71_M-704 - MECHANICAL CONTROLS.pdf

PDF 192 KB Posted

Attached to
Y1AZ--Design Build, Construct SICU and Renovate Operating Rooms
Solicitation number
36C10F22R0036
Issued by

View the file

Other files

File Type Posted
Award Notice 36C10F24C0002.pdf PDF
36C10F22R0036 0004.pdf PDF
36C10F22R0036 0003.pdf PDF
36C10F22R0036 0002.pdf PDF
36C10F22R0036 0001.pdf PDF
36C10F22R0036.pdf PDF
45_PL102 - EIGHTH FLOOR -PLUMBING WASTE AND VENT PLAN.pdf PDF
40_PPD101 - SEVENTH FLOOR -PLUMBING DOMESTIC WATER DEMOLITION PLAN.pdf PDF
61_MHP100 - MECHANICAL DUCT and PIPING PLAN -ROOF LEVEL.pdf PDF
17_AF702 - FINISH PLAN -EIGHTH FLOOR.pdf PDF
07_ELEVATOR NARRATIVE.pdf PDF
52_MDH100 - MECHANICAL DUCT DEMOLITION PLAN -SEVENTH FLOOR.pdf PDF
100 percent RFP PLUMBING CALCS.pdf PDF
48_PJ101 - SEVENTH FLOOR -PLUMBING MEDICAL GAS PLAN.pdf PDF
55_MDP100 - MECHANICAL PIPING DEMOLTION PLAN -SEVENTH FLOOR.pdf PDF
44_PL101 - SEVENTH FLOOR -PLUMBING WASTE AND VENT PLAN.pdf PDF
24_QH105 - EQUIPMENT PLAN -EIGHTH FLOOR -AREA 1.pdf PDF
04_FIRE PROTECTION.pdf PDF
OR-SICU 100 percent Digital Material Board.pdf PDF
28_QH109 - INTERIOR EQUIPMENT ELEVATIONS.pdf PDF
27_QH108 - INTERIOR EQUIPMENT ELEVATIONS.pdf PDF
84_EY301 - SEVENTH FLOOR ELECTRICAL LOW VOLTAGE PLAN.pdf PDF
4_GI102 - LIFE SAFETY PLAN -EIGHTH FLOOR.pdf PDF
86_EP401 - ELECTRICAL LIGHTNING PROTECTION PLAN.pdf PDF
21_QH102 - EQUIPMENT PLAN -SEVENTH FLOOR -AREA 2.pdf PDF
13_AE115 - DIMENSION PLAN -EIGHTH FLOOR.pdf PDF
90_EP504 - ELECTRICAL DETAILS.pdf PDF
88_EP502 - SCHEDULES AND DETAILS.pdf PDF
26_QH107 - EQUIPMENT PLAN -EIGHTH FLOOR -AREA 3 and INTERIOR EQUIPMENT ELEVATIONS.pdf PDF
39_PLD102 - EIGHTH FLOOR -PLUMBING WASTE AND VENT DEMOLITION PLAN.pdf PDF
9_AE111 - REFERENCE PLAN -SEVENTH FLOOR.pdf PDF
12_AE114 - DIMENSION PLAN -SEVENTH FLOOR.pdf PDF
14_AE211 - REFLECTED CEILING PLAN -SEVENTH FLOOR.pdf PDF
01_Mold Report.pdf PDF
Floor 7 Inventory OKC VAMC.pdf PDF
30_FA001 - FIRE ALARM_MASS NOTIFICATION GENERAL NOTES.pdf PDF
56_MDP101 - MECHANICAL PIPING DEMOLTION PLAN -EIGHTH FLOOR.pdf PDF
02_ARCHITECTURAL.pdf PDF
1_GI000 - COVER SHEET.pdf PDF
50_P-600 - PLUMBING SCHEDULES.pdf PDF
82_EL201 - SEVENTH FLOOR ELECTRICAL LIGHTING PLAN.pdf PDF
66_M-502 - MECHANICAL DETAILS.pdf PDF
60_MH103 - MECHANICAL ZONING and CONTROLS PLAN -EIGHTH FLOOR.pdf PDF
06_ELECTRICAL NARRATIVE.pdf PDF
02_STRUCTURAL NARRATIVE.pdf PDF
20_QH101 - EQUIPMENT PLAN -SEVENTH FLOOR -AREA 1.pdf PDF
38_PLD101 - SEVENTH FLOOR -PLUMBING WASTE AND VENT DEMOLITION PLAN.pdf PDF
Floor 8 Inventory OKC VAMC.pdf PDF
63_MP101 - MECHANICAL HVAC PIPING PLAN -EIGHTH FLOOR.pdf PDF
03_EQUIPMENT.pdf PDF
Show 40 more

Latest 50 of 122 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SEQUENCE OF OPERATIONS

EXHAUST FAN (EF-X)

GENERAL DESCRIPTION

The exhaust fans provide exhaust ventilation to the conditioned space(s) as shown on the drawings.

OPERATING MODES

NORMAL OPERATING MODE

The exhaust fan shall be in occupied mode per the project design conditions schedule shown on sheet M-701.

BACKUP MODE

Backup mode shall be activated upon failure of the lead exhaust fan. Backup mode shall be disabled by manual reset.

UNOCCUPIED MODE

The exhaust fan shall be in unoccupied mode for all periods not included in the occupied hours of operation.

SAFETIES, OVERRIDES, AND INTERLOCKS

The exhaust fan shall be disabled via hard wired interlock at the fan start circuit upon activation of the EA duct static pressure controller.

COMPONENT CONTROL LOOPS

EXHAUST FAN 1 – ON/OFF

• When the HOA switch is in hand position, the variable speed supply fan shall operate at a speed set manually by the operator at the user interface of the drive.

• When the HOA switch is in off position, the fan shall be off.

• When the HOA switch is in auto position, the variable speed supply fan shall operate subject to the unit enable signal, and unit operating modes.

NORMAL OPERATING MODE:

The controller shall measure the EA static pressure and modulate the exhaust fan to maintain the EA static pressure setpoint. The minimum fan speed shall be determined during testing and balancing.

BACKUP MODE:

The exhaust fan shall be off.

UNOCCUPIED MODE:

The exhaust fan shall be off.

EXHAUST FAN 2 – ON/OFF

• When the HOA switch is in hand position, the variable speed supply fan shall operate at a speed set manually by the operator at the user interface of the drive.

• When the HOA switch is in off position, the fan shall be off.

• When the HOA switch is in auto position, the variable speed supply fan shall operate subject to the unit enable signal, and unit operating modes.

NORMAL OPERATING MODE:

The exhaust fan shall be off.

BACKUP MODE:

Upon failure of the lead exhaust fan, the backup exhaust fan shall be activated and shall operate as the lead exhaust fan until manually reset to normal operating mode.

UNOCCUPIED MODE:

The exhaust fan shall be off.

MOTORIZED DAMPER 1

NORMAL OPERATING MODE:

The motorized damper shall be open. The motorized damper shall open 30 sec (adj.)

prior to activation of the exhaust fan.

BACKUP MODE:

The motorized damper shall operate as if in unoccupied mode.

UNOCCUPIED MODE:

The motorized damper shall be closed. The motorized damper shall close 30 sec (adj.) after the fan is OFF.

MOTORIZED DAMPER 2

NORMAL OPERATING MODE:

The motorized damper shall operate as if in unoccupied mode.

BACKUP MODE:

The motorized damper shall operate as the lead motorized damper until manually reset to normal operating mode.

UNOCCUPIED MODE:

The motorized damper shall be closed. The motorized damper shall close 30 sec (adj.) after the fan is OFF.

HL

EA

M

CT

VFD

N.C.

M

EA

M

CT

VFD

M

N.C.

BI

BO

BI

BO

AO

BI

EA DAMPER STATUS

EA DAMPER

EA DAMPER STATUS

EF START/STOP

EF VFD SPEED

EF VFD FAULT

BI

BO

BI

BO

AO

BI

EA DAMPER STATUS

EA DAMPER

EA DAMPER STATUS

EF START/STOP

EF VFD SPEED

EF VFD FAULT

BI LOW STATIC SHUTDOWN

BI LOW STATIC SHUTDOWN

HL

SEQUENCE OF OPERATIONS

MEDICAL GAS/VACUUM SYSTEM

GENERAL DESCRIPTION

The medical gas/vacuum system consists of a zone valve box, area alarm panel, master alarm panel, and a source of medical gas/vacuum.

MEDICAL

GAS/VACUUM

MASTER ALARM PANEL

MEDICAL

GAS/VACUUM

AREA ALARM PANEL

MEDICAL

GAS/VACUUM

ZONE VALVE BOX

NOTES:

1. FIELD VERIFY LOCATION OF EXISTING MEDICAL GAS/VACUUM MASTER ALARM PANEL.

NOT TO SCALE

TYPICAL ISOLATION EXHAUST FAN (EF-X) W/N+1 CONTROL DIAGRAM1

1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET XX-M-701 FOR APPLICABLE TREND INTERVALS.

NOTES:

LOW EA STATIC PRESSURE IF THE DUCT STATIC PRESSURE IS BELOW ITS SETPOINT BY 20% (ADJ.) X 10 MIN.

EF RUNTIME EXCEEDED FAN RUNTIME EXCEEDS A USER DEFINABLE LIMIT X 10 MIN.

EF IN HAND COMMANDED OFF, BUT THE STATUS IS ON X 10 MIN.

EF FAILURE COMMANDED ON, BUT THE STATUS IS OFF X 10 MIN.

EXHAUST AIR DAMPER IN HAND COMMANDED CLOSED, BUT THE STATUS IS OPEN X 10 MIN.

EXHAUST AIR DAMPER FAILURE COMMANDED OPEN, BUT THE STATUS IS CLOSED X 10 MIN.

ALARMS (TYP 2) DESCRIPTION ALARM ALARM DELAY

EXHAUST AIR DAMPER X X X

EXHAUST AIR DAMPER STATUS X X X

DAMPER (TYP 2)

LOW STATIC SHUTDOWN X X X

EF VFD VAULT X X X

EF START/STOP X X X

EF STATUS X X X

EF VFD SPEED X X X

EXHAUST FAN (TYP 2)

AI AO BI BO AV BV LOOP SCHED TREND ALARM

POINTS NAME

HARDWARE POINTS SOFTWARE POINTS SHOWN ON

GRAPHIC

POINTS LIST SCHEDULE - GENERAL EXHAUST FAN (EF-X)

1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET XX-M-701 FOR APPLICABLE TREND INTERVALS.

NOTES:

COMMON ALARM ALL APPLICABLE ALARMS AS REQUIRED BY NFPA 99. X N/A

ALARMS DESCRIPTION ALARM ALARM DELAY

MASTER ALARM PANEL ALL APPLICABLE POINTS AS REQUIRED BY NFPA 99.

MASTER ALARM PANEL

AI AO BI BO AV BV LOOP SCHED TREND ALARM

POINTS NAME

HARDWARE POINTS SOFTWARE POINTS

SHOWN ON GRAPHIC

POINTS LIST SCHEDULE - MASTER ALARM PANEL (MAP)

2. PROVIDE ALARM POINT FOR EACH MEDICAL GAS/VACUUM TYPE SHOWN ON PLAN.

1. SEE STANDARD TRENDING POINTS LIST SCHEDULE ON SHEET XX-M-701 FOR APPLICABLE TREND INTERVALS.

NOTES:

LOW MEDICAL GAS/VACUUM PRESSURE IF MEDICAL GAS/VACUUM PRESSURE DECREASES 20%. X N/A

HIGH MEDICAL GAS/VACUUM PRESSURE IF MEDICAL GAS/VACUUM PRESSURE INCREASES 20%. X N/A

ALARMS DESCRIPTION ALARM ALARM DELAY

MEDICAL GAS/VACUUM PRESSURE X X

MEDICAL GAS/VACUUM

AI AO BI BO AV BV LOOP SCHED TREND ALARM

POINTS NAME

HARDWARE POINTS SOFTWARE POINTS

SHOWN ON GRAPHIC

POINTS LIST SCHEDULE - AREA ALARM PANEL (AAP)

NOT TO SCALE

TYPICAL MEDICAL GAS/VACUUM SYSTEM CONTROL DIAGRAM2

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS:

Drawing #

VA Office Of Construction & Facilities Management Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

OK ARCH REG. NO. CA02295, EXP. 06/30/2023

OK ENGR REG. NO. CA7127, EXP. 06/30/2023

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FULLY SPRINKLERED

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

STRUCTURAL ENGINEER

H2B, INC.

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

MECH / ELEC / PLUMB / TECH ENGINEER

FIRE PROTECTION ENGINEER

POOLE FIRE PROTECTION, INC.

19910 WEST 161ST STREET

OLATHE, KANSAS 66062

(913) 829-8690

HEALTHCARE PLANNER

OCULUS INC.

1 S. MEMORIAL DR., SUITE 1500

ST. LOUIS, MO 63102

(314) 367-6100

SPUR PROJECT NUMBER: 1791.08

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(913) 369-7200

SEE FRONT COVER SHEET

FOR APPROVAL SIGNATURE

VERTICAL TRANSPORTATION

ENVIRONMENTAL HYGIENIST

TEC-AN, INC.

2517 S. PURDUE AVE.

OKLAHOMA CITY, OK 73128

(405) 681-7076

LERCH BATES

2001 BRYAN ST., SUITE 1930

DALLAS, TX 75201

(972) 294-5221

/2

/2

:2 :1

P

M

M-704

MECHANICAL CONTROLS

JLF

71 OF 92JRM

100% RFP DOCUMENTS

CONSTRUCT SURGICAL INTENSIVE

CARE UNIT & RENOVATE

OPERATING ROOMS

08/02/2021