H804 - CONTROL DIAGRAMS.pdf
PDF 491 KB Posted
- Solicitation number
- 47PM0325R0002
About this file
This is a mechanical control diagram and sequence of operations document for the AFRH Sheridan Renovation project showing the chiller plant flow diagram, mechanical controls legend, point list designations, and detailed sequence of operations for the primary-secondary chiller system controls, waterside economizer (free cooling), condenser water system, and emergency refrigerant leak exhaust fan.
The diagram details a complex HVAC system with two cooling towers (600 tons each), two chillers (CH-1 and CH-2), multiple chilled water pumps (CHWP-P1, CHWP-P2, CHWP-S1, CHWP-S2), condenser water pumps (CWP-1, CWP-2), and associated valves and controls. The sequence of operations describes detailed control logic for normal chiller operation, free cooling mode activation when ambient temperatures are below 48°F, lead/lag pump control, emergency protocols, and integration with the existing Siemens Apogee building automation system (BAS). The document includes comprehensive point lists detailing analog/digital inputs/outputs and system features for all major components.
View the file
Other files
Show 40 more
Latest 50 of 90 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(E)COOLING TOWER #1 (E)COOLING TOWER #2
(E)12"
(E)ISOLATION VALVE
(TYP.)
(E)12"
NOTE:
EXISTING COOLING TOWERS BASED
ON EVAPCO MODEL # USS-112-814
(NOMINAL 600 TONS EACH)
(E)TOWER
PLATFORM
PENETRATION (TYP)
(E)12"
GRADE
(E)AUTOMATIC
FLOW CONTROL
VALVE (TYP)
(E)12"
GRADE
CWP-1
(E)CHECK
VALVE (TYP)
(E)12"
(E)14"
(E)CWR
(E)CWS
(E)12" (E)14"
(E )C
W R (E
)C W
S
(E)CWR
(E)CWS
(E)14"
(E)14"
(E)14"
(E)14"
(E)CWS
(E)10"
(E)CWR
(E)CWS
(E)FLEX.
CONNECTION
(TYP)
DASHED AREA DENOTES
EQUIPMENT/PIPING WITHIN
MACHINERY ROOM
CONDENSER
CONDENSER
EVAPORATOR
EVAPORATOR
CH-2
CHWP-P2
CHWP-S1
CHWP-S2
CH-1
AS-1
(E)10"
(E )C
W R
(E )C
W S
(E)CWR
TC1
ET-1
(E)2"
(E)2" CW MAKE
UP
3-WAY
VALVE,
TYP.
(E)CHWR
(E)CHWS
(E )C
H W
S -P
CWP-2
(E)CHWR(E)CHWR
CHWP-P1
HX-1
(VALVES OPEN FOR FREE COOLING)
(E)FS TT-2
AI
(E)FS
AI
(E)FS
TT-1
AI
(E)FS
AO
(E)FS
V-10
DO
V-9
DO
V-12
DO
V-11
DO
V-14
AO
V-15AO
10" CWR
C W
R
A A V8
DO
V-2
DO
V-6
DO
V-5
DO
V-7
DO
V-3
DO
V-8
DO
V-1
DO
(E)6" CHWR
(E)3-WAY VALVE
MASTER CONTROL TC-1
V-13
DO
V-4
DO
TT-3
AI
TT-4
AI
TT-5
AI
(E)FS
OAT-1
V16
AO V17
AO
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
CLIENT:
418 BEAVER STREET
SEWICKLEY, PA 15143
PH: 412.287.7333
www.aeworks.com
PROFESSIONAL:
COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.
SUBMISSION:
CONSTRUCTION BID
DOCUMENTS
AE WORKS®
A u to d e s k D o c s /A
F R
H -0
S h e ri d a n /A
F R
H -0
M
E P
-2
.r v t
/1
/2
:3
:3
P
M
H804
AA
MJC
AFRH-033
CONTROL DIAGRAMS
AFRH SHERIDAN
RENOVATION
140 ROCK CREEK CHURCH
ROAD, NORTHWEST,
WASHINGTON, DC
ARMED FORCES
RETIREMENT HOME -
WASHINGTON D.C.
11-13-2024
NO DATE REVISION
1 2/12/2025 BID ADDENDUM
V-X VALVE DESIGNATION
TT-X TEMPERATURE TRANSMITTER
HX HEAT EXCHANGER
FS FLOW SWITCH
DO DIGITAL OUTPUT
DI DIGITAL INPUT
CWS CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN
CWP-X CONDENSER WATER PUMP
CHWS CHILLED WATER SUPPLY
CHWR CHILLED WATER RETURN
CHWP-X CHILLED WATER PUMP
CH-X CHILLER
AO ANALOG OUTPUT
AI ANALOG INPUT
SYMBOL DESCRIPTION
MECHANICAL CONTROLS LEGEND
*EXISTING TO REMAIN CONTROL POINTS NOT SHOWN
OUTSIDE AIR TEMPERATURE TRANSMITTER OAT-1
CHWS TO BUILDING (FREE COOLING) TT-5
CWS BACK TO CHILLERS TT-4
CHWS TO CHILLERS TT-3
CHWS FROM CH-2 TT-2
CHWS FROM CH-1 TT-1
CWS BYPASS TO HX-1 (FREE COOLING) V-15
CWR BYPASS TO HX-1 (FREE COOLING) V-14
CHWS FROM CHWP-P1 V-13
CHWR FROM HX-1 (FREE COOLING) V-12
CWR FROM HX-1 (FREE COOLING) V-11
CHWS FROM HX-1 (FREE COOLING) V-10
CWS TO HX-1 (FREE COOLING) V-9
CHWS FROM CH-2 V-8
CWS TO CH-2 V-7
CHWR TO CH-2 V-6
CWR FROM CH-2 V-5
CHWS FROM CH-1 V-4
CWS TO CH-1 V-3
CHWR TO CH-1 V-2
CWR FROM CH-1 V-1
POINT DEVICE
POINT LIST DESIGNTATIONS
PRIMARY-SECONDARY CHILLER SYSTEM CONTROLS
WHEN PRIMARY CHILLED WATER PUMP CHWP-P1 STARTS,
VALVE V-13 OPENS GRADUALLY (AT ADJUSTED RATE).
WHEN CHWP-P1 STOPS, V-13 CLOSES.
WHEN CHWP-P1 STARTS, CONDENSER WATER PUMP CWP-1
STARTS. CHILLER CH-1 STARTS WHEN CONDENSER FLOW
IS SENSED BY IF2 AND CHILLED WATER TEMPERATURE
CONTROLLER TC1.
WITH HOA SWITCH ON AUTOMATIC, ON STOP SIGNAL FROM
FC-1, CHWP-P1 AND CWP-1 WILL, THROUGH TIME DELAY,
CONTINUE TO OPERATE 1 MINUTE (ADJUSTABLE) AFTER
CH-1 IS OFF. WHEN CHILLER SAFETY CONTROL IS RESET,
PUMP CHWP-P1 WILL RESTART AND CHILLER WILL
RESTART THROUGH FLOW SWITCH IF1.
CONTROLS FOR CH-2 ARE SIMILAR.
EXISTING MASTER CONTROL TC1, WITH PROPORTIONAL
PLUS INTEGRAL FEATURE, IN COMMON WATER SUPPLY,
SET FOR 42 DEGREES F, CONTROLS CAPACITY OF BOTH
CHILLERS THROUGH LOW LIMIT CONTROLLERS AT EACH
MACHINE (T-1 AND T-2). THE CAPACITY OF BOTH
OPERATING CHILLERS IS NORMALLY MODULATED IN
UNISON. PROVIDE PROGRAMMING FOR EACH CHILLER TO
PERMIT ADJUSTMENT OF SEQUENCES.
SELECTOR SWITCH S-2 ON LOCAL CONTROL PANEL, WHEN
SET IN AUTOMATIC MODE, SHALL ENABLE CHILLER
SYSTEMS TO OPERATE UNDER AUTOMATIC FLOW
CONTROL AS REQUIRED BY BUILDING CHILLER WATER
FLOW DEMAND AS DESCRIBED BELOW, IN MANUAL MODE,
OPERATOR WILL START AND STOP CHILLER SYSTEMS.
IN AUTOMATIC MODE, SECONDARY PUMPS CHWP-S1 AND
CHWP-S2 OPERATING FLOW CONTROLLER FC1 WILL
OPERATE CHWP-P1 AND CHWP-P2.
THE PRIMARY CHILLED WATER PUMPS WILL BE
CONTROLLED BY THE CHILLER MASTER CONTROLLER. THE
CHILLER MASTER CONTROLLER WILL TIE INTO THE
EXISTING BAS CONTROL PANEL TO PROVIDE RESET
SCHEDULE AND STATUS OF CHILLERS.
THE SECONDARY CHILLED WATER PUMPS WILL OPERATE
IN A LEAD/LAG MANNER WITH THE PUMP HAVING THE
LEAST RUN TIME HOURS BECOMING THE "LEAD" PUMP. THE
SELECTION OF THE LEAD PUMP WILL OCCUR ON A
MONTHLY BASIS, THE LEAD CHILLED WATER PUMP WILL
RUN CONTINUOUSLY. DIFFERENTIAL PRESSURE INSTALLED
ACROSS EACH PUMP WILL CONFIRM THE STATUS (I.E.
ON/OFF) OF EACH PUMP AND TRIGGER THE STARTING OF
THE LAG PUMP SHOULD THE LEAD PUMP FAIL TO PRODUCE
FLOW FOR A CONTINUOUS 30 SECOND PERIOD.
THE ATC WILL PROVIDE START/STOP AND STATUS, PUMP
ALTERATION, ALARMING, AND VFD CONTROL.
THE ATC WILL PROVIDE A PRESSURE SENSOR AT THE END
OF THE CHILLED WATER LOOP TO CONTROL THE VFD'S.
THE VFD'S WILL BE FURNISHED AND INSTALLED BY THE
ATC CONTRACTOR. POWER WIRING WILL BE BY THE
ELECTRICAL CONTRACTOR.
THE REMOTE PRESSURE SENSOR WILL BE LOCATED IN THE
MAIN HEADER IF THE PUMPS RESET THE SETPOINT OF THE
FLOW METER SET POINT (ADJ.). WHENEVER THE DELTA P
IS LOW, THE FLOW WILL RESET THE REQUIRED FLOW
(GPM) UPWARD. ON A HIGH DELTA P, THE REVERSE WILL
OCCUR. WHENEVER THE LEAD CHILLED WATER PUMP IS AT
FULL OUTPUT FOR OVER 15 MINUTES (ADJ.), THE LAG
CHILLED WATER PUMP WILL ENERGIZE.
AN ADJUSTABLE TIME DELAY WILL IMPOSE A 15-MINUTE
DELAY (ADJUSTABLE) BETWEEN SUBSEQUENT STARTS
(AFTER INITIAL PUMP START) AND 5-MINUTE DELAY
BETWEEN SUBSEQUENT STOPS FOLLOWING THE
STARTING OR STOPPING OF ANY PRIMARY PUMP.
LEAD CHILLER IS LOCKED OFF UNTIL MINIMUM FLOW IS
SENSED BY FC-1 AND RETURN WATER TEMPERATURE AT
T4 IS 6 DEGREES F. HIGHER THAN TC-1 SETPOINT
(ADJUSTABLE). T-3 RESET IS ADJUSTABLE, AFTER START
OF LEAD CHILLER, T-3 IS LOCKED OUT OF CIRCUIT AND
WILL NOT PREVENT START OF OTHER CHILLER.
IN THE EVENT OF RESTORATION OF POWER FOLLOWING
FAILURE, DELAY BETWEEN SUBSEQUENT STARTS OF
PRIMARY PUMPS SHALL BE REDUCED TO 1-MINUTE.
SYSTEM LEAD-LAG SELECTOR SWITCH ON LOCAL
CONTROL PANEL WILL ENABLE SELECTION OF OPERATING
SEQUENCE OF CHILLER SYSTEM, 1.2, OR 2,1.
SECONDARY CHILLED WATER PUMPS CHWP-S1 AND CHWP-
S2 ARE STARTED AND STOPPED MANUALLY FROM THE
LOCAL CONTROL PANEL. THEY ARE VARIABLE SPEED
PUMPS WITH SPEED CONTROLLERS FURNISHED BY THE
PUMP MANUFACTURER. BOTH PUMPS START
SIMULTANEOUSLY ON SLOWEST SPEED AND GRADUALLY
SPEED UP IN RESPONSE TO PC1 AND PC2.
PRESSURE DIFFERENTIAL CONTROLLERS, PC1 AND PC2,
LOCATED TO SENSE SUPPLY AND RETURN PRESSURE
WHERE INDICTAED ON PLANS IN DISTRIBUTION PIPING WILL
CONTROL OPERATING PUMPS SPEEDS TO MAINTAIN A
MINIMUM DIFFERENTIAL OF 10 PSI AT EACH CONTROLLER.
PC1 AND PC2 ARE ADJUSTABLE FROM 5 PSI TO 25 PSI. PC1
AND PC2 WILL BE INDUSTRIAL QUALITY 4-20 MA.
REUSE EXISTING AUTOMATIC VALVE CONTROL PANEL.
COOLING TOWER CONTROLS, VALVES, SENSORS, AND
TRANSMITTERS ARE EXISTING TO REMAIN EXCEPT FOR
THE ADDITIONAL CONTROLS FOR FREE COOLING.
GENERAL NOTES:
1. ALL SETPOINTS WILL BE ADJUSTABLE.
2. ALL CONTROLS FOR CHILLED WATER PUMPS,
CONDENSER WATER PUMPS, CHILLERS, COOLING
TOWERS, FLOW SWITCHES, ETC. WILL TIE INTO
EXISTING "SIEMENS APOGEE" BAS CONTROL
SYSTEM.
CONDENSER WATER SYSTEM CONTROLS
ALL COOLING TOWER CONDENSER WATER CONTROLS AND SEQUENCES WILL BE EXISTING TO
REMAIN EXCEPT FOR THE ADDITION OF FREE COOLING BYPASS EXPLAINED ABOVE.
NEW PUMPS TO TIE INTO EXISTING BAS CONTROL SEQUENCES AND REPLACE EXISTING PUMPS.
EMERGENCY REFRIGERANT LEAK EXHAUST
FAN SEQUENCE OF OPERATION
UPON SENSING A REFRIGERANT LEAK AND RECEIVING SIGNAL FROM MONITORING SYSTEM, THE
EXISTING DAMPER WILL MODULATE TO 100% OPEN AND CYCLE THE EXISTING EXHAUST FAN ON.
SHERIDAN CHILLER PLAN - SEQUENCE OF OPERATIONS
WATERSIDE ECONOMIZER (FREE COOLING)
WHEN THE AMBIENT TEMPERATURE IS 48 DEG F (ADJ) AND THE CONDENSER WATER TEMPERATURE IS AT A MINIMUM OF 55 DEG F (ADJ), THE CHILLER OPERATION WILL CHANGE FROM NORMAL OPERATION
TO ECONOMIZER OPERATION UTILIZING THE FREE COOLING HEAT EXCHANGER TO REMOVE HEAT
FROM THE CHILLED WATER BY USING COLD CONDENSER WATER. COOLING TOWER BYPASS VALVE
V-16,17 WILL BYPASS THE COOLING TOWER UNTIL THE CONDENSER WATER IS AT AN ACCEPTABLE
TEMPERATURE FOR THE CHILLER.
ONCE THE CONDENSER WATER SUPPLY TEMPERATURE IS ACCEPTABLE AS SENSED BY THE EXISTING CONDENSER WATER TEMPERATURE TRANSMITTER, BYPASS VALVE V-14,15 WILL FULLY OPEN TO THE
HEAT EXCHANGER AND TEMPERATURE TRANSMITTER TT-4 WILL CONTINUE TO MONITOR THE
INCOMING CONDENSER WATER TEMPERATURE. AUTOMATIC CONTROL VALVE V-11 WILL FULLY OPEN TO ALLOW CONDENSER WATER RETURN BACK TO THE EXISTING COOLING TOWER. ON THE CHILLED WATER SIDE OF THE HEAT EXCHANGER BYPASS VALVE V-8 WILL BE IN THE BYPASS POSITION OPEN TO THE HEAT EXCHANGER. CHILLED WATER ISOLATION VALVE V-10 WILL FULLY OPEN TO ALLOW CHILLED WATER SUPPLY TO THE BUILDING. CHILLED WATER SUPPLY TEMPERATURE TO THE BUILDING WILL BE SENSED BY TEMPERATURE TRANSMITTER TT-5. SUPPLY WATER TEMPERATURE TO THE BUILDING WILL BE MAINTAINED BELOW 60 DEG F (ADJ). ONCE THE CHWS TEMPERATURE EXCEEDS 60 DEG F (ADJ) THE
SYSTEM WILL CHANGE OVER TO MECHANICAL COOLING. ONCE IN MECHANICAL COOLING MODE,
VALVES V-8, V-10, V-11, AND V-15 WILL GO TO THE FULLY CLOSED POSITION TO THE HEAT EXCHANGER, AND VALVES V-1, V-4, V-8, V-15, AND V-5 WILL FULLY OPEN TO THE CHILLER CONDENSER.
NOTES:
OA TEMPERATURE X X AMBIENT TEMPERATURE
FREE COOLING LEAVING TEMP TT-5 X X X X
TOWER BYPASS VALVE V16. V17 X X 3 WAY MODULATING VALVE
FREE COOLING BYPASS V15 X X 3 WAY MODULATING VALVE
BYPASS VALVE V14 X X X 3 WAY MODULATING VALVE
ISOLATION VALVE V13 X X X HX 2-POSITION VALVE
HX ISOLATION VALVE V12 X X X HX 2-POSITION VALVE
HX ISOLATION VALVE V11 X X X HX 2-POSITION VALVE
HX ISOLATION VALVE V10 X X X HX 2-POSITION VALVE
HX ISOLATION VALVE V9 X X X HX 2-POSITION VALVE
VALVE V8 X X X 3 WAY VALVE
VALVE V7 X X X
VALVE V6 X X X
VALVE V5 X X X
VALVE V4 X X X
VALVE V3 X X X
VALVE V2 X X X
VALVE V1 X X X
TC-1 X X X 3 Way Valve
FLOW METER X X
PC-2 X X DP controller in Distribution Piping
PC-1 X X DP controller in Distribution Piping
DPS-1 X X DP at the end of Chilled water loop
DPS-S2 X X Differential Pressure across pump
DPS-S1 X X Differential Pressure across pump
DPS-P2 X X Differential Pressure across pump
DPS-P1 X X Differential Pressure across pump
FLOW SWITCH IF4 X X CH-2 COND FLOW SWITCH
FLOW SWITCH IF3 X X CH-2 EVAP FLOW SWITCH
FLOW SWITCH IF2 X X CH-1 COND FLOW SWITCH
FLOW SWITCH IF1 X X CH-1 EVAP FLOW SWITCH
CWP-2 X X X X X X
CWP-1 X X X X X X
CHWP-S2 VFD X X X X X X X
CHWP-S1 VFD X X X X X X X
CHWP-P2 VFD X X X X X X X
CHWP-P1 VFD X X X X X X X
ENTERING COND. WATER TEMP TT-4 X X X X
LEAVING CHILLED WATER TEMP TT-2 X X X X
LEAVING CHILLED WATER TEMP TT-1 X X X X
ENTERING CHILLED WATER TEMP TT-3 X X X X
CHILLER CONTROL PANEL X X X
SYSTEM POINT DESCRIPTION
INPUT OUTPUT INPUT OUTPUT ALARMS PROGRAMSSHERIDAN CHILLER PLANT
ANALOG DIGITAL SYSTEMS FEATURES
NOTES
SYSTEM POINT LIST
12" = 1'-0"
SHERIDAN FLOW DIAGRAM
12-FEB-25
File details come from the government source that posted it. Updated .