This is a technical drawing sheet for water system details associated with the Deva Water and Wastewater System Rehabilitation project at Death Valley National Park. The drawing sheet (C3.15) illustrates four primary water infrastructure details: an air release valve, a curb stop assembly, an individual pressure reducing valve (PRV), and a blowoff valve, along with a typical tree protection detail for construction activities.

The air release valve detail specifies a Val-Matic Model 201C.2 or approved equal, integrated with a 1-inch electrofusion saddle tap on the HDPE water main, mounted to a 4x4 treated wood marker post with stainless steel straps. The curb stop assembly includes a Mueller H-10291 curb stop or approved equal, with a 2-inch Schedule 40 galvanized pipe wrapped in polyethylene plastic, drain pit with gravel, and adjustable cast iron valve box. The individual PRV detail requires a Watts Pressure Reducing Valve or approved salient equal, housed in a 14-inch by 19-inch NDS plastic irrigation box with lockable lid, supplied with 3/4-inch washed gravel base. The blowoff valve detail shows a 2-inch 45-degree bend configuration with drain waste ball valve and associated fittings. Tree protection requirements mandate temporary barriers placed at the drip-line of existing trees, with specifications referencing Project Spec Section 32 01 01, allowing for field adjustment by the Contracting Officer's Representative and contractor responsibility for maintaining perimeter fencing and tree protection throughout construction.

View the file

Other files

File Type Posted
B09_Amd11_-_B08_Attach3_-_WD_CA20260020_Mod2_0011.pdf PDF
Sol_140P2025R0082_Amd_0011.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_42_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_38_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_01-C4_40_Jan2026_0010.pdf PDF
B09_Amd10_QR_Tracker_-_DEVA_318717_Final_0010.xlsx XLSX spreadsheet
B09_Amd10_-_QR55_Attach_Drawing_01-C4_39_Jan2026_0010.pdf PDF
B09_Amd10_-_QR55_Attach_Drawing_00-C8_27_Jan2026_0010.pdf PDF
B09_Amd10_-_QR86_Attach_Drawing_C1_40_0010.pdf PDF
B09_Amd10_-_Drawing_G1_22_0010.pdf PDF
B09_Amd10_-_QR86_Attach_Drawing_C1_40B_0010.pdf PDF
Sol_140P2025R0082_Amd_0010.pdf PDF
B09_Amd10_-_B08_Attach4_-_DetailedContractPriceSchedule_0010.xlsx XLSX spreadsheet
B09_Amd10_-_Drawing_G1_2_0010.pdf PDF
B09_Amd10_-_Drawing_Coversheet_00_DEVA_318717_Jan2026x_0010.pdf PDF
B09_Amd10_-_Drawing_G1_21_0010.pdf PDF
Sol_140P2025R0082_Amd_0009.pdf PDF
B09_Amd8_-_Drawing_02-C5_29_Jan2026_0008.pdf PDF
B09_Amd8_-_Spec_33_14_19_-_VALVES___HYDRANTS_FOR_WATER_UTILITY_SERVICE_0008.pdf PDF
B09_Amd8_-_Drawing_02-G1_16_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_08_33_22_-_ALUMINUM_ROLLING_OVERHEAD_DOORS_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_29_Jan2026_0008.pdf PDF
B09_Amd8_-_QR22_Attach_Drawing_00-C7_1_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C5_25_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_00-C8_30_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_01-C4_42_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_01-C3_1_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_20_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_32_00_-_WASTEWATER_PUMPING_STATIONS_0008.pdf PDF
B09_Amd8_-_Spec_33_31_11_-_GRAVITY_SEWER_PIPELINE___MANHOLE_INSTALLATION_0008.pdf PDF
B09_Amd8_QR_Tracker_-_DEVA_318717_0008.xlsx XLSX spreadsheet
B09_Amd8_-_Drawing_Coversheet_00_DEVA_318717_Jan2026_0008.pdf PDF
Sol_140P2025R0082_Amd_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_31_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C6_7_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_00-G1_2_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-C7_5_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_11_13_-_POTABLE_WATER_SUPPLY_WELLS_0008.pdf PDF
B09_Amd8_-_Drawing_00-C3_18_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_02-C5_33_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_42_Jan2026_0008.pdf PDF
B09_Amd8_-_QR56_Attach_Drawing_02-C2_20_Dec2025_0008.pdf PDF
B09_Amd8_-_Spec_33_31_05_-_MANHOLE_LINING___REHABILITATION_0008.pdf PDF
B09_Amd8_-_Drawing_01-G1_15_Jan2026_0008.pdf PDF
B09_Amd8_-_QR56_Attach_Drawing_02-C2_18_Dec2025_0008.pdf PDF
B09_Amd8_-_Drawing_01-C1_67_Jan2026_0008.pdf PDF
B09_Amd8_-_Spec_46_33_11_-_CHEMICAL_FEED_-_LIQUID_SYSTEMS_0008.pdf PDF
B09_Amd8_-_Drawing_02-C2_22_Jan2026_0008.pdf PDF
B09_Amd8_-_Drawing_02-X1_2_Jan2026_0008.pdf PDF
B09_Amd8_-_QR22_Attach_Drawing_02-C5_64_Jan2026_0008.pdf PDF
Show 40 more

Latest 50 of 109 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

/3/

:51

LA

UR

EL

.O

TT

EY F

:\7

4.0

5 D

EV

A W

AT

ER

A

ND

W

AS

TE

W

AT

ER

S

YS

TE

M

RE

HA

B\

DR

AW

IN

GS

\D

W G\

CI

VI

L\5 S

HE

ET

P

RO

DU

CT

IO

N\

5_

DE

VA

W

_W W

D

ET

AI

LS

W .D

W G

NTS

D

C3.15

BLOWOFF VALVE

TREE PROTECTION NOTES:

1. REFER TO PLAN AND PROFILE SHEETS FOR TREE

PROTECTION LOCATIONS. TREE PROTECTION LOCATION

MAY BE ADJUSTED IN THE FIELD BY THE CONTRACTING

OFFICER'S REPRESENTATIVE.

2. OUTSIDE EDGE OF TEMPORARY BARRIER SHALL BE

PLACED AT DRIP-LINE OF TREE. TREE GUARDS MAY BE

PLACED AROUND SINGLE TREES OR GROUPS OF TREES.

3. MOVABLE BARRIERS MAY BE SUBSTITUTED FOR

IN-GROUND BARRIERS. IT IS THE CONTRACTOR'S

RESPONSIBILITY TO ENSURE THAT PERIMETER OF

FENCING REMAINS AT THE DRIP-LINE OF THE TREE AND

THAT TREES ARE PROTECTED.

FINISH

GRADE

3'-0"

MIN.

VARIES, 6'-0" MIN.

4' -0

TEMPORARY BARRIER

PER PROJECT SPEC SECTION

32 01 01 - TREE PROTECTION

EXISTING TREE TO BE

PROTECTED DURING

CONSTRUCTION

IN-GROUND OR MOVABLE

POSTS

NTS

B

C3.15

TYPICAL TREE PROTECTION DETAIL

NTS

C

C3.15

INDIVIDUAL PRV

WATTS PRESSURE REDUCING VALVE OR

APPROVED SALIENT EQUAL

14" x 19" NDS PLASTIC IRRIGATION BOX

WITH LOCKABLE LID OR APPROVED

SALIENT EQUAL

FINISHED GROUND

3/4" WASHED GRAVEL,

6" MIN. DEPTH

1" WATER SERVICE LINE

INFLOW OUTFLOW

DATE:

DESIGNED:

TECH. REVIEW:

SUB SHEET NO.

PMIS/PKG NO.

DRAWING NO.

SHEET

OF

TITLE OF SHEET

WATER DETAILS 143

178069

169 513

DJ&A

DJ&A

M. WHELEHON

1.17.2025

DEATH VALLEY

NATIONAL PARK

318717 00-

C3.15

NTS

A

C3.15

AIR RELEASE VALVE

WATER MAIN

1" ELECTROFUSION

SADDLE TAP

VAL-MATIC MODEL 201C.2

AIR RELEASE VALVE OR

APPROVED SALIENT EQUAL

5' MINIMUM

ED

G

E O

F R

O

AD

/T R

AI

L

CURB STOP

BOX LID

DRAIN PIT WITH 8 CU FT

OF 3/8" GRAVEL.

EXTENSION

TYPE BASE

CURB BOX

PIPE SUPPORT (TYP.)

CURB STOP MUELLER

H-10291 OR APPROVED

SALIENT EQUAL

CORP STOP

1" HDPE DR 9

UNION

2" 90° BEND

2" SCH. 40 GALV. PIPE WRAPPED

IN POLYETHYLENE PLASTIC

HDPE WATER MAIN

ELECTROFUSION

SADDLE TAP

CORP STOP

DRAIN WASTE

BALL VALVE

2" THREADED

CAP AND PLUG

FINISHED GROUND

ADJUSTABLE

VALVE BOX

CAST IRON

VALVE BOX LID

4" WASHED GRAVEL, 6" MIN.2" 45° BEND

45°'

MUELLER AIR RELEASE VALVE

VAULT OR APPROVED EQUAL

24 SS MESH

CORROSION-RESISTANT SCREEN

3/4" GALV. RELIEF LINE (LOCATION

WILL BE DETERMINED IN THE FIELD)

12-18"

4X4 TREATED WOOD

MARKER POST

MOUNT RISER TO

WOOD POST WITH

TWO SS STRAPS

UNION VALVE

Sheets and Views
Water Details 4