Atch 9 - BLDG 3 addendum.pdf

PDF 12 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud Federal contract opportunity
Solicitation number
36C77622B0035
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This federal contract opportunity solicitation requests contractor services for infrastructure upgrades and renovations at the St. Cloud Veterans Affairs Health Care System campus in Minnesota. The solicitation seeks a contractor to furnish all labor, materials, tools and equipment for electrical, bonding, UPS, building management system interfaces, and physical security upgrades to data center and server room systems. Additional requirements include assessing needs for and performing new and upgraded HVAC work, expanding and renovating existing space, installing a diversified fiber path to the data center for WAN access, and upgrading the fiber infrastructure backbone across campus buildings. The solicitation closes on Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud and is issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The selected contractor shall complete all work in accordance with specifications and contract drawings.

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud, newest first.
File Type Posted
Technical Questions - LATE - St. Cloud 8-10-22.pdf PDF
01-M204 - ROOF REMODEL -MECHANICAL.pdf PDF
Atch 41 - Construction Wage Rates - Stearns 7-29-22.pdf PDF
Specifications Addendum Information.pdf PDF
Drawings Addendum Information.pdf PDF
Atch 1 - Specifications Volume 1 addendum.pdf PDF
Atch 11 - BLDG 5 addendum.pdf PDF
Atch 17 - BLDG 11 addendum.pdf PDF
Atch 18 - BLDG 14 addendum.pdf PDF
Atch 28 - BLDG 108 addendum.pdf PDF
Atch 33 - BLDG 116 addendum.pdf PDF
Atch 3 - Specifications Volume 3 - Asbestos addendum.pdf PDF
Atch 4 - General 1 of 2 addendum.pdf PDF
Atch 6 - BLDG 1 - 1 of 2 addendum.pdf PDF
Atch 8 - BLDG 2 addendum.pdf PDF
Atch 12 - BLDG 6 addendum.pdf PDF
Atch 13 - BLDG 7 and 13 addendum.pdf PDF
Atch 27 - BLDG 96 addendum.pdf PDF
Atch 30 - BLDG 111 addendum.pdf PDF
Atch 31 - BLDG 112 addendum.pdf PDF
Site Visit Sign-in Sheets - 6-28-22 - 6-30-22.pdf PDF
Atch 4 - General 1 of 2.pdf PDF
Atch 5 - General 2 of 2.pdf PDF
Atch 8 - BLDG 2.pdf PDF
Atch 23 - BLDG 50.pdf PDF
Atch 24 - BLDG 51.pdf PDF
Atch 27 - BLDG 96.pdf PDF
Atch 31 - BLDG 112.pdf PDF
Atch 10 - BLDG 4.pdf PDF
Atch 34 - BLDG 118.pdf PDF
36C77622B0035 - 6-9-22.pdf PDF
Atch 6 - BLDG 1 - 1 of 2.pdf PDF
Atch 16 - BLDG 10.pdf PDF
Atch 19 - BLDG 28.pdf PDF
Atch 22 - BLDG 49.pdf PDF
Atch 35 - ADHC.pdf PDF
Atch 1 - Specifications Volume 1.pdf PDF
Atch 7 - BLDG 1 - 2 of 2.pdf PDF
Atch 12 - BLDG 6.pdf PDF
Atch 15 - BLDG 9.pdf PDF
Atch 18 - BLDG 14.pdf PDF
Atch 21 - BLDG 48.pdf PDF
Atch 25 - BLDG 54 and 69.pdf PDF
Atch 26 - BLDG 95 and 88.pdf PDF
Atch 28 - BLDG 108.pdf PDF
Atch 30 - BLDG 111.pdf PDF
Atch 32 - BLDG 115.pdf PDF
Atch 36 - Parking Structure.pdf PDF
Atch 40 - Limitations on Subcontracting - Construction.docx DOCX document
Atch 43 - Site Visit Instructions.pdf PDF
Show all 50

Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LEGEND

CORRIDOR OUTLINE

VFY EXIST

BUILDING OUTLINE

VFY EXIST

TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST

44TH AVE.

TRAIL 1

TRAIL 2

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2)

15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

GRAVEL

GRAVEL

GRAVEL

EXISTING

ROAD

CHAIN LINK FENCE

CHAIN LINK FENCE

16' GATE

GRAVEL

ELECTRICAL

SUBSTATION

G E N E R A T O R

FUEL LINES

CONDU ITS TO TU NNEL

M V

D U

C T

B A

N K

1 1 2 W

PHARMACY ADDITION

11 2 E

G E N E R A T O R

B

CORRIDOR LINK

A

C T

TR

A

IL

ER

174 s .f.

256 s .f.

185 s .f.

149 s ..f.

155 s .f.

104 s .f.

70 s. .f .

72 s .f.

110 s .f.

276 s .f.

112 s .f.

99 s .f.

57 s .f.

146 s .f.

434 s .f.

R A

MP

U P

1:

M A X

R A

MP

U P

1:

M A X

RA

M P

UP

1:2 0 M

AX

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2) 15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

.3

TRANSFORMER

BUILD ING

#91

5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN

O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW

C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D

P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S

R EC O M M EN D ATIO N S

N EW G AS SU P P LY M AIN

IN TO B U ILD IN G

SP AR E

P H O N E LIN E

EXTEN D S TO

E XISTIN G

P H O N E IN

B O ILER R O O M

P ER P LAN .

SP AR E

P H O N E

LIN E TO

M ETER

TU N N EL

E XTEN D S

A D D ITIO N AL

2'- 0" U N D ER

B U ILD IN G

FUEL LINE

VENT LINE

1,000 GAL.

UNDERGROUND

DIESEL FUEL

TANK

1,000/5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

S 1

LIG H T

N EW G AS SU P P LY

(C O O R D IN ATE W ITH SU P P LIER )

12"D

10"D

"D

TP TP

EXIST. BUILDING

EXIST.

BUS STOP

CC

L O

O P

16"

20"

12"

3"

8"

DN

0.

0’

BIRDCAGE

B

IR

D C

A G

E

NSP ELECTRICAL

FOR HWY DEPT

T101

I.T.

CHILLER

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

VESTIBULE

DN

DN

DN

FD

DN

F B

F

B

F B

F

B

F B

F

B

SOUTH

VESTIBULE

PASS

THROUGH

LINK TO

BUILDI NG 51

6 3. 32 56

1 13 5. 35 78

PARKING

NO

PARKING

93 49

37 6

109 5

1A

S M

O K

E B

L D

G

SMOKE

BLDG

SMOKE

BLDG

S M

O K

E B

L D

G

SMOKE

BLDG

M.H.

STOR.

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

STOR.

BIO-

HAZ.

SAUK RIVER

GP

HOLDING POND

OWNER AND

CONSULTANTS:

CONTACT:

ADDRESS:

MIKE ENGMARK

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

NAME:

ADDRESS:

CONTACT:

ADVANCED STRUCTURAL TECHNOLOGIES

7301 OHMS LANE; SUITE 215

EDINA, MN 55439

ZACHARY CRAIG

PHONE:

NAME:

ADDRESS:

CONTACT:

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

PHONE: 402-991-5520

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

IAN WEBER

763-412-4000

ARCHITECT:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

EDWARD MARKFORT

763-412-4000

952-854-9302

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

402-991-5520

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

COVER

DATE:

APPROVED: APPROVED: PROJECTS SECTION MANAGER

APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:

APPROVED: SAFETY MANAGER

APPROVED: CHIEF OF POLICE

APPROVED: PATIENT SAFETY

DATE:

DATE:

DATE: APPROVED: EMS MANAGER

APPROVED: M/O MANAGER

DATE:

DATE:

DATE:DATE:

APPROVED: MEDICAL CENTER DIRECTOR

APPROVED: PROJECT COR DATE:

APPROVED: INFECTION CONTROL NURSE DATE:

APPROVED: SERVICE LINE DIRECTOR

APPROVED: GEMS COORDINATOR DATE:

DATE:

APPROVED: NURSE EXECUTIVE

APPROVED: CHIEF OF STAFF DATE:

APPROVED: DIRECTOR FMS

APPROVED: ASSOCIATE DIRECTOR

DATE:

DATE:

DATE:

DATE:APPROVED: DATE:

APPROVED: DATE:

APPROVED: DATE:

Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System

N

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

VICINITY MAP:

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHONE: 320-252-1670

CIVIL ENGINEER:

VA COR:

TELECOMMUNICATIONS ENGINEER:

CONTACT:

ADDRESS:

JONATHAN WEST

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

PHONE: 504-250-2699

PROGRAM MANAGER:

EMAIL: Jonathan.West@vciint.com

STRUCTURAL ENGINEER:

MECH/ELEC/PLUMB/FIRE ENGINEER:

100% CONSTRUCTION DOCUMENTS

FOR BID - NOT FOR CONSTRUCTION

C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -3

-R E

M a rk fo rt

.r v t

/2

/2

:0 :2

P

M

3-GI000

BUILDING 3 COVER SHEET &

SHEET INDEX

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

BUILDING 3 - EHRM INFRASTRUCTURE UPGRADES

0APPROX 150' 300'75'

SHEET INDEX - BUILDING 3

SHEET NO. SHEET TITLE

3-GI000 BUILDING 3 COVER SHEET & SHEET INDEX

3-GI111 FIRST FLOOR - INFECTION CONTROL & PHASING PLAN

3-GI121 SECOND FLOOR INFECTION CONTROL & PHASING PLAN

3-HA-1A REFERENCE - BASEMENT FLOOR ASBESTOS RE-SURVEY

3-HA-2A REFERENCE - FIRST FLOOR ASBESTOS RE-SURVEY

3-HA-3A REFERENCE - SECOND FLOOR ASBESTOS RE-SURVEY

3-HA-4A REFERENCE - THIRD FLOOR / ATTIC ASBESTOS RE-SURVEY

3-AS110 BASEMENT AND FIRST FLOOR PLANS

3-AS120 SECOND FLOOR AND ATTIC PLANS

3-TD100 BASEMENT & FIRST FLOOR PLANS - TELECOM - DEMOLITION

3-TD120 SECOND & THIRD FLOOR PLANS - TELECOM - DEMOLITION

3-TN100 BASEMENT & FIRST FLOOR PLANS - TELECOMMUNICATIONS

3-TN120 SECOND & THIRD FLOOR PLANS - TELECOMMUNICATIONS

3-TN210 FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE

3-TN220 SECOND FLOOR PLAN - TELECOM - CABLE DISTANCE

3-TN300 ENLARGED PLANS - TELECOMMUNICATIONS - DEMO

3-TN400 ENLARGED PLANS - TELECOMMUNICATIONS

3-TN401 ENLARGED PLANS - TELECOMMUNICATIONS

03-E200 BASEMENT FLOOR PLAN - ELECTRICAL

03-E201 FIRST FLOOR - ELECTRICAL

03-E202 SECOND FLOOR - ELECTRICAL

03-E300 ELECTRICAL ENLARGED PLANS

03-E400 ELECTRICAL RISER DIAGRAMS

03-M101 FIRST FLOOR DEMOLITION - MECHANICAL

03-M102 SECOND FLOOR DEMOLITION - MECHANICAL

03-M201 FIRST FLOOR - MECHANICAL

03-M202 SECOND FLOOR REMODEL - MECHANICAL

SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION

ROOM SCHEDULE

NO. NAME C

A

B

LI

N G

P A

T C

H P

A N

E L

F

IB

E R

P O

W E

R

B O

N D

IN

G

U P

S

D E

D

IC

A T

E D

C O

O

LI

N G

T E

M P

E R

A T

U R

E

H U

M

ID

IT

Y

R A

C K

S E

N S

O R

S P

A C

E

AREA

WIDTH

(FT)

LENGTH

(FT) REMARKS

FIRST FLOOR

109 TELECOM ROOM 43 SF 5.4 8.0 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM

ROOM STANDARDS. SEE TELECOM DRAWINGS

SECOND FLOOR

205E TELECOM ROOM X X X X X X 81 SF 7.3 11.2 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM

ROOM STANDARDS. SEE TELECOM DRAWINGS

OPENING SCHEDULE

VA Building Number

ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION

H D

W G

R O

U P

F

IR

E L

A B

E L

(M

IN

G A

S K

E T

E

LE

C T

R

IC

A L

S L

A B

E L

COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT

PANEL

TYPE

2ND

PANEL

TYPE

PANEL

GLAZING FRAME TYPE

FRAME

GLAZING

HAZARDOUS MATERIAL SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

QUESTIONABLE HAZARDOUS

ELEMENT POSSIBLE ABATEMENT ACTION

FIRST FLOOR 109 TELECOM ROOM NONE. SEE 3-HA-1A NONE. ACM TO REMAIN UNDISTURBED

SECOND FLOOR 205E TELECOM ROOM NONE. SEE 3-HA-2A NONE. ACM TO REMAIN UNDISTURBED

HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT

DISTURB QUESTIONABLE HAZARDOUS MATERIAL.

ICRA PHASE CONSTRUCTION ROOM SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

CAI BLDG NAME /

FUNCTION

CONSTRUCTION

PROJECT ACTIVITY

INFECTION CONTROL

RISK GROUP

CONTROL

PROCEDURE CLASS SECTION

CONSTRUCTION ZONE /

OCCUPIED CONSTR

DAY /

NIGHT

FIRST FLOOR 109 TELECOM ROOM DENTAL TYPE C GROUP 1 CLASS II WEST OCCUPIED CONSTRUCTION NIGHT

SECOND FLOOR 205E TELECOM ROOM ADMINISTRATIVE TYPE C GROUP 1 CLASS II WEST OCCUPIED CONSTRUCTION NIGHT

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

1 UPDATE TO BID DOCUMENTS 06/29/22

2 UPDATE TO BID DOCUMENTS 07/26/22

POSSIBLE

PRINTER

LOCATION

24X24

D E

S K

X

T A

B L E

X

DENTAL

LAB

DENTAL

LAB

121A

CORRIDOR

C1F

MULTI

PURPOSE

OFFICE

CORRIDOR

C1C

CORRIDOR

C1E

VESTIBULE

VESTIBULE

STAIR

HALL

OPERATORY

EQUIP

DIGITAL

103A

STAIR

INSTRUMENT

PREP

CORRIDOR

C1B

CORRIDOR

C1A

DENTAL

LAB

DENTAL

LAB

121A

STAIR

HALL

STAIR

OPERATORY

STAFF

TOILET

LOCKER

SPS

RECEIVING

103B

DIGITAL/

PAN

OFFICE

OPERATORY

CLEAN

SPD

OFFICE

122 LOCKERS

DENTAL

CHIEF

ORAL

SURGERY

STAIR

SPS

RECEIVING

CLEAN

UTILITY

CORRIDOR

C1D

WAITING

WOMENS

TOILET

126B

MENS

TOILET

126A

POLISHER

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -3

-R E

M a rk fo rt

.r v t

/2

/2

:1 :1

A

M

3-GI111

FIRST FLOOR - INFECTION

CONTROL & PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

1/8" = 1'-0"

FIRST FLOOR - CONST BARRIER PLAN

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

FIRST FLOOR 109 TELECOM ROOM DENTAL TYPE C GROUP 1 CLASS II

SECOND FLOOR 205E TELECOM ROOM ADMINISTRATIVE TYPE C GROUP 1 CLASS II

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

N

0 8' 16'4'

D E

S K

30x66

D E

S K x6

LAT. FILE LAT. FILE

LAT. FILE LAT. FILE

LA

T

. F

IL

E

LAT. FILE

Key Cabinet

LAT. FILED

E

S K x6

Copier

ROOM

PLANS

211A

ROOM

PLOT/COPY

OFFICE

HAC

OFFICE

CORRIDOR

207A

OFFICE

207B

OFFICE

207C

CONFERENCE

STAIR

OFFICE

205A

OFFICE

205B

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

215B

OFFICE

215A

OFFICE

ALCOVE

213C

OFFICE

213B

OFFICE

213A

HOUSEKEEPING

OFFICE

CORRIDOR

OFFICE

C2C

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

WOMEN

MEN

205D

OFFICE

C2D

CORRIDOR

STAIR

221A

STAIR

LOBBY

205C

PASSAGE

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -3

-R E

M a rk fo rt

.r v t

/2

/2

:1 :0

A

M

3-GI121

SECOND FLOOR INFECTION

CONTROL & PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

03/30/2022

1/8" = 1'-0"

SECOND FLOOR - CONST BARRIER PLAN

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

FIRST FLOOR 109 TELECOM ROOM DENTAL TYPE C GROUP 1 CLASS II

SECOND FLOOR 205E TELECOM ROOM ADMINISTRATIVE TYPE C GROUP 1 CLASS II

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

0 8' 16'4'

-ASBESTOS-CONTAINING WRAP (FELT) ON PIPE GOING INTO SOIL

-ASBESTOS-CONTAINING WINDOW CAULK

CASTLE HILL ASSOCIATES, LLC.

N

S

W E

LEGEND BUILDING #3 - BASEMENT FLOOR PLAN

-ASBESTOS-CONTAINING FIRE DOOR

-ASBESTOS-CONTAINING TILE AND MASTIC

-ASBESTOS-CONTAINING WINDOW CAULK

-ASBESTOS-CONTAINING INSULATION INSIDE CONVECTORS

-ASBESTOS-CONTAINING WALL MASTIC

-ASBESTOS-CONTAINING COUNTERTOP

CASTLE HILL ASSOCIATES, LLC.

N

S

W E

BUILDING #3 - FIRST FLOOR PLAN

-ASBESTOS-CONTAINING FIRE DOOR

-ASBESTOS-CONTAINING WINDOW CAULK

-ASBESTOS-CONTAINING INSULATION INSIDE CONVECTORS

-ASBESTOS-CONTAINING WALL MASTIC

-ASBESTOS-CONTAINING FLOOR TILE AND MASTIC BENEATH CARPET

-ASBESTOS-CONTAINING MASTIC BENEATH CARPET

CASTLE HILL ASSOCIATES, LLC.

N

S

W E

BUILDING #3 - SECOND FLOOR PLAN

CASTLE HILL ASSOCIATES, LLC.

S

W E

BUILDING #3 - ATTIC FLOOR PLAN

POSSIBLE

PRINTER

LOCATION

24X24

D E

S K

X

T A

B L E

X

XFMR

MECHANICAL

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

UP

DN

7'-11 5/8"

5' -5

3-AS110

TELECOM

ROOM 109

TELECOM

ROOM

TELECOM

ROOM

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -3

-R E

M a rk fo rt

.r v t

/3

/2

:3 :5

P

M

3-AS110

BASEMENT AND FIRST FLOOR

PLANS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

03/30/2022

1/8" = 1'-0"

FIRST FLOOR - OVERALL PLAN

1/8" = 1'-0"

BASEMENT FLOOR - OVERALL PLAN

N

0 8' 16'4'

N

0 8' 16'4'

N

0 4' 8'2' 1/4" = 1'-0"

DEMOLITION PLAN - RM109

_DEMOLITION PLAN KEYED NOTES

DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM

REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_FLOOR PLAN KEYED NOTES

FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”

TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH

HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT

OVER FIRE RATING STAMP.

FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE

TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST

THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS

WITH FIRE CAULK.

FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_REFLECTED CEILING PLAN KEYED NOTES

RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET

ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE

VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET

ROW OR SECTION.

RC2 OPEN TO STRUCTURAL FLOOR ABOVE

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED

SIGNAGE SHALL BE PROVIDED BY THE CONTRACTORWITHIN TELECOM

ROOMS.

1/4" = 1'-0"

ENLARGED FLOOR PLAN - RM 109

N

0 4' 8'2' 1/4" = 1'-0"

REFLECTED CEILING PLAN - RM109

N

0 4' 8'2'

RC1 RC2

FL1

FL20

FL3

DE1

DE1

DE1

1 UPDATE TO BID DOCUMENTS 06/29/22

NORTH

E

S K

30x66

D E

S K x6

LAT. FILE LAT. FILE

LAT. FILE LAT. FILE

LA

T

. F

IL

E

LAT. FILE

Key Cabinet

LAT. FILED

E

S K x6

Copier

ROOM

PLANS

211A

ROOM

PLOT/COPY

OFFICE

HAC

OFFICE

CORRIDOR

207A

OFFICE

207B

OFFICE

207C

CONFERENCE

STAIR

OFFICE

205A

OFFICE

205B

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

215B

OFFICE

215A

OFFICE

ALCOVE

213C

OFFICE

213B

OFFICE

213A

HOUSEKEEPING

OFFICE

CORRIDOR

OFFICE

C2C

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

WOMEN

MEN

205D

OFFICE

C2D

CORRIDOR

STAIR

221A

STAIR

LOBBY

205C

PASSAGE

DN

SEE ROOF PLAN

SEE ROOF PLAN

ELEV

MACH

STAIR

MECH.

EQUIP.

ATTIC

ATTIC

ACCESS

PASSAGE

205E

TELECOM

ROOM

7' -3

/4

11'-2 1/4"

3-AS120

205E

TELECOM

ROOM

205E

TELECOM

ROOM

TELECOM

ROOM

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -3

-R E

M a rk fo rt

.r v t

/3

/2

:3 :2

P

M

3-AS120

SECOND FLOOR AND ATTIC

PLANS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

03/30/2022

1/8" = 1'-0"

SECOND FLOOR - OVERALL PLAN

N

0 8' 16'4' 1/8" = 1'-0"

ATTIC FLOOR - OVERALL PLAN

N

0 8' 16'4'

1/4" = 1'-0"

ENLARGED FLOOR PLAN - RM 205E

1/4" = 1'-0"

DEMOLITION PLAN - RM 205E

N

0 4' 8'2'

N

0 4' 8'2' 1/4" = 1'-0"

REFLECTED CEILING PLAN - RM 205E

N

0 4' 8'2'

DE1

RC1

_DEMOLITION PLAN KEYED NOTES

DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM

REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_FLOOR PLAN KEYED NOTES

FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”

TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH

HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT

OVER FIRE RATING STAMP.

FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE

TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST

THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS

WITH FIRE CAULK.

FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_REFLECTED CEILING PLAN KEYED NOTES

RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET

ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE

VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET

ROW OR SECTION.

RC2 OPEN TO STRUCTURAL FLOOR ABOVE

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

DE1

DE1

FL1

FL20

FL3

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED

SIGNAGE SHALL BE PROVIDED BY THE CONTRACTORWITHIN TELECOM

ROOMS.

RC2

1 UPDATE TO BID DOCUMENTS 06/29/22

R A M P

D N

R A M P

D N

UNEXCAVATED

UNEXCAVATED

PASSAGE

STAIR

SUMP

ELEC

MECHANICAL

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

NORTH

UP

DN

POSSIBLE

PRINTER

LOCATION

24X24

D E

S K

X

T A

B L E

X

POLISHER

POSSIBLE

PRINTER

LOCATION

24X24

D E

S K

X

T A

B L E

X

POLISHER

LIMITS OF DATA CABLING DEMOLITION

3"

E

EXISTING CONDUIT FROM

BUILDING 3 TO BUILDING 1

3-TN300

LIMITS OF DATA CABLING DEMOLITION

2D/1

4D4D 4D4D4D

4D/1

1D

2D 2D 2D 2D 2D

2D

3D

3D

3D

1D

1D/1

4D

4D2D2D

2D 2D 2D 2D 2D 2D 2D

4D

4D 1V

4D2D

2D 4D

4D

4D

4D

2D

4D

4D

2D

3D 3D

3D3D3D

2D

2D

WAP

WAP

WAP

WAP

WAP

WAP

E E E E E

E

E

E E E E E E E E E

E

E

E

E

E

E

E

E

E

E E E E E E E

E

E

E

E

E

EE

E

EE

E E

E

E

E

E

E E E

EE

E

UP AND

DOWN

E

E E

E

E

E

E E

E

E

E

E

8"x4"

8"x4"

8" x4

8" x4

8"x4"

8" x4

E 8"x4"

E

8" x4

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:0

:2

P

M

3-TD100

BASEMENT & FIRST FLOOR

PLANS - TELECOM -

DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/8" = 1'-0"

BASEMENT FLOOR PLAN - TELECOM - DEMOLITION

1/8" = 1'-0"

FIRST LEVEL FLOOR PLAN - TELECOM - DEMOLITION

N

0 8' 16'4'

N

0 8' 16'4'

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

C

ROOM

PLANS

211A

ROOM

PLOT/COPY

OFFICE

HAC

OFFICE

CORRIDOR

207A

OFFICE

207B

OFFICE

207C

CONFERENCE

STAIR

OFFICE

205A

OFFICE

205B

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

215B

OFFICE

215A

OFFICE

ALCOVE

213C

OFFICE

213B

OFFICE

213A

HOUSEKEEPING

OFFICE

CORRIDOR

OFFICE

C2C

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

WOMEN

MEN

205D

OFFICE

C2D

CORRIDOR

STAIR

221A

STAIR

LOBBY

205C

PASSAGE

DN

SEE ROOF PLAN

SEE ROOF PLAN

ELEV

MACH

STAIR

MECH.

EQUIP.

ATTIC

ATTIC

ACCESS

3-TN300

LIMITS OF DATA CABLING DEMOLITION

2D/12D/1

4D

4D

D

4D

3D/1

4D 2D/1 4D

2D/1 2D/1 2D/1

4D

4D

4D

4D 4D4D

4D

2D/12D/1

2D/1

2D/1

2D/1

4D

2D/1

2D/1

2D/1

4D

4D

4D

4D 4D

4D 4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

2D

2D/1

2D/1

2D/1

1D/1

WAP

WAP

WAP

WAP

WAP

EE

E

E

E

E

E

E

E E E

E

E

E

E

E E

E

E E

E

E

E

E E

E E

E

E

E

E

E

E

E E

E

E

E

E

E E E

E

E E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E 12"x4" 12"x4"

"x

4"

"x

4"

12"x4"

"x

4"

E

EE

E

E

"x

4"

"x

4"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:0

:2

P

M

3-TD120

SECOND & THIRD FLOOR

PLANS - TELECOM -

DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/8" = 1'-0"

SECOND FLOOR PLAN - TELECOM - DEMOLITION

1/8" = 1'-0"

THIRD FLOOR PLAN - TELECOM - DEMOLITION

N

0 8' 16'4'

N

0 8' 16'4'

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING

ROUTES.

XFMR

MECHANICAL

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

UNEXCAVATED

UP

DN

POSSIBLE

PRINTER

LOCATION

24X24

D E

S K

X

T A

B L E

X

POSSIBLE

PRINTER

LOCATION

24X24

D E

S K

X

T A

B L E

X

LIMITS OF DATA CABLING

REPLACEMENT FROM ROOM 205E

2"

3"4"4"4"4"

4"4"4"4"

EXISTING CONDUIT FROM

BUILDING 3 TO BUILDING 1

2"

E

JUNCTION BOX

3"

4"4"4"4"

TELECOM ROOM

LIMITS OF DATA CABLING REPLACEMENT

FROM ROOM 205E

4D

4D

4D

1V

4D

4D

3D

3D

3D

1D

1D/1

2D

1D

3D 3D 3D

3D3D

2D

2D

4D

4D 4D

2D 2D 2D 2D 2D 2D 2D 2D

4D 4D 4D 4D 4D

2D/1

4D/1 2D 2D 2D 2D 2D 2D 2D

WAP

WAP

WAP

WAP

WAP

WAP

2D

2D

2D

4D

4D

4D

E E E E E

E

E

E E E E E E E E E

E

E

E

E

E

E

E

E

E

E E E E E E E

E

E

E

E

E

EE

E

EE

E E

E

E

E

E

E E E

EE

E

HORIZONTAL AND

VERTICAL ROUTE TO

ROOM 205E

E

E E

8" x4

8" x4

8"x4"8"x4"

8" x4

8" x4

8"x4"

E

E

E

E E

E

E

E

E E

8" x4

8"x4"

3-TN400

E

C4

126"UPDOWN

2" F2

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:0

:2

P

M

3-TN100

BASEMENT & FIRST FLOOR

PLANS -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/8" = 1'-0"

BASEMENT FLOOR PLAN - TELECOMMUNICATIONS

N

0 8' 16'4'

N

0 8' 16'4'

1/8" = 1'-0"

FIRST LEVEL FLOOR PLAN - TELECOMMUNICATIONS

N

0 8' 16'4'

N

0 8' 16'4'

GENERAL NOTES:

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

SHEET NOTES:

1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING TELECOM CABLE TRAY.

2. PROVIDE JUNCTION BOX TO CONNECT FIBER CONDUIT ENTRY TO EXTEND CONDUIT PATHWAY TO THE NEW

TELECOM ROOM.

S K

30x66

D E

S K x6

LAT. FILE LAT. FILE

LAT. FILE LAT. FILE

LA

T

. F

IL

E

LAT. FILE

Key Cabinet

LAT. FILED

E

S K x6

Copier

ROOM

PLANS

211A

ROOM

PLOT/COPY

OFFICE

HAC

OFFICE

CORRIDOR

207A

OFFICE

207B

OFFICE

207C

CONFERENCE

STAIR

OFFICE

205A

OFFICE

205B

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

215B

OFFICE

215A

OFFICE

ALCOVE

213C

OFFICE

213B

OFFICE

213A

HOUSEKEEPING

OFFICE

CORRIDOR

OFFICE

C2C

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

WOMEN

MEN

205D

OFFICE

C2D

CORRIDOR

STAIR

221A

STAIR

LOBBY

205C

PASSAGE

D E

S K

30x66

D E

S K x6

LAT. FILE LAT. FILE

LAT. FILE LAT. FILE

LA

T

. F

IL

E

LAT. FILE

Key Cabinet

LAT. FILED

E

S K x6

Copier

ROOM

PLANS

211A

ROOM

PLOT/COPY

OFFICE

HAC

OFFICE

CORRIDOR

207A

OFFICE

207B

OFFICE

207C

CONFERENCE

STAIR

OFFICE

205A

OFFICE

205B

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

215B

OFFICE

215A

OFFICE

ALCOVE

213C

OFFICE

213B

OFFICE

213A

HOUSEKEEPING

OFFICE

CORRIDOR

OFFICE

C2C

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

WOMEN

MEN

205D

OFFICE

C2D

CORRIDOR

STAIR

221A

STAIR

LOBBY

205C

PASSAGE

C

DN

SEE ROOF PLAN

SEE ROOF PLAN

ELEV

MACH

STAIR

MECH.

EQUIP.

ATTIC

ATTIC

ACCESS

205E

TELECOM ROOM

LIMITS OF DATA CABLING REPLACEMENT

FROM ROOM 205E

F2

C4 126"

2D/1 2D/1

2D/1 4D 2D/1 2D/1

2D/1

2D/1

2D/1

2D/1

1D/1

2D

4D

4D

2D/12D/1

2D/1

2D/1

2D/1 2D/1

2D/1

2D/1

4D

4D

D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D

4D 4D

4D 4D

4D

4D

4D 4D

4D

4D

4D

3D/1

WAP

WAP

WAP

WAP

WAP

EE

E

E

E

E

E

E

E E E

E

E

E

E

E E

E

E E

E

E

E

E

E

E E

E

E

E

E

E

E

E E

E

E

E

E

E E E

E

E E

E

E

E

E

E

E

E

E

E

E

E

E

3-TN401

"x

4"

"x

4"

12"x4" 12"x4"

E

E

E

E

E

E

1 E

"x

4"

12"x4"

E2

E

E

12"x4"

"x

4"

"x

4"

F2

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:0

:2

P

M

3-TN120

SECOND & THIRD FLOOR

PLANS -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/8" = 1'-0"

SECOND FLOOR PLAN - TELECOMMUNICATIONS

1/8" = 1'-0"

THIRD FLOOR PLAN - TELECOMMUNICATIONS

N

0 8' 16'4'

N

0 8' 16'4'

GENERAL NOTES:

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

SHEET NOTES:

1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING TELECOM CABLE TRAY.

POSSIBLE

PRINTER

LOCATION

24X24

D E

S K

X

T A

B L E

X

POSSIBLE

PRINTER

LOCATION

24X24

D E

S K

X

T A

B L E

X

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:0

:2

P

M

3-TN210

FIRST FLOOR PLAN -

TELECOM - CABLE DISTANCE

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1" = 30'-0"

FIRST FLOOR PLAN - TELECOMMUNICATIONS - CABLE DISTANCE

0 30' 60'15'

S K

30x66

D E

S K x6

LAT. FILE LAT. FILE

LAT. FILE LAT. FILE

LA

T.

F

IL

E

LAT. F ILE

Key Cabinet

LAT. F ILED

E

S K x6

Copier

ROOM

PLANS

211A

ROOM

PLOT/COPY

OFFICE

HAC

OFFICE

CORRIDOR

207A

OFFICE

207B

OFFICE

207C

CONFERENCE

STAIR

OFFICE

205A

OFFICE

205B

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

215B

OFFICE

215A

OFFICE

ALCOVE

213C

OFFICE

213B

OFFICE

213A

HOUSEKEEPING

OFFICE

CORRIDOR

OFFICE

C2C

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

WOMEN

MEN

205D

OFFICE

C2D

CORRIDOR

STAIR

221A

STAIR

LOBBY

205C

PASSAGE

D E

S K

30x66

D E

S K x6

LAT. FILE LAT. FILE

LAT. FILE LAT. FILE

LA

T.

F

IL

E

LAT. F ILE

Key Cabinet

LAT. F ILED

E

S K x6

Copier

ROOM

PLANS

211A

ROOM

PLOT/COPY

OFFICE

HAC

OFFICE

CORRIDOR

207A

OFFICE

207B

OFFICE

207C

CONFERENCE

STAIR

OFFICE

205A

OFFICE

205B

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

215B

OFFICE

215A

OFFICE

ALCOVE

213C

OFFICE

213B

OFFICE

213A

HOUSEKEEPING

OFFICE

CORRIDOR

OFFICE

C2C

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

WOMEN

MEN

205D

OFFICE

C2D

CORRIDOR

STAIR

221A

STAIR

LOBBY

205C

PASSAGE

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:0

:3

P

M

3-TN220

SECOND FLOOR PLAN -

TELECOM - CABLE DISTANCE

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1" = 30'-0"

SECOND FLOOR PLAN - TELECOMMUNICATIONS - CABLE DISTANCE

0 30' 60'15'

F

PASSAGE

D

E

E

R

E

CABLE TRAY

DATA RACK

8"x4"

E R

D

E E R

W

E

CABLE TRAY

DATA RACK

R

E E

12"x4"

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:0

:3

P

M

3-TN300

ENLARGED PLANS -

TELECOMMUNICATIONS -

DEMO

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

1/4" = 1'-0"

ENALRGED PLAN - RM 109 - TELECOM - DEMO

0 4' 8'2'

N

1/4" = 1'-0"

ENALRGED PLAN - RM 205E - TELECOM - DEMO

0 4' 8'2'

N

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

SHEET NOTES:

1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION.

EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK PLANS FOR SERVING

COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE

RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE

PROJECT.

1. ROOM 109

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 185

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

2. ROOM 205E

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 192

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

R

A C

NOTES:

1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.

2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.

3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.

4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO

SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET. (NOT TO EXCEED 288 PORTS PER RACK).

5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.

6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.

7. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.

VERTICAL CABLE

MANAGEMENT (TYP)

RACK 1

1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL

1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)

1U 48 PORT CAT5E BACKBONE PATCH PANEL

1U CABLE MANAGEMENT

1U CABLE MANAGEMENT

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

6U 5KW RACK MOUNT UPS

6U SPACE FOR FUTURE USE. PROVIDE BLANK

PANELS FOR UNUSED SPACES.

V E

R T

IC

A

L R

A C

K P

D U

V E

R T

IC

A

L R

A C

K P

D U

NEMA L21-20R (TYP)

CHANNEL RACK (TYP)

D

PROVIDE DATA CABLE TO RACK

MOUNTED UPS FOR CONNECTION

TO MONITORING SYSTEM

RACK 1

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

1U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

SPACE FOR FUTURE HORIZONTAL CABLE

DISTRIBUTION. PROVIDE BLANKING PANELS FOR

UNUSED SPACES.

3-TN400

1 - a b

1 - c d

TELECOM ROOM

W

12"x4"

12"x4" 12"x4"

C4 126"

12"x4" 12"x4"

DATA

RACK

CABLE

TRAY

12"x4"

KEYPAD

8"x4" E

2"

F2

R

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:0

:3

P

M

3-TN400

ENLARGED PLANS -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

N

0 2' 4'1'

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.

THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED

FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE

PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.

1. ROOM 109

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 185

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6A): 185

DATA (CAT6): 0

NOT TO SCALE

COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - TR 109

0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'1/4" = 1'-0"

1 - a

1/4" = 1'-0"

1 - b

1/4" = 1'-0"

1 - c

1/4" = 1'-0"

1 - d

1/2" = 1'-0"

ENLARGED PLAN - TR 109 - TELECOM - CABLE TRAY AND DATA

PASSAGEPASSAGE

F A

C

C R

C

205E

TELECOM ROOM

12" LADDER

3-TN401

2 - a b

2 - c d

12"x4"

12"x4"

DATA RACK

CABLE TRAY

E

W

E

C4 126"

E

F2

E

12"x4"12"x4"

W

K E

Y P

A D

12"x4"

E

F2

R

NOTES:

1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.

2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.

3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.

4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO

SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET. (NOT TO EXCEED 288 PORTS PER RACK).

5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.

6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.

7. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.

VERTICAL CABLE

MANAGEMENT (TYP)

RACK 1

1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL

1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)

1U 48 PORT CAT5E BACKBONE PATCH PANEL

1U CABLE MANAGEMENT

1U CABLE MANAGEMENT

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

6U 5KW RACK MOUNT UPS

6U SPACE FOR FUTURE USE. PROVIDE BLANK

PANELS FOR UNUSED SPACES.

V E

R T

IC

A

L R

A C

K P

D U

V E

R T

IC

A

L R

A C

K P

D U

NEMA L21-20R (TYP)

CHANNEL RACK (TYP)

D

PROVIDE DATA CABLE TO RACK

MOUNTED UPS FOR CONNECTION

TO MONITORING SYSTEM

RACK 1

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

1U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

SPACE FOR FUTURE HORIZONTAL CABLE

DISTRIBUTION. PROVIDE BLANKING PANELS FOR

UNUSED SPACES.

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:0

:3

P

M

3-TN401

ENLARGED PLANS -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

N

0 2' 4'1'

0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'

GENERAL NOTES:

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.

THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED

FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE

PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.

1. ROOM 205E

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 192

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 185 FROM ROOM 109

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6A): 192

DATA (CAT6): 0

1/2" = 1'-0"

ENLARGED PLAN - TR 205E - TELECOM - CABLE TRAY AND DATA

1/4" = 1'-0"

2 - a

1/4" = 1'-0"

2 - b

1/4" = 1'-0"

2 - c

1/4" = 1'-0"

2 - d

NO SCALE

COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - TR 205E

XFMR

EXCAVATED

UNEXCAVATED

EXCAVATED

HEATER

ROOM

UNEXCAVATED

UP

DN

03-E300

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:4

:1

A M

03-E200

BASEMENT FLOOR PLAN -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

TBD GJL

16305

1/8" = 1'-0"

BASEMENT FLOOR PLAN - ELECTRICAL

0 8' 16'4'

N

100% CD 03/30

Brian.P.Koen Snapshot

Brian.P.Koen Typewritten Text 05-06-2022

POSSIBLE

PRINTER

LOCATION

24X24

D E

S K

X

T A

B L E

X

03-E300

03-E300

03-E300

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:4

:1

A M

03-E201

FIRST FLOOR - ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

Checker Author

16305

N O R

HT

1/8" = 1'-0"

FIRST FLOOR - ELECTRICAL

100% CD 03/30

Brian.P.Koen Snapshot

Brian.P.Koen

S K

30x66

D E

S K x6

LAT. FILE LAT. FILE

LAT. FILE LAT. FILE

LA

T

. F

IL

E

LAT. FILE

Key Cabinet

LAT. FILED

E

S K x6

Copier

03-E300

03-E300

03-E300

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:4

:1

A M

03-E202

SECOND FLOOR - ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

Checker Author

16305

N O R

HT

1/8" = 1'-0"

SECOND FLOOR - ELECTRICAL

100% CD 03/30

Brian.P.Koen Snapshot

Brian.P.Koen

UNEXCAVATED

PASSAGE3

ELEC

SD

3-MDP-1

ATS

ATS ATS

3-EQ3

3 4

B03IT-2-1

42"

B03IT-2-EQ-7

42"

B03IT-2-EQ-7

42"

B03IT-2-1

42"

B03IT-2-EQ-1,3,5

B03IT-2-3,5,7

B03IT-2-EQ

B03IT-2

A

B03IT-2-EQ

a

A

B03IT-2

b a b

B03IT-2-2,4,6

B03IT-2-EQ-2,4,6

3 4 1

A

B03IT-2-EQ

A

B03IT-2

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:4

:2

A M

03-E300

ELECTRICAL ENLARGED

PLANS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

TBD GJL

16305

1/4" = 1'-0"

BASEMENT ENLARGED - ELEC 3 -

ELECTRICAL

SHEET NOTES:

1. PROVIDE APC#AP8861 RPDU RACK PDU 2G

WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,

ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R

OUTLETS. PROVIDE TWO PER RACK, MOUNTED

PER MANUFACTURER'S REQUIREMENTS.

2. CONNECT SMOKE DETECTOR TO NEAREST

EXISTING SLC.

3. COORDINATE FINAL LOCATION OF

RECEPTACLE L21-20R WITH TELECOM

CONTRACTOR. PROVIDE 3/4"C-4#12, 1#12 GND

TO PANEL FOR EACH RECEPTACLE.

4. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-

PHASE, 4-WIRE RACK MOUNTED UPS FOR

EACH RACK TOWER.

SHEET NOTES:

1. REFER TO TECHNOLOGY PLANS FOR IT ROOM

LAYOUT AND RACK LAYOUT/DETAILS.

2. REFER TO SHEET 0-GE400 DETAIL FOR LAYOUT

& ONE-LINE OF RACK.

0 4' 8'2'

0 4' 8'2' 0 4' 8'2'

N

N N

1/4" = 1'-0"

SECOND FLOOR - TR 205E -

POWER & SYSTEM

5 1/4" = 1'-0"

SECOND FLOOR - TR 205E -

LIGHTING

N O R

HT

1/4" = 1'-0"

FIRST FLOOR - TR 109 - DEMO

ELECTRICAL

N

O R

HT

1/4" = 1'-0"

FIRST FLOOR - TR 109 - POWER &

SYSTEM

N O R

HT

1/4" = 1'-0"

SECOND FLOOR - TR 205E - DEMO

ELECTRICAL

0 4' 8'2'

N

N O R

HT

1/4" = 1'-0"

FIRST FLOOR - TR 109 - LIGHTING

0 4' 8'2'

0 4' 8'2'

N

N 0 4' 8'2'

N

100% CD 03/30

Brian.P.Koen Snapshot

Brian.P.Koen

FIRST FLOOR

3EQB-3

SECOND FLOOR

PENTHOUSE

B03IT-2-EQ

100Y

BASEMENT

3-MDP-1

B03IT-2

100Y

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:4

:2

A M

03-E400

ELECTRICAL DIAGRAMS &

SCHEDULES

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

TBD GJL

16305

12" = 1'-0"

PARTIAL POWER RISER

KEYNOTES:

1. PROVIDE NEW CIRCUIT BREAKER TO MATCH

EXISTING TYPE AND AIC RATING.

100% CD 03/30

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 15.4 A

TOTAL CONNECTED AMPS: 15.38 A

Receptacles 0.54 kVA 100.00% 0.54 kVA TOTAL ESTIMATED DEMAND LOAD: 5.54 kVA

Power 5 kVA 100.00% 5 kVA TOTAL CONNECTED LOAD: 5.54 kVA

Lighting 0 kVA 0.00% 0 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 17.12 13.89 15.62

Total Load: 2.03 kVA 1.67 kVA 1.85 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

11 WP GFI REC. 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING TR205E 20 A 1 0 10

-- 7 -- -- -- -- -- -- 1.67 0 1 20 A Lighting TR109 8

-- 5 -- -- -- -- -- -- 1.67 0 -- -- -- -- -- -- 6 --

3 L21-20R RACK TR205E 20 A 3 1.67 0 -- -- -- -- -- -- 4 --

1 TELECOM ROOM REC. TR205E 20 A 1 0.36 0 3 20 A L21-20R TR109 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES: PROVIDE INTEGRAL ELECTRIC METER IN PANEL.

SCCR: 10 kA

LOCATION: TELECOM ROOM 205E WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B03IT-2

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 14.9 A

TOTAL CONNECTED AMPS: 14.88 A

Receptacles 0.36 kVA 100.00% 0.36 kVA TOTAL ESTIMATED DEMAND LOAD: 5.36 kVA

Power 5 kVA 100.00% 5 kVA TOTAL CONNECTED LOAD: 5.36 kVA

Lighting 0 kVA 0.00% 0 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 16.89 13.89 13.89

Total Load: 2.03 kVA 1.67 kVA 1.67 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

13 0 -- -- -- 1 20 A SPARE 14 --

11 0 -- -- -- 1 20 A SPARE 12 --

9 Lighting TR205E 20 A 1 0 0 -- -- -- 1 20 A SPARE 10 --

7 TELECOM ROOM REC. TR205E 20 A 1 0.36 0 1 20 A Lighting TR109 8

-- 5 -- -- -- -- -- -- 1.67 0 -- -- -- -- -- -- 6 --

-- 3 -- -- -- -- -- -- 1.67 0 -- -- -- -- -- -- 4 --

1 L21-20R RACK TR205E 20 A 3 1.67 0 3 20 A L21-20R TR109 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

SCCR: 10 kA

LOCATION: TELECOM ROOM 205E WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B03IT-2-EQ

3-MPD-1

3-EQ3-1

Brian.P.Koen Snapshot

Brian.P.Koen

T

LOCKER

STAFF TOILET

CORRIDOR

CIB

IT

INSTRUMENT PREP

OPERATORY

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.M

R

.r v t

/5

/2

:5

:1

A

M

03-M101

FIRST FLOOR DEMOLITION -

MECHANICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

RDL JCL

16305

1/4" = 1'-0"

FIRST FLOOR DEMOLITION - MECHANICAL

0 8' 16'4'

N

FIELD VERIFICATION NOTES

1. THE HVAC CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT

THEIR BID. THE FOLLOWING ITEMS SHALL BE VERIFIED.

A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN

SCOPE OF WORK, WHETHER EXPLICITLY SHOWN OR NOT.

B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.

C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS, AND DIFFUSERS.

D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.

E. SIZE AND LCOATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING.

2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALLL THESE ITEMS PRIOR TO BID AND INCLUDE IN

THEIR BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.

3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.

4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER

AND ARCHITECT FOR DIRECTION.

KEYNOTES 1/03-M101:

1. EXISTING DATA RACK LOCATION. UNIT TO BE DEMOLISHED BY OTHERS.

2. EXISTING SUPPLY AIR DIFFUSER AND DUCTWORK. REMOVE BACK TO LOCATION AS

SHOWN AND CAP. COORDINATE WALL PATCHING WITH GENERAL CONTRACTOR.

3. EXISTING RETURN AIR GRILLE AND DUCTWORK. REMOVE BACK TO LOCATION AS

SHOWN AND CAP. COORDINATE WALL PATCHING WITH GENERAL CONTRACTOR.

4. REMOVE AND DISPOSE OF EXISTING THERMOSTATS AND ASSOCIATED WIRING.

5. REMOVE EXISTING SPRINKLER HEAD AND BRANCH LINE BACK TO LOCATION

SHOWN FOR RE-ROUTING. COORDINATE WALL PATCHING WITH GENERAL

CONTRACTOR.

6. CONTRACTOR TO PRE-MEASURE EXISTING AIRFLOWS FOR TERMINAL UNIT.

100% CD 03/30

OFFICE

WOMEN

MEN

IT

205E

OFFICE

OFFICE

OFFICE

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.M

R

.r v t

/5

/2

:5

:1

A

M

03-M102

SECOND FLOOR DEMOLITION -

MECHANICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

RDL JCL

16305

1/4" = 1'-0"

SECOND FLOOR DEMOLITION - MECHANICAL

0 8' 16'4'

N

FIELD VERIFICATION NOTES

1. THE HVAC CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT

THEIR BID. THE FOLLOWING ITEMS SHALL BE VERIFIED.

A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN

SCOPE OF WORK, WHETHER EXPLICITLY SHOWN OR NOT.

B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.

C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS, AND DIFFUSERS.

D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.

E. SIZE AND LCOATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING.

2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY.