1696746_DWG_5of5.pdf
PDF 9 MB Posted
- Attached to
- JFY 2022 PROJECT J-875, BATTLE STAFF TRAINING FACILITY, U. S. NAVSUPPACT MCB CAMP BLAZ, GUAM
- Solicitation number
- N62742-26-R-1306
About this file
These are architectural and engineering drawings for the Battle Staff Training Facility (Project J-875) at Marine Corps Base Camp Blaz, Guam, prepared by NAVFAC Pacific. The drawings include two-way communications system plans, audio-visual (AV) systems infrastructure, and related technical specifications for a military construction (MILCON) project under contract N62742-20-D-0001.
The two-way communications drawings (Sheets TT-001 through TT-502) specify emergency call stations, master control stations, and related equipment installations throughout a two-story facility, with general compliance requirements referencing UFC, NEC, NFPA, and ADA standards. The AV systems drawings (Sheets TA001 through TA704) detail infrastructure for multiple classroom and operations spaces, including flat-panel video monitors (ranging 55" to 98" diagonal), video conferencing cameras, ceiling-mounted microphones and loudspeakers, equipment cabinets, credential systems, and associated cabling/conduit pathways. Key AV equipment includes displays with integrated CATV tuners and HDMI inputs, assistive listening systems, multi-time zone clocks, room classification signage, and dedicated power/data outlets. The drawings specify AV system types A through H with varying configurations for different room functions (standalone training rooms, conference rooms, operations centers, and command decks). Installation requirements mandate EMT conduit, wire mesh cable trays below raised access flooring, proper bonding and grounding, and coordination with electrical, telecommunications, and other building systems. All materials must be UL-listed, and workmanship must conform to NEC standards and the American Electricians Handbook.
View the file
Other files
Show all 35
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
INSTALLATION SHALL COMPLY WITH UFC 3-600-01, UFC 1-200-01, UFC 4-010-06, 2023 NATIONAL ELECTRICAL CODE, NFPA 72, NFPA 1, NFPA 101, NFPA 1225, UL 2525, IBC, ABA, ADA, EQUIPMENT MANUFACTURER'S REQUIREMENTS AND NECA STANDARDS OF
INSTALLATION.
ALL CONDUCTORS INSTALLED IN EXTERIOR SPACES SHALL BE XHHW, INTERIOR WIRING MAY BE
THHW/THHN. UNLESS OTHERWISE NOTED
CONTRACTORS SHALL PROVIDE AND INSTALL AN EQUIPMENT GROUNDING CONDUCTOR IN ALL NEW
CONDUITS.
ALL CONDUCTOR SIZES SHOWN ARE BASED ON COPPER.
ALL EQUIPMENT AND MATERIALS ARE UL LISTED WHERE LISTING IS AVAILABLE FOR THAT TYPE OF
EQUIPMENT OR CONFORM TO ANSI OR NEMA STANDARDS
WORKMANSHIPS SHALL CONFORM TO CONSTRUCTION PRACTICES RECOMMENDED BY THE AMERICAN
ELECTRICIANS HANDBOOK BY CROFT (LATEST EDITION) AND WILL BE SUBJECTED TO THE APPROVAL
OF THE AGENCY THAT HAS JURISDICTION AND THE ENGINEER OF THE RECORD.
ALL METALLIC ENCLOSURES, RACEWAYS, AND ELECTRICAL EQUIPMENT SHALL BE GROUNDED IN
ACCORDANCE WITH THE REQUIREMENTS OF THE NEC ARTICLE 250, WITH THE GROUND WIRE IN EVERY RACEWAY.
RACEWAY SHALL BE SIZED IN ACCORDANCE WITH THE NEC TABLE 250-122.
TEST COMPLETED INSTALLATION AND CORRECT ALL DEFICIENCIES FOUND IN THE SYSTEM OR INSTALLATION.
ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL CONDUIT AND CONNECTIONS
BETWEEN RESPECTIVE DEVICES, FIXTURES, AND EQUIPMENT. CONTRACTOR HAS TO DETERMINE
EXACT ROUTING OF CONDUIT CONNECTIONS AND BETWEEN RESPECTIVE DEVICES, FIXTURES, AND
EQUIPMENT. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATIONS.
CONDUIT TO BE EMT UNLESS OTHERWISE NOTED. PROVIDE JUNCTION BOXES AS REQUIRED BY CODE.
PAINT EXPOSED CONDUIT, BOXES, AND SUPPORTS TO MATCH ADJACENT SURFACES.
PROVIDE SEPARATE NEUTRAL CONDUCTOR FOR ALL 120VAC CIRCUITS.
COORDINATE LOCATION OF ALL TWO WAY COMMUNICATIONS EQUIPMENT AND SIGNAGE WITH ARCHITECT PRIOR TO
START OF WORK.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
TWO WAY COMMUNICATIONS SYMBOL LIST
TWO WAY COMMUNICATIONS SYSTEM
ABBREVIATIONS
SYMBOL
A101
SIM
AF
C
CLF
CP
DP
DSN
DW
EL
EWC
GFI
HA
I
IG
L
LC
LB
MDP
MW
NL
PFB
R
REF
S
T
TR
WP
4X
ARC FAULT BREAKER
CONDUIT
CURRENT LIMITING FUSE
COPIER
DISPOSAL
DEFENSE SWITCHED NETWORK
DISHWASHER
EVENING LIGHT, TIMESWITCH CONTROLLED
ELECTRONIC WATER COOLER
GROUND FAULT CIRCUIT INTERRUPTER
HACR BREAKER
INSTRUCTIONAL
INSULATED GROUND CIRCUIT(S)
LIGHT(S)
LIGHTING CONTACTOR
LOCKABLE BREAKER
MAIN DISTRIBUTION PANEL
MICROWAVE
NIGHT LIGHT, TIMESWITCH CONTROLLED
PROVISIONS FOR BREAKER
RECEPTACLE(S)
REFRIGERATOR
SPARE BREAKER
TACTILE
TAMPER RESISTANT
WEATHERPROOF
NEMA 4X STAINLESS STEEL
VIEW REFERENCE
NORTH ARROW
CENTERLINE
NOTE REFERENCE
KEYNOTE REFERENCE
LUMINAIRE DESIGNATION,
REFER TO LUMINAIRE SCHEDULEABC
TWO WAY COMMUNICATIONS EMERGENCY CALL STATION, WALL MTD
TWO WAY COMMUNICATIONS MASTER STATION, WALL MTD
TWO WAY COMMUNICATIONS UPS, WALL MOUNTED IN CABINET
TWO WAY COMMUNICATIONS TWO WAY COMMUNICATION CONTROLLER,
WALL MOUNTED IN CABINET
TWO WAY COMMUNICATIONS INSTRUCTIONAL SIGN, WALL MOUNTED
TWO WAY COMMUNICATIONS ILLUMINATED SIGN WITH DIRECTIONAL
ARROWS AS INDICATED, WALL MOUNTED WITH BATTERY BACKUP
TWO WAY COMMUNICATIONS TACTILE SIGN, WALL MOUNTED
TWO WAY COMMUNICATIONS DIRECTIONAL SIGN, WALL MOUNTED
AR
AR
I
PS
MS
AR
T
AR
CM
I
H
IA
W
A
U
.S .A
LICENSED
PROFESSIONAL
ENGINEER
NO. 15212-E
J E
R E
MY B. D
O
W
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
M A
K A
L A
P A
H
A W
A
II
AS NOTED
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
P A
C
IF
IC
/1
/2
:2 :1
P
M
C U s e rs \t d a o \D o c u m e n ts
\2
J -8
B a tt le
S ta ff T ra in in g
T
R n e w to m m y .d a o
.r v t
TT-001
JF
Y
P
R O
JE
C
T J
-8
G E
N E
R A
L N
O
TE
S , A
B B
R E
V
IA
TI
O
N S
S
Y M
B O
LS
L
E G
E N
D
JD
17322318
JH LS
3/10/2026
NATHANIEL PYRON, MILCON
PLANNER, DPPH
B A
TT
LE
S
TA
FF
T
R A
IN
IN
G F
A C
IL
IT
Y
DKS/DMK
1696746
F
IN
E G
A Y
A N
, G U
A M
M A
R
IN
E C
O R
P S
B A
S E
, C A
M P
B
LA
Z
KYM
KYM
RYO
N A
V F
A C
P A
C
IF
IC
T T
-0
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
N62742-20-D-0001
03/ /2026
M S
PS
A R
A R
T A
R I
J
G
A
B
C
E
D
F
1 2 3 4 5 6 7 8 9
TA - HQ CAMP COMMANDANT
NURSING RM
TA - G3 FIRES
SVTC CONF RM / SIPR CAFE
GTR 1T (TRAINING TELECOM RM)
TRAINING MATERIAL STORAGE
STAIR 1A
S1A
TA - G4 LOGISTICS
MECHANICAL ENCLOSURE
ELEC RM
STAIR 1B
S1B
STAIR 1C
S1C
INTERIOR COC TRAINING PAD
EMERGENCY GENERATOR
BREAK RM
LOBBY 1
L1
ELEV 1
E1
GTR-1
TA - COC WATCH FLOOR
TA - G5 PLANS
ENTR VESTIBULE
MEN
JAN
CTR 1
CORRIDOR 1C
C1C
TA - G3 STRIKE CELL
110A
OFFICE
125A
TA - G3 OPS
105B
CORRIDOR 1A
C1A
WOMEN
CORRIDOR 1E
C1E
OFFICE
127A
TA - G2 COLLECTIONS AND ANALYSIS
108B
TA - G2 COLLECTIONS AND ANALYSIS
108A
TWO WAY
COMMUNICATION
MASTER STATION
CM
TWO WAY COMMUNICATION HEAD END EQUIPMENT. MAINTAIN
4'-0" FRONT CLEARANCE FROM FACE OF EQUIPMENT.
COORDINATE EQUIPMENT LOCATION WITH ELEC DWGS.
152mm SQ X 102mm D J-BOX WITH CAT 6 JACK AND OUTLET BOX. PROVIDE 27mm C, WITH CAT 6 TO NEAREST TR ROOM AND TERMINATE ON SPARE PATCH PANEL
PORT. COORDINATE PORT ASSIGNMENT WITH IT SYSTEM INSTALLER. PROVIDE
TELEPHONE LINE CONNECTION FOR TWO WAY COMMUNICATION SYSTEM.
PROVIDE 27mm C NIPPLE TO TWO WAY COMMUNICATION SUPERVISOR MODULE.
CAT 6 PATCH CABLE SHALL BE PROVIDED BY THE TWO WAY COMMUNICATION
INSTALLER. PROVIDE ID LABEL FOR CAT 6 JACK PER CAMPUS LABELLING SCHEME.
OFFICE
126B
OFFICE
126A
OFFICE
128B
OFFICE
128A
OFFICE
127B
TA - G1 OPERATIONS
128 TA - COMMAND DECK
TELECOM CLOSET
126C
AV CLOSET
126D
TA - MEDICAL CELL
MECH RM
ELEV MACHINE RM
TA - G3 STRIKE CELL
110B
CORRIDOR 1C
C1C
VESTIBULE 1C
V1C
ELEC CLOSET
CORRIDOR C1A NOT RAF
C1A NOT RAF
TA - G3 OPS
105A
TA - G7 COMM STAT
CORRIDOR 1B
C1B
ENTRY CONTROL POINT
102A
UTILITY CHASE
122A
I
H
IA
W
A
U
.S .A
LICENSED
PROFESSIONAL
ENGINEER
NO. 15212-E
J E
R E
MY B. D
O
W
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
M A
K A
L A
P A
H
A W
A
II
AS NOTED
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
P A
C
IF
IC
/1
/2
:2 :1
P
M
C U s e rs \t d a o \D o c u m e n ts
\2
J -8
B a tt le
S ta ff T ra in in g
T
R n e w to m m y .d a o
.r v t
TT-101
JF
Y
P
R O
JE
C
T J
-8
1S T
F
LO
O R
T W
O -W
A Y
C O
M M
U N
IC
A
TI
O
N P
LA
N
JD
17322319
JH LS
3/10/2026
NATHANIEL PYRON, MILCON
PLANNER, DPPH
B A
TT
LE
S
TA
FF
T
R A
IN
IN
G F
A C
IL
IT
Y
DKS/DMK
1696746
F
IN
E G
A Y
A N
, G U
A M
M A
R
IN
E C
O R
P S
B A
S E
, C A
M P
B
LA
Z
KYM
KYM
RYO
N A
V F
A C
P A
C
IF
IC
T T
-1
3/32" = 1'-0"1
1ST FLOOR TWO-WAY COMMUNICATION PLAN
2' 8' 32'0 4' 6' 24'16' 3/32" =1'-0"
PLAN
NORTH
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
AR
I
AR
T
AR
G
A
B
C
E
D
F
1 2 3 4 5 6 7 8 9
TWO WAY COMMUNICATION
CALL BOX
PRINT RM
ELEC CLOSET
TECH - ADMIN CELL AND LOGISTICS SECTION
TRAINING MATERIAL STORAGE
TRAINING MATERIAL STORAGE
TECG OFFICE / CONF RM
STAIR 2C
S2C
STAIR 2B
S2B
CTR
STORAGE
BREAK RM
TA - TECHCON
208A
JFACC / AVIATION OPS CENTER
227B
SIM TECH CONTROL JLVC / MCVP
OFFICE
211F
TA - G6 PRIMARY
ELEV 2A
EL
SVTC CONF RM / SIPR CAFE
JAN
WOMEN
MECH RM
GTR-2
GTR-2T (TRAINING/TELECOMM RM)
LOBBY 2
L2
OPPOSING FORCES CONTROL CELL
206B
MEN
TA - G9 EXPERIMENTATION
INTEL CONTROL CELL
205B
ELEC CLOSET
CONF RM
211A
OFFICE
211B
OFFICE
211C
OFFICE
211D
OFFICE
211E
STAIR 2A
S2A
VESTIBULE 2
V2
UTILITY CHASE
220A
TECG INTEL SECTION AND RED CELL
225B
HHQ RESPONSE CELL
BLUE / GREEN FORCES CONTROL CELL
226A
I
H
IA
W
A
U
.S .A
LICENSED
PROFESSIONAL
ENGINEER
NO. 15212-E
J E
R E
MY B. D
O
W
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
M A
K A
L A
P A
H
A W
A
II
AS NOTED
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
P A
C
IF
IC
/1
/2
:2 :2
P
M
C U s e rs \t d a o \D o c u m e n ts
\2
J -8
B a tt le
S ta ff T ra in in g
T
R n e w to m m y .d a o
.r v t
TT-102
JF
Y
P
R O
JE
C
T J
-8
2N D
F
LO
O R
T W
O -W
A Y
C O
M M
U N
IC
A
TI
O
N P
LA
N
JD
17322320
JH LS
3/10/2026
NATHANIEL PYRON, MILCON
PLANNER, DPPH
B A
TT
LE
S
TA
FF
T
R A
IN
IN
G F
A C
IL
IT
Y
DKS/DMK
1696746
F
IN
E G
A Y
A N
, G U
A M
M A
R
IN
E C
O R
P S
B A
S E
, C A
M P
B
LA
Z
KYM
KYM
RYO
N A
V F
A C
P A
C
IF
IC
T T
-1
3/32" = 1'-0"1
2ND FLOOR TWO-WAY COMMUNICATION PLAN
2' 8' 32'0 4' 6' 24'16' 3/32" =1'-0"
PLAN
NORTH
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
HELP PHONE
SOLID LIGHT:
BLINKING LIGHT:
CALLING
RECEIVED
EMERGENCY PHONE
Phone 1
Phone 2
Phone 3
Phone 4
Phone 5
Battery:
Green: Full Charge
Yellow: Mid-level Charge
Red: Low Charge
Battery
AC Power
Submaster 1
Submaster 2
Rescue Services Disconnect Call to Rescue Services
MASTER STATION
18 AWG 4 CONDUCTOR TWO
PAIR CABLE
UPS WITH BATTERIES
120VAC UPS OUTPUT
POWER. POWER CHORD
CONNECTION.
(CALL BOX) ELEV LOBBY 2
ENTRY VESTIBULE 101
NOTES:
1. ALL WIRING SHALL BE IN METALLIC CONDUIT, 27mm: MINIMUM TRADE SIZE.
2. PROVIDE DEDICATED 120V, 20A CIRCUIT FOR POWER SUPPLY. REFER TO ELECTRICAL DRAWINGS FOR CIRCUIT INFORMATION.
3. ALL COMMUNICATION WIRING SHALL BE 2 HOUR FIRE RATED AND SHALL HAVE A PATHWAY SURVIVABILITY OF 2 HOURS.
4. PROVIDE ALL WIRING PER THE TWO WAY COMMUNICATION SUPPLIER SHOP DRAWINGS.
5. PROVIDE ALL REQUIRED EQUIPMENT MOUNTING HARDWARE PER THE TWO WAY COMMUNICATION SUPPLIER SHOP DRAWINGS.
6. THE UPS SYSTEM FOR THE TWO-WAY EMERGENCY COMMUNICATIONS SYSTEMS SHALL BE CAPABLE OF OPERATING THE SYSTEM
UNDER QUIESCENT LOAD FOR A MINIMUM OF 24 HOURS AND THEN SUBSEQUENTLY DURING A FIRE OR OTHER EMERGENCY
CONDITION FOR A PERIOD OF 4 HOURS WITH ALL REMOTE CALL STATIONS ACTIVATED AND ALL MASTER CONTROL STATIONS
ANNUNCIATING THE CALLS.
7. FAILURE OF EITHER THE PRIMARY OR SECONDARY POWER SUPPLY SHALL RESULT IN A TROUBLE SIGNAL SENT TO THE FIRE
ALARM CONTROL PANEL.
8. PROVIDE STANDARD 483MM WALL MOUNT CABINET FOR TWO WAY SYSTEM CONTROLLER, AND UPS/BATTERIES. CABINET SHALL
BE LOCKABLE WITH SWINGING HINGED DOOR, REAR ACCESS TYPE HINGED, AND COOLING FANS. CABINET SIZE SHALL BE PER
TWO WAY COMMUNICATION SYSTEM SUPPLIER REQUIREMENTS.
120VAC, 50/60 HZ
UPS INPUT POWER PROVIDE
HARDWIRED CONNECTION
DSN PHONE LINE/EXTENSION REQUIREMENTS:
(1) MINIMUM OF 24V, 20 Ma OFF-HOOK (NO CURRENT IS DRAWN ON-HOOK).
(2) DSN PHONE LINE/EXTENSION SHOULD PROVIDE EITHER A DISCONNECT PULSE
(VOLTAGE DROP AT END OF CALL) OR 30-SECONDS OF SILENCE AFTER HANG-UP
(NO RE-ORDER OR HOWLER FEATURE).
(3) THERE MUST BE NO SPECIAL FEATURES (E.G., HOOK FLASH, CALL WAITING,
AUTO-REDIAL WHEN BUSY, VOICEMAIL, ETC.). THE DSN PHONE LINE/EXTENSION
MUST BE FEATURE FREE.
(4) IF THE PHONE LINE DOES NOT PROVIDE A CALLING PARTY DISCONNECT SIGNAL
(CPC), PROVIDE A SEPARATE CPC DISCONNECT DEVICE IN THE PHONE LINE TO
OBTAIN THE SIGNAL. THE DEVICE SHALL BE POWERED OFF THE PHONE LINE.
THE CPC DISCONNECT TIME SHALL BE 1 SECOND NOMINAL.
(5) PROVIDE A DEDICATED DSN LINE TO THE TWO WAY COMMUNICATION HEAD END
EQUIPMENT AND PROGRAM THE MASTER STATION TO AUTOMATICALLY
CONNECT WITH THE LOCAL BASE 911 DISPATCH AND VICE VERSA. THE BASE
SHALL INSTALL THE DSN LINE TO THE SCHOOL AND THE ELECTRICAL
CONTRACTOR SHALL RUN THE LINE FROM THE COMMS ROOM TO THE MASTER
STATION.
12 AWG 4 CONDUCTOR,
TWO PAIR CABLE
TWO-WAY
SYSTEM
CONTROLLER
UPS MONITOR ADDRESSABLE
FIRE ALARM
MONITOR
MODULE
(SEE FIRE
ALARM DWGS)
TO FIRE ALARM
CONTROL PANEL
POWER FAILURE
RELAY OUTPUT
ELEC 120
ELEC 120
1ST FLOOR
2ND FLOOR
27mmC, W/ CAT 6
DEDICATED DSN TELEPHONE LINE
SYSTEM FAULT. POWER
SUPPLY FAULT, BATTERY
FAULT
27mmC, W/ CAT 6 PATCH CABLE
152MM SQ. X 102MM D DEMARC J-BOX.
PROVIDE WITH CAT 6 JACK AND OUTLET BOX
J
3"
7.5"
14"
CONNECT TO NEAREST 120VAC
OR 277VAC EXIT SIGN CIRCUIT.
PROVIDE DOUBLE FACE SIGN
AND CHEVRONS AS REQUIRED.
3"
EMERGENCY
COMMUNICATIONS
EMERGENCY
COMMUNICATIONS
ILLUMINATED
SIGNAGE
ABOVE 60" BUT
BELOW 80" FROM
FLOOR TO TOP OF
SIGN COORDINATE
EXACT MOUNTING
HEIGHT WITH
ARCHITECT
TWO WAY COMMUNICATIONS
MASTER STATION
TACTILE
SIGNAGE
EMERGENCY
COMMUNICATIONS
INSTRUCTIONAL
SIGNAGE
48" - 60" FROM
FLOOR TO
LOWEST TACTILE
CHARACTER
60" FROM
FLOOR TO
CENTER
ABOVE OR
ADJACENT
TO EACH
CALL BOX
PUSH FOR HELP
PERSONS ABLE TO USE THE
EXIT STAIRWAY DO SO AS
SOON AS POSSIBLE, UNLESS
THEY ARE ASSISTING OTHERS.
LOCATION FLOOR
AFTER ACTIVATING THE TWO-
WAY EMERGENCY
COMMUNICATION SYSTEM,
WAIT HERE FOR ASSISTANCE.
CALL
BOX
48" FROM
FLOOR TO
PUSH
BUTTON
EMERGENCY
EVACUATION
ASSISTANCE
FINISHED FLOOR
EMERGENCY PHONE
DIRECTIONAL
SIGNAGE
48" - 60" FROM
FLOOR TO
LOWEST TACTILE
CHARACTER
EMERGENCY
COMMUNICATION
I
H
IA
W
A
U
.S .A
LICENSED
PROFESSIONAL
ENGINEER
NO. 15212-E
J E
R E
MY B. D
O
W
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
M A
K A
L A
P A
H
A W
A
II
AS NOTED
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
P A
C
IF
IC
/1
/2
:2 :2
P
M
C U s e rs \t d a o \D o c u m e n ts
\2
J -8
B a tt le
S ta ff T ra in in g
T
R n e w to m m y .d a o
.r v t
TT-501
JF
Y
P
R O
JE
C
T J
-8
TW
O
W A
Y C
O M
M U
N
IC
A
TI
O N
S D
E
TA
IL
S
D
IA
G
R A
M
JD
17322321
JH LS
3/10/2026
NATHANIEL PYRON, MILCON
PLANNER, DPPH
B A
TT
LE
S
TA
FF
T
R A
IN
IN
G F
A C
IL
IT
Y
DKS/DMK
1696746
F
IN
E G
A Y
A N
, G U
A M
M A
R
IN
E C
O R
P S
B A
S E
, C A
M P
B
LA
Z
KYM
KYM
RYO
N A
V F
A C
P A
C
IF
IC
T T
-5
NTSC1
TWO WAY COMMUNICATIONS
ILLUMINATED SIGN DETAIL
NTSA1
TWO WAY COMMUNICATIONS DIAGRAM
NTSC3
TWO WAY COMMUNICATIONS MOUNTING
HEIGHT DETAIL
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
SYSTEM INPUTS
SYSTEM OUTPUTS
A B C D
A C
TIV
A
TE V
IS
U
AL
ALE
R T A
T M
ASTER
S
TA
TIO
N S
O
LI
D L
IT
L
ED
IN
D
IC
ATE Z
O N E O
F C
ALL
B O X A
T M
ASTER
S
TATIO
N
A C
TIV
ATES V
IS
U
AL
A
LE
R T A
T M
ASTER
S
TATIO
N S
LO
W
B
LI
N
KIN
G
2-WAY SYSTEM COMMUNICATION FAILURE
A C
TIV
ATES
A
U D
IO
IN
D
IC
A
TO
R A
T M
ASTER
S
TATIO
N
A C
TIV
ATES V
IS
U A L
IN
D
IC
ATO
R A
T M
ASTER
S
TA
TIO
N
TR
AN
SM
IT
S U P
ER
VIS
O R Y S
IG
N
AL
TO
M
O N
IT
O R
IN
G S
TATIO
N
TR
AN
S M
IT
T
R O U B
LE
S
IG
N
AL
TO
M
O N
IT
O R
IN
G S
TA
TIO
N
E F G
2 2-WAY SYSTEM BATTERY FAILURE
E M
E R G
EN
C Y C
ALL
IN
P R O G R
ESS
LE
D
C A
LL
O N H
O
LD
3 2-WAY SYSTEM LOW BATTERY
4 AC POWER LOSS
5 DC POWER LOSS
6 2-WAY SYSTEM COMMON TROUBLE
7 2-WAY SYSTEM WIRE/LINE SUPERVISION
8 CALL BOX INITIATION
9 CALL BOX ON HOLD
10 CALL BOX IN PROGRESS
OUTSIDE PHONE LINE FAILURE
MASTER STATION FAILURE
CALL BOX FAILURE
LINE FAULT MONITOR
TR
AN
SM
IT
T R O U
BLE
S
IG
N
AL
TO
F
IR
E A
LA
R M
C O N
TR
O L
PA
N
EL
H
I
H
IA
W
A
U
.S .A
LICENSED
PROFESSIONAL
ENGINEER
NO. 15212-E
J E
R E
MY B. D
O
W
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
M A
K A
L A
P A
H
A W
A
II
AS NOTED
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
P A
C
IF
IC
/1
/2
:2 :2
P
M
C U s e rs \t d a o \D o c u m e n ts
\2
J -8
B a tt le
S ta ff T ra in in g
T
R n e w to m m y .d a o
.r v t
TT-502
JF
Y
P
R O
JE
C
T J
-8
TW
O
W A
Y C
O M
M U
N
IC
A
TI
O N
S S
E Q
U E
N C
E O
F O
P E
R A
TI
O
N M
A
TR
IX
JD
17322322
JH LS
3/10/2026
NATHANIEL PYRON, MILCON
PLANNER, DPPH
B A
TT
LE
S
TA
FF
T
R A
IN
IN
G F
A C
IL
IT
Y
DKS/DMK
1696746
F
IN
E G
A Y
A N
, G U
A M
M A
R
IN
E C
O R
P S
B A
S E
, C A
M P
B
LA
Z
KYM
KYM
RYO
N A
V F
A C
P A
C
IF
IC
T T
-5
NTSA1
TWO WAY COMMUNICATIONS SEQUENCE
OF OPERATION MATRIX
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
P A
C
IF
IC
M
A K
A L A
P A
H
A W
A
II
AS NOTED
/1
/2
:1 :1
P
M
A u to d e s k D o c s /J
-8
B S
T F
/B L
D G
-J
-1
-T A
.r v t
TA001
JF
Y
P
R O
JE
C
T J
-8
A V
S Y
S
TE
M S
G E
N E
R A
L N
O
TE
S
PKD
17322326
PKD DHC
3/10/2026
NATHANIEL PYRON, MILCON
PLANNER, DPPH
B A
TT
LE
S
TA
FF
T
R A
IN
IN
G F
A C
IL
IT
Y
DKS/DMK
1696746
N62742-20-D-0001
M C
B C
A M
P B
LA
Z
, G U
A M
U .S
. N A
V S
U P
P A
C T
KYM
KYM
RYO
N A
V F
A C
P A
C
IF
IC
T A
AV SYSTEMS GENERAL NOTES:
1. ADHERE TO GOVERNMENT RULES AND REGULATIONS, DIVISION 01, 11, 26, AND 27. SPECIFICATION
SECTIONS, AND DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND
SUPPLEMENTARY CONDITIONS AND DIVISION 01 SPECIFICATION SECTIONS.
2. THE DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY AND WHAT IS CALLED FOR (OR SHOWN) IN EITHER MUST BE PROVIDED AS IF CALLED FOR IN BOTH. IN CASE OF CONFLICT BETWEEN THE DRAWINGS
AND SPECIFICATIONS, THE MORE STRINGENT REQUIREMENT WILL BE ENFORCED, UNLESS THE
CONTRACTOR REQUESTS AND RECEIVES WRITTEN CLARIFICATION STATING OTHERWISE.
3. COORDINATE THE SEQUENCE OF WORK AND REPORT DISCREPANCIES BETWEEN THESE CONTRACT
DRAWINGS AND ACTUAL FIELD CONDITIONS TO THE CONTRACTING OFFICER.
4. DEFINITIONS:
A. "FURNISH" MEANS TO "SUPPLY" AND USUALLY REFERS TO AN ITEM OF EQUIPMENT, CABLING, OR
HARDWARE.
B. "INSTALL" MEANS TO SET IN PLACE, CONNECT, PLACE IN FULL OPERATIONAL ORDER, AND PERFORM
REQUIRED VERIFICATION TESTING.
C. "PROVIDE" MEANS TO "FURNISH AND INSTALL."
D. "EQUIVALENT" MEANS "MEETS THE SPECIFICATIONS OF THE REFERENCE PRODUCT OR ITEM IN
SIGNIFICANT ASPECTS." SIGNIFICANT ASPECTS MUST BE DETERMINED BY THE CONTRACTING
OFFICER.
E. "WORK BY OTHER(S) (CONTRACTOR):" "RE: DIVISION XX," AND SIMILAR EXPRESSIONS MEANS WORK PERFORMED UNDER THE CONTRACT DOCUMENTS, BUT NOT NECESSARILY UNDER THE DIVISION OR
SECTION OF THE WORK ON WHICH THE NOTE APPEARS. IT IS THE CONTRACTOR’S SOLE
RESPONSIBILITY TO COORDINATE THE WORK OF THE CONTRACT BETWEEN THEIR SUPPLIERS,
SUBCONTRACTORS, AND EMPLOYEES. IF CLARIFICATION IS REQUIRED, CONSULT CONTRACTING
OFFICER BEFORE SUBMITTING BID.
5. PROVIDE PATHWAYS, RELATED HARDWARE, EQUIPMENT AND CABLING SHOWN ON THESE DRAWINGS
EXCEPT WHERE OTHERWISE NOTED.
6. DEDICATED PATHWAYS / RACEWAYS MUST BE PROVIDED TO FULLY SUPPORT SYSTEM CABLING FOR THE ENTIRE DISTANCE. NO CABLING IS PERMITTED TO BE RUN UNSUPPORTED OR LAID OVER CEILING TILES, ELECTRICAL CONDUITS, HVAC DUCTS, PIPING, OR OTHER SUPPORTS OR CEILING MEMBERS NOT INTENDED
FOR THAT PURPOSE.
7. COORDINATE WITH OTHER TRADES AND ADJUST AND ADAPT WORK FOR ACTUAL PROJECT CONDITIONS SO FINAL INSTALLATION IS COMPATIBLE WITH MATERIALS, EQUIPMENT, ROUTING, AND CLEARANCES OF
TRADES.
A. EXAMINE THE CONTRACT DOCUMENTS OF TRADES (DRAWINGS FOR THE ARCHITECTURAL,
REFLECTED CEILING, TELECOMMUNICATIONS, CIVIL, HEMP SHIELDING, MECHANICAL HVAC,
ELECTRICAL POWER AND LIGHTING, FIRE PROTECTION, PLUMBING, ETC.).
B. ASSIST OTHER CONTRACTORS IN PREPARING SHOP DRAWINGS FOR COORDINATING INSTALLATION
OF WORK (LOCATION, CEILING CLEARANCES, CABLE TRAY ACCESSIBILITY AND PATHWAY
CLEARANCES THROUGHOUT, ETC.).
C. REFER TO ARCHITECTURAL DRAWINGS TO DETERMINE MINIMUM CLEARANCE REQUIREMENTS FROM
FINISHED FLOOR TO BOTTOM OF DUCTWORK, CONDUIT, CABLE TRAY, LIGHTING, ETC.
8. MAINTAIN A RUNNING UPDATE OF FIELD OR CONTRACT DOCUMENT CHANGES AND UPDATE "AS-BUILT"
DRAWINGS AS AN ONGOING PROCESS.
9. PROVIDE PATHWAYS / RACEWAYS FOR THE AV CABLING. THIS INCLUDES, BUT IS NOT LIMITED TO, CONDUIT, SLEEVES, STUB-UPS, WIREWAYS, J-HOOK CABLE SUPPORT PATHS, AND PERMANENTLY INSTALLED
JUNCTION BOXES IN FLOORS, WALLS, CEILINGS AND UNDERGROUND.
10. PATHWAYS MUST BE BONDED TO THE TELECOM BONDING AND GROUNDING SYSTEM FOR CONNECTION TO THE BUILDING GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH THE SPECIFICATIONS AND ANSI J- STD-607-D. PROVIDE GROUND CONDUCTORS, GROUND CLAMPS, COMPRESSION TAPS, LUGS AND ITEMS
REQUIRED FOR CONNECTION TO THE BONDING AND GROUNDING SYSTEM.
11. FOR WALL-MOUNTED AV DEVICES, PROVIDE RECESS-FLUSH MOUNTED BACKBOXES AND EXTENSION RINGS WITH TOTAL DEPTH TO MATCH THICKNESS OF COMPLETE WALL AND INSULATION ASSEMBLY. PROVIDE
CONDUITS AS INDICATED IN AV PATHWAY RISER DIAGRAMS.
12. REFER TO SYSTEM SPECIFIC DRAWINGS AND DETAILS FOR BACKBOX REQUIREMENTS SPECIFIC TO EACH TYPE. SELECT DEVICES MAY REQUIRE SPECIALIZED BACKBOX TYPES, SIZES, AND MOUNTING CONDITIONS
AS DEPICTED IN DRAWINGS.
13. CONDUITS FOR AV MUST BE SIZED AS INDICATED ON AV PATHWAY RISER DIAGRAMS.
14. CONDUITS FOR AV MUST BE OF NON-FLEXIBLE, RIGID-WALLED CONSTRUCTION, EXCEPT AS OTHERWISE
NOTED OR DETAILED ON THE DRAWINGS.
15. COORDINATE WITH CONTRACTING OFFICER AND OTHER TRADES PRIOR TO CONSTRUCTION FOR CONDUIT
AND BACKBOX LOCATIONS IN PRECAST WALLS, POURED CONCRETE, MASONRY, ETC.
16. OUTLET MOUNTING HEIGHTS INDICATED ARE TO CENTERLINE OF BOX UNLESS OTHERWISE NOTED.
17. DEVICES INDICATED TO BE INSTALLED AT DIFFERENT MOUNTING HEIGHTS AND LOCATED WITHIN ONE STUD
SPACE FROM EACH OTHER MUST ALIGN VERTICALLY ON THE SAME SIDE OF THE STUD.
18. PATHWAY MOUNTING HEIGHTS INDICATED ON PLANS ARE TO THE BOTTOM OF THE PATHWAY SUPPORTS
(STRUT CHANNEL TRAPEZE, ANGLE SUPPORT, CONDUIT CLAMP, ETC).
19. PROVIDE SEISMIC BRACING FOR PATHWAYS AND EQUIPMENT REQUIRED BY CODE, LOCAL GOVERNING
JURISDICTIONS, AND MANUFACTURERS’ SPECIFICATIONS.
20. AV PATHWAY SYSTEMS MUST BE DEDICATED FOR AV CABLING ONLY. OTHER SYSTEMS INCLUDING, BUT NOT LIMITED TO, FIRE ALARM, HVAC CONTROLS, LIGHTING CONTROLS, ETC. MUST BE SUPPORTED BY
OTHER MEANS AND MUST NOT BE ROUTED WITHIN THE AV PATHWAYS.
21. PROVIDE CONDUITS / SLEEVES THROUGH WALLS AND ACROSS INACCESSIBLE CEILING SPACES TO ENSURE
UNOBSTRUCTED PATHWAY BETWEEN END POINTS INDICATED ON AV PATHWAY RISER DIAGRAMS.
22. AV PATHWAYS ROUTED THROUGH ELECTRICAL ROOMS MUST BE PHYSICALLY CONTINUOUS.
23. PROVIDE NEMA 3R CORROSION RESISTANT OUTLETS, CONDUITS AND WIRING METHODS IN AREAS
EXPOSED TO WET CONDITIONS.
24. IN AREAS WHERE CORROSIVE CHEMICALS ARE PRESENT, PROVIDE NEMA 4X OR NEMA 12 FULLY- SEALED/GASKETED CORROSION-RESISTANT ENCLOSURES, OUTLET COVERS, CONDUITS AND WIRING
METHODS, CONSTRUCTED OF TYPE 316 STAINLESS STEEL, NO EXCEPTION.
25. INSTALL PATHWAYS PARALLEL OR PERPENDICULAR TO WALL OR STRUCTURAL MEMBERS TO FOLLOW STRUCTURAL SURFACE CONTOURS AND DO NOT OBSTRUCT PASSAGEWAYS. WHERE MULTIPLE RACEWAYS
ARE ROUTED THROUGH THE SAME AREA, GROUP SUCH RACEWAYS TOGETHER.
26. INSTALL CONDUIT WITH LARGE-RADIUS BENDS. THE RATIOS FOR MINIMUM BEND RADIUS TO CONDUIT
DIAMETER ARE:
A. 6:1 BEND RADIUS OF THE INSIDE CONDUIT DIAMETER FOR CONDUIT SIZES LESS THAN 2 IN.
B. 10:1 BEND RADIUS OF THE INSIDE CONDUIT DIAMETER FOR CONDUIT SIZES EQUAL TO OR GREATER
THAN 2 IN.
27. CONDUIT ROUTING MUST NOT EXCEED 180 DEG. FOR THE SUM OF ELBOWS, SWEEPS AND BENDS FOR A PARTICULAR CONDUIT RUN WITHOUT AN APPROVED PULL-BOX, HAND HOLE, OR VAULT. THE MAXIMUM BEND FOR ANY LOCATION MUST NOT EXCEED 90 DEG. 3-POINT SADDLE BENDS ARE NOT PERMITTED IN
CONDUIT ROUTES.
28. INSIDE CONDUIT RUNS MUST NOT EXCEED 100 FT BETWEEN PULL POINTS WITHOUT AN APPROVED PULL-
BOX.
29. PROVIDE PULL-BOXES AND HAND HOLES IN STRAIGHT SECTIONS OF CONDUIT ONLY. DO NOT USE PULL- BOXES OR HAND HOLES TO CHANGE PATHWAY DIRECTION, UNLESS SPECIFICALLY SHOWN WITH A CHANGE
IN DIRECTION ON THE DRAWINGS.
30. CONDUIT OUTLET BODIES (I.E., CONDULET, C, LB, LL, LR, T), MUST NOT BE USED AS CABLE PULL POINTS OR TO CHANGE PATHWAY DIRECTION IN ANY LOCATIONS. THESE DEVICES ARE COMMONLY USED FOR ELECTRICAL/POWER PATHWAYS AND ARE NOT APPROVED FOR LOW VOLTAGE CABLING. SPECIALTY "SMART LB" CONDUIT OUTLET BODIES DESIGNED FOR LARGE-BEND RADIUS CABLE ENTRY THROUGH EXTERIOR WALLS MAY BE PERMITTED ONLY WHEN SPECIFICALLY INDICATED ON PLANS OR PRE-APPROVED
IN WRITING BY THE CONTRACTING OFFICER.
31. PROVIDE PROTECTIVE INSULATED BUSHINGS ON CONDUIT ENDS INCLUDING RISER CONDUITS/SLEEVES, HORIZONTAL CONDUITS, DEVICE CONDUITS, AND SLEEVES.
32. STUB UP RISER CONDUIT A MINIMUM OF 6 IN. AFF.
33. PROVIDE CONDUIT QUANTITIES AND SIZES AS SHOWN. DO NOT COMBINE CONDUIT RUNS WITHOUT THE
WRITTEN PERMISSION OF THE CONTRACTING OFFICER.
34. PROVIDE LISTED EXPANSION FITTINGS IN CONDUIT OR RACEWAY CROSSING BUILDING EXPANSION JOINTS.
REFERENCE ARCHITECTURAL DRAWINGS FOR EXPANSION JOINT LOCATIONS.
35. PROVIDE EMPTY RACEWAY SYSTEMS WITH A PULL LINE OR TAPE INSTALLED WITH THREE FEET EXTENDING FROM EACH END, KNOTTED AND SECURED TO REMAIN IN PLACE. FOR INDOOR APPLICATIONS, USE PULL LINE HAVING NOT LESS THAN 200 LB. TENSILE STRENGTH. FOR OUTDOOR APPLICATIONS USE PULL TAPE
OR WIRE HAVING NOT LESS THAN 1200-LB. TENSILE STRENGTH.
36. SEAL PENETRATIONS THROUGH RATED ASSEMBLIES (WALLS, FLOORS, ETC.) AS INDICATED ON ARCHITECTURAL DRAWINGS TO MAINTAIN THE ASSEMBLY RATING AROUND AND WITHIN THE PATHWAY.
37. PROVIDE APPROVED REMOVABLE PILLOW-TYPE FIRESTOPPING SYSTEMS TO SEAL PENETRATIONS THROUGH RATED WALLS, FLOORS, ASSEMBLIES AND CONDUIT/SLEEVE OPENINGS FOR AV CABLING.
FIRESTOPPING SYSTEMS AND MATERIALS MUST BE RATED AND APPROVED FOR PREVENTION OF FLAMES, HOT GASSES AND SMOKE WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC
FOR APPLICABLE CODES AND AHJ REQUIREMENTS.
38. JUNCTION BOXES AND BACKBOXES FOR DATA, VOICE, VIDEO, POWER, OR OTHER UTILITIES MUST BE SEPARATED BY AT LEAST ONE STUD CAVITY WHEN SERVING OPPOSITE SIDES OF ACOUSTICALLY RATED PARTITIONS. ALL JUNCTION BOXES LOCATED WITHIN THE SAME STUD CAVITY MUST MAINTAIN A MINIMUM
OF 24 INCHES SEPARATION OR BE SEALED WITH PUTTY PADS.
39. DATA GIVEN ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED. ABSOLUTE ACCURACY IS NOT
GUARANTEED. THE DRAWINGS ARE DIAGRAMMATICAL IN NATURE, AND SYMBOLS AND LINEWORK
CONTAINED THEREIN MUST NOT BE SCALED.
40. PATHWAY ROUTING ON THESE DRAWINGS PRIMARILY SHOWS INTERCONNECTIONS BETWEEN TERMINAL POINTS. COORDINATE THE EXACT ROUTING OF PATHWAYS BASED ON FIELD CONDITIONS PRIOR TO SUBMITTING SHOP DRAWINGS OR INITIATING WORK IN THE FIELD. SHOP DRAWINGS SHOWING ROUTING OF
THESE PATHWAYS MUST BE SUBMITTED AS SPECIFIED IN DIVISION 27 AND APPROVED BY THE
CONTRACTING OFFICER PRIOR TO INSTALLATION. EXTRA TIME MUST BE ALLOWED FOR THE
COORDINATION, SUBMITTAL REVIEW AND APPROVAL PROCESS.
41. ANY PROPOSED OR REQUIRED EXCEPTIONS TO THE AV PATHWAY ROUTING REQUIREMENTS IN THESE DRAWINGS AND ASSOCIATED SPECIFICATIONS MUST BE DETAILED IN CONTRACTOR SHOP DRAWINGS AND SUBMITTALS AND APPROVED PRIOR TO INSTALLATION. ANY REMEDIATION TO AV PATHWAY AND ROUTING TO MEET REQUIREMENTS WILL BE THE TOTAL RESPONSIBILITY OF THE CONTRACTOR AT NO ADDITIONAL
COST TO THE GOVERNMENT.
42. CONDUITS SMALLER THAN 2 IN. TRADE SIZE HAVE NOT BEEN MODELED OR INDICATED ON THESE DRAWINGS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DESIGN AND ROUTE CONDUITS SMALLER THAN 2
IN. FROM THE SOURCE TO THE DESTINATION POINTS.
43. SEQUENCING OF SYSTEMS EQUIPMENT AND PROVISIONING WITHIN THE PROJECT SCOPE MUST BE
COORDINATED WITH THE CONTRACTING OFFICER FOR GOVERNMENT FURNISHED SYSTEMS AND
EQUIPMENT.
44. THE AV DRAWINGS DESCRIBE (A) THE MILCON CONTRACTOR'S BASE "INFRASTRUCTURE" PROVISIONS FOR AV SYSTEMS - SPECIFICALLY INCLUDING AV-RELATED INFRASTRUCTURE (CONDUIT RACEWAYS, BOXES, STRUCTURAL MOUNTING SUBSTRATES, AND AV-SPECIFIC EQUIPMENT CABINETS) TO SUPPORT ALL AV
EQUIPMENT, REGARDLESS OF WHICH VENDOR OR INSTALLER IS HANDLING THE AV EQUIPMENT
INSTALLATION; AND (B) THE SCOPE OF AV EQUIPMENT/SYSTEMS APPROPRIATED AS AV-SPECIFIC "SPECIALTY" COLLATERAL EQUIPMENT (CEQ) ITEMS BY MEANS OF THE CEQ CONTRACT MODIFICATION PROCESS; AND (C) THE SCOPE OF AV EQUIPMENT/SYSTEMS APPROPRIATED AS GOVERNMENT-FURNISHED, GOVERNMENT-INSTALLED (GFGI) ITEMS BY MISSION USERS AND/OR C4IT-DELEGATED TURN-KEY
INSTALLER.
45. REFER TO SPECIFICATION SECTION 27 41 00 "AUDIO-VISUAL SYSTEMS" FOR ADDITIONAL REQUIREMENTS TO
COMPLEMENT THESE DRAWINGS.
46. AV EQUIPMENT AND CABLING IDENTIFIED ON THESE DRAWINGS (AND IN THE RELATED SPECIFICATIONS) AS AV-SPECIFIC "SPECIALTY" COLLATERAL EQUIPMENT (CEQ), MUST BE PROVIDED WITHIN THE AV CEQ PACKAGE. REFER TO THE COMPREHENSIVE INTERIOR DESIGN (CID) PACKAGE'S "AV CEQ" DOCUMENTS
(INCLUDING BASIS OF DESIGN NARRATIVE AND AV EQUIPMENT SCHEDULES) FOR ADDITIONAL
INFORMATION. THE AV-SPECIFIC "SPECIALTY" COLLATERAL EQUIPMENT (CEQ) MUST BE PROVIDED BY A QUALIFIED AND MANUFACTURER-APPROVED AV TRADE CONTRACTOR SPECIALIZING IN THE SALE AND
INSTALLATION OF COMMERCIAL-GRADE AUDIO-VIDEO (AV) SYSTEMS.
47. AV CABLING WILL BE PROVIDED AS PART OF GFGI SCOPE. FOR AV CABLING (WITHOUT EXCEPTION), PROVIDE CABLE RACEWAY INFRASTRUCTURE AS IDENTIFIED ON THESE DRAWINGS.
48. POWER AND DATA COORDINATION REQUIREMENTS ARE CLARIFIED IN THE AV EQUIPMENT SCHEDULES ON THESE DRAWINGS, BUT THE FINAL POWER AND DATA SCOPE IS INDICATED ON THE RESPECTIVE
ELECTRICAL POWER AND TELECOMMUNICATIONS DRAWINGS.
49. NOT ALL PARTS AND PIECES ARE NECESSARILY SHOWN FOR A COMPLETE SYSTEM. UNLESS NOTED OTHERWISE, THE CONTRACTOR AND AV-SPECIFIC CEQ VENDOR/INSTALLER ARE RESPONSIBLE FOR
PROVIDING ONLY THE COMPONENTS SPECIFIED IN THE AV DRAWINGS AND SPECIFICATIONS.
50. THE MILCON GENERAL CONTRACTOR AND THEIR SUB-CONTRACTORS MUST PROVIDE ALL HARDWARE ATTACHED TO THE BUILDING. THIS INCLUDES, BUT IS NOT LIMITED TO, CEILING-MOUNTED EQUIPMENT SUPPORTS, WALL-MOUNTED BACKING SUPPORTS, CABLE TRAY, J-HOOK CABLE SUPPORT PATHS, RACEWAY
AND CONDUIT SYSTEMS, TECHNICAL BONDING/GROUNDING, BRANCH-CIRCUIT POWER
OUTLETS/CONNECTIONS, AND TELE/DATA WORK AREA OUTLETS SPECIFIC TO AV EQUIPMENT PROVISIONS.
51. WHERE DIMENSIONS ARE SHOWN FOR EQUIPMENT SIZES OR MOUNTING HEIGHTS, SUCH DIMENSIONS ARE NOMINAL AND MAY REQUIRE SMALL ADJUSTMENTS FOR FINAL INSTALLATION BASED ON EXACT EQUIPMENT
PROVIDED. WHERE DIMENSIONS ARE CRITICAL, THEY ARE MARKED AS "CRITICAL".
52. PROVIDE BACKING MATERIAL FOR EQUIPMENT WEIGHT THAT IS RATED TO SUPPORT A MINIMUM OF FIVE
TIMES (5X) THE WEIGHT OF THE EQUIPMENT ANCHORED THERETO.
53. THE AV-SPECIFIC CEQ VENDOR/INSTALLER WILL VERIFY THE QUANTITIES OF ALL AV CEQ MATERIALS
SCHEDULED HEREIN, AND PROVIDE THOSE QUANTITIES ACCORDINGLY.
54. AV RACEWAYS MUST BE LABELED WITH PERMANENT TYPED/PRINTED LABELS AT BOTH ENDS OF SYSTEM, AND AT INTERMEDIATE PULL BOXES.
SHEET NO.
NAVFAC DWG. NO. SHEET TITLENO. SHEET
438 TA001 17322326 AV SYSTEMS GENERAL NOTES
439 TA002 17322327 AV SYSTEMS SYMBOLS, LEGEND, AND ABBREVIATIONS
440 TA101 17322328 OVERALL AV FIRST FLOOR PLAN
441 TA102 17322329 PARTIAL AV FIRST FLOOR PLAN - A
442 TA103 17322330 PARTIAL AV FIRST FLOOR PLAN - B
443 TA104 17322331 PARTIAL AV FIRST FLOOR CABLE TRAY PLAN - A
444 TA105 17322332 PARTIAL AV FIRST FLOOR CABLE TRAY PLAN - B
445 TA106 17322333 OVERALL AV SECOND FLOOR PLAN
446 TA107 17322334 PARTIAL AV SECOND FLOOR PLAN - A
447 TA108 17322335 PARTIAL AV SECOND FLOOR PLAN - B
448 TA109 17322336 PARTIAL AV SECOND FLOOR CABLE TRAY PLAN - A
449 TA110 17322337 PARTIAL AV SECOND FLOOR CABLE TRAY PLAN - B
450 TA401 17322338 AV INTERIOR ELEVATIONS
451 TA402 17322339 AV INTERIOR ELEVATIONS
452 TA403 17322340 AV INTERIOR ELEVATIONS
453 TA404 17322341 AV INTERIOR ELEVATIONS
454 TA405 17322342 ENLARGED AV PLANS & INTERIOR ELEVATIONS
455 TA406 17322343 ENLARGED AV PLANS & INTERIOR ELEVATIONS
456 TA407 17322344 ENLARGED AV PLANS & INTERIOR ELEVATIONS
457 TA408 17322345 ENLARGED AV PLANS
458 TA409 17322346 ENLARGED AV PLANS
459 TA410 17322347 AV INTERIOR ELEVATIONS & SECTIONS
460 TA501 17322348 AV INFRASTRUCTURE DETAILS
461 TA502 17322349 AV INFRASTRUCTURE DETAILS
462 TA503 17322350 AV INFRASTRUCTURE DETAILS
463 TA504 17322351 AV INFRASTRUCTURE DETAILS
464 TA601 17322352 AV SYSTEMS SCHEDULES
465 TA701 17322353 AV INFRASTRUCTURE RISER DIAGRAMS
466 TA702 17322354 AV INFRASTRUCTURE RISER DIAGRAMS
467 TA703 17322355 AV INFRASTRUCTURE RISER DIAGRAMS
468 TA704 17322356 AV INFRASTRUCTURE RISER DIAGRAMS
AV SYSTEMS TYPES
LOBBY 1A-1
TYPE DESCRIPTION PLANS / ELEVATIONS RISER DIAGRAM
TA701
N/A
ENTRY CONTROL POINTA-2 TA701
TA102 TA401
TA102 TA104
BREAK ROOMB
TA102 TA108
TA401
TA401 TA402
TA - STANDALONE ROOM / AREA WITH RAFC-1 TA701
TA102 TA103 TA104
TA105 TA107 TA108
TA109 TA110 TA401
TA403 TA404
TA - STANDALONE ROOM / AREA, NO RAFC-2 TA701TA108 TA404
TA - STANDALONE ROOM / AREA WITH RAFC-3
TA102 TA104 TA107
TA109 TA401 TA403
TA702
TECG CONFERENCE ROOME
TA - COC WATCH FLOORH TA704
TA105 TA408
TA409 TA410
TA - COMMAND DECKG TA703
TA105 TA408
TA409 TA410
TA109 TA406 TA702
SVTC CONFERENCE ROOM / SIPR CAFEF
TA104 TA109
TA405 TA407
TA703
TA - DIVISIBLE / COMBINABLE ROOMS / AREASD TA702
TA102 TA104 TA107
TA108 TA109 TA110
TA401 TA402 TA403
TA404
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
APRIL 30, 2028
SIGNATURE EXPIRATION DATE OF LICENSE
Expires:
11/30/2027
Patrick Durham #404250
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
P A
C
IF
IC
M
A K
A L A
P A
H
A W
A
II
AS NOTED
/1
/2
:1 :1
P
M
A u to d e s k D o c s /J
-8
B S
T F
/B L
D G
-J
-1
-T A
.r v t
TA002
JF
Y
P
R O
JE
C
T J
-8
A V
S Y
S
TE
M S
S Y
M B
O
LS
, L E
G E
N D
, A N
D A
B B
R E
V
IA
TI
O
N S
PKD
17322327
PKD DHC
3/10/2026
NATHANIEL PYRON, MILCON
PLANNER, DPPH
B A
TT
LE
S
TA
FF
T
R A
IN
IN
G F
A C
IL
IT
Y
DKS/DMK
1696746
N62742-20-D-0001
M C
B C
A M
P B
LA
Z
, G U
A M
U .S
. N A
V S
U P
P A
C T
KYM
KYM
RYO
N A
V F
A C
P A
C
IF
IC
T A
GENERAL DRAWING SYMBOLS
SECTION / CALLOUT VIEW REFERENCE
XX
XX
XX
XX
NUMBER OF DETAIL ON SHEET
NUMBER OF SHEET WHERE DETAIL APPEARS
CENTERLINECL
MATCHLINE WITH VIEW REFERENCE
KEYED NOTEX
REVISION NUMBERX
ROOM NAME AND NUMBER
DOOR TAG - REFERENCE ARCHITECTURAL DOOR SCHEDULE FOR MORE
INFORMATION
ROOM NAME
XXX
XXX NEW
GRAPHICAL REPRESENTATION OF PHASING (TYP FOR ALL SYMBOLS)
XXX GOVERNMENT-FURNISHED OR FUTURE, AS NOTED
RACEWAY SYMBOLS & LINETYPES
CONDUIT, RACEWAY, OR CABLE TRAY CONCEALED IN WALL OR ABOVE CEILING
CONDUIT, RACEWAY, OR CABLE TRAY IN RAF, BELOW FLOOR OR GRADE
CONDUIT STUB OUT WITH NYLON BUSHINGS
CONDUIT RISER UP/DOWN
HOMERUN CONDUIT
(XX) ##
YY
YY = DESTINATION
## = CONDUIT TRADE SIZE
XX = CONDUIT QUANTITY (ONE IF NONE LISTED)
LADDER-STYLE CABLE TRAY
WIRE MESH-STYLE CABLE TRAY
CHANNEL-STYLE CABLE TRAY
FIRE-RATED PATHWAY DEVICE
X#
NOTES:
F = FIRE-RATED PATHWAY
S = SMOKE & ACOUSTICAL PATHWAY
# = NUMBER OF PATHWAY DEVICES
AV SYSTEMS SYMBOLS
AV ROOM CLASSIFICATION "DIGITAL SIGN" DISPLAY - WALL (GFGI)
AV RECESSED FLOOR OUTLET BOX (CFCI / MILCON)
FLAT PANEL VIDEO MONITOR FOR LOCAL PRESENTATION / CONFERENCING
ACTIVITIES AND CABLE TV FEED (BY AV CEQ VENDOR)
"xx" INDICATES DIAGONAL SCREEN SIZE
FBx
VIDEO CONFERENCING (VTC) CAMERA (GFGI)
LOUDSPEAKER - RECESSED OR SURFACE-MOUNTED (GFGI)Sx
AV-EQUIPPED FURNITURE (BY AV CEQ VENDOR)
AV EQUIPMENT RACK/CABINET (CFCI/MILCON)
XX
XX
RCx
FP2-xx
VCx
AV SYSTEMS ABBREVIATIONS
MATCHLINE
XX / XX
# POUNDS (SAME AS "LB" AND "LBS")
A AMPERE
ABA ARCHITECTURAL BARRIERS ACT
AC ABOVE COUNTER
ADA AMERICANS WITH DISABILITIES ACT
ADDL ADDITIONAL
ADJ ADJUSTABLE
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
ALS ASSISTIVE LISTENING SYSTEM
ALT ALTERNATE
AMP AMPLIFIER
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
ANT ANTENNA
APPROX APPROXIMATE, APPROXIMATELY
ARCH ARCHITECTURAL
ATC AUDIO TELECONFERENCING
AUX AUXILIARY
AV AUDIO-VIDEO, AUDIO-VISUAL, AUDIOVISUAL
AVC AUDIO-VIDEO SYSTEMS CONTRACTOR
AVOIP AUDIO-VIDEO OVER INTERNET PROTOCOL
AWG AMERICAN WIRE GAUGE
BB BACK BOX
BC BONDING CONDUCTOR
BET BUILDING ENTRANCE TERMINAL
BFC BELOW FINISHED CEILING
BLDG BUILDING
C CONDUIT
C4I/IT COMMAND, CONTROL, COMMUNICATIONS, COMPUTERS AND INFORMATION TECHNOLOGY
CAB EQUIPMENT CABINET
CAM CAMERA
CAT CATEGORY (TWISTED PAIR CABLING)
CATV COMMUNITY ACCESS TELEVISION OR CABLE TELEVISION
CC CONTACT CLOSURE
CEQ COLLATERAL EQUIPMENT
CFCI CONTRACTOR-FURNISHED, CONTRACTOR-INSTALLED
CH CHANNEL
CID COMPREHENSIVE INTERIOR DESIGN
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CLK CLOCK
CM COMMUNICATIONS MULTIPURPOSE (CABLE)
CMP COMMUNICATIONS PLENUM RATED (CABLE)
CMR COMMUNICATIONS RISER RATED (CABLE)
CO CONTRACTING OFFICER
COAX COAXIAL
COC COMMAND OPERATIONS CENTER
CODEC ENCODER / DECODER
COMM COMMUNICATIONS
CONF CONFERENCE
CONT'D CONTINUED
CP CONTROL PANEL
CPU CENTRAL PROCESSING UNIT
CT CABLE TRAY
CTR COMMERCIAL TELECOMMUNICATIONS ROOM
CTRL CONTROL
DB DECIBEL
DED DEDICATED
DEG DEGREES
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPLAY
DIST DISTRIBUTION
DOR DESIGNER OF RECORD
DSP DIGITAL SIGNAL PROCESSOR
DWG DRAWING
EA EACH
EC ELECTRICAL CONTRACTOR
EGC EQUIPMENT GROUNDING CONDUCTOR
ELEC, ELECT ELECTRICAL
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
ENT ELECTRICAL NON-METALLIC TUBING
EPTZ ELECTRONIC PAN-TILT-ZOOM
EQ EQUAL, EQUIVALENT
EQUIP EQUIPMENT
ER EQUIPMENT RACK
ESS ELECTRONIC SECURITY SYSTEM(S)
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FB FLOOR BOX
FC FERRULE CONNECTOR (FIBER-OPTIC TERMINATION)
FF FINISHED FLOOR
FF&E FURNITURE, FIXTURES & EQUIPMENT
FIXT FIXTURE
FLR FLOOR
FMC FLEXIBLE METAL CONDUIT
FO FIBER OPTIC
FP FLAT PANEL VIDEO MONITOR
FPS FRAMES PER SECOND
FT FOOT, FEET
FTP FOILED TWISTED PAIR CABLE
G, GND GROUND
GALV GALVANIZED
GC GENERAL CONTRACTOR
GFCI GOVERNMENT FURNISHED, CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED, GOVERNMENT INSTALLED
GOVT GOVERNMENT
GRC GALVANIZED RIGID CONDUIT (A TYPE OF "RMC")
GTR GOVERNMENT TELECOMMUNICATIONS ROOM
GYP GYPSUM
HDBT HDBASET
HDMI HIGH-DEFINITION MULTIMEDIA INTERFACE
HDPE HIGH-DENSITY POLYETHYLENE CONDUIT
HDR HIGH DYNAMIC RANGE
HF HIGH FREQUENCY
HH HAND HOLE (IN-GRADE PULL BOX)
HORIZ HORIZONTAL
HZ HERTZ
I/O INPUT / OUTPUT
IBC INTERNATIONAL BUILDING CODE
IC INTERCOM
ICT INFORMATION AND COMMUNICATIONS TECHNOLOGY
ID INSIDE DIAMETER
IDF INTERMEDIATE DISTRIBUTION FRAME
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IN INCH, INCHES
INCL INCLUDE, INCLUDED
IP INTERNET PROTOCOL
IR INFRARED
IT INFORMATION TECHNOLOGY
J, JB, J-BOX JUNCTION BOX
KO KNOCK-OUT
KP KEYPAD
KTR CONTRACTOR
KVM KEYBOARD-VIDEO-MOUSE
KYBD KEYBOARD
LAN LOCAL AREA NETWORK
LB, LBS POUNDS (SAME AS "#")
LC LATCHING CONNECTOR (FIBER OPTIC TERMINATION)
LCD LIQUID CRYSTAL DISPLAY
LCR LEFT/CENTER/RIGHT AUDIO
LED LIGHT EMITTING DIODE
LF LOW FREQUENCY
LFMC LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT
LFNC LIQUID-TIGHT FLEXIBLE NON-METALLIC CONDUIT
LR LEFT/RIGHT (STEREO) AUDIO
LT LIQUID TIGHT
LTG LIGHTING
LV LOW-VOLTAGE
MAX MAXIMUM
MDF MAIN DISTRIBUTION FRAME
MECH MECHANICAL
MFR MANUFACTURER
MIC MICROPHONE
MILCON MILITARY CONSTRUCTION
MIN MINIMUM
MISC MISCELLANEOUS
MM MULTIMODE (OPTICAL FIBER)
MNS MASS NOTIFICATION SYSTEM
MOD MODIFIED
MON MONITOR
MTC MULTI-TIME ZONE CLOCK
MTD MOUNTED
MTG MOUNTING
NAVFAC NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OSP OUTSIDE PLANT
PA PUBLIC ADDRESS
PB PULL BOX
PBB PRIMARY BONDING BUSBAR
PC PERSONAL COMPUTER
PDU POWER DISTRIBUTION UNIT
PJ, PROJ PROJECTOR
PLYWD PLYWOOD
PNL PANEL
POE POWER OVER ETHERNET
PR PAIR
PS PROJECTION SCREEN
PTZ PAN-TILT-ZOOM
PVC POLYVINYL CHLORIDE
PWR POWER
QTY QUANTITY
RAF RAISED ACCESS FLOORING
RBB RACK BONDING BUSBAR
RBC RACK BONDING CONDUCTOR
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
RE, REF REFER (TO) OR REFERENCE
REQ REQUIRED
RF RADIO FREQUENCY
RGB RED-GREEN-BLUE
RIO ROUGH-IN ONLY
RM ROOM
RMC RIGID METAL CONDUIT
RSD ROOM STATUS DISPLAY / INDICATOR LIGHT
RU RACK UNIT(S)
RX RECEIVER
S, SPKR SPEAKER, LOUDSPEAKER
SBB SECONDARY BONDING BUSBAR
SC SUBSCRIBER CONNECTOR (FIBER-OPTIC TERMINATION)
SCC STRUCTURED CABLING CONTRACTOR
SCHED SCHEDULE
SCRN SCREEN
SCS STRUCTURED CABLING SYSTEM
SFP SMALL FORM-FACTOR PLUGGABLE
SIM SIMILAR
SM SINGLEMODE (OPTICAL FIBER)
SPD SURGE PROTECTIVE DEVICE
SPECS SPECIFICATIONS
SPL SOUND PRESSURE LEVEL
SS SPECIAL SYSTEMS
SST STAINLESS STEEL
ST STRAIGHT TERMINUS CONNECTOR (FIBER OPTIC TERMINATION)
STD STANDARD
STP SHIELDED TWISTED PAIR CABLE
STR STRAND
STRUCT STRUCTURAL
TA TRAINING AUDIENCE
TBB TELECOM BONDING BACKBONE
TBC TELECOM BONDING CONDUCTOR
TBD TO BE DETERMINED
TCP/IP TRANSMISSION CONTROL PROTOCOL / INTERNET PROTOCOL
TELECOM TELECOMMUNICATIONS
TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION
TP TOUCH PANEL
TR TELECOMMUNICATIONS ROOM
TV TELEVISION
TX TRANSMITTER
TYP TYPICAL
UC UNDER COUNTER
UFC UNIFIED FACILITIES CRITERIA
UG UNDERGROUND
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
USB UNIVERSAL SERIAL BUS
UTP UNSHIELDED TWISTED PAIR CABLE
V VOLT(S)
VA VOLT-AMP(S)
VAC VOLTS ALTERNATING CURRENT
VC VIDEO CAMERA
VCD VOLUME CONTROL (VOLUME ATTENUATOR) DEVICE
VDC VOLTS DIRECT CURRENT
VERT VERTICAL
VIF VERIFY IN FIELD
VOIP VOICE OVER INTERNET PROTOCOL
VOL VOLUME
VR VANDAL RESISTANT
VTC VIDEO TELECONFERENCING
W WATT(S)
WL WIRELESS
WP WEATHERPROOF
XCVR TRANSCEIVER
FLAT PANEL VIDEO MONITOR FOR LOCAL PRESENTATION / CONFERENCING
ACTIVITIES (BY AV CEQ VENDOR)
"xx" INDICATES DIAGONAL SCREEN SIZE
FP1-xx
FLAT PANEL VIDEO MONITOR FOR CABLE TV FEED ONLY
(BY AV CEQ VENDOR)
"xx" INDICATES DIAGONAL SCREEN SIZE
FP3-xx
FLAT PANEL VIDEO MONITOR (GFGI)
FP0-xx
AV PULL BOX - CEILING (CFCI / MILCON)Jx
AV JUNCTION BOX FOR WALL DEVICE / WALL PLATE (CFCI / MILCON)Jx
MICROPHONE - CEILING (GFGI)Mx
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
APRIL 30, 2028
SIGNATURE EXPIRATION DATE OF LICENSE
Expires:
11/30/2027
A
B
C
D
E
F
G
TA103
A1
TA102
A1
1 2 3 4 5 6 7 8 9
TA - G4 LOGISTICS
TA - G7 COMM
STRAT
TA - G3 FOPS
105B
TA - G3 FOPS
105A
TA - G2
COLLECTIONS
AND ANALYSIS
108A
TA - HQ CAMP
COMMANDANT
TA - G3 FIRES
TA - G3 STRIKE
CELL
110A
TA - G3 STRIKE
CELL
110B
INTERIOR COC
TRAINING PAD
TA - G2
COLLECTIONS
AND ANALYSIS
108B
GTR 1T (TRAINING
TELECOMM RM)
GTR 1
SVTC CONF RM /
SIPR CAFE
MECH RM
ELEC RM
TA - MEDICAL
CELL
TA - COC WATCH
FLOOR
TA - G5 PLANS
TA - COMMAND
DECK
TA - G1
OPERATIONS
LOBBY 1
L1
ENTRY VESTIBULE
CTR 1
ELEV MACHINE RM
ELEV 1
E1
NURSING RM
BREAK RM
ENTRY CONTROL
POINT
102A
CORRIDOR 1C
C1C
VESTIBULE 1A
V1A
VESTIBULE 1C
V1C
VESTIBULE 1D
V1D
CORRIDOR 1A
C1A
ELEC CLOSET
CORRIDOR 1B
C1B
WOMEN
MEN
JAN
CORRIDOR 1E
C1E
OFFICE
128B
OFFICE
128A
OFFICE
127B
OFFICE
127A
OFFICE
126B
OFFICE
126A
VESTIBULE 1E
V1E
TELCOM CLOSET
126C
AV CLOSET
126D
STAIR 1C
S1C
STAIR 1B
S1B
STAIR 1A
S1A
OFFICE
125A
TRAINING
MATERIAL
STORAGE
EMERGENCY
GENERATOR
TA105
A1
TA104
A1
1. REFER TO TA001 & TA002 FOR AV REQUIREMENTS AND SYMBOLS SHOWN ON THESE DRAWINGS. WORK MUST BE
PERFORMED IN COMPLIANCE WITH DIVISION 27 SPECIFICATIONS.
2. NOT ALL ARCHITECTURAL, TELECOM AND ELECTRICAL ELEMENTS HAVE BEEN INCLUDED ON THE DRAWINGS, CONTRACTOR MUST REFER TO THOSE RESPECTIVE DISCIPLINES' SHEETS FOR ADDITIONAL BUILDING-MOUNTED ELEMENTS AND SCOPE OF WORK THAT MAY INTERFACE WITH, OR IMPACT, THE AV SCOPE OF WORK.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
P A
C
IF
IC
M
A K
A L A
P A
H
A W
A
II
AS NOTED
/1
/2
:1 :1
P
M
A u to d e s k D o c s /J
-8
B S
T F
/B L
D G
-J
-1
-T A
.r v t
TA101
JF
Y
P
R O
JE
C
T J
-8
O V
E R
A
LL
A V
F
IR
S T
F
LO
O R
P
LA
N
PKD
17322328
PKD DHC
3/10/2026
NATHANIEL PYRON, MILCON
PLANNER, DPPH
B A
TT
LE
S
TA
FF
T
R A
IN
IN
G F
A C
IL
IT
Y
DKS/DMK
1696746
N62742-20-D-0001
M C
B C
A M
P B
LA
Z
, G U
A M
U .S
. N A
V S
U P
P A
C T
KYM
KYM
RYO
N A
V F
A C
P A
C
IF
IC
T A
PLAN
NORTH
1/16" = 1' - 0" 0 5' 10' 20' 30' 60'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEY PLAN
1/16" = 1'-0"
OVERALL AV SYSTEMS FIRST FLOOR PLAN
A1
AREA A AREA B
M A
T C
H
LI
N E
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
APRIL 30, 2028
SIGNATURE EXPIRATION DATE OF LICENSE
Expires:
11/30/2027
J1
FP3-55
FP
2-
J1
FP2-75
FP1-98
J2
J1
J1
J1 J1
J1 J1
J1 J1
J1
MTCMTC
M
TC
M
TC
M
TC
M
TC
MTC
M
TC
M
TC
A
B
C
D
E
F
G
TA401
TA405
A1
TA405
A3
RCP
C1
MATCHLIN
E
TA103
MATCHLINE
TA103
TA402 C1
TA401
TA401
B1
B2
TA401
D3
TA402A1
TA401
C3
TA402 B1
TA401 A1
1 2 3 4 5 6
TA401 B3
C2
AV SYSTEM
TYPE B
AV SYSTEM
TYPE C-3
AV SYSTEM
TYPE A-2
AV SYSTEM
TYPE A-1
AV SYSTEM
TYPE C-1
AV SYSTEM
TYPE C-1
AV SYSTEM
TYPE C-1
AV SYSTEM TYPE D
A V
S Y
S T
E M
T Y
P E
D
A V
S Y
S T
E M
T Y
P E
D
TA401 D1
TA - G4 LOGISTICS
TA - G7 COMM
STRAT
TA - HQ CAMP
COMMANDANT
ENTRY CONTROL
POINT
102A
ENTRY VESTIBULE
LOBBY 1
L1
BREAK RM
NURSING RM
ELEC CLOSET
TA - G3 FIRES
TA - G3 STRIKE
CELL
110A
TA - G3 STRIKE
CELL
110B
CORRIDOR 1C
C1C
TA - G2
COLLECTIONS
AND ANALYSIS
108A
TA - G2
COLLECTIONS
AND ANALYSIS
108B
INTERIOR COC
TRAINING PAD
TA - G3 FOPS
105B
TA - G3 FOPS
105A
SVTC CONF RM /
SIPR CAFE
GTR 1
GTR 1T (TRAINING
TELECOMM RM)
CTR 1
ELEV MACHINE RM
ELEV 1
E1
VESTIBULE 1D
V1D
VESTIBULE 1A
V1A
STAIR 1B
S1B
CORRIDOR 1B
C1B
CORRIDOR 1A
C1A
CORRIDOR 1D
C1D
MECH RM
EQ EQ
11' - 5"
11' - 6" 11' - 6"
9' - 4"
TO FP2-75 IN
LOBBY 1
4' - 6"
(A V
-4
(AV-6)
(AV-3)
(AV-4)
(A V
-3
(AV-3)(AV-3)
(AV-3)
(A V
-3
(A V
-3
(A V
-3
(A V
-3
(A V
-3
FP1-98FP1-98
FP
1-
FP1-98
FP
1-
FP
1-
FP
1-
FP
1-
FP
1-
1. REFER TO TA001 & TA002 FOR AV REQUIREMENTS AND SYMBOLS SHOWN ON THESE DRAWINGS. WORK MUST BE
PERFORMED IN COMPLIANCE WITH DIVISION 27 SPECIFICATIONS.
2. NOT ALL ARCHITECTURAL, TELECOM AND ELECTRICAL ELEMENTS HAVE BEEN INCLUDED ON THE DRAWINGS, CONTRACTOR MUST REFER TO THOSE RESPECTIVE DISCIPLINES' SHEETS FOR ADDITIONAL BUILDING-MOUNTED ELEMENTS AND SCOPE OF WORK THAT MAY INTERFACE WITH, OR IMPACT, THE AV SCOPE OF WORK.
3. CONDUIT RACEWAYS SHOWN ON PLAN AND RCP VIEWS ARE ONLY SHOWN IF A SPECIFIC ROUTE IS REQUIRED.
REFER TO PATHWAY RISER DIAGRAMS FOR CONDUIT RACEWAY REQUIREMENTS. COORDINATE ROUTING AND ROOM ENTRY LOCATIONS FOR AV SYSTEMS CONDUIT AND PATHWAYS DURING SHOP DRAWING PROCESS.
4. VERIFY AND COORDINATE WALL SPACE REQUIREMENTS WITH OTHER TRADES DURING SHOP DRAWING
PROCESS TO CONFIRM FINAL PLACEMENT OF AV ROUGH-IN’S AND EQUIPMENT.
5. VERIFY EQUIPMENT ROUGH-IN DIMENSIONS WITH VENDOR/INSTALLER.
6. REFER TO I-SERIES (INTERIOR DESIGN) DRAWINGS FOR FINAL DIMENSIONS OF:
a. HORIZONTAL MOUNTING OF WALL-MOUNTED AV-EQUIPMENT
b. POSITIONING OF AV-RELATED FURNITURE/FURNISHINGS. FOR AV EQUIPMENT CABINETS, REFER TO
DIMENSIONS ON THE TA-SERIES DRAWINGS.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
P A
C
IF
IC
M
A K
A L A
P A
H
A W
A
II
AS NOTED
/1
/2
:1 :1
P
M
A u to d e s k D o c s /J
-8
B S
T F
/B L
D G
-J
-1
-T A
.r v t
TA102
JF
Y
P
R O
JE
C
T J
-8
P A
R
TI
A L
A V
F
IR
S T
F
LO
O R
P
LA
N
A
PKD
17322329
PKD DHC
3/10/2026
NATHANIEL PYRON, MILCON
PLANNER, DPPH
B A
TT
LE
S
TA
FF
T
R A
IN
IN
G F
A C
IL
IT
Y
DKS/DMK
1696746
N62742-20-D-0001
M C
B C
A M
P B
LA
Z
, G U
A M
U .S
. N A
V S
U P
P A
C T
KYM
KYM
RYO
N A
V F
A C
P A
C
IF
IC
T A
1/8" = 1'-0"
AV SYSTEMS FIRST FLOOR PLAN - A
A1
AREA A AREA B
M A
T C
H
LI
N E
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEY PLAN
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
APRIL 30, 2028
SIGNATURE EXPIRATION DATE OF LICENSE
Expires:
11/30/2027
M
TC
A
B
C
D
E
F
G
TA408
A1
TA409
A1
RCP
MATCHLIN
E
TA102
MATCHLINE
TA102
5 6 7 8 9
AV SYSTEM
TYPE C-1
TA402 C3
ENTRY VESTIBULE
LOBBY 1
L1
CTR 1
ELEV MACHINE RM
ELEV 1
E1
CORRIDOR 1D
C1D
TA - COC WATCH
FLOOR
VESTIBULE 1E
V1E
OFFICE
126A
OFFICE
126B
OFFICE
127B
OFFICE
127A
OFFICE
128A
OFFICE
128B
TA - G1
OPERATIONS
TA - COMMAND
DECK
TA - G5 PLANS
STAIR 1A
S1A
MECH RM
ELEC RM
MEN
JAN
WOMEN
OFFICE
125A
TA - MEDICAL
CELL
TELCOM CLOSET
126C
AV CLOSET
126D
STAIR 1C
S1C
CORRIDOR 1E
C1E
TELCOM CLOSET
128C
TRAINING
MATERIAL
STORAGE
EMERGENCY
GENERATOR
(A V
-3
FP
1-
1. REFER TO TA001 & TA002 FOR AV REQUIREMENTS AND SYMBOLS SHOWN ON THESE DRAWINGS. WORK MUST BE
PERFORMED IN COMPLIANCE WITH DIVISION 27 SPECIFICATIONS.
2. NOT ALL ARCHITECTURAL, TELECOM AND ELECTRICAL ELEMENTS HAVE BEEN INCLUDED ON THE DRAWINGS, CONTRACTOR MUST REFER TO THOSE RESPECTIVE DISCIPLINES' SHEETS FOR ADDITIONAL BUILDING-MOUNTED ELEMENTS AND SCOPE OF WORK THAT MAY INTERFACE WITH, OR IMPACT, THE AV SCOPE OF WORK.
3. CONDUIT RACEWAYS SHOWN ON PLAN AND RCP VIEWS ARE ONLY SHOWN IF A SPECIFIC ROUTE IS REQUIRED.
REFER TO PATHWAY RISER DIAGRAMS FOR CONDUIT RACEWAY REQUIREMENTS. COORDINATE ROUTING AND ROOM ENTRY LOCATIONS FOR AV SYSTEMS CONDUIT AND PATHWAYS DURING SHOP DRAWING PROCESS.
4. VERIFY AND COORDINATE WALL SPACE REQUIREMENTS WITH OTHER TRADES DURING SHOP DRAWING
PROCESS TO CONFIRM FINAL PLACEMENT OF AV ROUGH-IN’S AND EQUIPMENT.
5. VERIFY EQUIPMENT ROUGH-IN DIMENSIONS WITH VENDOR/INSTALLER.
6. REFER TO I-SERIES (INTERIOR DESIGN) DRAWINGS FOR FINAL DIMENSIONS OF:
a. HORIZONTAL MOUNTING OF WALL-MOUNTED AV-EQUIPMENT
b. POSITIONING OF AV-RELATED FURNITURE/FURNISHINGS. FOR AV EQUIPMENT CABINETS, REFER TO
DIMENSIONS ON THE TA-SERIES DRAWINGS.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D
P A
C
IF
IC
M
A K
A L A
P A
H
A W
A
II
AS NOTED
/1
/2
:1 :1
P
M
A u to d e s k D o c s /J
-8
B S
T F
/B L
D G
-J
-1
-T A
.r v t
TA103
JF
Y
P
R O
JE
C
T J
-8
P A
R
TI
A L
A V
F
IR
S T
F
LO
O R
P
LA
N
B
PKD
17322330
PKD DHC
3/10/2026
NATHANIEL PYRON, MILCON
PLANNER, DPPH
B A
TT
LE
S
TA
FF
T
R A
IN
IN
G F
A C
IL
IT
Y
DKS/DMK
1696746
N62742-20-D-0001
M C
B C
A M
P B
LA
Z
, G U
A M
U .S
. N A
V S
U P
P A
C T
KYM
KYM
RYO
N A
V F
A C
P A
C
IF
IC
T A
1/8" = 1'-0"
AV SYSTEMS FIRST FLOOR PLAN - B
A1
AREA A AREA B
M A
T C
H
LI
N E
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEY PLAN
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
APRIL 30, 2028
SIGNATURE EXPIRATION DATE OF LICENSE
Expires:
11/30/2027
C
D
E
F
G
1 2 3 4 5 6
TA - G4 LOGISTICS
TA - G7 COMM
STRAT
TA - HQ CAMP
COMMANDANT
ENTRY CONTROL
POINT
102A
ENTRY VESTIBULE
LOBBY 1
L1
BREAK RM
NURSING RM
ELEC CLOSET
TA - G3 FIRES
TA - G3 STRIKE
CELL
110A
TA - G3 STRIKE
CELL
110B
CORRIDOR 1C
C1C
TA - G2
COLLECTIONS
AND ANALYSIS
108A
TA - G2
COLLECTIONS
AND ANALYSIS
108B
INTERIOR COC
TRAINING PAD
TA - G3 FOPS
105B
TA - G3 FOPS
105A
SVTC CONF RM /
SIPR CAFE
GTR 1
GTR 1T (TRAINING
TELECOMM RM)
CTR 1
ELEV MACHINE RM
ELEV 1
E1
VESTIBULE 1D
V1D
VESTIBULE 1A
V1A
STAIR 1B
S1B
CORRIDOR 1B
C1B
CORRIDOR 1A
C1A
CORRIDOR 1D
C1D
OFFICE
128B
MECH RM
4"x2" WIRE
MESH CABLE
TRAY
4"x2" WIRE
MESH CABLE
TRAY
4"x2" WIRE
MESH CABLE
TRAY
4"x2" WIRE
MESH CABLE
TRAY
4"x2" WIRE
MESH CABLE
TRAY
4"x2" WIRE
MESH CABLE
TRAY
4"x2" WIRE
MESH CABLE
TRAY
4"x2" WIRE
MESH CABLE
TRAY
4"x2" WIRE
MESH CABLE
TRAY
MATCHLIN
E
TA105
MATCHLINE
TA105
1. REFER TO TA001 & TA002 FOR AV REQUIREMENTS AND SYMBOLS SHOWN ON THESE DRAWINGS. WORK MUST BE
PERFORMED IN COMPLIANCE WITH DIVISION 27 SPECIFICATIONS.
2. NOT ALL ARCHITECTURAL, TELECOM AND ELECTRICAL ELEMENTS HAVE BEEN INCLUDED ON THE DRAWINGS, CONTRACTOR MUST REFER TO THOSE RESPECTIVE DISCIPLINES' SHEETS FOR ADDITIONAL BUILDING-MOUNTED ELEMENTS AND SCOPE OF WORK THAT MAY INTERFACE WITH, OR IMPACT, THE AV SCOPE OF WORK.
3. CONDUIT RACEWAYS SHOWN ON PLAN AND RCP VIEWS ARE ONLY SHOWN IF A SPECIFIC ROUTE IS REQUIRED.
REFER TO PATHWAY RISER DIAGRAMS FOR CONDUIT RACEWAY REQUIREMENTS. COORDINATE ROUTING AND ROOM ENTRY LOCATIONS FOR AV SYSTEMS CONDUIT AND PATHWAYS DURING SHOP DRAWING PROCESS.
4. VERIFY AND COORDINATE WALL SPACE REQUIREMENTS WITH OTHER TRADES DURING SHOP DRAWING
PROCESS TO CONFIRM FINAL PLACEMENT OF AV ROUGH-IN’S AND EQUIPMENT.
5. VERIFY EQUIPMENT ROUGH-IN DIMENSIONS WITH VENDOR/INSTALLER.
6. REFER TO I-SERIES (INTERIOR DESIGN) DRAWINGS FOR FINAL DIMENSIONS OF:
a. HORIZONTAL MOUNTING OF WALL-MOUNTED AV-EQUIPMENT
b. POSITIONING OF AV-RELATED FURNITURE/FURNISHINGS. FOR AV EQUIPMENT CABINETS, REFER TO
DIMENSIONS ON THE TA-SERIES DRAWINGS.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M…