7TH FLOOR ROOF
N
8TH FLOOR SICU
8TH FLOOR KEY PLAN
1. EXISTING CONDITIONS ARE BASED ON INFORMATION OBTAINED FROM EXISTING DRAWINGS AND
FIELD SURVEY, AND SHALL NOT BE CONSTRUED "AS BUILT." THE CONTRACTOR SHALL FIELD
VERIFY EXISTING CONDITIONS PRIOR TO ONSET OF CONSTRUCTION.
2. THE CONTRACTOR SHALL COORDINATE WITH OWNER FOR ALL EXISTING EQUIPMENT AND
FURNITURE ITEMS THAT ARE TO BE SALVAGED OR REINSTALLED PRIOR TO THE
COMMENCEMENT OF DEMOLITION.
3. THE OWNER SHALL HAVE THE FIRST RIGHT TO ALL MATERIALS AND EQUIPMENT THAT ARE
REMOVED BY THE CONTRACTOR. THE CONTRACTOR SHALL VERIFY WHEN REMOVAL OF ITEMS
ARE TO BE RETAINED BY THE OWNER AT THE PRE CONSTRUCTION MEETING.
4. PATCH AND REPAIR SURFACES AND FINISHES AFFECTED BY THE DEMOLITION OR THE REMOVAL
OF CONSTRUCTION AS NECESSARY TO MAINTAIN THE FINISH QUALITY OF NEW SPACE.
5. FILL ALL DUCT AND PIPE PENETRATIONS IN DEMO AREA WITH 2 - HOUR RATED ASSEMBLY.
6. CONTRACTOR TO DEMOLISH BACK TO AND CAP ALL TAPS OFF OF MAIN BRANCHES PER
KEYNOTES ABOVE.
7. CONTRACTOR SHALL PROTECT REMAINING DUCTWORK AND PIPING FROM DAMAGE
THROUGHOUT CONSTRUCTION.
8. DESIGN BUILD TEAM AND A/E OF RECORD MUST FOLLOW ALL CURRENT NATIONAL TIL
STANDARDS, THROUGHOUT DESIGN AND CONSTRUCTION.
GENERAL DEMOLITION FLOOR PLAN NOTES
K
J
I
H
G2
G
F
E
21 3 4 5 6 7 8 9 9A 10 11 11a 12
16"ø 10"ø 6"ø18"ø
VAV-151
14"ø24"x18" SA28"x18" SA32"x18" SA
14"ø
VAV-122
6"ø
8"ø
VAV-125
18"ø 16"ø
12"ø 8"ø
VAV-129
12"ø
10"ø
14"ø
10"ø
14"ø
10"ø
VAV-121
34"x18" SA32"x18" SA28"x18" SA24"x18" SA
20"x18" SA
18"x18" SA
"ø
S A
14"ø SA
"x
S A
VAV-116
VAV-115
VAV-114
10"ø
14"ø
10"ø
10"ø 8"ø
6"ø
6"ø
14"ø12"ø
10"ø
VAV-148
14"ø
6"ø
10"ø 8"ø
8"ø
8"ø
8"ø
VAV-117
12"ø
10"ø
10"ø
VAV-118
14"ø
10"ø
10"ø
VAV-119
14"ø
10"ø
ACV-121
12"ø
6"ø
6"ø 6"ø
6"x6" EA8"x8" EA
12"x12" EA
14"x14" EA
6"ø
6"ø
6"ø
14"ø
22"x18" RA 24"x18" RA 30"x18" RA 34"x18" RA
8"x8"
18"x18" RA
8"x14" RA
14"x14"
14"x14"
14"x14"
10"x10"
"x
R A
12"x12" RA
12"ø 14"ø VAV-113
"ø
"ø
VAV-112
14"ø
12"ø
10"ø
10"ø
20"x18" SA16"ø SA 22"x18" SA 24"x18" SA 26"x18" SA 28"x18" SA 30"x18" SA 32"x18" SA 34"x18" SA
"x
S A 22"x18" SA 18"ø SA
14"ø 12"ø
VAV-100
12"ø
6"ø
46"x16" RA
"x
R A
14"x14" EA
"x
E A
14"ø
22"x18" EA24"x18" EA26"x18" EA28"x18" EA
12"x12" 8"x8"
8"x8"
4"x4" 4"x4"
8"ø8"x8"
4"x4"
4"x4"
8"ø
12"ø
10"ø10"ø
10"x10" 10"x10"
6"ø6"ø6"ø6"ø6"ø6"ø6"ø6"ø
VAV-102
12"ø
10"ø
VAV-103
12"ø
10"ø
VAV-104
12"ø
10"ø
VAV-105
10"ø
VAV-106
10"ø
VAV-107
10"ø
VAV-108
10"ø
VAV-109
5"ø
10"ø
VAV-110
"ø
"x
16"ø14"ø
6"ø 10"ø
14"x14" RA
16"x14" RA 18"x14" RA 20"x14" RA 24"x14" RA 26"x14" RA 28"x14" RA
"x
R A
"x
R A
8"x8"
8"x8" RA
D1
D2
D3
D2
D1
46"x16" RA36"x18" RA
"x
10"ø
6"ø 6"ø
14"ø
10"x10"
10"x14"
14"x14" 14"x14"
14"x14"
14"x14"
EF-X
14"x14" 14"x14"
14"x14"
28"x18" EA14"ø
14"ø
14"x14" 14"x14" 14"x14"
12"ø 12"ø
7"ø 7"ø
8"ø
10"ø
8"ø
12"ø 8"ø
VAV-146
6"x6"
VAV-142
12"x8"
8"ø
12"ø
VAV-140
6"ø
8"ø
8"ø
VAV-130
12"x8"
10"ø
6"ø
6"ø
6"ø
6"ø 14"x6"
FCU-133
16"x10"
VAV-152
12"x8"
FCU-135
VAV-135
12"x8"
6"ø
6"ø
6"ø
12"ø
8"ø
6"ø
12"x10"
6"ø
10"x10"
8"x8"
8"x8"
FCU-143
10"ø
16"x10"
8"ø
8"ø
8"x8"
10"ø
VAV-120
10"ø
26"x8"
ACV-122
"x
12"ø
D3
D2
D1
D3 D3 D3 D3 D3
D3
D3D3
D4
D3
D1
D2 D1
D4
D3
D1 D2
D2
D1D2
D1
D1
D4
D2
D1D1
D4
D2D2
D1
D1
D2
D4
D4
D1
D2
D4
D1 D2
D3
D1
D1 D2
D4D4
D1D2
D2
D1
D4
D1
D1 D2
D4
D1
D2
D1
D4D4
D1 D2
D1
D2
D1
D2
D4
D4
D1
D1
D2
D2
D1
D2
D1
D4
D3
D4
D2
D1
D2 D1
D3D3
D1
D3 D1
D3
D4
D4
D2
D4
D4
D1
D2
D3
D1 D2
D5
D8
20"X12" EA
UP TO ROOF
D16D16
D5
60"X20" RA
UP TO ROOF
(3) 20"X30" SA
UP TO ROOF
28"X18" EA UP
TO ROOF
36"X24" SA
UP TO ROOF
56"X74" RA
UP TO ROOF
D23
D24
DEMOLITION KEYNOTES
D1 CONTRACTOR TO VERIFY AND DISCONNECT AIR TERMINAL UNIT. REMOVE AND STORE UNIT IN A
SECURE LOCATION TO PREVENT ANY DAMAGE PRIOR TO RE-INSTALLATION OF UNIT.
D2 CONTRACTOR TO DEMOLISH SUPPLY DUCTWORK BACK TO MAIN BRANCH AND CAP.
D3 CONTRACTOR TO DEMOLISH EXHAUST DUCTWORK BACK TO MAIN BRANCH AND CAP.
D4 CONTRACTOR TO DEMOLISH RETURN DUCTWORK BACK TO MAIN BRANCH AND CAP.
D5 CONTRACTOR TO DEMOLISH EXISTING EXHAUST FAN.
D8 CONTRACTOR TO DEMOLISH EXHAUST DUCTWORK UP TO ROOF. PROVIDE SEAL OF PENETRATION
THROUGH ROOF.
D16 CONTRACTOR TO DEMOLISH EXHAUST DUCTWORK UP TO EXHAUST FAN ON ROOF.
D23 CONTRACTOR TO DEMOLISH SUPPLY DUCT UP TO AHU ON ROOF.
D24 CONTRACTOR TO DEMOLISH RETURN DUCT UP TO AHU ON ROOF.
N
1/8" = 1'-0"
MECHANICAL DUCT DEMOLITION PLAN - EIGHTH FLOOR1
VAV (HYDRONIC HEAT) - DEMOLITION
MARK
INLET
SIZE
AIRFLOW
(CFM) NOTES
7TH FLOOR
VAV-06 6" 300 TO BE REUSED IN NEW CONSTRUCTION.
VAV-X 5" 0 EXISTING CFM UNKNOWN, BOX WILL NOT BE REUSED.
VAV-X 5" 0 EXISTING CFM UNKNOWN, BOX WILL NOT BE REUSED.
VAV-X 4" 0 EXISTING CFM UNKNOWN, BOX WILL NOT BE REUSED.
VAV-X 4" 0 EXISTING CFM UNKNOWN, BOX WILL NOT BE REUSED.
VAV-X 5" 0 EXISTING CFM UNKNOWN, BOX WILL NOT BE REUSED.
VAV-X 4" 0 EXISTING CFM UNKNOWN, BOX WILL NOT BE REUSED.
8TH FLOOR
VAV-100 7" 570 TO BE REUSED IN NEW CONSTRUCTION.
VAV-102 5" 290 TO BE REUSED IN NEW CONSTRUCTION.
VAV-103 5" 270 TO BE REUSED IN NEW CONSTRUCTION.
VAV-104 5" 605 TO BE REUSED IN NEW CONSTRUCTION.
VAV-105 5" 320 TO BE REUSED IN NEW CONSTRUCTION.
VAV-106 5" 320 TO BE REUSED IN NEW CONSTRUCTION.
VAV-107 5" 325 TO BE REUSED IN NEW CONSTRUCTION.
VAV-108 5" 305 TO BE REUSED IN NEW CONSTRUCTION.
VAV-109 5" 310 TO BE REUSED IN NEW CONSTRUCTION.
VAV-110 10" 1,105 TO BE REUSED IN NEW CONSTRUCTION.
VAV-112 8" 695 TO BE REUSED IN NEW CONSTRUCTION.
VAV-113 7" 630 TO BE REUSED IN NEW CONSTRUCTION.
VAV-114 8" 670 TO BE REUSED IN NEW CONSTRUCTION.
VAV-115 7" 635 TO BE REUSED IN NEW CONSTRUCTION.
VAV-116 7" 605 TO BE REUSED IN NEW CONSTRUCTION.
VAV-117 7" 565 TO BE REUSED IN NEW CONSTRUCTION.
VAV-118 7" 620 TO BE REUSED IN NEW CONSTRUCTION.
VAV-119 7" 620 TO BE REUSED IN NEW CONSTRUCTION.
VAV-120 7" 590 TO BE REUSED IN NEW CONSTRUCTION.
VAV-121 8" 200 TO BE REUSED IN NEW CONSTRUCTION.
VAV-122 7" 345 TO BE REUSED IN NEW CONSTRUCTION.
VAV-125 4" 465 TO BE REUSED IN NEW CONSTRUCTION.
VAV-129 12" 1,420 TO BE REUSED IN NEW CONSTRUCTION.
VAV-130 6" 450 TO BE REUSED IN NEW CONSTRUCTION.
VAV-135 8" 900 TO BE REUSED IN NEW CONSTRUCTION.
VAV-140 6" 430 TO BE REUSED IN NEW CONSTRUCTION.
VAV-142 5" 335 TO BE REUSED IN NEW CONSTRUCTION.
VAV-146 6" 430 TO BE REUSED IN NEW CONSTRUCTION.
VAV-148 9" 680 TO BE REUSED IN NEW CONSTRUCTION.
VAV-151 14" 1,485 TO BE REUSED IN NEW CONSTRUCTION.
VAV-152 5" 1,200 TO BE REUSED IN NEW CONSTRUCTION.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Office Of Construction & Facilities Management Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
OK ARCH REG. NO. CA02295, EXP. 06/30/2023
OK ENGR REG. NO. CA7127, EXP. 06/30/2023
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
HEALTHCARE PLANNER
OCULUS INC.
1 S. MEMORIAL DR., SUITE 1500
ST. LOUIS, MO 63102
(314) 367-6100
SPUR PROJECT NUMBER: 1791.08
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
SEE FRONT COVER SHEET
FOR APPROVAL SIGNATURE
VERTICAL TRANSPORTATION
ENVIRONMENTAL HYGIENIST
TEC-AN, INC.
2517 S. PURDUE AVE.
OKLAHOMA CITY, OK 73128
(405) 681-7076
LERCH BATES
2001 BRYAN ST., SUITE 1930
DALLAS, TX 75201
(972) 294-5221
/2
/2
:2 :3
P
M
MDH101
MECHANICAL DUCT DEMOLITION PLAN -
EIGHTH FLOOR
JLF
53 OF 92JRM
100% RFP DOCUMENTS
CONSTRUCT SURGICAL INTENSIVE
CARE UNIT & RENOVATE
OPERATING ROOMS
08/02/2021
635-436
OKLAHOMA CITY VA HEALTHCARE SYSTEM
921 NE 13TH ST, OKLAHOMA CITY, OK 73104
No. REVISION DESCRIPTION DATE