7TH FLOOR ROOF
N
8TH FLOOR SICU
8TH FLOOR KEY PLAN
LIFE SAFETY LEGEND
FEC FIRE EXTINGUISHER CABINET
EXIT LIGHT / SIGN
NOT IN SCOPE
BUILDING EXIT
ACTUAL OCCUPANT LOAD
EGRESS PATH
000 ALLOWABLE OCCUPANT LOAD
SMOKE COMPARTMENT BOUNDARY
BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER SYSTEM THROUGHOUT
CONSTRUCTION TYPE (TABLE A.8.2.1.2):
• TYPE II (111)
FIRE RESISTANCE RATINGS (TABLE A.8.2.1.2):
• COLUMNS: 1 HR
• BEAM, GIRDERS, TRUSSES: 1 HR
• FLOOR/CEILING ASSEMBLIES: 1 HR
• ROOF/CEILING ASSEMBLIES: 1 HR
• EXTERIOR NON-BEARING WALLS: 0 HR
• INTERIOR NON-BEARING WALLS: 0 HR
FIRE-RESISTIVE REQUIREMENTS:
• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK,
EXTERIOR NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)
BUILDING OCCUPANCY (CH. 19)
• EXISTING HEALTHCARE OCCUPANCY
OCCUPANT LOAD FACTORS (TABLE 7.3.1.2):
SEVENTH FLOOR:
• HEALTHCARE USE, AMBULATORY = 150 SF/PERSON
• ASSEMBLY USE, LESS CONCENTRATED WITHOUT FIXED SEATING = 15 SF/PERSON
• BUSINESS USE, GENERAL = 150 SF/PERSON
• STORAGE USE, IN OTHER THAN STORAGE AND MERCANTILE OCCUPANCIES = 300 SF/PERSON
EIGHTH FLOOR :
• ASSEMBLY USE, LESS CONCENTRATED WITHOUT FIXED SEATING = 15 SF/PERSON
• BUSINESS USE, GENERAL = 150 SF/PERSON
• HEALTHCARE USE, INPATIENT TREATMENT DEPARTMENT = 240 SF/PERSON
• STORAGE USE, IN OTHER THAN STORAGE AND MERCANTILE OCCUPANCIES = 500 SF/PERSON
SHAFTS MINIMUM 1-HOUR RATING (8.6.5)
CORRIDOR MINIMUM FIRE RATING: 1/2 HR (19.3.6.2.2)
SEVENTH & EIGHTH FLOOR - EXISTING HEALTHCARE (APPENDIX TABLE A.7.6)
• DEAD END CORRIDOR MAXIMUM DISTANCE: 30 FEET
• MAXIMUM COMMON PATH OF TRAVEL: NO REQUIREMENT
• MAXIMUM TRAVEL DISTANCE: 200'
EXIT DOORS CLEAR EXIT WIDTH (7.2.1.2.3.2)
• MINIMUM DOOR OPENING WIDTH OF 32"
PROTECTED AREAS:
• STORAGE ROOMS/CLEAN/SOILED - REQUIRED VA FIRE PROTECTION DESIGN MANUAL 3.1.A AND
PER NFPA 101: 19.3.2.1 AND 8.7 FIRE RATED PARTITIONS WITH SPRINKLER PROTECTION, PROVIDED.
• MEDICAL RECORDS STORAGE - 1 HR PER VA FIRE PROTECTION DESIGN MANUAL SECTION 3.1.B.
SMOKE COMPARTMENTALIZATION: NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.
FIRE ALARM SYSTEM: REQUIRED/PROVIDED MANUAL SYSTEM.
STANDPIPES: NO MODIFICATION TO EXISTING STANDPIPES REQUIRED.
LIFE SAFETY CODE INFORMATION - NFPA 101-2021 EDITION
RATED PARTITIONS & BARRIERS
1 HR FIRE RATING
2 HR FIRE RATING
EXISTING CONSTRUCTION
NEW CONSTRUCTION
1 2 3 4 5 6 7 8 9 10 11 11a
E
F
G
H
I
J
K
9A
G2
FEC
F E
C
FEC
335 SF
SICU PATIENT
ISOLATION ROOM
(ACC.)
811B
SICU PATIENT
ISOLATION ROOM
(ACC.)
811B
60 SF
ICU TOILET
811C
ICU TOILET
811C
74 SF
ANTE ROOM
811A
ANTE ROOM
811A
47 SF
ICU TOILET
810B
ICU TOILET
810B
272 SF
SICU PATIENT
ROOM
810A
SICU PATIENT
ROOM
810A
239 SF
SICU PATIENT
ROOM
809A
SICU PATIENT
ROOM
809A
247 SF
SICU PATIENT
ROOM
808A
SICU PATIENT
ROOM
808A
261 SF
SICU PATIENT
ROOM
807A
SICU PATIENT
ROOM
807A
46 SF
ICU TOILET
807B
ICU TOILET
807B
258 SF
SICU PATIENT
ROOM
806A
SICU PATIENT
ROOM
806A
46 SF
ICU TOILET
806B
ICU TOILET
806B
46 SF
ICU TOILET
805B
ICU TOILET
805B
249 SF
SICU PATIENT
ROOM
805A
SICU PATIENT
ROOM
805A
245 SF
SICU PATIENT
ROOM
804A
SICU PATIENT
ROOM
804A
292 SF
SICU PATIENT
ROOM (ACC.)
803A
SICU PATIENT
ROOM (ACC.)
803A
45 SF
ICU TOILET
803B
ICU TOILET
803B
52 SF
ICU TOILET
802C
ICU TOILET
802C
320 SF
SICU PATIENT
ISOLATION ROOM
(ACC.)
802B
SICU PATIENT
ISOLATION ROOM
(ACC.)
802B
67 SF
ANTE ROOM
802A
ANTE ROOM
802A
49 SF
ICU TOILET
801B
ICU TOILET
801B
272 SF
SICU PATIENT
ROOM (ACC.)
801A
SICU PATIENT
ROOM (ACC.)
801A
67 SF
TOILET
TOILET
63 SF
TOILET
TOILET
202 SF
SICU WAITING
SICU WAITING
262 SF
SICU PATIENT
825A
SICU PATIENT
825A
322 SF
SICU PATIENT
ISOLATION ROOM
(ACC.)
824B
SICU PATIENT
ISOLATION ROOM
(ACC.)
824B99 SF
ANTE ROOM
824A
ANTE ROOM
824A
53 SF
ICU TOILET
824C
ICU TOILET
824C
45 SF
ICU TOILET
825B
ICU TOILET
825B
99 SF
ANTE ROOM
823A
ANTE ROOM
823A
57 SF
ICU TOILET
823C
ICU TOILET
823C
310 SF
SICU PATIENT
ISOLATION ROOM
(ACC.)
823B
SICU PATIENT
ISOLATION ROOM
(ACC.)
823B243 SF
SICU PATIENT
ROOM
822A
SICU PATIENT
ROOM
822A
46 SF
ICU TOILET
822B
ICU TOILET
822B
46 SF
ICU TOILET
821B
ICU TOILET
821B
236 SF
SICU PATIENT
ROOM
821A
SICU PATIENT
ROOM
821A
245 SF
SICU PATIENT
ROOM
820A
SICU PATIENT
ROOM
820A
46 SF
ICU TOILET
820B
ICU TOILET
820B
84 SF
ON-CALL
ON-CALL
70 SF
ON-CALL
TOILET/SHOWER
ON-CALL
TOILET/SHOWER
62 SF
STAFF TOILET
STAFF TOILET
176 SF
STAFF BREAK
STAFF BREAK
87 SF
SHARED OFFICE
SHARED OFFICE
93 SF
SINGLE OFFICE
SINGLE OFFICE
185 SF
TEAM WORK
TEAM WORK
68 SF
MED GAS
MED GAS
60 SF
HAC
HAC
269 SF
EQUIP. STORAGE
EQUIP. STORAGE
120 SF
NOURISH.
NOURISH.
91 SF
COMM
COMM
80 SF
ELEC
ELEC
145 SF
CLEAN UTILITY
CLEAN UTILITY
133 SF
SOILED UTILITY
SOILED UTILITY
13 SF
ALCOVE
ALC-8-5
ALCOVE
ALC-8-5
179 SF
MEDS
MEDS
167 SF
CLEAN SUPPLY /
LINEN
CLEAN SUPPLY /
LINEN
16 SF
ALCOVE
ALC-8-1
ALCOVE
ALC-8-1
278 SF
NURSE STATION
NURSE STATION
37 SF
ALCOVE
ALC-8-3
ALCOVE
ALC-8-3
36 SF
ALCOVE
ALC-8-4
ALCOVE
ALC-8-4
374 SF
NURSE STATION/
TEAM COLLAB.
NURSE STATION/
TEAM COLLAB.
10 SF
ALCOVE, ICE
ALC-8-2
ALCOVE, ICE
ALC-8-2
45 SF
ICU TOILET
809B
ICU TOILET
809B
46 SF
ICU TOILET
804B
ICU TOILET
804B
46 SF
ICU TOILET
808B
ICU TOILET
808B
23 SF
COMM
COMM
350 SF
ELEVATOR LOBBY
COR-8-1
ELEVATOR LOBBY
COR-8-1
41 SF
COMM
COMM
97 SF
ELEVATOR
P-9
ELEVATOR
P-9
93 SF
ELEVATOR
P-10
ELEVATOR
P-10
87 SF
ELEVATOR
P-8
ELEVATOR
P-8
87 SF
ELEVATOR
P-7
ELEVATOR
P-7
76 SF
ELEVATOR LOBBY
COR-8-7
ELEVATOR LOBBY
COR-8-7
150 SF
ELEVATOR
P-12
ELEVATOR
P-12
216 SF
CORRIDOR
COR-8-4
CORRIDOR
COR-8-4
187 SF
CORRIDOR
COR-8-6
CORRIDOR
COR-8-6
571 SF
CORRIDOR
COR-8-5
CORRIDOR
COR-8-5
631 SF
CORRIDOR
COR-8-9
CORRIDOR
COR-8-9
623 SF
CORRIDOR
COR-8-10
CORRIDOR
COR-8-10
532 SF
CORRIDOR
COR-8-8
CORRIDOR
COR-8-8
539 SF
CORRIDOR
COR-8-3
CORRIDOR
COR-8-3
ASSEMBLY, LESS CONCENTRATED
BUSINESS
HEALTHCARE, AMBULATORY
HEALTHCARE, INPATIENT
STORAGE USE, OTHER
S T
A
IR
S T
A
IR
TRAVEL DISTANCE = 156' - 6"
TRAVEL DISTANCE = 160' - 5"
STAIR 8
STAIR 8
STAIR 10
STAIR 10
OCCUPANT TYPE LEGEND
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
Building Number
Drawing Number
CONSULTANTS:
Drawing #
VA Office Of Construction & Facilities Management Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
OK ARCH REG. NO. CA02295, EXP. 06/30/2023
OK ENGR REG. NO. CA7127, EXP. 06/30/2023
The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.
FULLY SPRINKLERED
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
STRUCTURAL ENGINEER
H2B, INC.
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
MECH / ELEC / PLUMB / TECH ENGINEER
FIRE PROTECTION ENGINEER
POOLE FIRE PROTECTION, INC.
19910 WEST 161ST STREET
OLATHE, KANSAS 66062
(913) 829-8690
HEALTHCARE PLANNER
OCULUS INC.
1 S. MEMORIAL DR., SUITE 1500
ST. LOUIS, MO 63102
(314) 367-6100
SPUR PROJECT NUMBER: 1791.08
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(913) 369-7200
SEE FRONT COVER SHEET
FOR APPROVAL SIGNATURE
VERTICAL TRANSPORTATION
ENVIRONMENTAL HYGIENIST
TEC-AN, INC.
2517 S. PURDUE AVE.
OKLAHOMA CITY, OK 73128
(405) 681-7076
LERCH BATES
2001 BRYAN ST., SUITE 1930
DALLAS, TX 75201
(972) 294-5221
/2
/2
:1 :1
A
M
GI102
LIFE SAFETY PLAN - EIGHTH FLOOR
ZDL
4 OF 92JNK
100% RFP DOCUMENTS
CONSTRUCT SURGICAL INTENSIVE
CARE UNIT & RENOVATE
OPERATING ROOMS
08/02/2021
635-436
OKLAHOMA CITY VA HEALTHCARE SYSTEM
921 NE 13TH ST, OKLAHOMA CITY, OK 73104
N
1/8" = 1'-0"
EIGHTH FLOOR LIFE SAFETY PLAN
OCCUPANT LOAD PER NFPA 101-2021 - EIGHTH FLOOR
OCCUPANT TYPE
PER TABLE 7.3.1.2.
AREA
OCC. LOAD
FACTOR IN SF
OCC. LOAD
7TH FLOOR
ASSEMBLY, LESS CONCENTRATED 565 SF 15 SF 38
BUSINESS 20969 SF 150 SF 140
HEALTHCARE, AMBULATORY 6850 SF 150 SF 46
STORAGE USE, OTHER 3125 SF 500 SF 6
31508 SF 229
8TH FLOOR
ASSEMBLY, LESS CONCENTRATED 202 SF 15 SF 13
BUSINESS 6950 SF 150 SF 46
HEALTHCARE, INPATIENT 6690 SF 240 SF 28
STORAGE USE, OTHER 989 SF 500 SF 2
14831 SF 90
No. REVISION DESCRIPTION DATE