

4D

WHEELCHAIR

CLINIC OFFICE

4E

EMPLOYEE

LOUNGE

6 WHEELCHAIR

CLINIC

OFFICE

4B

H.A.C.

TOILET

4A

FEMALE

LOCKER

BATHROOM

2A

SOILED

UTILITY

1A

PROSTHETICS

OFFICE

PROSTHETICS

STORAGE

OFFICE

9A

[PROSTHETICS

STAIR

HALL

UPPER

SERVICE ROOM

10A

OFFICE

PIPE

CHASE

19A

EXAM

23C

PHONE

CLOSET

1B

CORRIDOR

C0C

INTAKE

23C

WAITING

OCCUPATIONAL

THERAPY

KITCHEN

21B

STORAGE

BATHROOM

21C

SPEECH

THERAPY

21A

FEMALE

TOILET

MALE

TOILET

SOILED

LINEN

STORAGE

ACTIVITIES

HAC

HALL

12A

STAIR

12B

REHAB

OFFICE

17B

SPEECH

OFFICE

17A

MECHANICAL

STAIR

HALL

CORRIDOR

STAFF

17M

TREATMENT 4

17D

TREATMENT 3

17C

TREATMENT 1

17L

ENTRY

12C

ELEV

EQUIP

12D

EQUIP.

STORAGE

17G

TOUCHDOWN

ROOM

17H

STAIR

STAIR

SCI CLINIC

17F

TREATMENT 5

17E

TREATMENT 2

17K

STOR.

17J

INTAKE

17I

RECEPTION

OFFICE

PASSAGE

COCA

STOR.

17J

8'-2"

'-2

/2

51-AS100

TELECOM

ROOM

147 SF

TELECOM

ROOM

IN-03.01

'-3

/2

2'

-6

5' -5

1'-11 1/4" 4'-8 1/2" 1'-6 1/4"

147 SF

TELECOM

ROOM

TELECOM

ROOM

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/3

/2

:2 :1

P

M

51-AS100

BASEMENT PLANS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

03/30/2022

N 0 8' 16'4'

1/8" = 1'-0"

BASEMENT FLOOR - OVERALL PLAN

N

0 4' 8'2'

DE2

RC1 RC2

_DEMOLITION PLAN KEYED NOTES

DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM

REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS

DE2 REMOVE AND SALVAGE DOOR AND PREPARE OPENING TO

ACCOMMODATE PLAN. SEE FLOOR PLAN AND DOOR SCHEDULE

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_FLOOR PLAN KEYED NOTES

FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”

TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH

HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT

OVER FIRE RATING STAMP.

FL2 DOOR, SIZE AS SCHEDULED, FIRE RESISTANT AS SCHEDULED

FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE

TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST

THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS

WITH FIRE CAULK.

FL4 PATCH TO MATCH FINISHES DISTURBED BY CONSTRUCTION TO MATCH

EXISTING; FLOOR AND WALL. CONTRACTOR TO PROVIDE LABOR AND

MATERIAL.

FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_REFLECTED CEILING PLAN KEYED NOTES

RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET

ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE

VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET

ROW OR SECTION.

RC2 OPEN TO STRUCTURAL FLOOR ABOVE

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

DE1

DE1

1/4" = 1'-0"

PARTIAL FLOOR PLAN - RM 001

1/4" = 1'-0"

PARTIAL DEMOLITION PLAN - RM 001

N

0 4' 8'2'

DE1

FL1

FL3

1/4" = 1'-0"

REFLECTED CEILING PLAN

N

0 4' 8'2'

FL20

FL2

FL3

FL3

FL4

FL4

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED

SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN TELECOM

ROOMS.

FL3

1 UPDATE TO BID DOCUMENTS 06/29/22

T

LI

G

H T

LI

G

H T

LIGHTLIGHT

LIG

H

T

LIGHTLIGHT

LIG

H

T

LIGHT

LIGHT

LIG

H

T

LIGHT

LI

G

H T

LIGHT

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

ENTRY

ELECT.

ROOM

STORAGE

116A

RECREATION

CLOSET

TOILET

111A

2 BED

2 BED

2 BED

CLOSET

TOILET

112A

1 BED

NURSES

SUBSTATION

MULTI.

ROOM

1 BED

TOILET

108A

OFFICE

CONF

CLASS

LINEN

CHUTE

DINING

SOILED

UTILITY

STAIR 1

1 BED

CLEAN

UTIL/LINEN

BATHING

CONGREGATE

HAC

1 BED

TOILET

121A

TOILET

126A

2 BED

STAFF

TOILET

NURSE

STATION

MED

TOILET

123A

STAIR

2 BED

2 BED

EQ STOR

VISITATION WARD

SUPPLY

CLEAN

UTIL/LINEN

TOILET

150A

2 BED

PUBLIC

TOILET

OFFICE

ADMIN.

ASSIST

ALCOVE

ELEV

BATH

163A

NURSE

PRACTIONER

CLOSET

2 BED

2 BED

TOILET

156A

2 BED

CORR

TOILET

157A

1 BED

SOILED

UTILITY

1 BED

TOILET

153A

CLOSET

2 BED

HAC

141STAIR

134B

STORAGE

STOR

135A

TOILET

136A

2 BED

DINING

VESTIBULE

134A

STAIR

2 BED

2 BED

2 BED

TOILET

138A

2 BED

TOILET

147A

CLOSET

CLOSET

2 BED

LOUNGE

142 STORAGE

CONGREGATE BATH

PATIENT LAUNDRY

STAIR

CORRIDOR

C1C

CORRIDOR

C1NE

CORRIDOR

C1SE

CORRIDOR

C1W

VESTIBULE

102A

103A

EXIST RM

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/2

/2

:3 :2

P

M

51-AS110

FIRST FLOOR - OVERALL PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

03/30/2022

1/8" = 1'-0"

FIRST FLOOR - OVERALL PLAN

N 0 4' 8'2'

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED

SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN TELECOM

ROOMS.

L

IG

H T

LIGHTLIGHT

LIGHT

LIGHT

LIGHT

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

CL. LIN.

ELEC.

CLOS.

OFFICE

ANTE

ROOM

1 BED

ISOLATION

BATH

TREATMENT &

NURSE PRAC.

OFFICE

STAIR

HALL

1 BED

BATH

1 BED

PATIENT

ROOM

4 BED

DAYROOM

STAIR

2 BED

BATH

2 BED

TOILET

STOR.

2 BED

2 BED

BATH

1 BED

1 BED

1 BED

1 BED

2 BED

HSKPG

SOILED

UTIL

CONF.

GROUP RM

ELEVATOR

E02

STORAGE

DINING

MULTI-PURPOSE

LAUNDRY

CHUTE

BATH

TOILET

2 BED

CLEAN

UTILITY

244SOILED

UTILITY

STOR

HSKPG

STOR.

2 BED

1 BED

1 BED

1 BED

BATH

1 BED

2 BED

2 BED

TOILET

2 BED

BATH

STAIR

HALL

2 BED

4 BED

2 BED

2 BED

BATH

1 BED

STAIR

HALL 1

LOCKER

MEDICATION

CHART

NURSES

STATION

DAY ROOM

CORRIDOR

CORR

297A

STAIR

297B

CORRIDOR

C2C

CORRIDOR

C2W

CORRIDOR

C2E

SHOWER

SHOWER

CLEAN

LINEN

STOR.

SHOWER

SHOWER

SHOWER

LINEN

CART

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -5

-R

E

M a rk fo rt

.r v t

/2

/2

:3 :2

P

M

51-AS120

SECOND FLOOR - OVERALL

PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

03/30/2022

1/8" = 1'-0"

SECOND FLOOR - OVERALL PLAN

N 0 4' 8'2'

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED

SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN TELECOM

ROOMS.

376 212 292

89 52

3 3

13 6

14 14

4C

STORAGE

WHEELCHAIR

4D

WASHER

WHLCHAIR

4B

OFFICE

CORR4E

CLINIC

WHEELCHAIR

LOUNGE

EMPLOYEE

STORAGE

PROSTHETICS

OFFICE

PROSTHETICS

9A

OFFICE

STAIR

10A

SERVICE ROOM

UPPER

OFFICE

LOCKER

FEMALE 1A

UTILITY

SOILED

2A

BATH

23D

EXAM

23C

INTAKE

WAITING

C0C

CORRIDOR

ACTIVITIES

12A

CORRIDOR

12B

STAIR

12D

MECH

ELEV

12C

ENTRY

STORAGE 14

HAC

MECHANICAL

STAIR

LINEN

CLEAN

STORAGE

21C

BATH

21B

KITCHEN

BATH

FEMALE

BATH

MALE

19A

CHASE

PIPE

21A

THERAPY

SPEECH

THERAPY

OCCUPATIONAL

STAIR

STAIR

17E

TREATMENT 5

17K

TREATMENT 2

17D

TREATMENT 4

17C

TREATMENT 3

17L

TREATMENT 1

17M

STAFF

17B

OFFICE

REHAB

17A

OFFICE

SPEECH

17J

STOR.

17I

INTAKE

CORRIDOR

23B

OFFICECOCA

CORRIDOR

23A

RECEPTION

17J

STOR.

17F

CLINIC

SCI

17G

STORAGE

EQUIP

17H

ROOM

TOUCHDOWN

LIMITS OF DATA CABLING DEMOLITION

2D/2

4D

4D2D/2

5D

4D 6D/1

4D

4D

4D

3D

2D

1V

4D 4D

4D 4D

8D

4D 4D

4D

2D/2 3D/1

3D/1

4D

4D

4D

4D

4D

4D

4D

3D

4D4D

2D

1V

3D/2

2D

D

3D

4D 4D

4D4D

4D

4D

4D

WAP

4D

4D

4D

2D

3D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

D

4D

4D D

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E E

E

E

E

E

E

E E E

E E

E

E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E E

E

E

E

E

E

51-TD100

E

E

E

E

E 12"x4"12"x4"

WAP

"x

4"

E

"x

4"

12"x4"

"x

4"

WAP

TELECOM ROOM

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/2

/2

:1

:5

P

M

51-TD100

BASEMENT FLOOR PLAN -

ELECTRICAL DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

06/29/2022

KSB SSK

16305

N

0 8' 16'4' 1/8" = 1'-0"

BASEMENT FLOOR PLAN - TELECOM - DEMOLITION

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

1/4" = 1'-0"

TELECOM DEMO - ENLARGED PLAN - EXIST TR 001

N

0 4' 8'2'

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

WS1

WS3WS4

WS2

LIG

H

T

LI

G

H T

LI

G

H T

LIGHTLIGHT

LIG

H

T

LIGHTLIGHT

LIG

H

T

LIGHT

LIGHT

LIG

H

T

LIGHT

LI

G

H T

LIGHT

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

2 BED

111A

BATH

2 BED

C1NE

CORR

2 BED

CLOSET

CLOSET

112A

BATH

1 BED

116A

STORAGE

1 BED

STATION

NURSE

ROOM

MULTI.

DINING

WARD

LOCKED

OFFICE

STAIR

UTILITY

CLEAN

UTILITY

SOILED

1 BED

126A

BATH

BATH

HAC

1 BED

1221A

BATH

STAIR

2 BED

EQUIP STOR

C1SE

CORRIDOR

2 BED

123A

BATH

2 BED

STAFF

MED

STATION

NURSE

CONF

CLASS

LAUNDRY

CHUTE

ELECT

ENTRY

OFFICE

ASSIST.

ADMIN.

BATH

E01

ELEV

PRACTIONER

NURSE

163A

BATH

C1C

CORRIDOR

135A

STOR

136A

BATH

2 BED

STORAGE

DINING

134A

CORRIDOR

134B

STAIR

2 BED

UTILITY

SOILED

SUPPLY

WARD

C1W

CORR

1 BED

CLOSET

157A

BATH

CLOSET

2 BED 155

2 BED

2 BED

156A

BATH

153A

BATH

1 BED

2 BED

150A

BATH

UTILITY

CLEAN

2 BED137

STAIR

2 BED 149

2 BED

CLOSET

CLOSET

138A

BATH

147A

BATH

2 BED

2 BED

HAC

LOUNGE

ROOM

SHOWER

STORAGE

STAIR

108A

BATH

134C

VESTIBULE

CONVECTOR

WS1

WS2

WS1

WS3WS4

WS2

LIG

H

T

LI

G

H T

LI

G

H T

LIGHTLIGHT

LIG

H

T

LIGHTLIGHT

LIG

H

T

LIGHT

LIGHT

LIG

H

T

LIGHT

LI

G

H T

LIGHT

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

2 BED

111A

BATH

2 BED

C1NE

CORR

2 BED

CLOSET

CLOSET

112A

BATH

1 BED

116A

STORAGE

1 BED

STATION

NURSE

ROOM

MULTI.

DINING

WARD

LOCKED

OFFICE

STAIR

UTILITY

CLEAN

UTILITY

SOILED

1 BED

126A

BATH

BATH

HAC

1 BED

1221A

BATH

STAIR

2 BED

EQUIP STOR

C1SE

CORRIDOR

2 BED

123A

BATH

2 BED

STAFF

MED

STATION

NURSE

CONF

CLASS

LAUNDRY

CHUTE

ELECT

ENTRY

OFFICE

ASSIST.

ADMIN.

BATH

E01

ELEV

PRACTIONER

NURSE

163A

BATH

C1C

CORRIDOR

135A

STOR

136A

BATH

2 BED

STORAGE

DINING

134A

CORRIDOR

134B

STAIR

2 BED

UTILITY

SOILED

SUPPLY

WARD

C1W

CORR

1 BED

CLOSET

157A

BATH

CLOSET

2 BED 155

2 BED

2 BED

156A

BATH

153A

BATH

1 BED

2 BED

150A

BATH

UTILITY

CLEAN

2 BED137

STAIR

2 BED 149

2 BED

CLOSET

CLOSET

138A

BATH

147A

BATH

2 BED

2 BED

HAC

LOUNGE

ROOM

SHOWER

STORAGE

STAIR

108A

BATH

134C

VESTIBULE

CONVECTOR

WS1

WS2

ELECT

ELECT

51-TD110

LIMITS OF DATA CABLING DEMOLITION

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

2V 2V

2V 2V

2V2V

2V2V

2V 2V

2V 2V

2V2V

2V

2V

2V

2V

D

2D/2

2D

2D 1V

4D/1

4D

4D

4D

2D

2D

5D

2D

5D

2D/2

D D

D

2D

2V2V

2V

2V

2V

D

4D

4D 2V 2V

2V 2V

2V 2V

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E E

E E

E E

E E

E

EE

E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E

E

E

E

E

E

E

E

E

E E

E

EE

E

E

E E E

E

E

E E

E E

2V

2V 2V

2V

E

3D/2V

E

E

E

E

E E EE

E E

E

E

E

E

"x

2"

"x 2"

12"x2"

"x

2"

"x

2"

12"x2"

12"x2"

"x

2"

"x 2"

12"x4"

CABLE

TRAY (E)

DR

TW

PP

SP

R

E

E

D

CABLE

TRAY

E

DATA

RACK

2 3 12 "x

2"

D

EE

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/2

/2

:1

:5

P

M

51-TD110

FIRST FLOOR PLAN -

ELECTRICAL DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

06/29/2022

KSB SSK

16305

N

0 8' 16'4' 1/8" = 1'-0"

FIRST FLOOR PLAN - TELECOM - DEMOLITION

1/4" = 1'-0"

TELECOM DEMO - ENLARGED PLAN - EXIST RM 103A

N

0 4' 8'2'

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

2. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION.

EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK PLANS FOR SERVING

COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.

3. EXISTING CABLE TRAY, SECURITY CAMERAS, GROUND BUS BARS, AND RACKS FROM DECOMMISSIONED

ROOMS ARE TO BE REUSED, WHEN POSSBILE, IN NEW CONSTRUCTION TRS.

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE

RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE

PROJECT.

1. ROOM 103A

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 398

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

1 UPDATE TO BID DOCUMENTS 6/29/2022

CC

1 BED

LI

G

H T

LIGHTLIGHT

LIGHT

LIGHT

LIGHT

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

A O

V

AOVAOV

AOV

AOV

AOV

AOV AOV

A O

V A O

V

AOV

AOV

AOV

AOV

AOV

AOV

AOV

AOV

AOV

AOV

AOV

AOV

AOV

AOV

BATH

WS5

WS3 WS2 WS1

WS4

WS6

WS7

MIN.

4'-10"

2'-4"

NC

NC

1 BED

BATH 236

1 BED

1 BED

2 BED

1 BED

2 BED

2 BED

TOILET

STOR

C2E

CORRIDOR

HAC

STOR

UTILITY

SOILED

SUPPLY

SPD 245

2 BED

BATH

BATH

LAUNDRY CHUTE

STATION

NURSE

CHART

MED

LOCKER207

LINEN

CLEAN

STAIR

2 BED

BATH

2 BED

STAIR

4 BED

2 BED

2 BED

BATH

1 BED

DINING

DATA

PHONE/

E01

ELEV

C2C

CORRIDOR

ROOM

ANTE

ISOLATION

1 BED

OFFICE

BATH

OFFICE

ROOM

GROUP

STORAGE

UTILITY

SOILED

MANAGER

NURSE

STAIR

DAY ROOM

297A

CORRIDOR

297B

STAIR

1 BED

BATH 263

1 BED

2 BED

1 BED

1 BED

2 BED

2 BED

CL LIN

HAC

C2W

CORRIDOR

STORAGE

BATH

2 BED

1 BED

BATH

1 BED

ROOM

PATIENT

DAYROOM

2 BED

STAIR

BATH

SHOWER

SHOWER

CART

LINEN

297C

VESTIBULE

VESTIBULE

LIMITS OF DATA CABLING DEMOLITION

WAP

WAP

WAP

WAP

WAP

WAP

D/1 D/1

2D 3D/2

3D 3D

D/1

D/1

D/1 4D

2V 2V

2V

2V

2V

2V

2V

2V

2V

2V

4D

4D

4D

4D

2V

2V

2V

2V

2V

2V

4D

2V

2V

2V

2V 2V

2V

2V

2V

2V

2V

2V

2V

2V

2V

2V

2V 2V

2V

2V

E

E

E

E

E

E

EE

E

E E

E

E

E

E

E

E

E

E

E E

E

E

E

E

E

E

EE

E

E E E

E

E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E

E

E

E

E

E

E

E

E

4D E

E E

E

E

E

E

E

E

"x

2"

"x

2"

"x

2"

12"x2"

"x

2"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/2

/2

:1

:5

P

M

51-TD120

SECOND FLOOR PLAN -

ELECTRICAL DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

06/29/2022

KSB SSK

16305

N

0 8' 16'4' 1/8" = 1'-0"

SECOND FLOOR PLAN - ELECTRICAL - DEMOLITION

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

STORAGE

4C

WHEELCHAIR

WASHER

4D

WHEELCHAIR

CLINIC OFFICE

4E

EMPLOYEE

LOUNGE

6 WHEELCHAIR

CLINIC

OFFICE

4B

H.A.C.

TOILET

4A

FEMALE

LOCKER

BATHROOM

2A

SOILED

UTILITY

1A

PROSTHETICS

OFFICE

PROSTHETICS

STORAGE

OFFICE

9A

[PROSTHETICS

STAIR

HALL

UPPER

SERVICE ROOM

10A

OFFICE

PIPE

CHASE

19A

EXAM

23C

PHONE

CLOSET

1B

CORRIDOR

C0C

INTAKE

23C

WAITING

OCCUPATIONAL

THERAPY

KITCHEN

21B

STORAGE

BATHROOM

21C

SPEECH

THERAPY

21A

FEMALE

TOILET

MALE

TOILET

SOILED

LINEN

STORAGE

ACTIVITIES

HAC

HALL

12A

STAIR

12B

REHAB

OFFICE

17B

SPEECH

OFFICE

17A

MECHANICAL

STAIR

HALL

CORRIDOR

STAFF

17M

TREATMENT 4

17D

TREATMENT 3

17C

TREATMENT 1

17L

ENTRY

12C

ELEV

EQUIP

12D

EQUIP.

STORAGE

17G

TOUCHDOWN

ROOM

17H

STAIR

STAIR

SCI CLINIC

17F

TREATMENT 5

17E

TREATMENT 2

17K

STOR.

17J

INTAKE

17I

RECEPTION

OFFICE

PASSAGE

COCA

STOR.

17J

LIMITS OF DATA CABLING REPLACEMENT

FROM ROOM 001

5D

2D/2 4D

4D

6D/14D

4D

4DWAP

WAP

3D

2D

WAP

1V 4D

4D 4D

WAP

WAP

4D

WAP

WAP

WAP

4D

4D D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

WAP

3D

3D

3D

D

4D WAP

WAP

2D/2

4D

WAP

4D

4D

3D/1

3D/12D/2

WAP

3D/2

1V

2D

2D

2D

4D

4D

4D 4D

4D4D

4D 4D

4D

4D

4D

4D

D

4D

4D

WAP

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E E

E

E

E

E

E

E E E

E E

E

E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E E

E

E

E

E

12"x4"12"x4"

VERTICAL AND

HORIZONTAL CABLING

ROUTE TO ROOM 103A

E

CABLE TRAY

TELECOM ROOM

51-TN400

E

E

E

E

E

"x

4"

WAP4"

C4 126"

E

12"x4"

"x

4"

"x

4"

E

E

4"4"

4"4"

"x

4"

"x 4"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/2

/2

:1

:5

P

M

51-TN100

BASEMENT FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

06/29/2022

KSB SSK

16305

N

0 8' 16'4' 1/8" = 1'-0"

BASEMENT FLOOR PLAN - TELECOMMUNICATIONS

SHEET NOTES:

1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING TELECOM CABLE

TRAY.

2. PROVIDE JUNCTION BOX TO CONNECT EXISTING FIBER CONDUIT ENTRY TO EXTEND CONDUIT

PATHWAY TO THE NEW TELECOM ROOM.

GENERAL NOTES:

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

T

LI

G

H T

LI

G

H T

LIGHTLIGHT

LIG

H

T

LIGHTLIGHT

LIG

H

T

LIGHT

LIGHT

LIG

H

T

LIGHT

LI

G

H T

LIGHT

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

ENTRY

ELECT.

ROOM

STORAGE

116A

RECREATION

CLOSET

TOILET

111A

2 BED

2 BED

2 BED

CLOSET

TOILET

112A

1 BED

NURSES

SUBSTATION

MULTI.

ROOM

1 BED

TOILET

108A

OFFICE

CONF

CLASS

LINEN

CHUTE

DINING

SOILED

UTILITY

STAIR 1

1 BED

CLEAN

UTIL/LINEN

BATHING

CONGREGATE

HAC

1 BED

TOILET

121A

TOILET

126A

2 BED

STAFF

TOILET

NURSE

STATION

MED

TOILET

123A

STAIR

2 BED

2 BED

EQ STOR

VISITATION WARD

SUPPLY

CLEAN

UTIL/LINEN

TOILET

150A

2 BED

PUBLIC

TOILET

OFFICE

ADMIN.

ASSIST

ALCOVE

ELEV

BATH

163A

NURSE

PRACTIONER

CLOSET

2 BED

2 BED

TOILET

156A

2 BED

155CORR

TOILET

157A

1 BED

SOILED

UTILITY

1 BED

TOILET

153A

CLOSET

2 BED

HAC

141STAIR

134B

STORAGE

STOR

135A

TOILET

136A

2 BED

DINING

VESTIBULE

134A

STAIR

2 BED

2 BED

2 BED

TOILET

138A

2 BED

TOILET

147A

CLOSET

CLOSET

2 BED

LOUNGE

142 STORAGE

CONGREGATE BATH

PATIENT LAUNDRY

STAIR

CORRIDOR

C1C

CORRIDOR

C1NE

CORRIDOR

C1SE

CORRIDOR

C1W

VESTIBULE

102A

LIG

H

T

LI

G

H T

LI

G

H T

LIGHTLIGHT

LIG

H

T

LIGHTLIGHT

LIG

H

T

LIGHT

LIGHT

LIG

H

T

LIGHT

LI

G

H T

LIGHT

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

ENTRY

ELECT.

ROOM

STORAGE

116A

RECREATION

CLOSET

TOILET

111A

2 BED

2 BED

2 BED

CLOSET

TOILET

112A

1 BED

NURSES

SUBSTATION

MULTI.

ROOM

1 BED

TOILET

108A

OFFICE

CONF

CLASS

LINEN

CHUTE

DINING

SOILED

UTILITY

STAIR 1

1 BED

CLEAN

UTIL/LINEN

BATHING

CONGREGATE

HAC

1 BED

TOILET

121A

TOILET

126A

2 BED

STAFF

TOILET

NURSE

STATION

MED

TOILET

123A

STAIR

2 BED

2 BED

EQ STOR

VISITATION WARD

SUPPLY

CLEAN

UTIL/LINEN

TOILET

150A

2 BED

PUBLIC

TOILET

OFFICE

ADMIN.

ASSIST

ALCOVE

ELEV

BATH

163A

NURSE

PRACTIONER

CLOSET

2 BED

2 BED

TOILET

156A

2 BED

155CORR

TOILET

157A

1 BED

SOILED

UTILITY

1 BED

TOILET

153A

CLOSET

2 BED

HAC

141STAIR

134B

STORAGE

STOR

135A

TOILET

136A

2 BED

DINING

VESTIBULE

134A

STAIR

2 BED

2 BED

2 BED

TOILET

138A

2 BED

TOILET

147A

CLOSET

CLOSET

2 BED

LOUNGE

142 STORAGE

CONGREGATE BATH

PATIENT LAUNDRY

STAIR

CORRIDOR

C1C

CORRIDOR

C1NE

CORRIDOR

C1SE

CORRIDOR

C1W

VESTIBULE

102A

103A

EXIST RM

LIMITS OF DATA CABLING REPLACEMENT

FROM ROOM 103A

WAP

WAP

WAP

WAP

4D

4D

D

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

WAP

5D

5D

4D 4D

4D

4D/1

1V 2D

2D

WAP

2V

2V

2V

2V

2V 2V

2V 2V

2V

2V

2V

2V

2V

2V 2V

2V 2V

2V

2V

2V

2V

D

D D

2D

2D

2D

2D 2D/2

2D/2

D

2V

2V

2V2V

2V 2V

2V2V

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E E

E E

E E

E E

E

EE

E

E

E

E

E

E

E

E

E

E

E

E E

E

E

E

E

E

E

E

E

E

E

E

E E

E

EE

E

E

E E E

E

E

12"x2" 12"x2"

"x

2"

"x

2"

12"x2"

1CABLE TRAY

2V

2V

2V

2V

E E

E E

E

3D/2V

E

E

E

E

E

E

E

E

E E

E

E

E

E

"x

2"

"x 2"

"x

2"

"x 2"

C4 126"

12" LADDER

F2

12"x4"

CABLE

TRAY (E)

"x

4"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/2

/2

:1

:5

P

M

51-TN110

FIRST FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

06/29/2022

KSB SSK

16305

N

0 8' 16'4' 1/8" = 1'-0"

FIRST FLOOR PLAN - TELECOMMUNICATIONS

SHEET NOTES:

1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF

THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND

DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING

TELECOM CABLE TRAY.

GENERAL NOTES:

CC

LI

G

H T

LIGHTLIGHT

LIGHT

LIGHT

LIGHT

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

LIGHT

CL. LIN.

ELEC.

CLOS.

OFFICE

ANTE

ROOM

1 BED

ISOLATION

BATH

TREATMENT &

NURSE PRAC.

OFFICE

STAIR

HALL

1 BED

BATH

1 BED

PATIENT

ROOM

4 BED

DAYROOM

STAIR

2 BED

BATH

2 BED

TOILET

STOR.

2 BED

2 BED

BATH

1 BED

1 BED

1 BED

1 BED

2 BED

HSKPG

SOILED

UTIL

CONF.

GROUP RM

ELEVATOR

E02

STORAGE

DINING

MULTI-PURPOSE

LAUNDRY

CHUTE

BATH

TOILET

2 BED

CLEAN

UTILITY

244SOILED

UTILITY

STOR

HSKPG

STOR.

2 BED

1 BED

1 BED

1 BED

BATH

1 BED

2 BED

2 BED

TOILET

2 BED

BATH

STAIR

HALL

2 BED

4 BED

2 BED

2 BED

BATH

1 BED

STAIR

HALL 1

LOCKER

MEDICATION

CHART

NURSES

STATION

DAY ROOM

CORRIDOR

CORR

297A

STAIR

297B

CORRIDOR

C2C

CORRIDOR

C2W

CORRIDOR

C2E

SHOWER

SHOWER

CLEAN

LINEN

STOR.

SHOWER

SHOWER

SHOWER

LINEN

CART

LIMITS OF DATA CABLING REPLACEMENT

FROM ROOM 103A

4D

4D

4D

4D

3D3D

D/1

WAP

WAP

WAP

WAP

WAP

WAP

2D

D/1

3D/2

D/1

D/1

D/1

4D

4D

2V

2V

2V

2V

2V

2V

2V 2V

2V

2V

2V

2V

2V

2V

2V

2V

E

E

E

E

E

E

EE

E

E E

E

E

E

E

E

E

E

E

E E

E

E

E

E

E

E

EE

E

E E E

E

E

E

2V

2V

2V

2V

2V

2V 2V

2V

2V

2V

2V

2V

2V

2V

2V

2V

2V

2V

2V

E

E

E

E

E

E

E

E

E

E E

E

E

E

E

E

E

E

E

12"x2"

E

E

E

CABLE TRAY

E 4D

"x

2"

"x 2"

"x

2"

"x 2"

E E

E

E

E

E

E

E

"x

4"

12" LADDER

F2

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/2

/2

:1

:5

P

M

51-TN120

SECOND FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

06/29/2022

KSB SSK

16305

N

0 8' 16'4' 1/8" = 1'-0"

SECOND FLOOR PLAN - TELECOMMUNICATIONS

SHEET NOTES:

1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF

THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND

DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING

TELECOM CABLE TRAY.

GENERAL NOTES:

WHEELC HAIR

STOR AGE

4C

WHEELC HAIR

WASH ER

4D

WHEELC HAIR

CLINIC OFFICE

4E

EMP LOYE E

LOU NGE

6 WHEELC HAIR

CLINIC

OFFICE

4B

H.A.C.

TOILET

4A

FEMALE

LOCK ER

BATHR OOM

2A

SOILED

UTILITY

1A

PROS THETICS

OFFICE

PROS THETICS

STOR AGE

OFFICE

9A

[PROSTH ETICS

STAIR

HALL

UPPER

SERVI CE R OOM

10A

OFFICE

PIPE

CHASE

19A

EXA M

23C

PHONE

CLOSE T

1B

CORRI DOR

C0C

INTAKE

23C

WAITING

OCCU PATION AL

THER APY

KITCHEN

21B

STOR AGE

BATHR OOM

21C

SPEECH

THER APY

21A

FEMALE

TOILET

MALE

TOILET

SOILED

LINEN

STOR AGE

ACTIVITIES

HAC

HALL

12A

STAIR

12B

REHAB

OFFICE

17B

SPEECH

OFFICE

17A

MECHAN ICAL

STAIR

HALL

CORRI DOR

STA FF

17M

TREA TMEN T 4

17D

TREA TMEN T 3

17C

TREA TMEN T 1

17L

ENTRY

12C

ELEV

EQUIP

12D

EQUIP.

STOR AGE

17G

TOU CH DOWN

ROOM

17H

STAIR

STAIR

SCI CLINIC

17F

TREA TMEN T 5

17E

TREA TMEN T 2

17K

STOR.

17J

INTAKE

17I

RECEP TION

OFFICE

PAS SA GE

COC A

STOR.

17J

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/2

/2

:1

:0

P

M

51-TN200

BASEMENT FLOOR PLAN -

TELECOM - CABLE DISTANCE

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

06/29/2022

KSB SSK

16305

1" = 30'-0"

BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE

0 30' 60'15'

CR

AC

C

51-TN400

1 - a b

1 - c d

TELECOM ROOM

W

KEYPAD

CABLE TRAY

DATA RACK

C4 126"

18"x4"

"x

4"

18"x4"

18"x4"

"x

4"

"x

4"

"x 4"

"x

4"

E

4"

4"

4"

4"

AC1

NOTES:

1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.

2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.

3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.

4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO

SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET. (NOT TO EXCEED 288 PORTS PER RACK).

5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.

6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER

ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.

7. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.

VERTICAL CABLE

MANAGEMENT (TYP)

RACK 1

1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL

1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)

1U 48 PORT CAT5E BACKBONE PATCH PANEL

1U CABLE MANAGEMENT

1U CABLE MANAGEMENT

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

6U 5KW RACK MOUNT UPS

V E

R T

IC

A

L R

A C

K P

D U

V E

R T

IC

A

L R

A C

K P

D U

NEMA L21-20R (TYP)

CHANNEL RACK (TYP)

D

PROVIDE DATA CABLE TO RACK

MOUNTED UPS FOR CONNECTION

TO MONITORING SYSTEM

RACK 1

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

1U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

6U 5KW RACK MOUNT UPS

V E

R T

IC

A

L R

A C

K P

D U

V E

R T

IC

A

L R

A C

K P

D U

NEMA L21-20R (TYP)

D

RACK 2

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

1U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

RACK 2

6U SPACE FOR FUTURE USE. PROVIDE BLANK

PANELS FOR UNUSED SPACES.

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

SPACE FOR FUTURE HORIZONTAL CABLE

DISTRIBUTION. PROVIDE BLANKING PANELS FOR

UNUSED SPACES.

6U SPACE FOR FUTURE USE. PROVIDE BLANK

PANELS FOR UNUSED SPACES.

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

SPACE FOR FUTURE HORIZONTAL CABLE

DISTRIBUTION. PROVIDE BLANKING PANELS FOR

UNUSED SPACES.

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/2

/2

:1

:0

P

M

51-TN400

ENLARGED PLANS -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

06/29/2022

KSB SSK

16305

N

0 2' 4'1'

0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.

THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED

FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE

PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.

1. ROOM 001

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 398 FROM ROOM 103A

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6A): 398

DATA (CAT6): 0

1/4" = 1'-0"

1 - a

1/4" = 1'-0"

1 - b

1/4" = 1'-0"

1 - c

1/4" = 1'-0"

1 - d

1/2" = 1'-0"

ENLARGED PLAN - TR 001 - TELECOM - CABLE TRAY AND DATA

GENERAL NOTES:

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

NOT TO SCALE

COMMUNICATIONS - TYPICAL TWO RACK ELEVATION WITH RACK MOUNT UPS - EXIST TR 001

SHEET NOTES:

1. IF NO ACCESS CONTROL PANEL IS PRESENT, PROVIDE A NEW ACCESS CONTROL PANEL TO BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND KEYPAD FOR THIS ROOM TO BE WIRED TO THE NEW ACCESS CONTROL PANEL. EXISTING CARD READERS AND KEYPADS WILL BE MOVED TO THE NEW CONTROL PANEL

UNDER A DIFFERENT PROJECT.

SOLARIUM

WHEELCHAIR

STORAGE

4C

WHEELCHAIR

WASHER

4D

WHEELCHAIR

CLINIC OFFICE

4E

EMPLOYEE

LOUNGE

6 WHEELCHAIR

CLINIC

OFFICE

4B

H.A.C.

TOILET

4A

FEMALE

LOCKER

BATHROOM

2A

SOILED

UTILITY

1A

PROSTHETICS

OFFICE

PROSTHETICS

STORAGE

OFFICE

9A

[PROSTHETICS

STAIR

HALL

UPPER

SERVICE ROOM

10A

OFFICE

PIPE

CHASE

19A

EXAM

23C

PHONE

CLOSET

1B

CORRIDOR

C0C

INTAKE

23C

WAITING

OCCUPATIONAL

THERAPY

KITCHEN

21B

STORAGE

BATHROOM

21C

SPEECH

THERAPY

21A

FEMALE

TOILET

MALE

TOILET

SOILED

LINEN

STORAGE

ACTIVITIES

HAC

HALL

12A

STAIR

12B

REHAB

OFFICE

17B

SPEECH

OFFICE

17A

MECHANICAL

STAIR

HALL

CORRIDOR

STAFF

17M

TREATMENT 4

17D

TREATMENT 3

17C

TREATMENT 1

17L

ENTRY

12C

ELEV

EQUIP

12D

EQUIP.

STORAGE

17G

TOUCHDOWN

ROOM

17H

STAIR

STAIR

SCI CLINIC

17F

TREATMENT 5

17E

TREATMENT 2

17K

STOR.

17J

INTAKE

17I

RECEPTION

OFFICE

PASSAGE

COCA

STOR.

17J

8'-2"

'-2

/2

TELECOM

ROOM

51-ECB-1

51-E300

51-E300

51-E300

51-E300

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/2

/2

:3

:4

P

M

51-E100

BASEMENT FLOOR PLAN -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

0 8' 16'4'

N

SCALE: 1/8" = 1'-0"51-E100

1 BASEMENT FLOOR PLAN - ELECTRICAL

100% CD 03/30

53095

E

H

T

LI

G

H T

LI

G

H T

LIGHTLIGHT

LIG

H

T

LIGHTLIGHT

LIG

H

T

LIGHT

LIGHT

LIG

H

T

LIGHT

LI

G

H T

LIGHT

LIGHT LIGHT

LIGHT

LIGHT

LIGHT

ENTRY

ELECT.

ROOM

STORAGE

116A

RECREATION

CLOSET

TOILET

111A

2 BED

2 BED

2 BED

CLOSET

TOILET

112A

1 BED

NURSES

SUBSTATION

MULTI.

ROOM

1 BED

TOILET

108A

OFFICE

CONF

CLASS

LINEN

CHUTE

DINING

SOILED

UTILITY

STAIR 1

1 BED

CLEAN

UTIL/LINEN

BATHING

CONGREGATE

HAC

1 BED

TOILET

121A

TOILET

126A

2 BED

STAFF

TOILET

NURSE

STATION

MED

TOILET

123A

STAIR

2 BED

2 BED

EQ STOR

VISITATION WARD

SUPPLY

CLEAN

UTIL/LINEN

TOILET

150A

2 BED

PUBLIC

TOILET

OFFICE

ADMIN.

ASSIST

ALCOVE

ELEV

BATH

163A

NURSE

PRACTIONER

CLOSET

2 BED

2 BED

TOILET

156A

2 BED

155CORR

TOILET

157A

1 BED

SOILED

UTILITY

1 BED

TOILET

153A

CLOSET

2 BED

HAC

141STAIR

134B

STORAGE

STOR

135A

TOILET

136A

2 BED

DINING

VESTIBULE

134A

STAIR

2 BED

2 BED

2 BED

TOILET

138A

2 BED

TOILET

147A

CLOSET

CLOSET

2 BED

LOUNGE

142 STORAGE

CONGREGATE BATH

PATIENT LAUNDRY

STAIR

CORRIDOR

C1C

CORRIDOR

C1NE

CORRIDOR

C1SE

CORRIDOR

C1W

VESTIBULE

102A

103A

EXIST RM

B51IT-1-CR-5,7

B51IT-1-5

WP

GFI

CU-51-1

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/2

/2

:3

:4

P

M

51-E101

FIRST FLOOR PLAN -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

0 8' 16'4'

N

SCALE: 1/8" = 1'-0"51-E101

1 FIRST FLOOR PLAN - ELECTRICAL

KEYNOTES:

1. PROVIDE ELECTRICAL CONNECTION TO

CONDENSING UNIT, AS REQUIRED.

COORDINATE FINAL LOCATION AND

CONNECTION REQUIREMENTS WITH

MECHANICAL.

MECHANICAL

H

E

SD

51MDP 51-ATS

ES-ATS

EC-TS

8'-2"

'-2

/2

TELECOM

ROOM

8'-2"

'-2

/2

TELECOM

ROOM

A

B51IT-1-CR

a

A

B51IT-1

b a b

8'-2"

'-2

/2

TELECOM

ROOM

B51IT-1

B51IT-1-CR

AC-51-1

B51IT-1-1

B51IT-1-CR-1

B51IT-1-1

B51IT-1-CR-1

B51IT-1-1

B51IT-1-CR-1

B51IT-1-CR-2,4,6

B51IT-1-2,4,6

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/2

/2

:3

:5

P

M

51-E300

ENLARGED PLANS -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

N O R

HT

1/4" = 1'-0"

BASEMENT FLOOR PLAN ENLARGED - ELECTRICAL

N O R

HT

1/4" = 1'-0"

TELECOM ROOM - ELECTRICAL DEMOLITION

N O R

HT

1/4" = 1'-0"

TELECOM ROOM - LIGHTING

N O R

HT

1/4" = 1'-0"

TELECOM ROOM - POWER & SYSTEM

KEYNOTES:

1. INDOOR UNIT TO BE POWERED BY OUTDOOR

UNIT. COORDINATE EXACT LOCATION WITH

M.C.

2. CONNECT SMOKE DETECTOR TO NEAREST

EXISTING SLC.

3. DISCONNECT AND REMOVE EXISTING LIGHTS

AND RECEPTACLES IN ROOM. MAINTAIN

CIRCUIT CONTINUITY TO ADJOINING ROOMS.

4. COORDINATE FINAL LOCATION OF

RECEPTACLE L21-30R WITH TELECOM

CONTRACTOR. PROVIDE 3/4"C-4#10, 1#12 GND

TO PANEL FOR EACH RECEPTACLE.

5. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-

PHASE,4-WIRE RACK MOUNTED UPS FOR EACH

RACK TOWER.

6. PROVIDE APC#AP8861 RPDU RACK PDU 2G

WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,

ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R

OUTLETS. PROVIDE TWO PER RACK, MOUNTED

PER MANUFACTURER'S REQUIREMENTS.

7. PROVIDE ONE RACK MOUNTED ZONE PDU

UNIT. 30 AMP 3 PHASE, 120/208V, 5-WIRE WITH

(4) L21-30R, (6) 5-20R AND TWO 10' POWER

CORDS. ZONIT#ZPDS-208V-30A-L21-4L21-20R-

CR.#

BASEMENT

FIRST FLOOR

B51IT-1

100Y

51MDP

B51IT-1-CR

100Y

51EC-B1

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/2

/2

:3

:5

P

M

51-E500

ELECTRICAL DIAGRAMS

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

N O R

HT

12" = 1'-0"

PARTIAL POWER RISER

KEYNOTES:

1. PROVIDE NEW 100A/3P CIRCUIT BREAKERS IN

EXISTING PANEL TO MATCH EXISTING TYPE

AND AIC RATING.

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/2

/2

:3

:5

P

M

51-E600

ELECTRICAL SCHEDULES

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 18.2 A

TOTAL CONNECTED AMPS: 18.15 A

Receptacles 0.54 kVA 100.00% 0.54 kVA TOTAL ESTIMATED DEMAND LOAD: 6.54 kVA

Power 6 kVA 100.00% 6 kVA TOTAL CONNECTED LOAD: 6.54 kVA

Lightin…

This is the start of the file's text. The full file is on GovTribe.