H702 - HVAC SCHEDULES.pdf
PDF 420 KB Posted
- Solicitation number
- 47PM0325R0002
About this file
This is a mechanical drawing showing HVAC equipment schedules for a renovation project at the Armed Forces Retirement Home in Washington D.C. The schedules detail specifications for various HVAC systems including unit heaters, air ionization devices, air handling units, chillers, heat exchangers, pumps, air separators, and expansion tanks.
Key equipment specifications include two 400-ton water-cooled centrifugal chillers (CH-1 and CH-2) manufactured by Daikin, six pumps manufactured by Bell & Gossett (including primary/secondary chilled water and condenser water pumps ranging from 10-75 HP), four existing ventilation air handling units (VAU-1 through VAU-4) with capacities between 11,000-12,100 CFM, and one plate/frame heat exchanger (HX-1) with 6,114.80 MBH capacity. The schedules provide detailed technical specifications including flow rates, temperatures, electrical requirements, physical dimensions, and other performance parameters for each piece of equipment. All major equipment is noted as "Government Furnished / Contractor Installed."
View the file
Other files
Show 40 more
Latest 50 of 90 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DATE:
DRAWN BY:
CHECKED BY:
PROJ. NO:
DRAWING NO:
DRAWING TITLE:
PROJECT NAME:
CLIENT:
418 BEAVER STREET
SEWICKLEY, PA 15143
PH: 412.287.7333
www.aeworks.com
PROFESSIONAL:
COPYRIGHT 2024 BY AE WORKS LTD ALL RIGHTS RESERVED.
SUBMISSION:
CONSTRUCTION BID
DOCUMENTS
AE WORKS®
A u to d e s k D o c s /A
F R
H -0
S h e ri d a n /A
F R
H -0
M
E P
-2
.r v t
/1
/2
:3
:3
P
M
H702
AA
MJC
AFRH-033
HVAC SCHEDULES
AFRH SHERIDAN
RENOVATION
140 ROCK CREEK CHURCH
ROAD, NORTHWEST,
WASHINGTON, DC
ARMED FORCES
RETIREMENT HOME -
WASHINGTON D.C.
11-13-2024
1. PROVIDE WALL MOUNTED THERMOSTAT, MOUNTING BRACKET, LOUVERS,
NOTES
UH-1 S-120 51 3 0.156 120 1 1/3
(MBH) (GPM) FT H20 HP
UNIT TAG MODEL NO. HEATING CAPACITY HW FLOW FLUID PD VOLTAGE PH MOTOR
UNIT HEATER
1 ALL VAUs - EXISTING TO REMAIN, FOR REFERENCE
NOTES:
VAU-4 VENTILATION A 12,100 12,100 3.70 13.9 15 1130 18 93 78 54.8 54.3 1004.0 505.4 134.0 12.0 24.3 498 2 11 1.00 8 0 50.0 695.2 44.0 2.90 0.12 23.3 519 2 10 1 460/3/60
VAU-3 VENTILATION A 11,400 11,400 3.70 12.8 15 1132 18 93 78 54.7 54.3 949.8 477.8 126.6 16.3 24.3 469 2 12 1.07 6 0 50.0 656.7 41.5 9.6 0.10 23.3 489 2 9 1 460/3/60
VAU-2 VENTILATION A 11,400 11,400 3.70 12.8 15 1132 18 93 78 54.7 54.3 949.8 477.8 126.6 16.3 24.3 469 2 12 1.07 6 0 50.0 656.7 41.5 9.6 0.10 23.3 489 2 9 1 460/3/60
VAU-1 VENTILATION A 11,000 11,000 3.70 12.1 15 1124 18 93 78 54.5 54.3 922.3 463.3 122.2 15.3 24.3 453 2 12 1.01 6 0 50.0 605.1 40.0 5.5 0.16 23.3 471 2 13 1 460/3/60
BHP HP DB WB DB WB
AIRFLOW
(CFM)
MIN OA
CFM
TSP IN
H20
MOTOR TYPE
RPM
WHEEL
DIA INCH
EAT °F LAT °F TOTAL
LOAD
MBH
SENS
LOAD
MBH
GPM @
45°F EWT
60F LWT
MAXIMUM
H20 PD FT
H20
MIN TOTAL
FACE AREA
FT2
MAXIMUM
FACE VEL
FPM
No. of
COILS
MAX FIN
SPACING
FINS/IN
MAXIMUM
AIR PD IN
H20
MIN
ROWS EAT °F LAT °F
MBH @ 180°F
EWT
GPM @
30°F ▲T
MAXIMUM
H20 PD FT
H20
MAXIMUM
AIR PD IN
H20
MIN TOTAL
FACE AREA
FT2
MAXIMUM
FACE VEL
FPM
No. of
COILS
MAX FIN
SPACING
FINS
MIN
ROWSDESIG DUTY
TYPE
(SEE
SPEC)
FAN SECTION COOLING COIL SECTION HEATING COIL SECTION
ELECTRICAL
VOLTS/PH/
HERTZ
EXISTING AIR HANDLING UNIT SCHEDULE
AHU-2 BOTTOM
COIL
VAV
7500 PER
COIL
150 GPS-iMOD
1 PER COOLING
COIL
80" 30" 24-240 15 AHU
140 MILLION
PER 1.0"
1 TO 14, 15,
16 ,17
AHU-2 TOP COIL VAV
7500 PER
COIL
150 GPS-iMOD
1 PER COOLING
COIL
80" 30" 24-240 15 AHU
140 MILLION
PER 1.0"
1 TO 14, 15,
16 ,17
AHU-1 VAV 10000 150 GPS-iMOD
1 PER COOLING
COIL
EXAMPLE - 72" 40" 24-240 15 AHU
140 MILLION
PER 1.0"
1 TO 14, 15,
16 ,17
ZONE TAG FLOW CFM
O/A
FLOW
GPS
MODEL
GPS QUANTITY COIL WIDTH
COIL
HEIGHT
VOLTAGE (AC) WATTS
MOUNTING
LOCATION
ION DENSITY
(IONS/CC)
NOTES
AIR IONIZATION DEVICE SCHEDULE - MODULAR COIL CLEANING
NO DATE REVISION
1 2/12/2025 BID ADDENDUM
HX-1 BELL & GOSSETT AP100
SHERIDAN
MECHANICAL ROOM
GASKETED, WATER 6,114.80 88.9 32.5 51.2 150 5,945 61.7 49 960 46 56 1,218
MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) EWT (DEG F) LWT (DEG F)
FLOW
(GPM)
MARK
BASIS OF DESIGN
LOCATION TYPE CAPACITY (MBH)
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
DESIGN
PRESSURE (PSI)
WEIGHT
(LBS)
EVAPORATOR CONDENSER
PLATE AND FRAME HEAT EXCHANGER SCHEDULE - GOVERNMENT FURNISHED / CONTRACTOR INSTALLED
AS-1
AMERICAN
WHEATLEY
TASS008
SHERIDAN
MECHANICAL ROOM
44.625 28 20 8 150 260
MANUFACTURER MODEL
MARK
BASIS OF DESIGN
LOCATION HEIGHT (IN)
WIDTH WITH FLANGES
(IN)
DIAMETER
(IN)
CONNECTION SIZE
(IN)
WORKING PRESSURE
(PSI)
WEIGHT
(LBS)
AIR SEPARATOR - GOVERNMENT FURNISHED / CONTRACTOR INSTALLED
ET-1
AMERICAN
WHEATLEY
BDT-060
SHERIDAN
MECHANICAL ROOM
60 48 24 1-1/2" 150 220
MANUFACTURER MODEL
MARK
BASIS OF DESIGN
LOCATION
ACCEPTANCE VOLUME
(GAL)
HEIGHT (IN)
DIAMETER
(IN)
CONNECTION SIZE
(IN)
WORKING PRESSURE
(PSI)
WEIGHT
(LBS)
EXPANSION TANK - GOVERNMENT FURNISHED / CONTRACTOR INSTALLED
CH-2 DAIKIN WMC 400TR 44-54 85-95
SHERIDAN
MECHANICAL ROOM
CENTRIFUGAL, WATER
COOLED
400 94.5 55.2 184.3 15,054 56 42 667.6 85 95 1118 340 383 238.7 500 460/3/60
CH-1 DAIKIN WMC 400TR 42-56 85-95
SHERIDAN
MECHANICAL ROOM
CENTRIFUGAL, WATER
COOLED
400 94.5 55.2 184.3 15,054 56 42 667.6 85 95 1118 340 383 238.7 500 460/3/60
MANUFACTURER MODEL EWT (DEG F) LWT (DEG F) FLOW (GPM) EWT (DEG F) LWT (DEG F) FLOW (GPM) RLA (A) MCA KW MOCP (A) V/PH/HZ
MARK
BASIS OF DESIGN
LOCATION TYPE TONS
HEIGHT
(IN)
WIDTH
(IN)
LENGTH
(IN)
WEIGHT
(LBS)
EVAPORATOR CONDENSER ELECTRICAL
CHILLER SCHEDULE - GOVERNMENT FURNISHED / CONTRACTOR INSTALLED
CWP-2 BELL & GOSSETT VIS 8X8X13C CONDENSER WATER SHERIDAN COOLING TOWER BUILDING INLINE, VFD 365 150 1,200 84.1 75 1800 460/3/60
CWP-1 BELL & GOSSETT BGE80SC6X6X135-365P-1-IN CONDENSER WATER SHERIDAN COOLING TOWER BUILDING INLINE, VFD 365 150 1,200 84.1 75 1800 460/3/60
CHWP-S2 BELL & GOSSETT BG-E1510-4GC-SS-326T-L
SECONDARY CHILLED
WATER
SHERIDAN MECHANICAL ROOM END SUCTION, VFD 326 150 800 82 50 1800 460/3/60
CHWP-S1 BELL & GOSSETT BG-E1510-4GC-SS-326T-L
SECONDARY CHILLED
WATER
SHERIDAN MECHANICAL ROOM END SUCTION, VFD 326 150 800 82 50 1800 460/3/60
CHWP-P2 BELL & GOSSETT BG-E1510-4BD-SS-215T-S PRIMARY CHILLED WATER SHERIDAN MECHANICAL ROOM END SUCTION, VFD 215 40 700 81.1 10 1800 460/3/60
CHWP-P1 BELL & GOSSETT BG-E1510-4BD-SS-215T-S PRIMARY CHILLED WATER SHERIDAN MECHANICAL ROOM END SUCTION, VFD 215 40 700 81.1 10 1800 460/3/60
MANUFACTURER MODEL V/PH/HZ
MARK
BASIS OF DESIGN
SYSTEM LOCATION TYPE NEMA FRAME HEAD (FT)
FLOW
(GPM)
EFFICIENCY (%) HP RPM
ELECTRICAL
PUMP SCHEDULE - GOVERNMENT FURNISHED / CONTRACTOR INSTALLED
12-FEB-25