Atch 13 - BLDG 7 and 13 addendum.pdf

PDF 16 MB Posted

Attached to
Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud Federal contract opportunity
Solicitation number
36C77622B0035
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document includes details for a federal solicitation seeking construction services. The solicitation seeks a contractor to perform infrastructure upgrades at the St. Cloud Veterans Affairs Health Care System, including electrical, bonding, UPS, building management systems, access security, HVAC assessments and upgrades, data center/server room physical security upgrades, fiber infrastructure installation and upgrades both within and between buildings, and hazardous materials abatement. The work must be completed in accordance with provided specifications and contract drawings. The soliciting agency is the Department of Veterans Affairs Technology Acquisition Center Austin. The solicitation number is 36C77622B0035 and is titled "Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud."

View the file

Other files for this federal contract opportunity

Other files attached to Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud, newest first.
File Type Posted
Atch 41 - Construction Wage Rates - Stearns 7-29-22.pdf PDF
Technical Questions - LATE - St. Cloud 8-10-22.pdf PDF
01-M204 - ROOF REMODEL -MECHANICAL.pdf PDF
Atch 3 - Specifications Volume 3 - Asbestos addendum.pdf PDF
Atch 4 - General 1 of 2 addendum.pdf PDF
Atch 6 - BLDG 1 - 1 of 2 addendum.pdf PDF
Atch 8 - BLDG 2 addendum.pdf PDF
Atch 9 - BLDG 3 addendum.pdf PDF
Atch 12 - BLDG 6 addendum.pdf PDF
Atch 27 - BLDG 96 addendum.pdf PDF
Atch 30 - BLDG 111 addendum.pdf PDF
Atch 31 - BLDG 112 addendum.pdf PDF
Specifications Addendum Information.pdf PDF
Drawings Addendum Information.pdf PDF
Atch 1 - Specifications Volume 1 addendum.pdf PDF
Atch 11 - BLDG 5 addendum.pdf PDF
Atch 17 - BLDG 11 addendum.pdf PDF
Atch 18 - BLDG 14 addendum.pdf PDF
Atch 28 - BLDG 108 addendum.pdf PDF
Atch 33 - BLDG 116 addendum.pdf PDF
Site Visit Sign-in Sheets - 6-28-22 - 6-30-22.pdf PDF
36C77622B0035 - 6-9-22.pdf PDF
Atch 6 - BLDG 1 - 1 of 2.pdf PDF
Atch 16 - BLDG 10.pdf PDF
Atch 19 - BLDG 28.pdf PDF
Atch 22 - BLDG 49.pdf PDF
Atch 35 - ADHC.pdf PDF
Atch 4 - General 1 of 2.pdf PDF
Atch 5 - General 2 of 2.pdf PDF
Atch 8 - BLDG 2.pdf PDF
Atch 23 - BLDG 50.pdf PDF
Atch 24 - BLDG 51.pdf PDF
Atch 27 - BLDG 96.pdf PDF
Atch 31 - BLDG 112.pdf PDF
Atch 10 - BLDG 4.pdf PDF
Atch 34 - BLDG 118.pdf PDF
Atch 2 - Specifications Volume 2.pdf PDF
Atch 3 - Specifications Volume 3 - Asbestos.pdf PDF
Atch 9 - BLDG 3.pdf PDF
Atch 11 - BLDG 5.pdf PDF
Atch 13 - BLDG 7 and 13.pdf PDF
Atch 14 - BLDG 8.pdf PDF
Atch 17 - BLDG 11.pdf PDF
Atch 29 - BLDG 109 and 57.pdf PDF
Atch 33 - BLDG 116.pdf PDF
Atch 37 - Brand Name Justification - St. Cloud.pdf PDF
Atch 38 - Contractor Core Work Hours.pdf PDF
Atch 39 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Atch 41 - Construction Wage Rates - Stearns 4-1-22.pdf PDF
Atch 42 - Contractor Safety - Environmental Form.docx DOCX document
Show all 50

Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LEGEND

CORRIDOR OUTLINE

VFY EXIST

BUILDING OUTLINE

VFY EXIST

TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST

44TH AVE.

TRAIL 1

TRAIL 2

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2)

15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

GRAVEL

GRAVEL

GRAVEL

EXISTING

ROAD

CHAIN LINK FENCE

CHAIN LINK FENCE

16' GATE

GRAVEL

ELECTRICAL

SUBSTATION

G E N E R A T O R

FUEL LINES

CONDU ITS TO TU NNEL

M V

D U

C T

B A

N K

1 1 2 W

PHARMACY ADDITION

11 2 E

G E N E R A T O R

B

CORRIDOR LINK

A

C T

TR

A

IL

ER

174 s .f.

256 s .f.

185 s .f.

149 s ..f.

155 s .f.

104 s .f.

70 s. .f .

72 s .f.

110 s .f.

276 s .f.

112 s .f.

99 s .f.

57 s .f.

146 s .f.

434 s .f.

R A

MP

U P

1:

M A X

R A

MP

U P

1:

M A X

RA

M P

UP

1:2 0 M

AX

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2) 15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

.3

TRANSFORMER

BUILD ING

#91

5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN

O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW

C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D

P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S

R EC O M M EN D ATIO N S

N EW G AS SU P P LY M AIN

IN TO B U ILD IN G

SP AR E

P H O N E LIN E

EXTEN D S TO

E XISTIN G

P H O N E IN

B O ILER R O O M

P ER P LAN .

SP AR E

P H O N E

LIN E TO

M ETER

TU N N EL

E XTEN D S

A D D ITIO N AL

2'- 0" U N D ER

B U ILD IN G

FUEL LINE

VENT LINE

1,000 GAL.

UNDERGROUND

DIESEL FUEL

TANK

1,000/5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

S 1

LIG H T

N EW G AS SU P P LY

(C O O R D IN ATE W ITH SU P P LIER )

12"D

10"D

"D

TP TP

EXIST. BUILDING

EXIST.

BUS STOP

CC

L O

O P

16"

20"

12"

3"

8"

DN

0.

0’

BIRDCAGE

B

IR

D C

A G

E

NSP ELECTRICAL

FOR HWY DEPT

T101

I.T.

CHILLER

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

VESTIBULE

DN

DN

DN

FD

DN

F B

F

B

F B

F

B

F B

F

B

SOUTH

VESTIBULE

PASS

THROUGH

LINK TO

BUILDI NG 51

6 3. 32 56

1 13 5. 35 78

PARKING

NO

PARKING

93 49

37 6

6 107

109 5

1A

S M

O K

E B

L D

G

SMOKE

BLDG

SMOKE

BLDG

S M

O K

E B

L D

G

SMOKE

BLDG

M.H.

STOR.

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

STOR.

BIO-

HAZ.

SAUK RIVER

GP

HOLDING POND

PROPOSED TR

SEE 6-GI000

SEE 112-GI000

SEE 54-GI000

SEE 54-GI000

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

OWNER AND

CONSULTANTS:

CONTACT:

ADDRESS:

MIKE ENGMARK

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

NAME:

ADDRESS:

CONTACT:

ADVANCED STRUCTURAL TECHNOLOGIES

7301 OHMS LANE; SUITE 215

EDINA, MN 55439

ZACHARY CRAIG

PHONE:

NAME:

ADDRESS:

CONTACT:

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

PHONE: 402-991-5520

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

IAN WEBER

763-412-4000

ARCHITECT:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

EDWARD MARKFORT

763-412-4000

952-854-9302

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

402-991-5520

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

COVER

DATE:

APPROVED: APPROVED: PROJECTS SECTION MANAGER

APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:

APPROVED: SAFETY MANAGER

APPROVED: CHIEF OF POLICE

APPROVED: PATIENT SAFETY

DATE:

DATE:

DATE: APPROVED: EMS MANAGER

APPROVED: M/O MANAGER

DATE:

DATE:

DATE:DATE:

APPROVED: MEDICAL CENTER DIRECTOR

APPROVED: PROJECT COR DATE:

APPROVED: INFECTION CONTROL NURSE DATE:

APPROVED: SERVICE LINE DIRECTOR

APPROVED: GEMS COORDINATOR DATE:

DATE:

APPROVED: NURSE EXECUTIVE

APPROVED: CHIEF OF STAFF DATE:

APPROVED: DIRECTOR FMS

APPROVED: ASSOCIATE DIRECTOR

DATE:

DATE:

DATE:

DATE:APPROVED: DATE:

APPROVED: DATE:

APPROVED: DATE:

Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System

N

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

VICINITY MAP:

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHONE: 320-252-1670

CIVIL ENGINEER:

VA COR:

TELECOMMUNICATIONS ENGINEER:

CONTACT:

ADDRESS:

JONATHAN WEST

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

PHONE: 504-250-2699

PROGRAM MANAGER:

EMAIL: Jonathan.West@vciint.com

STRUCTURAL ENGINEER:

MECH/ELEC/PLUMB/FIRE ENGINEER:

C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -7

-R E

M a rk fo rt

.r v t

/2

/2

:1

:0

P

M

7-GI000

BUILDINGS 7 & 13 COVER

SHEET & SHEET INDEX

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

BUILDINGS 7 AND 13 - EHRM INFRASTRUCTURE UPGRADES

7 & 13

03/30/2022

0APPROX 150' 300'75'

SHEET INDEX - BUILDING 7 & 13

SHEET NO. SHEET TITLE

7-GI000 BUILDINGS 7 & 13 COVER SHEET & SHEET INDEX

7-GI001 FIRST FLOOR LIFE SAFETY PLAN

7-GI111 FIRST FLOOR - INFECTION CONTROL & PHASING PLAN

7-HA-1A REFERENCE - FIRST FLOOR ASBESTOS RE-SURVEY

7-HA-2A REFERENCE - SECOND FLOOR ASBESTOS RE-SURVEY

13-HA-1A REFERENCE - FIRST FLOOR - ASBESTOS RE-SURVEY

7-AS110 FIRST FLOOR PLANS

7-S110 FIRST FLOOR PLANS

7-TD110 FIRST FLOOR PLAN - TELECOM - DEMOLITION

7-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS

7-TN210 FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE

7-TN300 ENLARGED PLANS - TELECOMMUNICATIONS - DEMO

7-TN400 ENLARGED PLANS - TELECOMMUNICATIONS

07-E100 FIRST FLOOR DEMOLITION PLAN - ELECTRICAL

07-E200 FIRST FLOOR PLAN - ELECTRICAL

07-E300 ELECTRICAL ENLARGED PLANS

07-E500 ELECTRICAL ONE-LINE DIAGRAMS

07-E600 ELECTRICAL SCHEDULES

07-M101 FIRST FLOOR DEMOLITION - MECHANICAL

07-M201 FIRST FLOOR REMODEL - MECHANICAL

SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION

1" = 50'-0"

KEY PLAN

ROOM SCHEDULE

NO. NAME C

A

B

LI

N G

P A

T C

H P

A N

E L

F

IB

E R

P O

W E

R

B O

N D

IN

G

U P

S

D E

D

IC

A T

E D

C O

O

LI

N G

T E

M P

E R

A T

U R

E

H U

M

ID

IT

Y

R A

C K

S E

N S

O R

S P

A C

E

AREA

WIDTH

(FT)

LENGTH

(FT)

HT TO

CLG

STRUCT REMARKS

FIRST FLOOR

102A TELECOM ROOM X X X X X X X X X X X 103 SF 7.0 14.7 10'-0" CONSTRUCT TO EHRM TELECOM ROOM STANDARDS.

SEE TELECOM DRAWINGS. CMU PARTITION BLOCK

INFILL WINDOWS. INFILL ROOF SMOKE VENTS. FLOOR

DRAIN.

FIRST FLOOR

PLACEHOLDER

BUILDING 13

12 SF SEE BUILDING 7 FOR TELECOM ROOM. SEE

TELECOMMUNICATION DRAWINGS

OPENING SCHEDULE

VA Building Number

ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION

H D

W G

R O

U P

F

IR

E L

A B

E L

(M

IN

G A

S K

E T

E

LE

C T

R

IC

A L

S L

A B

E L

COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT

PANEL

TYPE

2ND

PANEL

TYPE

PANEL

GLAZING FRAME TYPE

FRAME

GLAZING

7 TELECOM ROOM 102A 3'-0" 7'-0" HM-FS NONE HMM-1S NONE HW-3.2 45 Y Y Y

HAZARDOUS MATERIAL SCHEDULE

BUILDING

ROOM

NO. ROOM NAME

QUESTIONABLE HAZARDOUS

ELEMENT POSSIBLE ABATEMENT ACTION

FIRST FLOOR

7 102A TELECOM ROOM ASBESTOS - CONTAINING PIPE

INSULATION. SEE 7-HA-1A

NONE. PIPE INSULATION TO REMAIN UNDISTURBED

13 PLACEHOLDER

BUILDING 13

ACM. SEE 13-HA-1A NONE. MATERIAL TO REMAIN UNDISTURBED

HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT

DISTURB QUESTIONABLE HAZARDOUS MATERIAL.

ICRA PHASE CONSTRUCTION ROOM SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

CAI BLDG NAME /

FUNCTION

CONSTRUCTION

PROJECT ACTIVITY

INFECTION CONTROL

RISK GROUP

CONTROL

PROCEDURE CLASS SECTION

CONSTRUCTION ZONE /

OCCUPIED CONSTR

DAY /

NIGHT

FIRST FLOOR 102A TELECOM ROOM BOILERHOUSE TYPE D GROUP 1 CLASS III/IV CENTER ZONE7 DAY

FIRST FLOOR PLACEHOLDER

BUILDING 13

FACILITIES OFFICE CENTER OCCUPIED CONSTRUCTION DAY

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

1 UPDATE TO BID DOCUMENTS 06/29/22

536 175

1082 170

STORAGE

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

TELECOM

ROOM

TRAVEL DISTANCE

42'-0"

LIFE SAFETY SYMBOLS

SMOKE TIGHT

ASSEMBLY

1 HOUR FIRE

BARRIER

2 HOUR FIRE

BARRIER

3 HOUR FIRE

BARRIER

1 HOUR FIRE &

SMOKE BARRIER

2 HOUR FIRE &

SMOKE BARRIER

3 HOUR FIRE &

SMOKE BARRIER

HE

TRAVEL DISTANCE

100'-10"

TRAVEL DISTANCE

EA

EDEXIT EXIT

HORIZONTAL EXIT

EXIT DISCHARGE

EXIT ACCESS

FIRE

EXTINGUISHER

FE

FIRE

EXTINGUISHER

CABINET

FEC

LIMITS OF

CONSTRUCTION

SMOKE

COMPARTMENT

BOUNDARY

HEALTH CARE

SUITE

NOTE: NOT ALL SYMBOLS MY BE USED ON EACH PLAN

OCCUPANCY

SEPARATION

SHAFT

ADJACENT SYMBOLS SHOW PARTITION RATING AND

DAMPER REQUIREMENTS

HAZARDOUS USE

ADJACENT SYMBOLS SHOW PARTITION RATING.

OPENINGS REQUIRE CLOSER & LATCH

EXIT PASSAGEWAY

RATE AS STAIR

ALL OPENINGS TO BE RATED AS STAIR SHAFT

CORRIDOR

WALLS TO LIMIT THE TRANSFER OF SMOKE

ADJUNCT CORRIDOR or PSYCHIATRIC AREA or CONSTRUCTED WITH MIN. 4'-0" CLEAR

WITH (PER CHAPTER 19)

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -7

-R E

M a rk fo rt

.r v t

/2

/2

:2 :4

P

M

7-GI001

FIRST FLOOR LIFE SAFETY

PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

7 & 13

03/30/2022

3/32" = 1'-0"

FIRST LEVEL LIFE SAFETY PLAN

N

0 8' 16'4'

536 175

1082 170

STORAGE

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

E

101 102

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

102A

TELECOM

ROOM

PLACEHOLDER

BUILDING 13

BUILDING 13

BUILDING 7

ZONE 7

CONSTRUCTION / ICRA BARRIER

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of

Minnesota.

Name:

Date: License Number: MN# 18157

Typed or Printed Name: Tom Olesak

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10 C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -7

-R E

M a rk fo rt

.r v t

/2

/2

:2 :1

P

M

7-GI111

FIRST FLOOR - INFECTION

CONTROL & PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

7 & 13

03/30/2022

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

FIRST FLOOR 102A TELECOM ROOM BOILERHOUSE TYPE D GROUP 1 CLASS III/IV

FIRST FLOOR PLACEHOLDER

BUILDING 13

FACILITIES OFFICE

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

1/8" = 1'-0"

FIRST FLOOR - CONST BARRIER PLAN

-ASBESTOS-CONTAINING PIPE TAR/COATING

-ASBESTOS-CONTAINING PIPE INSULATION DEBRIS

-ASBESTOS-CONTAINING SINK UNDERCOATING

-ASBESTOS-CONTAINING PIPE INSULATION

CASTLE HILL ASSOCIATES, LLC.

N S

W E

BUILDING #7 - FIRST FLOOR PLAN

-ASBESTOS-CONTAINING WINDOW GLAZING

CASTLE HILL ASSOCIATES, LLC.

N S

W E

BUILDING #7 - SECOND FLOOR PLAN

-ASBESTOS-CONTAINING WINDOW GLAZING

-ASBESTOS-CONTAINING PIPE INSULATION IN SUB-FLOOR PIT

CASTLE HILL ASSOCIATES, LLC.

N

S

W E

BUILDING #13 - FIRST FLOOR PLAN

STORAGE

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

101 102

102A

TELECOM

ROOM

PLACEHOLDER

BUILDING 13

7' -0

/8

14'-8 3/8"

7-AS110

BUILDING 13

BUILDING 7

PROPOSED TR

SEE 6-GI000

SEE 112-GI000

SEE 54-GI000

SEE 54-GI000

102A

TELECOM

ROOM

MA8

MA8

2A

IN-03.01

7-AS110

S

LO

P E

D

SLOPE

DN

S

LO

P E

D N

SLOPE

DN

4'-0" 2'-6" 6'-8" 2'-6"

6' -4

2'

-6

8'-1" 7'-6"

8' -2

7' -4

/4

V

F Y

15'-0 1/4", VFY

TELECOM

ROOM

CMU BLOCK INFILL

EXTERIOR INTERIOR

102A

TELECOM

ROOM

BRINE

ROOM

MA8

ROOF CAPPED CURB

OVERHEAD LEAK DIVERTER,

SEE MECHANICAL

FIRE RATED PLYWOOD,

FINISH

FLUID-APPLIED

WATERPROOFING

4" HOUSEKEEPING PAD

6" CONCRETE SLAB,

SLOPE TO FLOOR DRAIN.

SEE STRUCT & MECH

7-AS110

7-AS110

SLOPE

2"

3"

ONE PIECE STAINLESS

STEEL CURB CAP

FLASHING WITH

INTEGRAL DRIP EDGE -

WELD ALL SEAMS &

JOINTS WATERTIGHT -

SECURE WITH RUBBER

WASHERED

FASTENERS (TWO PER

SIDE MINIMUM)

ANGLE CLOSURES AT

DECK ENDS

SELF-ADHERED

UNDERLAYMENT

RIGID INSULATION,

PROVIDE TAPERED

INSULATION TO

MINIMUM 1/4" PER

FOOT SLOPE

COVER BOARD

EXISTING CURB

EXISTING ROOF

MEMBRANE

METAL DECK - SECURE

TO CURB AT 6" O.C.

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

100% CONSTRUCTION DOCUMENTS

FOR BID - NOT FOR CONSTRUCTION

C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -7

-R E

M a rk fo rt

.r v t

/3

/2

:0

:2

P

M

7-AS110

FIRST FLOOR PLANS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

7 & 13

N

0 8' 16'4'1/8" = 1'-0"

FIRST FLOOR PLAN

1" = 50'-0"

KEY PLAN

1/4" = 1'-0"

ENLARGED FLOOR PLAN

N

0 4' 8'2'

NN

N

N

1/4" = 1'-0"

PARTIAL DEMOLITION PLAN

N

0 8' 16'4'

N

N

0 4' 8'2'

N

1/4" = 1'-0"

REFLECTED CEILING PLAN

DE1

DE15

FL3

FL20

RC1 RC2

_DEMOLITION PLAN KEYED NOTES

DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM

REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS

DE10 PREPARE FLOOR FOR FLOOR BUILDUP

DE15 REMOVE 30"X18" GLASS BLOCK WINDOW, PREPARE FOR INFILL

DE16 PREPARE ROOF MOUNTED PRESSURE RELIEF VENT FOR INFILL

DE33 PARTIALLY REMOVE FLOOR FOR FLOOR DRAIN

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_FLOOR PLAN KEYED NOTES

FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”

TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH

HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT

OVER FIRE RATING STAMP.

FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE

TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST

THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS

WITH FIRE CAULK.

UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE

TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST

THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS

WITH FIRE CAULK.

FL7 WALL INFILL, MATCH EXISTING CONSTRUCTION

FL8 FLOOR DRAIN, SEE MECHANICAL

FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.

FL21 OVERHEAD LEAK DIVERTER, SEE PLUMBING.

FL22 LEAK PREVENTION BARRIER WATERPROOFING DETAIL,

SEE AS601

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_REFLECTED CEILING PLAN KEYED NOTES

RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET

ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE

VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET

ROW OR SECTION.

RC2 OPEN TO STRUCTURAL FLOOR ABOVE

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

BRINE

ROOM

FL22

FL22

DE16

DE15

FL1_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED

SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN TELECOM

ROOMS.

DE15

DE1

FL3

FL22

3/8" = 1'-0"

PARTIAL BUILDING SECTION - BUILDING 7 TELECOM ROOM 102A

3" = 1'-0"

SECTION DETAIL - ROOF CAPPED CURB

DE33DE10

FL8

ABOVE

DE16

ABOVE

FL7 FL7

FL7

FL21

1 UPDATE TO BID DOCUMENTS 06/29/22

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

102A

TELECOM

ROOM

S E

E A

R C

H

SEE ARCH.

INFILL WINDOWS WITH CMU

CMU PARTITION

7-S110

PROPOSED TR

SEE 6-GI000

SEE 112-GI000

102A

TELECOM

ROOM S

E E

A R

C H

SEE ARCH.

MW2

M W

L1

S600

@ INFILL OPENINGS

NEW 6" HOUSEKEEPING PAD

7-S110

S500

NEW INTERIOR NON-LOAD

BEARING CMU PARTITION

DOWELS TO MATCH

SIZE AND SPACING

OF VERT. BARS

DRILL AND EPOXY INTO EXIST.

SOG. HILTI HY 200 EPOXY

ALL NEW REBAR IN BUILDING 7

SHALL BE EPOXY COATED OR

GALVANIZED FOR CORROSION

PROTECTION

1 1/2" MIN.

4" E

M B

E D

EXIST. SOG.

NEW 6"

HOUSEKEEPING PAD.

SEE 7/S500

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

7301 OHMS LANE

SUITE #215

(952) 854-9302 TEL.

EDINA, MN 55439

ASTENG.COM

AST PROJECT NUMBER: MN 1964

03/30/2022

ZDC JRO

656-21-235

EHRM INFRASTRUCTURE

UPGRADES

C U s e rs

\j o b ri e n \D o c u m e n ts

\1

-7

-R jo b ri e n

K Q

E N

.r v t

/2

/2

:4

:0

A

M

7-S110

FIRST FLOOR PLANS

16305

0 8' 16'4'1/8" = 1'-0"

FIRST FLOOR PLAN

1" = 50'-0"

KEY PLAN

3/8" = 1'-0"

ENLARGED FLOOR PLAN

N

N

N

N

N

SHEET NOTES:

1. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE CONTRACTOR PRIOR TO CONSTRUCTION.

ANY EXISTING CONDITIONS THAT DIFFER FROM THOSE SHOWN ON THE STRUCTURAL DRAWINGS MUST

BE BROUGHT TO THE IMMEDIATE ATTENTIONS OF THE STRUCTURAL ENGINEER (IN WRITING).

2. THE INFORMATION SHOWN ON THE DRAWING IS BASED ON THE EXISTING STRUCTURAL DRAWINGS, SURVEYED DATA AND PHOTOGRAPHS OF THE EXISTING BUILDING PROVIDED BY ARCH.

3. SEE ARCHITECTURAL PLANS FOR ALL OPENING LOCATIONS, DIMENSIONS AND INTERIOR PARTITIONS.

4. SEE PLAN, SCHEDULES AND SHEET S100 FOR DESIGN LOADS.

5. DO NOT CUT, CORE OR DEMOLISH ANY EXISTING BEAMS. OPENINGS MUST SHIFT TO AVOID AS-BUILT

LOCATION OF BEAMS.

6. ALL EXISTING PARTITIONS ARE ASSUMED TO BE OF LIGHT GAUGE CONSTRUCTION UNLESS NOTED

OTHERWISE. GC TO NOTIFY EOR IF DEMO WORK AT INTERIOR PARTITIONS CONTAIN

STRUCTURAL/ROLLED STEEL OR ARE OF MASONRY/CIP CONSTRUCTION.

7. ALL NEW OPENINGS GREATER THAN 5" IN DIAMETER OR 5"x5" ARE REQUIRED TO BE REINFORCED.

8. INDICATES 8" CMU WALL. #6 VERT. BARS AT 48" OC

9. AT ENDS OF CMU WALLS AND AT OPENINGS, GROUT (2) CONSECUTIVE CELLS SOLID WITH (1) #6 VERT BAR IN

EACH CELL.

10. SEE S600 FOR THE LINTEL SCHEDULE FOR NEW CMU PARTITIONS.

11. BRACE TOP OF MASONRY WALL WITH L4X4X1/4. 12" LONG @ 4'-0" O.C. SPACING. ALTERNATE SIDES OF THE MASONRY WALL. ANCHOR HORIZONTAL LEG AT UNDERSIDE OF EXIST. CONC. SLAB W/ (2) HILTI KWIK BOLT

3 WEDGE ANCHOR. 3/8" DIA. 2 1/4" LONG.

MW2

3/4" = 1'-0"

DETAIL AT NEW BUILDING 7 CMU PARTITION

REGISTRATION

LICENSE #:

I HEREBY CERTIFY THAT THIS PLAN,

SPECIFICATION, OR REPORT WAS

PREPARED BY ME OR UNDER MY

DIRECT SUPERVISION AND THAT I AM

A DULY LICENSED PROFESSIONAL

ENGINEER UNDER THE LAWS OF THE

STATE OF MINNESOTA.

PRINT NAME:

SIGNATURE:

DATE:

Zachary D. Craig

57219

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

CONFERENCE

M & O

OFFICE

M&O

101A

CLOSET

STORAGE

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

CONFERENCE

M & O

OFFICE

M&O

101A

CLOSET

7-TN300

7-TN300

2D

2D

4DD

D 2D

4D 2V 4D

WAP

WAP

WAP

WAP

E

E E

E E E

E E E

E

E E

E

LIMITS OF DATA CABLING DEMOLITION

PROPOSED TR

SEE 6-GI000

SEE 112-GI000

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:3

:3

P

M

7-TD110

FIRST FLOOR PLAN -

TELECOM - DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

7 & 13

N

0 8' 16'4'

1/8" = 1'-0"

FIRST FLOOR PLAN - TELECOM - DEMOLITION

1" = 50'-0"

KEY PLAN

NN

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

SHEET NOTES:

1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.

REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.

2. FOR EXISTING CABLE COUNT:

DATA CAT5e: 64 BLDG 6 (ROOM 104B) DATA CAT5e: 4 BLDG 12 (NO TELECOM ROOM) DATA CAT5e: 10 BLDG 54 (NO TELECOM ROOM) DATA CAT5e: 10 BLDG 69 (NO TELECOM ROOM)

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

SCALE: 1/4" = 1'-0"

BUILDING 13

101 102

STORAGE

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

SCALE: 1/4" = 1'-0"

BUILDING 13

101 102

7-TN400

102A

TELECOM ROOM

PLACEHOLDER BUILDING 13

4D 2V 4D

2D D

WAP

WAP

WAP

WAP

2DD

2D

4D

E

E E

E E E

E E E

E

E E

E

4" 1

PROPOSED TR

SEE 6-GI000

SEE 112-GI000

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:3

:3

P

M

7-TN110

FIRST FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

7 & 13

N

0 8' 16'4'

1/8" = 1'-0"

FIRST FLOOR PLAN - TELECOMMUNICATIONS

1" = 50'-0"

KEY PLAN

NN

SHEET NOTES:

1. PROVIDE JUNCTION BOX TO CONNECT FIBER CONDUIT ENTRY TO EXTEND CONDUIT PATHWAY TO THE

NEW TELECOM ROOM.

GENERAL NOTES:

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

SCALE: 1/4" = 1'-0"

BUILDING 13

101 102

STORAGE

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

SCALE: 1/4" = 1'-0"

BUILDING 13

101 102

PROPOSED TR

SEE 6-GI000

SEE 112-GI000

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:3

:3

P

M

7-TN210

FIRST FLOOR PLAN -

TELECOM - CABLE DISTANCE

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

7 & 13

1" = 30'-0"

FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE

N

0 30' 60'15' 1" = 50'-0"

KEY PLAN

NN

101A

CLOSET

101A

CLOSET

WAP

E1

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:3

:3

P

M

7-TN300

ENLARGED PLANS -

TELECOMMUNICATIONS -

DEMO

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

7 & 13

1/4" = 1'-0"

ENLARGED PLAN - BUILDING 7 - TR 102A - TELECOM - DEMO

1/4" = 1'-0"

ENLARGED PLAN - BUILDING 13 - EXIST RM 101 - TELECOM - DEMO

0 4' 8'2'

N

N

0 4' 8'2'

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

SHEET NOTES:

1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION.

EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK PLANS FOR SERVING

COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE

RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE

PROJECT.

1. ROOM 102A (BUILDING 7)

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 6

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

2. ROOM 101 (BUILDING 13)

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 12

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

AC

CR

C

7-TN400

1 - a b

1 - c d

W 12"x4"

12"x4"

12"x4"

102A

TELECOM ROOM

C2 126"

DATA RACK

CABLE TRAY

KEYPAD

WAP

E

12"x4"12"x4"

4"

AC

R

NOTES:

1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.

2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.

3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.

4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO

SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET. (NOT TO EXCEED 288 PORTS PER RACK).

5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.

6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.

7. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.

VERTICAL CABLE

MANAGEMENT (TYP)

RACK 1

1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL

1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)

1U 48 PORT CAT5E BACKBONE PATCH PANEL

1U CABLE MANAGEMENT

1U CABLE MANAGEMENT

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

6U 5KW RACK MOUNT UPS

6U SPACE FOR FUTURE USE. PROVIDE BLANK

PANELS FOR UNUSED SPACES.

V E

R T

IC

A

L R

A C

K P

D U

V E

R T

IC

A

L R

A C

K P

D U

NEMA L21-20R (TYP)

CHANNEL RACK (TYP)

D

PROVIDE DATA CABLE TO RACK

MOUNTED UPS FOR CONNECTION

TO MONITORING SYSTEM

RACK 1

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

1U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

SPACE FOR FUTURE HORIZONTAL CABLE

DISTRIBUTION. PROVIDE BLANKING PANELS FOR

UNUSED SPACES.

Nathan M. TimmNo DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/1

/2

:3

:4

P

M

7-TN400

ENLARGED PLANS -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

7 & 13

N

0 2' 4'1'

0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'

GENERAL NOTES:

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.

THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED

FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE

PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.

1. ROOM 102A (BUILDING 7)

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 28 FROM BLDG 6, 6 FROM BLDG 7, 12 FROM BLDG 13, 11 FROM BLDG 54, 10 FROM BLDG 69, 4 FROM BLDG 112

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6A): 71

DATA (CAT6): 0

1/2" = 1'-0"

ENLARGED PLAN - BUILDING 7 - TR 102A - TELECOM - CABLE TRAY AND DATA

1/4" = 1'-0"

1 - a

1/4" = 1'-0"

1 - b

1/4" = 1'-0"

1 - c

1/4" = 1'-0"

1 - d

NOT TO SCALE

COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - BUILDING 7 - TR 102A

SHEET NOTES:

1. PROVIDE A NEW ACCESS CONTROL PANEL TO BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND KEYPAD FOR THIS ROOM TO BE WIRED TO THE NEW ACCESS CONTROL PANEL. EXISTING CARD READERS AND KEYPADS WILL BE MOVED TO THE NEW CONTROL PANEL UNDER A DIFFERENT PROJECT.

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

CONFERENCE

M & O

OFFICE

M&O

101A

CLOSET

07-E300

7-P3 7-L1-1 7-P2 7-P1

7-ES

PROPOSED TR

SEE 6-GI000

SEE 112-GI000

SEE 54-GI000

SEE 54-GI000

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:1

:4

A

M

07-E100

FIRST FLOOR DEMOLITION

PLAN - ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

IMEG IMEG

16305

1/8" = 1'-0"

FIRST FLOOR DEMOLITION PLAN - ELECTRICAL

NO SCALE

KEY PLAN

N

N

100% CD 03/30 05-06-2022

SALT

101B

STAIR

101A

CORR

ROOM

BRINE

ROOM

SOFTENER

OFFICE

104A

CLOSET

ROOM

BOILER

STORAGE

REPAIR &

ROOM

DEISEL

ROOM

DEISEL

LOCKER

PLUMBING

105A

CORRIDOR

109A

STORAGE

TOOL 110A

BATH

STORAGE

MASON

109B

STORAGE

MASON

SHOP

PLUMBING

111A

OFFICE

STOR.

SAFETY

SCALE: 1/4" = 1'-0"

UPDATED 12/10/01

BUILDING 13

101 102

E

7-P3 7-L1-1 7-P2 7-P1

7-ES

FAP

07-E300

07-E300

CU-7-1

B7IT-1-11

WP

102A

TELECOM

ROOM

PLACEHOLDER

BUILDING 13

PROPOSED TR

SEE 6-GI000

SEE 112-GI000

SEE 54-GI000

SEE 54-GI000

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:1

:5

A

M

07-E200

FIRST FLOOR PLAN -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

IMEG IMEG

16305

1/8" = 1'-0"

FIRST FLOOR PLAN - ELECTRICAL

KEYNOTES:

1. PROVIDE ELECTRICAL CONNECTION TO

CONDENSING UNIT, AS REQUIRED.

COORDINATE FINAL LOCATION AND

CONNECTION REQUIREMENTS WITH

MECHANICAL.

NO SCALE

KEY PLAN

N

N

ROOM

BRINE

ROOM

BRINE

SD

E

101A

CORR

ROOM

BRINE

A

B7IT-1

a

A

B7IT-1

a

A

B7IT-2

b

A

B7IT-2

b ab

102A

TELECOM

ROOM

B7IT-1

AC-7-1

B7IT-1-3,5,7

B7IT-2-1,3,5

B7IT-1-1

42"

B7IT-2-7

42"

B7IT-1-1

42"

B7IT-2-7

42"

B7IT-1-1

42"

B7IT-2

102A

TELECOM

ROOM

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:1

:5

A

M

07-E300

ELECTRICAL ENLARGED

PLANS

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

IMEG IMEG

16305

N O R

HT

1/4" = 1'-0"

FIRST FLOOR ENLARGED - TR 102A - LIGHTING

N O R

HT

1/4" = 1'-0"

FIRST FLOOR ENLARGED - TR 102A - POWER & SYSTEM

N O R

HT

1/4" = 1'-0"

FIRST FLOOR DEMOLITION ENLARGED - ELEC 102 - ELECTRICAL

KEYNOTES:

1. DISCONNECT AND REMOVE LIGHTS AND

RECEPTACLES IN AREA OF NEW IT ROOM.

MAINTAIN CIRCUIT CONTINUITY TO ADJOINING

SPACES.

2. INDOOR UNIT TO BE POWERED BY OUTDOOR

UNIT. COORDINATE EXACT LOCATION WITH

M.C.

3. CONNECT SMOKE DETECTOR TO NEAREST

EXISTING SLC.

4. COORDINATE FINAL LOCATION OF

RECEPTACLE L21-20R WITH TELECOM

CONTRACTOR. PROVIDE 3/4"C-4#12, 1#12 GND

TO PANEL FOR EACH RECEPTACLE.

5. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-

PHASE, 4-WIRE RACK MOUNTED UPS FOR

EACH RACK TOWER.

6. PROVIDE APC#AP8861 RPDU RACK PDU 2G

WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,

ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R

OUTLETS. PROVIDE TWO PER RACK, MOUNTED

PER MANUFACTURER'S REQUIREMENTS.

7. RELOCATE EXISTING LIGHT FIXTURE TO THE

NORTH TO AVOID NEW WALL.

SHEET NOTES:

1. REFER TO TECHNOLOGY PLANS FOR IT ROOM

LAYOUT AND RACK LAYOUT/DETAILS.

2. REFER TO SHEET 0-GE400 DETAIL FOR LAYOUT

& ONE-LINE OF RACK.

BASEMENT

FIRST FLOOR

B7IT-1

100Y

7-P3

B7IT-2

100Y

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/6

/2

:1

:5

A

M

07-E500

ELECTRICAL ONE-LINE

DIAGRAMS & SCHEDULES

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

IMEG IMEG

16305

N O R

HT

12" = 1'-0"

PARTIAL POWER RISER

KEYNOTES:

1. PROVIDE NEW 100A/3P CIRCUIT BREAKER IN

EXISTING PANEL TO MATCH EXISTING TYPE

AND AIC RATING.

100% CD 03/30

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 21.9 A

TOTAL CONNECTED AMPS: 21.92 A

Receptacles 0.72 kVA 100.00% 0.72 kVA TOTAL ESTIMATED DEMAND LOAD: 7.898 kVA

Power 7 kVA 100.00% 7 kVA TOTAL CONNECTED LOAD: 7.90 kVA

Lighting 0.178 kVA 100.00% 0.178 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 28.00 24.98 15.39

Total Load: 3.21 kVA 2.84 kVA 1.85 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 -- -- -- -- -- -- 1 0 -- -- -- 1 20 A SPARE 16 --

13 CU-7-1 20 A 2 1 0 -- -- -- 1 20 A SPARE 14 --

11 WP GFI REC. 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 1.67 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 1.67 0 -- -- -- 1 20 A SPARE 6 --

3 L21-20R RACK 20 A 3 1.67 0 -- -- -- 1 20 A SPARE 4 --

1 TELECOM ROOM REC. 20 A 1 0.54 0 -- -- -- 1 20 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES: PROVIDE INTEGRAL ELECTRIC METER IN PANEL.

SCCR: 10 kA

LOCATION: TELECOM ROOM 102A WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B7IT-1

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 15.4 A

TOTAL CONNECTED AMPS: 15.37 A

Receptacles 0.36 kVA 100.00% 0.36 kVA TOTAL ESTIMATED DEMAND LOAD: 5.538 kVA

Power 5 kVA 100.00% 5 kVA TOTAL CONNECTED LOAD: 5.54 kVA

Lighting 0.178 kVA 100.00% 0.178 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 17.12 15.60 13.89

Total Load: 2.03 kVA 1.84 kVA 1.67 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

7 TELECOM ROOM REC. 20 A 1 0.36 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 1.67 0 -- -- -- 1 20 A SPARE 6 --

-- 3 -- -- -- -- -- -- 1.67 0 -- -- -- 1 20 A SPARE 4 --

1 L21-20R RACK 20 A 3 1.67 0 -- -- -- 1 20 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES: PROVIDE INTEGRAL ELECTRIC METER IN PANEL.

SCCR: 10 kA

LOCATION: TELECOM ROOM 102A WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B7IT-2

7-P3

7-P3

05-06-2022

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/2

/2

:5

:3

A

M

07-E600

ELECTRICAL SCHEDULES

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

09/17/21

IMEG IMEG

16305

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 21.9 A

TOTAL CONNECTED AMPS: 21.92 A

Receptacles 0.72 kVA 100.00% 0.72 kVA TOTAL ESTIMATED DEMAND LOAD: 7.898 kVA

Power 7 kVA 100.00% 7 kVA TOTAL CONNECTED LOAD: 7.90 kVA

Lighting 0.178 kVA 100.00% 0.178 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 28.00 24.98 15.39

Total Load: 3.21 kVA 2.84 kVA 1.85 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 -- -- -- -- -- -- 1 0 -- -- -- 1 20 A SPARE 16 --

13 CU-7-1 20 A 2 1 0 -- -- -- 1 20 A SPARE 14 --

11 WP GFI REC. 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 1.67 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 1.67 0 -- -- -- 1 20 A SPARE 6 --

3 L21-20R RACK 20 A 3 1.67 0 -- -- -- 1 20 A SPARE 4 --

1 TELECOM ROOM REC. 20 A 1 0.54 0 -- -- -- 1 20 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES: PROVIDE INTEGRAL ELECTRIC METER IN PANEL.

SCCR: 10 kA

LOCATION: TELECOM ROOM 102A WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B7IT-1

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 15.4 A

TOTAL CONNECTED AMPS: 15.37 A

Receptacles 0.36 kVA 100.00% 0.36 kVA TOTAL ESTIMATED DEMAND LOAD: 5.538 kVA

Power 5 kVA 100.00% 5 kVA TOTAL CONNECTED LOAD: 5.54 kVA

Lighting 0.178 kVA 100.00% 0.178 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 17.12 15.60 13.89

Total Load: 2.03 kVA 1.84 kVA 1.67 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

9 LIGHTING 20 A 1 0.18 0 -- -- -- 1 20 A SPARE 10 --

7 TELECOM ROOM REC. 20 A 1 0.36 0 -- -- -- 1 20 A SPARE 8 --

-- 5 -- -- -- -- -- -- 1.67 0 -- -- -- 1 20 A SPARE 6 --

-- 3 -- -- -- -- -- -- 1.67 0 -- -- -- 1 20 A SPARE 4 --

1 L21-20R RACK 20 A 3 1.67 0 -- -- -- 1 20 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES: PROVIDE INTEGRAL ELECTRIC METER IN PANEL.

SCCR: 10 kA

LOCATION: TELECOM ROOM 102A WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B7IT-2

7-P3 7-P3

100% CD 03/30

53095

TELECOM ROOM

102A

CORR

101A

STAIR

101B

SOFTNER ROOM

OFFICE

1"COND-E

4"STM-E

2"STM-E

PROPOSED

TR

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTA ARCHITECT/ENGINEER OF STAM

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 1

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.M

R

.r v t

/1

/2

:1

:1

P

M

07-M101

FIRST FLOOR

DEMOLITION -

MECHANICAL

EHRM

INFRASTRUCTURE

UPGRADES

656‐21‐235

RDL JCL

16305

7 & 13

1/4" = 1'-0"

FIRST FLOOR DEMOLITION - TELECOM 102A

KEYNOTES 1/07-M101:

1. REMOVE AND DISPOSE OF CAST IRON STEAM RADIATOR AND

ASSOCIATED PIPING AS SHOWN.

2. EXISTING 1" CONDENSATE RETURN TO BE DEMO'D BACK TO

LOCATION SHOWN. PREPARE PIPING FOR RECONNECTION.

3. REMOVE EXISTING 4" STEAM PIPING AS SHOWN AND PREPARE

ENDS FOR RECONNECTION. REFER TO 1/07-M201 FOR

REINSTALLATION.

4. REMOVE EXISTING 2" STEAM PIPING AS SHOWN AND PREPARE

ENDS FOR RECONNECTION. REFER TO 1/07-M201 FOR

REINSTALLATION.

5. REMOVE EXISTING 1" CONDENSATE PIPING AS SHOWN AND

PREPARE ENDS FOR RECONNECTION. REFER TO 1/07-M201 FOR

REINSTALLATION.

6. SUSPENDED STEAM HEATING UNIT TO REMAIN.

7. 12" DOMESTIC WATER LINE TO REMAIN.

8. 1-1/2" STEAM LINE SERVING RADIATOR TO BE DEMO'D

BACK AND CAPPED.

9. EXISTING STEAM GENERATOR TO REMAIN.

#FIELD VERIFICATION NOTES

1. THE HVAC CONTRACTOR SHOULD VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT

THEIR BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:

A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER, AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN SCOPE OF

WORK, WHETHER EXPLICITLY SHOWN OR NOT.

B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.

C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.

D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.

E. SIZE AND LOCATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING.

2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBILIY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO BID AND INCLUDE IN

THEIR BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.

3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.

4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND

ARCHITECT FOR DIRECTION.

NO SCALE

KEY PLAN

N

N

0 4' 8'2'

100% CD 03/3

T

BRINE ROOM

TELECOM ROOM

102A

CORR

101A

STAIR

101B

SOFTNER ROOM

OFFICE

AC-7-1

RACK

PROVIDED

BY OTHERS

CU-7-1

1" PC

CP-7-1

PROPOSED

TR

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTA ARCHITECT/ENGINEER OF STAM

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 1

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.M

R

.r v t

/1

/2

:1

:1

P

M

07-M201

FIRST FLOOR REMODEL -

MECHANICAL

EHRM

INFRASTRUCTURE

UPGRADES

656‐21‐235

RDL JCL

16305

7 & 13

1/4" = 1'-0"

FIRST FLOOR - MECHANICAL - TELECOM 102A

KEYNOTES 1/07-M201:

1. REROUTE AND RECONNECT EXISTING 4" STEAM LINE.

FIELD VERIFY EXACT LOCATION.

2. RE-PIPE AND SLEEVE EXISTING 1" CONDENSATE LINE.

3. NEW WALL MOUNTED DUCTLESS COOLING UNIT AC-7-1.

4. RE-ROUTE AND RECONNECT AND RECONNECT EXISTING

1" CONDENSATE LINE.

5. RE-ROUTE AND RECONNECT EXISTING 2" STEAM LINE.

6. ROUTE NEW REFRIGERANT PIPING TO AC-7-1 UNIT IN

TELECOM 102A.

7. NEW AIR-COOLED CONDENSING UNIT. PROVIDE

CONCRETE PAD. REFER TO 1/0-GM400 FOR

REFRIGERANT PIPING DETAIL. REFER TO 3/0-GM401 FOR

UNIT MOUNTING DETAIL.

8. PROVIDE NEW THERMOSTAT

9. ROUTE 1" CONDENSATE LINE TO EXISTING SUMP. FIELD

VERIFY REQUIREMENTS.

10. EXISTING SUSPENDED STEAM HEATING UNIT TO REMAIN.

11. EXISTING DOMESTIC WATER LINE. VERIFY NEW WALL

PROXIMITY AND COORDINATE WITH

ARCHITECT/ENGINEER.

12. EXTEND EXISTING 4" STEAM LINE 10 FEET TO THE EAST.

13. PROVIDE PIPE DRIP PAN AND PIPE WRAP ON TWO 4"

PLUMBING PIPE RUN. SEE DETAIL 6/01-M400.

14. ROUTE NEW REFRIGERANT PIPING THROUGH EXISTING

OPENING IN WALL. SEAL WALL PENETRATION AS

SPECIFIED.

15. EXISTING STEAM GENERATOR TOREMAIN.

16. REFERE TO 4/0-GM401 FOR WALL PENETRATION SEALING

DETAIL.

FIELD VERIFICATION NOTES

1. THE HVAC CONTRACTOR SHOULD VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT

THEIR BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:

A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER, AND CONDITION OF ALL EXISTING HVAC

EQUIPMENT WITHIN SCOE OF WORK, WHETHER EXPLICITLY SHOWN OR NOT.

B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.

C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.

D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.

E. SIZE AND LOCATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING.

2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBILIY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO BID AND INCLUDE IN

THEIR BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.

3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.

4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND

ARCHITECT FOR DIRECTION.

N

0 4' 8'2'

NO SCALE

KEY PLAN

N

NO SCALE

TELECOM 102A PHOTOS

100% CD 03/3

7-GI000 - BUILDINGS 7 & 13 COVER SHEET & SHEET INDEX
7-GI001 - FIRST FLOOR LIFE SAFETY PLAN
7-GI111 - FIRST FLOOR - INFECTION CONTROL & PHASING PLAN
7-HA-1A - REFERENCE - FIRST FLOOR ASBESTOS RE-SURVEY
7-HA-2A - REFERENCE - SECOND FLOOR ASBESTOS RE-SURVEY
13-HA-1A - REFERENCE - FIRST FLOOR - ASBESTOS RE-SURVEY
7-AS110 - FIRST FLOOR PLANS
7-S110 - FIRST FLOOR PLANS
7-TD110 - FIRST FLOOR PLAN - TELECOM - DEMOLITION
7-TN110 - FIRST FLOOR PLAN - TELECOMMUNICATIONS
7-TN210 - FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE
7-TN300 - ENLARGED PLANS - TELECOMMUNICATIONS - DEMO
7-TN400 - ENLARGED PLANS - TELECOMMUNICATIONS
07-E100 - FIRST FLOOR DEMOLITION PLAN - ELECTRICAL
07-E200 - FIRST FLOOR PLAN - ELECTRICAL
07-E300 - ELECTRICAL ENLARGED PLANS
07-E500 - ELECTRICAL ONE-LINE DIAGRAMS
07-E600 - ELECTRICAL SCHEDULES
07-M101 - FIRST FLOOR DEMOLITION - MECHANICAL
07-M201 - FIRST FLOOR REMODEL - MECHANICAL