This pre-solicitation announcement provides details for an upcoming Invitation for Bid for interior renovation work at a Veterans Administration Medical Center facility. The project involves approximately 14,000 square feet of existing basement, sub-basement, electrical shop, and recreation therapy office space. Renovations will improve efficiency and functionality through an updated layout and upgrades to mechanical, electrical and plumbing systems. Asbestos abatement is also included. The solicitation will be issued on or around March 20, 2023 with a magnitude of cost estimated between $1 million and $5 million. The government intends to award a firm fixed price contract within 120 days of bid opening to a verified Service-Disabled Veteran Owned Small Business. Offerors should monitor the Contract Opportunities website for additional details and amendments to the forthcoming solicitation.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
C U s e rs
\j b o n b \D o c u m e n ts
\R e v it L o c a l F ile s \2
\A n n A rb o r B ld g
W B a s e m e n t_
M E
P ja c k .b o n b ri g h tT
D B
.r v t
/1
/2
:5
:4
P
M
E602
PANELBOARD SCHEDULES
01/13/2023 JB HT
UPGRADE BASEMENT,
BUILDING 1 WEST
506-20-102
ANN ARBOR, MICHIGAN
BID DOCUMENTSANN ARBOR VA
MEDICAL
CENTER Approved: Veteran's Affairs Medical Center
Notes:
Total Est. Demand Current: 12 A
Total Conn. Current: 12 A
Receptacle 2580 VA 100.00% 2580 VA Total Est. Demand: 4267 VA
Power 67 VA 100.00% 67 VA Total Conn. Load: 4267 VA
Motor 180 VA 100.00% 180 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 6 A 2 A 30 A
Total Load: 607 VA 180 VA 3480 VA
41 SPACE -- -- 0 VA 0 VA 42
39 SPARE 20 A 1 0 VA 0 VA
2 30 A AB29 UPS(EXISTING)
37 GARBAGE DISPOSAL - GROSSING TABLE 20 A 1 0 VA 0 VA -- -- SPACE 38
35 Receptacle 20 A 1 1500... 540 VA 1 20 A AB31 RCPT. 36
33 FG104A GROSSING TABLE RCPT. 20 A 1 0 VA 180 VA 1 20 A EF-3 34
31 XRAY AB201 PNT LIFT(EXISTING) 20 A 1 0 VA 540 VA 1 20 A AB40 RCPT. 32
29 XRAY AB201 AUTO DOOR (EXISTING) 20 A 1 0 VA 540 VA 1 20 A FG104A RCPT. 30
27 FG104A AUTOPSY TABLE RCPT. 20 A 1 0 VA 0 VA 28
25 XRAY AB201 RCPT.(EXISTING) 20 A 1 0 VA 0 VA
2 20 A SPLIT UNIT BB07(EXISTING)
23 XRAY AB201 RCPT.(EXISTING) 20 A 1 0 VA 0 VA 24
21 XRAY AB201 WARNING LITE(EXISTING) 20 A 1 0 VA 0 VA 22
19 FG104A CADAVER LIFT 20 A 1 0 VA 0 VA
3 30 A MORGUE COMPRESSOR(EXISTING)
17 HU-001(EXISTING) 20 A 1 0 VA 0 VA 1 20 A DOOR BB93(EXISTING) 18
15 RO-101(EXISTING) 20 A 1 0 VA 0 VA 1 20 A DOOR BB91(EXISTING) 16
13 AB33J RCPT.(EXISTING) 20 A 1 0 VA 0 VA 1 20 A FIRE DAMPER(EXISTING) 14
11 0 VA 900 VA 1 20 A FG104B RCPT. 12
UPS IT CLOSET(EXISTING) 30 A 2
0 VA 0 VA 1 20 A EXISTING 10
7 0 VA 0 VA 1 20 A WIRELESS DETECTOR(EXISTING) 8
UPS IT CLOSET(EXISTING) 30 A 2
0 VA 0 VA 1 20 A PARM AB200 PIXIS(EXISTING) 6
3 RCPT. CRASH CART(EXISTING) 20 A 1 0 VA 0 VA 1 20 A PARM AB200 HOOD(EXISTING) 4
1 RCPT. A22a, CORRIDOR(EXISTING) 20 A 1 0 VA 67 VA 1 20 A Power MECHANICAL B1W.09 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
1. CIRCUITS 2, 12, 19: UTILIZE SPARE 20A/1P BREAKER FOR NEW CIRCUIT.
2. PROVIDE NEW 20A/1P BREAKER IN PANELBOARD FOR CIRCUITS 30, 32-34, 36.
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MCB
Location: ELEC. AB35 Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: CRBD-1
Notes:
Total Est. Demand Current: 2 A
Total Conn. Current: 2 A
Total Est. Demand: 1524 VA
Total Conn. Load: 1524 VA
Lighting 640 VA 100.00% 640 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 4 A 0 A 3 A
Total Load: 884 VA 0 VA 640 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34
31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32
29 SPACE -- -- 0 VA 0 VA -- -- SPACE 30
27 SPACE -- -- 0 VA 0 VA -- -- SPACE 28
25 SPACE -- -- 0 VA 0 VA -- -- SPACE 26
23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24
21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22
19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20
17 SPACE -- -- 0 VA 0 VA 18
15 SPACE -- -- 0 VA 0 VA 16
13 SPACE -- -- 0 VA 0 VA
3 150 A SPARE
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 BLDG 28 MORGUE LIGHTS 20 A 1 0 VA 0 VA 1 20 A SPARE 8
5 Lighting Rooms BB09, AB21, AB31, BB18, AB46... 20 A 1 640 VA 0 VA 1 20 A SPARE 6
3 LINEN(EXISTING) 20 A 1 0 VA 0 VA 1 20 A SPARE 4
1 SPACE -- -- 0 VA 884 VA 1 20 A BLDG.28 CORRIDOR LTS. 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
1. UTILIZE SPARE 20A/1P BREAKERS FOR NEW CIRCUITS.
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MCB
Location: ELEC. AB35 Volts: 480/277 Wye A.I.C. Rating:
Branch Panel: LBD-1
Notes:
Total Est. Demand Current: 52 A
Receptacle 1747 VA 100.00% 1747 VA Total Conn. Current: 52 A
Lighting 163 VA 100.00% 163 VA Total Est. Demand: 42973 VA
Other 100 VA 100.00% 100 VA Total Conn. Load: 42973 VA
Motor 37302 VA 100.00% 37302 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 57 A 46 A 55 A
Total Load: 15354 VA 12788 VA 14831 VA
41 SPACE -- -- 0 VA 0 VA 42
39 SPACE -- -- 0 VA 0 VA 40
37 SPACE -- -- 0 VA 0 VA
3 70 A (EXISTING)
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34
31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32
29 SPACE -- -- 0 VA 0 VA -- -- SPACE 30
27 SPACE -- -- 0 VA 0 VA -- -- SPACE 28
25 SPACE -- -- 0 VA 0 VA -- -- SPACE 26
23 1466... 0 VA -- -- SPACE 24
21 1278... 0 VA -- -- SPACE 22
45 kVA XFMR CLBD 100 A 3
1535... 0 VA -- -- SPACE 20
17 0 VA 0 VA 18
15 0 VA 0 VA 16
WATER FOUNTAIN CHILLER(EXISTING) 50 A 3
0 VA 0 VA
3 50 A FLUID COOLER BLDG 28
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 LINEN LTS.(EXISTING) 20 A 1 0 VA 0 VA 1 20 A SPARE 8
5 Lighting Room BB05, AB40, AB31 20 A 1 163 VA 0 VA 1 20 A SPARE 6
3 AB35 LTS.(EXISTING) 20 A 1 0 VA 0 VA 1 20 A SPARE 4
1 AB35 LTS.(EXISTING) 20 A 1 0 VA 0 VA 1 20 A SPARE 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
1. CIRCUIT 5: UTILIZE SPARE 20A/1P BREAKER FOR NEW CIRCUIT.
2. PROVIDE NEW 100A/3P AND 50A/3P BREAKERS FOR NEW TRANSFORMER AND FLUID COOLER CIRCUITS.
Notes:
Enclosure: Type 1 MCB Rating: 225 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: Phases: 3 Mains Type: MCB
Location: ELEC. AB35 Volts: 480/277 Wye A.I.C. Rating:
Branch Panel: CLBD-1
Notes:
Total Est. Demand Current: 119 A
Total Conn. Current: 119 A
Receptacle 1747 VA 100.00% 1747 VA Total Est. Demand: 42811 VA
Other 100 VA 100.00% 100 VA Total Conn. Load: 42811 VA
Motor 37302 VA 100.00% 37302 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 130 A 107 A 125 A
Total Load: 15354 VA 12788 VA 14669 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 36
33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 EF-5 20 A 1 800 VA 0 VA 1 20 A SPARE 32
29 UC-5, FAN 15 A 1 240 VA 960 VA 1 20 A P-3B 30
27 SPARE 20 A 1 0 VA 960 VA 1 20 A P-3A 28
25 250 VA 661 VA 1 20 A UC-4 LIGHT, DOOR HEATER CABLE 26
UC-4, FAN 15 A 2
250 VA 1711... 24
21 3459... 1711...
2 20 A ACCU-1
19 3459... 3224... 20
WCCU-4 60 A 3
3459... 3224...
2 20 A UC-4, DEFROST HEATER
15 865 VA 935 VA 1 20 A UC-3, FAN, LIGHTS 16
13 865 VA 865 VA 14
WCCU-3 15 A 3
865 VA 865 VA 12
9 2570... 865 VA
3 15 A WCCU-2
7 2570... 1237... 1 20 A UC-2, FAN, LIGHTS 8
WCCU-1 40 A 3
2570... 526 VA 1 20 A UC-1 LIGHT, DOOR HEATER CABLE 6
3 187 VA 1238... 4
UC-1, FAN 15 A 2
187 VA 1238...
2 15 A UC-1, DEFROST HEATER
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
1. 150A M.C.B.
Notes:
Enclosure: Type 1 MCB Rating: 150 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: XFMR CLBD Phases: 3 Mains Type: MCB
Location: MECHANICAL AB21A Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: CLBD-2
EXISTING EXISTING EXISTING
NEW NEW
Notes:
Total Est. Demand Current: 2 A
Total Conn. Current: 2 A
Total Est. Demand: 900 VA
Total Conn. Load: 900 VA
Receptacle 900 VA 100.00% 900 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 4 A 1 A 3 A
Total Load: 450 VA 150 VA 300 VA
29 SPACE -- -- 0 VA 0 VA -- -- SPACE 30
27 SPACE -- -- 0 VA 0 VA -- -- SPACE 28
25 SPACE -- -- 0 VA 0 VA -- -- SPACE 26
23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24
21 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 22
19 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 20
17 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 18
15 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 16
13 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 14
11 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 12
9 B28.06 DOOR ACCESS CONTROL PANEL 20 A 1 0 VA 0 VA 1 20 A SPARE 10
7 AB46 DOOR ACCESS CONTROL PANEL 20 A 1 150 VA 0 VA 1 20 A SPARE 8
5 BB18 DOOR ACCESS CONTROL PANEL 20 A 1 150 VA 150 VA 1 20 A C3.5 DOOR ACCESS CONTROL PANEL 6
3 BB09 DOOR ACCESS CONTROL PANEL 20 A 1 150 VA 4
1 B1W.31 DOOR ACCESS CONTROL PANEL 20 A 1 150 VA 150 VA 1 20 A BB13 DOOR ACCESS CONTROL PANEL 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
1. 150A MCB.
Notes:
Enclosure: Type 1 MCB Rating: 150 A
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: XFMR LBD Phases: 3 Mains Type: MCB
Location: MECHANICAL AB21A Volts: 120/208 Wye A.I.C. Rating: 10,000
Branch Panel: LSBD-2
01/13/2023No. Revisions: Date:
BID DOCUMENTS 01/13/2023
ADDENDUM 02 05/17/2023
| Sheets |
| E602 - PANELBOARD SCHEDULES |