This is a specification section for temporary facilities and controls required during construction operations (Section 01 50 00 from contract DEVA-318717). The section establishes comprehensive requirements for temporary utilities, support facilities, and security and protection measures that contractors must provide throughout the construction period.
The contractor must provide temporary toilets segregated by gender in weatherproof, sight-proof, handicap-accessible enclosures maintained weekly and completely removed upon project completion. A separate Contracting Officer (CO) Field Office is required as a prefabricated, job-built, or mobile structure of minimum 80 square feet in excellent condition with air conditioning, heating, operable windows, security screens, paneling or painted walls, resilient flooring, exterior door with dead bolt keyed from outside, 20-square-foot landing and steps, broadband access, and phone connection. Temporary utilities must include non-potable water from campus hydrants (no trucking potable water required), SCE temporary power drop or generator of sufficient capacity, temporary lighting with local switching, and satellite communication for contractor crews. Support facilities must use incombustible construction within 50 feet of building lines per NFPA 241. The contractor must install orange plastic safety barrier fencing (minimum 4 feet height), portable UL-rated fire extinguishers (one per 1,500 square feet with 75-foot maximum travel distance to nearest extinguisher), and temporary fire protection compliant with NFPA 241 including a designated fire protection responsible person. Additional requirements include traffic control per MUTCD standards, dust control treatment, equipment cleaning to prevent exotic species introduction, erosion and sedimentation control, historic and cultural resource protection including historic utility tunnel preservation, environmental protection measures, and parking in designated areas. All temporary facilities must be removed at Substantial Completion, with permanent facilities cleaned and renovated for occupancy.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEVA – 318717 01 50 00 - 1
TEMPORARY FACILITIES AND CONTROLS
SECTION 01 50 00 - TEMPORARY FACILITIES AND CONTROLS
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes requirements for temporary utilities, support facilities, and security and protection facilities.
1.2 USE CHARGES
A. General: Cost or use charges for temporary facilities shall be included in the Contract Sum as required.
1.3 QUALITY ASSURANCE
A. Electric Service: Comply with NECA, NEMA, and UL standards and regulations for temporary electric service. Install service to comply with NFPA 70.
B. Environmental Protection: Provide environmental protection as required by agency(ies) with jurisdiction and as indicated in the Contract Documents. Coordinate with requirements of the following:
1. Regulatory Requirements.
2. Noise & Acoustics Management.
3. Environmental Management.
4. Construction Waste Management.
1.4 PROJECT CONDITIONS
A. Temporary Use of Permanent Facilities: Installer of each permanent service shall assume responsibility for operation, maintenance, and protection of each permanent service during its use as a construction facility before NPS acceptance, regardless of previously assigned responsibilities.
PART 2 - PRODUCTS
2.1 MATERIALS
A. Temporary materials may be new or used, but must be adequate in capacity for the required usage, must not create unsafe conditions, and must not violate requirements of applicable codes and standards.
B. Safety Barrier Fence: Orange plastic fence, minimum height, 4 feet.
DEVA – 318717 01 50 00 - 2
2.2 TEMPORARY FACILITIES
A. Toilets: Sufficiently lighted and ventilated toilet facilities in weatherproof, sight proof, handicap accessible, sturdy enclosures with privacy locks.
1. Provide separate toilet facilities for men and women.
B. The Construction Contractor shall provide the Contracting Officer’s (CO) Field Office in accordance with the following, as a separate structure from the Construction Contractor's Field
Office.
1. Prefabricated, job-built, or a mobile unit; excellent condition, structurally sound, nonflammable exterior construction, weather tight, minimum 80 square feet.
2. Operable windows and security screens, adjustable ventilation.
3. Air conditioner and heater.
4. Paneling or freshly painted walls, acoustical tile or painted ceilings, and resilient flooring.
5. Minimum of one exterior door with dead bolt keyed from outside,
6. Minimum 20-square-foot landing and steps at exterior door(s).
7. Broadband access (no internet service) and phone connection.
C. The CO Field Office shall be located within the vicinity of the Construction Contractor’s Field
Office and Admin Camp, if applicable, and contractor-provided restroom facilities.
2.3 EQUIPMENT
A. Fire Extinguishers: Portable, UL rated; with class and extinguishing agent as required by locations and classes of fire exposures.
PART 3 - EXECUTION
3.1 INSTALLATION, GENERAL
A. Locate facilities where they will serve Project adequately and result in minimum interference with performance of the Work. Relocate and modify facilities as required by progress of the Work.
B. Provide each facility ready for use when needed to avoid delay. Do not remove until facilities are no longer needed or are replaced by authorized use of completed permanent facilities.
3.2 TEMPORARY UTILITY INSTALLATION
A. General: Install temporary service or connect to existing service.
1. Arrange with NPS, and existing users for time when service can be interrupted, if necessary, to make connections for temporary services. Acquire all necessary permits.
B. Non-potable water for construction is available from various hydrant locations on the campus, coordinate with the Contracting Officer. Install piping and connections as required. There will be no need to truck potable water to the site.
DEVA – 318717 01 50 00 - 3
C. Sanitary Facilities: Provide temporary toilets, and wash facilities for use by construction personnel.
1. Place in approved locations secluded from public observation and convenient to work stations. Relocate as work progress requires.
2. Maintain and clean toilet facilities at least weekly.
3. Completely remove sanitary facilities on completion of work.
D. Electric Power Service: Provide SCE temporary power drop or generator of sufficient size, capacity, and power characteristics required for construction operations.
E. Lighting: Provide temporary lighting with local switching that provides adequate illumination for construction operations, observations, inspections, and traffic conditions.
1. Install and operate temporary lighting that fulfills security and protection requirements without operating entire system.
F. Telephone Service: No telephone service is available on site for Contractor's use. Contractor to provide satellite communication for his/her crews.
3.3 SUPPORT FACILITIES INSTALLATION
A. General: Comply with the following:
1. Provide incombustible construction for offices, shops, and sheds located within construction area or within 50 feet of building lines. Comply with NFPA 241.
2. Maintain support facilities until near Substantial Completion. Remove structures, equipment, and furnishings, and terminate services after punch list is 100 percent completed or when directed by Contracting Officer. Personnel remaining after Substantial
Completion will be permitted to use permanent facilities, under conditions acceptable to
Contracting Officer.
3. Provide dust-control treatment that is nonpolluting and non-tracking. Reapply treatment as required to minimize dust.
B. Traffic Controls: Erect and maintain barricades, lights, danger signals, and warning signs in accordance with Manual on Uniform Traffic Control Devices (MUTCD), Part IV, latest edition.
1. Protect existing site improvements to remain including curbs, pavement, and utilities.
2. Maintain access for fire-fighting equipment and access to fire hydrants.
3. Illuminate barricades and obstructions at night; keep safety lights burning from sunset to sunrise.
4. Adequately barricade and post open cuts in or adjacent to thoroughfares.
5. Protect pedestrian traffic by guardrails or fences.
6. When pedestrian traffic is detoured onto a roadway, provide temporary walkways with protection as required at ends and overhead. For walkways, use lumber running parallel to direction of traffic movement and provide ramps at changes of elevation.
7. Cover pipes, hoses, and power lines crossing sidewalks and walkways with troughs using beveled edge boards.
DEVA – 318717 01 50 00 - 4
8. Install Barrier Tape where directed by Contracting Officer. Keep a minimum of two rolls on site at all times
C. Parking: Use designated areas of existing parking areas for construction personnel.
D. Waste Disposal Facilities: Provide waste-collection containers in sizes adequate to handle waste from construction operations. Comply with requirements of agency(ies) with jurisdiction.
3.4 SECURITY AND PROTECTION FACILITIES INSTALLATION
A. Environmental Protection: Provide protection, operate temporary facilities, and conduct construction in ways and by methods that comply with environmental regulations and that minimize possible air, waterway, and subsoil contamination or pollution or other undesirable effects.
B. Historic and Cultural Resource Protection: Conduct construction in ways and by methods that will ensure protection of the existing cultural landscape and historic features of the site, including the existing historic utility tunnels. Refer to Section 01 11 00 "Summary of Work".
C. Cleaning of Equipment: The Contractor shall ensure that prior to moving on to the Project Area, all equipment, is free of soil, seeds, vegetative matter, or other debris that could contain or hold seeds. Ensure that all equipment has been pressure washed and is free of exotic species prior to start-up of operations and moving of equipment to Project Area. Equipment shall be considered free of soil, seeds, and other debris when a visual inspection does not disclose such material.
Disassembly of equipment components or specialized inspection tools are not required.
D. Temporary Erosion and Sedimentation Control: Refer to Section 01 57 23 “Temporary Storm
Water Pollution Prevention”.
E. Tree and Plant Protection: Refer to Section 01 11 00 “Summary of Work”.
F. Site Enclosure Fence: Before construction operations begin, furnish and install orange plastic fence in a manner that will prevent people and animals from easily entering site except by entrance gates.
G. Temporary Fire Protection: Install and maintain temporary fire-protection facilities of types needed to protect against reasonably predictable and controllable fire losses. Comply with
NFPA 241.
1. Responsible Person: A capable and qualified person shall be placed in charge of fire protection. The responsibilities shall include locating and maintaining fire protective equipment and establishing and maintaining safe torch cutting and welding procedures.
2. Smoking: Smoking within buildings or temporary storage sheds is prohibited.
3. Develop and supervise an overall fire-prevention and -protection program for personnel at
Project site. Review needs with local fire department and establish procedures to be followed. Instruct personnel in methods and procedures. Post warnings and information.
4. Hazard Control: Take all necessary precautions to prevent fire during construction. Do not store flammable or combustible liquids in historic structures. Provide adequate ventilation during use of volatile or noxious substances.
DEVA – 318717 01 50 00 - 5
5. Spark Arresters: Equip all gasoline or diesel powered equipment used during periods of potential fire hazards or in potential forest and grass fire locations with spark arresters approved by the USDA Forest Service.
a. Written determinations of periods and areas of potential fire hazard will be issued by Contracting Officer.
6. Buildings: Furnish a minimum of one extinguisher for each 1,500 square feet of area or major fraction thereof.
a. Travel distance from any work station to the nearest extinguisher shall not exceed
75 feet.
7. Vehicles and Equipment: Provide one extinguisher on each vehicle or piece of equipment.
3.5 OPERATION, TERMINATION, AND REMOVAL
A. Supervision: Enforce strict discipline in use of temporary facilities. To minimize waste and abuse, limit availability of temporary facilities to essential and intended uses.
B. Maintenance: Maintain facilities in good operating condition until removal.
1. Maintain operation of temporary enclosures, heating, cooling, humidity control, ventilation, and similar facilities on a 24-hour basis where required to achieve indicated results and to avoid possibility of damage.
C. Temporary Facility Changeover: Do not change over from using temporary security and protection facilities to permanent facilities until Substantial Completion.
D. Termination and Removal: Remove each temporary facility when need for its service has ended, when it has been replaced by authorized use of a permanent facility, or no later than Substantial
Completion. Complete or, if necessary, restore permanent construction that may have been delayed because of interference with temporary facility. Repair damaged Work, clean exposed surfaces, and replace construction that cannot be satisfactorily repaired.
1. Materials and facilities that constitute temporary facilities are property of Contractor. NPS reserves right to take possession of Project identification signs.
2. At Substantial Completion, clean and renovate permanent facilities used during construction period.
END OF SECTION 01 50 00