SEQUENCE OF OPERATIONS
EXHAUST FAN (EF-X)
GENERAL DESCRIPTION
The exhaust fans provide exhaust ventilation to the conditioned space(s) as shown on the drawings.
OPERATING MODES
NORMAL OPERATING MODE
The exhaust fan shall be in occupied mode per the project design conditions schedule shown on sheet M-701.
BACKUP MODE
Backup mode shall be activated upon failure of the lead exhaust fan. Backup mode shall be disabled by manual reset.
UNOCCUPIED MODE
The exhaust fan shall be in unoccupied mode for all periods not included in the occupied hours of operation.
SAFETIES, OVERRIDES, AND INTERLOCKS
The exhaust fan shall be disabled via hard wired interlock at the fan start circuit upon activation of the EA duct static pressure controller.
COMPONENT CONTROL LOOPS
EXHAUST FAN 1 – ON/OFF
• When the HOA switch is in hand position, the variable speed supply fan shall operate at a speed set manually by the operator at the user interface of the drive.
• When the HOA switch is in off position, the fan shall be off.
• When the HOA switch is in auto position, the variable speed supply fan shall operate subject to the unit enable signal, and unit operating modes.
NORMAL OPERATING MODE:
The controller shall measure the EA static pressure and modulate the exhaust fan to maintain the EA static pressure setpoint. The minimum fan speed shall be determined during testing and balancing.
BACKUP MODE:
The exhaust fan shall be off.
UNOCCUPIED MODE:
The exhaust fan shall be off.
EXHAUST FAN 2 – ON/OFF
• When the HOA switch is in hand position, the variable speed supply fan shall operate at a speed set manually by the operator at the user interface of the drive.
• When the HOA switch is in off position, the fan shall be off.
• When the HOA switch is in auto position, the variable speed supply fan shall operate subject to the unit enable signal, and unit operating modes.
NORMAL OPERATING MODE:
The exhaust fan shall be off.
BACKUP MODE:
Upon failure of the lead exhaust fan, the backup exhaust fan shall be activated and shall operate as the lead exhaust fan until manually reset to normal operating mode.
UNOCCUPIED MODE:
The exhaust fan shall be off.
MOTORIZED DAMPER 1
NORMAL OPERATING MODE:
The motorized damper shall be open. The motorized damper shall open 30 sec (adj.)
prior to activation of the exhaust fan.
BACKUP MODE:
The motorized damper shall operate as if in unoccupied mode.
UNOCCUPIED MODE:
The motorized damper shall be closed. The motorized damper shall close 30 sec (adj.) after the fan is OFF.
MOTORIZED DAMPER 2
NORMAL OPERATING MODE:
The motorized damper shall operate as if in unoccupied mode.
BACKUP MODE:
The motorized damper shall operate as the lead motorized damper until manually reset to normal operating mode.
UNOCCUPIED MODE:
The motorized damper shall be closed. The motorized damper shall close 30 sec (adj.) after the fan is OFF.
HL
EA
M
CT
VFD
N.C.
M
EA
M
CT
VFD
M
N.C.
BI
BO
BI
BO
AO
BI
EA DAMPER STATUS
EA DAMPER
EA DAMPER STATUS
EF START/STOP
EF VFD SPEED
EF VFD FAULT
BI
BO
BI
BO
AO
BI
EA DAMPER STATUS
EA DAMPER
EA DAMPER STATUS
EF START/STOP
EF VFD SPEED
EF VFD FAULT
BI LOW STATIC SHUTDOWN
BI LOW STATIC SHUTDOWN
HL
SEQUENCE OF OPERATIONS
MEDICAL GAS/VACUUM SYSTEM
GENERAL DESCRIPTION
The medical gas/vacuum system consists of a zone valve box, area alarm panel, master alarm panel, and a source of medical gas/vacuum.
MEDICAL
GAS/VACUUM
MASTER ALARM PANEL
MEDICAL
GAS/VACUUM
AREA ALARM PANEL
MEDICAL
GAS/VACUUM
ZONE VALVE BOX
NOTES:
1. FIELD VERIFY LOCATION OF EXISTING MEDICAL GAS/VACUUM MASTER ALARM PANEL.
NOT TO SCALE
TYPICAL ISOLATION EXHAUST FAN (EF-X) W/N+1 CONTROL DIAGRAM1
1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET XX-M-701 FOR APPLICABLE TREND INTERVALS.
NOTES:
LOW EA STATIC PRESSURE IF THE DUCT STATIC PRESSURE IS BELOW ITS SETPOINT BY 20% (ADJ.) X 10 MIN.
EF RUNTIME EXCEEDED FAN RUNTIME EXCEEDS A USER DEFINABLE LIMIT X 10 MIN.
EF IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.
EF FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.
EXHAUST AIR DAMPER IN HAND COMMANDED CLOSED, BUT THE STATUS IS OPEN X 10 MIN.
EXHAUST AIR DAMPER FAILURE COMMANDED OPEN, BUT THE STATUS IS CLOSED X 10 MIN.
ALARMS (TYP 2) DESCRIPTION ALARM ALARM DELAY
EXHAUST AIR DAMPER X X X
EXHAUST AIR DAMPER STATUS X X X
DAMPER (TYP 2)
LOW STATIC SHUTDOWN X X X
EF VFD VAULT X X X
EF START/STOP X X X
EF STATUS X X X
EF VFD SPEED X X X
EXHAUST FAN (TYP 2)
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINTS NAME
HARDWARE POINTS SOFTWARE POINTS SHOWN ON
GRAPHIC
POINTS LIST SCHEDULE - GENERAL EXHAUST FAN (EF-X)
1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET XX-M-701 FOR APPLICABLE TREND INTERVALS.
NOTES:
COMMON ALARM ALL APPLICABLE ALARMS AS REQUIRED BY NFPA 99. X N/A
ALARMS DESCRIPTION ALARM ALARM DELAY
MASTER ALARM PANEL ALL APPLICABLE POINTS AS REQUIRED BY NFPA 99.
MASTER ALARM PANEL
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINTS NAME
HARDWARE POINTS SOFTWARE POINTS
SHOWN ON GRAPHIC
POINTS LIST SCHEDULE - MASTER ALARM PANEL (MAP)
2. PROVIDE ALARM POINT FOR EACH MEDICAL GAS/VACUUM TYPE SHOWN ON PLAN.
1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET XX-M-701 FOR APPLICABLE TREND INTERVALS.
NOTES:
LOW MEDICAL GAS/VACUUM PRESSURE IF MEDICAL GAS/VACUUM PRESSURE DECREASES 20%. X N/A
HIGH MEDICAL GAS/VACUUM PRESSURE IF MEDICAL GAS/VACUUM PRESSURE INCREASES 20%. X N/A
ALARMS DESCRIPTION ALARM ALARM DELAY
MEDICAL GAS/VACUUM PRESSURE X X
MEDICAL GAS/VACUUM
AI AO BI BO AV BV LOOP SCHED TREND ALARM
POINTS NAME
HARDWARE POINTS SOFTWARE POINTS
SHOWN ON GRAPHIC
POINTS LIST SCHEDULE - AREA ALARM PANEL (AAP)
NOT TO SCALE
TYPICAL MEDICAL GAS/VACUUM SYSTEM CONTROL DIAGRAM2
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Office Of Construction & Facilities Management Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
OK ARCH REG. NO. CA02295, EXP. 06/30/2023
OK ENGR REG. NO. CA7127, EXP. 06/30/2023
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
HEALTHCARE PLANNER
OCULUS INC.
1 S. MEMORIAL DR., SUITE 1500
ST. LOUIS, MO 63102
(314) 367-6100
SPUR PROJECT NUMBER: 1791.08
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
SEE FRONT COVER SHEET
FOR APPROVAL SIGNATURE
VERTICAL TRANSPORTATION
ENVIRONMENTAL HYGIENIST
TEC-AN, INC.
2517 S. PURDUE AVE.
OKLAHOMA CITY, OK 73128
(405) 681-7076
LERCH BATES
2001 BRYAN ST., SUITE 1930
DALLAS, TX 75201
(972) 294-5221
/2
/2
:2 :1
P
M
M-704
MECHANICAL CONTROLS
JLF
71 OF 92JRM
100% RFP DOCUMENTS
CONSTRUCT SURGICAL INTENSIVE
CARE UNIT & RENOVATE
OPERATING ROOMS
08/02/2021
635-436
OKLAHOMA CITY VA HEALTHCARE SYSTEM
921 NE 13TH ST, OKLAHOMA CITY, OK 73104
No. REVISION DESCRIPTION DATE