This announcement provides details for an upcoming federal contract opportunity to renovate basement spaces at a Department of Veterans Affairs medical center in Ann Arbor, Michigan. The renovation project includes approximately 14,000 square feet of existing basement, sub-basement, electrical shop, and recreation therapy office space. Work will upgrade mechanical, electrical and plumbing systems, improve layouts for efficiency of flow and function, and includes asbestos abatement. The procurement will be conducted as a total set-aside for qualified Service-Disabled Veteran Owned Small Businesses. The solicitation is planned for release on March 20, 2023 via SAM.gov and will include bid documents, specifications and drawings. The contract type will be firm-fixed-price. The government intends to award within 120 days of bid opening with a magnitude of cost between $1 million to $5 million.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
36C25023B0027 – 0007 – 506-20-102 – Upgrade Basement Building 1W – Ann Arbor VAMC
5. PROJECT NUMBER (if applicable)
CODE 7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO. 1. CONTRACT ID CODE
FACILITY CODE CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30 PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243
(Type or print) (Type or print)
(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code)
(If other than Item 6)
(Specify type of modification and authority)
(such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
1 2
0007 06-02-2023
506-20-102
36C250
Department of Veterans Affairs
Network Contracting Office (NCO) 10
5500 Armstrong Rd., Bldg. 9 Rm. 105
Battle Creek MI 49037
36C250
Department of Veterans Affairs
Network Contracting Office (NCO) 10
24 Frank Lloyd Wright Dr. Lobby M2200
Ann Arbor MI 48105
To all Offerors/Bidders
36C25023B0027
06-02-2023
X
X X
X 1
The purpose of this Amendment is:
1. To provide responses to the Request for Information (RFIs).
End of Amendment 0007
SCOTT D. BRENNAN
Contracting Specialist
NCO1115LE-0962
36C25023B0027 – 0007 – 506-20-102 – Upgrade Basement Building 1W – Ann Arbor VAMC
Question 30: A branch of EF-1 serves the Safety Cabinet. Clarify if this Branch associated with VV-2 is the only duct to be stainless steel, or if the entire EF-1 duct run shall be stainless steel.
Specification referenced:
E. Biological Safety Cabinet, Hl2, Hood Exhaust and Associated Ductwork:
1.3 mm (18 gage) all welded stainless steel.
Answer 30: The specimen storage cabinet is not considered by this project to be a biological safety cabinet. Specification section referenced is standard VA language and may be considered not applicable.
Question 31: EF-1 duct system is specified at 3.1 ESP, and a portion serves the autopsy as noted. Please clarify if EF-1 shall be constructed of galvanized steel or stainless steel. EF-2 duct system serves the Nuclear Waste Storage at 0.6 In ESO. Please clarify galvanized or stainless steel.
Specification referenced:
F. Duct for Negative Pressure Up to 750 Pa (3-inch W.G.): Provide for exhaust duct between HEPA filters and exhaust fan inlet including systems for Autopsy
Suite exhaust.
1. Round Duct: Galvanized steel, spiral lock seam construction with standard slip joints.
2. Rectangular Duct: Galvanized steel, minimum 1.0 mm (20 gage), Pittsburgh lock seam, companion angle joints 32 mm by 3.2 mm ( 1-1/4 by 1/8 inch) minimum at not more than 2.4 m (8 feet) spacing.
Approved pre-manufactured joints are acceptable in lieu of companion angles.
Answer 31: The specification does not require the referenced exhaust systems to be stainless steel.