14.15_E602 - PANELBOARD SCHEDULES RFI 28 - 506-20-102.pdf

PDF 456 KB Posted

Attached to
Z2DA--506-20-102 Upgrade Basement Building 1W (23NR9KA30)
Solicitation number
36C25023B0027
Issued by

About this file

This pre-solicitation announcement provides details for an upcoming Invitation for Bid for interior renovation work at a Veterans Administration Medical Center facility. The project involves approximately 14,000 square feet of existing basement, sub-basement, electrical shop, and recreation therapy office space. Renovations will improve efficiency and functionality through an updated layout and upgrades to mechanical, electrical and plumbing systems. Asbestos abatement is also included. The solicitation will be issued on or around March 20, 2023 with a magnitude of cost estimated between $1 million and $5 million. The government intends to award a firm fixed price contract within 120 days of bid opening to a verified Service-Disabled Veteran Owned Small Business. Offerors should monitor the Contract Opportunities website for additional details and amendments to the forthcoming solicitation.

View the file

Other files

File Type Posted
Notice of Award Contract 36C25024C0025 Oct 31 - 506-20-102.pdf PDF
36C25023B0027 0007.pdf PDF
36C25023B0027 0006.pdf PDF
1-AE114 - PHASE A5 NEW WORK PLAN RFI 29 - 506-20-102.pdf PDF
105126 Plastic Lockers for RFI 29 Answer - 506-20-102.pdf PDF
1-AE112 - PHASE A3 NEW WORK PLAN RFI 29 - 506-20-102.pdf PDF
123100 Metal Casework for RFI 29 Answer - 506-20-102.pdf PDF
000110 TOC for RFI 29 Answer - 506-20-102.pdf PDF
36C25023B0027 0005.pdf PDF
14.03_1-EP101 - BASEMENT POWER PLAN - NEW WORK - RFI 28 - 506-20-102.pdf PDF
36C25023B0027 0004.pdf PDF
S04 - Pre-Bid 2nd Site Visit Agenda - 506-20-102.pdf PDF
S04 - Pre Bid 2nd Site Visit Attendance Log - 506-20-102 signed.pdf PDF
BID SPECIFICATIONS 2023-0510 Update - 506-20-102.pdf PDF
36C25023B0027 0003.pdf PDF
Addendum 01 Section 11 41 21 - 506-20-102.pdf PDF
36C25023B0027 0002.pdf PDF
RFI No. 14 Drawing Q and A - 506-20-102.pdf PDF
Asbestos Assessment-07.2022 - 506-20-102.pdf PDF
Addendum 01 Section 11 73 00 - 506-20-102.pdf PDF
Addendum 01 Section 01 00 00 - 506-20-102.pdf PDF
S04 - Pre-Bid Walk Through Attendance Sheet signed - 506-20-102.pdf PDF
36C25023B0027 0001 - 506-20-102.pdf PDF
S04 - Pre-Bid Site Visit Agenda signed - 506-20-102.pdf PDF
RFI Form - 506-20-102.pdf PDF
EMR Certification Form - 506-20-102.pdf PDF
Brand Name Only Justification Security Cameras - 506-20-102.pdf PDF
Brand Name Only Justification Fire Alarm System - 506-20-102.pdf PDF
Brand Name Only Justification Nuclear Storage Flooring - 506-20-102.pdf PDF
Drawings - 506-20-102.pdf PDF
Brand Name Only Justification Building Controls - 506-20-102.pdf PDF
36C25023B0027 Apr 6 - 506-20-102.pdf PDF
SPECIFICATIONS 2023-0405 - 506-20-102.pdf PDF
Wage Determination MI20230101 Feb 24 - 506-20-102.pdf PDF
36C25023B0027.docx DOCX document
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

C U s e rs

\j b o n b \D o c u m e n ts

\R e v it L o c a l F ile s \2

\A n n A rb o r B ld g

W B a s e m e n t_

M E

P ja c k .b o n b ri g h tT

D B

.r v t

/1

/2

:5

:4

P

M

E602

PANELBOARD SCHEDULES

01/13/2023 JB HT

UPGRADE BASEMENT,

BUILDING 1 WEST

506-20-102

ANN ARBOR, MICHIGAN

BID DOCUMENTSANN ARBOR VA

MEDICAL

CENTER Approved: Veteran's Affairs Medical Center

Notes:

Total Est. Demand Current: 12 A

Total Conn. Current: 12 A

Receptacle 2580 VA 100.00% 2580 VA Total Est. Demand: 4267 VA

Power 67 VA 100.00% 67 VA Total Conn. Load: 4267 VA

Motor 180 VA 100.00% 180 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 6 A 2 A 30 A

Total Load: 607 VA 180 VA 3480 VA

41 SPACE -- -- 0 VA 0 VA 42

39 SPARE 20 A 1 0 VA 0 VA

2 30 A AB29 UPS(EXISTING)

37 GARBAGE DISPOSAL - GROSSING TABLE 20 A 1 0 VA 0 VA -- -- SPACE 38

35 Receptacle 20 A 1 1500... 540 VA 1 20 A AB31 RCPT. 36

33 FG104A GROSSING TABLE RCPT. 20 A 1 0 VA 180 VA 1 20 A EF-3 34

31 XRAY AB201 PNT LIFT(EXISTING) 20 A 1 0 VA 540 VA 1 20 A AB40 RCPT. 32

29 XRAY AB201 AUTO DOOR (EXISTING) 20 A 1 0 VA 540 VA 1 20 A FG104A RCPT. 30

27 FG104A AUTOPSY TABLE RCPT. 20 A 1 0 VA 0 VA 28

25 XRAY AB201 RCPT.(EXISTING) 20 A 1 0 VA 0 VA

2 20 A SPLIT UNIT BB07(EXISTING)

23 XRAY AB201 RCPT.(EXISTING) 20 A 1 0 VA 0 VA 24

21 XRAY AB201 WARNING LITE(EXISTING) 20 A 1 0 VA 0 VA 22

19 FG104A CADAVER LIFT 20 A 1 0 VA 0 VA

3 30 A MORGUE COMPRESSOR(EXISTING)

17 HU-001(EXISTING) 20 A 1 0 VA 0 VA 1 20 A DOOR BB93(EXISTING) 18

15 RO-101(EXISTING) 20 A 1 0 VA 0 VA 1 20 A DOOR BB91(EXISTING) 16

13 AB33J RCPT.(EXISTING) 20 A 1 0 VA 0 VA 1 20 A FIRE DAMPER(EXISTING) 14

11 0 VA 900 VA 1 20 A FG104B RCPT. 12

UPS IT CLOSET(EXISTING) 30 A 2

0 VA 0 VA 1 20 A EXISTING 10

7 0 VA 0 VA 1 20 A WIRELESS DETECTOR(EXISTING) 8

UPS IT CLOSET(EXISTING) 30 A 2

0 VA 0 VA 1 20 A PARM AB200 PIXIS(EXISTING) 6

3 RCPT. CRASH CART(EXISTING) 20 A 1 0 VA 0 VA 1 20 A PARM AB200 HOOD(EXISTING) 4

1 RCPT. A22a, CORRIDOR(EXISTING) 20 A 1 0 VA 67 VA 1 20 A Power MECHANICAL B1W.09 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

1. CIRCUITS 2, 12, 19: UTILIZE SPARE 20A/1P BREAKER FOR NEW CIRCUIT.

2. PROVIDE NEW 20A/1P BREAKER IN PANELBOARD FOR CIRCUITS 30, 32-34, 36.

Notes:

Enclosure: Type 1 MCB Rating: 225 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: Phases: 3 Mains Type: MCB

Location: ELEC. AB35 Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: CRBD-1

Notes:

Total Est. Demand Current: 2 A

Total Conn. Current: 2 A

Total Est. Demand: 1524 VA

Total Conn. Load: 1524 VA

Lighting 640 VA 100.00% 640 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 4 A 0 A 3 A

Total Load: 884 VA 0 VA 640 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32

29 SPACE -- -- 0 VA 0 VA -- -- SPACE 30

27 SPACE -- -- 0 VA 0 VA -- -- SPACE 28

25 SPACE -- -- 0 VA 0 VA -- -- SPACE 26

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22

19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20

17 SPACE -- -- 0 VA 0 VA 18

15 SPACE -- -- 0 VA 0 VA 16

13 SPACE -- -- 0 VA 0 VA

3 150 A SPARE

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 BLDG 28 MORGUE LIGHTS 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 Lighting Rooms BB09, AB21, AB31, BB18, AB46... 20 A 1 640 VA 0 VA 1 20 A SPARE 6

3 LINEN(EXISTING) 20 A 1 0 VA 0 VA 1 20 A SPARE 4

1 SPACE -- -- 0 VA 884 VA 1 20 A BLDG.28 CORRIDOR LTS. 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

1. UTILIZE SPARE 20A/1P BREAKERS FOR NEW CIRCUITS.

Notes:

Enclosure: Type 1 MCB Rating: 225 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: Phases: 3 Mains Type: MCB

Location: ELEC. AB35 Volts: 480/277 Wye A.I.C. Rating:

Branch Panel: LBD-1

Notes:

Total Est. Demand Current: 52 A

Receptacle 1747 VA 100.00% 1747 VA Total Conn. Current: 52 A

Lighting 163 VA 100.00% 163 VA Total Est. Demand: 42973 VA

Other 100 VA 100.00% 100 VA Total Conn. Load: 42973 VA

Motor 37302 VA 100.00% 37302 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 57 A 46 A 55 A

Total Load: 15354 VA 12788 VA 14831 VA

41 SPACE -- -- 0 VA 0 VA 42

39 SPACE -- -- 0 VA 0 VA 40

37 SPACE -- -- 0 VA 0 VA

3 70 A (EXISTING)

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32

29 SPACE -- -- 0 VA 0 VA -- -- SPACE 30

27 SPACE -- -- 0 VA 0 VA -- -- SPACE 28

25 SPACE -- -- 0 VA 0 VA -- -- SPACE 26

23 1466... 0 VA -- -- SPACE 24

21 1278... 0 VA -- -- SPACE 22

45 kVA XFMR CLBD 100 A 3

1535... 0 VA -- -- SPACE 20

17 0 VA 0 VA 18

15 0 VA 0 VA 16

WATER FOUNTAIN CHILLER(EXISTING) 50 A 3

0 VA 0 VA

3 50 A FLUID COOLER BLDG 28

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 LINEN LTS.(EXISTING) 20 A 1 0 VA 0 VA 1 20 A SPARE 8

5 Lighting Room BB05, AB40, AB31 20 A 1 163 VA 0 VA 1 20 A SPARE 6

3 AB35 LTS.(EXISTING) 20 A 1 0 VA 0 VA 1 20 A SPARE 4

1 AB35 LTS.(EXISTING) 20 A 1 0 VA 0 VA 1 20 A SPARE 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

1. CIRCUIT 5: UTILIZE SPARE 20A/1P BREAKER FOR NEW CIRCUIT.

2. PROVIDE NEW 100A/3P AND 50A/3P BREAKERS FOR NEW TRANSFORMER AND FLUID COOLER CIRCUITS.

Notes:

Enclosure: Type 1 MCB Rating: 225 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: Phases: 3 Mains Type: MCB

Location: ELEC. AB35 Volts: 480/277 Wye A.I.C. Rating:

Branch Panel: CLBD-1

Notes:

Total Est. Demand Current: 119 A

Total Conn. Current: 119 A

Receptacle 1747 VA 100.00% 1747 VA Total Est. Demand: 42811 VA

Other 100 VA 100.00% 100 VA Total Conn. Load: 42811 VA

Motor 37302 VA 100.00% 37302 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 130 A 107 A 125 A

Total Load: 15354 VA 12788 VA 14669 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36

33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34

31 EF-5 20 A 1 800 VA 0 VA 1 20 A SPARE 32

29 UC-5, FAN 15 A 1 240 VA 960 VA 1 20 A P-3B 30

27 SPARE 20 A 1 0 VA 960 VA 1 20 A P-3A 28

25 250 VA 661 VA 1 20 A UC-4 LIGHT, DOOR HEATER CABLE 26

UC-4, FAN 15 A 2

250 VA 1711... 24

21 3459... 1711...

2 20 A ACCU-1

19 3459... 3224... 20

WCCU-4 60 A 3

3459... 3224...

2 20 A UC-4, DEFROST HEATER

15 865 VA 935 VA 1 20 A UC-3, FAN, LIGHTS 16

13 865 VA 865 VA 14

WCCU-3 15 A 3

865 VA 865 VA 12

9 2570... 865 VA

3 15 A WCCU-2

7 2570... 1237... 1 20 A UC-2, FAN, LIGHTS 8

WCCU-1 40 A 3

2570... 526 VA 1 20 A UC-1 LIGHT, DOOR HEATER CABLE 6

3 187 VA 1238... 4

UC-1, FAN 15 A 2

187 VA 1238...

2 15 A UC-1, DEFROST HEATER

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

1. 150A M.C.B.

Notes:

Enclosure: Type 1 MCB Rating: 150 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: XFMR CLBD Phases: 3 Mains Type: MCB

Location: MECHANICAL AB21A Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: CLBD-2

EXISTING EXISTING EXISTING

NEW NEW

Notes:

Total Est. Demand Current: 2 A

Total Conn. Current: 2 A

Total Est. Demand: 900 VA

Total Conn. Load: 900 VA

Receptacle 900 VA 100.00% 900 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 4 A 1 A 3 A

Total Load: 450 VA 150 VA 300 VA

29 SPACE -- -- 0 VA 0 VA -- -- SPACE 30

27 SPACE -- -- 0 VA 0 VA -- -- SPACE 28

25 SPACE -- -- 0 VA 0 VA -- -- SPACE 26

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22

19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20

17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18

15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16

13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14

11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12

9 B28.06 DOOR ACCESS CONTROL PANEL 20 A 1 0 VA 0 VA 1 20 A SPARE 10

7 AB46 DOOR ACCESS CONTROL PANEL 20 A 1 150 VA 0 VA 1 20 A SPARE 8

5 BB18 DOOR ACCESS CONTROL PANEL 20 A 1 150 VA 150 VA 1 20 A C3.5 DOOR ACCESS CONTROL PANEL 6

3 BB09 DOOR ACCESS CONTROL PANEL 20 A 1 150 VA 4

1 B1W.31 DOOR ACCESS CONTROL PANEL 20 A 1 150 VA 150 VA 1 20 A BB13 DOOR ACCESS CONTROL PANEL 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

1. 150A MCB.

Notes:

Enclosure: Type 1 MCB Rating: 150 A

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: XFMR LBD Phases: 3 Mains Type: MCB

Location: MECHANICAL AB21A Volts: 120/208 Wye A.I.C. Rating: 10,000

Branch Panel: LSBD-2

01/13/2023No. Revisions: Date:

BID DOCUMENTS 01/13/2023

ADDENDUM 02 05/17/2023

Sheets
E602 - PANELBOARD SCHEDULES

File details come from the government source that posted it. Updated .