Atch 30 - BLDG 111 addendum.pdf
PDF 7 MB Posted
- Attached to
- Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud Federal contract opportunity
- Solicitation number
- 36C77622B0035
About this file
This solicitation requests proposals for infrastructure upgrades at the St. Cloud Veterans Affairs Health Care System campus. The contractor shall provide all labor, materials, tools and equipment to perform electrical, bonding, UPS, building management system, access security, HVAC, data center/server room physical security, and fiber infrastructure upgrades across multiple buildings. The work includes renovating and expanding existing spaces as required. The solicitation is issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.
View the file
Other files for this federal contract opportunity
Show all 50
Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEGEND
CORRIDOR OUTLINE
VFY EXIST
BUILDING OUTLINE
VFY EXIST
TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST
44TH AVE.
TRAIL 1
TRAIL 2
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2)
15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
GRAVEL
GRAVEL
GRAVEL
EXISTING
ROAD
CHAIN LINK FENCE
CHAIN LINK FENCE
16' GATE
GRAVEL
ELECTRICAL
SUBSTATION
G E N E R A T O R
FUEL LINES
CONDU ITS TO TU NNEL
M V
D U
C T
B A
N K
1 1 2 W
PHARMACY ADDITION
11 2 E
G E N E R A T O R
B
CORRIDOR LINK
A
C T
TR
A
IL
ER
174 s .f.
256 s .f.
185 s .f.
149 s ..f.
155 s .f.
104 s .f.
70 s. .f .
72 s .f.
110 s .f.
276 s .f.
112 s .f.
99 s .f.
57 s .f.
146 s .f.
434 s .f.
R A
MP
U P
1:
M A X
R A
MP
U P
1:
M A X
RA
M P
UP
1:2 0 M
AX
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2) 15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
.3
TRANSFORMER
BUILD ING
#91
5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN
O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW
C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D
P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S
R EC O M M EN D ATIO N S
N EW G AS SU P P LY M AIN
IN TO B U ILD IN G
SP AR E
P H O N E LIN E
EXTEN D S TO
E XISTIN G
P H O N E IN
B O ILER R O O M
P ER P LAN .
SP AR E
P H O N E
LIN E TO
M ETER
TU N N EL
E XTEN D S
A D D ITIO N AL
2'- 0" U N D ER
B U ILD IN G
FUEL LINE
VENT LINE
1,000 GAL.
UNDERGROUND
DIESEL FUEL
TANK
1,000/5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
S 1
LIG H T
N EW G AS SU P P LY
(C O O R D IN ATE W ITH SU P P LIER )
12"D
10"D
"D
TP TP
EXIST. BUILDING
EXIST.
BUS STOP
CC
L O
O P
16"
20"
12"
3"
8"
DN
0.
0’
BIRDCAGE
B
IR
D C
A G
E
NSP ELECTRICAL
FOR HWY DEPT
T101
I.T.
CHILLER
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
VESTIBULE
DN
DN
DN
FD
DN
F B
F
B
F B
F
B
F B
F
B
SOUTH
VESTIBULE
PASS
THROUGH
LINK TO
BUILDI NG 51
6 3. 32 56
1 13 5. 35 78
PARKING
NO
PARKING
93 49
37 6
109 5
1A
S M
O K
E B
L D
G
SMOKE
BLDG
SMOKE
BLDG
S M
O K
E B
L D
G
SMOKE
BLDG
M.H.
STOR.
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
STOR.
BIO-
HAZ.
SAUK RIVER
GP
HOLDING POND
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
OWNER AND
CONSULTANTS:
CONTACT:
ADDRESS:
MIKE ENGMARK
ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
NAME:
ADDRESS:
CONTACT:
ADVANCED STRUCTURAL TECHNOLOGIES
7301 OHMS LANE; SUITE 215
EDINA, MN 55439
ZACHARY CRAIG
PHONE:
NAME:
ADDRESS:
CONTACT:
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
PHONE: 402-991-5520
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
IAN WEBER
763-412-4000
ARCHITECT:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
EDWARD MARKFORT
763-412-4000
952-854-9302
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
402-991-5520
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
COVER
DATE:
APPROVED: APPROVED: PROJECTS SECTION MANAGER
APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:
APPROVED: SAFETY MANAGER
APPROVED: CHIEF OF POLICE
APPROVED: PATIENT SAFETY
DATE:
DATE:
DATE: APPROVED: EMS MANAGER
APPROVED: M/O MANAGER
DATE:
DATE:
DATE:DATE:
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: PROJECT COR DATE:
APPROVED: INFECTION CONTROL NURSE DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: GEMS COORDINATOR DATE:
DATE:
APPROVED: NURSE EXECUTIVE
APPROVED: CHIEF OF STAFF DATE:
APPROVED: DIRECTOR FMS
APPROVED: ASSOCIATE DIRECTOR
DATE:
DATE:
DATE:
DATE:APPROVED: DATE:
APPROVED: DATE:
APPROVED: DATE:
Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System
N
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
VICINITY MAP:
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHONE: 320-252-1670
CIVIL ENGINEER:
VA COR:
TELECOMMUNICATIONS ENGINEER:
CONTACT:
ADDRESS:
JONATHAN WEST
ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
PHONE: 504-250-2699
PROGRAM MANAGER:
EMAIL: Jonathan.West@vciint.com
STRUCTURAL ENGINEER:
MECH/ELEC/PLUMB/FIRE ENGINEER:
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:4
:2
P
M
111-GI000
BUILDING 111 COVER SHEET &
SHEET INDEX
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
BUILDING 111 - EHRM INFRASTRUCTURE UPGRADES
03/30/2022
0APPROX 150' 300'75'
SHEET INDEX - BUILDING 111
SHEET NO. SHEET TITLE
111-GI000 BUILDING 111 COVER SHEET & SHEET INDEX
111-GI101 BASEMENT FLOOR - INFECTION CONTROL & PHASING PLAN
111-GI111 FIRST FLOOR - INFECTION CONTROL & PHASING PLAN
111-AS100 BASEMENT FLOOR PLANS
111-AS110 FIRST FLOOR PLANS
111-TD100 BASEMENT FLOOR PLAN - TELECOM - DEMOLITION
111-TN100 BASEMENT FLOOR PLAN - TELECOMMUNICATIONS
111-TD110 FIRST FLOOR PLAN - TELECOM - DEMOLITION
111-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS
111-TN210 FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE
111-TN200 BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE
111-TN400 ENLARGED PLANS - TELECOMMUNICATIONS
111-TN401 ENLARGED PLANS - TELECOMMUNICATIONS
111-E200 BASEMENT FLOOR PLAN - ELECTRICAL
111-E201 FIRST FLOOR PLAN - ELECTRICAL
111-E300 ELECTRICAL ENLARGED PLANS
SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION
ROOM SCHEDULE
NO. NAME C
A
B
LI
N G
P A
T C
H P
A N
E L
F
IB
E R
P O
W E
R
B O
N D
IN
G
U P
S
D E
D
IC
A T
E D
C O
O
LI
N G
T E
M P
E R
A T
U R
E
H U
M
ID
IT
Y
R A
C K
S E
N S
O R
S P
A C
E
AREA
WIDTH
(FT)
LENGTH
(FT) REMARKS
BASEMENT
062 TELECOM ROOM X X X X X X X X X X X 70 SF 5.2 13.5 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM ROOM
STANDARDS. SEE TELECOM DRAWINGS
FIRST FLOOR
129 TELECOM ROOM X X X X X X X X X X X 75 SF 5.6 14.1 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM ROOM
STANDARDS. SEE TELECOM DRAWINGS
OPENING SCHEDULE
VA Building Number
ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION
H D
W G
R O
U P
F
IR
E L
A B
E L
(M
IN
G A
S K
E T
E
LE
C T
R
IC
A L
S L
A B
E L
COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT
PANEL
TYPE
2ND
PANEL
TYPE
PANEL
GLAZING FRAME TYPE
FRAME
GLAZING
HAZARDOUS MATERIAL SCHEDULE
LEVEL
ROOM
NO. ROOM NAME
QUESTIONABLE HAZARDOUS
ELEMENT POSSIBLE ABATEMENT ACTION
BASEMENT 062 TELECOM ROOM NONE NONE
FIRST FLOOR 129 TELECOM ROOM NONE NONE
HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT
DISTURB QUESTIONABLE HAZARDOUS MATERIAL.
ICRA PHASE CONSTRUCTION ROOM SCHEDULE
LEVEL
ROOM
NO. ROOM NAME
CAI BLDG NAME /
FUNCTION
CONSTRUCTION
PROJECT ACTIVITY
INFECTION CONTROL
RISK GROUP
CONTROL
PROCEDURE CLASS SECTION
CONSTRUCTION ZONE /
OCCUPIED CONSTR
DAY /
NIGHT
BASEMENT 062 TELECOM ROOM OUTPATIENT MENTAL
HEALTH
TYPE C GROUP 1 CLASS II EAST OCCUPIED CONSTRUCTION NIGHT
FIRST FLOOR 129 TELECOM ROOM OUTPATIENT MENTAL
HEALTH
TYPE C GROUP 2 CLASS III EAST OCCUPIED CONSTRUCTION NIGHT
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
1 UPDATE TO BID DOCUMENTS 06/29/22
B U F F E R
C C B U F F E R
LINK
CONCOURSE
S-01
S-02
S-01
S-02
STAIR
STAIR
STAIR
STAIR PSYCH
OFFICE/COUN
IT/DATA
EX. ELEC.
ROOM2-HR FIRE
H R
F
IR
E
2-HR FIRE
1-HR FIRE
H R
F
IR
E
UP
UP
BUILDING 111BUILDING 28
WOMEN
MEN
STORAGE
CORRIDOR
C03
WHEEL
CHAIR
B28-B
EXISTING
B28-B
EXISTING
MAA
OFFICE
POLICE
PHARMACY
PHARMACY
PHARMACY
SUB
WAITING
LOBBY
C02
VESTIBULE
C01
CORRIDOR
C12
B28-B
EXISTING
HAC
ENCLOSED
LOADING
OXYGEN
STORAGE
HAC
VENDING
15A
WAITING
CORRIDOR
C04
TRIAGE
TRIAGE
PSYCH
OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
23 CLINIC
OFFICE
CLEAN
UTILITY
MECH
ROOM
STAIR
M2
VEST
C09
CONFERENCE
STAFF
PIPE CHASE
29A
EXAM 13
CNS
PSYCH
OFFICE
CORRIDOR
C11
PSYCH
OFFICE
TREATMENT
CNS
OFFICE
NURSE
PHONE
TOILET
VITAL
SIGNS
EXAM 1
EXAM 2
SOILED
UTILITY
STAFF
NURSE
PRACTIONER
NURSE
PRACTIONER
NURSE
PRACTIONER
C
LE
R
IC
A L/
N U
R S
E S
T A
T
IO
N
TOILET
PIPE CHASE
61A
CORRIDOR
C05
C O
R R
ID
O
R C
C O
R R
ID
O
R C
MEDS
VITAL
SIGNS
EXAM 3
EXAM 7
EXAM 8
EXAM 9
C O
R R
ID
O
R C
EXAM 4
EXAM 10
EXAM 5
EXAM 11
EXAM 6
EXAM 12
NURSE
PRACTIONER
NURSE
PRACTIONER
C O
R R
ID
O
R C
PSYCH
OFFICE
CRASH
CART
PSYCH
OFFICE
INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND
LIMITS OF CONSTRUCTION
1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER
LOCATION, AND DOOR, WHERE SHOWN
TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER
LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.
UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA
TELECOM
ROOM
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:1 :0
A
M
111-GI101
BASEMENT FLOOR -
INFECTION CONTROL &
PHASING PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM BMW
16305
03/30/2022
ROOM ICRA SCHEDULE
LEVEL
ROOM
NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS
BASEMENT 062 TELECOM ROOM OUTPATIENT MENTAL HEALTH TYPE C GROUP 1 CLASS II
FIRST FLOOR 129 TELECOM ROOM OUTPATIENT MENTAL HEALTH TYPE C GROUP 2 CLASS III
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
1/8" = 1'-0"
BASEMENT FLOOR - CONST BARRIER PLAN
N
0 8' 16'4'
S
C1-08
C1-10
C1-11
C1-06
C1-05
C1-07
114 116
S-01
S-02
P-1
115 117 119 120 122
121 123 125
144 142 140
141143145150
146148
S-03
VTEL
PSYCH
OFFICE/COUN
MEETING/
BREAKROOM
CORR.
CORR.
CORR.
CORR.
CORR.
CORR.
LPN
INTAKE
LPN
INTAKE
LPN
INTAKE LPN
INTAKE
LPN
WORKROOM
MED
ROOM
STORAGE
ELECT
MECHANICAL
TOILET
TOILET
TOILET
TOILET
GROUP
ROOM
STORAGE
WHEEL
CHAIR
WAITING
RECEPTION
STAIR
STAIR
LOBBY
ELEV.
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
HSKP
LOCKERS
IT/DATA
WAITING
CHASE
CHASE
CHASE
STAIR
TOILET
TOILET
HALL
UP
UP
DN
DN
INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND
LIMITS OF CONSTRUCTION
1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER
LOCATION, AND DOOR, WHERE SHOWN
TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER
LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.
UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:1 :1
A
M
111-GI111
FIRST FLOOR - INFECTION
CONTROL & PHASING PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
03/30/2022
ROOM ICRA SCHEDULE
LEVEL
ROOM
NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS
BASEMENT 062 TELECOM ROOM OUTPATIENT MENTAL HEALTH TYPE C GROUP 1 CLASS II
FIRST FLOOR 129 TELECOM ROOM OUTPATIENT MENTAL HEALTH TYPE C GROUP 2 CLASS III
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
1/8" = 1'-0"
FIRST FLOOR - CONST BARRIER PLAN
N
0 8' 16'4'
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
B U F F E R
C C B U F F E R
LINK
CONCOURSE
S-01
S-02
S-01
S-02
STAIR
STAIR
STAIR
STAIR
PSYCH
OFFICE/COUN
IT/DATA
EX. ELEC.
ROOM2-HR FIRE
H R
F
IR
E
2-HR FIRE
1-HR FIRE
H R
F
IR
E
UP
UP
WOMEN
MEN
STORAGE
CORRIDOR
C03
WHEEL
CHAIR
B28-B
EXISTING
B28-B
EXISTING
MAA
OFFICE
POLICE
PHARMACY
PHARMACY
PHARMACY
SUB
WAITING
LOBBY
C02
VESTIBULE
C01
CORRIDOR
C12
B28-B
EXISTING
HAC
ENCLOSED
LOADING
OXYGEN
STORAGE
HAC
VENDING
15A
WAITING
CORRIDOR
C04
TRIAGE
TRIAGE
PSYCH
OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
23 CLINIC
OFFICE
CLEAN
UTILITY
MECH
ROOM
STAIR
M2
VEST
C09
CONFERENCE
STAFF
PIPE CHASE
29A
EXAM 13
CNS
PSYCH
OFFICE
CORRIDOR
C11
PSYCH
OFFICE
TREATMENT
CNS
OFFICE
NURSE
PHONE
TOILET
VITAL
SIGNS
EXAM 1
EXAM 2
SOILED
UTILITY
STAFF
NURSE
PRACTIONER
NURSE
PRACTIONER
NURSE
PRACTIONER
C
LE
R
IC
A L/
N U
R S
E S
T A
T
IO
N
TOILET
PIPE CHASE
61A
CORRIDOR
C05
C O
R R
ID
O
R C
C O
R R
ID
O
R C
MEDS
VITAL
SIGNS
EXAM 3
EXAM 7
EXAM 8
EXAM 9
C O
R R
ID
O
R C
EXAM 4
EXAM 10
EXAM 5
EXAM 11
EXAM 6
EXAM 12
NURSE
PRACTIONER
NURSE
PRACTIONER
C O
R R
ID
O
R C
PSYCH
OFFICE
CRASH
CART
PSYCH
OFFICE
IT/DATA
2-HR FIRE
IT/DATA
2-HR FIRE
VEST
5' -2
/2
13'-5 1/2"
TELECOM
ROOM
BUILDING 28
BUILDING 28
TELECOM
ROOM
TELECOM
ROOM
4'-8 3/32" 3'-0" 5'-9 13/32"
TELECOM
ROOM
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:1 :1
A
M
111-AS100
BASEMENT FLOOR PLANS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
03/30/2022
1/8" = 1'-0"
BASEMENT FLOOR - OVERALL PLAN
N
0 8' 16'4'
_DEMOLITION PLAN KEYED NOTES
DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM
REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_FLOOR PLAN KEYED NOTES
FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”
TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH
HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT
OVER FIRE RATING STAMP.
FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE
TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST
THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS
WITH FIRE CAULK.
FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_REFLECTED CEILING PLAN KEYED NOTES
RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET
ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE
VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION.
RC2 OPEN TO STRUCTURAL FLOOR ABOVE
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
N
0 4' 8'2'
N
0 4' 8'2'
N
0 4' 8'2'
DE1
RC1
DE1
DE1
FL20
RC2
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
DEMOLITION AND CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS
DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED
SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN TELECOM
ROOMS.
1/4" = 1'-0"
DEMOLITION PLAN
1/4" = 1'-0"
ENLARGED FLOOR PLAN
FL1
FL3
FL3
1/4" = 1'-0"
REFLECTED CEILING PLAN
PATIENT
ROOM
PATIENT
ROOM
OFFICE
MED
PATIENT
ROOM
LAUNDRY
147A
TOILET
145A
TOILET
151A
TOILET
C1-08
C1-10
C1-11
C1-06
C1-05
C1-07
114 116
S-01
S-02
P-1
115 117 119 120 122
121 123 125
144 142 140
141143145150
146148
S-03
VTEL
PSYCH
OFFICE/COUN
MEETING/
BREAKROOM
CORR.
CORR.
CORR.
CORR.
CORR.
CORR.
LPN
INTAKE
LPN
INTAKE
LPN
INTAKE LPN
INTAKE
LPN
WORKROOM
MED
ROOM
STORAGE
ELECT
MECHANICAL
TOILET
TOILET
TOILET
TOILET
GROUP
ROOM
STORAGE
WHEEL
CHAIR
WAITING
RECEPTION
STAIR
STAIR
LOBBY
ELEV.
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
PSYCH
OFFICE/COUN
HSKP
LOCKERS
IT/DATA
WAITING
CHASE
CHASE
CHASE
STAIR
TOILET
TOILET
HALL
UP
UP
DN
DN
IT/DATA
IT/DATA
5' -7
14'-1 1/2"
TELECOM
ROOM
BUILDING 28
BUILDING 28
TELECOM
ROOM
5'-1 1/4" 3'-0" 5'-4 1/4"
TELECOM
ROOM
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:1 :2
A
M
111-AS110
FIRST FLOOR PLANS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
03/30/2022
N
0 8' 16'4'
1/8" = 1'-0"
FIRST FLOOR PLAN - OVERALL
_DEMOLITION PLAN KEYED NOTES
DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM
REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_FLOOR PLAN KEYED NOTES
FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”
TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH
HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT
OVER FIRE RATING STAMP.
FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE
TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST
THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS
WITH FIRE CAULK.
FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_REFLECTED CEILING PLAN KEYED NOTES
RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET
ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE
VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION.
RC2 OPEN TO STRUCTURAL FLOOR ABOVE
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
N
0 4' 8'2'
N
0 4' 8'2'
N
0 4' 8'2'
DE1
RC1
FL1 FL20
RC2
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
DEMOLITION AND CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS
DETERMINED BY VA) WITH WALL MOUNT BRACKET AND CODE REQUIRED
SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN TELECOM
ROOMS.
1/4" = 1'-0"
DEMOLITION PLAN
DE1
DE1
1/4" = 1'-0"3
ENLARGED FLOOR PLAN
FL3
FL3
1/4" = 1'-0"
REFLECTED CEILING PLAN
NORTH
B U F F E R
C C B U F F E R
LINK
CONCOURSE
S-01
S-02
S-01
S-02
STAIR
STAIR
STAIR
STAIR PSYCH
OFFICE/COUN
IT/DATA
EX. ELEC.
ROOM2-HR FIRE
H R
F
IR
E
2-HR FIRE
1-HR FIRE
H R
F
IR
E
UP
UP
EXAM 7
EXAM 1
TREATMENT
PSYCH
OFFICE
NURSE
PHONE
OFFICE
CNS
VESTIBULE
C01
PHARMACY
PHARMACY
PHARMACY
WAITING
LOBBY
C02
EXISTING
MAA
OFFICE
POLICE
WOMEN
SUB
WAITING
CORRIDOR
C03
MEN
STORAGE
ENCLOSED
LOADING
CORRIDOR
C12
B28-B
EXISTING
B28-B
EXISTING HAC
CORRIDOR
C04
WHEEL
CHAIR
HAC
OXYGEN
STORAGE
14 VENDING
15A
PIPE CHASE
61A
TOILET
TOILET
C
LE
R
IC
A L /
N U
R S
E S
TA
T I
O N
VITAL
SIGNS
C O
R R
ID
O
R C
6 MEDS
VITAL
SIGNS
TRIAGE
TRIAGE
PSYCH
OFFICE
C O
R R
ID
O
R C
PSYCH
OFFICE
PSYCH
OFFICE
CNS
EXAM 13
NURSE
PRACTIONER
VEST
C09
EXAM 11
EXAM 5
CLEAN
UTILITY
EXAM 9
EXAM 8
CORRIDOR
C11
EXAM 2
EXAM 3
EXAM 10
EXAM 4
C O
R R
ID
O
R C
PSYCH
OFFICE
CORRIDOR
C05
PSYCH
OFFICE
CLINIC
OFFICE
NURSE
PRACTIONER
NURSE
PRACTIONER
NURSE
PRACTIONER
EXAM 12
EXAM 6
NURSE
PRACTIONER
STAFF
CONFERENCE
C O
R R
ID
O
R C
SOILED
UTILITY
STAIR
M2
PIPE CHASE
STAFF
CRASH
CART
PSYCH
OFFICE
IT/DATA
2-HR FIRE
TELECOM
ROOM
111-TD100
E
E
E
E
E
E
E
E
E
E
E
E
"x
2"
"x 2"
"x
2"
12"x2"
12"x2"
12"x2"
12"x2"
"x
2"
"x
2"
"x
2"
12"x2"
12"x2"
E
E 12"x2"
LIMITS OF DATA CABLING
TELECOM
ROOM
R R
DATA RACK
12"x2"
E
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:5
P
M
111-TD100
BASEMENT FLOOR PLAN -
TELECOM - DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 8' 16'4' 1/8" = 1'-0"
BASEMENT FLOOR PLAN - TELECOM - DEMOLITION
1/4" = 1'-0"
ENALRGED PLAN - RM 062 - TELECOM - DEMO
N
0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE
RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE
PROJECT.
1. ROOM 062
EXISTING CABLE COUNT
DATA (CAT6): 100
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 100
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 100
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
SHEET NOTES:
1. EXISTING 2 POST RACKS WILL BE DEMOLISHED AND REPLACED BY A SINGLE 4 POST CHANNEL RACK.
2. NEW COPPER BACKBONE WILL BE PULLED TO EACH NEW TR AND INSTALLED TO A 48 PORT PATCH PANEL IN
THE RACK.
3. RETAIN DATA CABLE: EXISTING DATA CABLE THROUGHOUT THIS AREA IS SUFFICIENT TO REMAIN. NEW
CABLING NOT REQUIRED. RETAIN EXISTING CABLING IN SERVICE.
U F F E R
C C B U F F E R
UP
UP
DN
DN
EXISTING
CANOPY ROOFS
BELOW -
PROTECT
EXISTING CANOPY BELOW
S
B U F F E R
C C B U F F E R
UP
UP
DN
DN
EXISTING
CANOPY ROOFS
BELOW -
PROTECT
EXISTING CANOPY BELOW
111-TD110
E
E
E
E
E
E
E
E
E
"x
2"
"x 2"
12"x2"
12"x2"
"x
2"
12"x2"
12"x2"
"x
2"
12"x2"
LIMITS OF DATA CABLING
DATA RACK
RR
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:0
P
M
111-TD110
FIRST FLOOR PLAN -
TELECOM - DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/8" = 1'-0"
FIRST FLOOR PLAN - TELECOM - DEMOLITION
1/4" = 1'-0"
ENALRGED PLAN - RM 129 - TELECOM - DEMO
N
0 8' 16'4'
N
0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE
RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE
PROJECT.
1. ROOM 129
EXISTING CABLE COUNT
DATA (CAT6): 100
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 100
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 100
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
SHEET NOTES:
1. EXISTING 2 POST RACKS WILL BE DEMOLISHED AND REPLACED BY A SINGLE 4 POST CHANNEL RACK.
2. NEW COPPER BACKBONE WILL BE PULLED TO EACH NEW TR AND INSTALLED TO A 48 PORT PATCH PANEL IN
THE RACK.
3. RETAIN DATA CABLE: EXISTING DATA CABLE THROUGHOUT THIS AREA IS SUFFICIENT TO REMAIN. NEW
CABLING NOT REQUIRED. RETAIN EXISTING CABLING IN SERVICE.
F F E R
C C B U F F E R
LINK
CONCOURSE
S-01
S-02
S-01
S-02
STAIR
STAIR
STAIR
STAIR
PSYCH
OFFICE/COUN
IT/DATA
EX. ELEC.
ROOM2-HR FIRE
H R
F
IR
E
2-HR FIRE
1-HR FIRE
H R
F
IR
E
UP
UP
BUILDING 111
BUILDING 28 BUILDING 111
BUILDING 111
B-115
TO
LAST UPDATED: 12-23-19
WOMEN
MEN
STORAGE
CORRIDOR
C03
WHEEL
CHAIR
MAA
OFFICE
PHARMACY
PHARMACY
PHARMACY
SUB
WAITING
LOBBY
C02
VESTIBULE
C01
CORRIDOR
EXISTING
HAC
ENCLOSED
LOADING
OXYGEN
STORAGE
HAC
VENDING
15A
WAITING
CORRIDOR
C04
TRIAGE
TRIAGE
PSYCH
OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
23 CLINIC
OFFICE
CLEAN
UTILITY
MECH
ROOM
STAIR
M2
VEST
C09
CONFERENCE
STAFF
PIPE CHASE
29A
EXAM 13
CNS
PSYCH
OFFICE
CORRIDOR
C11
PSYCH
OFFICE
TREATMENT
CNS
OFFICE
NURSE
PHONE
TOILET
VITAL
SIGNS
EXAM 1
EXAM 2
SOILED
UTILITY
STAFF
NURSE
PRACTIONER
NURSE
PRACTIONER
NURSE
PRACTIONER
C
LE
R
IC
A L/
N U
R S
E S
TA
TI
O N
TOILET
PIPE CHASE
61A
CORRIDOR
C05
C O
R R
ID
O
R C
C O
R R
ID
O
R C
MEDS
VITAL
SIGNS
EXAM 3
EXAM 7
EXAM 8
EXAM 9
C O
R R
ID
O
R C
EXAM 4
EXAM 10
EXAM 5
EXAM 11
EXAM 6
EXAM 12
NURSE
PRACTIONER
NURSE
PRACTIONER
C O
R R
ID
O
R C
PSYCH
OFFICE
CRASH
CART
PSYCH
OFFICE
B U F F E R
C C B U F F E R
LINK
CONCOURSE
S-01
S-02
S-01
S-02
STAIR
STAIR
STAIR
STAIR
PSYCH
OFFICE/COUN
IT/DATA
EX. ELEC.
ROOM2-HR FIRE
H R
F
IR
E
2-HR FIRE
1-HR FIRE
H R
F
IR
E
UP
UP
BUILDING 111
BUILDING 28 BUILDING 111
BUILDING 111
B-115
TO
LAST UPDATED: 12-23-19
WOMEN
MEN
STORAGE
CORRIDOR
C03
WHEEL
CHAIR
MAA
OFFICE
PHARMACY
PHARMACY
PHARMACY
SUB
WAITING
LOBBY
C02
VESTIBULE
C01
CORRIDOR
EXISTING
HAC
ENCLOSED
LOADING
OXYGEN
STORAGE
HAC
VENDING
15A
WAITING
CORRIDOR
C04
TRIAGE
TRIAGE
PSYCH
OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
23 CLINIC
OFFICE
CLEAN
UTILITY
MECH
ROOM
STAIR
M2
VEST
C09
CONFERENCE
STAFF
PIPE CHASE
29A
EXAM 13
CNS
PSYCH
OFFICE
CORRIDOR
C11
PSYCH
OFFICE
TREATMENT
CNS
OFFICE
NURSE
PHONE
TOILET
VITAL
SIGNS
EXAM 1
EXAM 2
SOILED
UTILITY
STAFF
NURSE
PRACTIONER
NURSE
PRACTIONER
NURSE
PRACTIONER
C
LE
R
IC
A L/
N U
R S
E S
TA
TI
O N
TOILET
PIPE CHASE
61A
CORRIDOR
C05
C O
R R
ID
O
R C
C O
R R
ID
O
R C
MEDS
VITAL
SIGNS
EXAM 3
EXAM 7
EXAM 8
EXAM 9
C O
R R
ID
O
R C
EXAM 4
EXAM 10
EXAM 5
EXAM 11
EXAM 6
EXAM 12
NURSE
PRACTIONER
NURSE
PRACTIONER
C O
R R
ID
O
R C
PSYCH
OFFICE
CRASH
CART
PSYCH
OFFICE
/2
13'-5 1/2"
TELECOM
ROOM062
TELECOM ROOM111-TN400
12"x2"
12"x2"
12"x2"
12"x2"
"x
2"
"x
2"
"x
2"
"x
2"
"x 2"
"x
2"
12"x2"
12"x2"
E
E
E
E
E
E
E
E
E
E
E
E
E
E 12"x2"
4"
4"
4"
4"
4"
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:0
P
M
111-TN100
BASEMENT FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/8" = 1'-0"
BASEMENT FLOOR PLAN - TELECOMMUNICATIONS
N
0 8' 16'4'
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
UP
UP
DN
DN
EXISTING
CANOPY ROOFS
BELOW -
PROTECT
EXISTING CANOPY BELOW
S
UP
UP
DN
DN
EXISTING
CANOPY ROOFS
BELOW -
PROTECT
EXISTING CANOPY BELOW
14'-1 1/2"
TELECOM
ROOM
TELECOM ROOM
111-TN401
"x
2"
12"x2"
"x
2"
"x 2"
12"x2"
12"x2"
"x
2"
12"x2"
12"x2"
E
E
E
E
E
E
E
E
E
C2 126"
F2
12" LADDER
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:0
P
M
111-TN110
FIRST FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/8" = 1'-0"
FIRST FLOOR PLAN - TELECOMMUNICATIONS
N
0 8' 16'4'
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
F F E R
C C B U F F E R
LINK
CONCOURSE
S-01
S-02
S- 0 1
S-02
STAIR
STAIR
STAIR
STAIR PSYCH
OFFICE/COUN
IT/DATA
EX. ELEC.
ROOM2-HR FIRE
H R
F
IR
E
2-HR F IRE
1-HR FIRE
H R
F
IR
E
UP
UP
BUILDING 111
BUILDING 28 BUILDING 111
BUILDING 111
B-115
TO
LAST UPDATED: 12-23-19
WOME N
MEN
STOR AGE
CORRI DOR
C0 3
WHE EL
CHAIR
MAA
OFFICE
PHARMACY
PHARMACY
PHARMACY
SUB
WAITING
LOB BY
C0 2
VESTI BULE
C0 1
CORRI DOR
EXISTING
HAC
ENC LOS ED
LOAD ING
OXY GE N
STOR AGE
HAC
VENDING
15A
WAITING
CORRI DOR
C0 4
TRIAGE
TRIAGE
PSYCH
OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
23 CLINIC
OFFICE
CLEAN
UTILITY
MECH
ROOM
STAIR
M2
VEST
C0 9
CONFERE NCE
STA FF
PIPE CHASE
29A
EXAM 13
CNS
PSYCH
OFFICE
CORRI DOR
C1 1
PSYCH
OFFICE
TREA TME NT
CNS
OFFICE
NURSE
PHONE
TOILET
VITAL
SIGNS
EXAM 1
EXAM 2
SOILED
UTILITY
STA FF
NURSE
PRACTI ONER
NURSE
PRACTI ONER
NURSE
PRACTI ONER
C
LE
R
IC
AL
N U
RS
E
S
TA
TI
O
N
TOILET
PIPE CHASE
61A
CORRI DOR
C0 5
C O
R R
ID
O
R C
C O
R R
ID
O
R C
MEDS
VITAL
SIGNS
EXAM 3
EXAM 7
EXAM 8
EXAM 9
C O
R R
ID
O
R C
EXAM 4
EXAM 10
EXAM 5
EXAM 11
EXAM 6
EXAM 12
NURSE
PRACTI ONER
NURSE
PRACTI ONER
C O
R R
ID
O
R C
PSYCH
OFFICE
CRASH
CART
PSYCH
OFFICE
B U F F E R
C C B U F F E R
LINK
CONCOURSE
S-01
S-02
S- 0 1
S-02
STAIR
STAIR
STAIR
STAIR PSYCH
OFFICE/COUN
IT/DATA
EX. ELEC.
ROOM2-HR FIRE
H R
F
IR
E
2-HR F IRE
1-HR FIRE
H R
F
IR
E
UP
UP
BUILDING 111
BUILDING 28 BUILDING 111
BUILDING 111
B-115
TO
LAST UPDATED: 12-23-19
WOME N
MEN
STOR AGE
CORRI DOR
C0 3
WHE EL
CHAIR
MAA
OFFICE
PHARMACY
PHARMACY
PHARMACY
SUB
WAITING
LOB BY
C0 2
VESTI BULE
C0 1
CORRI DOR
EXISTING
HAC
ENC LOS ED
LOAD ING
OXY GE N
STOR AGE
HAC
VENDING
15A
WAITING
CORRI DOR
C0 4
TRIAGE
TRIAGE
PSYCH
OFFICE
PSYCH
OFFICE
PSYCH
OFFICE
23 CLINIC
OFFICE
CLEAN
UTILITY
MECH
ROOM
STAIR
M2
VEST
C0 9
CONFERE NCE
STA FF
PIPE CHASE
29A
EXAM 13
CNS
PSYCH
OFFICE
CORRI DOR
C1 1
PSYCH
OFFICE
TREA TME NT
CNS
OFFICE
NURSE
PHONE
TOILET
VITAL
SIGNS
EXAM 1
EXAM 2
SOILED
UTILITY
STA FF
NURSE
PRACTI ONER
NURSE
PRACTI ONER
NURSE
PRACTI ONER
C
LE
R
IC
AL
N U
RS
E
S
TA
TI
O
N
TOILET
PIPE CHASE
61A
CORRI DOR
C0 5
C O
R R
ID
O
R C
C O
R R
ID
O
R C
MEDS
VITAL
SIGNS
EXAM 3
EXAM 7
EXAM 8
EXAM 9
C O
R R
ID
O
R C
EXAM 4
EXAM 10
EXAM 5
EXAM 11
EXAM 6
EXAM 12
NURSE
PRACTI ONER
NURSE
PRACTI ONER
C O
R R
ID
O
R C
PSYCH
OFFICE
CRASH
CART
PSYCH
OFFICE
/2
13'-5 1/2"
TELECOM
ROOM
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:0
P
M
111-TN200
BASEMENT FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 30' 60'15'
1" = 30'-0"
BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE
UP
UP
DN
DN
EXISTING
CANOPY ROOFS
BELOW -
PROTECT
EXISTING CANOPY BELOW
S
UP
UP
DN
DN
EXISTING
CANOPY ROOFS
BELOW -
PROTECT
EXISTING CANOPY BELOW
14'-1 1/2"
TELECOM
ROOM
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:0
P
M
111-TN210
FIRST FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 30' 60'15' 1" = 30'-0"
FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE
IT/DATA
2-HR FIRE
IT/DATA
2-HR FIRE
C R
C
A C
TELECOM
ROOM
DATA RACK
111-TN400
1 - a b
1 - c d
111-TN401
2 - a
111-TN401
b
111-TN401
2 - c
111-TN401
d
W
12"x2"
12"x2"
12"x2"
12"x2" 12"x2"
12"x2"
12"x2"
KEYPAD
CABLE TRAY
C2 126"
12"x2"
E
2" 4"
UP
AC
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET. (NOT TO EXCEED 288 PORTS PER RACK).
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER
ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
7. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
VERTICAL CABLE
MANAGEMENT (TYP)
RACK 1
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)
1U 48 PORT CAT5E BACKBONE PATCH PANEL
1U CABLE MANAGEMENT
1U CABLE MANAGEMENT
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
6U 5KW RACK MOUNT UPS
6U SPACE FOR FUTURE USE. PROVIDE BLANK
PANELS FOR UNUSED SPACES.
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
NEMA L21-20R (TYP)
CHANNEL RACK (TYP)
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
RACK 1
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE BLANKING PANELS FOR
UNUSED SPACES.
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:0
P
M
111-TN400
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 2' 4'1'
0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM 062
EXISTING CABLE COUNT
DATA (CAT6): 100
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 100
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6A): 0
DATA (CAT6): 100
1/2" = 1'-0"
ENLARGED PLAN - TR 062 - TELECOM - CABLE TRAY AND DATA
1/4" = 1'-0"
1 - a
1/4" = 1'-0"
1 - b
1/4" = 1'-0"
1 - c
1/4" = 1'-0"
1 - d
NOT TO SCALE
COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - TR 062
SHEET NOTES:
1. IF NO ACCESS CONTROL PANEL IS PRESENT IN THE TR, PROVIDE A NEW ACCESS CONTROL PANEL TO
BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND KEYPAD FOR THIS ROOM TO BE
WIRED TO THE NEW ACCESS CONTROL PANEL. EXISTING CARD READERS AND KEYPADS WILL BE
MOVED TO THE NEW CONTROL PANEL UNDER A DIFFERENT PROJECT.
C R
C
A C
TELECOM
ROOM
111-TN400
1 - a b
1 - c d
111-TN401
2 - a
111-TN401
b
111-TN401
2 - c
111-TN401
d
DATA RACK
CABLE TRAY
KEYPADW
C2 126"
12"x2"12"x2"
12"x2" 12"x2"
12"x2"
12"x2"
12"x2"
E
12"x2"
2" DOWN
12" LADDER
F2
AC
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET. (NOT TO EXCEED 288 PORTS PER RACK).
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER
ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
7. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
VERTICAL CABLE
MANAGEMENT (TYP)
RACK 1
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)
1U 48 PORT CAT5E BACKBONE PATCH PANEL
1U CABLE MANAGEMENT
1U CABLE MANAGEMENT
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
6U 5KW RACK MOUNT UPS
6U SPACE FOR FUTURE USE. PROVIDE BLANK
PANELS FOR UNUSED SPACES.
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
NEMA L21-20R (TYP)
CHANNEL RACK (TYP)
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
RACK 1
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE BLANKING PANELS FOR
UNUSED SPACES.
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:5
:0
P
M
111-TN401
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 2' 4'1'
0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM 129
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 100
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6A): 100
DATA (CAT6): 0
1/2" = 1'-0"
ENLARGED PLAN - TR 129 - TELECOM - CABLE TRAY AND DATA
1/4" = 1'-0"
2 - a
1/4" = 1'-0"
2 - b
1/4" = 1'-0"
2 - c
1/4" = 1'-0"
2 - d
NOT TO SCALE
COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - TR 129
SHEET NOTES:
1. IF NO ACCESS CONTROL PANEL IS PRESENT IN THE TR, PROVIDE A NEW ACCESS CONTROL PANEL TO
BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND KEYPAD FOR THIS ROOM TO BE
WIRED TO THE NEW ACCESS CONTROL PANEL. EXISTING CARD READERS AND KEYPADS WILL BE
MOVED TO THE NEW CONTROL PANEL UNDER A DIFFERENT PROJECT.
F F E R
C C B U F F E R
2-HR FIRE
H R
F
IR
E
2-HR FIRE
1-HR FIRE
H R
F
IR
E
UP
UP
BUILDING 111
111-E300
TELECOM
ROOM
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/6
/2
:0
:5
P
M
111-E200
BASEMENT FLOOR PLAN -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
TBD GJL
16305
1/8" = 1'-0"
BASEMENT FLOOR PLAN - ELECTRICAL
0 8' 16'4'
N
100% CD 03/30
STAMP
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN# hereby certify that this plan, specification or port was prepared by me or under my direc upervision and that I am a duly Licensed ngineer under the laws of the State of Minn ame:
ate: 03/30/2022 cense Number: MN# 05-06-2022
F F E R
C C B U F F E R
UP
UP
BUILDING 111
111-E300
TELECOM ROOM
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/6
/2
:0
:0
P
M
111-E201
FIRST FLOOR PLAN -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
TBD GJL
16305
1/8" = 1'-0"
FIRST FLOOR PLAN - ELECTRICAL
0 8' 16'4'
N
100% CD 03/30
STAMP
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN# hereby certify that this plan, specification or port was prepared by me or under my direc upervision and that I am a duly Licensed ngineer under the laws of the State of Minn ame:
ate: 03/30/2022
2-HR FIRE
L1-1 / 37,39,41 L1-2 / 37,39,41
1 2 3
TELECOM ROOM
4 4
1 2 3
P2 / 37,39,41 P1 / 37,39,41
TELECOM
ROOM
4 4
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/6
/2
:0
:0
P
M
111-E300
ELECTRICAL ENLARGED
PLANS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
TBD GJL
16305
KEYNOTES:
1. COORDINATE FINAL LOCATION OF
RECEPTACLE L21-20R WITH TELECOM
CONTRACTOR. PROVIDE 3/4"C-4#12, 1#12 GND
TO PANEL FOR EACH RECEPTACLE.
2. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-
PHASE,4-WIRE RACK MOUNTED UPS FOR EACH
RACK TOWER.
3. PROVIDE APC#AP8861 RPDU RACK PDU 2G
WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,
ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R
OUTLETS. PROVIDE TWO PER RACK, MOUNTED
PER MANUFACTURER'S REQUIREMENTS.
4. VERIFY EXACT CIRCUIT AVAILABILITY IN PANEL.
#SHEET NOTES:
1. REFER TO TECHNOLOGY PLANS FOR IT ROOM
LAYOUT AND RACK LAYOUT/DETAILS.
2. REFER TO SHEET 0-GE400 DETAIL LAYOUT &
ONE-LINE OF RACK.
1/4" = 1'-0"
FIRST FLOOR ENLARGED - TR 129
- POWER & SYSTEM
1/4" = 1'-0"
BASEMENT ENLARGED - TR 162 -
POWER & SYSTEM
0 4' 8'2'
N
0 4' 8'2'
N
100% CD 03/30
STAMP
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN# hereby certify that this plan, specification or port was prepared by me or under my direc upervision and that I am a duly Licensed ngineer under the laws of the State of Minn ame:
ate: 03/30/2022
| 111-GI000 - BUILDING 111 COVER SHEET & SHEET INDEX |
| 111-GI101 - BASEMENT FLOOR - INFECTION CONTROL & PHASING PLAN |
| 111-GI111 - FIRST FLOOR - INFECTION CONTROL & PHASING PLAN |
| 111-AS100 - BASEMENT FLOOR PLANS |
| 111-AS110 - FIRST FLOOR PLANS |
| 111-TD100 - BASEMENT FLOOR PLAN - TELECOM - DEMOLITION |
| 111-TD110 - FIRST FLOOR PLAN - TELECOM - DEMOLITION |
| 111-TN100 - BASEMENT FLOOR PLAN - TELECOMMUNICATIONS |
| 111-TN110 - FIRST FLOOR PLAN - TELECOMMUNICATIONS |
| 111-TN200 - BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE |
| 111-TN210 - FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE |
| 111-TN400 - ENLARGED PLANS - TELECOMMUNICATIONS |
| 111-TN401 - ENLARGED PLANS - TELECOMMUNICATIONS |
| 111-E200 - BASEMENT FLOOR PLAN - ELECTRICAL |
| 111-E201 - FIRST FLOOR PLAN - ELECTRICAL |
| 111-E300 - ELECTRICAL ENLARGED PLANS |
File details come from the government source that posted it. Updated .